This architectural drawing is a basement floor plan showing HVAC removals for a Department of Veterans Affairs (VA) project at the Dayton VAMC (Medical Center). The document details phased removal of existing steam and chilled water piping, with specific annotations for CWR/CWS (Chilled Water Return/Supply) and condensate drain modifications across four distinct construction phases. The plan is part of the 36C25025B0036AMEND0002 solicitation for infrastructure deficiencies correction, with a bid opening scheduled for July 23, 2025, at 10:00 a.m. local time at the Network Contracting Office 10 in Kettering, OH. The technical drawing is prepared by Heapy Engineering and Guidon Design Inc., with the project number 2018-05164, and includes detailed ductwork, pipe routing, and equipment removal specifications for the basement area.
View the file
Other files
Show all 15
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DN
AHU
CWR/CWS UP AND
CONDENSATE DRAIN.
18x12
12x8
10x88x8 12x8 10x8 x1
24x12
9 9
CWR/CWS UP AND
CONDENSATE DRAIN.
CWR/CWS UP AND
CONDENSATE DRAIN.
CWR/CWS UP AND
CONDENSATE DRAIN.
CWR/CWS UP.
PHASE 1
8 9
PHASE 3PHASE 4
P: 937-224-0861 www.heapy.com
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
GUIDON DESIGN INC.
905 N. CAPITOL AVE. SUITE 100 | INDIANAPOLIS, IN. 46204
317.800.6388 | WWW.GUIDONDESIGN.COM
SUSTAINABLE ARCHITECTURE + ENGINEERING
PROJECT LEAD
Architect, Structural Engineer, Civil Engineer
PROJECT NO. STATE COA FIRM NO.2018-05164 01528
/9
/2
:2
:2
P M
MD100
BASEMENT FLOOR PLAN -
REMOVALS
CORRECT
INFRASTRUCTURE
DEFICIENCIES, B408
DAYTON, OHIO 45428
552-19-102
PHIL WEST, COR
May 2nd, 2025 GSE WJS
BID DOCUMENTS
FULLY SPRINKLERED
GENERAL NOTES
PLAN NOTES
A. REFER TO SHEET M001 FOR LEGEND, ABBREVIATIONS, INDEX OF DRAWINGS,
AND ADDITIONAL GENERAL NOTES.
1. EXISTING DUCTWORK TO REMAIN.
2. REMOVE EXISTING STEAM AND CONDENSATE PIPE RISERS AND ASSOCIATED
SUPPORTS, ETC.
3. REMOVE EXISTING DUCTWORK AND ASSOCIATED ACCESSORIES, SUPPORTS, ETC.
4. REMOVE EXISTING DUCT TO THIS POINT FOR RECONNECTION IN NEW WORK.
5. REMOVE EXISTING AIR HANDLING UNIT AND ASSOCIATED DUCTWORK, PIPING,
CONTROLS, ETC.
6. REMOVE EXISTING PIPING AND ASSOCIATED ACCESSORIES, SUPPORTS, ETC. AFTER
NEW CHW AND HHW SYSTEMS ARE OPERATIONAL.
7. REMOVE ALL EXISTING CHILLED WATER SYSTEM COMPONENTS AFTER THE NEW
CHILLERS ARE INSTALLED AND OPERATIONAL.
8. REMOVE EXISTING DUCTWORK TO FLOOR PENETRATION. EXISTING AIR DEVICE ON
FIRST FLOOR TO REMAIN.
9. CAP UNDER FLOOR.
10. REMOVE EXISTING PIPING TO THIS POINT AND CAP AFTER NEW CHW AND HHW
SYSTEMS ARE OPERATIONAL.
11. REMOVE EXISTING AIR HANDLING UNIT STRUCTURAL SUPPORTS. AHU LOCATED ON
FIRST FLOOR.
SCALE: 1/8" = 1'-0"MD100
1 BASEMENT-HVAC-REMOVALS
N
ALL EXISTING STEAM AND CHILLED
WATER PIPING SHALL BE REMOVED
FROM THE BASEMENT/CRAWL
SPACE. THIS REMOVAL WORK SHALL
TAKE PLACE AFTER THE NEW
CHILLED WATER AND HOT WATER
SYSTEMS ARE OPERATIONAL. SOME
OF THE PIPING IS SHOWN ON THIS
FLOOR PLAN.
Revisions: Date:
ADDENDUM #1 07/09/2025
| Sheets |
| M601 - SCHEDULES |
| M602 - SCHEDULES |
| M603 - SCHEDULES |
| M701 - CONTROLS AND AUTOMATION |
| MD100 - BASEMENT FLOOR PLAN - REMOVALS |
| MD101 - FIRST FLOOR PLAN - REMOVALS |
| MD102 - SECOND FLOOR PLAN - REMOVALS |
| MD103 - ATTIC FLOOR PLAN - REMOVALS |
| MP100 - BASEMENT FLOOR PLAN - PIPING |
| MP101 - FIRST FLOOR PLAN - PIPING |
| MP102 - SECOND FLOOR PLAN - PIPING |
| MP103 - ATTIC FLOOR PLAN - PIPING |