This document is a Schedules file for a Department of Veterans Affairs (VA) infrastructure project at the Dayton VAMC (Medical Center), specifically focused on HVAC and air distribution system documentation. The file contains detailed technical schedules for four pipe fan coil units, air distribution devices, duct construction specifications, and HVAC design data, including precise specifications for 30+ fan coil units with specific cooling requirements, air flow measurements, and environmental design conditions. Key technical details include outdoor design conditions of 90.4°F DB summer temperature, 2°F DB winter temperature, and design altitude of 1,004 feet, with specifications for horizontal concealed ducted and vertical floor set units featuring electronically commutated motors (ECM) and condensate overflow detection devices.
The schedules are part of Solicitation Number 36C25025B0036AMEND0002 for infrastructure deficiencies at Building 408, with a bid opening date of July 23, 2025, at 10:00 a.m. local time. The project is being managed by the VA Veterans Health Administration's Veterans Integrated Service Network 10, with design work completed by Heapy Engineering and Guidon Design Inc. The technical documentation provides comprehensive engineering specifications for HVAC system components, including air distribution device types, duct construction standards, sealing requirements, and detailed performance characteristics for multiple fan coil units across different spaces and configurations.
View the file
Other files
Show all 15
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DUCT CONSTRUCTION, SEALING, AND INSULATION
GENERAL NOTES:
A. REFER TO SPECIFICATIONS FOR DUCT CONSTRUCTION:
SHEET METAL DUCT; INTERIOR LINING; EXTERIOR
INSULATION; FIBERGLASS DUCTBOARD; ETC.
B. DUCT CONSTRUCTION AND SEALING SHALL BE PER
LATEST S.M.A.C.N.A. STANDARDS.
NOTES:
1. ROUND SHEET METAL RUN-OUTS TO AIR DEVICES DOWNSTREAM OF VAV BOXES SHALL BE EXTERNALLY INSULATED.
2. INSULATE FROM 24" UPSTREAM OF BACKDRAFT / ISOLATION DAMPER TO PENETRATION OF WALL / ROOF.
3. CONCEALED ROUND RUNOUT DUCTS TO AIR DEVICES MAY BE 1" S.P. CLASS LONGITUDINAL SEAM.
DUCT SYSTEM
S.P. CON-
STRUCT.
SEAL
CLASS
LEAKAGE
CLASS
S.M.A.C.N.A. CLASS.
INTERNALLY
LINED
EXTERNAL
INSULATION
NOT
INSULATED
SEE
NOTE
DOUBLE
WALL
INSULATEDRECT RND
1,3
NOTE 3
+3" A 8
+1" 16
16 8
A
A
A
SUPPLY DUCTWORK UPSTREAM OF
VAV BOXES FOR AHU-
SUPPLY DUCTWORK DOWNSTREAM OF
VAV BOXES AHU-
RETURN DUCTWORK -2"
TOILET OR GENERAL EXHAUST
DUCTWORK
-1" 16 -
HVAC DESIGN DATA
GENERAL NOTES:
A. OUTDOOR DESIGN CONDITIONS:
90.4°F DB SUMMER
73.5°F WB SUMMER
2°F DB WINTER
NOTES:
1. LISTED RH IS MAXIMUM ANTICIPATED AT LISTED DB TEMPERATURE.
2. REFER TO ATC SEQUENCES FOR ACTUAL ROOM SETPOINTS.
3. LISTEN RH IS MINIMUM ANTICIPATED AT LISTED DB TEMPARTURE.
SPACE NAME / TYPE °F DB
INTERIOR DESIGN DATA
SEE NOTE
OFFICES 2
SUMMER WINTER
% RH
(NOTE 1) °F DB
% RH
(NOTE 3)
75 60 70 20
- - 68 -
81 60 64 30
75 60 70
75 60 70
80 - 60 -
BATHROOMS AND TOILET
ROOMS
DATA CLOSETS
CONFERENCE ROOMS
ALL OTHER SPACES
UNOCCUPIED MODE
B. DESIGN ALTITUDE: 1004 FT.
FOUR PIPE FAN COIL UNIT SCHEDULE
TYPE
1 PROVIDE HIGH STATIC ELECTRONICALLY COMMUTATED MOTOR (ECM) OPTION.
2 FURNISH WITH CONDENSATE OVERFLOW DETECTION DEVICE. FLOAT SWITCH IN THE AUXILIARY DRAIN PAN TO STOP THE FAN WHEN WATER LEVEL IN THE PAN RISES TO A NEAR OVERFLOW LEVEL.
NO.
UNIT
HEATING REQUIREMENTS WITH
180°F ENT. WATER TEMP.
GPM
COOLING REQUIREMENTS WITH
44°F ENT. WATER TEMP.
MIN.
MBH
TOTAL
FAN
CFM
MIN.
MBH
SENS.
ENT. AIR F°
WbDb
MAX. LOSS
FT. WATER
THRU COILGPM
AUTO
VALVE
TYPE
RUN-
SIZE
OUT
MIN.
MBH
ENT.
AIR
FAN MOTOR
AUTO
VALVE
RUN-
SIZE
OUT
W (QTY.)
NOM. HP
APPROXIMATE SIZE
L
VOLT.-
HW
NOTES
NOTES:
MAX. LOSS
THRU COIL
AUTO
VALVE
AUTO
VALVE
TYPE
408-FCU-2
408-FCU-3
408-FCU-4
408-FCU-5
408-FCU-1A
ESP
O.A.
CFM
(30% PROPYLENE GLYCOL)
408-FCU-7
408-FCU-8
408-FCU-9
408-FCU-10
408-FCU-6
408-FCU-11
408-FCU-12
408-FCU-13
408-FCU-14
408-FCU-15
408-FCU-16
408-FCU-17
408-FCU-18
408-FCU-19
408-FCU-20
408-FCU-21
408-FCU-22
408-FCU-23
408-FCU-24
408-FCU-25
408-FCU-26
408-FCU-27A
408-FCU-28
408-FCU-29
408-FCU-30
408-FCU-31
408-FCU-10A
408-FCU-27
408-FCU-23A
408-FCU-5A
408-FCU-14A
408-FCU-23B
408-FCU-23C
408-FCU-23D
13.7670 100 12.7 2.5 5.0 25.8 70 5.0 142 (4) 115-1 1,20.75"1.2 2563.075.0 10691.71"HORIZONTAL CONCEALED DUCTED 1.20.4" 2-WAY 2-WAY
13.5660 100 12.6 2.4 5.0 25.6 70 5.0 140 (4) 115-1 1,20.75"1.163.075.0
1.70.75" 0.42-WAYHORIZONTAL CONCEALED DUCTED 0.4" 2-WAY
9.4450 70 8.7 1.7 5.0 70 5.0 80 (2) 115-1 1,20.75"0.8 2-WAY63.075.0
1.10.75" 0.2HORIZONTAL CONCEALED DUCTED 17.00.4" 2-WAY
7.5330 55 6.8 1.4 5.0 70 5.0 71 (2) 115-1 1,20.75"63.075.0
1.00.75" 0.20.7 2-WAYHORIZONTAL CONCEALED DUCTED 14.40.4" 2-WAY
7.6340 200 6.9 1.4 5.0 70 5.0 73 (2) 115-1 1,20.75"63.075.0
1.00.75" 0.20.7 2-WAYHORIZONTAL CONCEALED DUCTED 14.60.4" 2-WAY
0.32-WAY 2-WAY3.6140 65 3.1 0.7 5.0 6.1 70 5.0 29 115-10.75"63.075.0 0.50.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2
14.3640 235 13.0 2.6 5.0 21.7 70 5.0 134 (4) 115-1 1,20.75"1.263.075.0 1.50.75" 0.42-WAYHORIZONTAL CONCEALED DUCTED 0.4" 2-WAY
9.3440 70 8.5 1.7 5.0 70 5.0 78 (2) 115-1 1,20.75"0.8 2-WAY63.075.0
1.10.75" 0.2HORIZONTAL CONCEALED DUCTED 16.90.4" 2-WAY
10.6520 80 9.9 1.9 5.0 20.5 70 5.0 105 (2) 115-1 1,20.75"0.963.075.0
1.40.75" 0.42-WAYHORIZONTAL CONCEALED DUCTED 0.4" 2-WAY
21.2980 220 19.5 4.0 5.0 30.5 70 5.0 430 (2) 115-1 1,20.75"1.963.075.0
2.01"HORIZONTAL CONCEALED DUCTED 0.30.4" 2-WAY2-WAY
0.22-WAY 2-WAY2.9100 45 2.4 0.5 5.0 5.3 70 5.0 23 115-10.75"63.075.0 370.50.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2
13.0410 130 12.0 2.3 5.0 21.1 70 5.0 132 (4) 115-1 1,20.75"1.163.075.0 691.40.75" 0.42-WAYHORIZONTAL CONCEALED DUCTED 0.4" 2-WAY
0.42-WAY 2-WAY4.4195 - 4.0 0.8 5.0 8.1 70 5.0 39 115-10.75"63.075.0 370.50.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2
17.0865 130 16.0 3.1 5.0 32.4 70 5.0 169 (4) 115-1 1,20.75"1.563.075.0 762.21"HORIZONTAL CONCEALED DUCTED 0.30.4" 2-WAY2-WAY
12.4555 235 11.2 2.3 5.0 20.2 70 5.0 122 (4) 115-1 1,20.75"1.163.075.0 691.30.75" 0.42-WAYHORIZONTAL CONCEALED DUCTED 0.4" 2-WAY
12.2545 125 11.0 2.2 5.0 21.0 70 5.0 121 (4) 115-1 1,20.75"1.063.075.0 690.75" 0.42-WAYHORIZONTAL CONCEALED DUCTED 0.4" 2-WAY
0.32-WAY 2-WAY4.0180 50 3.6 0.7 5.0 8.8 70 5.0 35 115-10.75"63.075.0 330.60.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2
12.2550 90 11.0 2.2 5.0 21.1 70 5.0 121 (4) 115-1 1,20.75"1.063.075.0 690.75" 0.42-WAYHORIZONTAL CONCEALED DUCTED 0.4" 2-WAY
0.32-WAY 2-WAY3.6140 135 3.1 0.7 5.0 6.1 70 5.0 29 115-10.75"63.075.0 370.50.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2
10.6535 85 10.0 1.9 5.0 20.1 70 5.0 109 (2) 115-1 1,20.75"0.963.075.0 590.75" 0.42-WAYHORIZONTAL CONCEALED DUCTED 0.4" 2-WAY
0.32-WAY 2-WAY3.1120 30 2.7 0.6 5.0 5.5 70 5.0 26 115-10.75"63.075.0 330.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2
12.9530 155 11.3 2.3 5.0 20.7 70 5.0 116 (4) 115-1 1,20.75"1.163.075.0 760.75" 0.42-WAYHORIZONTAL CONCEALED DUCTED 0.4" 2-WAY
12.2540 200 11.0 2.2 5.0 20.9 70 5.0 120 (4) 115-1 1,20.75"1.063.075.0 690.75" 0.42-WAYHORIZONTAL CONCEALED DUCTED 0.4" 2-WAY
17.0865 130 16.0 3.1 5.0 32.4 70 5.0 169 (4) 115-1 1,20.75"1.563.075.0 2.21"HORIZONTAL CONCEALED DUCTED 0.30.4" 2-WAY2-WAY
17.0865 140 16.0 3.1 5.0 32.4 70 5.0 169 (4) 115-1 1,20.75"1.563.075.0 2.21"HORIZONTAL CONCEALED DUCTED 0.30.4" 2-WAY2-WAY
0.42-WAY 2-WAY4.4195 - 4.0 0.8 5.0 8.1 70 5.0 39 115-10.75"63.075.0 0.50.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2
0.42-WAY 2-WAY4.6210 200 4.2 0.8 5.0 8.4 70 5.0 41 115-10.75"63.075.0 0.60.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2
0.32-WAY 2-WAY3.9250 130 3.8 0.7 5.0 7.7 70 5.0 48 115-10.75"63.075.0 100.50.75" 0.2VERTICAL FLOOR SET 0.4" 1,2
17.8960 265 17.1 3.2 5.0 34.1 70 5.0 185 (4) 115-1 1,20.75"1.563.075.0 762.31"HORIZONTAL CONCEALED DUCTED 0.30.4" 2-WAY2-WAY
17.8960 240 17.1 3.2 5.0 34.1 70 5.0 185 (4) 115-1 1,20.75"1.563.075.0 762.31"HORIZONTAL CONCEALED DUCTED 0.30.4" 2-WAY2-WAY
16.0775 120 14.8 2.9 5.0 27.9 70 5.0 155 (4) 115-1 1,20.75"1.463.075.0 761.90.75" 0.42-WAYHORIZONTAL CONCEALED DUCTED 0.4" 2-WAY
9.8490 75 9.2 1.8 5.0 19.8 70 5.0 56 (2) 115-1 1,20.75"0.8 2563.075.0 10551.30.75" 0.42-WAYHORIZONTAL CONCEALED DUCTED 0.4" 2-WAY
8.0370 55 7.3 1.5 5.0 70 5.0 78 (2) 115-1 1,20.75"0.7 2-WAY63.075.0 481.00.75" 0.2HORIZONTAL CONCEALED DUCTED 15.30.4" 2-WAY
13.4935 215 13.2 2.4 5.0 28.4 70 5.0 120 (4) 115-1 1,20.75"1.163.075.0
1.91"VERTICAL FLOOR SET 0.30.4" 2-WAY2-WAY
11.7820 270 11.5 2.1 5.0 20.4 70 5.0 115 (4) 115-1 1,20.75"1.063.075.0 101.41"VERTICAL FLOOR SET 0.30.4" 2-WAY2-WAY
-VERTICAL FLOOR SET
VERTICAL FLOOR SET
VERTICAL FLOOR SET
15.2710 215 14.0 2.8 5.0 26.6 70 5.0 145 (4) 115-1 1,20.75"1.363.075.0
1.81"HORIZONTAL CONCEALED DUCTED 0.30.4" 2-WAY2-WAY
NOM
408-FCU-1B HORIZONTAL CONCEALED DUCTED 11.4485 75 10.2 2.1 5.0 21.5 70 5.0 110 (4) 115-1 1,20.75"- 2563.075.0 10
1.30.75" 0.40.4" 2-WAY 2-WAY
1.4
1.4
1.4
1.4
1.4
0.5
25 10
25 10
25 10
25 10
25 10
25 10
25 10
25 10
77 24
25 10
25 10
25 10
25 10
25 10
25 10
25 10
25 10
25 10
45 24
25 10
25 10
25 10
25 10
25 10
32 17
25 10
25 10
25 10
25 10
85 24
25 10
25 10
25 10
25 10
11.7820 270 11.5 2.1 5.0 20.4 70 5.0 115 (4) 115-1 1,20.75"1.063.075.0 101.41" 0.30.4" 2-WAY2-WAY 77 24
0.42-WAY 2-WAY4.4195 - 4.0 0.8 5.0 8.1 70 5.0 39 115-10.75"63.075.0 0.50.75" 0.20.4" 1,225 1037
0.42-WAY 2-WAY4.4195 - 4.0 0.8 5.0 8.1 70 5.0 39 115-10.75"63.075.0 0.50.75" 0.20.4" 1,225 1037
EGGCRATE CEILING REGISTERCR1
DAMPER
OPPOSED BLADE
SURFACE
TYPE MOUNTING
DESCRIPTION
EGGCRATE CEILING GRILLE
STANDARD SQ. PLAQUE CEILING
DIFFUSER ROUND NECK
SYMBOL
CD1
CG1
LAY-IN
FINISH
E.C.L.STEEL ALUM.
MATERIAL
ACCESSORIES
W.B.E.
SEE
EGGCRATE CEILING GRILLE
CG2
STANDARD SQ. PLAQUE CEILING
DIFFUSER ROUND NECK
CD2
NOTES:
1. PROVIDE 48" LONG DEVICE WITH 3 - 1" SLOTS. PROVIDE CENTER NOTCH AS REQUIRED TO ACCOMMODATE 2'X2' GRID.
LINEAR PLENUM SLOT
ADJUSTABLE BLADE DIFFUSER
CD3 1
EGGCRATE CEILING REGISTERCR2
DAMPER
OPPOSED BLADE
EGGCRATE CEILING FILTER GRILLE
CG3
EGGCRATE CEILING FILTER GRILLE
CG4
NOTE
FILTER
FILTER
TR1
DAMPER
OPPOSED BLADE
TR2
DAMPER
OPPOSED BLADE
ADJUSTABLE AIRFOIL BLADE SUPPLY
REGISTER - DOUBLE DEFLECTION
FIXED AIRFOIL BLADE RETURN
REGISTER
AIR DISTRIBUTION DEVICES
P: 937-224-0861 www.heapy.com
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
GUIDON DESIGN INC.
905 N. CAPITOL AVE. SUITE 100 | INDIANAPOLIS, IN. 46204
317.800.6388 | WWW.GUIDONDESIGN.COM
SUSTAINABLE ARCHITECTURE + ENGINEERING
PROJECT LEAD
Architect, Structural Engineer, Civil Engineer
PROJECT NO. STATE COA FIRM NO.2018-05164 01528
/9
/2
:2
:2
P M
M601
SCHEDULES CORRECT
INFRASTRUCTURE
DEFICIENCIES, B408
DAYTON, OHIO 45428
552-19-102
PHIL WEST, COR
May 2nd, 2025 GSE WJS
BID DOCUMENTS
FULLY SPRINKLERED
Revisions: Date:
ADDENDUM #1 07/09/2025
| Sheets |
| M601 - SCHEDULES |
| M602 - SCHEDULES |
| M603 - SCHEDULES |
| M701 - CONTROLS AND AUTOMATION |
| MD100 - BASEMENT FLOOR PLAN - REMOVALS |
| MD101 - FIRST FLOOR PLAN - REMOVALS |
| MD102 - SECOND FLOOR PLAN - REMOVALS |
| MD103 - ATTIC FLOOR PLAN - REMOVALS |
| MP100 - BASEMENT FLOOR PLAN - PIPING |
| MP101 - FIRST FLOOR PLAN - PIPING |
| MP102 - SECOND FLOOR PLAN - PIPING |
| MP103 - ATTIC FLOOR PLAN - PIPING |
File details come from the government source that posted it. Updated .