The document is a Schedules file for a Veterans Affairs Medical Center (VAMC) infrastructure project in Dayton, Ohio, containing multiple technical equipment schedules for mechanical systems. The schedules include detailed specifications for Energy Recovery Ventilators (ERVs), Cooling Only Split Systems, Chilled Water Cooling Coils, Pre-Heat Coils, Steam Pressure Reducing Valves, Steam Condensate Pumps, Buffer Tanks, and Room Heating Units. Key technical requirements for the ERVs include low-profile design, no virus crossover, energy recovery effectiveness >60%, water washable cores, direct drive ECM fans, double wall insulated casing, BACnet IP controls, filter monitoring, and UL/CSA certifications.
The project (Solicitation Number 36C25025B0036AMEND0002) is part of an infrastructure deficiencies improvement project for the Dayton VAMC, with a bid opening scheduled for July 23, 2025, at 10:00 a.m. local time at the Network Contracting Office 10 in Kettering, OH. The document is part of Amendment 0002, which includes RFI responses and Addendum 1, and is associated with the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 10.
View the file
Other files
Show all 15
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ENERGY RECOVERY VENTILATORS
NOTES:
1. LOW PROFILE – FOR CEILING OR WALL INSTALLATION
2. NO HEAT EXCHANGER VIRUS CROSSOVER - ASTM F1671 TESTED FOR NO VIRUS PENETRATION
3. LOW CROSS-OVER ENERGY RECOVERY COUNTER FLOW CORE <0.5% EATR TESTED TO AHRI 1060
4. TOTAL ENERGY RECOVERY EFFECTIVENESS >60% TESTED TO AHRI 1060
5. MAINTENANCE – WATER WASHABLE ENERGY/HEAT RECOVERY CORE WITH NO MOVING PARTS. PAPER CORES ARE NOT ACCEPTABLE.
6. DIRECT DRIVE PLENUM ECM FANS (< 1 W/CFM)
7. DOUBLE WALL INSULATED CASING WITH MINIMUM R4 PER INCH
8. FACTORY MOUNTED BACNET IP CONTROLS WITH BTL CERTIFICATION
9. HUMAN INTERFACE CONTROLLER.
10. FILTER MONITORING WITH REMOTE ALARM VIA PRESSURE MEASUREMENT ACROSS THE FILTER. MERV13 FILTERS ON OA AND MERV8 FILTERS ON RA.
11. CERTIFICATIONS: UL AND CSA
12. FACTORY MOUNTED HYDRONIC COILS PROVIDED WITH LOOSE VALVES AND ACTUATORS
13. SCR CONTROL ELECTRIC HEATERS
14. SINGLE-POINT POWER CONNECTION WITH UNIT AND ELECTRIC HEATER. MAIN POWER TO THE ELECTRIC HEATER.
MANUFCTR MODEL
SUPPLY EXHAUST SUPPLY EXHAUST
PRE-HEAT ELECTRIC HEATER HEAT EXCHANGER - SUMMER HEAT EXCHANGER - WINTER CHILLED WATER COOLING COIL HOT WATER HEATING COIL ELECTRICAL CONNECTION
EAT LAT CAPACITY CAPACITY
OUTDOOR AIR RETURN AIR SUPPLY AIR EFFICIENCY OUTDOOR AIR RETURN AIR SUPPLY AIR EFFICIENCY EAT LAT
TOTAL
FLUID TEMP.
FLUID
FLUID EAT LAT SENSIBLE FLOW
FLUID TEMP.
FLUID
FLUID
SINGLE POINT POWER
EDB EWB EDB EWB EDB EWB SENSIBLE LATENT TOTAL EDB EWB EDB EWB EDB EWB SENSIBLE LATENT TOTAL DB WB DB WB EWT LWT EWT LWT VOLTAGE FLA MCA RFS
CFM CFM in W.G. in W.G. oF oF (kW) (kW) % % % % % % MBH GPM % MBH GPM °F °F % (V) (A) (A) (A)
408-ERV1 OXYGEN8 H30_IN 3000 2700 1.50 1.50 3.2 5.2 2.1 4.0 90.7 73.8 75.0 63.0 80.0 67.1 76.0 65.8 70.2 5.2 4.7 70.0 52.9 49.0 39.6 75.1 64.6 73.0 80.0 67.1 63.3 60.3 68.1 11.9 45.0 57.0
GLCL
30.0 49.0 80.1 100.9 6.9 180 150 WATER 100 208V/3ph 28.6 35.4 40
408-ERV2
408-ERV3
AIRFLOW AIRFLOW ESP ESP
TYPE
PERCENTRATECAPACITYPERCENT
TYPE
PROP
°F°F°F°F
FLOW
RATECAPACITY
°F°F°F°F°F°F°F°F
REQUIRED MAX.
°F°F°F°F°F°F°F°F
OXYGEN8 H30_IN 3000 2700 1.50 1.50 3.2 5.2 2.1 4.0 90.7 73.8 75.0 63.0 80.0 67.1 76.0 65.8 70.2 5.2 4.7 70.0 52.9 49.0 39.6 75.1 64.6 73.0 80.0 67.1 63.3 60.3 68.1 11.9 45.0 57.0
GLCL
30.0 49.0 80.1 100.9 6.9 180 150 WATER 100 208V/3ph 28.6 35.4 40
PROP
OXYGEN8 H30_IN 3000 2700 1.50 1.50 3.2 5.2 2.1 4.0 90.7 73.8 75.0 63.0 80.0 67.1 76.0 65.8 70.2 5.2 4.7 70.0 52.9 49.0 39.6 75.1 64.6 73.0 80.0 67.1 63.3 60.3 68.1 11.9 45.0 57.0
GLCL
30.0 49.0 80.1 100.9 6.9 180 150 WATER 100 208V/3ph 28.6 35.4 40
PROP
1 COIL CAPACITY BASED ON STANDARD AIR AT 0 FT. ALTITUDE. COIL SHALL BE MINIMUM 6 ROWS DEEP.
408-CC1
COIL
NO.
NOTES:
SYSTEM
ERV-1
CFM
3,000 75.1
Wb
ENT. AIR FMAX.
LOSS
FACE
VEL
MAX.
S.P.
FPM.
0.47" 80.8
Db
LVG. AIR F
Db FLUIDWb
GLYCOL 30%
PROPYLENE
LOSS
MAX.
8.69
FT.
TEMP.
CIRCULATING FLUID
INGPM
°F
22.11
OUT
TEMP.
57.1
°F
AUTO
VALVE
CV
AUTO
VALVE
TYPE
MINIMUM
MBH
128.1
TOTAL (1)
MBH
MINIMUM
54.3
SENS. (1)
9.952-WAY
CHILLED WATER COOLING COIL SCHEDULE
408-CC2 ERV-2 3,000 75.1450 0.47" 80.8 6465 GLYCOL 30% 8.694522.11 57.1 128.1 54.39.952-WAY
408-CC3 ERV-3 3,000 75.1450 0.47" 80.8 6465 GLYCOL 30% 8.694522.11 57.1 128.1 54.39.952-WAY
ERV-2
ERV-1
ERV-3
408-PH2
408-PH3
408-PH1 3,000 667
FPM.
SYSTEM
COIL
NO. CFM
FACE
VEL
MAX.
LOSS
WATER
WATER
WATER
00.33"
0.33"
0.33"
80 17.73
F
F
FLUID
TEMP. AIR FMAX.
S.P.
ENT. LVG.
TEMP.
CIRCULATING FLUID
GPM
TEMP.
OUTIN
FT. FLUID
8.9 261.6
MAX. LOSS MIN.
MBH
AUTO
VALVE
CV
AUTO
VALVE
TYPE
8-
PRE-HEAT COIL SCHEDULE
261.6
261.6
17.73
17.73
3,000 667
3,000 667
0 80
0 80
8.9
8.9
2" 3"
3" 4"
NOTE: REDUCING VALVE AND RELIEF VALVE TO BE SIZED BY SUPPLIER. ASSEMBLY SHALL BE INSTALLED PER DETAIL AND MANUFACTURER'S RECOMMENDATIONS.
LOCATIONNUMBER
PRV PSIG
STEAM PRESSURE
INLET OUTLET
PRESSURE
RELIEF
SAFETY
MAXIMUM
CAPACITY LBS/HR
REQUIRED
PIPE SIZES
D1 D2
SAFETY RELIEF VALVE
MIN. CAPACITY
LB/HR
SET PRESSURE
PSIG
408-PRV1B 450 560 N/A N/A
408-PRV1A 900 1,130 1,130 40 PSI120 30 40 PSI
120 30BASEMENT
MECH. ROOM
BASEMENT
MECH. ROOM
EQUIPMENT/
HEATING HOT
WATER
AREA SERVED
N/A
HEATING HOT
WATER
STEAM PRESSURE REDUCING VALVE/SAFETY RELIEF VALVE SCHEDULE
BE PROVIDED. REFER TO ARCHITECTURAL DRAWINGS.
LINTELS IN MASONRY WALLS FOR FULL &
SEMI-RECESSED UNIT WALL OPENINGS SHALL
RECESSED UNITS TO HAVE FOUR(4) SIDE
OVERLAP UNLESS OTHERWISE NOTED.
APPROX. CABINET DIMENSIONS
HEATING CAPACITY BASED ON 60 ENT. AIR &
180 ENT. WATER.
MAXIMUM WATER PRESS. DROP THRU COIL
DESCRIPTION
NO.
FT-*
UNIT
FIN TUBE CONVECTOR
1 FT.
GENERAL NOTES
VERIFY/COORDINATE CABINET DIMENSIONS,
MOUNTING & RECESS REQUIREMENTS WITH
ARCHITECTURAL DWGS. PRIOR TO ORDERING.
ELEMENTS
WALL HUNG - 0'-24" AFF
MOUNTING
RUNOUT
MBH
1.5/FT
HTG.
GPM
0.5
SIZE
0.75"
LENGTHVALVE CV
0.2
MIN. AUTO
NOTE 2
DEPTH
6" 1
RECESS
HEIGHT
20"
SEE NOTE
NOTES
1. REFER TO FLOOR PLANS FOR ELEMENT LENGTHS.
2. CABINET LENGTH AS REQUIRED TO CONCEAL ELEMENT AND PIPING.
ROWS OF
STANDARD SLOPED TOP ENCLOSURE.
ROOM HEATING UNITS
UNIT
NO.
408-BT1
DIAMETER
TANK
VOLUME
MIN.
CONN.
SIZE HEIGHT
DIMENSIONS
SHIPPING
WEIGHT
6" 36" 81" 850
BUFFER TANK
2 @ 2 208-36.4
LOCATIONNUMBER
PUMP
PRESSURE
DISCHARGE
GALLONS
SIZE
RECEIVER
LB/HR
MOTOR
NOM. HP PHASE
REMARKS
408-CP1 1600 3500 RPM MOTOR8BASEMENT
MECH. ROOM
DUPLEX
TYPE UNIT
VOLT
50 PSI
CAST IRON RECEIVER
GPM
STEAM CONDENSATE PUMP SCHEDULE
POWER CIRCUIT (MCA / MOCP)
VOLTAGE & PHASE
MOUNTING
NOMINAL TONS
VOLTAGE & PHASE
SENSIBLE CAP (NET MBH)
DB ENTERING AIR
WB ENTERING AIR
C O
O L
IN
G
DESCRIPTION
F A
N
TOTAL CAP (NET MBH)
MOTOR HP
CFM
UNIT NUMBER (INDOOR / OUTDOOR)
AREA SERVED
208 / 1
38 W
AC-1
GENERAL NOTES:
DESCRIPTION AIR COOLED HEAT PUMP
9.09
10.9
COMM 103B
CONFIGURATION WALL MOUNTED
CONDENSATE PUMP
YES
7.8 / 15
208 / 1
GRADE
CU-1 (NOTE 1)
AC-2
AIR COOLED HEAT PUMP
COMM 101B
WALL MOUNTED
208 / 1
GRADE
CU-2
AC-3
AIR COOLED HEAT PUMP
COMM 202H
WALL MOUNTED
208 / 1
GRADE
CU-3
ELECTRIC SERVICES FOR OUTDOOR UNIT AND INDOOR UNIT - SINGLE
POWER SERVICE TO EACH UNIT. ADEQUACY OF LISTED CIRCUIT SIZES
MUST BE VERIFIED BY CONTRACTOR. COST FOR INCREASE OR CHANGE OF
ELECTRICAL SERVICE FOR EQUIPMENT SELECTED SHALL BE BORNE BY
CONTRACTOR.
CONDENSATE DRAIN PIPING FROM INDOOR UNITS SHALL BE 0.75" UNLESS
NOTED OTHERWISE.
0.75
7 / 15
0.75
7 / 15
208 / 1
38 W
8.04
8.9
YES
208 / 1
38 W
8.04
8.9
YES
COOLING ONLY SPLIT SYSTEMS
O U
T D
O O
R U
N
IT
IN
D
O O
R U
N
IT
NOTES:
1. UNIT SHALL BE ON EMERGENCY POWER
MOTOR HP 41 W 41 W 41 W
P: 937-224-0861 www.heapy.com
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
GUIDON DESIGN INC.
905 N. CAPITOL AVE. SUITE 100 | INDIANAPOLIS, IN. 46204
317.800.6388 | WWW.GUIDONDESIGN.COM
SUSTAINABLE ARCHITECTURE + ENGINEERING
PROJECT LEAD
Architect, Structural Engineer, Civil Engineer
PROJECT NO. STATE COA FIRM NO.2018-05164 01528
/9
/2
:2
:2
P M
M603
SCHEDULES CORRECT
INFRASTRUCTURE
DEFICIENCIES, B408
DAYTON, OHIO 45428
552-19-102
PHIL WEST, COR
May 2nd, 2025 GSE WJS
BID DOCUMENTS
FULLY SPRINKLERED
Revisions: Date:
ADDENDUM #1 07/09/2025
| Sheets |
| M601 - SCHEDULES |
| M602 - SCHEDULES |
| M603 - SCHEDULES |
| M701 - CONTROLS AND AUTOMATION |
| MD100 - BASEMENT FLOOR PLAN - REMOVALS |
| MD101 - FIRST FLOOR PLAN - REMOVALS |
| MD102 - SECOND FLOOR PLAN - REMOVALS |
| MD103 - ATTIC FLOOR PLAN - REMOVALS |
| MP100 - BASEMENT FLOOR PLAN - PIPING |
| MP101 - FIRST FLOOR PLAN - PIPING |
| MP102 - SECOND FLOOR PLAN - PIPING |
| MP103 - ATTIC FLOOR PLAN - PIPING |