M603 - SCHEDULES.pdf

PDF 405 KB Posted

Attached to
Y1AA--Infrastructure Deficiencies B408 [552-19-102] Dayton VAMC
Solicitation number
36C25025B0036AMEND0002
Issued by

About this file

The document is a Schedules file for a Veterans Affairs Medical Center (VAMC) infrastructure project in Dayton, Ohio, containing multiple technical equipment schedules for mechanical systems. The schedules include detailed specifications for Energy Recovery Ventilators (ERVs), Cooling Only Split Systems, Chilled Water Cooling Coils, Pre-Heat Coils, Steam Pressure Reducing Valves, Steam Condensate Pumps, Buffer Tanks, and Room Heating Units. Key technical requirements for the ERVs include low-profile design, no virus crossover, energy recovery effectiveness >60%, water washable cores, direct drive ECM fans, double wall insulated casing, BACnet IP controls, filter monitoring, and UL/CSA certifications.

The project (Solicitation Number 36C25025B0036AMEND0002) is part of an infrastructure deficiencies improvement project for the Dayton VAMC, with a bid opening scheduled for July 23, 2025, at 10:00 a.m. local time at the Network Contracting Office 10 in Kettering, OH. The document is part of Amendment 0002, which includes RFI responses and Addendum 1, and is associated with the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 10.

View the file

Other files

Show all 15

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ENERGY RECOVERY VENTILATORS

NOTES:

1. LOW PROFILE – FOR CEILING OR WALL INSTALLATION

2. NO HEAT EXCHANGER VIRUS CROSSOVER - ASTM F1671 TESTED FOR NO VIRUS PENETRATION

3. LOW CROSS-OVER ENERGY RECOVERY COUNTER FLOW CORE <0.5% EATR TESTED TO AHRI 1060

4. TOTAL ENERGY RECOVERY EFFECTIVENESS >60% TESTED TO AHRI 1060

5. MAINTENANCE – WATER WASHABLE ENERGY/HEAT RECOVERY CORE WITH NO MOVING PARTS. PAPER CORES ARE NOT ACCEPTABLE.

6. DIRECT DRIVE PLENUM ECM FANS (< 1 W/CFM)

7. DOUBLE WALL INSULATED CASING WITH MINIMUM R4 PER INCH

8. FACTORY MOUNTED BACNET IP CONTROLS WITH BTL CERTIFICATION

9. HUMAN INTERFACE CONTROLLER.

10. FILTER MONITORING WITH REMOTE ALARM VIA PRESSURE MEASUREMENT ACROSS THE FILTER. MERV13 FILTERS ON OA AND MERV8 FILTERS ON RA.

11. CERTIFICATIONS: UL AND CSA

12. FACTORY MOUNTED HYDRONIC COILS PROVIDED WITH LOOSE VALVES AND ACTUATORS

13. SCR CONTROL ELECTRIC HEATERS

14. SINGLE-POINT POWER CONNECTION WITH UNIT AND ELECTRIC HEATER. MAIN POWER TO THE ELECTRIC HEATER.

MANUFCTR MODEL

SUPPLY EXHAUST SUPPLY EXHAUST

PRE-HEAT ELECTRIC HEATER HEAT EXCHANGER - SUMMER HEAT EXCHANGER - WINTER CHILLED WATER COOLING COIL HOT WATER HEATING COIL ELECTRICAL CONNECTION

EAT LAT CAPACITY CAPACITY

OUTDOOR AIR RETURN AIR SUPPLY AIR EFFICIENCY OUTDOOR AIR RETURN AIR SUPPLY AIR EFFICIENCY EAT LAT

TOTAL

FLUID TEMP.

FLUID

FLUID EAT LAT SENSIBLE FLOW

FLUID TEMP.

FLUID

FLUID

SINGLE POINT POWER

EDB EWB EDB EWB EDB EWB SENSIBLE LATENT TOTAL EDB EWB EDB EWB EDB EWB SENSIBLE LATENT TOTAL DB WB DB WB EWT LWT EWT LWT VOLTAGE FLA MCA RFS

CFM CFM in W.G. in W.G. oF oF (kW) (kW) % % % % % % MBH GPM % MBH GPM °F °F % (V) (A) (A) (A)

408-ERV1 OXYGEN8 H30_IN 3000 2700 1.50 1.50 3.2 5.2 2.1 4.0 90.7 73.8 75.0 63.0 80.0 67.1 76.0 65.8 70.2 5.2 4.7 70.0 52.9 49.0 39.6 75.1 64.6 73.0 80.0 67.1 63.3 60.3 68.1 11.9 45.0 57.0

GLCL

30.0 49.0 80.1 100.9 6.9 180 150 WATER 100 208V/3ph 28.6 35.4 40

408-ERV2

408-ERV3

AIRFLOW AIRFLOW ESP ESP

TYPE

PERCENTRATECAPACITYPERCENT

TYPE

PROP

°F°F°F°F

FLOW

RATECAPACITY

°F°F°F°F°F°F°F°F

REQUIRED MAX.

°F°F°F°F°F°F°F°F

OXYGEN8 H30_IN 3000 2700 1.50 1.50 3.2 5.2 2.1 4.0 90.7 73.8 75.0 63.0 80.0 67.1 76.0 65.8 70.2 5.2 4.7 70.0 52.9 49.0 39.6 75.1 64.6 73.0 80.0 67.1 63.3 60.3 68.1 11.9 45.0 57.0

GLCL

30.0 49.0 80.1 100.9 6.9 180 150 WATER 100 208V/3ph 28.6 35.4 40

PROP

OXYGEN8 H30_IN 3000 2700 1.50 1.50 3.2 5.2 2.1 4.0 90.7 73.8 75.0 63.0 80.0 67.1 76.0 65.8 70.2 5.2 4.7 70.0 52.9 49.0 39.6 75.1 64.6 73.0 80.0 67.1 63.3 60.3 68.1 11.9 45.0 57.0

GLCL

30.0 49.0 80.1 100.9 6.9 180 150 WATER 100 208V/3ph 28.6 35.4 40

PROP

1 COIL CAPACITY BASED ON STANDARD AIR AT 0 FT. ALTITUDE. COIL SHALL BE MINIMUM 6 ROWS DEEP.

408-CC1

COIL

NO.

NOTES:

SYSTEM

ERV-1

CFM

3,000 75.1

Wb

ENT. AIR FMAX.

LOSS

FACE

VEL

MAX.

S.P.

FPM.

0.47" 80.8

Db

LVG. AIR F

Db FLUIDWb

GLYCOL 30%

PROPYLENE

LOSS

MAX.

8.69

FT.

TEMP.

CIRCULATING FLUID

INGPM

°F

22.11

OUT

TEMP.

57.1

°F

AUTO

VALVE

CV

AUTO

VALVE

TYPE

MINIMUM

MBH

128.1

TOTAL (1)

MBH

MINIMUM

54.3

SENS. (1)

9.952-WAY

CHILLED WATER COOLING COIL SCHEDULE

408-CC2 ERV-2 3,000 75.1450 0.47" 80.8 6465 GLYCOL 30% 8.694522.11 57.1 128.1 54.39.952-WAY

408-CC3 ERV-3 3,000 75.1450 0.47" 80.8 6465 GLYCOL 30% 8.694522.11 57.1 128.1 54.39.952-WAY

ERV-2

ERV-1

ERV-3

408-PH2

408-PH3

408-PH1 3,000 667

FPM.

SYSTEM

COIL

NO. CFM

FACE

VEL

MAX.

LOSS

WATER

WATER

WATER

00.33"

0.33"

0.33"

80 17.73

F

F

FLUID

TEMP. AIR FMAX.

S.P.

ENT. LVG.

TEMP.

CIRCULATING FLUID

GPM

TEMP.

OUTIN

FT. FLUID

8.9 261.6

MAX. LOSS MIN.

MBH

AUTO

VALVE

CV

AUTO

VALVE

TYPE

8-

PRE-HEAT COIL SCHEDULE

261.6

261.6

17.73

17.73

3,000 667

3,000 667

0 80

0 80

8.9

8.9

2" 3"

3" 4"

NOTE: REDUCING VALVE AND RELIEF VALVE TO BE SIZED BY SUPPLIER. ASSEMBLY SHALL BE INSTALLED PER DETAIL AND MANUFACTURER'S RECOMMENDATIONS.

LOCATIONNUMBER

PRV PSIG

STEAM PRESSURE

INLET OUTLET

PRESSURE

RELIEF

SAFETY

MAXIMUM

CAPACITY LBS/HR

REQUIRED

PIPE SIZES

D1 D2

SAFETY RELIEF VALVE

MIN. CAPACITY

LB/HR

SET PRESSURE

PSIG

408-PRV1B 450 560 N/A N/A

408-PRV1A 900 1,130 1,130 40 PSI120 30 40 PSI

120 30BASEMENT

MECH. ROOM

BASEMENT

MECH. ROOM

EQUIPMENT/

HEATING HOT

WATER

AREA SERVED

N/A

HEATING HOT

WATER

STEAM PRESSURE REDUCING VALVE/SAFETY RELIEF VALVE SCHEDULE

BE PROVIDED. REFER TO ARCHITECTURAL DRAWINGS.

LINTELS IN MASONRY WALLS FOR FULL &

SEMI-RECESSED UNIT WALL OPENINGS SHALL

RECESSED UNITS TO HAVE FOUR(4) SIDE

OVERLAP UNLESS OTHERWISE NOTED.

APPROX. CABINET DIMENSIONS

HEATING CAPACITY BASED ON 60 ENT. AIR &

180 ENT. WATER.

MAXIMUM WATER PRESS. DROP THRU COIL

DESCRIPTION

NO.

FT-*

UNIT

FIN TUBE CONVECTOR

1 FT.

GENERAL NOTES

VERIFY/COORDINATE CABINET DIMENSIONS,

MOUNTING & RECESS REQUIREMENTS WITH

ARCHITECTURAL DWGS. PRIOR TO ORDERING.

ELEMENTS

WALL HUNG - 0'-24" AFF

MOUNTING

RUNOUT

MBH

1.5/FT

HTG.

GPM

0.5

SIZE

0.75"

LENGTHVALVE CV

0.2

MIN. AUTO

NOTE 2

DEPTH

6" 1

RECESS

HEIGHT

20"

SEE NOTE

NOTES

1. REFER TO FLOOR PLANS FOR ELEMENT LENGTHS.

2. CABINET LENGTH AS REQUIRED TO CONCEAL ELEMENT AND PIPING.

ROWS OF

STANDARD SLOPED TOP ENCLOSURE.

ROOM HEATING UNITS

UNIT

NO.

408-BT1

DIAMETER

TANK

VOLUME

MIN.

CONN.

SIZE HEIGHT

DIMENSIONS

SHIPPING

WEIGHT

6" 36" 81" 850

BUFFER TANK

2 @ 2 208-36.4

LOCATIONNUMBER

PUMP

PRESSURE

DISCHARGE

GALLONS

SIZE

RECEIVER

LB/HR

MOTOR

NOM. HP PHASE

REMARKS

408-CP1 1600 3500 RPM MOTOR8BASEMENT

MECH. ROOM

DUPLEX

TYPE UNIT

VOLT

50 PSI

CAST IRON RECEIVER

GPM

STEAM CONDENSATE PUMP SCHEDULE

POWER CIRCUIT (MCA / MOCP)

VOLTAGE & PHASE

MOUNTING

NOMINAL TONS

VOLTAGE & PHASE

SENSIBLE CAP (NET MBH)

DB ENTERING AIR

WB ENTERING AIR

C O

O L

IN

G

DESCRIPTION

F A

N

TOTAL CAP (NET MBH)

MOTOR HP

CFM

UNIT NUMBER (INDOOR / OUTDOOR)

AREA SERVED

208 / 1

38 W

AC-1

GENERAL NOTES:

DESCRIPTION AIR COOLED HEAT PUMP

9.09

10.9

COMM 103B

CONFIGURATION WALL MOUNTED

CONDENSATE PUMP

YES

7.8 / 15

208 / 1

GRADE

CU-1 (NOTE 1)

AC-2

AIR COOLED HEAT PUMP

COMM 101B

WALL MOUNTED

208 / 1

GRADE

CU-2

AC-3

AIR COOLED HEAT PUMP

COMM 202H

WALL MOUNTED

208 / 1

GRADE

CU-3

ELECTRIC SERVICES FOR OUTDOOR UNIT AND INDOOR UNIT - SINGLE

POWER SERVICE TO EACH UNIT. ADEQUACY OF LISTED CIRCUIT SIZES

MUST BE VERIFIED BY CONTRACTOR. COST FOR INCREASE OR CHANGE OF

ELECTRICAL SERVICE FOR EQUIPMENT SELECTED SHALL BE BORNE BY

CONTRACTOR.

CONDENSATE DRAIN PIPING FROM INDOOR UNITS SHALL BE 0.75" UNLESS

NOTED OTHERWISE.

0.75

7 / 15

0.75

7 / 15

208 / 1

38 W

8.04

8.9

YES

208 / 1

38 W

8.04

8.9

YES

COOLING ONLY SPLIT SYSTEMS

O U

T D

O O

R U

N

IT

IN

D

O O

R U

N

IT

NOTES:

1. UNIT SHALL BE ON EMERGENCY POWER

MOTOR HP 41 W 41 W 41 W

P: 937-224-0861 www.heapy.com

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

GUIDON DESIGN INC.

905 N. CAPITOL AVE. SUITE 100 | INDIANAPOLIS, IN. 46204

317.800.6388 | WWW.GUIDONDESIGN.COM

SUSTAINABLE ARCHITECTURE + ENGINEERING

PROJECT LEAD

Architect, Structural Engineer, Civil Engineer

PROJECT NO. STATE COA FIRM NO.2018-05164 01528

/9

/2

:2

:2

P M

M603

SCHEDULES CORRECT

INFRASTRUCTURE

DEFICIENCIES, B408

DAYTON, OHIO 45428

552-19-102

PHIL WEST, COR

May 2nd, 2025 GSE WJS

BID DOCUMENTS

FULLY SPRINKLERED

Revisions: Date:

ADDENDUM #1 07/09/2025

Sheets
M601 - SCHEDULES
M602 - SCHEDULES
M603 - SCHEDULES
M701 - CONTROLS AND AUTOMATION
MD100 - BASEMENT FLOOR PLAN - REMOVALS
MD101 - FIRST FLOOR PLAN - REMOVALS
MD102 - SECOND FLOOR PLAN - REMOVALS
MD103 - ATTIC FLOOR PLAN - REMOVALS
MP100 - BASEMENT FLOOR PLAN - PIPING
MP101 - FIRST FLOOR PLAN - PIPING
MP102 - SECOND FLOOR PLAN - PIPING
MP103 - ATTIC FLOOR PLAN - PIPING