This document is a detailed engineering schedules file for a Department of Veterans Affairs (VA) infrastructure project at the Dayton VAMC (Medical Center). The file contains multiple comprehensive technical equipment schedules including four pipe fan coil units, converters, HVAC pumps, expansion tanks, hot water unit heaters, and air-cooled chiller units. Key technical specifications include equipment locations (primarily basement mechanical rooms), electrical requirements (voltage/phase), performance metrics, and specific operational parameters such as water temperatures, fluid flow rates, and motor characteristics.
The schedules provide granular engineering details for multiple mechanical systems, with most units designed for horizontal concealed ducted installation. Specific equipment highlights include two air-cooled chillers (408-ACCH1 and 408-ACCH2) with minimum capacity performance requirements, multiple pump configurations for chilled and hot water systems, and fan coil units with electronically commutated motors and condensate overflow detection devices. The project is associated with Solicitation Number 36C25025B0036AMEND0002, with a bid opening date of July 23, 2025, at 10:00 a.m. local time, managed by the VA's Network Contracting Office 10 in Kettering, Ohio.
View the file
Other files
Show all 15
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FOUR PIPE FAN COIL UNIT SCHEDULE (CONTINUED)
TYPE
1 PROVIDE HIGH STATIC ELECTRONICALLY COMMUTATED MOTOR (ECM) OPTION.
2 FURNISH WITH CONDENSATE OVERFLOW DETECTION DEVICE. FLOAT SWITCH IN THE AUXILIARY DRAIN PAN TO STOP THE FAN WHEN WATER LEVEL IN THE PAN RISES TO A NEAR OVERFLOW LEVEL.
NO.
UNIT
HEATING REQUIREMENTS WITH
180°F ENT. WATER TEMP.
GPM
COOLING REQUIREMENTS WITH
44°F ENT. WATER TEMP.
MIN.
MBH
TOTAL
FAN
CFM
MIN.
MBH
SENS.
ENT. AIR F
WbDb
MAX. LOSS
FT. WATER
THRU COILGPM
AUTO
VALVE
TYPE
RUN-
SIZE
OUT
MIN.
MBH
ENT.
AIR
FAN MOTOR
AUTO
VALVE
RUN-
SIZE
OUT
W (QTY.)
NOM. HP
APPROXIMATE SIZE
L
VOLT.-
HW
NOTES
NOTES:
MAX. LOSS
THRU COIL
AUTO
VALVE
AUTO
VALVE
TYPE
ESP
O.A.
CFM
(30% PROPYLENE GLYCOL)
408-FCU-32
408-FCU-33
408-FCU-34
408-FCU-35
408-FCU-36
408-FCU-37
408-FCU-38
408-FCU-39
408-FCU-40
408-FCU-41
408-FCU-42
408-FCU-43
408-FCU-44
408-FCU-45
408-FCU-46
408-FCU-47
408-FCU-48
408-FCU-49
408-FCU-50
408-FCU-51
408-FCU-52
408-FCU-53
408-FCU-54
408-FCU-55
408-FCU-56
408-FCU-57
408-FCU-58
408-FCU-59
408-FCU-60
408-FCU-61
408-FCU-62
408-FCU-63
408-FCU-64
408-FCU-65
408-FCU-66
408-FCU-67
408-FCU-68
408-FCU-69
408-FCU-70
408-FCU-71
408-FCU-72
408-FCU-73
408-FCU-40A
0.42-WAY 2-WAY4.6210 170 4.2 0.8 5.0 8.4 70 5.0 41 115-10.75" 25 10370.60.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2
0.22-WAY 2-WAY2.9100 35 2.4 0.5 5.0 5.3 70 5.0 23 115-10.75" 25 100.50.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2
0.22-WAY 2-WAY2.9100 40 2.4 0.5 5.0 5.3 70 5.0 23 115-10.75" 25 100.50.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2
0.22-WAY 2-WAY2.965 2.4 0.5 5.0 5.3 70 5.0 23 115-10.75" 25 100.50.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2
0.22-WAY 2-WAY2.935 2.4 0.5 5.0 5.3 70 5.0 23 115-10.75"0.50.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2
0.52-WAY 2-WAY5.2185 90 4.3 1.0 5.0 9.0 70 5.0 44 (2) 115-10.75" 480.60.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2
0.22-WAY 2-WAY2.9100 160 2.4 0.5 5.0 5.3 70 5.0 23 115-10.75"0.50.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2
0.32-WAY 2-WAY3.0105 170 2.5 0.6 5.0 5.5 70 5.0 24 115-10.75"0.50.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2
0.42-WAY 2-WAY4.6205 30 4.1 0.8 5.0 8.3 70 5.0 40 115-10.75"0.60.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2
0.22-WAY 2-WAY2.9125 2.4 0.5 5.0 5.3 70 5.0 23 115-10.75"0.50.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2
0.32-WAY 2-WAY3.6150 45 3.2 0.6 5.0 6.3 70 5.0 31 115-10.75" 330.50.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2
0.32-WAY 2-WAY3.6150 180 3.2 0.6 5.0 6.3 70 5.0 31 115-10.75" 330.50.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2
0.52-WAY 2-WAY5.4220 90 4.7 1.0 5.0 8.7 70 5.0 47 (2) 115-10.75" 430.60.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2
0.42-WAY 2-WAY4.6210 210 4.2 0.8 5.0 8.4 70 5.0 41 115-10.75"0.60.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2
0.22-WAY 2-WAY2.9100 35 2.4 0.5 5.0 5.3 70 5.0 23 115-10.75" 370.50.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2
0.22-WAY 2-WAY2.9100 35 2.4 0.5 5.0 5.3 70 5.0 23 115-10.75"0.50.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2
0.32-WAY 2-WAY3.6140 50 3.1 0.7 5.0 6.1 70 5.0 29 115-10.75"0.50.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2
0.42-WAY 2-WAY4.6205 200 4.1 0.8 5.0 8.3 70 5.0 40 115-10.75"0.60.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2
0.42-WAY 2-WAY4.5200 200 4.1 0.8 5.0 8.2 70 5.0 39 115-10.75"0.50.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2
0.42-WAY 2-WAY4.5200 150 4.1 0.8 5.0 8.2 70 5.0 39 115-10.75"0.50.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2
16.9860 140 15.9 3.1 5.0 32.2 70 5.0 169 (4) 115-1 1,20.75"1.5 25 10762.21"HORIZONTAL CONCEALED DUCTED 0.30.4" 2-WAY2-WAY
24.41270 195 23.2 4.5 5.0 34.5 70 5.0 430 (2) 115-1 1,20.75"2.1 672.31"HORIZONTAL CONCEALED DUCTED 0.30.4" 2-WAY2-WAY
20.81020 155 19.4 3.9 5.0 29.2 70 5.0 430 (2) 115-1 1,20.75"1.8 631.81"HORIZONTAL CONCEALED DUCTED 0.30.4" 2-WAY2-WAY
16.2795 120 15.1 2.9 5.0 31.0 70 5.0 158 (4) 115-1 1,20.75"1.4 2.11"HORIZONTAL CONCEALED DUCTED 0.30.4" 2-WAY2-WAY
17.3905 275 16.4 3.1 5.0 33.1 70 5.0 176 (4) 115-1 1,20.75"1.5 2.21"HORIZONTAL CONCEALED DUCTED 0.30.4" 2-WAY2-WAY
27.41600 240 27.4 5.1 5.0 45.3 70 5.0 430 (2) 115-1 1,20.75"2.4 693.01"HORIZONTAL CONCEALED DUCTED 0.30.4" 2-WAY2-WAY
12.8625 365 12.8 2.4 5.0 17.8 70 5.0 132 (4) 115-1 1,20.75"1.1 1.21"HORIZONTAL CONCEALED DUCTED 0.30.4" 2-WAY2-WAY
23.71205 185 23.7 4.4 5.0 33.6 70 5.0 430 (2) 115-1 1,20.75"2.1 692.21"HORIZONTAL CONCEALED DUCTED 0.30.4" 2-WAY2-WAY
13.0615 95 12.0 2.3 5.0 21.2 70 5.0 133 (4) 115-1 1,20.75"1.1 25 10691.40.75" 0.42-WAYHORIZONTAL CONCEALED DUCTED 0.4" 2-WAY
13.0605 95 11.9 2.3 5.0 21.1 70 5.0 131 (4) 115-1 1,20.75"1.1 691.40.75" 0.42-WAYHORIZONTAL CONCEALED DUCTED 0.4" 2-WAY
10.3560 145 9.6 1.8 5.0 20.0 70 5.0 88 2) 115-1 1,20.75"0.8 551.30.75" 0.42-WAYHORIZONTAL CONCEALED DUCTED 0.4" 2-WAY
12.4555 85 11.2 2.3 5.0 20.1 70 5.0 144 115-1 1,20.75"1.1 691.30.75" 0.42-WAYHORIZONTAL CONCEALED DUCTED 0.4" 2-WAY
2.9- 2.4 0.5 5.0 5.3 70 5.0 23 115-1 1,20.75"0.2 0.50.75" 0.42-WAYVERTICAL FLOOR SET 0.4" 2-WAY
2.9100 - 2.4 0.5 5.0 5.3 70 5.0 23 115-1 1,20.75"0.2 0.50.75" 0.42-WAYHORIZONTAL CONCEALED DUCTED 0.4" 2-WAY
9.1395 185 9.1 1.6 5.0 15.9 70 5.0 71 (2) 115-1 1,20.75"1.6 551.10.75" 0.42-WAYHORIZONTAL CONCEALED DUCTED 0.4" 2-WAY
9.4450 70 8.6 1.7 5.0 70 5.0 80 (2) 115-1 1,20.75"0.8 252-WAY 10551.10.75" 0.2HORIZONTAL CONCEALED DUCTED 17.00.4" 2-WAY
7.5330 150 6.7 1.4 5.0 70 5.0 71 (2) 115-1 1,20.75"0.7 2-WAY 480.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 2-WAY
8.3400 65 7.7 1.5 5.0 70 5.0 84 (2) 115-1 1,20.75"0.7 2-WAY 480.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 2-WAY
8.0370 65 7.3 1.5 5.0 70 5.0 78 (2) 115-1 1,20.75"0.7 2-WAY 481.00.75" 0.2HORIZONTAL CONCEALED DUCTED 15.30.4" 2-WAY
NOM
0.32-WAY 2-WAY3.3130 40 2.8 0.6 5.0 5.8 70 5.0 27 115-10.75" 330.50.75" 0.2HORIZONTAL CONCEALED DUCTED 0.4" 1,2
6.8280 45 6.0 1.2 5.0 70 5.0 62 115-1 1,20.75" 480.90.75" 0.20.6 2-WAYHORIZONTAL CONCEALED DUCTED 13.00.4" 2-WAY
6.9290 45 6.1 1.3 5.0 70 5.0 64 (2) 115-1 1,20.75" 480.90.75" 0.20.6 2-WAYHORIZONTAL CONCEALED DUCTED 13.30.4" 2-WAY
15.0690 105 13.7 2.7 5.0 26.2 70 5.0 142 (4) 115-1 1,20.75"1.3 761.80.75" 0.42-WAYHORIZONTAL CONCEALED DUCTED 0.4" 2-WAY
63.075.0
14.4 1.0
16.0 1.1
25 10
25 10
25 10
25 10
25 10
25 10
25 10
25 10
25 10
25 10
25 10
25 10
25 10
25 10
25 10
25 10
25 10
25 10
25 10
32 17
25 10
25 10
25 10
25 10
25 10
25 10
25 10
25 10
25 10
25 10
25 10
25 10
32 10
32 10
25 10
25 10
63.075.0
63.075.0
63.075.0
63.075.0
63.075.0
63.075.0
63.075.0
63.075.0
63.075.0
63.075.0
63.075.0
63.075.0
63.075.0
63.075.0
63.075.0
63.075.0
63.075.0
63.075.0
63.075.0
63.075.0
63.075.0
63.075.0
63.075.0
63.075.0
63.075.0
63.075.0
63.075.0
63.075.0
63.075.0
63.075.0
63.075.0
63.075.0
63.075.0
63.075.0
63.075.0
63.075.0
63.075.0
63.075.0
63.075.0
63.075.0
63.075.0
63.075.0
CONVERTER SIZED TO HANDLE 50 PERCENT OF THE PROJECT HEATING LOAD.
CONVERTER SHALL BE SIZED WITH .001 FOULING FACTOR.
APPROXIMATE SIZE: 8" DIA X 40" LONG.
BASEMENT MECH. ROOM
NOTES:
CONVERTER
NO.
408-C1
LOCATION
FLUID
WATER
CONVERTER
ENTERING
STEAM PSIG
MAX. LOSS
IN F
TEMP
CIRCULATING FLUID
GPM
54 160
OUT F
TEMP
ENTERING
FT. FLUID
VALVE
CONTROL
MBH
CAPACITY
HEATING
80013.1 S.F.
HEATING
SURFACE
MINIMUM
CONTROL
LBS/HR
VALVE
843 1686
TRAP
LBS/HR
1,2,3
NOTES
BASEMENT MECH. ROOM408-C2 WATER 13054 160 5 30 80013.1 S.F.15 843 1686 1,2,3
408-C3 BASEMENT MECH. ROOM WATER 54 130 160 5 30 15 13.1 S.F. 800 843 1686 1,2,3
CONVERTER SCHEDULE
TYPE
IN-LINE
VERTICAL
FLUID
CLEAR WATER
LOCATION
NO.
408-HWP1
PUMP
NOTES:
SYSTEM
°F
TEMP
CIRCULATING FLUID
GPM
PUMP HEAD
FT. FLUID
GR.
SP.
EFF.
RPM
NOM.
HP PHASE
MOTOR
208-3
VOLT.-
YES
VFD NOTES
1 MOTOR SHALL BE NEMA PREMIUM EFFICIENCY TYPE.
WATER
HEATING HOT
50 73
MIN.
7.5MECHANICAL ROOM
IN-LINE
VERTICAL
30% GLYCOL408-CWP1 44200 1.03 1750208-3 YES 1
WATER
CHILLED
36 73 10MECHANICAL ROOM
BASEMENT
IN-LINE
VERTICAL
CLEAR WATER408-HWP1 180108 1 1750208-3 YES 1
WATER
HEATING HOT
50 73 7.5MECHANICAL ROOM
IN-LINE
VERTICAL
30% GLYCOL408-CWP1 44200 1.03 1750208-3 YES 1
WATER
CHILLED
36 73 10MECHANICAL ROOM
30% GLYCOL408-GCWP1 5
WATER
CHILLED
MECHANICAL ROOM 44 1.0313 --
IN-LINE
HORIZONTAL
0.25 120-1 1750 NO
BASEMENT
BASEMENT
BASEMENT
BASEMENT
HVAC PUMP SCHEDULE
PRESS.
INITIAL
IN TANK
408-HWET1
408-CWET1
HOT
UNIT
NO.
SYSTEM
MAX.MIN.
402000
SYSTEM
TEMP.
RANGE °F
GAL.
APPROX.
SYSTEM
VOLUME
PSIG.
MAX. OPER. PRESS.
TANK
PSIG.
FILL
PSIG.
PRESS.
AT TANK
ATRELIEF
VALVE
PSIG.
21.7 11.3 408-CWAS1
ACCEPT.
VOLUME
MIN.
VOL.
MIN.
GAL.
GAL.
NO.
UNIT
5 200
NO
NO
MAX.
FT.
P.D.
AIR SEPARATOR
GPMIN.
SIZE BUILT-IN
STRAINER
1"
1"
1"
1"
FILL SIZE
WATER
COLDPIPE
SIZE
IN.
TO TANK
IN.
WATER
CHILLED
WATER
HORIZONTAL
TYPE
DIAPHRAGM
NOTES
77 341000 408-HWAS1HORIZONTAL
DIAPHRAGM
EXPANSION TANK SCHEDULE
MBH
MIN.UNIT
NO.
NOTES:
LOCATION
UNIT
TYPE
CFM
ENT. TEMP.
°F
WATERAIR
GPM
AUTO
VALVE
TYPE
RUNOUT
SIZE
AUTO
VALVE
CV
MOTOR
HEIGHT
APPROX. CABINET DIMS.
LENGTH DEPTH
HP
VOLT.-
PHASE
NOTES
(W)
MAX. LOSS
FT. WATER
THRU COIL
1 VERIFY/COORDINATE CABINET DIMENSIONS, MOUNTING & RECESS REQUIREMENTS PRIOR TO ORDERING.
8.0408-UH1 HORIZONTAL PROPELLERSEE PLANS 245 60 180 20.8 0.75" 3-WAY 0.4 (25)16"18" 10" 115-1 1
18.4408-UH2 HORIZONTAL PROPELLERSEE PLANS 500 60 180 21.9 0.75" 3-WAY 0.9 (25)16"18" 10" 115-1 1
24.8408-UH3 HORIZONTAL PROPELLERSEE PLANS 580 60 180 22.5 0.75" 3-WAY 1.2 (25)16"18" 10" 115-1 1
HOT WATER UNIT HEATER SCHEDULE
REMARKS
FT. MAX.
WATER P.D.
WITH 0°F AMBIENT TEMP.
SHALL PERFORM SATISFACTORILY
AT MIN. COMPRESSOR CAPACITY
OF CAPACITY REDUCTION TO 25%
CHILLER SHALL BE CAPABLE
2. HIGH SCCR 65k CURRENT RATING.
48 TONS
PERFORMANCE
MINIMUM CAPACITY
WITH 95°F AMBIENT TEMP.
PROVIDE ABOVE PERFORMANCE
AIR COOLED CONDENSER SHALL
LOCATIONEQUIPMENT
CONDENSER
AIR COOLED
COMPRESSOR
NO.
UNIT
408-ACCH1 CHILLER 100 GPM
57°F WATER IN
45°F WATER OUT
MOCP
208-3
11.5
SINGLE POINT UNIT ELECTRIC
NOTES:
VOLT.-
PHASE
MCA
236 250
EFFICIENCY
16.55
MIN. IPLV
(NOTE 1)
MAX A-WEIGHTED
SOUND POWER LEVEL, dBA PRESSURE
(NOTE 1)
SOUND
GRADE
408-ACCH2
1. MANUFACTURER SHALL PROVIDE ALL SOUND MINIMIZING OPTIONS AVAILABLE.
(NOTE 2)
NEW PACKAGED AIR COOLED CHILLER UNIT SCHEDULE
P: 937-224-0861 www.heapy.com
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
GUIDON DESIGN INC.
905 N. CAPITOL AVE. SUITE 100 | INDIANAPOLIS, IN. 46204
317.800.6388 | WWW.GUIDONDESIGN.COM
SUSTAINABLE ARCHITECTURE + ENGINEERING
PROJECT LEAD
Architect, Structural Engineer, Civil Engineer
PROJECT NO. STATE COA FIRM NO.2018-05164 01528
/9
/2
:2
:2
P M
M602
SCHEDULES CORRECT
INFRASTRUCTURE
DEFICIENCIES, B408
DAYTON, OHIO 45428
552-19-102
PHIL WEST, COR
May 2nd, 2025 GSE WJS
BID DOCUMENTS
FULLY SPRINKLERED
Revisions: Date:
ADDENDUM #1 07/09/2025
| Sheets |
| M601 - SCHEDULES |
| M602 - SCHEDULES |
| M603 - SCHEDULES |
| M701 - CONTROLS AND AUTOMATION |
| MD100 - BASEMENT FLOOR PLAN - REMOVALS |
| MD101 - FIRST FLOOR PLAN - REMOVALS |
| MD102 - SECOND FLOOR PLAN - REMOVALS |
| MD103 - ATTIC FLOOR PLAN - REMOVALS |
| MP100 - BASEMENT FLOOR PLAN - PIPING |
| MP101 - FIRST FLOOR PLAN - PIPING |
| MP102 - SECOND FLOOR PLAN - PIPING |
| MP103 - ATTIC FLOOR PLAN - PIPING |
File details come from the government source that posted it. Updated .