This combined synopsis and solicitation requests quotes for an upgraded chilled water system at the Fleet Readiness Center South West (FRCSW) in San Diego, California. The Navy seeks to procure two new Carrier brand chilled water units, pumps, and a water storage tank. The work includes relocating two existing units and installing, testing, calibrating, and training personnel on the new system. Quotes are due by June 10, 2022. The award will be a fixed-price contract to the lowest priced technically acceptable offer. The contractor must provide a minimum one-year warranty following project completion and acceptance. The place of performance is Building 378 at FRCSW NAS North Island in San Diego. The solicitation is set aside for small businesses with less than 1,250 employees.

View the file

Other files

File Type Posted
SOW Chiller V6.docx DOCX document
Final QA Chilled Water.pdf PDF
RFQ Full Text Clauses and Provisions.docx DOCX document
RFQ Full Text Clauses and Provisions.docx DOCX document
SOW Chiller V5 (1).docx DOCX document
Addendum to P97595 (Controls Sequencing).docx DOCX document
Contractor Environmental GuidelinesEPO 2021.pdf PDF
M01RevB.pdf PDF
M04RevB.pdf PDF
M03RevB.pdf PDF
A26 - GFP - Chill Water.xlsx XLSX spreadsheet
Chilled Water Combined Synopsis-Solicitation.docx DOCX document
E-1.pdf PDF
M05RevB.pdf PDF
B1 - JA Chiller_V4_030222_signed.pdf PDF
Schedule of Items.docx DOCX document
CDRL - Chilled Water.pdf PDF
M02RevB.pdf PDF
Show all 18

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

INDUSTRIAL PLANNING AND DESIGN OFFICE

FRCSW

NAVAL BASE CORONADO, SAN DIEGO, CA

UPGRADE CHILLED WATER SYSTEM IN

GENERATOR SHOP

M-06

DWG NOCODE IDENT NO.SIZE

SHEET OF

AUTOCAD

SCALE:

SHOWN

DESIGN:

CHECKED:

BLDG.

REF

FILE

01/22D. MCADAMS

WR50438 E 91145

6 6

P97595

P97595M06.DWG

EQUIPMENT SCHEDULE (ALL EQUIPMENT TO BE PROCURED BY CONTRACTOR)

WT-1

THIS EQUIPMENT SCHEDULE SHOWS ONLY NEW EQUIPMENT TO BE PURCHASED AS PART OF THIS PROJECT BY CONTRACTOR. IT DOES NOT SHOW TWO EXISTING CHILLERS (WC-1 AND WC-2), BECAUSE THEY ARE ALREADY ON-SITE AND DO NOT REQUIRE PURCHASING. HOWEVER, EXISTING CHILLERS WC-1 AND WC-2 SHALL BE USED IN THIS PROJECT AS SHOWN ON SHEETS M-01, M-02, M-03 AND M-05.

THIS DRAWING REFERENCES SPECIFIC MANUFACTURERS AND THEIR RESPECTIVE EQUIPMENT AND MODEL NUMBERS. THESE SPECIFIC EQUIPMENT SELECTIONS WERE MADE BECAUSE THEY FULFILL THE REQUIREMENTS OF THIS DESIGN. EQUIVALENT PROPOSALS FROM COMPETING MANUFACTURERS ARE ACCEPTABLE PROVIDED THEY FULFILL THE PERFORMANCE AND FABRICATION SPECIFICATIONS, QUALITY, AND LOCATION SPECIFIC REQUIREMENTS (ACCESSORIES, FEATURES AND INSTALLED OPTIONS) OF THE EQUIPMENT LISTED. IT WILL BE THE RESPONSIBILITY OF THE EQUIPMENT PURCHASING AGENT (THE CONTRACTOR) TO VERIFY THAT ALTERNATIVE EQUIPMENT IS EQUIVALENT AND FULFILLS ALL OF THESE REQUIREMENTS. IF IN DOUBT, PLEASE CONSULT THE DESIGN ENGINEER.

FLAG DESCRIPTION

CHILLED WATER BUFFER TANK

CAPACITY

1040 GALLONS

CODE

ASME SECTION VIII DIV 1

CONNECTIONS

2 EIGHT INCH FLANGED, OPPOSITE SIDES OF TANK

1 ONE INCH NPT TOP CENTER VENT

1 ONE INCH NPT BOTTOM CENTER DRAIN

NOTE: EQUIVALENT TANKS FROM DIFFERENT

MANUFACTURERS WITH INLET/OUTLET NEAR TANK

BOTTOM ARE ACCEPTABLE. IF A TANK WITH INLET/

OUTLET NEAR TANK BOTTOM IS USED, 8" PIPING

TO/FROM CHILLED WATER SUPPLY AND RETURN

MANIFOLDS SHALL BE ROUTED ACCORDINGLY.

LOCATIONS OF CHILLED WATER SUPPLY AND

RETURN MANIFOLDS SHALL REMAIN AS SHOWN IN

THIS DRAWING.

DESIGN PRESSURE MATERIAL

125 PSI CARBON STEEL

MANUFACTURER MODEL FEATURES AND INSTALLED OPTIONS

CBT-60-096-TCNILES STEEL TANK

- 12" X 16" MANWAY

- PRIMED PAINTED EXTERIOR

- INTERNAL BAFFLE

- R-16 POLYURETHANE CLOSED CELL SPRAY FOAM INSULATION

W/ ACRYLIC TOPCOAT

WATER STORAGE TANK

WATER CHILLERS

FLAG DESCRIPTION

WC-3

WC-4

WATER CHILLER

WATER CHILLER

MANUFACTURER MODEL NUMBER

CARRIER

CARRIER

30RAP02066C0DF18

30RAP02066C0DF18

TONS GPM PRESSURE DROP

18.8

18.8

45.2

45.2

14.2 FT WG

14.2 FT WG

EWT* LWT*

55 DEG F

57.5 DEG F

45 DEG F

47.5 DEG F

VOLTS PHASE HZ

460 3 60

3 60

-CRANKCASE HEATER

-MICRO CHANNEL CONDENSER COIL WITH E-COAT

-SEISMIC KIT (SDS LEVEL 2.5)

-R-410A REFRIGERANT

-FLOW SWITCH WITH MANUAL RESET

-LOW TEMPERATURE SWITCH WITH MANUAL RESET

- FLOW REGULATOR

ACCESSORIES AND INSTALLED OPTIONS

* EWT (ENTERING WATER TEMPERATURE) AND LWT (LEAVING WATER TEMPERATURE) SHOWN ARE FOR START-UP TEMPERATURES OF EACH CHILLER. DURING PERIODS OF NORMAL OPERATION, THESE

NUMBERS WILL VARY DEPENDING ON THE SPECIFIC OPERATING CONDITIONS AT THAT TIME.

OPERATING WEIGHT

1133 POUNDS MAXIMUM

-CRANKCASE HEATER

-MICRO CHANNEL CONDENSER COIL WITH E-COAT

-SEISMIC KIT (SDS LEVEL 2.5)

-R-410A REFRIGERANT

-FLOW SWITCH WITH MANUAL RESET

-LOW TEMPERATURE SWITCH WITH MANUAL RESET

-FLOW REGULATOR

1133 POUNDS MAXIMUM

PUMPS

FLAG DESCRIPTION MANUFACTURER SERIES

CP-1

CP-2

CP-3

CP-4

CP-5

CP-6

CP-7

CIRCULATION PUMP

(AECTS LOOP #3)

CIRCULATION PUMP

(AECTS LOOP #5)

CIRCULATION PUMP

(AECTS LOOP #4)

CIRCULATION PUMP

(AECTS LOOP #2)

CIRCULATION PUMP

(CHILLER LOOP CH-3)

CIRCULATION PUMP

(CHILLER LOOP CH-4)

CIRCULATION PUMP

(AECTS LOOP #1)

ARMSTRONG

4030 END SUCTION

BASE MOUNTED

SPLIT COUPLED

3 X 2 X 8

ARMSTRONG

ARMSTRONG

ARMSTRONG

ARMSTRONG

ARMSTRONG

ARMSTRONG

4030 END SUCTION

BASE MOUNTED

SPLIT COUPLED

3 X 2 X 8

4030 END SUCTION

BASE MOUNTED

SPLIT COUPLED

3 X 2 X 8

IMPELLER DIA. GPM HEAD (FT WG) HP RPM MOTOR TYPE VOLTS PHASE HZ

480 3 60

3 60

3 60

3 60

3 60

3 60

3 60

NOTES

WEIGHT: 231 LBS

7.31 IN 45.2 45 3 1800 ODP

45.2 45 ODP

30 45 ODP

7.31 IN 3 1800

7.31 IN 3 1800

3 1800 ODP

3 1800 ODP

3 1800 ODP

3 1800 ODP

7.31 IN

7.31 IN

7.31 IN

7.31 IN

4030 END SUCTION

BASE MOUNTED

SPLIT COUPLED

3 X 2 X 8

4030 END SUCTION

BASE MOUNTED

SPLIT COUPLED

3 X 2 X 8

4030 END SUCTION

BASE MOUNTED

SPLIT COUPLED

3 X 2 X 8

4030 END SUCTION

BASE MOUNTED

SPLIT COUPLED

3 X 2 X 8

RP-1 RE-CIRCULATION PUMP FRANKLIN Electric ITEM #555502

MODEL 360 LITTLE

GIANT PONY PUMP

1154.2 10 1/10 ODP 60

PURCHASE OPTIONAL STRAINER

WEIGHT: 231 LBS

WEIGHT: 231 LBS

WEIGHT: 231 LBS

WEIGHT: 231 LBS

WEIGHT: 231 LBS

WEIGHT: 231 LBS

CP-8 CIRCULATION PUMP

(AECTS LOOP #6)

ARMSTRONG 3 6030 50 3 1800 ODP7.31 IN

4030 END SUCTION

BASE MOUNTED

SPLIT COUPLED

3 X 2 X 8

480 WEIGHT: 231 LBS

CP-9 CIRCULATION PUMP

(AVTRON LOOP #1)

ARMSTRONG 3 6025 40 3 1800 ODP7.31 IN

4030 END SUCTION

BASE MOUNTED

SPLIT COUPLED

3 X 2 X 8

480 WEIGHT: 231 LBS

CP-10 CIRCULATION PUMP

(AVTRON LOOP #2)

ARMSTRONG 3 6030 60 3 1800 ODP8.13 IN

4030 END SUCTION

BASE MOUNTED

SPLIT COUPLED

3 X 2 X 8

480 WEIGHT: 231 LBS