This federal solicitation seeks proposals for facilities investment services including preventive maintenance, repair, and alteration of heating, ventilation, and air conditioning (HVAC) equipment at sites in Pennsylvania. The anticipated contract will be a base period of one year with four optional one-year extensions not exceeding 60 months total. Services are required at the Philadelphia Navy Yard Annex and Naval Support Activity in Philadelphia. Prospective contractors must register in the System for Award Management database, and maintain active registration through final invoice payment if awarded the contract. The soliciting agency is the Naval Facilities Engineering Command of the Department of the Navy.
View the file
Other files
Show all 24
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
NSWC
| PNSY Service Call Log | |||||||
| Date | Comp Date | PNSY # | SC # | Job Status | Bldg # / Unit | Job Description | Notes |
| 7/9/19 | A0001 | 5768 | quote sent | 633 | AHU-1 investigate condensate leak | 7/10 per BJ Unit needs new condensate pan hub/drain. Material is onsite, cannot install until the scheduled September building shutdown. On the schedule to install during Sept shutdown. 8/19 as pers parts but work not completed until the September shutdown. will schedule to install during september shutdown. |
9/11- attempeted to install the drian pan hub unable to get it in the whole have to put in for a TF1 due to so we can moved chilled water out of place to put the hub back in place - 8H - On hold untill we get permission for the TF1- Completed for now . customer wants done on overtime, TF-1 was sent *rn*
| 7/9/19 | 7/11/19 | A0002 | 5769 | complete | 1000 | Rm 496 investigate excessive temperature | 7/11 look at service call and area was comfortable at this time. Did not seem to have any problems at this time, he did not apply any time to this call and is closing it out for now *rn* |
| 7/9/19 | 7/30/19 | A0003 | 5800 | quote sent | 87 | Bild 87- Rm 1505 Investigate PTAC units not working | 7/30/19 PTAC unit needs to be replaced. call complete, TF-1 needed |
| 7/9/19 | 7/15/19 | A0004 | 5775 | complete | 633 | Investigate Motor Coupling On CHWP #2 | 7/15/19 Replaced bad pump coupling. Call complete. |
| 7/9/19 | 7/25/19 | A0005 | 5802 | complete | 633 | Investigate Alarms on Chiller #1 & #2 | 7/25/19 found chiller in alarm due to pump #2 being off line because of a bad pump coupling. Made repairs to coupling under service call A0004 on 7/15, reset, check and chiller now has no alarm and is cooling properly. Rechecked on 7/25 to ensure there are no more problems. call complete. |
| 7/9/19 | 7/16/19 | A0006 | 5796 | complete | 633 | Investigate High Bay UPS Enclouser HVAC unit not cooling | 7/16/2019 found and replaced bad motor. Call complete. |
| 7/10/19 | 7/18/19 | A0007 | 5803 | complete | 4 | Investigate and repair Liebert contactors | 7/18/19 replaced contactors on units 4-3, 4-4 and 4-5. call complete. |
| 7/11/19 | 9/3/19 | A0008 | 5809 | complete | 4 | AHU-2 Add grease line for 3rd bearing | 9/3 as per chris rockhill he closed this call out but did not apply anytime due to working on warranty issues with blower wheel that this is associated with. Peterson is in the process of redoing the shaft and bearings again. We should not touch until this is resolved so it does not void any warranties *rn* |
| 7/11/19 | 7/12/19 | A0009 | cancelled | 87 | cancels by Robert Nazian | 7/12/19 cancelled However, our tech did find that units #24, 25, and 26 need to be replaced due to bad compressors. Quote sent to customer. | |
| 7/12/19 | 9/4/19 | A0010 | 5810 | cancelled | 1000 | AS-12 investigate and repair chilled water valve | 9/4 this is a duplicate of call A0062 which BJ is currently on. Refer to call A0062 and cancel this call *rn* |
| 7/12/19 | 7/16/19 | A0011 | 5813 | complete | 29 | Chiller - investigate chiller alarms | 7/16/19 nuisance alarm that is able to be reset. No issue with chiller, call is complete. |
| 7/12/19 | 7/16/19 | A0012 | 5814 | complete | 633 | VAV - investigate condesation drip in lobby | 7/16/19 cleaned out line, call complete. |
| 7/12/19 | 7/17/19 | A0013 | 5818 | complete | 1000 | AHU-104 - investigate excessive air flow room # 112 | 7/17 looked over ductwork and fan motor. Made adjustment to damper, air flow now good. Call complete. |
| 7/15/19 | 7/18/19 | A0014 | 5834 | quote sent | 4 | Chiller #1 - investigate chiller surge and purge unit | 7/18 shaft seal replacement and motor alignment needed. TF-1 needed. |
| 7/16/19 | 10/2/19 | A0015 | 5838 | complete | 29 | 2nd Fl, Rm 218 is hot, Jeff Gosett X8765 | 7/17 per chris will return to pull strainer, believe that might be the issue but will troubleshoot further, it does seem comfortable right now. 8/1 went to look at but room is occupied 10/2 Reale looking into call today and will followup with BJ to ensure we get completed asap. 10/2 room occupied again, Jeff who placed the call is away for the week, but occupants said there are no problems that the room is comfortable. we are closing out at this time *rn* 10/2-Reale- per customer temp room was okay- completed ch |
| 7/16/19 | 7/24/19 | A0016 | 5944 | complete | 633 | P104 Control Rm - investigate no cooling | 7/24/19 found unit off on high head pressure. Cleaned coil, changed filter call complete. |
| 7/16/19 | 7/20/19 | A0017 | 5934 | quote sent | 4 | Roof top chiller - investigate chiller not running - alarms | 7/16 new motors, blades, and contactors needed. TF-1 sent to customers |
| 7/16/19 | 8/7/19 | A0018 | 5947 | complete | 29 | VAV-14, Rm 16 - investigate no cooling | 8/7/19 found and replaced bad vav motor |
| 7/16/19 | 8/7/19 | A0019 | 5948 | complete | 4 | Rm 330 - investigate condensate leak from diffuser in SE corner | 8/7/19 found and replaced bad vav motor. Call complete. |
| 7/17/19 | 7/19/19 | A0020 | 5877 | quote sent | 4 | ACU-101 investigate compressor failure | 7/19/19 TF-1 needed, bad compressor. |
| 7/17/19 | 7/18/19 | A0021 | 5878 | quote sent | 77H | HP-3 investigate cooling and noisy compressor | 7/18/19 TF-1 needed, bad compressor. |
| 7/17/19 | 7/24/19 | A0022 | 5943 | complete | 4 | Rm 3800 relocate diffuser in office | 7/24/19 relocated diffuser. Call is complete. |
| 7/17/19 | 7/24/19 | A0023 | 5949 | complete | 4 | 1st Fl, rm 1411 FCU-43 rm is warm | 7/24 relocated diffuser, call complete. This should not be part of routine service calls.8/12 after desk was moved had to return to replace zone valve as well. |
| 7/18/19 | 7/22/19 | A0024 | 5889 | complete | 87 | Rm 1206, 1207, 1208 - investigate condensate leak | 7/22/2019 insulated sweatting diffusers, call complete. This should not be part of a routine service call, |
| 7/18/19 | 7/22/19 | A0025 | 5951 | complete | 1000 | Rm 435 - investigate condensate leak | 7/22/2019 insulated sweating diffusers, call complete. This should not be part of a routine service call, |
| 7/19/19 | 7/22/19 | A0026 | 5952 | complete | 1000 | Lab 437 - investigate condensate leak | 7/22/2019 insulated sweating diffusers, call complete. This should not be part of a routine service call, |
| 7/22/19 | 8/7/19 | A0027 | 5953 | complete | 29 | Investigate chiller failed on July 21, required reset | 8/7/2019 found chiller off on low liquid level due glycol pressure low. Added glycol, chiller is running, call is completed |
| 7/22/19 | 10/7/19 | A0028 | 5954 | complete | 4 | M801 - investigate poor cooling in M801 | 9/4 chris looked at real quick, seems to be ductwork issues, not an emergency . May not being part of a service call . 10/7 per bob f duct had good airflow and space was 67. call complete. We notices issues with the concrete sweating on hot days. this is due to the location of the lieberts blowing down air on the concrete, not related to service. rockhill spoke to nazian about this, if customer wants sweating issues handled it would turn into a TF-1 and is a major job *rn* |
| 7/23/19 | A0029 | 5955 | cancelled | 4 | Rm 2450/cube 17 - investigate leak above desk | this is related to diffusers and piping that need to be relocated and or insulated throughout the building. This should be under a TF-1 to insulate diffusers and piping throughout the building, instead of breaking out into several service calls to keep under $2500.00 | |
| 7/23/19 | 11/20/19 | A0030 | 5956 | complete | 29 | Rm 10D/VAV-22 investigate no cooling | 7/23 looked at call briefly seemed to be cooling ok at this time. 10/3 BJ sent back to verify still no issues, may not apply time to call if everything is still running ok *rn* 10/4 found bad actuator needs to be replaced, on order through trane on backorder need to followup with delivery date *rn***CH11/20- removed old motor from vav and installed new motor and cap wired system tested operations- at this time mechanicall okay - going to keep an eye on unit due to issues found while testing w/ communication end of the controls. ** |
| 7/23/19 | 11/21/19 | A0031 | 5957 | complete | 1000 | EF-106 - investigate high static pressure | 10/2 BJ scheduled. 10/3 per bj acuator is bad, and he ordered today. 7-10 day leadtime for material *rn* 10/23 parts ready for pickup at universal, bj scheduled for 10/28**CH11/21- installed transducer in panel found bad wire it was kinked- got kink out- wired and programed controls - checked operation - completed |
| 7/23/19 | A0032 | 5958 | cancelled | 4 | Rm 2011 - investigate condensate leak | this is related to diffusers and piping that need to be relocated and or insulated throughout the building. This should be under a TF-1 to insulate diffusers and piping throughout the building, instead of breaking out into several service calls to keep under $2500.00 | |
| 7/23/19 | 7/30/19 | A0033 | 5979 | quote needed | 633 | Lobby/ Fan Cool Unit - investigate return air flow | 7/30/19 found air flow issued due to needing ductwork added. |
| 7/23/19 | 10/2/19 | A0034 | 6180 | complete | 77H | Site 92-62 - compressed air systems - clean and open diffusers | 9/4 scheduling Chris Reale or Brain Starner for this week or next. 10/2 chris reale scheduled for 10/2 *rn*- 10/2-Reale-cleaned diffisers and opened vents-completed. 10/3 This was not related to service and should not have been a service call *rn* |
| 7/24/19 | 7/31/19 | A0035 | 6181 | complete | 77L | Lab 1507 - investigate condensate leak at AC unit | 7/31/19 cleaned and repaired condensate. Call complete. |
| 7/24/19 | 8/7/19 | A0036 | 5998 | complete | 87 | AC-2 investigate noise in AC-2 unit | 8/7/19 Found bad timer for VFD. Repaired, and call complete. |
| 7/25/19 | 7/30/19 | A0037 | 5999 | complete | 633 | Chiller ToAC - investigate alarms, chiller is running | 7/30 needed to clear maintenance alarm. Cleared alarm, call complete. |
| 7/25/19 | 7/30/19 | A0038 | 6000 | complete | 4 | Liebert 4-3 investigate overcooling, rm is 60 deg | 7/30/19 had to make adjustments to setpoints. Space now comfortable, call complete. |
| 7/25/19 | 7/31/19 | A0039 | 6183 | complete | 4 | FCU 2450 - investigate operation and clean FCU's in rm | 7/31/19 cleaned (13) fan coil units and flushed out clogged drain lines, call complete. |
| 7/25/19 | 7/31/19 | A0040 | 6034 | complete | 29 | 2nd FL, AHU-2 investigate motor overload tripping | 7/31/19 found and replaced bad overload. Call is complete. |
| 7/29/19 | 9/27/19 | A0041 | 6184 | complete | 87 | Lab 1117 - investigate warm room POC Justin Delborrello 267-882-8095 | 9/4 per chris r waiting on customer to coordinate for us to work in this area. Chris will remind smargiassi. 9/27 call complete reale replace capacitor, fuses and tstat. *rn* |
| 7/30/19 | 9/16/19 | A0042 | 6185 | quote needed | 4 | condensate pmp 1 - investigate leak at pump | 9/4/19 pump is going to need rebuild. Need permission from Teti to switch over to the backup pump so we can take this for rebuild *rn* 9/16-per Frank this will be turned into a TF-1 valves and not holding and need to be replaced and pump will need to be brought to jarvis for rebuild. should be done after cooling season if TF-1 is approved *rn* |
| 8/1/19 | 11/6/19 | A0043 | 6064 | complete | 4 | ACU-101 - investigate no cooling (north infill) | 10/3 frank r scheduled for 10/25 *rn* 11/1 frank r returning to complete on 11/4. 11/6 frank found and repairs leak call complete *rn* |
| 8/1/19 | 8/9/19 | A0044 | 6128 | complete | 633 | return fan #1 - investigate / change belts | 8/9/19 fan needed new belts. Replaced belts, call complete. |
| 8/1/19 | A0045 | 6187 | 1000 | Lab 1046 - insulate ductwork to prevent condensation leaks | this is related to diffusers and piping that need to be relocated and or insulated throughout the building. This should be under a TF-1 to insulate diffusers and piping throughout the building, instead of breaking out into several service calls to keep under $2500.00 | ||
| 8/1/19 | 8/12/19 | A0046 | 6126 | quote needed | 77L | McQuay chiller - investigate chiller in alarm | 9/9 per Frank this service call is complete due to being turned into a TF1. Starter, contactor, thermistor, found to need replacement and also found 2 bad motors on call # A0091. These 2 call (A0046 and A0091 tie in together)both finding will be combined together on a TF-1. *rn* |
| 8/2/19 | 8/16/19 | A0047 | 6146 | complete | 1000 | AHU-2 investigate AHU-2 not running | 8/2 found motor starter needs to be replaced. Starter due in week of 8/12/19. Chris R scheduled to install on 8/19/19 . 8/20/19 motor starter replaced ahead on schedule on 8/16/19, call complete *rn* |
| 8/2/19 | 8/7/19 | A0048 | 6100 | complete | 87 | North Chiller wont run | 8/7/19 cleaned chiller, chiller up and running upon departure. |
| 8/6/19 | A0049 | 6249 | quote needed | 87 | P107 (MNDIF) - Pump CH-2 repair missing pump insulation | 9/4 per chris r waiting on customer to coordinate for us to work in this area. Chris will remind smargiassi. While on inspection around 1st week of september Chris Reale looked into this and found that all insulation was ripped off pump and piping by others. this will need to be a TF-1, will need reinsulate pipe, take off old armaflex, install new armaflex and insulate pump housing *rn* | |
| 8/7/19 | 8/9/19 | A0050 | 6121 | complete | 633 | Chiller 1 wont run T068, circ b comp return | 8/9/19 replaced bad thermistor, call complete. |
| 8/7/19 | 8/30/19 | A0051 | 6122 | complete | 633 | HW Pmp 2 - coupling needs adjustment | 8/7 per frank couplling needs to be replaced, he has on order. 8/15 received coupling will tentatively schedule for week of 8/19/19. 8/30 frank r replaced coupling on 8/22, call is complete *rn* |
| 8/7/19 | 9/16/19 | A0052 | 6123 | complete | 633 | AHU-2 filters are dirty, investigate noisy supply fan | 9/4 per Chris R this needs to be done during shutdown *rn* 9/16 call completed by chris reale on 9/16. was complete during shutdown on inspection *rn* |
| 8/7/19 | 8/14/19 | A0053 | 6188 | complete | 4 | 4-1-1 investigate noise at return dan/ return fan motor | 8/14- rockhill - checked over fan motor and vfd - found motor was running hot but the motor is running with the spec of the motor - the motor will need to be watched just in case it starts to go bad. Complete for now *rn* |
| 8/8/19 | 8/9/19 | A0054 | 6137 | complete | 1000 | Main Lobby ceiling tile - investigate condensate drip onto ceiling tile | 8/9/19 drip pan added, call complete. |
| 8/8/19 | 11/29/19 | A0055 | 6155 | complete | 633 | FCU 2.1 mens highbay - belt is loose, provide belt size to bob smargiassi | 9/4 as per Chris Rockhill needs to be done during shut down, need slim person for job. 11/26 per rockhill he spoke with teti this does not need to be done during shutdown, we schedule for starner once he is back at PNSY *rn* **11/29CH- Unit had a bad belt and clogged filter- changed both and checked operations - completed - ch ** |
| 8/9/19 | 9/16/19 | A0056 | 6156 | complete | 633 | Chiller - clean chiller coils | 9/16- frank - 4 H - Completd - clened condesenors in chiller 1 & 2 |
| 8/10/19 | 8/20/19 | A0057 | 6190 | complete | 4 | NE Wing 1st deck - investigate and repair FCU not working | 8/20 found Fcu-31 having pnuematic problem, switch line FCU-33 unit complete, Fcu-33 has bad motor, motor replaced under PNSY # A0075, FCU-34 has bad motor, motor replaced under PNSY# A0076. this call is closed and complete as of 8/20/19 *rn* |
| 8/13/19 | 8/16/19 | A0058 | 6191 | complete | 633 | High Bay center office - investigate ac unit freezing up | 8/16/19 replaced filters, changed setting in tstat and cleaned coil call complete *rn* |
| 8/14/19 | 8/14/19 | A0059 | 6198 | complete | 77L | AC-1, S-1 - replace broken belts | 8/14/19 replace broken belt, call complete *rn* |
| 8/14/19 | 8/19/19 | A0060 | 6205 | complete | 4 | spare tower pump - investigate leak | 8/19/19 repaired leak, call complete *rn* |
| 8/15/19 | 8/20/19 | A0061 | 6216 | complete | 4 | Rm 2552 investigate leak dripping onto 1st floor ceiling | 8/20/19 reinsulated pipe, |
| 8/15/19 | 9/12/19 | A0062 | 6222 | complete | 1000 | AS-12 investigate and repair chilled water valve | 8/16/19 per bj there appears to be a water flow problem. We need to return to remove pipe insulation to check water temps to see if the problem is the 3way valve or gate valves that is the problem *rn* 9/12- Bj - troubleshoot the chilled water the booster pump installed in wrong location in the piping- have to wait to talk to jim teti on how to proceed. 10/3 per BJ when he spoke to jim teti about this jim said he will decide later what he wants done with this, and that he is not overly concern with it at this time to close it out for now *rn* |
| 8/15/19 | 10/11/19 | A0063 | 6223 | complete | 87 | East Bay Rm 1190 - investigate no cooling - chris lester | 9/6 per chris r waiting on customer to coordinate for us to work in this area. Chris will remind smargiassi. 10/3 we have attempted to call chris lester several times to coordinate but there has been no response from him. Bj spoke to smargiassi today to see if chris lester has and email and smargiassi said he is sending him an email now. per smargiassi he received a reply from Chris Lester saying at this time he can not retrieve his email, which I have a copy of, so we will continue to wait to coordinate with customer *rn* 10/11 per chris reale window unit needs to be replaced which is not under our contract. customer is taking care of *rn* |
| 8/15/19 | A0064 | 6242 | complete | 633 | Non Contract Equipment - exhaust fans remove and replace broken belts | 9/4 as per chris rockhill he believes reale completed this call, he may have placed the time against the inspection. This was for equipment that was not under contract but Teti needed done as an emergency. Call is complete, rockhill will confirm with reale where he placed his time *rn* 9/9/19 crhis reale completed on 8/19 under this job, call is complete | |
| 8/16/19 | 8/20/19 | A0065 | 6243 | quote needed | 77L | McQuay chiller - investigate chiller alarm and clock | 8/21 found bad fan motors and associated parts. Will be a TF-1, waiting on pricing from vendor to prepare quote *rn* |
| 8/19/19 | 8/19/19 | A0066 | 6244 | complete | 77L | York - investigate chiller not making setpoint | 8/19- frank - chiller running @ 55f chiller water can not maintain 44F set point - checked + found prv actuator linkage not connected to vanes - manually opened vanes went to supply hose to get hardwear to make repairs - repairs PRV actuator to valve linkage tested calibrated PRV. call is complete *rn* |
| 8/19/19 | 8/21/19 | A0067 | 6247 | complete | 4 | York 1 - investigatre chiller surging | 8/21 surging due to air in system relating back to shaft seal that needs to be replaced and TF-1 quote already provided to customer. Russo reset for now and is complete at this time *rn* |
| 8/19/19 | 8/21/19 | A0068 | 6260 | complete | 77L | 34-1 investigate condensate leak (up yellow steps) | 8/21/19 clean main drain line, drip and trap. Call complete *rn* |
| 8/19/19 | 2/11/20 | A0069 | 6265 | complete | 29 | Mess Room 101A - investigate, room is cold | 8/20 area checked during inspection, seems comfortable at this time. 10/3 BJ revisited this call with smargiassi on computer and they are showing damper problems. BJ is scheduled to look into this today *rn* 10/4 per bj will need to further troubleshoot *rn* 2/11 Rockhill checked over the VAV found to be working ok |
| 8/20/19 | 2/11/20 | A0070 | 6264 | complete | 29 | Mess Room 101B - investigate, room is cold | 8/20 area checked during inspection, seems comfortable at this time. 10/3 BJ revisited this call with smargiassi on computer and they are showing damper problems. BJ is scheduled to look into this today *rn* 10/4 per bj will need to further troubleshoot *rn* 2/11 Rockhill checked over the VAV found to be working ok |
| 8/20/19 | A0071 | 6263 | 4 | Room 3300/Cube 28B - investigate condensate dripping | this is related to diffusers and piping that need to be relocated and or insulated throughout the building. This should be under a TF-1 to insulate diffusers and piping throughout the building, instead of breaking out into several service calls to keep under $2500.00 | ||
| 8/20/19 | 10/3/19 | A0072 | 6262 | quote needed | 29 | Chem Lab RTU-1 - investigate VFD Tripping | 8/27 as per chris will need to further troubleshoot to see why it keeps locking out. seems like vfd may be shot if so that will be a TF-1. 10/3 per bj since vfd was overheating it should be replaced. Bj gather info for replacement and TF-1 being sent , once bj gets with customer to see where it can be moved to. *rn* |
| 8/20/19 | 8/21/19 | A0073 | 6269 | complete | 756 | investigate no cooling | 8/21/19 replaced cap, and added r22. call complete *rn* |
| 8/20/19 | 10/4/19 | A0074 | 6266 | quote sent | 77H | AHU-3 investigate and repair condensate leak | 9/4 as per rockhill parts (fan blade) just received, tentatively scheduled for 9/5. Rescheduled for BJ and reale on 10/4 *rn* 10/4 per bj this job will be a TF-1 needs blower wheels, shaft, bearings, pulleys etc. TF1 sent to customer |
| 8/21/19 | 8/22/19 | A0075 | 6279 | complete | 4 | FCU-33 replace bad motor | 8/22/19 reale and vinnie replaced motor, call is complete *rn* |
| 8/21/19 | 8/23/19 | A0076 | 6290 | complete | 4 | FCU-34 replace bad motor | 8/23/19 reale replaced motor, call is complete *rn* |
| 8/22/19 | A0077 | 6299 | 4 | Investigate condensate dripping from diffuser above cubicle | this is related to diffusers and piping that need to be relocated and or insulated throughout the building. This should be under a TF-1 to insulate diffusers and piping throughout the building, instead of breaking out into several service calls to keep under $2500.00 | ||
| 8/22/19 | 8/22/19 | A0078 | 6342 | complete | 4 | 2nd Deck NE Pavilion - investigate FCU condensate leak | 10/3 per bj he has the service ticket form that says closed out by rockhill on 9/3 completed by brian starner on 8/22. form states cleaned FCU pan out, call complete. starner complete this call on 8/22 along with call A0080, he placed all his time on A0080 by mistake instead of splitting it between the 2 calls *rn* |
| 8/22/19 | 11/7/19 | A0079 | 6297 | complete | 633 | boiler shop boiler - investigate low water | 9/4 per chris he is waiting on scholz or nazian to notify him where the water shut from for system so he can then work on it *rn* 10/3 bj has call and is going to followup nazian today *rn* 10/23 rockhill followingup tomorrow with to see what is going on with this call and the water *rn* **CH11/21-- 11/7- ran and tested unit after dscovering it was filled w/ water - everything is okay at this time ** |
| 8/22/19 | 8/30/19 | A0080 | 6334 | complete | 4 | Rm 2150 - investigate wet rug, condensate leak fan coil #90 | 8/30/19 cleaned and blew out cond lines, call complete. Starner also completed call A0078 under this call but mistakenly placed all time here instead of splitting between the 2 calls *rn* |
| 8/22/19 | 8/30/19 | A0081 | 6335 | complete | 77L | Rm 1507 - investigate/repair condensate leak | 8/30/19 repair pipe leak and clean line *rn* |
| 8/23/19 | 8/30/19 | A0082 | 6336 | complete | 1000 | Cooling tower #2 - investigate high water alarm on tower | 8/30/19 clean and fix float, call complete *rn* |
| 8/23/19 | 9/5/19 | A0083 | 6339 | complete | 4 | 2nd fl N. wing FCU investigate minor drip from FCU | 9/5- reale completed - the pan was pitched a little off so the water was pulling to the one side - changed the pitch of the pan and now the water is flowing in one way. |
| 8/23/19 | 10/8/19 | A0084 | 6320 | quote needed | 87 | AC-3 investigate return fan not running | 10/3 spoke to bj need to get scheduled asap *rn*. 10/8 bob ferrara investigated and found vfd needs to be replaced and relocated. bj will return to get info for a tf-1 10/23 vfd needs to be replaced and relocate for this and 3 other drives. bj looked into all under service call A0128 and all have been written up as a tf-1 *rn* |
| 8/26/19 | 8/26/19 | A0085 | 6321 | complete | 29 | investigate chiller alarm, chiller not running | 8/26/2019 per russo found chiller in ICP communication alarm, went through connections and found bad connection @ P11/J11 on main board. He repaired connections and will recheck in a few days to make sure connection was source of alarm. Tentatively on the schedule for week of 9/9/19 *rn* 9/9 chiller rechecked all seems ok at this time. close out and complete call, no time applied on 9/9 to this call all went to A0088 *rn* |
| 8/26/19 | 9/9/19 | A0086 | 6322 | complete | 29 | chiller - investigate low suction alarm | 8/28/19 per russo found chiller low on R134A. Found and repairs leak at thermistor but still picking up another leak with detector. Scheduled for 9/5 to further leak check *rn* |
9/9- topped off charge in cicuitt #2 put unit back together including all panels -chiller now working properly, call is complete *rn*
| 8/26/19 | 10/14/19 | A0087 | 6324 | complete | 4 | Room 1200 diffuser - investigate noise from hvac diffuser | 8/27 Chris Reale is scheduled for this call, we have tried to do a few times but lady who occupies this area is not available. 10/3 chris reale tried to do this call again but the lady still is not back, rockhill spoke to teti not to long ago and teti mentioned he is not sure when the lady will be back, and apparently no one has information on her return *rn*10/14 as per chris reale damper was not fully closing making a whistling noise. he installed new foam gasket and tighten bolt. call is now complete *rn* |
| 8/27/19 | 9/6/19 | A0088 | 6340 | complete | 1000 | penthouse air compressor - investigate auto bleed drain | 9/4- rockhill - the auto drain for air compressor needs to be replaced - comprssor is full of water. |
9/5- per rockhill he wil be ready for pickup auto drain tomorrow and install 9/6- per rockhill auto drain installed and call is complete 8/28/19 10/30/19 A0089 6232 633 exhaust fan - investigate why EF-2 has no status. Non Contract Exhaust Fan 8/19- Non-Contract Equipment, requested by Teti as emergency. Chris Reale - pcking up the Parts - the last two belts that need to be changed - replaced last of the belts all units are up and running and runnong okaty 4H 8/16- chris got all the info off the units grease the pllow block bearings changed 4 out of 6 belts due to back order changing the last two today. 8H 9/4- Reale - installed new belt started and it threw the belt off - seems to be an alignment issue that we have to correct tomorrow - 3h 9/19- Reale - made adjustments to align pulleys resecured motor bc of the unts not having power could not test operations. we are waiting for customer to tell us when captain will bring power back on to the fans. 10/3 per smargiassi power still is not on, they may possibly have it back on at the end of this week. *rn* ***CH11/21- 10/30 russo checked exhaust fan for proepr alignment and started and checked opertation- completed **
| 9/18/19 | 9/18/19 | A0090 | 6370 | complete | 1000 | Cooling tower #2 - investigate low water alarm on tower | 9/18- Reale - looked over the tower found no leaks and tower was filled - checked sensor- found no alarms. Call is complete *rn* | |
| 8/30/19 | A0091 | 6371 | quote needed | 77L | mcquay chiller - investigate failed condenser fans | 9/9 related to A0046. Notes from A0046 - per Frank this service call is complete due to being turned into a TF1. Starter, contactor, thermistor, found to need replacement and also found 2 bad motors on call # A0091. These 2 call (A0046 and A0091 tie in together)both finding will be combined together on a TF-1. *rn* | ||
| 9/3/19 | 9/20/19 | A0092 | 6373 | complete | 633 | CWP #2 - adjust coupling insert | 9/20 frank changed out coupling insert. Call is complete *rn* | |
| 9/3/19 | 9/3/19 | A0093 | 6374 | complete | 77H | investigate HP# 3 & #1 condensate leak | 9/3/19 clear condensate line, call complete *rn* | |
| 9/3/19 | 10/29/19 | A0094 | 6375 | complete | 633 | chiller #2 - replace rgt thermistor not reading correctly | 9/4 per russo superheat not correct checked out system + found RGTthermistor for circuit B reading off by 30 F new thermistor is on backorder. Due in beginning of october *rn* 10/28 thermistor just came in, frank scheduled for 10/29 **CH- Installed new RGT Thermistor and checked opeeation completd ** | |
| 9/4/19 | A0095 | 6378 | complete | 4 | AHU-8 investigate noise coming from unit. | 9/3/19 problem with ddc talking to vfd, rockhill made adjusts with smargiassi call complete. 9/4 verified operation ok still *rn* | ||
| 9/4/19 | 9/13/19 | A0096 | 6380 | complete | 633 | CRAC-4 (TOAC) investigate noisy unit | 9/12- per reale blower housing needed to be secured and pulleys need to be replaced. will return tomorrow to replace pulleys. 9/13 replaced pulleys checked operation and call is complete *rn* | |
| 9/5/19 | 12/6/19 | A0097 | 6397 | complete | 633 | P104 Cntrl Rm - investigate condensate leak from control | 10/3 need to scheduled asap *rn* 10/4 as per Chris Rockhills discussion from beginning of September; Leak is coming on the outside piping, customer (Nazian and Scholz) wants to reroute and rerun condensate line inside the control house then back into the existing line to prevent flooding issues in a critic space. Waiting for customer to let us know when we are able to get in to rerun. 11/26 chris to followup with customer again today to see if they have a time when we are ok to begin work *rn* ***12/6CH- Bob F was assigned to this call** **12/6CH Picked up parts repair and rerouted condensate lines so it did not leak onto electrical equipment** | |
| 9/5/19 | 10/7/19 | A0098 | 6398 | complete | 4 | glycol leak - investigate glycol leak | 9/6-rockhill- turn the valve off to the unit - cleaned glycol up off of the floor- need to return to look at leak. 9/28 frank russo assigned to call for 10/2 *rn* 10/7 per russo he changed packing and actuator. Call is complete *rn* | |
| 9/5/19 | 9/6/19 | A0099 | 6399 | complete | 633 | UPS Enclosure - investigate condenser fan | 9/5- per rockhill found motor and blade needs to be replaced. ordered and will be ready for pickup tomorrow morning. 9/6 rockhill replaced motor, blade and capactior call complete *rn* | |
| 9/5/19 | 9/6/19 | A0100 | 6405 | complete | 1000 | Chiller #3 - chilled water supply is cycling between 45 - 54 degrees | 9/6 per frank he redid electric connections, removed sensor from well, put heat transfer tape on it and reinstalled sensor in well. call is now complete *rn* | |
| 9/9/19 | 9/12/19 | A0101 | 6420 | complete | 633 | BLDG.- 633- TREE HOUSE SPACE,NEAR MAIN ENTRANCE. - INVESTIGATE WARM | 9/12- Reale & Rockhill- Replaced capacitor & Relay- tested operations completed at this time. | |
| 9/10/19 | 9/10/19 | A0102 | 6449 | complete | 77L | Lab1507- investigate condensate leak from a/c unit. Should have been warranty on Peterson, | 9/10- reale investigated the leak - found the coil headers on evap coil ( recently installed by peterson) - it was installed to far forward which is allowing it to drip overtop of the pan and down the panel to the floor - using a peice of plastic he was able to channel the water back into the pan. blue trash can plastic provided by navy yard escort | |
| 9/11/19 | 9/30/19 | A0103 | 6450 | quote needed | 77L | York chiller - Investigate Halogen Leak Detector alarm | 9/30 service call complete, followup will be a TF-1. found that the Halogen tank filters need to be replaced and will be turned into TF1 per BJ and Smargiassi discussion *rn* | |
| 9/12/19 | 9/17/19 | A0104 | 6476 | complete | 4 | BLDG.- 4 - CAPTAINS CONF. ROOM #1048 - INVESTIGATE ROOM TEMP. IS COLD | 9/17- BJ- had to adjust hand damper in duct work per teti's request, call is complete *rn* | |
| 9/13/19 | 9/17/19 | A0105 | 6481 | complete | 633 | BLDG.- 633 - TOAC CRAC UNITS 12.1 THRU 12.5- INVESTIGATE CONTACTORS | 9/13 chris reale ordered contactors to replace on all units. 9/17 reale replaced all contactors call is complete *rn* | |
| 9/13/19 | 9/13/19 | A0106 | 6482 | complete | 4 | BLDG.- 4 - CIRCULATION PUMP #3 - INVESTIGATE PUMP. | 9/13- Pump is backup pump and was seized, bj greased bearings and got running. Call is complete *rn* | |
| 9/13/19 | 10/4/19 | A0107 | 6484 | complete | 77H | BLDG.- 77H - SPLIT 2, 77H-5 - SPACE IS HOT. | 9/13 rockhill briefly looked at call unit seemed to be ok and space was comfortable. Will reassign later to double check before closing out call *rn* 10/3 BJ scheduled for 10/4 to recheck. 10/4 rechecked and space is still comfortable. Will close out call no time applied *rn* | |
| 9/16/19 | 9/16/19 | A0108 | 6492 | complete | 1000 | BLDG.- 1000 - OUTSIDE ROOM # 286 - INVESTIGATE CONDESATION LEAK.. | 9/16- per Reale - leak is coming from ceiling of 3rd floor and is not HVAC related. Call complete *rn* | |
| 9/18/19 | 9/25/19 | A0109 | 6502 | quote needed | 4 | BLDG.- 4 - AHU-1 - INVESTIGATE NOISY RETURN FAN. | 9/25 per reale motor needs replacement and will need to be a TF-1 *rn* | |
| 9/18/19 | 10/9/19 | A0110 | 6517 | complete | 4 | BLDG.- 4 - ROOM 1030 - INVESTIGATE NO AIR FLOW. (CHERYL DIORISIO X7755) | 9/18 per cheryl this needs to be rescheduled for 10/9 which is the only day she will not be occupying the space. Reale scheduled for 10/9 *rn* 10/9 bob f returned to complete call. Found volumn damper closed. Reopened damper to allow air flow, check operation and call is complete *rn* | |
| 9/20/19 | 10/4/19 | A0111 | 6531 | complete | 4 | FCU-3 - INVESTIGATE NO COOLING ( CEILING FCU 3RD FL RAMP) | 9/4 unit was cooling upon arrival, no time applied. If problem arrised in the future will revisit under new service call | |
| 9/20/19 | A0112 | 6534 | complete | 77L | AC-5- INVESTIGATE OA DAMPERS NOT WORKING | 9/26 per bj began troubleshooting and will need to return. 9/30 per bj found damper linkage needs to be replaced and has on order. 10/1 installed linkage and found that extension arm bracket is also needed, extension arm bracket on order 7-10 business day lead time *rn* 10/23 extention are received, bj scheduled for 11/4 or 11/5 *rn* **CH 11/21- installed damper shaft bracket on unit AC5- connect Pneumatic actuator - found damper is a 90 Degree and the pnumatic actuator will not work w/ damper - further troubleshoot needed. also see service call A0186 *** | ||
| 9/20/19 | 9/20/19 | A0113 | 6535 | complete | 1000 | COOLING TOWER #2- INVESTIGATE HIGH AND LOW WATER | 9/20 per frank checked out cooling tower. No problems found at this time all ok *rn* | |
| 9/24/19 | 9/24/19 | A0114 | 6560 | quote needed | 1000 | AS-10- Investigate condensate leak at unit. | 9/24- per reale pan is corroded and rotting away, he cleaned as much as he could and flushed drain lines to avoid clogs. found bottom of coil rotting away as well. this will be an ongoing problem until coil and pan gets replaced. rockhill will be talking to teti about this, but pan and coil replacement need to be a TF-1. this call is complete 10/3 BJ is going to talk to teti about this as well, teti is not in today *rn* | |
| 9/23/19 | 9/24/19 | A0115 | 6561 | complete | 4 | ROOM 1200/FCU'S-INVESTIGATE CONDENSATE LEAK | 9/24- per Brian s pulled all drain ;line ran cleaner through them and put a new stone french drain ( customer supply) - completed | |
| 9/24/19 | 10/18/19 | A0116 | 6572 | complete | 4 | CHILLER #2- INVESTIGATE CHILLER SURGING | russo scheduled for 10/7. 10/18 rechecked chiller, chiller is still not surging. Closing out call, job complete *rn* | |
| 9/25/19 | 10/8/19 | A0117 | 6578 | complete | 4 | BLDG.- 4 - FCU-67 (S.E.) - INVESTIGATE NO COOLING. | 9/30 as per reale found bad motor and blower wheels. Parts on order, due in week of 10/7 *rn* 10/8 bob f and reale replacement motor and squirrel cage, job is complete *rn* | |
| 9/25/19 | 9/30/19 | A0118 | 6579 | complete | 4 | BLDG.- 4 - FCU-69 (RM. 1500) - INVESTIGATE NO COOLING. (NO AIR MOVEMENT) | 9/30 per reale he replaced speed switch and call is now complete *rn* | |
| 9/27/19 | 10/14/19 | A0119 | 6601 | complete | 4 | BLDG.- 4 - RM. 1500 - INVESTIGATE PNEUMATIC LEAK IN OVERHEAD | 9/27- per reale leak is coming from above the wire tray which was caused by a rub out where the pneumatic line is tied cross thread. reale and BJ will return on 10/3 to relook at job due to the complexity of the repair. *rn* 10/14 per bj him and reale repair leaks on pnuematic line and air compressor. call complete *rn* | |
| 10/1/19 | 10/8/19 | A0120 | 6631 | complete | 633 | BLDG.- 633 - CHWP #2 -ADJUST COUPLING FOR PUMP MOTOR | **ch10/8- made adjustments tp chwp #2 - verfied everything - tested operations - completed **8 | |
| 10/2/19 | A0121 | 6632 | cancelled | 1000 | BLDG.- 1000 - EF-106 - INVESTIGATE NO STATIC PRESSURE. | Cancel call, duplicate of SC# A0031, which BJ is handling and has parts on order for *rn* | ||
| 10/2/19 | 10/2/19 | A0122 | 6659 | complete | 87 | BLDG.- 87 -P-107 ELEVATOR MP SPLIT - CLEAN CONDENSATE COIL ON P-107 ELEVATOR MP SPLIT | 10/2 reale scheduled for this call today *rn*--10/2-Reale- vacuumed coil- cleaned and wiped down grill- completed ch | |
| 10/3/19 | 11/4/19 | A0123 | 6646 | complete | 633 | BLDG.- 633 - VAULT AHU - INVESTIGATE COMPRESSOR STATUS. | Frank r scheduled for 11/4 11/4 per frank r unit operates properly. Compressor barely runs due to the unit being oversized for the space. | |
| 10/3/19 | 10/3/19 | A0124 | 6650 | complete | 4 | BLDG.- 4 - FCU -REPAIR CONDENSATE ON FCU BY EAST HANDICAP DOOR. | *ch10/3- found condensate pan clogged and overflowing- unclogged drain and vacuumed debris and slug from the pan- tested operations completed ** | |
| 10/7/19 | 10/11/19 | A0125 | 6691 | complete | 77L | BLDG.- 77L - ROOM 1500 / AC-1 -COMPRESSOR 1 FAILED TO RUN! | **ch10/11- everything was running - checked operatiuons and everything is okay at this time** | |
| 10/8/19 | 11/4/19 | A0126 | 6693 | complete | 4 | BLDG.- 4 - SPARE CONDENSOR WATER PUMP 3 - THE THERMAL OVERLOAD KEEPS Tripping | **ch10/10- ran the pumps/overloads/ tested amp reading- everything was working fine - Tati requested we order new overloads for unit - 6693-17877- holding until parts come in ** 11/1 overloads received, bob f scheduled for 11/4 *rn* **CH11/21- 11/4- 4H completed -changed motor starter and heaters and start and checked operation -** | |
| 10/8/19 | 11/4/19 | A0127 | 6694 | complete | 1000 | BLDG.- 1000 -CHILLER 1 - THE CHILLER WILL NOT RUN! | 11/1 Frank Russo schedule to check again on 11/4, all has been ok on weekly inspections *rn* chiller call closed out, problem is with pump which a different service call was opened for *rn* | |
| 10/8/19 | 10/18/19 | A0128 | 6692 | quote needed | 87 | BLDG.- 87 -AC-2 - THE RETURN FAN WILL NOT RUN! | **ch10/09- return fan was disconnect was off - also found supply fan vfd is bad will need to further investigate. VFD needs to be replaced and relocated. TF-1 to follow *rn* | |
| 10/10/19 | 2/11/20 | A0129 | 6725 | complete | 4 | BLDG.- 4 - ROOM 1250 / CUBE 23 - INVESTIGATE NOISY VENT - (EILEEN HERNANDEZ | ||
| X3036) | Found the diffuser was noisy. |
Removed and repaired the diffuser.
| 10/10/19 | 10/18/19 | A0130 | 6726 | complete | 633 | BLDG.- 633 - UPS ENCLOSURE - INVESTIGATE CONDENSER NOT RUNNING! | **ch10/10- condensor fan motor slide through the bracket and stopped themotor from running- needs new motor fan, blkade and brackets - parts ordered on 10/10(6726-17876) - waiting for material ** 10/18 bob f installed new motor, check operation and call is complete *rn* |
| 10/10/19 | 10/14/19 | A0131 | 6730 | complete | 4 | Bldg. 4 - AHU-8 Fan Making noise, investigate at 47 Hz. | **ch10/14- found the outside air actuator parts came loose, arm connecting was loose everything was making noise due to the rattling of it all being loose- tighted everything completed ** |
| 10/14/19 | 10/14/19 | A0132 | 6753 | complete | 77H | Bldg. 77H - Investigate HP-1 off in alarm | **ch10/14- found disconnect off - and a blown low voltage fuse - replaced - retuned to service ** |
| 10/14/19 | A0133 | 6754 | quote needed | 87 | Bldg. 87 AC-2 - Investigate supply fan off in alarm. | this is related to the vfds that need to be moved, TF-1 *rn* | |
| 10/14/19 | 10/15/19 | A0134 | 6749 | complete | 1032 | Bldg. 1032 - Investigate Boiler Alarm (Boiler not running) | **ch10/15-investigated found circulator pump needed to be replaced - replaced thermo and circulator pump- added shut off valve- filled and checked boiler completed ** |
| 10/14/19 | 10/14/19 | A0135 | 6752 | complete | 4 | Bldg. 4 - Investigate LP Air Leak at Comnpressor | **ch10/14- found a leak on discharge link on copper 90 - repaired leak |
| 10/15/19 | 10/16/19 | A0136 | 6759 | quote needed | 77H | BLDG.- 77H - AHV-3- INVESTIGATE SUPPLY FAN BLOWER WHEEL! | **ch10/17- investigated and got material list for replacement parts being quoted ** |
| 10/16/19 | 10/21/19 | A0137 | 6777 | complete | 1000 | BLDG.- 1000- ROOM 261/OFFICE SPACE -VAV-2004 LEAKING VALVE | **ch10/17-found valve body leaking from steam- purchased new valve body and actuator- installed but the fan did not start up- have to go back ** 10/21 per bob drained coil, removed and replaced valve. Call complete *rn* |
| 10/16/19 | 12/2/19 | A0138 | 6778 | complete | 4 | BLDG.- 4 - ROOM 963 -INVESTIGATE LEAKING/HISSING WALL STAT | 12/2 - per chris rockhill and bob ferrara, they rechecked this stat again and there is no problem, stat is not hissing or leaking. They did not apply any time to this call *rn* |
| 10/17/19 | 10/14/19 | A0139 | 6670 | complete | 77H | Bldg. 77H - HP#5/6 Investigate excessive condensate. | **ch-10/14-pans were full of water, drained blew out with nitrogen, troubleshot,checked operations eveyrhting okay at this time** |
| 10/18/19 | 10/25/19 | A0140 | 6810 | complete | 542 | GH-1 under mezz- no heat | 10/25 tripped out due to clogged filter. Changed and call is complete *rn* |
| 10/18/19 | 12/18/19 | A0141 | 6827 | quote sent | 633 | UPS ENCLOUSER ( TWO 10 TON SPLIT SYSTEMS) INVESTIGATE THE DIFFERENCE IN THE CONDENSER FAN OPERATION BTW THE TWO UNITS - ON UNIT #2 THE CONDENSOER FAN CYCLES VERY FREEQUETL;Y IT DOESN’T APPEAR THE CONDENSORT FAN FOR UNIT 1 CYCLES AT ALL. | **12/18CH-- checked unit & found fan cycling bad on 1 unit & incorrect type on the other unit- need to install a P66 fan control on each unit- Beyond scope of work needs TF1** |
| 10/22/19 | 10/22/19 | A0142 | 6828 | complete | 520 | GAS PIPING - INVESTIGATE OPEN ENDED GAS PIPING | investiaged the job there is another contractor onsite there is a gas line that runs through - they wants to know if we could add a valve on there to get it back on - this other contractor to completed if he gets it done then we dont contunine they do if they dont compete we will contunine - 2H not competed. 1/16 closing call out, if customer needs us to open up a call later we will *rn* |
| 10/22/19 | 10/23/19 | A0143 | 6829 | complete | 77L | RTU-1 MELVILLE- INVESTIGATE UNIT WILL NOT RUN | 10/28- Bob - job is completd - repaired loose connections and melted wiring. Replaced vfd *rn* |
| 10/23/19 | 10/23/19 | A0144 | 6835 | complete | 77L | NSWC-A-0144- Biler Reapire - Replace the valve | 10/23- Bob - job is completd - installed new actuator gas valve and had to take it apart and put it back together. |
| 10/23/19 | 1/27/20 | A0145 | 6876 | complete | 633 | HVU-1 (P104) EXHAUST Fan- vfd trips once a week. | frank r scheduled for 1/17/20 - found VFD in alarm, reset alarm |
check alarm history started troubleshooting for overcurrent alarm, but VFD & motor running within oarameters st this time need to return & continue troubleshooting if & when VFD trips again
| 10/25/19 | 10/25/19 | A0146 | 6887 | complete | 77H | 77H Boiler Room investigate wate rleak @ valve by meter | 10/25 per bob d replaced valve, call is complete *rn* |
| 10/26/19 | 10/31/19 | A0147 | 6901 | complete | 4 | service- service fcu's in SE pavilion ( Change filters, clean, check cooling operation) as funriture is not currently blocking units. | **Completed Pm - had a blockage in the coil or on the line - flushed everyhting out cleaned coil - took the temps and evryhting is working at this time -ch |
| 10/28/19 | 11/12/19 | A0148 | 6903 | complete | 77L | Lab 703- ductless split system- investigate water spitting out | 11/12 Flushed Pan out sucked condensate lines - put pan taps in pump and pan and cleaned evap and washed filters -ch |
| 10/28/19 | 12/5/19 | A0149 | 6904 | quote needed | 29 | checm lab - rtu 1 - relocate vfd from missing box to electrical cabinet | **12/5CH-The vfd continues to go into alarm when it is hot out. |
The current vfd in the unit is wore out it needs to be replaced The vfd needs to be moved to the compressor section of the unit This will involve rewiring the supply fan wiring.
This is beyond the scope of work and is a TF1**
| 10/28/19 | 11/12/19 | A0150 | 6914 | 4 | room 3800 3rd fl south cube 19- investigate air blowing directly on customer | 11/12 ** Reloacted the diffuser and reconneded - completed -ch. Relocating diffuser is should not be part of the contract, service calls need to stop being placed for relocating them *rn* | |
| 9/11/19 | A0151 | 6915 | complete | 77L | RTU-1 Melville, Investigate Exhaust Fan and compressors not running | completed under different service call per rockhill, no time applied *rn* | |
| 10/29/19 | 10/30/19 | A0152 | 6916 | complete | 633 | High Bay Northeast- Investigate Gas smell Near IR9- ** See smagrassi w/ any questions | ** found another leak at regulator on IR9, repaired leak on regulator vent plug |
-area still has a slight gas odor
- leaked check IR8 too and did not find anymore leaks- CH
| 10/29/19 | 12/5/19 | A0153 | 6917 | complete | 29 | Room 108 - Clean Diffusers | **12/5CH- Cleaned (3) Diffusers in the space ** |
| 10/29/19 | 1/17/20 | A0154 | 6927 | complete | 4 | Roof top Chiller - Investigate Alarm | 1/17/20 per frank low saturated alarm, unit is down for winter. In past he took care of under PM and will revisit in spring during pm *rn* |
| 10/29/19 | 11/8/19 | A0155 | 6928 | complete | 776 | Fuel Cell Building - Investigate No Heat | 11/8 Found breaker off at amin power to the thermostat- thermostat wires were cut inside the wall- ran thermostat wire checked operation completed - ch |
| 10/29/19 | A0156 | /A | 433 | Per Email Chain - Building 433 is not on Core Mechanicals Equipment List | |||
| 10/30/19 | 11/8/19 | A0157 | 6929 | complete | 670 | UH-1 And UH-2- Investigate No Heat | 11/8 Investigated found pilot and flame sensor assembly bad - got parts installed new poilt and flame senor assembly -ch |
| 10/30/19 | 11/22/19 | A0158 | 6930 | complete | 77H | UH-7- Investigate no Heat | **11/22CH-Found the heat was off. |
Check over the unit.
Found it tripped the high limit.
Reset the unit Unit is operational this time
| 10/31/19 | 11/1/19 | A0159 | 6941 | complete | 633 | Northeast Corner High Bay - Investigate Gas Leak | 11/1 found leak on T's - purchased blakc Ion Fittings- picked up fittings for repair lines removed flex gas line plugged t w/ black iron plug - turned gas on checked for more leaks no leaks and no more gas smell in the area compleetd -ch |
| 10/31/19 | 11/1/19 | A0160 | 6953 | complete | 4 | Room 1411- Investigate No cooling | 11/1 flushed coils from supply and return water until it was clean completed -ch |
| 10/31/19 | 11/18/19 | A0161 | 6971 | complete | 1000 | boiler 1- investigate boiler not running | 11/8 connection board is bad have to get new one on hold -ch. 11/18 replaced board, and repair wire call is complete *rn* |
| 11/1/19 | 11/22/19 | A0162 | 6976 | complete | 745 | vestibule - investigate no heat | **11/22CH- Found the heat was off. |
Check over the unit.
Found it tripped the high limit.
Reset the unit Unit is operational this time
| 11/4/19 | 12/31/19 | A0163 | 6973 | complete | 1000 | vestibule - investigate no heat | **12/31CH- Found the fan coil was not working. Found a cube relay overheated and began to melt Also a communication board was not working Replaced the cube relay Check all wiring connections found several loose wiring connections. Repaired the wiring connections. Reset the unit is running ok now. |
| 11/4/19 | 11/21/19 | A0164 | 6974 | complete | 4 | Server Room 2800- investigate AC error code - short cycle comprssor #1 | **CH11/20- - checked unit for proper operation - ok |
- unit seems to be short cycling because unit setpoint, is 2 degrees higher then other unit that serves same area
- adjusted setpoints, will folliw up to see if adjustments solved the short cycling issue** **11/21CH- followed up to check proper operation of Lieberts 4 & 5
- found units fighting each other, one running cooling & other heating
- adjusted both unit setpoints to 68.0°F & Sensativity to 3.0°F
- determined short cycling issue is because of low load
- to correct short cycling customer should run one unit at a time & leave other for a backup or Control both units together & setup up for 4 stages of cooling**
| 11/4/19 | 11/21/19 | A0165 | 7013 | complete | 29 | Boiler Room - Repair & Makeup Hot water | **CH 11/21-cut and measure new pvc piping for the back flow preventor drain hung new pipe hangers up got it leveled and outside- completed** |
| 11/4/19 | A0166 | 7014 | quote needed | 29 | Boiler #1 - Pump - investigate & Repair pump noise | ** CH11/21- Got pump information further troublehsoot needed- contacting venders). Pump needs to be replaced. Will be TF-1 *rn* | |
| 11/4/19 | 12/10/19 | A0167 | 7015 | complete | 1000 | Chiller #1 - condense Pump - Investigate & Repair Chiller #1 condense pump | **12/2CH- valved off pump and drained |
- disconnected motor to pump coupling
- removed pump from housing to check impeller - ok
- re-assembled pump and motor coupling
- can't run pump because cooling tower drained for winter. Will retest on cooling startup** Have to recheck in the spring**
| 11/4/19 | 11/4/19 | A0168 | 6979 | complete | 29 | Boiler #2 - investigate relief valve piping | **11/4- repipe boiler relief valve drain lines per customers request. Call complete *rn* |
| 11/4/19 | 11/6/19 | A0169 | 6980 | complete | 29 | Boiler #2 Investigate alarm | **11/4&11/5- investigated - found rib relays incorrect - purchased cprrect relays and installed - completed -ch |
| 11/5/19 | 12/19/19 | A0170 | 7016 | complete | 77L | Room 1500, AC1-Inestigate Compressor #1 Failed to Run | **12/19CH- checked the preassures and voltage at compressor - found unit running and cyclng as normal operations - unit is okay at this time ** |
| 11/5/19 | 11/5/19 | A0171 | 7017 | quote needed | 77L | S-1 AC-1- HW Vlave is passing, valve is in chiller room above compressor | 11/5- Investigated overheating- vinny & bob found the actuator stuck- worked on getting it off the by pass was open so there is no control valve body and actuator - shut off valve needs to be turned into a TF1-ch |
| 11/5/19 | 11/6/19 | A0172 | 7003 | complete | 4 | Penthouse- Repair Valve Handle | *11/6- Repaired valve - completed - ch |
| 11/5/19 | 5/20/20 | A0173 | 7018 | complete | 77L | AC-5- Replace Pneumatic Actuator w/ digital actuator | Needs linkage, on backorder from greenheck. Also related to SC# 186. schedule both together *rn* |
| 11/5/19 | 11/15/19 | A0174 | 7019 | complete | 4 | Boilers- Pipe Boiler PRV's to drain | **11/15- pro pressed the piping and the unions together and attached to the extisting prv 2H completed-ch |
| 11/5/19 | 11/22/19 | A0175 | 7020 | complete | 4 | Boiler Emergency off switch - repair broken cover on boiler emergency shut down | **11/12- Checked E- Stop for boiler - found lockout cover broken - need to return w/ new lock out cover and install . 11/22 Frank r completed *rn* |
| 11/5/19 | 11/7/19 | A0176 | 7021 | complete | 4 | ACU-101-Inestigate leak at drain Pan | **11/7- picked up material from supply house. complete |
| 10/25/19 | 12/3/19 | A0177 | 7022 | complete | 4 | Inestigate and repair viberation from Leibert Units 4/5 | **11/5- Investigate Vibration & Noise issues, replaced belts which helped alittle but compressor may be an issue, will return to investigate. 11/21 - found floor plenum not sealed, behind Liebert #5, which is causing rattling noise and possibly the Vibration. The area behind unit is not sealed, is very difficult to access but will return to put insulation in area to try and help with noise, you really cant access the plenum floor area so this will just be an attempt to help with the noise. frank scheduled to return 12/2 *rn* **12/3CH- Sealed off floor plenum behind unit w/ insulation to stop noise and Vibration** |
| 11/6/19 | 12/11/19 | A0178 | 7031 | quote needed | 29 | Room 108- Mess Level- Investigate Air Flow, Jeff Gosch X8765 | **12/5CH- Found the diffusers in the space to have either too much and some to little in others airflow. |
Look over the ductwork to find the balancing dampers.
Going to need to go in the room next door to find the dampers.
Need to work with facilities to correct the issues- other room is a restricted area ** **12/11ch- Had to find a escort to get in the secured space Trace out the ductwork Found the balancing damper was broken this is beyond a call a TF1 is going to be written up and sent to the office**