This solicitation is for facilities investment services for preventive maintenance, repair, and alteration of heating, ventilation, and air conditioning (HVAC) equipment at sites in Philadelphia, Pennsylvania. The anticipated contract will be for a base period of five years with four one-year option periods not exceeding 60 months total. Services include all labor, management, supervision, tools, material, and equipment necessary to perform HVAC services. Offerors must register in the System for Award Management database, with active registration required at time of proposal submission and maintained through final invoice payment if awarded the contract. The soliciting agency is the Department of the Navy Naval Facilities Engineering Command.
View the file
Other files
Show all 24
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
For the best experience, open this PDF portfolio in
Acrobat X or Adobe Reader X, or later.
Get Adobe Reader Now!
http://www.adobe.com/go/reader
CERTIFICATION MANAGEMENT DIVISION
BOILER INSPECTION REPORT
NAVAL FACILITIES ENGINEERING COMMAND MID-ATLANTIC
Philadelphia ANNEXSupervisor Utilities
UEM PHILADELPHIA
PHILADELHIA UEM
National Board: 229348 Serial: H12H10229348
Manufacturer: Lochinvar Boiler Model: KBN601
Asset:
Year Built:2012
Shipyard Site
Capacity: 600,000 BTUH
Type: Coil Production: Hot Water Use: Heat
Boiler Data
Building: 1 Property No. B2 1350390953B-
Operational Controls: Lochinvar
Last Strength Test: Strength Test Result:
Design:
Operating:
Test:
Pressure Test Result: Satisfactory
Pressure Test Comment:
Internal: 11/2/2020 External: 11/2/2020 Hydrostatic: 11/5/2020 Operation: 11/5/2020
394 394 394 394
Inspection Dates
Inspection Results
Nonexistent
Waterside Condition:
Fireside Condition: Satisfactory psi psi psi
Manufacturer: Weksler Calibration Date: 10/28/2019
Calibration Comments:
PSI: 0-100 Degrees: 30--230
Feed Water Treatment
Unsatisfactory
Pressure
Pressure Guage
F o
Internal/ExternalComment:
Internal inspection sat.
Burner Equipment
Manufacturer
Type
Fuel Grade
In Service Alternate
Lochinvar None
Ceramic None
Natural Gas None
Safety Valves
Reason If Not Certified
Inspector: John Gilb (NAVFAC 394)
General Comments
Need to start an chemical program. In order to test the high gas switch it will have to be relocated behind the manual gas valve.
Expires On: 11/30/2021
Wayne Carper By Direction
Inspectors
Dates
Certificate Issued: Yes
Manufacturer Capacity Size
PSI
Setting Condition Comment Reseat
Watts 1,352,000 BTU .75 50 Satisfactory Test Manual Testin
For questions, comments or to schedule next inspection call the Certification Management Division at 757-462-4750 Page 1 of 2
Forced Draft " WC
Smoke Test:
Combustion CO2: 8.69
Stack Temperature: 110
Combustion Efficiency: 94
Combustion DataCombustion Characteristics
Basis: Dry
Before: CO (PPM): 16
After: CO (PPM): % excess O2:
% excess O2: 5.5
Component Test Result
SatisfactoryFlame Safeguard System
SatisfactoryAir-to-Fuel Ratio Control System
SatisfactoryHigh Gas Pressure Control
SatisfactoryCombustion Air Speed Control
SatisfactoryHigh Temperature 200F
SatisfactoryFlame Pattern
SatisfactoryWater Flow Switch
SatisfactoryCirculation Pump
SatisfactoryEmergency Switch
SatisfactoryLow Gas Pressure Control
SatisfactoryLow Water Probe w/Manual Reset
SatisfactoryOperational Temperature
SatisfactoryHigh Temperature w/Manual Reset
SatisfactoryBurner
For questions, comments or to schedule next inspection call the Certification Management Division at 757-462-4750 Page 2 of 2
2020-11-10T09:50:02-0500
GILB.JOHN.CARL.1206717226
National Board: Serial:
Manufacturer: Weil McLain Boiler Company Model: LGB-5
Year Built:2017
Capacity: 520 PPH
Type: Cast Iron Production: Steam Use: Heat
Building: 712 Property No. B1 1572443397B-
Operational Controls: UT Electronics
Internal: 11/2/2020 External: 11/2/2020 Hydrostatic: 11/4/2020 Operation: 11/5/2020
Existing
Waterside Condition: Satisfactory
Manufacturer: U. S. Gauge Calibration Date: 10/30/2019
Calibration Comments: Comparison Tested
PSI: 0-30 Degrees:
Satisfactory
Weil McClain None
Gas Tray None
Apollo 643 PPH 1,0 15 Satisfactory Test Manual Testin
For questions, comments or to schedule next inspection call the Certification Management Division at 757-462-4750 Page 1 of 2
Natural Draft
Combustion CO2: 6.9
Stack Temperature: 269
Combustion Efficiency: 84
Before: CO (PPM): 0
% excess O2: 8.7
SatisfactoryOperational Steam Pressure 2-5 psi
SatisfactoryLow Water/Condensate Pump Control
SatisfactoryHigh Steam Pressure 8 psi
SatisfactoryLow Water Cut-Off w/Manual Reset
For questions, comments or to schedule next inspection call the Certification Management Division at 757-462-4750 Page 2 of 2
2020-11-10T09:44:26-0500
GILB.JOHN.CARL.1206717226
National Board: 217216 Serial: G12H10217216
Manufacturer: Lochinvar Boiler Model: KBN701
Capacity: 700,000 BTUH
Building: 1 Property No. B3 1534076271B-
PSI: 0-100 Degrees: 30-230
Internal inspection sat, Need to start a chemical program. In order to test the high gas switch it will have to be relocated behind the manual gas valve.
For questions, comments or to schedule next inspection call the Certification Management Division at 757-462-4750 Page 1 of 2
Combustion CO2: 8.47
Stack Temperature: 109
Combustion Efficiency: 94
Before: CO (PPM): 19
% excess O2: 5.9
SatisfactoryHigh Temperature
For questions, comments or to schedule next inspection call the Certification Management Division at 757-462-4750 Page 2 of 2
2020-11-10T09:48:53-0500
GILB.JOHN.CARL.1206717226
National Board: Serial: CP7633234
Year Built:2018
Building: 712 Property No. B2 1731563258B-
No leaks
Internal: 8/15/2022 External: 8/15/2022 Hydrostatic: 8/16/2022 Operation: 8/16/2022
Manufacturer: U. S. Gauge Calibration Date: 10/31/2019
Soft deposits on waterside. Have CORE start water softening/chemistry.
Weil McLain None
Flame safeguard system trips boiler , but it must be electrically reconnected to start boiler. Investigate wiring of safeguard system.
Expires On: 8/31/2023
Brock Frey By Direction
Apollo 643 PPH 1.0 15 Satisfactory Test Manual Testin
For questions, comments or to schedule next inspection call the Certification Management Division at 757-462-4750 Page 1 of 2
Combustion CO2: 6.61
Stack Temperature: 189
Combustion Efficiency: 86
Before: CO (PPM): 1
% excess O2: 9.2
SatisfactoryHigh Steam Pressure 8psi
For questions, comments or to schedule next inspection call the Certification Management Division at 757-462-4750 Page 2 of 2
2022-08-17T11:24:33-0400
GILB.JOHN.CARL.1206717226
National Board: 228317 Serial: H12H10228317
Building: 1 Property No. B1 1572289926B-
Internal: 8/15/2022 External: 8/15/2022 Hydrostatic: 8/15/2022 Operation: 8/15/2022
Need to establish a water treatment program. In order to test the high gas switch it will have to be relocated behind the manual gas valve.
Apollo 697,000 BTU .75 50 Satisfactory Test Manual Testin
For questions, comments or to schedule next inspection call the Certification Management Division at 757-462-4750 Page 1 of 2
Combustion CO2: 8.98
Stack Temperature: 134
Combustion Efficiency: 89
Before: CO (PPM): 18
% excess O2: 5
High Gas Pressure Control
For questions, comments or to schedule next inspection call the Certification Management Division at 757-462-4750 Page 2 of 2
2022-08-15T14:01:32-0400
GILB.JOHN.CARL.1206717226
Internal: 8/15/2022 External: 8/15/2022 Hydrostatic: 8/16/2022 Operation: 8/16/2022
Manufacturer: U. S. Gauge Calibration Date: 10/30/2019 soft deposits on watersides. Have CORE start water softening/chemistry.
Weil McClain None
Flame safeguard system trips boiler but must be electricallly reconnected to resart. Investigate wiring of safeguard system.
Apollo 643 PPH 1,0 15 Satisfactory Test Manual Testin
For questions, comments or to schedule next inspection call the Certification Management Division at 757-462-4750 Page 1 of 2
Combustion CO2: 8.02
Stack Temperature: 177
Combustion Efficiency: 87
Before: CO (PPM): 7
% excess O2: 6.7
SatisfactoryHigh Steam Pressure 8 psi
For questions, comments or to schedule next inspection call the Certification Management Division at 757-462-4750 Page 2 of 2
2022-08-17T11:27:35-0400
GILB.JOHN.CARL.1206717226
PSI: 0-100 Degrees: 30--230
Need to start an chemical program. In order to test the high gas switch it will have to be relocated behind the manual gas valve.
For questions, comments or to schedule next inspection call the Certification Management Division at 757-462-4750 Page 1 of 2
Combustion CO2: 8.75
Stack Temperature: 133
Combustion Efficiency: 89
Before: CO (PPM): 23
% excess O2: 5.4
For questions, comments or to schedule next inspection call the Certification Management Division at 757-462-4750 Page 2 of 2
2022-08-15T14:04:27-0400
GILB.JOHN.CARL.1206717226
Need to start a chemical program. In order to test the high gas switch it will have to be relocated behind the manual gas valve.
For questions, comments or to schedule next inspection call the Certification Management Division at 757-462-4750 Page 1 of 2
Combustion CO2: 8.36
Stack Temperature: 128
Combustion Efficiency: 90
Before: CO (PPM): 30
% excess O2: 6.1
For questions, comments or to schedule next inspection call the Certification Management Division at 757-462-4750 Page 2 of 2
2022-08-15T14:07:08-0400
GILB.JOHN.CARL.1206717226
National Board: 241961 Serial: G12H00241961
Manufacturer: Lochinvar Boiler Model: CHN0992
Capacity: 990,000 BTUH
Building: 1081 Property No. B1 -1662933673B-
Manufacturer: Unknown Calibration Date: 10/30/2019
PSI: 0-75 Degrees: 50-320
Need to establish a water treatment program. The emission test only reflects 2 stages of burners on due to warm weather and no load on building.
For questions, comments or to schedule next inspection call the Certification Management Division at 757-462-4750 Page 1 of 2
Combustion CO2: 5.19
Stack Temperature: 153
Before: CO (PPM): 150
% excess O2: 11.7
SatisfactoryCombustion Air Control
For questions, comments or to schedule next inspection call the Certification Management Division at 757-462-4750 Page 2 of 2
2020-11-10T09:43:21-0500
GILB.JOHN.CARL.1206717226
National Board: 241962 Serial: G12H00241962
Manufacturer: Lochinvar Boiler Model: CHNo992
Building: 1081 Property No. B2 1957673712B-
For questions, comments or to schedule next inspection call the Certification Management Division at 757-462-4750 Page 1 of 2
Combustion CO2: 4.01
Stack Temperature: 172
Combustion Efficiency: 83
Before: CO (PPM): 51
% excess O2: 13.8
For questions, comments or to schedule next inspection call the Certification Management Division at 757-462-4750 Page 2 of 2
2020-11-10T09:42:08-0500
GILB.JOHN.CARL.1206717226
Internal: 11/2/2020 External: 8/16/2022 Hydrostatic: 11/5/2020 Operation: 8/16/2022
For questions, comments or to schedule next inspection call the Certification Management Division at 757-462-4750 Page 1 of 2
Combustion CO2: 7.23
Stack Temperature: 167
Combustion Efficiency: 88
Before: CO (PPM): 100
% excess O2: 8.1
For questions, comments or to schedule next inspection call the Certification Management Division at 757-462-4750 Page 2 of 2
2022-08-17T11:31:36-0400
GILB.JOHN.CARL.1206717226
Internal: 11/2/2020 External: 8/17/2022 Hydrostatic: 11/5/2020 Operation: 8/17/2022
For questions, comments or to schedule next inspection call the Certification Management Division at 757-462-4750 Page 1 of 2
Combustion CO2: 4.63
Stack Temperature: 165
Before: CO (PPM): 50
% excess O2: 4.63
For questions, comments or to schedule next inspection call the Certification Management Division at 757-462-4750 Page 2 of 2
2022-08-17T11:35:12-0400
GILB.JOHN.CARL.1206717226
National Board: 228330 Serial: N12H10228330
Manufacturer: Lochinvar Boiler Model: KBN 601
Year Built:2012Capacity: 600,000 BTUH
Building: 1082 Property No. B1 1572368703B-
Pressure Test Result:
Internal: 12/14/2017 External: 11/2/2020 Hydrostatic: 11/5/2020 Operation: 11/5/2020
394 372 394
Boiler is already running for season.
Need to establish a water treatment program. Boiler is running for the season. Operational test only.
For questions, comments or to schedule next inspection call the Certification Management Division at 757-462-4750 Page 1 of 2
National Board: 228330 Serial: N12H10228330
Manufacturer: Lochinvar Boiler Model: KBN 601
Year Built:2012Capacity: 600,000 BTUH
Building: 1082 Property No. B1 1572368703B-
Combustion CO2: 7.9
Stack Temperature: 120
Before: CO (PPM): 3
% excess O2: 6.9
For questions, comments or to schedule next inspection call the Certification Management Division at 757-462-4750 Page 2 of 2
2020-11-10T09:41:04-0500
GILB.JOHN.CARL.1206717226
National Board: 228312 Serial: H12H10228312
Building: 1082 Property No. B2 35050885B-
Internal: 12/14/2017 External: 11/2/2020 Hydrostatic: 11/5/2020 Operation: 11/5/2020
394 394 394
Boiler is already running for the season.
Need to establish a water treatment program. Boiler is on for the season. Operational only. Safety valve leaks. Replace before next inspection.
For questions, comments or to schedule next inspection call the Certification Management Division at 757-462-4750 Page 1 of 2
National Board: 228312 Serial: H12H10228312
Building: 1082 Property No. B2 35050885B-
Combustion CO2: 5.31
Stack Temperature: 123
Before: CO (PPM): 40
% excess O2: 11.5
SatisfactoryHigh Temperature 210F
For questions, comments or to schedule next inspection call the Certification Management Division at 757-462-4750 Page 2 of 2
2020-11-10T09:39:44-0500
GILB.JOHN.CARL.1206717226
National Board: 242020 Serial: G12H00242020
Manufacturer: Lochinvar Boiler Model: CHN0402
Capacity: 399,999 BTUH
Building: 545 Property No. B1 -659356629B-
PSI: 0-75 Degrees: 60-260
For questions, comments or to schedule next inspection call the Certification Management Division at 757-462-4750 Page 1 of 2
Combustion CO2: 8.64
Stack Temperature: 224
% excess O2: 5.6
For questions, comments or to schedule next inspection call the Certification Management Division at 757-462-4750 Page 2 of 2
2020-11-10T09:47:50-0500
GILB.JOHN.CARL.1206717226
For questions, comments or to schedule next inspection call the Certification Management Division at 757-462-4750 Page 1 of 2
Combustion CO2: 8.64
Stack Temperature: 224
% excess O2: 5.6
For questions, comments or to schedule next inspection call the Certification Management Division at 757-462-4750 Page 2 of 2
2020-11-10T09:46:40-0500
GILB.JOHN.CARL.1206717226
For questions, comments or to schedule next inspection call the Certification Management Division at 757-462-4750 Page 1 of 2
Combustion CO2: 8.75
Stack Temperature: 244
Before: CO (PPM): 37
% excess O2: 5.4
For questions, comments or to schedule next inspection call the Certification Management Division at 757-462-4750 Page 2 of 2
2022-08-17T11:39:17-0400
GILB.JOHN.CARL.1206717226
National Board: 242021 Serial: G12H00242021
Building: 545 Property No. B2 1991367241B-
Need to establish a water treatment program.
For questions, comments or to schedule next inspection call the Certification Management Division at 757-462-4750 Page 1 of 2
National Board: 242021 Serial: G12H00242021
Building: 545 Property No. B2 1991367241B-
Combustion CO2: 8.47
Stack Temperature: 213
Before: CO (PPM): 27
% excess O2: 5.9
For questions, comments or to schedule next inspection call the Certification Management Division at 757-462-4750 Page 2 of 2
2022-08-17T11:41:58-0400
GILB.JOHN.CARL.1206717226
Need to establish a water treatment program. In order to test the high gas switch it will have to be relocated behind the manual gas valve.
For questions, comments or to schedule next inspection call the Certification Management Division at 757-462-4750 Page 1 of 2
Combustion CO2: 9.08
Stack Temperature: 107
Combustion Efficiency: 95
Before: CO (PPM): 20
% excess O2: 5.5
High Gas Pressure Control
For questions, comments or to schedule next inspection call the Certification Management Division at 757-462-4750 Page 2 of 2
2020-11-10T09:51:04-0500
GILB.JOHN.CARL.1206717226
No leaks
Internal: 11/2/2020 External: 11/2/2020 Hydrostatic: 11/4/2020 Operation: 11/5/2020
Manufacturer: U. S. Gauge Calibration Date: 10/31/2019
Waterside and firesides clean. No scale present
Weil McLain None
Apollo 643 PPH 1.0 15 Satisfactory Test Manual Testin
For questions, comments or to schedule next inspection call the Certification Management Division at 757-462-4750 Page 1 of 2
Combustion CO2: 7.8
Stack Temperature: 235
Before: CO (PPM): 11
% excess O2: 7.1
SatisfactoryHigh Steam Pressure 8psi
For questions, comments or to schedule next inspection call the Certification Management Division at 757-462-4750 Page 2 of 2
2020-11-10T09:45:36-0500
GILB.JOHN.CARL.1206717226