GSA WNRC Retaining Wall-100_ Final Submission-Project Manual.pdf

PDF 819 KB Posted

Attached to
SOLICITATION NOTICE FY24 NCR Construction IDIQ
Solicitation number
NCRFY24SolicitationConstructionIDIQ
Issued by

About this file

This document contains structural calculations and design details for a retaining wall project at the Washington National Records Center in Suitland, Maryland. The project involves repairing an existing retaining wall, including calculations for a restrained retaining wall with tie beams, cantilevered retaining wall segments of varying heights, and a concrete tie beam to connect the wall sections. The calculations determine soil pressures, sliding resistance, overturning stability, footing sizing, rebar requirements, and other structural elements. Reinforcing details, load combinations, and allowable stresses are provided. The scope of work includes demolition and replacement of failing portions of the retaining wall surrounding the facility.

View the file

Other files

File Type Posted
Solicitation Amendment 47PM0123R0023_0010-executed 24 01 09.pdf PDF
Solicitation Amendment 47PM0123R0023_0009-executed 24 01 05.pdf PDF
Bid Form_version 8_2024 01 05 .xlsx XLSX spreadsheet
RFI Round 3 Clarifications-FINAL 23 12 20.pdf PDF
GSA WNRC-Geotechnical Report-20210621.pdf PDF
UNIT PRICING SHEET for SEED WNRC RET WALL.xlsx XLSX spreadsheet
GSA WNRC Retaining Wall-100_ Final Submission-Project Manual 2312 20.pdf PDF
Solicitation Amendment 47PM0123R0023_0008-executed 23 12 20.pdf PDF
RFI Clarifications - IDIQ 2024 - Round 2 RFI.pdf PDF
Site Visit Attendee List 23 10 17.pdf PDF
Solicitation Amendment 47PM0123R0023_0007-executed 23 12 19.pdf PDF
Solicitation Amendment 47PM0123R0023_0006-executed 23 12 11 .pdf PDF
MDE Stamped Plans - WNRC Ret Wall Replacement GSA-Site Plans-2022-02-23.pdf PDF
Solicitation Amendment 47PM0123R0023_0005-executed 23 12 01.pdf PDF
SOW 2023 12 1_rev.pdf PDF
Bid Form version 7_23 12 01.xlsx XLSX spreadsheet
22-SF-0088 - MDE Final Approval - WNRC Ret Wall Replacement GSA.pdf PDF
055213 Pipe and Tube Railings.pdf PDF
RFI Response 23 12 01.pdf PDF
Solicitation Amendment 47PM0123R0023_0004-executed 23 11 28.pdf PDF
Solicitation Amendment 47PM0123R0023_0003 .pdf PDF
Form D - Subcontractor Relationships Form v2 23 11 07.docx DOCX document
Form E-IDIQ Management Plan V1 23 11 07.docx DOCX document
Form B - Prior Experience Form v2 23 11 07.docx DOCX document
Form C - Key Personnel Form v2 23 11 07.docx DOCX document
The Solicitation v2 23 11 07.pdf PDF
Solicitation Amendment 47PM0123R0023_0002-executed 23 10 30.pdf PDF
NCR Pre-Proposal Conference Presentation 10 16 2023v1.pdf PDF
Solicitation Amendment 47PM0123R0023_0001-executed 23 10 16 .pdf PDF
Virtual Site Visit Attendees 23 10 16.pdf PDF
Form D - Subcontractor Relationships Form v1 23 10 12.docx DOCX document
47PM0123R0023 SF1442 v1 23 10 12.pdf PDF
Form B - Prior Experience Form v1 23 10 12.docx DOCX document
Form C - Key Personnel Form v1 23 10 12.docx DOCX document
Wage Determination MD20230054 23 09 01.pdf PDF
Offeror Representations and Certifications Form 23 10 05.pdf PDF
SEED SOW 23 02 16.pdf PDF
GSA Form 527.pdf PDF
Site Visit Authorization Request (VAR) Template.xlsx XLSX spreadsheet
Pre-Proposal Request for Information (RFI) Template.xlsx XLSX spreadsheet
The Solicitation 23 10 05.pdf PDF
SF1442 47PM0123R0023 .pdf PDF
Form F - Socio Economic Status Form.docx DOCX document
GSA WNRC Retaining Wall-100_ Final Submission-Drawings .pdf PDF
Form E-IDIQ Management Plan.docx DOCX document
GSA WNRC Retaining Wall-100_ Final Submission-Specifications.pdf PDF
Price Proposal Pricing Bid Form.xlsx XLSX spreadsheet
The Agreement 23 10 05.pdf PDF
Form A - Past Performance Form.docx DOCX document
Form C - Key Personnel Form.docx DOCX document
Show 40 more

Latest 50 of 52 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PROJECT MANUAL

(100% FINAL Submission)

WASHINGTON NATIONAL RECORDS

RETAINING WALL PROJECT

SUITLAND FEDERAL CENTER

4205 SUITLAND ROAD; SUITLAND, MARYLAND 20746

Submitted to:

GENERAL SERVICES ADMINISTRATION

NATIONAL CAPITAL REGION

1800 F STREET, NW ROOM 4040

WASHINGTON, DC 20405

RFQ #47PM0420R0023

Submitted by:

JANUARY 11, 2022

PROPERTY OF THE UNITED STATES GOVERNMENT

COPYING, DISSEMINATION, OR DISTRIBUTION OF THESE DRAWINGS, PLANS, OR SPECIFICATIONS TO

UNAUTHORIZED USERS IS PROHIBITED

Do not remove this notice

Properly destroy documents when no longer needed

TABLE OF CONTENTS

1. Structural Calculations

Consulting Structural Engineers

11800 Sunrise Valley Drive, Suite 430 Reston, Virginia 20191

Telephone: (703) 556- 0651 Facsimile: (703) 481- 0378 Email: Mcma@mcmse.com

STRUCTURAL CALCULATIONS

WNRC Retain Wall Design

Suitland, MD

Prepared for: U.S. General Services Administrations

Prepared by: McMullan & Associates, Inc.

M&A Project No. 3638-60

JANUARY 06, 2022

PROJECT DESIGN CRITERIA

Restrained Retaining Wall LIC# : KW-06014738, Build:20.21.10.12 MCMULLAN & ASSOCIATES (c) ENERCALC INC 1983-2021

DESCRIPTION: Wall with Tie Beam

Project File: WNRC Retaining Wall.ec6

Project Title: WNRC Retaining Wall Engineer: JDO Project ID: 3989-05 Project Descr: Retaining Wall Repair

Code References Calculations per IBC 2018 1807.3, CBC 2019, ASCE 7-16

22.0 0.50

40.0

3,500.0

55.4

0.0 psf/ft

318.0

Criteria Soil Data

Retained Height = ft Wall height above soil = ft

At-Rest Heel Pressure = psf/ftft=

Slope Behind Wall Height of Soil over Toe in pcf

135.0= Soil Density

Passive Pressure = psf/ft

Allow Soil Bearing = psf

Total Wall Height

14.50Top Support Height = ft

Soil height to ignore Footing||Soil Friction = 0.4 psf for passive pressure = 12 in

Equivalent Fluid Pressure Method

Surcharge Loads Adjacent Footing Load

250.0 Lateral Load = #/ft

Axial Load Applied to Stem Wall to Ftg CL Dist = ft

Uniform Lateral Load Applied to Stem

Surcharge Over Heel = psf Adjacent Footing Load = lbs

Axial Dead Load = lbs

Footing Type Line Load

Surcharge Over Toe psf Footing Width = ft...Height to Top = ft Eccentricity = in...Height to Bottom = ft

>>>Used To Resist Sliding & Overturning

Used for Sliding & Overturning

Poisson's Ratio

= ft Axial Live Load =

Base Above/Below Soil lbs

Axial Load Eccentricity = Wind acts left-to-right toward retention side. = at Back of WallWind on Exposed Stem = 0.00 psf

0.3in

Load Type (Strength Level) Wind (W)=

(Strength Level)

Earth Pressure Seismic Load psf= Added seismic per unit area 0.0Kh =0.2 gSoil Density Multiplier

Sliding Calcs Lateral Sliding Force 8,974.15 lbs=

Stem is FREE to rotate at top of footing

= 9,864.83 lbs 11,463.5 lbsShear Force @ this height

Shear.....Actual = 60.894 psi 70.762 psi 100.623Shear.....Allowable = psi 100.623 psi

Load Factors Dead Load 1.2 Live Load 1.6 Earth, H 1.6 Wind, W 1 Seismic, E 1

Design Summary =Total Bearing Load 19,042.2 lbs

...resultant ecc. -4.814 in

Top & Base ft-#

Soil Pressure @ Toe = 1,703.63 psf OK Soil Pressure @ Heel 3,261.74 psf OK

16.00

Soil Pressure Less Than Allowable ACI Factored @ Toe = 2,044.35 psf

Allowable psf=

ACI Factored @ Heel = 3,914.08 psf Footing Shear @ Toe = 15.880 psi OK psi OK Allowable = 88.741 psi

Footing Shear @ Heel = -16.677

Concrete Stem Construction

@ Top Support Mmax Between

Stem OKStem OK Stem OK

@ Base of Wall

Design Height Above Ftg ft= 14.50 ft0.006.289 ft

Thickness = in

Rebar Size = ## #6 7 6 Rebar Spacing = 12.00 12.00in 12.00in in Rebar Placed at = Edge in lbsReaction at Bottom 8,974.15

Edge Edge lbs= 8,459.75Reaction at Top

Design Data= fb/FB + fa/Fa = Moment....Actual = 10,839.4 ft-# ft-#33,934.9 0.0 ft-# Moment.....Allowable = 26,158.9 35,388.0ft-# 26,158.9ft-#

Wall Weight = 200.0 psf

Rebar Depth 'd' = 13.50 in in13.50 13.50

Vertical component of active lateral soil pressure IS NOT considered in the calculation of soil bearing

DESCRIPTION: Wall with Tie Beam

Project File: WNRC Retaining Wall.ec6

Project Title: WNRC Retaining Wall Engineer: JDO Project ID: 3989-05 Project Descr: Retaining Wall Repair

Footing Strengths & Dimensions

2.670 5.0

16.0

=Min. As % 0.0018 f'c = 3,500.0 psi

Toe Width = ft

Key Distance from Toe =

Heel Width =

Key Width = in

Footing Thickness =

Key Depth = in in

7.670= ft

Cover @ Top = 2 in @ Btm.= 3 in

Total Footing Width

= 150 pcfFooting Concrete Density Fy = 40000 psi

Footing Design Results Toe Heel

Factored Pressure = 2,044.35 3,914.08 psf Mu' : Upward = 8,060.33 ft-# Mu' : Downward = 2,780.27 ft-# Mu: Design = 5,280 5,041 ft-# Actual 1-Way Shear = 15.880 psi psiAllow 1-Way Shear = 88.741 88.741

Min footing T&S reinf Area Min footing T&S reinf Area per foot If one layer of horizontal bars:

2.65 0.35

Key: # 0 @ 0.00 in

#4@ 6.94 in #5@ 10.76 in

No key defined-or-

#6@ 15.28 in in2

Toe:

in2

Heel:

/ft If two layers of horizontal bars:

#4@ 13.89 in #5@ 21.53 in #6@ 30.56 in

Other Acceptable Sizes & Spacings:

#4@ 6.94 in, #5@ 10.76 in, #6@ 15.27 in, #7@ 20.83 in, #8@ 27.43 in, #9@ 34# 7 @ 12.00 in #4@ 6.94 in, #5@ 10.76 in, #6@ 15.27 in, #7@ 20.83 in, #8@ 27.43 in, #9@ 34

-or- -or-# 4 @ 12.00 in

Summary of Forces on Footing : Slab is NOT resisting sliding, stem is PINNED at footing

VerticalDistance Moment Lateral Distance Moment Overturning Moments...

Lateral

Soil Over Heel

7,164.68 lbs

916.67

0.0

1.333 ft

-9,552.91 Heel Active Pressure ft-# lbs =Stem Shear @ Top of Footing Surcharge Over Heel

1,809.47 =Axial Dead Load on Stem = 1.335 1,604.0

0.6606 -1,195.38 Sliding Force =

Overturning Moment = -10,748.3 8,974.15

Adjacent Footing Load = 0.0

Resisting Moments... lbs ft ft-#

Soil Over Toe

= 3.337 15,015.0

1,201.50 = 0.0 0.0

Surcharge Over Toe

5.837 5,350.28

0.0 0.0

Stem Weight

10,890.0 5.837 63,561.3

0.0 0.0

4,500.0

=Footing Weight

0.0

3.835 5,882.89

Resisting Moment =

1,534.0

91,413.5

Footing Overturning Stability Ratio 8.505

Overturning > Resisting! NO UNIFORM SOIL PRESSURE CALCS DONE!

Forces acting on footing for overturning, sliding, & soil pressure

Total Vertical Force 19,042.2 lbs

Net Moment Used For Soil Pressure Calculations -7,638.48 ft-#

Net Mom. at Stem/Ftg Interface = -7,638.48 ft-#

Vertical component of active lateral soil pressure IS NOT considered in the calculation of Sliding Resistance.

CHECKED. OK

DESCRIPTION: Wall with Tie Beam

Project File: WNRC Retaining Wall.ec6

Project Title: WNRC Retaining Wall Engineer: JDO Project ID: 3989-05 Project Descr: Retaining Wall Repair

Rebar Lap & Embedment Lengths Information

DESCRIPTION: Wall with Tie Beam

Project File: WNRC Retaining Wall.ec6

Project Title: WNRC Retaining Wall Engineer: JDO Project ID: 3989-05 Project Descr: Retaining Wall Repair

DESCRIPTION: Wall with Tie Beam

Project File: WNRC Retaining Wall.ec6

Project Title: WNRC Retaining Wall Engineer: JDO Project ID: 3989-05

General Beam Analysis

DESCRIPTION: Wall Reactions - At-Rest

Project File: WNRC Retaining Wall.ec6

Project Title: WNRC Retaining Wall Engineer: JDO Project ID: 3989-05 Project Descr: Retaining Wall Repair

General Beam Properties Elastic Modulus ksi4,702.0

4,096.0Span #1 in^4Area = in^2 Moment of Inertia =Span Length = 192.07.0 ft 4,096.0Span #2 in^4Area = in^2 Moment of Inertia =Span Length = 192.015.50 ft

.Service loads entered. Load Factors will be applied for calculations.Applied Loads Loads on all spans...

Varying Uniform Load : H = 0.0->1.245 k/ft, Extent = 0.0 -->> 22.50 ft

Load(s) for Span Number 2 Point Load : L = 2.340 k @ 2.167 ft, (Vehicular LL)

.DESIGN SUMMARY

Maximum Bending =

Load Combination +L+H Span # where maximum occurs Span # 2 Location of maximum on span 8.227 ft

7.556 k

Span # where maximum occurs Location of maximum on span

Span # 2 Load Combination +L+H

Maximum Shear =

15.500 ft

25.576 k-ft

Maximum Deflection Max Downward Transient Deflection 0.007 in 26876 Max Upward Transient Deflection -0.013 in 12760 Max Downward Total Deflection 0.058 in 3200 Max Upward Total Deflection -0.077 in 2184

.Maximum Forces & Stresses for Load Combinations

Span # Summary of Moment Values (k-ft)Load Combination Shear Values (k)Max Stress Ratios

M V Mmax -Mmax + Rm VnxMa - Max Mnx/Omega Cb Va MaxMnx Vnx/OmegaSegment Length Overall MAXimum Envelope

Dsgn. L = 7.00 ft 1 -3.16 3.16 7.43 Dsgn. L = 15.50 ft 2 25.58 -3.16 25.58 7.56

H Only Dsgn. L = 7.00 ft 1 -3.16 3.16 5.42 Dsgn. L = 15.50 ft 2 23.27 -3.16 23.27 7.23

+L+H Dsgn. L = 7.00 ft 1 -3.16 3.16 7.43 Dsgn. L = 15.50 ft 2 25.58 -3.16 25.58 7.56

Location in SpanLoad CombinationMax. "-" Defl Location in SpanLoad Combination Span Max. "+" Defl Overall Maximum Deflections

+L+H1 0.0000 0.000 -0.0769 0.000 +L+H 2 0.0581 7.869 0.0000 0.000

Load Combination Support 1 Support 2 Support 3 Vertical Reactions Support notation : Far left is #1 Values in KIPS

Overall MAXimum 7.5568.790 Overall MINimum H Only 7.2296.777 +L+H 7.5568.790 +0.750L+H 7.4748.287 +0.60H 4.3374.066 L Only 0.3272.013

Cantilevered Retaining Wall

DESCRIPTION: New Wall Between Grid 6 & 8

Project File: WNRC Retaining Wall.ec6

Project Title: WNRC Retaining Wall Engineer: JDO Project ID: 3989-05 Project Descr: Retaining Wall Repair

Code References Calculations per IBC 2018 1807.3, CBC 2019, ASCE 7-16

7.50 0.50 0.00

44.00

3,500.0

35.0

0.0 318.0

Criteria Soil Data

Retained Height = ft Wall height above soil = ft Active Heel Pressure = psf/ft Slope Behind Wall Height of Soil over Toe in Water height over heel = ft

135.00= pcf

Soil Density, Heel

Passive Pressure = psf/ft

Allow Soil Bearing = psf

Soil Density, Toe 120.00 pcf Footing||Soil Friction = 0.400 Soil height to ignore for passive pressure = 12.00 in

Equivalent Fluid Pressure Method

Surcharge Loads Adjacent Footing Load

Load Type

250.0 Lateral Load = 0.0 #/ft

0.0

0.0 0.0 0.0

Axial Load Applied to Stem Wall to Ftg CL Dist = 0.00 ft

Wind on Exposed Stem psf0.0=

Lateral Load Applied to Stem Surcharge Over Heel = psf Adjacent Footing Load = 0.0 lbs

Axial Dead Load (Service Level)

= lbs

Footing Type Spread Footing

Surcharge Over Toe Footing Width = 0.00 ft...Height to Top = 0.00 ft Eccentricity = 0.00 in...Height to Bottom = 0.00 ft

NOT Used To Resist Sliding & Overturning

NOT Used for Sliding & Overturning

== 0.0 ft Axial Live Load =

Base Above/Below Soil lbs

Axial Load Eccentricity = =Poisson's Ratio 0.300 at Back of Wall in (Strength Level)

Wind (W)=

DESCRIPTION: New Wall Between Grid 6 & 8

Project File: WNRC Retaining Wall.ec6

Project Title: WNRC Retaining Wall Engineer: JDO Project ID: 3989-05 Project Descr: Retaining Wall Repair

Design Summary

Wall Stability Ratios Overturning = 2.63

Global Stability = 3.83

OK

Sliding = 3.02 OK

Total Bearing Load = 5,435 lbs ...resultant ecc. = 0.69 in

Soil Pressure @ Toe = 946 psf OK Soil Pressure @ Heel = 1,097 psf OK

Allowable = 3,500 psf Soil Pressure Less Than Allowable

ACI Factored @ Toe = 1,445 psf ACI Factored @ Heel = 1,676 psf Footing Shear @ Toe = 4.2 psi OK Footing Shear @ Heel = 12.1 psi OK

Allowable = 82.2 psi

Sliding Calcs Lateral Sliding Force = 1,815.3 lbs less 100% Passive Force less 100% Friction Force Added Force Req'd

....for 1.5 Stability = 0.0=

2,174.0 3,303.7

0.0 lbs lbs lbs OK lbs OK

Masonry Block Type =

Stem Construction Bottom Stem OK

Shear.....Actual

Design Height Above Ftg = 0.00ft Wall Material Above "Ht" = Concrete

Thickness = 16.00 Rebar Size = # 4 Rebar Spacing = 12.00 Rebar Placed at = Edge

Design Data fb/FB + fa/Fa = 0.541 Total Force @ Section

= 2,352.8lbs

Moment....Actual = 6,854.2ft-#

Moment.....Allowable = 12,648.0

= 13.8psi

Shear.....Allowable = 82.2psi

Wall Weight = 200.0psf

Rebar Depth 'd' = 14.25in Masonry Data f'm =psi Fs =psi Solid Grouting = Modular Ratio 'n' =

Short Term Factor = Equiv. Solid Thick. =

Concrete Data f'c = 3,000.0psi Fy = 60,000.0

Masonry Design Method ASD=

Load Factors Building Code Dead Load 0.000 Live Load 0.000 Earth, H 0.000 Wind, W 0.000 Seismic, E 0.000 psi

Service Level = 2,352.8lbsStrength Level

Service Level Strength Level = 6,854.2ft-#

Service Level Strength Level = 13.8psi

Design Method = SD SD SD

Vertical component of active lateral soil pressure IS considered in the calculation of soil bearing pressures.

Anet (Masonry) =in2

DESCRIPTION: New Wall Between Grid 6 & 8

Project File: WNRC Retaining Wall.ec6

Project Title: WNRC Retaining Wall Engineer: JDO Project ID: 3989-05 Project Descr: Retaining Wall Repair

Concrete Stem Rebar Area Details Bottom Stem Vertical Reinforcing Horizontal Reinforcing As (based on applied moment) : 0.1093 in2/ft (4/3) * As : 0.1458 in2/ft Min Stem T&S Reinf Area 3.072 in2 200bd/fy : 200(12)(14.25)/60000 : 0.57 in2/ft Min Stem T&S Reinf Area per ft of stem Height : 0.384 in2/ft 0.0018bh : 0.0018(12)(16) : 0.3456 in2/ft Horizontal Reinforcing Options :

============ One layer of : Two layers of :

Required Area : 0.3456 in2/ft #4@ 6.25 in #4@ 12.50 in Provided Area : 0.2 in2/ft #5@ 9.69 in #5@ 19.38 in Maximum Area : 2.3165 in2/ft #6@ 13.75 in #6@ 27.50 in

1.58 3.07

12.00

Footing Torsion, Tu = ft-lbs0.00 Min. As %

Footing Allow. Torsion, phi Tu

0.0018

= ft-lbs

Footing Data

If torsion exceeds allowable, provide f'c

0.00

= 3,000 psi

Toe Width = ft Heel Width =

Key Distance from Toe Key Depth Key Width = in

= in

0.00 0.00

0.00 ft

Footing Thickness = in 4.65=

Cover @ Top =2.00 in@ Btm.= 3.00 in

Total Footing Width

= 150.00 pcfFooting Concrete Density Fy = 40,000 psi

Footing Design Results

Key:

Factored Pressure Mu' : Upward Mu' : Downward Mu: Design

Actual 1-Way Shear Allow 1-Way Shear

Toe:

= None Spec'd

1,445 1,841

4.24 82.16

Heel:

1,676 2,471 4,602 2,131

12.08 82.16

HeelToe psf ft-# ft-# ft-# psi psi

Heel Reinforcing = # 4 @ 12.00 in

Other Acceptable Sizes & Spacings

Key Reinforcing

Toe Reinforcing = # 4 @ 12.00 in

Min footing T&S reinf Area Min footing T&S reinf Area per foot If one layer of horizontal bars:

1.21 0.26

#4@ 9.26 in #5@ 14.35 in #6@ 20.37 in in2 in2 /ft

If two layers of horizontal bars:

#4@ 18.52 in #5@ 28.70 in #6@ 40.74 in supplemental design for footing torsion.

phiMin 5,7725,172= ft-#

DESCRIPTION: New Wall Between Grid 6 & 8

Project File: WNRC Retaining Wall.ec6

Project Title: WNRC Retaining Wall Engineer: JDO Project ID: 3989-05 Project Descr: Retaining Wall Repair

Summary of Overturning & Resisting Forces & Moments

.....RESISTING..........OVERTURNING

Force Distance Moment Distance Moment Item

Force ft-# lbs ftft ft-#lbs

Sloped Soil Over Heel 2,341.44.25550.9=Surcharge over Heel

Surcharge Over Heel

Adjacent Footing Load =Adjacent Footing Load

Axial Dead Load on Stem = =* Axial Live Load on Stem

Soil Over Toe Surcharge Over Toe

Surcharge Over Toe

Load @ Stem Above Soil

696.1 0.79 550.6=

Stem Weight(s)

1,600.0 2.25 3,597.9 Earth @ Stem Transitions

=Footing Weight

697.5 2.33 1,621.7 Key Weight

Added Lateral Load lbs

= 5,923.8

Vert. Component 685.0 4.65 3,185.1

Total

5,434.9 15,598.9

* Axial live load NOT included in total displayed, or used for overturning resistance, but is included for soil pressure calculation.

Total = R.M.

=1,815.3 O.T.M.

Resisting/Overturning Ratio = 2.63

Vertical Loads used for Soil Pressure = 5,434.9 lbs

Vertical component of active lateral soil pressure IS considered in the calculation of Sliding Resistance.

Vertical component of active lateral soil pressure IS considered in the calculation of Overturning Resistance.

Soil Over HL (ab. water tbl) Soil Over HL (bel. water tbl)

1,756.4 3.78 3.78

6,643.7 6,643.7

Watre Table Buoyant Force =

HL Act Pres (ab water tbl) HL Act Pres (be water tbl)

1,264.4 2.83 3,582.4

Hydrostatic Force

Tilt Horizontal Deflection at Top of Wall due to settlement of soil (Deflection due to wall bending not considered)

Soil Spring Reaction Modulus 250.0 pci Horizontal Defl @ Top of Wall (approximate only) 0.000 in The above calculation is not valid if the heel soil bearing pressure exceeds that of the toe, because the wall would then tend to rotate into the retained soil.

DESCRIPTION: New Wall Between Grid 6 & 8

Project File: WNRC Retaining Wall.ec6

Project Title: WNRC Retaining Wall Engineer: JDO Project ID: 3989-05 Project Descr: Retaining Wall Repair

Rebar Lap & Embedment Lengths Information Stem Design Segment: Bottom Stem Design Height: 0.00 ft above top of footing

Lap Splice length for #4 bar specified in this stem design segment = 17.09 in Development length for #4 bar specified in this stem design segment = 13.15 in

Hooked embedment length into footing for #4 bar specified in this stem design segment = 7.67 in As Provided = 0.2000 in2/ft As Required = 0.3456 in2/ft

DESCRIPTION: New Wall Between Grid 6 & 8

Project File: WNRC Retaining Wall.ec6

Project Title: WNRC Retaining Wall Engineer: JDO Project ID: 3989-05

DESCRIPTION: New Wall Between Grid 6 & 8

Project File: WNRC Retaining Wall.ec6

Project Title: WNRC Retaining Wall Engineer: JDO Project ID: 3989-05

DESCRIPTION: New Wall Between Grid 9 & 10

Project File: WNRC Retaining Wall.ec6

Project Title: WNRC Retaining Wall Engineer: JDO Project ID: 3989-05 Project Descr: Retaining Wall Repair

Code References Calculations per IBC 2018 1807.3, CBC 2019, ASCE 7-16

14.50 0.50 0.00

56.00

3,500.0

35.0

0.0 318.0

Criteria Soil Data

Retained Height = ft Wall height above soil = ft Active Heel Pressure = psf/ft Slope Behind Wall Height of Soil over Toe in Water height over heel = ft

135.00= pcf

Soil Density, Heel

Passive Pressure = psf/ft

Allow Soil Bearing = psf

Soil Density, Toe 120.00 pcf Footing||Soil Friction = 0.400 Soil height to ignore for passive pressure = 12.00 in

Equivalent Fluid Pressure Method

Surcharge Loads Adjacent Footing Load

Load Type

250.0 Lateral Load = 0.0 #/ft

0.0

0.0 0.0 0.0

Axial Load Applied to Stem Wall to Ftg CL Dist = 0.00 ft

Wind on Exposed Stem psf0.0=

Lateral Load Applied to Stem Surcharge Over Heel = psf Adjacent Footing Load = 0.0 lbs

Axial Dead Load (Service Level)

= lbs

Footing Type Spread Footing

Surcharge Over Toe Footing Width = 0.00 ft...Height to Top = 0.00 ft Eccentricity = 0.00 in...Height to Bottom = 0.00 ft

NOT Used To Resist Sliding & Overturning

NOT Used for Sliding & Overturning

== 0.0 ft Axial Live Load =

Base Above/Below Soil lbs

Axial Load Eccentricity = =Poisson's Ratio 0.300 at Back of Wall in (Strength Level)

Wind (W)=

DESCRIPTION: New Wall Between Grid 9 & 10

Project File: WNRC Retaining Wall.ec6

Project Title: WNRC Retaining Wall Engineer: JDO Project ID: 3989-05 Project Descr: Retaining Wall Repair

Design Summary

Wall Stability Ratios Overturning = 1.95

Global Stability = 2.61

OK

Sliding = 2.01 OK

Total Bearing Load = 15,726 lbs ...resultant ecc. = 1.63 in

Soil Pressure @ Toe = 1,544 psf OK Soil Pressure @ Heel = 1,908 psf OK

Allowable = 3,500 psf Soil Pressure Less Than Allowable

ACI Factored @ Toe = 2,313 psf ACI Factored @ Heel = 2,858 psf Footing Shear @ Toe = 12.2 psi OK Footing Shear @ Heel = 6.1 psi OK

Allowable = 82.2 psi

Sliding Calcs Lateral Sliding Force = 5,413.4 lbs less 100% Passive Force less 100% Friction Force Added Force Req'd

....for 1.5 Stability = 0.0=

5,339.6 5,565.0

0.0 lbs lbs lbs OK lbs OK

Masonry Block Type =

Stem Construction Bottom Ratio > 1.0

Shear.....Actual

Design Height Above Ftg = 0.00ft Wall Material Above "Ht" = Concrete

Thickness = 16.00 Rebar Size = # 6 Rebar Spacing = 9.00 Rebar Placed at = Edge

Design Data fb/FB + fa/Fa = 1.094 Total Force @ Section

= 7,390.7lbs

Moment....Actual = 39,355.7ft-#

Moment.....Allowable = 35,954.8

= 45.2psi

Shear.....Allowable = 821.6psi

Wall Weight = 200.0psf

Rebar Depth 'd' = 13.63in Masonry Data f'm =psi Fs =psi Solid Grouting = Modular Ratio 'n' =

Short Term Factor = Equiv. Solid Thick. =

Concrete Data f'c = 300,000.0psi Fy = 60,000.0

Masonry Design Method ASD=

Load Factors Building Code Dead Load 0.000 Live Load 0.000 Earth, H 0.000 Wind, W 0.000 Seismic, E 0.000 psi

Service Level = 7,390.7lbsStrength Level

Service Level Strength Level = 39,355.7ft-#

Service Level Strength Level = 45.2psi

Design Method = SD SD SD

Vertical component of active lateral soil pressure IS considered in the calculation of soil bearing pressures.

Anet (Masonry) =in2

DESCRIPTION: New Wall Between Grid 9 & 10

Project File: WNRC Retaining Wall.ec6

Project Title: WNRC Retaining Wall Engineer: JDO Project ID: 3989-05 Project Descr: Retaining Wall Repair

Concrete Stem Rebar Area Details Bottom Stem Vertical Reinforcing Horizontal Reinforcing As (based on applied moment) : 0.6536 in2/ft (4/3) * As : 0.8714 in2/ft Min Stem T&S Reinf Area 5.760 in2 3sqrt(f’c)bd/fy : 3sqrt(300000)(12)(13.625)/60000 :4.4776 in2/ft Min Stem T&S Reinf Area per ft of stem Height : 0.384 in2/ft 0.0018bh : 0.0018(12)(16) : 0.3456 in2/ft Horizontal Reinforcing Options :

============ One layer of : Two layers of :

Required Area : 0.8714 in2/ft #4@ 6.25 in #4@ 12.50 in Provided Area : 0.5867 in2/ft #5@ 9.69 in #5@ 19.38 in Maximum Area : 169.3758 in2/ft #6@ 13.75 in #6@ 27.50 in

2.67 5.07

16.00

Footing Torsion, Tu = ft-lbs0.00 Min. As %

Footing Allow. Torsion, phi Tu

0.0018

= ft-lbs

Footing Data

If torsion exceeds allowable, provide f'c

0.00

= 3,000 psi

Toe Width = ft Heel Width =

Key Distance from Toe Key Depth Key Width = in

= in

0.00 0.00

0.00 ft

Footing Thickness = in 7.73=

Cover @ Top =2.00 in@ Btm.= 3.00 in

Total Footing Width

= 150.00 pcfFooting Concrete Density Fy = 40,000 psi

Footing Design Results

Key:

Factored Pressure Mu' : Upward Mu' : Downward Mu: Design

Actual 1-Way Shear Allow 1-Way Shear

Toe:

= None Spec'd

2,313 8,448 3,542 4,906

12.16 82.16

Heel:

2,858 18,959 20,834 1,874

6.05 82.16

HeelToe psf ft-# ft-# ft-# psi psi

Heel Reinforcing = # 7 @ 12.00 in

Other Acceptable Sizes & Spacings

Key Reinforcing

Toe Reinforcing = # 6 @ 4.50 in

Min footing T&S reinf Area Min footing T&S reinf Area per foot If one layer of horizontal bars:

2.67 0.35

#4@ 6.94 in #5@ 10.76 in #6@ 15.28 in in2 in2 /ft

If two layers of horizontal bars:

#4@ 13.89 in #5@ 21.53 in #6@ 30.56 in supplemental design for footing torsion.

phiMin 23,70741,739= ft-#

DESCRIPTION: New Wall Between Grid 9 & 10

Project File: WNRC Retaining Wall.ec6

Project Title: WNRC Retaining Wall Engineer: JDO Project ID: 3989-05 Project Descr: Retaining Wall Repair

Summary of Overturning & Resisting Forces & Moments

.....RESISTING..........OVERTURNING

Force Distance Moment Distance Moment Item

Force ft-# lbs ftft ft-#lbs

Sloped Soil Over Heel 8,124.47.921,026.2=Surcharge over Heel

Surcharge Over Heel

Adjacent Footing Load =Adjacent Footing Load

Axial Dead Load on Stem = =* Axial Live Load on Stem

Soil Over Toe Surcharge Over Toe

Surcharge Over Toe

Load @ Stem Above Soil

1,493.5 1.33 1,991.6=

Stem Weight(s)

3,000.0 3.33 10,001.0 Earth @ Stem Transitions

=Footing Weight

1,546.8 3.87 5,981.5 Key Weight

Added Lateral Load lbs

= 31,278.8

Vert. Component

Total

13,349.0 60,855.2

* Axial live load NOT included in total displayed, or used for overturning resistance, but is included for soil pressure calculation.

Total = R.M.

=5,413.4 O.T.M.

Resisting/Overturning Ratio = 1.95

Vertical Loads used for Soil Pressure = 15,725.7 lbs

Vertical component of active lateral soil pressure IS NOT considered in the calculation of Sliding Resistance.

Vertical component of active lateral soil pressure IS NOT considered in the calculation of Overturning Resistance.

Soil Over HL (ab. water tbl) Soil Over HL (bel. water tbl)

7,308.7 5.87 5.87

42,881.1 42,881.1

Watre Table Buoyant Force =

HL Act Pres (ab water tbl) HL Act Pres (be water tbl)

4,387.2 5.28 23,154.4

Hydrostatic Force

Tilt Horizontal Deflection at Top of Wall due to settlement of soil (Deflection due to wall bending not considered)

Soil Spring Reaction Modulus 250.0 pci Horizontal Defl @ Top of Wall (approximate only) 0.000 in The above calculation is not valid if the heel soil bearing pressure exceeds that of the toe, because the wall would then tend to rotate into the retained soil.

DESCRIPTION: New Wall Between Grid 9 & 10

Project File: WNRC Retaining Wall.ec6

Project Title: WNRC Retaining Wall Engineer: JDO Project ID: 3989-05 Project Descr: Retaining Wall Repair

Rebar Lap & Embedment Lengths Information Stem Design Segment: Bottom Stem Design Height: 0.00 ft above top of footing

Lap Splice length for #6 bar specified in this stem design segment = 15.60 in Development length for #6 bar specified in this stem design segment = 12.00 in

Hooked embedment length into footing for #6 bar specified in this stem design segment = 11.50 in As Provided = 0.5867 in2/ft As Required = 0.8714 in2/ft

DESCRIPTION: New Wall Between Grid 9 & 10

Project File: WNRC Retaining Wall.ec6

Project Title: WNRC Retaining Wall Engineer: JDO Project ID: 3989-05

DESCRIPTION: New Wall Between Grid 9 & 10

Project File: WNRC Retaining Wall.ec6

Project Title: WNRC Retaining Wall Engineer: JDO Project ID: 3989-05

Concrete Beam

DESCRIPTION: Wall Beam @ Ties

Project File: WNRC Retaining Wall.ec6

Project Title: WNRC Retaining Wall Engineer: JDO Project ID: 3989-05 Project Descr: Retaining Wall Repair

CODE REFERENCES

Calculations per ACI 318-14, IBC 2018, CBC 2019, ASCE 7-16 Load Combination Set : ASCE 7-16

Material Properties 5.0

7.50 145.0

Elastic Modulus 4,074.28 ksi

60.0 29,000.0

40.0 29,000.0

4= 2.0

= 0.90 0.750 f'c ksi fy - Main Rebar ksi

Density

1/2 fr = f'c * 530.33 pcf

E - Main Rebar ksi psi

= 1.0LtWt Factor Fy - Stirrups ksi

E - Stirrups ksi

0.80

Shear :

Stirrup Bar Size #

Number of Resisting Legs Per Stirrup

Phi Values Flexure :

.Cross Section & Reinforcing Details Rectangular Section, Width = 24.0 in, Height = 16.0 in Span #1 Reinforcing

8-#8 at 3.125 in from Bottom, from 0.0 to 11.250 ft in this span 8-#8 at 3.125 in from Top, from 0.0 to 11.250 ft in this span

Load for Span Number 1 Uniform Load : L = 2.013, H = 6.770 k/ft, Tributary Width = 1.0 ft, (Horizontal Earth)

.Design OKDESIGN SUMMARY Maximum Bending Stress Ratio = 0.471 : 1

Span # where maximum occurs Span # 1 Location of maximum on span 11.250 ft

Mn * Phi : Allowable 314.496 k-ft

Typical SectionSection used for this span Mu : Applied -148.212 k-ft

Maximum Deflection

0 <360.0

Ratio = 0 <180.0

Max Downward Transient Deflection 0.004 in 31069Ratio = >=360.0 Max Upward Transient Deflection 0.000 in Ratio = Max Downward Total Deflection 0.025 in Ratio = >=180.0 Max Upward Total Deflection 0.000 in

Span: 1 : L Only Span: 1 : L Only Span: 1 : +L+H Span: 1 : +L+H

Load Combination Support 1 Support 2 Vertical Reactions Support notation : Far left is #1

Overall MAXimum 49.404 49.404 Overall MINimum 11.323 11.323 H Only 38.081 38.081 +L+H 49.404 49.404 +0.750L+H 46.574 46.574 +0.60H 22.849 22.849 L Only 11.323 11.323

DESCRIPTION: Wall Beam @ Ties

Project File: WNRC Retaining Wall.ec6

Project Title: WNRC Retaining Wall Engineer: JDO Project ID: 3989-05 Project Descr: Retaining Wall Repair

Detailed Shear Information

Load Combination Vu (k)Span Distance 'd' Comment Phi*Vs

Req'd Phi*Vnd*Vu/MuMu

(ft) (k)(in) (k)Actual Suggest(k-ft)Number (k) Spacing (in)

Design Phi*Vc

+1.60L+1.60H 1 0.00 12.88 79.05 79.05 148.21 0.57 37.92 PhiVc < Vu 41.130 89.4 3.8 3.0 +1.60L+1.60H 1 0.12 12.88 77.32 77.32 138.60 0.60 38.23 PhiVc < Vu 39.091 89.7 4.0 3.0 +1.60L+1.60H 1 0.25 12.88 75.59 75.59 129.20 0.63 38.57 PhiVc < Vu 37.017 90.1 4.2 3.0 +1.60L+1.60H 1 0.37 12.88 73.86 73.86 120.01 0.66 38.96 PhiVc < Vu 34.903 90.5 4.4 3.0 +1.60L+1.60H 1 0.49 12.88 72.14 72.14 111.04 0.70 39.40 PhiVc < Vu 32.740 90.9 4.7 3.0 +1.60L+1.60H 1 0.61 12.88 70.41 70.41 102.27 0.74 39.89 PhiVc < Vu 30.520 91.4 5.1 3.0 +1.60L+1.60H 1 0.74 12.88 68.68 68.68 93.72 0.79 40.45 PhiVc < Vu 28.228 92.0 5.5 3.0 +1.60L+1.60H 1 0.86 12.88 66.95 66.95 85.38 0.84 41.11 PhiVc < Vu 25.847 92.6 6.0 3.0 +1.60L+1.60H 1 0.98 12.88 65.22 65.22 77.26 0.91 41.87 PhiVc < Vu 23.355 93.4 6.4 3.0 +1.60L+1.60H 1 1.11 12.88 63.50 63.50 69.35 0.98 42.78 PhiVc < Vu 20.719 94.3 6.4 3.0 +1.60L+1.60H 1 1.23 12.88 61.77 61.77 61.65 1.00 42.99 PhiVc < Vu 18.783 94.5 6.4 3.0 +1.60L+1.60H 1 1.35 12.88 60.04 60.04 54.16 1.00 42.99 PhiVc < Vu 17.055 94.5 6.4 3.0 +1.60L+1.60H 1 1.48 12.88 58.31 58.31 46.88 1.00 42.99 PhiVc < Vu 15.328 94.5 6.4 3.0 +1.60L+1.60H 1 1.60 12.88 56.59 56.59 39.82 1.00 42.99 PhiVc < Vu 13.60 94.5 6.4 3.0 +1.60L+1.60H 1 1.72 12.88 54.86 54.86 32.97 1.00 42.99 PhiVc < Vu 11.872 94.5 6.4 3.0 +1.60L+1.60H 1 1.84 12.88 53.13 53.13 26.33 1.00 42.99 PhiVc < Vu 10.144 94.5 6.4 3.0 +1.60L+1.60H 1 1.97 12.88 51.40 51.40 19.90 1.00 42.99 PhiVc < Vu 8.416 94.5 6.4 3.0 +1.60L+1.60H 1 2.09 12.88 49.67 49.67 13.69 1.00 42.99 PhiVc < Vu 6.689 94.5 6.4 3.0 +1.60L+1.60H 1 2.21 12.88 47.95 47.95 7.69 1.00 42.99 PhiVc < Vu 4.961 94.5 6.4 3.0 +1.60L+1.60H 1 2.34 12.88 46.22 46.22 1.90 1.00 42.99 PhiVc < Vu 3.233 94.5 6.4 3.0 +1.60L+1.60H 1 2.46 12.88 44.49 44.49 3.68 1.00 42.99 PhiVc < Vu 1.505 94.5 6.4 3.0 +1.60L+1.60H 1 2.58 12.88 42.76 42.76 9.04 1.00 42.99 PhiVc/2 < Vu <=Min 9.6.3.1 68.7 6.4 6.0 +1.60L+1.60H 1 2.70 12.88 41.04 41.04 14.19 1.00 42.99 PhiVc/2 < Vu <=Min 9.6.3.1 68.7 6.4 6.0 +1.60L+1.60H 1 2.83 12.88 39.31 39.31 19.13 1.00 42.99 PhiVc/2 < Vu <=Min 9.6.3.1 68.7 6.4 6.0 +1.60L+1.60H 1 2.95 12.88 37.58 37.58 23.86 1.00 42.99 PhiVc/2 < Vu <=Min 9.6.3.1 68.7 6.4 6.0 +1.60L+1.60H 1 3.07 12.88 35.85 35.85 28.37 1.00 42.99 PhiVc/2 < Vu <=Min 9.6.3.1 68.7 6.4 6.0 +1.60L+1.60H 1 3.20 12.88 34.12 34.12 32.68 1.00 42.99 PhiVc/2 < Vu <=Min 9.6.3.1 68.7 6.4 6.0 +1.60L+1.60H 1 3.32 12.88 32.40 32.40 36.77 0.95 42.34 PhiVc/2 < Vu <=Min 9.6.3.1 68.1 6.4 6.0 +1.60L+1.60H 1 3.44 12.88 30.67 30.67 40.64 0.81 40.73 PhiVc/2 < Vu <=Min 9.6.3.1 66.5 6.4 6.0 +1.60L+1.60H 1 3.57 12.88 28.94 28.94 44.31 0.70 39.44 PhiVc/2 < Vu <=Min 9.6.3.1 65.2 6.4 6.0 +1.60L+1.60H 1 3.69 12.88 27.21 27.21 47.76 0.61 38.38 PhiVc/2 < Vu <=Min 9.6.3.1 64.1 6.4 6.0 +1.60L+1.60H 1 3.81 12.88 25.49 25.49 51.00 0.54 37.49 PhiVc/2 < Vu <=Min 9.6.3.1 63.2 6.4 6.0 +1.60L+1.60H 1 3.93 12.88 23.76 23.76 54.03 0.47 36.73 PhiVc/2 < Vu <=Min 9.6.3.1 62.5 6.4 6.0 +1.60L+1.60H 1 4.06 12.88 22.03 22.03 56.84 0.42 36.06 PhiVc/2 < Vu <=Min 9.6.3.1 61.8 6.4 6.0 +1.60L+1.60H 1 4.18 12.88 20.30 20.30 59.44 0.37 35.48 PhiVc/2 < Vu <=Min 9.6.3.1 61.2 6.4 6.0 +1.60L+1.60H 1 4.30 12.88 18.57 18.57 61.83 0.32 34.95 PhiVc/2 < Vu <=Min 9.6.3.1 60.7 6.4 6.0 +1.60L+1.60H 1 4.43 12.88 16.85 16.85 64.01 0.28 34.48 Vu < PhiVc/2Not Reqd 9.6.3 34.5 0.0 0.0 +1.60L+1.60H 1 4.55 12.88 15.12 15.12 65.98 0.25 34.05 Vu < PhiVc/2Not Reqd 9.6.3 34.0 0.0 0.0 +1.60L+1.60H 1 4.67 12.88 13.39 13.39 67.73 0.21 33.65 Vu < PhiVc/2Not Reqd 9.6.3 33.6 0.0 0.0 +1.60L+1.60H 1 4.80 12.88 11.66 11.66 69.27 0.18 33.28 Vu < PhiVc/2Not Reqd 9.6.3 33.3 0.0 0.0 +1.60L+1.60H 1 4.92 12.88 9.93 9.93 70.60 0.15 32.92 Vu < PhiVc/2Not Reqd 9.6.3 32.9 0.0 0.0 +1.60L+1.60H 1 5.04 12.88 8.21 8.21 71.71 0.12 32.59 Vu < PhiVc/2Not Reqd 9.6.3 32.6 0.0 0.0 +1.60L+1.60H 1 5.16 12.88 6.48 6.48 72.61 0.10 32.27 Vu < PhiVc/2Not Reqd 9.6.3 32.3 0.0 0.0 +1.60L+1.60H 1 5.29 12.88 4.75 4.75 73.30 0.07 31.96 Vu < PhiVc/2Not Reqd 9.6.3 32.0 0.0 0.0 +1.60L+1.60H 1 5.41 12.88 3.02 3.02 73.78 0.04 31.66 Vu < PhiVc/2Not Reqd 9.6.3 31.7 0.0 0.0 +1.60L+1.60H 1 5.53 12.88 1.30 1.30 74.05 0.02 31.36 Vu < PhiVc/2Not Reqd 9.6.3 31.4 0.0 0.0 +1.60L+1.60H 1 5.66 12.88 -0.43 0.43 74.10 0.01 31.21 Vu < PhiVc/2Not Reqd 9.6.3 31.2 0.0 0.0 +1.60L+1.60H 1 5.78 12.88 -2.16 2.16 73.94 0.03 31.51 Vu < PhiVc/2Not Reqd 9.6.3 31.5 0.0 0.0 +1.60L+1.60H 1 5.90 12.88 -3.89 3.89 73.57 0.06 31.81 Vu < PhiVc/2Not Reqd 9.6.3 31.8 0.0 0.0 +1.60L+1.60H 1 6.02 12.88 -5.62 5.62 72.99 0.08 32.11 Vu < PhiVc/2Not Reqd 9.6.3 32.1 0.0 0.0 +1.60L+1.60H 1 6.15 12.88 -7.34 7.34 72.19 0.11 32.43 Vu < PhiVc/2Not Reqd 9.6.3 32.4 0.0 0.0 +1.60L+1.60H 1 6.27 12.88 -9.07 9.07 71.18 0.14 32.76 Vu < PhiVc/2Not Reqd 9.6.3 32.8 0.0 0.0 +1.60L+1.60H 1 6.39 12.88 -10.80 10.80 69.96 0.17 33.10 Vu < PhiVc/2Not Reqd 9.6.3 33.1 0.0 0.0 +1.60L+1.60H 1 6.52 12.88 -12.53 12.53 68.52 0.20 33.46 Vu < PhiVc/2Not Reqd 9.6.3 33.5 0.0 0.0 +1.60L+1.60H 1 6.64 12.88 -14.25 14.25 66.88 0.23 33.85 Vu < PhiVc/2Not Reqd 9.6.3 33.8 0.0 0.0 +1.60L+1.60H 1 6.76 12.88 -15.98 15.98 65.02 0.26 34.26 Vu < PhiVc/2Not Reqd 9.6.3 34.3 0.0 0.0 +1.60L+1.60H 1 6.89 12.88 -17.71 17.71 62.95 0.30 34.71 PhiVc/2 < Vu <=Min 9.6.3.1 60.5 6.4 6.0

DESCRIPTION: Wall Beam @ Ties

Project File: WNRC Retaining Wall.ec6

Project Title: WNRC Retaining Wall Engineer: JDO Project ID: 3989-05 Project Descr: Retaining Wall Repair

Detailed Shear Information

Load Combination Vu (k)Span Distance 'd' Comment Phi*Vs

Req'd Phi*Vnd*Vu/MuMu

(ft) (k)(in) (k)Actual Suggest(k-ft)Number (k) Spacing (in)

Design Phi*Vc

+1.60L+1.60H 1 7.01 12.88 -19.44 19.44 60.66 0.34 35.21 PhiVc/2 < Vu <=Min 9.6.3.1 61.0 6.4 6.0 +1.60L+1.60H 1 7.13 12.88 -21.17 21.17 58.17 0.39 35.76 PhiVc/2 < Vu <=Min 9.6.3.1 61.5 6.4 6.0 +1.60L+1.60H 1 7.25 12.88 -22.89 22.89 55.46 0.44 36.38 PhiVc/2 < Vu <=Min 9.6.3.1 62.1 6.4 6.0 +1.60L+1.60H 1 7.38 12.88 -24.62 24.62 52.54 0.50 37.09 PhiVc/2 < Vu <=Min 9.6.3.1 62.8 6.4 6.0 +1.60L+1.60H 1 7.50 12.88 -26.35 26.35 49.41 0.57 37.92 PhiVc/2 < Vu <=Min 9.6.3.1 63.7 6.4 6.0 +1.60L+1.60H 1 7.62 12.88 -28.08 28.08 46.06 0.65 38.89 PhiVc/2 < Vu <=Min 9.6.3.1 64.6 6.4 6.0 +1.60L+1.60H 1 7.75 12.88 -29.80 29.80 42.50 0.75 40.05 PhiVc/2 < Vu <=Min 9.6.3.1 65.8 6.4 6.0 +1.60L+1.60H 1 7.87 12.88 -31.53 31.53 38.73 0.87 41.49 PhiVc/2 < Vu <=Min 9.6.3.1 67.2 6.4 6.0 +1.60L+1.60H 1 7.99 12.88 -33.26 33.26 34.75 1.00 42.99 PhiVc/2 < Vu <=Min 9.6.3.1 68.7 6.4 6.0 +1.60L+1.60H 1 8.11 12.88 -34.99 34.99 30.55 1.00 42.99 PhiVc/2 < Vu <=Min 9.6.3.1 68.7 6.4 6.0 +1.60L+1.60H 1 8.24 12.88 -36.72 36.72 26.14 1.00 42.99 PhiVc/2 < Vu <=Min 9.6.3.1 68.7 6.4 6.0 +1.60L+1.60H 1 8.36 12.88 -38.44 38.44 21.52 1.00 42.99 PhiVc/2 < Vu <=Min 9.6.3.1 68.7 6.4 6.0 +1.60L+1.60H 1 8.48 12.88 -40.17 40.17 16.69 1.00 42.99 PhiVc/2 < Vu <=Min 9.6.3.1 68.7 6.4 6.0 +1.60L+1.60H 1 8.61 12.88 -41.90 41.90 11.64 1.00 42.99 PhiVc/2 < Vu <=Min 9.6.3.1 68.7 6.4 6.0 +1.60L+1.60H 1 8.73 12.88 -43.63 43.63 6.39 1.00 42.99 PhiVc < Vu 0.6414 94.5 6.4 3.0 +1.60L+1.60H 1 8.85 12.88 -45.35 45.35 0.92 1.00 42.99 PhiVc < Vu 2.369 94.5 6.4 3.0 +1.60L+1.60H 1 8.98 12.88 -47.08 47.08 4.77 1.00 42.99 PhiVc < Vu 4.097 94.5 6.4 3.0 +1.60L+1.60H 1 9.10 12.88 -48.81 48.81 10.66 1.00 42.99 PhiVc < Vu 5.825 94.5 6.4 3.0 +1.60L+1.60H 1 9.22 12.88 -50.54 50.54 16.77 1.00 42.99 PhiVc < Vu 7.553 94.5 6.4 3.0 +1.60L+1.60H 1 9.34 12.88 -52.27 52.27 23.09 1.00 42.99 PhiVc < Vu 9.280 94.5 6.4 3.0 +1.60L+1.60H 1 9.47 12.88 -53.99 53.99 29.62 1.00 42.99 PhiVc < Vu 11.008 94.5 6.4 3.0 +1.60L+1.60H 1 9.59 12.88 -55.72 55.72 36.37 1.00 42.99 PhiVc < Vu 12.736 94.5 6.4 3.0 +1.60L+1.60H 1 9.71 12.88 -57.45 57.45 43.32 1.00 42.99 PhiVc < Vu 14.464 94.5 6.4 3.0 +1.60L+1.60H 1 9.84 12.88 -59.18 59.18 50.49 1.00 42.99 PhiVc < Vu 16.192 94.5 6.4 3.0 +1.60L+1.60H 1 9.96 12.88 -60.91 60.91 57.87 1.00 42.99 PhiVc < Vu 17.919 94.5 6.4 3.0 +1.60L+1.60H 1 10.08 12.88 -62.63 62.63 65.47 1.00 42.99 PhiVc < Vu 19.647 94.5 6.4 3.0 +1.60L+1.60H 1 10.20 12.88 -64.36 64.36 73.28 0.94 42.30 PhiVc < Vu 22.058 93.8 6.4 3.0 +1.60L+1.60H 1 10.33 12.88 -66.09 66.09 81.30 0.87 41.47 PhiVc < Vu 24.617 93.0 6.3 3.0 +1.60L+1.60H 1 10.45 12.88 -67.82 67.82 89.53 0.81 40.77 PhiVc < Vu 27.050 92.3 5.7 3.0 +1.60L+1.60H 1 10.57 12.88 -69.54 69.54 97.97 0.76 40.16 PhiVc < Vu 29.383 91.7 5.3 3.0 +1.60L+1.60H 1 10.70 12.88 -71.27 71.27 106.63 0.72 39.63 PhiVc < Vu 31.638 91.1 4.9 3.0 +1.60L+1.60H 1 10.82 12.88 -73.00 73.00 115.50 0.68 39.17 PhiVc < Vu 33.828 90.7 4.6 3.0 +1.60L+1.60H 1 10.94 12.88 -74.73 74.73 124.58 0.64 38.76 PhiVc < Vu 35.965 90.3 4.3 3.0 +1.60L+1.60H 1 11.07 12.88 -76.46 76.46 133.87 0.61 38.40 PhiVc < Vu 38.059 89.9 4.1 3.0 +1.60L+1.60H 1 11.19 12.88 -78.18 78.18 143.38 0.59 38.07 PhiVc < Vu 40.115 89.6 3.9 3.0

.Maximum Forces & Stresses for Load Combinations

Span # Bending Stress Results ( k-ft )Location (ft)Load Combination

Mu : Max Stress RatioSegment Phi*Mnxalong Beam MAXimum BENDING Envelope

Span # 1 1 11.250 -148.21 314.50 0.47 +1.60H

Span # 1 1 11.250 -114.24 314.50 0.36 +1.60L+1.60H

Span # 1 1 11.250 -148.21 314.50 0.47 +L+1.60H

Span # 1 1 11.250 -135.47 314.50 0.43 +0.90H

Span # 1 1 11.250 -64.26 314.50 0.20

Location in Span (ft)Load CombinationMax. "-" Defl (in)Location in Span (ft)Load Combination Span Max. "+" Defl (in) Overall Maximum Deflections

+L+H 1 0.0247 5.625 0.0000 0.000