G640 ACM REPORT.pdf
PDF 50 KB Posted
- Attached to
- MCAS Multiple Building Painting/Flooring Repairs
- Solicitation number
- N4008526R9069
About this file
This is an Asbestos Inspection Report for Building G640 (SOI Dining Hall) at MCB Camp Lejeune, printed August 14, 2025. The building was constructed in 1972 and has a hazard ranking of 2A/Yellow as of July 2022.
The inspection identifies friable asbestos-containing materials (ACM) consisting of pipe insulation on the low-pressure steam riser (6/8") in the southeast mechanical room, east location, totaling 4 linear feet. This material was documented across multiple inspection dates (1/6/2011, 1/15/2014, 2/7/2012, 6/7/2016, and 7/20/2022) and is noted as deteriorated and friable with repairs unlikely to last. The report also documents numerous tested non-ACM materials and removed materials including fiberglass insulation sealant, beige floor tiles and adhesive (620 square feet), roofing materials, exterior caulking, vinyl base, and gasket materials. Health guidance emphasizes that ACM only presents a hazard when asbestos fibers are airborne and inhaled, and that intact, undisturbed ACM is not considered a significant health hazard. The report mandates that personnel avoid disturbance, sanding, grinding, or abrasion of ACM and report any damage or changes in condition to the Asbestos Program Manager at 910-451-5837. ACM will be inspected periodically to evaluate condition changes, with the Camp Lejeune Asbestos Program Manager maintaining survey records.
View the file
Other files
Show all 33
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ASBESTOS INSPECTION REPORT of:
Building # G640
MCB CAMP LEJEUNE
Thursday, August 14, 2025
Print Date
Thursday, August 14, 2025 Page 1 of 7Print Date:
INSPECTION SUMMARY
BLDG #:
OCCUPANT:
YEAR BUILT:
BUILDING COMMENTS:
G640
SOI DINING HALL
HAZ RANK 2A/YELLOW [AH JUL2022]
ACM INSULATION, NE MECH RM ON LOW PRESSURE STEAM DETERIORATED AND FRIABLE, REPAIRS LIKELY WILL NOT LAST
JUN2016
ACM REMAINS
JAN2014
PVS. ACM REMAINS, CONDITIONS FAIR IN MECH ROOM, BUT REPAIRS TO TSI NOT EXPECTED TO LAST LONG
FEB2012
ACM INSULATION REMAINS, HAD DETERIORATED, ADDL MATERIAL ID'D; TILE TESTED ACM VIA TEM, MIXED RESULTS EVERY INSPECTION, MUST CONSIDER ACM; PVS. ACM SEALANT REMAINS; ADDL SAMPLING, NO ADDL ACM ID'D
JAN2011
PVS. ACM REMAINS, ADDL SAMPLING, ACM INCLUDES:
PIPE INSULATION
JUN08
ADDL SAMPLING, ACM INCLUDES:
MASTIC UNDER 12" BEIGE TILE
DEC01 AES
NO ASBESTOS CONTAINING MATERIALS IDENTIFIED
ASBESTOS MANAGER: 910-451-5837
Friable ACM(s) identified
Non-friable ACM(s) identified
NOTICE: The following asbestos-containing materials have been identified in this structure. Refer to survey findings for additional information or contact the Asbestos Program Manager. Please note ACM that is intact and undisturbed is not considered a significant health hazard to building occupants.
DESCRIPTION LOCATION Date Quantity
DESCRIPTION LOCATION Date Quantity
NOTIFICATION OF ACM IN BUILDING
PIPE INSULATION 4 LFSOUTHEAST MECHANICAL ROOM, EAST
LOW PRESSURE STEAM RISER (6/8")
1/6/2011
PIPE INSULATION 4 LFSOUTHEAST MECHANICAL ROOM, EAST
LOW PRESSURE STEAM RISER (6/8")
7/20/2022
PIPE INSULATION 4 LFSOUTHEAST MECHANICAL ROOM, EAST
LOW PRESSURE STEAM RISER (6/8")
1/15/2014
PIPE INSULATION 4 LFSOUTHEAST MECHANICAL ROOM, EAST
LOW PRESSURE STEAM RISER (6/8")
2/7/2012
PIPE INSULATION 4 LFSOUTHEAST MECHANICAL ROOM, EAST
LOW PRESSURE STEAM RISER (6/8")
6/7/2016
Thursday, August 14, 2025 Page 2 of 7Print Date:
Tested Non ACM or REMOVED Materials
DESCRIPTION LOCATION Date
FIBERGLASS INSULATION SEALANT 2 LFSOUTHEAST MECHANICAL ROOM, EAST
LOW PRESSURE STEAM RISER, HM24
ACM INSULATED LINE
1/6/2011
12" BEIGE FLOOR TILE AND ADHESIVE 620 SFNORTHEAST OFFICE AREAS, MULTIPLE
TYPES MIXED
7/20/2022
FIBERGLASS INSULATION SEALANT 2 LFSOUTHEAST MECHANICAL ROOM, EAST
LOW PRESSURE STEAM RISER, HM24
ACM INSULATED LINE
7/20/2022
FIBERGLASS INSULATION SEALANT 2 LFSOUTHEAST MECHANICAL ROOM, EAST
LOW PRESSURE STEAM RISER, HM24
ACM INSULATED LINE
1/15/2014
12" BEIGE FLOOR TILE AND ADHESIVE 620 SFNORTHEAST OFFICE AREAS, MULTIPLE
TYPES MIXED
1/15/2014
12" BEIGE FLOOR TILE AND ADHESIVE 620 SFNORTHEAST OFFICE AREAS, MULTIPLE
TYPES MIXED
6/26/2008
FIBERGLASS INSULATION SEALANT 16 LFSOUTHEAST MECHANICAL ROOM, EAST
LOW PRESSURE STEAM RISER, HM24
ACM INSULATED LINE
2/7/2012
12" BEIGE FLOOR TILE AND ADHESIVE 540 SFNORTHEAST OFFICE AREAS, MULTIPLE
TYPES MIXED
1/6/2011
12" BEIGE FLOOR TILE AND ADHESIVE 620 SFNORTHEAST OFFICE AREAS, MULTIPLE
TYPES MIXED
2/7/2012
12" BEIGE FLOOR TILE AND ADHESIVE 620 SFNORTHEAST OFFICE AREAS, MULTIPLE
TYPES MIXED
6/7/2016
FIBERGLASS INSULATION SEALANT 2 LFSOUTHEAST MECHANICAL ROOM, EAST
LOW PRESSURE STEAM RISER, HM24
ACM INSULATED LINE
6/7/2016
12" BEIGE FLOOR TILE AND ADHESIVE NORTHEAST OFFICE AREAS, MULTIPLE
TYPES MIXED
12/20/2001
ROOFING SEALANT, GRAY ROOF VENT AND HATCH FLASHING
PATCHING
6/26/2008
ROOFING MATERIAL, ROOFING SYSTEM AT SEAMS AND
FLASHING
6/26/2008
EXTERIOR CAULKING, METAL DOORS 6/26/2008
ROLLED ROOFING ROOFING SYSTEM 6/26/2008
BROWN VINYL BASE AND ADHESIVE, 4" NORTHEAST OFFICE AREAS w/HM01
TILES
6/26/2008
GASKET MATERIAL SOUTHEAST MECHANICAL ROOM AT
TANK
1/6/2011
GASKET MATERIAL SOUTHEAST MECHANICAL ROOM,
DEBRIS
1/6/2011
Thursday, August 14, 2025 Page 3 of 7Print Date:
ACM only presents a health hazard when asbestos fibers are airborne and inhaled.
Avoid disturbance which will release fibers. The presence of asbestos does not constitute a health hazard.
HEALTH ASPECTS:
Do not disturb or cause damage to ACM. Do not sand, grind or abrade materials or cause damage with any type of equipment.
CONDITIONS TO AVOID:
Report any damage, dust or debris that may come from ACM or suspect ACM, or any change in the condition of materials, or accidental disturbance to the Asbestos
Program Manager.
REPORTS OF DAMAGE:
Corrective action initiated to minimize fiber release and protect personnel. RESPONSE ACTION:
ACM will be inspected periodically to evaluate any changes in condition.INSPECTION:
The Camp Lejeune Asbestos Program Manager maintains a copy of the survey for the building.
RECORDKEEPING:
CAMP LEJEUNE Asbestos Program Manager: Phone: (910) 451-5837
FOIL BACKED TAPE OVERHEAD HVAC DUCTS AT SEAMS 1/6/2011
CLOTH LAGGING MATERIAL INTERIOR ACCESSIBLE VERTICAL PIPES
OVER FIBERGLASS (SEE ALSO HM31)
1/6/2011
VINYL THRESHOLD MATERIAL NORTHEAST OFFICE AREAS w/HM01
TILES
2/7/2012
CLOTH LAGGING MATERIAL SOUTHEAST MECHANICAL ROOM ON
FIBERGLASS PIPING AND HVAC DUCT
INSULATION; CRAWLSPACE ON
FIBERGLASS PIPING (SEE ALSO HM28)
2/7/2012
FIBERGLASS INSULATION SEALANT SOUTHEAST MECHANICAL ROOM AND
OVERHEAD PIPING SYSTEMS
1/6/2011
MUDDED FITTING(S) SOUTHEAST MECHANICAL ROOM 1/6/2011
EXTERIOR CAULKING, WINDOWS 1/6/2011
BROWN VINYL BASE AND ADHESIVE, 4" NORTHEAST OFFICE AREAS w/HM01
TILES
1/6/2011
Thursday, August 14, 2025 Page 4 of 7Print Date:
SAMPLES COLLECTED
Sample Sample
Date
HA Sample Location Chr
Amo
Oth
Description
G640-01-00ri10 1/6/201101 N/A 9 9 912" BEIGE FLOOR TILE
AND ADHESIVE
w/BRN-WHT STREAKS
G640-01-00ri13 1/15/201401 N/A 9 9 912" BEIGE FLOOR TILE
AND ADHESIVE
w/BRN-WHT STREAKS
G640-01-00ri16 6/7/201601 N/A 9 9 912" BEIGE FLOOR TILE
AND ADHESIVE
w/BRN-WHT STREAKS
G640-01-01 12/20/200101 NE MILITARY OFFICE 0 0 012" BEIGE FLOOR TILE
AND ADHESIVE
w/BRN-WHT STREAKS
G640-01-02 12/20/200101 NE CIVILIAN OFFICE 0 0 012" BEIGE FLOOR TILE
AND ADHESIVE
w/BRN-WHT STREAKS
G640-01-10 6/26/200801 NE OFFICES 2 0 012" BEIGE FLOOR TILE
AND ADHESIVE
w/BRN-WHT STREAKS
G640-01-10tem 6/26/200801 NE OFFICES 0 0 012" BEIGE FLOOR TILE
AND ADHESIVE
w/BRN-WHT STREAKS
G640-01-11 6/26/200801 NE OFFICES 0 0 012" BEIGE FLOOR TILE
AND ADHESIVE
w/BRN-WHT STREAKS
G640-01-20 1/6/201101 NE LOCKER RM 0 0 012" BEIGE FLOOR TILE
AND ADHESIVE
w/BRN-WHT STREAKS
G640-01-20tem 1/6/201101 NE LOCKER RM 0 0 012" BEIGE FLOOR TILE
AND ADHESIVE
w/BRN-WHT STREAKS
G640-01-30 2/7/201201 NE LOCKER RM 0 0 012" BEIGE FLOOR TILE
AND ADHESIVE
w/BRN-WHT STREAKS
G640-01-30tem 2/7/201201 NE LOCKER RM 1.2 0 012" BEIGE FLOOR TILE
AND ADHESIVE
w/BRN-WHT STREAKS
G640-01-60 7/20/202201 NE OFFICE AREA, OFFICE 0 0 012" BEIGE FLOOR TILE
AND ADHESIVE
w/BRN-WHT STREAKS
G640-01-60tem 7/20/202201 NE OFFICE AREA, OFFICE 0 0 012" BEIGE FLOOR TILE
AND ADHESIVE
w/BRN-WHT STREAKS
G640-10-10 6/26/200810 ROOF, CNTR EAST 0 0 0ROLLED ROOFING
G640-10-11 6/26/200810 ROOF, CNTR SOUTH 0 0 0ROLLED ROOFING
G640-11-10 6/26/200811 ROOF, EAST CNTR 0 0 0ROOFING MATERIAL, TAR
G640-11-11 6/26/200811 ROOF, SOUTH CNTR 0 0 0ROOFING MATERIAL, TAR
G640-12-10 6/26/200812 ROOF, NE HATCH 0 0 0ROOFING SEALANT,
GRAY
Thursday, August 14, 2025 Page 5 of 7Print Date:
HA Sample Location Chr
Amo
Oth
Description
G640-12-11 6/26/200812 ROOF, NW VENT 0 0 0ROOFING SEALANT,
GRAY
G640-13-10 6/26/200813 NE OFFICE 0 0 0BROWN VINYL BASE
AND ADHESIVE, 4"
G640-13-2920 1/6/201113 NE OFFICE 0 0 0BROWN VINYL BASE
AND ADHESIVE, 4"
G640-14-10 6/26/200814 SOUTHSIDE, EAST ENTRY 0 0 0EXTERIOR CAULKING, GRAY
G640-14-11 6/26/200814 WESTSIDE, SOUTH ENTRY 0 0 0EXTERIOR CAULKING, GRAY
G640-20-20 1/6/201120 NORTHSIDE, CNTR WEST 0 0 0EXTERIOR CAULKING, WHITE
G640-20-21 1/6/201120 SOUTHSIDE, CNTR WEST 0 0 0EXTERIOR CAULKING, WHITE
G640-21-20 1/6/201121 SE MECH RM 0 0 0FIBERGLASS
INSULATION SEALANT
WHITE
G640-22-20 1/6/201122 SE MECH RM 0 0 0MUDDED FITTING(S) GRAY
G640-23-20 1/6/201123 SE MECH RM 0 0 0GASKET MATERIAL RED
G640-24-00ri13 1/15/201424 N/A 9 9 9PIPE INSULATION
G640-24-00ri16 6/7/201624 N/A 9 9 9PIPE INSULATION
G640-24-20 1/6/201124 SE MECH RM, EAST 0 3 0PIPE INSULATION
G640-24-21 1/6/201124 SE MECH RM, EAST 0 4 0PIPE INSULATION
G640-24-30 2/7/201124 SE MAIN MECH RM, NORTH
CNTR OVHD
0 2 0PIPE INSULATION
G640-25-20 1/6/201125 SE MECH RM 0 0 0GASKET MATERIAL GRAY
G640-26-00ri13 1/15/201426 N/A 9 9 9FIBERGLASS
INSULATION SEALANT
GRAY/ BLACK/ SILVER
G640-26-00ri16 6/7/201626 N/A 9 9 9FIBERGLASS
INSULATION SEALANT
GRAY/ BLACK/ SILVER
G640-26-20 1/6/201126 SE MECH RM, EAST 3 0 0FIBERGLASS
INSULATION SEALANT
GRAY/ BLACK/ SILVER
G640-26-30 2/7/201226 SE MECH RM, EAST CNTR 8 0 0FIBERGLASS
INSULATION SEALANT
GRAY/ BLACK/ SILVER
G640-27-20 1/6/201127 NE ENTRY CORRIDOR OVHD 0 0 0FOIL BACKED TAPE
G640-28-20 1/6/201128 NE KITCHEN/ BAKERY, NW 0 0 0CLOTH LAGGING
MATERIAL
Thursday, August 14, 2025 Page 6 of 7Print Date:
HA Sample Location Chr
Amo
Oth
Description
G640-30-30 2/7/201230 NE OFFICE AT HALLWAY 0 0 0VINYL THRESHOLD
MATERIAL
1" BROWN
G640-31-30 2/7/201231 SE MECH RM PIPE, EAST
CNTR
0 0 0CLOTH LAGGING
MATERIAL
G640-31-31 2/7/201231 SE MECH RM DUCT, NORTH
CNTR
0 0 0CLOTH LAGGING
MATERIAL
G640-31-32 2/7/201231 CRAWLSPACE PIPE, SE AT
MECH RM TUNNEL
0 0 0CLOTH LAGGING
MATERIAL
Thursday, August 14, 2025 Page 7 of 7Print Date: