This file is a Facility Maintenance Plan (FMP) for the Yongsan Garrison fuel service station in Seoul, Korea, prepared by APTIM Federal Services, LLC under contract W912DY-21-F-0076 with the U.S. Army Corps of Engineers Pacific Ocean Division. The document details a comprehensive maintenance plan for a fuel service station with multiple underground storage tanks, including (3) 10,000-gallon diesel tanks and (2) 10,000-gallon Mogas tanks, along with multiple dispensers, offloading areas, and associated infrastructure.
The maintenance plan includes a detailed task matrix with specific maintenance requirements for various system components, covering quarterly, semi-annual, and annual maintenance frequencies. Key maintenance elements include inspecting and testing equipment such as ball valves, check valves, ground reels, centrifugal pumps, dispensers, hoses, nozzles, electrical systems, and containment areas. The document provides precise tracking information using Component Unique Identifiers (CUID) and references specific Unified Facilities Criteria (UFC) sections for maintenance guidelines. The plan is part of a broader effort by the U.S. Army Corps of Engineers to maintain fuel infrastructure at the Yongsan Garrison site.
View the file
Other files
Show all 37
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Administrative
| ADMINISTRATIVE | ||
| Location | Installation Name | Yongsan Garrison |
| DLA Site Code | YSG | |
| RPSUID | 7992 | |
| Hours of Operation | 0800-1630 | |
| Address | Seoul, Korea | |
| Contract | Contractor | |
| Contract # | ||
| Local POCs | Primary QAE | |
| QAE Phone | ||
| QAE Email | ||
| Alternate QAE | ||
| Alt QAE Phone | ||
| Alt QAE Email | ||
| Contractor POCs | Contractor PM | |
| Contractor PM Phone | ||
| Contractor PM Email | ||
| Contractor QC Manager | ||
| Contractor QC Phone | ||
| Contractor QC Email | ||
| Contractor SOE | ||
| Contractor SOE Phone | ||
| Contractor SOE Email | ||
| Contractor RM | ||
| Contractor RM Phone | ||
| Contractor RM Email | ||
| Contractor SM | ||
| Contractor SM Phone | ||
| Contractor SM Email | ||
| USACE POCs | USACE PM/COR | |
| USACE PM/COR Phone | ||
| USACE PM/COR Email | ||
| USACE PE | ||
| USACE PE Phone | ||
| USACE PE Email | ||
| USACE KO | ||
| USACE KO Phone | ||
| USACE KO Email | ||
| USACE Monthly Report Inbox |
Pacific Ocean Division, POD-AF
| W912DY-21-F-0076 | &"-,Bold"&16Yongsan Garrison |
| YSG | Facility Maintenance Plan |
OY3 Q1
&A &P of &N APTIM Federal Services, LLC
Instructions:
This table shows the minimum information required. Additional details should be included based on site specific requirements. Additional POCs may be required.
General Facility Description
| General Facility Description | |
| Installation Name | Yongsan Garrison |
| DLA Site Code | YSG |
| Location | Seoul, Korea |
| Service Station: (3) 10,000-gallon diesel USTs (Tanks 1-3 - 580, 581, 582), (2) 10,000-gallon Mogas USTs (Tanks 4-5 - 583, 584), (5) dispensers for diesel each with (2) nozzles, (3) dispensers for Mogas each with (2) nozzles (571), office, retail sales office, and awning/canopy over dispensers. | |
| Ahntech Corporation operates the system and performs routine maintenance, daily, weekly, quarterly and annually. |
Pacific Ocean Division, POD-AF
| W912DY-21-F-0076 | &"-,Bold"&16Yongsan Garrison |
| YSG | Facility Maintenance Plan |
OY3 Q1
&A &P of &N APTIM Federal Services, LLC
Instructions:
Include a general facility overview and description of each fuel system for the sites in accordance with UFC 3-460-01. Examples include: Bulk Storage Facilities, Aircraft Fueling Facilities, Marine and Dispensing Facilities, Ground Products Fueling Facilities, Alternate POL Facilities, and Support Facilities. Also include facility #s, facility names, fuel type, photos, and any other pertinent information.
Include Site Specific Conditions and Restrictions in this tab.
Communication Plan
Pacific Ocean Division, POD-AF
| W912DY-21-F-0076 | &"-,Bold"&16Yongsan Garrison |
| YSG | Facility Maintenance Plan |
OY3 Q1
&A &P of &N APTIM Federal Services, LLC
Instructions:
Communication plan shall address in/out briefs, lines of communication, coordination for access, etc.
Site Specific Safety Plan
Pacific Ocean Division, POD-AF
| W912DY-21-F-0076 | &"-,Bold"&16Yongsan Garrison |
| YSG | Facility Maintenance Plan |
&A &P of &N APTIM Federal Services, LLC
Instructions:
Site Specific Addendum and Activity Hazard Analysis, which are Attachments to the APP, specific to activities or tasks related to recurring maintenance for this site.
PM Schedule
Pacific Ocean Division, POD-AF
| W912DY-21-F-0076 | &"-,Bold"&16&K000000Yongsan Garrison |
| YSG | Facility Maintenance Plan |
OY3 Q1
&A &P of &N APTIM Federal Services, LLC
Instructions:
Link PM schedule here
Task Matrix
| Applicable Facility Assets | UFC System Level Maintenance Frequency | Special Considerations | ||||||||||||||||||
| RPUID | Real Property Facility # | Facility Name | Operational Area | Component Type | Base Asset Name | Component Unique ID CUID | APTIM Asset ID | Asset Description | Make | Model | Capacity / Size | Quarterly | Semi Annual | Annual | UFC Section Reference | Additional Manufacturer RM Requirements | Operator/Equipment Requirements | System Availability | Other Contract | Comments |
| 999000058000035 | YSG-5704-02 | 5704-02-TK TRK LD/UNLD (UNDER FAC_5704 CANOPY) | SERVICE STATION | MV-Ball Valves | R1 | YSG-5704-BLVL-178090 | YSG00001 | Located on the inlet side of the MOGAS offloading pump. (Valve R1) | Flow-Tek | X | Section 6-6.2.4 | Notify Facility | ||||||||
| 999000058000035 | YSG-5704-02 | 5704-02-TK TRK LD/UNLD (UNDER FAC_5704 CANOPY) | SERVICE STATION | MV-Ball Valves | R2 | YSG-5704-BLVL-175638 | YSG00002 | Located on the 3 inch MOGAS receipt piping | Flow-Tek | X | Section 6-6.2.4 | Notify Facility | ||||||||
| 999000058000035 | YSG-5704-02 | 5704-02-TK TRK LD/UNLD (UNDER FAC_5704 CANOPY) | SERVICE STATION | MV-Ball Valves | R3 | YSG-5704-BLVL-175639 | YSG00003 | Located on the inlet side of the diesel offloading pump. (Valve R3) | Flow-Tek | X | Section 6-6.2.4 | Notify Facility | ||||||||
| 999000058000035 | YSG-5704-02 | 5704-02-TK TRK LD/UNLD (UNDER FAC_5704 CANOPY) | SERVICE STATION | MV-Ball Valves | R4 | YSG-5704-BLVL-175640 | YSG00004 | Located on the 3 inch diesel receipt piping. (Valve R4) | Flow-Tek | X | Section 6-6.2.4 | Notify Facility | ||||||||
| 999000058000035 | YSG-5704-02 | 5704-02-TK TRK LD/UNLD (UNDER FAC_5704 CANOPY) | SERVICE STATION | MV-Ball Valves | YSG-5704-BLVL-175710 | YSG00005 | Located inside the Diesel Pump Offload cabinet | MATCO-NORCA | 752N | X | Section 6-6.2.4 | Notify Facility | ||||||||
| 999000058000035 | YSG-5704-02 | 5704-02-TK TRK LD/UNLD (UNDER FAC_5704 CANOPY) | SERVICE STATION | MV-Ball Valves | YSG-5704-BLVL-175493 | YSG00006 | Located inside the MOGAS Pump Offload cabinet | MATCO-NORCA | 752N | X | Section 6-6.2.4 | Notify Facility | ||||||||
| 999000058000035 | YSG-5704-02 | 5704-02-TK TRK LD/UNLD (UNDER FAC_5704 CANOPY) | SERVICE STATION | MV-Check Valves | YSG-5704-CKVL-175711 | YSG00007 | Located on the outlet side of the diesel offloading pump | X | Section 6-6.2.8 | Operate System to Test | ||||||||||
| 999000058000035 | YSG-5704-02 | 5704-02-TK TRK LD/UNLD (UNDER FAC_5704 CANOPY) | SERVICE STATION | MV-Check Valves | YSG-5704-CKVL-175494 | YSG00008 | Located on the outlet side of the MOGAS offloading pump | X | Section 6-6.2.8 | Operate System to Test | ||||||||||
| 999000058000035 | YSG-5704-02 | 5704-02-TK TRK LD/UNLD (UNDER FAC_5704 CANOPY) | SERVICE STATION | EC-Ground Reels - Static Grounding Systems | YSG-5704-STGS-178091 | YSG00009 | Located next to the MOGAS offloading cabinet | SAMKOOK Ind. Co., Ltd. | K-REEL ER-315 | X | X | Section 9-1.6.2 | MAX WINDING LENGTH 15 M | |||||||
| 999000058000035 | YSG-5704-02 | 5704-02-TK TRK LD/UNLD (UNDER FAC_5704 CANOPY) | SERVICE STATION | PM-Centrifugal Pumps | YSG-5704-CENP-178092 | YSG00010 | Diesel offload pump located at the truck offloading area | Gorman-Rupp | O2K3-X2 1P | X | X | X | Section 3-8.1 | Operate System to Test | ||||||
| 999000058000035 | YSG-5704-02 | 5704-02-TK TRK LD/UNLD (UNDER FAC_5704 CANOPY) | SERVICE STATION | PM-Centrifugal Pumps | YSG-5704-CENP-175712 | YSG00011 | MOGAS offload pump located at the truck offloading area | Gorman-Rupp | O2K3-X2 1P | X | X | X | Section 3-8.1 | Operate System to Test | ||||||
| 999000058000035 | YSG-5704-02 | 5704-02-TK TRK LD/UNLD (UNDER FAC_5704 CANOPY) | SERVICE STATION | FT-Basket Strainer | YSG-5704-ASSET-178093 | YSG00012 | Y strainer located on the 3 inch piping from the Diesel Offload Pump | Morrison Bros. Co. | X | X | Section 3-6.4 | |||||||||
| 999000058000035 | YSG-5704-02 | 5704-02-TK TRK LD/UNLD (UNDER FAC_5704 CANOPY) | SERVICE STATION | FT-Basket Strainer | YSG-5704-ASSET-175495 | YSG00013 | Y strainer located on the 3 inch piping from the MOGAS Offload Pump | Morrison Bros. Co. | X | X | Section 3-6.4 | |||||||||
| 999000058000035 | YSG-5704-02 | 5704-02-TK TRK LD/UNLD (UNDER FAC_5704 CANOPY) | SERVICE STATION | MV-Check Valves | YSG-5704-CKVL-175641 | YSG00020 | Located on the 3 inch diesel receipt line for Tank-2 | Magnatrol Valve Corporati | TYPE F44AV49 | X | Section 6-6.2.8 | Operate System to Test | ||||||||
| 999000058000035 | YSG-5704-02 | 5704-02-TK TRK LD/UNLD (UNDER FAC_5704 CANOPY) | SERVICE STATION | MV-Check Valves | YSG-5704-CKVL-175496 | YSG00021 | Located on the 3 inch diesel receipt line for Tank-3 | Magnatrol Valve Corporati | TYPE F44AV49 | X | Section 6-6.2.8 | Operate System to Test | ||||||||
| 999000058000035 | YSG-5704-02 | 5704-02-TK TRK LD/UNLD (UNDER FAC_5704 CANOPY) | SERVICE STATION | MV-Check Valves | YSG-5704-CKVL-175713 | YSG00023 | Located on the 3 inch MOGAS receipt line for Tank-5 | Magnatrol Valve Corporati | TYPE F44AV49 | X | Section 6-6.2.8 | Operate System to Test | ||||||||
| 973582 | YSG-5704 | 5704-OVERHEAD PROT | SERVICE STATION | SF-Canopies | YSG-5704-CNPY-175642 | YSG00024 | Truck offload canopy | X | Section 11-2.2 | |||||||||||
| 999000058000035 | YSG-5704-02 | 5704-02-TK TRK LD/UNLD (UNDER FAC_5704 CANOPY) | SERVICE STATION | SF-Fuel Truck Containment Areas | YSG-5704-FTKRCC-178094 | YSG00025 | Truck offload containment under canopy | X | X | Section 11-1.1 | ||||||||||
| 999000058000035 | YSG-5704-02 | 5704-02-TK TRK LD/UNLD (UNDER FAC_5704 CANOPY) | SERVICE STATION | EQ-Real Property | YSG-5704-ASSET-175643 | YSG00026 | Asphalt along side containment under canopy - NOT containment | Non-Appx G Class | ||||||||||||
| 999000058000035 | YSG-5704-02 | 5704-02-TK TRK LD/UNLD (UNDER FAC_5704 CANOPY) | SERVICE STATION | PC-Aboveground Piping and Equipment Coating | YSG-5704-AGPCT-175714 | YSG00027 | Exposed Piping: Diesel and MOGAS 3 inch receipt piping | Section 6-10.1 | ||||||||||||
| 999000058000035 | YSG-5704-02 | 5704-02-TK TRK LD/UNLD (UNDER FAC_5704 CANOPY) | SERVICE STATION | PC-Aboveground Piping and Equipment Coating | YSG-5704-AGPCT-175497 | YSG00028 | Exposed Piping: Diesel and MOGAS 2 inch receipt piping | Section 6-10.1 | ||||||||||||
| 971025 | YSG-5708 | 5708-FUEL/POL BLDG | SERVICE STATION | EC-Panelboards | PA | YSG-5708-PNB-178095 | YSG00029 | Panelboard (PA) located inside facility S5708 | Square D | X | Section 9-1.5 | Coordinate with Facility | ||||||||
| 971132 | YSG-571 | 571-GAS STATION MOGAS | SERVICE STATION | SF-Fuel Truck Containment Areas | YSG-571-FTKRCC-175498 | YSG00030 | Service station containment around dispenser islands | X | X | Section 11-1.1 | ||||||||||
| 971132 | YSG-571 | 571-GAS STATION MOGAS | SERVICE STATION | DS-Dispenser Cabinet | S 571A | YSG-571-DSCB-165628 | YSG00032 | Diesel Dispensers 3 & 4 | Gasboy | 9853KXTW1 | X | Section 7-7 | Key Required to Open Dispenser | |||||||
| 971132 | YSG-571 | 571-GAS STATION MOGAS | SERVICE STATION | DS-Dispenser Cabinet | S 571D | YSG-571-DSCB-165629 | YSG00035 | MOGAS Dispensers 9 & 10 | Gasboy | 9853KXTW1 | X | Section 7-7 | Key Required to Open Dispenser | |||||||
| 971132 | YSG-571 | 571-GAS STATION MOGAS | SERVICE STATION | DS-Dispenser Cabinet | S 571E | YSG-571-DSCB-165630 | YSG00036 | MOGAS Dispensers 11 & 12 | Gasboy | 9853KXTW1 | X | Section 7-7 | Key Required to Open Dispenser | |||||||
| 971132 | YSG-571 | 571-GAS STATION MOGAS | SERVICE STATION | DS-Dispenser Cabinet | S 571G | YSG-571-DSCB-165631 | YSG00038 | Diesel Dispensers 15 &16 | Gasboy | 9853KXTW1 | X | Section 7-7 | Key Required to Open Dispenser | |||||||
| 971132 | YSG-571 | 571-GAS STATION MOGAS | SERVICE STATION | GF-Gov SS EFSO Systems | YSG-571-EFSO-175715 | YSG00039 | EFSO located across from dispensers 13 & 14 | X | Section 7-16 | Operate System to Test | ||||||||||
| 1214461 | YSG-572 | 572-OVERHEAD PROT | SERVICE STATION | SF-Canopies | YSG-571-CNPY-175716 | YSG00040 | Canopy for dispensers | X | Section 11-2.2 | |||||||||||
| 971132 | YSG-571 | 571-GAS STATION MOGAS | SERVICE STATION | GF-Gov SS EFSO Systems | YSG-571-EFSO-175499 | YSG00041 | EFSO located at the site entrance gate | X | Section 7-16 | Operate System to Test | ||||||||||
| 971132 | YSG-571 | 571-GAS STATION MOGAS | SERVICE STATION | GF-Gov SS EFSO Systems | YSG-571-EFSO-175717 | YSG00042 | EFSO located at the site exit gate | X | Section 7-16 | Operate System to Test | ||||||||||
| 974475 | YSG-5700 | 5700-FUEL/POL BLDG | SERVICE STATION | GF-Gov SS EFSO Systems | YSG-5700-EFSO-175718 | YSG00043 | EFSO located inside building 5700 | X | Section 7-16 | Operate System to Test | ||||||||||
| 971132 | YSG-571 | 571-GAS STATION MOGAS | SERVICE STATION | DS-Breakaways | YSG-571-DSBW-168138 | YSG00044 | Diesel Dispenser #3 | Emco Wheaton | X | Section 7-4 | ||||||||||
| 971132 | YSG-571 | 571-GAS STATION MOGAS | SERVICE STATION | DS-Breakaways | YSG-571-DSBW-178096 | YSG00045 | Diesel Dispenser #4 | Emco Wheaton | X | Section 7-4 | ||||||||||
| 971132 | YSG-571 | 571-GAS STATION MOGAS | SERVICE STATION | DS-Dispenser Filters | YSG-571-DSFLR-175644 | YSG00046 | Diesel Dispenser #3 | Cim-Tek Filtration | X | Section 7-9 | Key Required to Open Dispenser | |||||||||
| 971132 | YSG-571 | 571-GAS STATION MOGAS | SERVICE STATION | DS-Dispenser Filters | YSG-571-DSFLR-178097 | YSG00047 | Diesel Dispenser #4 | Cim-Tek Filtration | X | Section 7-9 | Key Required to Open Dispenser | |||||||||
| 971132 | YSG-571 | 571-GAS STATION MOGAS | SERVICE STATION | DS-Dispenser Hoses | YSG-571-DSHS-175645 | YSG00048 | Diesel Dispenser #3 Short Hose | LRPCO | X | Section 7-3 | ||||||||||
| 971132 | YSG-571 | 571-GAS STATION MOGAS | SERVICE STATION | DS-Dispenser Hoses | YSG-571-DSHS-175500 | YSG00049 | Diesel Dispenser #3 Long Hose | LRPCO | X | Section 7-3 | ||||||||||
| 971132 | YSG-571 | 571-GAS STATION MOGAS | SERVICE STATION | DS-Dispenser Hoses | YSG-571-DSHS-175646 | YSG00050 | Diesel Dispenser #4 Short Hose | LRPCO | X | Section 7-3 | ||||||||||
| 971132 | YSG-571 | 571-GAS STATION MOGAS | SERVICE STATION | DS-Dispenser Hoses | YSG-571-DSHS-165782 | YSG00051 | Diesel Dispenser #4 Long Hose | LRPCO | X | Section 7-3 | ||||||||||
| 971132 | YSG-571 | 571-GAS STATION MOGAS | SERVICE STATION | DS-Dispenser Meters | YSG-571-DSMTR-165805 | YSG00052 | Diesel Dispenser #3 | Gasboy | T20150 | X | Section 7-8 | Key Req to Open Dispenser; Operate for Calibration | ||||||||
| 971132 | YSG-571 | 571-GAS STATION MOGAS | SERVICE STATION | DS-Dispenser Meters | YSG-571-DSMTR-165806 | YSG00053 | Diesel Dispenser #4 | Gasboy | T20150 | X | Section 7-8 | Key Req to Open Dispenser; Operate for Calibration | ||||||||
| 971132 | YSG-571 | 571-GAS STATION MOGAS | SERVICE STATION | DS-Dispenser Nozzles | YSG-571-DSNZ-175647 | YSG00054 | Diesel Dispenser #3 | CATLOW | X | Section 7-2 | Operate System to Test | |||||||||
| 971132 | YSG-571 | 571-GAS STATION MOGAS | SERVICE STATION | DS-Dispenser Nozzles | YSG-571-DSNZ-178098 | YSG00055 | Diesel Dispenser #4 | OPW | X | Section 7-2 | Operate System to Test | |||||||||
| 971132 | YSG-571 | 571-GAS STATION MOGAS | SERVICE STATION | DS-Dispenser Sumps | YSG-571-DSSMP-175648 | YSG00056 | Diesel Dispensers 3 & 4 | X | Section 7-13 | Key Required to Open Dispenser | ||||||||||
| 971132 | YSG-571 | 571-GAS STATION MOGAS | SERVICE STATION | DS-Emergency Shutoff Valves (Shear Valves) | YSG-571-ESHVL-178099 | YSG00057 | Diesel Dispensers 3 & 4 | EBW | X | Section 7-12 | Operate System to Test | |||||||||
| 971132 | YSG-571 | 571-GAS STATION MOGAS | SERVICE STATION | DS-Hose Retriever | YSG-571-HSRTV-165854 | YSG00058 | Diesel Dispenser #3 | Gasboy | X | Section 7-6 | ||||||||||
| 971132 | YSG-571 | 571-GAS STATION MOGAS | SERVICE STATION | DS-Hose Retriever | YSG-571-HSRTV-165855 | YSG00059 | Diesel Dispenser #4 | Gasboy | X | Section 7-6 | ||||||||||
| 971132 | YSG-571 | 571-GAS STATION MOGAS | SERVICE STATION | DS-Swivels | YSG-571-DSSW-175501 | YSG00060 | Diesel Dispenser #3 | X | Section 7-5 | No Swivel | ||||||||||
| 971132 | YSG-571 | 571-GAS STATION MOGAS | SERVICE STATION | DS-Swivels | YSG-571-DSSW-178100 | YSG00061 | Diesel Dispenser #4 | OPW | X | Section 7-5 | ||||||||||
| 971132 | YSG-571 | 571-GAS STATION MOGAS | SERVICE STATION | DS-Breakaways | YSG-571-DSBW-175502 | YSG00062 | MOGAS Dispenser #9 | OPW | X | Section 7-4 | ||||||||||
| 971132 | YSG-571 | 571-GAS STATION MOGAS | SERVICE STATION | DS-Breakaways | YSG-571-DSBW-165604 | YSG00063 | MOGAS Dispenser #10 | OPW | X | Section 7-4 | ||||||||||
| 971132 | YSG-571 | 571-GAS STATION MOGAS | SERVICE STATION | DS-Dispenser Filters | YSG-571-DSFLR-175503 | YSG00064 | MOGAS Dispenser #9 | Cim-Tek Filtration | X | Section 7-9 | Key Required to Open Dispenser | |||||||||
| 971132 | YSG-571 | 571-GAS STATION MOGAS | SERVICE STATION | DS-Dispenser Filters | YSG-571-DSFLR-175719 | YSG00065 | MOGAS Dispenser #10 | Cim-Tek Filtration | X | Section 7-9 | Key Required to Open Dispenser | |||||||||
| 971132 | YSG-571 | 571-GAS STATION MOGAS | SERVICE STATION | DS-Dispenser Hoses | YSG-571-DSHS-165783 | YSG00066 | MOGAS Dispenser #9 Short Hose | LRPCO | X | Section 7-3 | ||||||||||
| 971132 | YSG-571 | 571-GAS STATION MOGAS | SERVICE STATION | DS-Dispenser Hoses | YSG-571-DSHS-165784 | YSG00067 | MOGAS Dispenser #9 Long Hose | LRPCO | X | Section 7-3 | ||||||||||
| 971132 | YSG-571 | 571-GAS STATION MOGAS | SERVICE STATION | DS-Dispenser Hoses | YSG-571-DSHS-165785 | YSG00068 | MOGAS Dispenser #10 Short Hose | LRPCO | X | Section 7-3 | ||||||||||
| 971132 | YSG-571 | 571-GAS STATION MOGAS | SERVICE STATION | DS-Dispenser Hoses | YSG-571-DSHS-165786 | YSG00069 | MOGAS Dispenser #10 Long Hose | LRPCO | X | Section 7-3 | ||||||||||
| 971132 | YSG-571 | 571-GAS STATION MOGAS | SERVICE STATION | DS-Dispenser Meters | YSG-571-DSMTR-165807 | YSG00070 | MOGAS Dispenser #9 | Gasboy | T20150 | X | Section 7-8 | Key Req to Open Dispenser; Operate for Calibration | ||||||||
| 971132 | YSG-571 | 571-GAS STATION MOGAS | SERVICE STATION | DS-Dispenser Meters | YSG-571-DSMTR-165808 | YSG00071 | MOGAS Dispenser #10 | Gasboy | T20150 | X | Section 7-8 | Key Req to Open Dispenser; Operate for Calibration | ||||||||
| 971132 | YSG-571 | 571-GAS STATION MOGAS | SERVICE STATION | DS-Dispenser Nozzles | YSG-571-DSNZ-175651 | YSG00072 | MOGAS Dispenser #9 | OPW | X | Section 7-2 | Operate System to Test | |||||||||
| 971132 | YSG-571 | 571-GAS STATION MOGAS | SERVICE STATION | DS-Dispenser Nozzles | YSG-571-DSNZ-175720 | YSG00073 | MOGAS Dispenser #10 | OPW | X | Section 7-2 | Operate System to Test | |||||||||
| 971132 | YSG-571 | 571-GAS STATION MOGAS | SERVICE STATION | DS-Dispenser Sumps | YSG-571-DSSMP-175653 | YSG00074 | MOGAS Dispensers 9 & 10 | X | Section 7-13 | Key Required to Open Dispenser | ||||||||||
| 971132 | YSG-571 | 571-GAS STATION MOGAS | SERVICE STATION | DS-Emergency Shutoff Valves (Shear Valves) | YSG-571-ESHVL-178101 | YSG00075 | MOGAS Dispensers 9 & 10 | EBW | X | Section 7-12 | Operate System to Test | |||||||||
| 971132 | YSG-571 | 571-GAS STATION MOGAS | SERVICE STATION | DS-Hose Retriever | YSG-571-HSRTV-165856 | YSG00076 | MOGAS Dispenser #9 | Gasboy | X | Section 7-6 | ||||||||||
| 971132 | YSG-571 | 571-GAS STATION MOGAS | SERVICE STATION | DS-Hose Retriever | YSG-571-HSRTV-165857 | YSG00077 | MOGAS Dispenser #10 | Gasboy | X | Section 7-6 | ||||||||||
| 971132 | YSG-571 | 571-GAS STATION MOGAS | SERVICE STATION | DS-Swivels | YSG-571-DSSW-175504 | YSG00078 | MOGAS Dispenser #9 | OPW | X | Section 7-5 | ||||||||||
| 971132 | YSG-571 | 571-GAS STATION MOGAS | SERVICE STATION | DS-Swivels | YSG-571-DSSW-178102 | YSG00079 | MOGAS Dispenser #10 | OPW | X | Section 7-5 | ||||||||||
| 971132 | YSG-571 | 571-GAS STATION MOGAS | SERVICE STATION | DS-Breakaways | YSG-571-DSBW-165605 | YSG00080 | MOGAS Dispenser #11 | Emco Wheaton | X | Section 7-4 | ||||||||||
| 971132 | YSG-571 | 571-GAS STATION MOGAS | SERVICE STATION | DS-Breakaways | YSG-571-DSBW-165606 | YSG00081 | MOGAS Dispenser #12 | Emco Wheaton | X | Section 7-4 | ||||||||||
| 971132 | YSG-571 | 571-GAS STATION MOGAS | SERVICE STATION | DS-Dispenser Filters | YSG-571-DSFLR-175655 | YSG00082 | MOGAS Dispenser #11 | Cim-Tek Filtration | X | Section 7-9 | Key Required to Open Dispenser | |||||||||
| 971132 | YSG-571 | 571-GAS STATION MOGAS | SERVICE STATION | DS-Dispenser Filters | YSG-571-DSFLR-175657 | YSG00083 | MOGAS Dispenser #12 | Cim-Tek Filtration | X | Section 7-9 | Key Required to Open Dispenser | |||||||||
| 971132 | YSG-571 | 571-GAS STATION MOGAS | SERVICE STATION | DS-Dispenser Hoses | YSG-571-DSHS-165787 | YSG00084 | MOGAS Dispenser #11 Short Hose | LRPCO | X | Section 7-3 | ||||||||||
| 971132 | YSG-571 | 571-GAS STATION MOGAS | SERVICE STATION | DS-Dispenser Hoses | YSG-571-DSHS-165788 | YSG00085 | MOGAS Dispenser #11 Long Hose | Parker | X | Section 7-3 | ||||||||||
| 971132 | YSG-571 | 571-GAS STATION MOGAS | SERVICE STATION | DS-Dispenser Hoses | YSG-571-DSHS-165789 | YSG00086 | MOGAS Dispenser #12 Short Hose | LRPCO | X | Section 7-3 | ||||||||||
| 971132 | YSG-571 | 571-GAS STATION MOGAS | SERVICE STATION | DS-Dispenser Hoses | YSG-571-DSHS-165790 | YSG00087 | MOGAS Dispenser #12 Long Hose | LRPCO | X | Section 7-3 | ||||||||||
| 971132 | YSG-571 | 571-GAS STATION MOGAS | SERVICE STATION | DS-Dispenser Meters | YSG-571-DSMTR-165809 | YSG00088 | MOGAS Dispenser #11 | Gasboy | T20150 | X | Section 7-8 | Key Req to Open Dispenser; Operate for Calibration | ||||||||
| 971132 | YSG-571 | 571-GAS STATION MOGAS | SERVICE STATION | DS-Dispenser Meters | YSG-571-DSMTR-165810 | YSG00089 | MOGAS Dispenser #12 | Gasboy | T20150 | X | Section 7-8 | Key Req to Open Dispenser; Operate for Calibration | ||||||||
| 971132 | YSG-571 | 571-GAS STATION MOGAS | SERVICE STATION | DS-Dispenser Nozzles | YSG-571-DSNZ-178103 | YSG00090 | MOGAS Dispenser #11 | OPW | X | Section 7-2 | Operate System to Test | |||||||||
| 971132 | YSG-571 | 571-GAS STATION MOGAS | SERVICE STATION | DS-Dispenser Nozzles | YSG-571-DSNZ-175659 | YSG00091 | MOGAS Dispenser #12 | OPW | X | Section 7-2 | Operate System to Test | |||||||||
| 971132 | YSG-571 | 571-GAS STATION MOGAS | SERVICE STATION | DS-Dispenser Sumps | YSG-571-DSSMP-178104 | YSG00092 | MOGAS Dispensers 11 & 12 | X | Section 7-13 | Key Required to Open Dispenser | ||||||||||
| 971132 | YSG-571 | 571-GAS STATION MOGAS | SERVICE STATION | DS-Emergency Shutoff Valves (Shear Valves) | YSG-571-ESHVL-178105 | YSG00093 | MOGAS Dispensers 11 & 12 | EBW | X | Section 7-12 | Operate System to Test | |||||||||
| 971132 | YSG-571 | 571-GAS STATION MOGAS | SERVICE STATION | DS-Hose Retriever | YSG-571-HSRTV-165858 | YSG00094 | MOGAS Dispenser #11 | Gasboy | X | Section 7-6 | ||||||||||
| 971132 | YSG-571 | 571-GAS STATION MOGAS | SERVICE STATION | DS-Hose Retriever | YSG-571-HSRTV-165859 | YSG00095 | MOGAS Dispenser #12 | Gasboy | X | Section 7-6 | ||||||||||
| 971132 | YSG-571 | 571-GAS STATION MOGAS | SERVICE STATION | DS-Swivels | YSG-571-DSSW-175721 | YSG00096 | MOGAS Dispenser #11 | Emco Wheaton | X | Section 7-5 | ||||||||||
| 971132 | YSG-571 | 571-GAS STATION MOGAS | SERVICE STATION | DS-Swivels | YSG-571-DSSW-175505 | YSG00097 | MOGAS Dispenser #12 | CATLOW | X | Section 7-5 | ||||||||||
| 971132 | YSG-571 | 571-GAS STATION MOGAS | SERVICE STATION | DS-Breakaways | YSG-571-DSBW-165607 | YSG00098 | Diesel Dispenser #15 | Emco Wheaton | X | Section 7-4 | ||||||||||
| 971132 | YSG-571 | 571-GAS STATION MOGAS | SERVICE STATION | DS-Breakaways | YSG-571-DSBW-165608 | YSG00099 | Diesel Dispenser #16 | Emco Wheaton | X | Section 7-4 | ||||||||||
| 971132 | YSG-571 | 571-GAS STATION MOGAS | SERVICE STATION | DS-Dispenser Filters | YSG-571-DSFLR-175661 | YSG00100 | Diesel Dispenser #15 | Cim-Tek Filtration | X | Section 7-9 | Key Required to Open Dispenser | |||||||||
| 971132 | YSG-571 | 571-GAS STATION MOGAS | SERVICE STATION | DS-Dispenser Filters | YSG-571-DSFLR-175722 | YSG00101 | Diesel Dispenser #16 | Cim-Tek Filtration | X | Section 7-9 | Key Required to Open Dispenser | |||||||||
| 971132 | YSG-571 | 571-GAS STATION MOGAS | SERVICE STATION | DS-Dispenser Hoses | YSG-571-DSHS-165791 | YSG00102 | Diesel Dispenser #15 Short Hose | LRPCO | X | Section 7-3 | ||||||||||
| 971132 | YSG-571 | 571-GAS STATION MOGAS | SERVICE STATION | DS-Dispenser Hoses | YSG-571-DSHS-165792 | YSG00103 | Diesel Dispenser #15 Long Hose | LRPCO | X | Section 7-3 | ||||||||||
| 971132 | YSG-571 | 571-GAS STATION MOGAS | SERVICE STATION | DS-Dispenser Hoses | YSG-571-DSHS-165793 | YSG00104 | Diesel Dispenser #16 Short Hose | LRPCO | X | Section 7-3 | ||||||||||
| 971132 | YSG-571 | 571-GAS STATION MOGAS | SERVICE STATION | DS-Dispenser Hoses | YSG-571-DSHS-165794 | YSG00105 | Diesel Dispenser #16 Long Hose | LRPCO | X | Section 7-3 | ||||||||||
| 971132 | YSG-571 | 571-GAS STATION MOGAS | SERVICE STATION | DS-Dispenser Meters | YSG-571-DSMTR-165811 | YSG00106 | Diesel Dispenser #15 | Gasboy | T20150 | X | Section 7-8 | Key Req to Open Dispenser; Operate for Calibration | ||||||||
| 971132 | YSG-571 | 571-GAS STATION MOGAS | SERVICE STATION | DS-Dispenser Meters | YSG-571-DSMTR-165812 | YSG00107 | Diesel Dispenser #16 | Gasboy | T20150 | X | Section 7-8 | Key Req to Open Dispenser; Operate for Calibration | ||||||||
| 971132 | YSG-571 | 571-GAS STATION MOGAS | SERVICE STATION | DS-Dispenser Nozzles | YSG-571-DSNZ-178106 | YSG00108 | Diesel Dispenser #15 | CATLOW | X | Section 7-2 | Operate System to Test | |||||||||
| 971132 | YSG-571 | 571-GAS STATION MOGAS | SERVICE STATION | DS-Dispenser Nozzles | YSG-571-DSNZ-175723 | YSG00109 | Diesel Dispenser #16 | OPW | X | Section 7-2 | Operate System to Test | |||||||||
| 971132 | YSG-571 | 571-GAS STATION MOGAS | SERVICE STATION | DS-Dispenser Sumps | YSG-571-DSSMP-175506 | YSG00110 | Diesel Dispensers 15 & 16 | X | Section 7-13 | Key Required to Open Dispenser | ||||||||||
| 971132 | YSG-571 | 571-GAS STATION MOGAS | SERVICE STATION | DS-Emergency Shutoff Valves (Shear Valves) | YSG-571-ESHVL-175507 | YSG00111 | Diesel Dispensers 15 & 16 | EBW | X | Section 7-12 | Operate System to Test | |||||||||
| 971132 | YSG-571 | 571-GAS STATION MOGAS | SERVICE STATION | DS-Hose Retriever | YSG-571-HSRTV-165860 | YSG00112 | Diesel Dispenser #15 | Gasboy | X | Section 7-6 | ||||||||||
| 971132 | YSG-571 | 571-GAS STATION MOGAS | SERVICE STATION | DS-Hose Retriever | YSG-571-HSRTV-165861 | YSG00113 | Diesel Dispenser #16 | Gasboy | X | Section 7-6 | ||||||||||
| 971132 | YSG-571 | 571-GAS STATION MOGAS | SERVICE STATION | DS-Swivels | YSG-571-DSSW-175724 | YSG00114 | Diesel Dispenser #15 | X | Section 7-5 | |||||||||||
| 971132 | YSG-571 | 571-GAS STATION MOGAS | SERVICE STATION | DS-Swivels | YSG-571-DSSW-175725 | YSG00115 | Diesel Dispenser #16 | X | Section 7-5 | No Swivel | ||||||||||
| 1162750 | YSG-581 | 581-DIESEL STR TANK UNGD | SERVICE STATION | TK-Underground Double-Walled Shop-Fabricated Tanks | S 581 | YSG-581-UGDSFT-175726 | YSG00117 | Underground Diesel Tank-2 | Containment Solutions, In | Type II (8ft) | X | Section 8-5.4.2 | ||||||||
| 1162750 | YSG-581 | 581-DIESEL STR TANK UNGD | SERVICE STATION | EQ-Air Vent | YSG-581-ASSET-175727 | YSG00118 | Tank vent for Diesel Tank 2 | Non-Appx G Class | At Height-Ladder Required | |||||||||||
| 1162750 | YSG-581 | 581-DIESEL STR TANK UNGD | SERVICE STATION | GF-Remote Dispenser Pumps | YSG-581-RDSP-175663 | YSG00119 | Red Jacket Pump located inside manway | FE Petro | X | X | X | Section 7-15.1 | Operate System to Test | |||||||
| 1162751 | YSG-582 | 582-DIESEL STR TANK UNGD (TANK 3) | SERVICE STATION | TK-Underground Double-Walled Shop-Fabricated Tanks | S 582 | YSG-582-UGDSFT-175665 | YSG00120 | Underground Diesel Tank-3 | Containment Solutions, In | Type II (8ft) | X | Section 8-5.4.2 | ||||||||
| 1162751 | YSG-582 | 582-DIESEL STR TANK UNGD (TANK 3) | SERVICE STATION | EQ-Air Vent | YSG-582-ASSET-175728 | YSG00121 | Tank vent for Diesel Tank-3 | Non-Appx G Class | At Height-Ladder Required | |||||||||||
| 1162751 | YSG-582 | 582-DIESEL STR TANK UNGD (TANK 3) | SERVICE STATION | GF-Remote Dispenser Pumps | YSG-582-RDSP-175666 | YSG00122 | Red Jacket Pump located inside manway | FE Petro | X | X | X | Section 7-15.1 | Operate System to Test | |||||||
| 1162929 | YSG-584 | 584-MOGAS STR TANK UNGD (TANK 5) | SERVICE STATION | TK-Underground Double-Walled Shop-Fabricated Tanks | S 584 | YSG-584-UGDSFT-175508 | YSG00124 | Underground MOGAS Tank-5 | Containment Solutions, In | Type II (8ft) | X | Section 8-5.4.2 | ||||||||
| 1162929 | YSG-584 | 584-MOGAS STR TANK UNGD (TANK 5) | SERVICE STATION | EQ-Air Vent | YSG-584-ASSET-175509 | YSG00125 | Tank vent for MOGAS Tank-5 | Non-Appx G Class | At Height-Ladder Required | |||||||||||
| 1162929 | YSG-584 | 584-MOGAS STR TANK UNGD (TANK 5) | SERVICE STATION | GF-Remote Dispenser Pumps | YSG-584-RDSP-175668 | YSG00126 | Red Jacket Pump located inside manway | FE Petro | X | X | X | Section 7-15.1 | Operate System to Test | |||||||
| 1162750 | YSG-581 | 581-DIESEL STR TANK UNGD | SERVICE STATION | GF-Ground Vehicle Fuel Piping | YSG-581-GVFP-175699 | YSG00144 | Issue piping for diesel dispensers 1, 2, 3, and 4 | X | X | Section 7-11 | Coordinate with Facility | |||||||||
| 1162751 | YSG-582 | 582-DIESEL STR TANK UNGD (TANK 3) | SERVICE STATION | GF-Ground Vehicle Fuel Piping | YSG-582-GVFP-175700 | YSG00145 | Issue piping for diesel dispenser 15 and 16 | X | X | Section 7-11 | Coordinate with Facility | |||||||||
| 1162929 | YSG-584 | 584-MOGAS STR TANK UNGD (TANK 5) | SERVICE STATION | GF-Ground Vehicle Fuel Piping | YSG-584-GVFP-175701 | YSG00146 | Issue piping for MOGAS dispensers 9, 10, 11, and 12 | X | X | Section 7-11 | Coordinate with Facility | |||||||||
| 974118 | YSG-5709 | 5709-ADMIN OFFICE (TMP) | SERVICE STATION | SF-Emergency Eyewash/Showers | YSG-5709-EMEWSH-175510 | YSG00147 | Located on the side of facility S5709 | Haws Corporation | X | X | X | Section 11-3 | Notify Facility | |||||||
| 973677 | YSG-578 | 578-GRV OIL/GRE SEP | SERVICE STATION | SF-Oil/Water Separators | YSG-571-OWS-175511 | YSG00148 | Located near the exit gate | X | X | Section 11-5 | Notify Facility | |||||||||
| 1162750 | YSG-581 | 581-DIESEL STR TANK UNGD | SERVICE STATION | MV-Ball Valves | YSG-581-BLVL-175702 | YSG2203151011 | Ball valve located on the red jacket pump issue issue line. | X | Section 6-6.2.4 | Notify Facility | ||||||||||
| 1162751 | YSG-582 | 582-DIESEL STR TANK UNGD (TANK 3) | SERVICE STATION | MV-Ball Valves | YSG-582-BLVL-175703 | YSG2203151012 | Ball valve located on the red jacket pump issue issue line. | X | Section 6-6.2.4 | Notify Facility | ||||||||||
| 1162929 | YSG-584 | 584-MOGAS STR TANK UNGD (TANK 5) | SERVICE STATION | MV-Ball Valves | YSG-584-BLVL-175512 | YSG2203151013 | Ball valve located on the red jacket pump issue issue line. | X | Section 6-6.2.4 | Notify Facility | ||||||||||
| 974475 | YSG-5700 | 5700-FUEL/POL BLDG | SERVICE STATION | EC-Panelboards | PB | YSG-5700-PNB-178107 | YSG2206220825 | Panelboard (PB) located inside facility S5700 | Square D | X | Section 9-1.5 | Coordinate with Facility | ||||||||
| 974475 | YSG-5700 | 5700-FUEL/POL BLDG | SERVICE STATION | EC-Panelboards | PB1 | YSG-5700-PNB-175704 | YSG2206220826 | Panelboard (PB1) located inside facility S5700 | Square D | X | Section 9-1.5 | Coordinate with Facility | ||||||||
| 974118 | YSG-5709 | 5709-ADMIN OFFICE (TMP) | SERVICE STATION | EC-Panelboards | DP | YSG-5709-PNB-175705 | YSG2206220827 | Panelboard (DP) located inside facility S5709 | Square D | X | Section 9-1.5 | Coordinate with Facility | ||||||||
| 1214461 | YSG-572 | 572-OVERHEAD PROT | SERVICE STATION | EC-Lighting | YSG-571-LIGHT-175706 | YSG2206220828 | Dispenser canopy lighting. Total 16 lights at heights, two switches, and one photocell | X | X | Section 9-1.8 | At Height-Manlift Required | |||||||||
| 973582 | YSG-5704 | 5704-OVERHEAD PROT | SERVICE STATION | EC-Lighting | YSG-5704-LIGHT-175729 | YSG2206220829 | Truck offload canopy lighting. Total 6 lights at heights and one switch. No photocells. | X | X | Section 9-1.8 | At Height-Manlift Required | |||||||||
| 999000058000035 | YSG-5704-02 | 5704-02-TK TRK LD/UNLD (UNDER FAC_5704 CANOPY) | SERVICE STATION | CS-Containment Drain Valves | YSG-5700-CSGEN-167828 | YSG2206220830 | Containment drain valve (gate valve) for the truck offloading area. | X | Section 8-10.1 | Key Required | ||||||||||
| 999000058000035 | YSG-5704-02 | 5704-02-TK TRK LD/UNLD (UNDER FAC_5704 CANOPY) | SERVICE STATION | GF-Transition Sumps | YSG-5704-TRSMP-198701 | YSG328231 | Transition sump for diesel offload | X | Section 7-14 | |||||||||||
| 999000058000035 | YSG-5704-02 | 5704-02-TK TRK LD/UNLD (UNDER FAC_5704 CANOPY) | SERVICE STATION | GF-Transition Sumps | YSG-5704-TRSMP-198702 | YSG328232 | Transition sump for MOGAS offload | X | Section 7-14 |
Pacific Ocean Division, POD-AF
| W912DY-21-F-0076 | &"-,Bold"&16Yongsan Garrison |
| YSG | Facility Maintenance Plan |
OY3 Q1
&A &P of &N APTIM Federal Services, LLC
Instructions:
1. Input all data as indicated on the sheet.
2. Additional documents referred to in the Special Considerations column shall be included as an appendix to this FMP.
3. The contractor shall generate a Component Unique Identifier (CUID) for each component utilizing the Component Acronym Sheet within this Work Book. The unique identifier must use the following:
Three letter Site Code - Facility # - Component Acronym - Sequential number Example: AAD-00063A-RCVL-0001
If component acronym is not listed, the contractor shall request an acronym be established through the HNC Project Manager and Project Engineer via email. Contractors may utilize other means of tracking/labeling assets such as QR codes in addition to the required CUID however, tracking/labeling must correlate with the CUID. This CUID shall be the standard for all DLA capitalized equipment. Base Asset ID if used by site shall be cross referenced with CUID appropriately.
4. Utilize the UFC Section Reference Work Category as noted on the Component Acronym Sheet.
5. Enter any applicable manufacturer requirements not stated in the UFC. References are acceptable with attachments.
6. Enter any applicable operator support or government owned equipment required to complete the RM task.
7. Enter impact on system availability by performing the RM task. This could include shutdown, lockout, or similar impacts.
8. Enter contract information for any other contract, contractor, or government personnel performing the applicable task. This is applicable to other Centrally Managed Programs, SRM, MILCON, or Public Works/Civil Engineering projects.
9. Print Hard Copies as 11x17.
FS-PF Schedule
| FILTER SEPARATOR/PRE-FILTER MAINTENANCE SCHEDULES | |||||||||||||||
| Applicable Facility Assets | Coalescer/Separator Information | Special Considerations | |||||||||||||
| Real Property Unique Identifier | |||||||||||||||
| (RPUID) | Real Property Facility # | Real Property Facility Name | Operational Area | Component Type | Base Asset ID | Component Unique Identifier (CUID) | APTIM Asset ID* | Asset Description | Make | Model | Capacity (GPM) | UFC Section Reference | Number of Coalescer Cartridges | Number of | |
| Separator Cartridges | Coalescer Cartridges | ||||||||||||||
| Model # | Separator Cartridge | ||||||||||||||
| Model # | Clean or Replace | ||||||||||||||
| Separator Cartridge | Gasket | ||||||||||||||
| Model # | Date Last Replaced | Replacement Due Date | Operator/ Equipment Requirements | System Availability | Site Self Performs | ||||||||||
| (Y/N) | Comments | ||||||||||||||
| No FS/PF for YSG |
Pacific Ocean Division, POD-AF
| W912DY-21-F-0076 | &"-,Bold"&16Yongsan Garrison |
| YSG | Facility Maintenance Plan |
OY3 Q1
&A &P of &N APTIM Federal Services, LLC
Instructions:
1. Input all data as indicated on the sheet.
2. Additional documents referred to in the Special Considerations column shall be included as an appendix to this FMP.
3. The contractor shall generate a Component Unique Identifier (CUID) for each component utilizing the Component Acronym Sheet within this Work Book. The unique identifier must use the following:
Three letter Site Code - Facility # - Component Acronym - Sequential number Example: AAD-00063A-RCVL-0001
If component acronym is not listed, the contractor shall request an acronym be established through the HNC Project Manager and Project Engineer via email. Contractors may utilize other means of tracking/labeling assets such as QR codes in addition to the required CUID however, tracking/labeling must correlate with the CUID. This CUID shall be the standard for all DLA capitalized equipment.
4. Utilize the UFC Section Reference Work Category as noted on the Component Acronym Sheet.
5. Enter any applicable manufacturer requirements not stated in the UFC. References are acceptable with attachments.
6. Enter any applicable operator support or government owned equipment required to complete the RM task.
7. Enter impact on system availability by performing the RM task. This could include shutdown, lockout, or similar impacts.
8. Filter Separators and Pre-Filters identified here shall also be provided in the Task Matrix Tab.
9. Print Hard Copies as 11x17.
Component Acronyms
| Component Unique Identifier: | Site Code-Facility #-Component Acronym-Sequential # | ||
| Example: | AAD-00063A-RCVL-0001 | ||
| NOTE: If component acronym is not listed, the contractor shall request an acronym be established through the HNC Project Manager and Project Engineer via email. Contractors may utilize other means of tracking/labeling assets such as QR codes in addition to the required CUID however, tracking/labeling must correlate with the CUID. This CUID shall be the standard for all DLA capitalized equipment | |||
| DLA Work Type Category | UFC Section Reference Work Category | ||
| (Revised per Change 1, 29 April 2021) | Component Acronym | ||
| Air Compressors | Air Compressors | AIRC | |
| Alarms | Externally Mounted Level Alarms (Section 8-9.9.1) | EMLA | |
| Internally Mounted Level Alarms (Section 8-9.9.3) | IMLA | ||
| Bollard | Bollards | BLRD | |
| Building | Building HVAC | BHVAC | |
| Building Domestic Water System | BWTR | ||
| Building Waste Water | BWSW | ||
| Building - Lighting | BLTG | ||
| Building - Architectural | BARCH | ||
| Building - Fire Sprinkler System | BFIRE | ||
| Containment/Joints | Containment Systems (General) (Section 8-10.1) | CSGEN | |
| Concrete and Cement Brick Dike/Berm Walls (Section 8-10.2.1) | DKBW | ||
| Dike/Berm Floors (Section 8-10.2.2) | DKBF | ||
| Earthen Dike Walls (Section 8-10.3) | ETHDW | ||
| Self-Diking or Vaulted Tank Containment (Section 8-10.4) | SDVTCS | ||
| Flexible Membrane Liners (Section 8-10.5) | FXML | ||
| Fuel Truck and Rail Car Containment Areas (Section 11-1.1) | FTKRCC | ||
| Remote Spill Containment (Section 11-1.2) | RSCS | ||
| Piers and Wharves Fuel Containment Systems (Section 5-1.2) - Testing | FPWCT | ||
| Fuel Pier/Wharf Containment (PWS Section 3) | FPWC | ||
| Corrosion Control/Coatings | Aboveground Piping and Equipment Coatings (Section 6-10.1) | AGPCT | |
| Miscellaneous | Miscellaneous Deactivated Components (Section 12-5) | MDEAC | |
| Electrical/Lighting | Lighting (Section 9-1.8) | LIGHT | |
| Electrical/Power | Electrical Equipment (Section 9-1.2) | ELEQ | |
| Power Cables (Section 9-1.3) | PWRCBL | ||
| Motor Controls (Section 9-1.4) | MTRCT | ||
| Panelboards (Section 9-1.5) | PNLB | ||
| Electric Motors (Section 9-1.7) | ELEMT | ||
| Electronic Equipment (9-1.9) | ELTREQ | ||
| Card and Key Locks (Section 9-3) | CKLK | ||
| Electrical/Protection | Power Grounding Systems (Section 9-1.6.1) | PWRGS | |
| Static Grounding Systems (Section 9-1.6.2) | STGS | ||
| Cathodic Protection (Section 9-2.1) | CP | ||
| Lightning Surge Arresters (Section 9-2.2.1) | LSAR | ||
| Lightning Protection Systems (Section 9-4) | LPTS | ||
| Ground Verification System (Section 9-5) | GRVS | ||
| Electronic Overfill Protection Systems (Section 9-6) | EOPS | ||
| Eyewash/Shower | Emergency Eyewash/Showers (Section 11-3) | EMEWSH | |
| Fencing/ | |||
| Gates | Fencing | FENC | |
| Gates | GATE | ||
| Filtration | Pre-Filters (Section 3-6.1) | PFVSL | |
| Filter Separators (Section 3-6.2) | FLSP | ||
| Haypack Filters (Section 3-6.3) | HPKF | ||
| Basket Strainers (Section 3-6.4) | BSTR | ||
| Filter Separator Sump Heaters (Section 3-6.5) | FSSH | ||
| Sidestream Filtration Systems (Section 8-9.11) | SSFTS | ||
| Fire Suppression Equipment | Flame Arrestors (Section 8-9.5) | FLMARR | |
| Foam Fire Protection Systems (Section 8-9.15) | FFPS | ||
| Fire Protection Systems - Wet Pipe | FPRS | ||
| Fuel Laboratories | Ventilation Hoods (Section 11-4.1) | VENTHD | |
| Gauges | Pressure and Pressure/Vacuum Gauges (Section 6-7.1) | PVGA | |
| Differential Pressure Gauges (Section 6-7.2) | DPGA | ||
| Mechanical Tape Gauges (Section 8-9.7) | MTGA | ||
| Mechanically Operated Tape Gauge (Section 8-9.8.1) | MOTGA | ||
| Magnetostrictive Probes (Section 8-9.8.2) | MRPRB | ||
| Servo Gauge (Section 8-9.8.3) | SRVGA | ||
| Generators | Back-Up Power Generators | BGEN | |
| Heating Coils | Steam Type Heating Coils (Section 8-9.16.1) | STHC | |
| Thermal Fluid Type Heating Coils (Section 8-9.16.2) | TFTHC | ||
| Electric Rod Type Heating (Section 8-9.16.3) | ERTH | ||
| Hoses | Loading Fuel Hoses (Section 3-9.1) | LDHS | |
| Offloading Fuel Hoses (Section 3-9.2) | OLHS | ||
| Aircraft Fueling Hoses (Section 4-7.5) | ACFHS | ||
| Hydrazine | Hydrazine Charging Units (Section 10-3) | HDZCU | |
| Inspections | Trouble Shoot | TRBST | |
| API 510 Inspections | API510 | ||
| API 653 or STI Inspection | API653 | ||
| Coatings Condition Survey | CCS | ||
| Issue/Receive - Ground | Dispenser Nozzles (Section 7-2) | DSNZ | |
| Dispenser Hoses (Section 7-3) | DSHS | ||
| Breakaways (Section 7-4) | DSBW | ||
| Swivels (Section 7-5) | DSSW | ||
| Hose Retriever (Section 7-6) | HSRTV | ||
| Dispenser Cabinet (Section 7-7) | DSCB | ||
| Dispenser Meters (Section 7-8) | DSMTR | ||
| Dispenser Filters (Section 7-9) | DSFLR | ||
| Dispenser Strainers (Section 7-10) | DSSTR | ||
| Ground Vehicle Fuel Piping (Section 7-11) | GVFP | ||
| Emergency Shutoff Valves (Shear Valves) (Section 7-12) | ESHVL | ||
| Dispenser Sumps (Section 7-13) | DSSMP | ||
| Transition Sumps (Section 7-14) | TRSMP | ||
| Remote Dispenser Pumps (Section 7-15.1) | RDSP | ||
| Self-Contained Dispenser Pumps (Section 7-15.2) | SCDSP | ||
| EFSO Systems (Section 7-16) | EFSO | ||
| Stage I Vapor Recovery (Section 7-17.1) | SIVP | ||
| Stage II Vapor Recovery (Section 7-17.2) | SIIVP | ||
| Vapor Burners (Section 7-17.3) | VPBNR | ||
| Point Sensor - Dry (Section 7-19.1.1) | PSDRY | ||
| Automatic Line Leak Detector (Section 7-19.1.2) | ALLD | ||
| Visual Monitoring (Section 7-20.1) | VSLM | ||
| Issue/Receive - Marine | Marine Receipt (Section 5-2) | MRNRCP | |
| Marine Issue (Section 5-3) | MRNISU | ||
| Marine Loading Arms (Section 5-4) | MRNLA | ||
| Marine Transfer Hoses (Section 5-5.1) | MBTHS | ||
| Underwater Hoses (Section 5-5.2) | UWHS | ||
| Single Point Mooring Systems (Section 5-7.1) | SPMSS | ||
| Multi Point Mooring Systems (Section 5-7.2) | MPMSS | ||
| Submerged Piping Systems (Section 5-8) | SMPS | ||
| Boom Reels (Section 5-9) | BMRL | ||
| Liquefied Petroleum | Liquefied Petroleum Tanks (Section 10-1.1) | LPTANK | |
| Liquefied Petroleum Pipelines (Section 10-1.2) | LPPIPE | ||
| Liquefied Petroleum Vapor Lines (Section 10-1.3) | LPVPL | ||
| LPG Vaporizers (Section 10-1.4) | LPGVPZ | ||
| Petroleum Gas Regulators (Section 10-1.5) | PGREG | ||
| Liquefied Petroleum Gas Hoses (Section 10-1.6) | LPGHS | ||
| Meter/ | |||
| calibrations | Positive Displacement Meters (Section 3-7.1) | PDMT | |
| Turbine Flow Meters (Section 3-7.2) | TBFMT | ||
| Orifice Flow Meters (Section 3-7.3) | OFMT | ||
| Natural Disaster | Natural Disaster | ||
| Natural Gas | CNG Piping (Section 10-2.1) | NGPIPE | |
| CNG Compressors (Section 10-2.2) | NGCOMP | ||
| CNG Storage (Section 10-2.3) | NGSTOR | ||
| CNG Dispensers (Section 10-2.4) | NGDS | ||
| CNG Dispenser Hoses (Section 10-2.5) | NGDSHS | ||
| Nozzle | Hydrant Adapters (Section 4-7.2) | HADP | |
| Fueling Nozzles (Section 4-7.3) | FLNZ | ||
| Other | Fuel Additive Injectors (Section 3-11) | FAIJ | |
| Pantograph | Fixed Pantographs (Section 4-7.1.1) | FXPNT | |
| Detachable Pantographs (Section 4-7.1.2) | DTPNT | ||
| Piping | On-Base Pipelines (Section 6-1.1) | OBPL | |
| Non-DOT Regulated (Section 6-1.2.1) | NDPL | ||
| Aboveground Piping (Section 6-1.3) | AGPL | ||
| Double-Wall Piping (Section 6-1.4) | DWPL | ||
| Low Point Drains (Section 6-12.1) | LPDN | ||
| High Point Vents (Section 6-12.2) | HPVT | ||
| Sight Flow Indicators (Section 6-12.3) | SFND | ||
| Rope Sensor Systems (Section 6-13.1.1) | RPSS | ||
| Point Sensor - Dry (Section 6-13.1.2) | PSDRY | ||
| Visual Monitoring (Section 6-14.1) | VSLM | ||
| Pipe Penetrations (Section 8-10.6) | PPEN | ||
| Deactivated Petroleum Fuel Pipelines (Section 12-3) | DEACPL | ||
| Pressure/Temperature Control | Air Eliminator Tanks (Section 3-10.1) | AELT | |
| Automatic Air Vents (Section 3-10.2) | AAVT | ||
| Surge Suppressors (Section 4-7.4) | SRGSP | ||
| Thermal and Pressure Relief Valves (Section 6-6.3) | TPRVL | ||
| Pressure Transmitters (Section 6-7.3) | PRTR | ||
| Differential Pressure Transmitters (Section 6-7.4) | DPTR | ||
| Flexible Ball Joints (Section 6-8) | FBLJT | ||
| Dial Thermometer (Section 6-9.1) | DTHMR | ||
| Emergency Vents (Section 8-9.4) | EMGVT | ||
| Pump | Centrifugal Pumps (Section 3-8.1) | CENP | |
| Vertical Inline Pumps (Section 3-8.2) | VILP | ||
| Vertical Turbine/Submerged Turbine Pumps (Section 3-8.3) | VTSP | ||
| Sliding Vane Pumps (Section 3-8.5) | SLVP | ||
| Gear Pumps (Section 3-8.6) | GERP | ||
| Diaphragm Pumps (Section 3-8.7) | DIAP | ||
| Internal Combustion Drives (Section 3-8.8) | ICDR | ||
| Gearboxes (Section 3-8.9) | GRBX | ||
| Deactivated Petroleum Fuel Pumps (Section 12-4) | DEACP | ||
| Signage/Markings | Signage and Markings (Section 2-7) | SIGN | |
| Structures | Pumphouse/Filter Buildings (Section 11-2.1) | PFBLDG | |
| Canopies (Section 11-2.2) | CNPY | ||
| Cranes and Hoists (Section 11-6) | CRNHST | ||
| Tank | Aboveground Field-Erected Tanks (Section 8-4) | AGFET | |
| Geodesic Dome Roofs (Section 8-4.2) | GEODR | ||
| Foundations (Section 8-4.3) | FOUND | ||
| Aboveground Shop Fabricated Tanks (Section 8-5.1) | AGSFP | ||
| Self-Diking or Vaulted Tanks (Section 8-5.2) | SDVT | ||
| Rectangular Concrete-Encased Tanks (Section 8-5.3) | RCET | ||
| Single-Walled Underground Shop-Fabricated Tanks (Section 8-5.4.1) | UGSSFT | ||
| Double-Walled Underground Shop-Fabricated Tanks (Section 8-5.4.2) | UGDSFT | ||
| Underground Field-Constructed Tanks (Cut and Cover Tanks) (Section 8-6) | UGFET | ||
| Tank Cleaning (Section 8-7) | TCLEAN | ||
| Aluminum Honeycomb Floating Pans (Section 8-9.1.1) | AHFP | ||
| Steel Floating Pans (Section 8-9.1.2) | STLFP | ||
| Pontoon Floating Pans (Section 8-9.1.3) | PTNFP | ||
| Floating Roofs (Section 8-9.1.4) | FLTRF | ||
| Floating Roof and Pan Pressure/Vacuum Vents (Section 8-9.1.5) | FPPVV | ||
| Floating Roof and Pan Legs (Section 8-9.1.6) | FRPLG | ||
| Secondary Tank Bottoms (Section 8-9.2) | SNDTB | ||
| Tank Pressure/Vacuum Vents (Section 8-9.3) | TPVVT | ||
| Product Saver Tanks (Section 8-9.10) | PRDST | ||
| Fill Ports (Section 8-9.12) | FPRT | ||
| Point Sensor - Dry (Section 8-9.13.1) | PSDRY | ||
| Point Sensor - Wet (Section 8-9.13.2) | PSWET | ||
| Point Sensor - Pressure/Vacuum (Section 8-9.13.3) | PSPV | ||
| Visual Leak Detection (Section 8-9.13.4) | VSLLD | ||
| Floating Suction Lines (Section 8-9.14) | FLTSL | ||
| Stilling Wells (Section 8-9.17) | STGW | ||
| Deactivated Petroleum Fuel Tanks (Section 12-2) | DEACT | ||
| Testing | Pressure Testing | ||
| Underground Pits | Isolation Valve Pits (Section 6-11.1) | ISVLP | |
| Hydrant Fuel Pits (Section 6-11.2) | HDFP | ||
| High Point Vent Pits (Section 6-11.3) | HPVP | ||
| Low Point Drain Pits (Section 6-11.4) | LPDP | ||
| Lateral Control Pits (Section 6-11.5) | LTCP | ||
| Valves | General System Control Valves (Section 4-3.2.1) | GSCVL | |
| Refuel Control Valves (Section 4-3.2.5) | RCVL | ||
| Pressure Relief Valves (Section 4-3.2.6) | PRCVL | ||
| Defuel Control Valve (Section 4-3.2.7) | DFCVL | ||
| Dual Rate-of-Flow Control Valves (Section 4-3.2.8) | DRFCVL | ||
| Combination Dual Rate-of-Flow Control and Solenoid Valves (Section 4-3.3.1) | CFSCVL | ||
| Dual Pressure Relief, Solenoid Shutoff, and Check Valves (Section 4-3.3.2) | DPSCVL | ||
| Non-Surge Check Valves (Section 4-4.2.1) | NSCKVL | ||
| Filter Separator Control Valves (Section 4-4.2.2) | FSCVL | ||
| Defuel/Flush Valves (Section 4-4.2.3) | DFFCVL | ||
| Issue Venturi (Section 4-4.2.4) | ISVTR | ||
| Return Venturi (Section 4-4.2.5) | RTVTR | ||
| Back Pressure Control Valves (Section 4-4.2.6) | BPCVL | ||
| Pressure Control Valves (Section 4-4.2.7) | PCVL | ||
| Hydrant Control Valves (Section 4-4.2.8) | HCVL | ||
| Emergency Shut-off Valves (Section 4-4.2.9) | ESOVL | ||
| Pantograph Control Valves (Section 4-5.2.12) | PTCVL | ||
| Pantograph Pressure Control Valves (Section 4-5.2.13) | PTPCVL | ||
| Overfill Valve for Product Recovery Tanks (Section 4-8.1) | OVLPRT | ||
| Plug Valves - Lubricated (Section 6-6.2.1) | PLVL | ||
| Plug Valves - Non-lubricated (Section 6-6.2.2) | NPLVL | ||
| Gate Valves (Section 6-6.2.3) | GTVL | ||
| Ball Valves (Section 6-6.2.4) | BLVL | ||
| Double Block and Bleed Valves (Section 6-6.2.5) | DBBVL | ||
| Butterfly Valves (Section 6-6.2.6) | BFVL | ||
| Globe Valves (Section 6-6.2.7) | GLVL | ||
| Check Valves (Section 6-6.2.8) | CKVL | ||
| Line Blanks, Ring Spacers, and Spectacle Blinds (Section 6-6.2.9) | BLIND | ||
| Manual Valve Gear Operators (Section 6-6.2.10) | MVLGO | ||
| Fire Valves (Section 6-6.4.1) | FRVL | ||
| Fusible Link Butterfly Valves (Section 6-6.4.2) | FLBFVL | ||
| Truck Fill Valves (Section 6-6.5.1) | TFVL | ||
| Motor Operators (Section 6-6.6) | MTROP | ||
| External High Level Shutoff Valves (HLSO) (Section 8-9.6.1) | EHLSVL | ||
| Internal HLSO Valves (Section 8-9.6.2) | IHLSVL | ||
| Waste | Oil/Water Separators (Section 11-5) | OWS |
Pacific Ocean Division, POD-AF
| W912DY-21-F-0076 | &"-,Bold"&16Yongsan Garrison |
| YSG | Facility Maintenance Plan |
&A &P of &N APTIM Federal Services, LLC
Versions and Notes
| Version | Date | Description of changes |
| v2.0 | 8/18/21 | Updated Task Matrix to meet UFC 3-460-03 Change 1 , 29 April 2021 |
| Updated Component Acronym Tab to meet UFC 3-460-03 Change 1 , 29 April 2021 | ||
| v2.1 | 4/20/22 | Task Matrix Tab - Deleted all services facility # columns and combined into one. Renamed "Real Property Facility #" |
| Task Matrix Tab - Added "RPUID" to Real Property Unique Identifier column | ||
| Task Matrix Tab - Added "Real Property" to Facility Name | ||
| Task Matrix Tab - Added column for "Base Asset ID" | ||
| Task Matrix Tab - Added "Additional" and "RM" to Manufacturer Requirements | ||
| Task Matrix Tab - Changed Comment note for Filter Separator | ||
| Task Matrix Tab - Changed Note #3 To add "Base Asset ID if used by site shall be cross referenced with CUID appropriately." | ||
| Task Matrix Tab - Changed note #7 under instructions for Task Matrix to clarify this column | ||
| Task Matrix Tab - Changed note #8 under instructions for Task Matrix to clarify this column | ||
| Added new tab for RM schedule to be included | ||
| Added new Tab for Filter Separator/Pre-Filter Schedule with instructions | ||
| Administrative Tab - changed Installation to Site and added Site Code to comply with new requirements as the three letter DLA site code is obsolete | ||
| General Facility Description - Changed the Instructions | ||
| Reversed columns 'Base Asset ID' and 'CUID' to match RM report for all tabs | ||
| Added FMP version to footer | ||
| v2.2 | 10/10/24 | Administrative Tab- Changed USACE PE name and contact information to reflect current changes |
| Administrative Tab- Changed USACE KO name and contact information to reflect current changes |
File details come from the government source that posted it. Updated .