FMP POF CSY_20251029.xlsx

XLSX spreadsheet 132 KB Posted

Attached to
DRAFT Solicitation CEHNC Fuels Pacific Ocean Division - Far East (POF)
Solicitation number
DRAFTW912DY26RA005
Issued by

About this file

This Excel file is a Facility Maintenance Plan (FMP) for Camp Casey, a Defense Logistics Agency (DLA) fuel facility located in Dongducheon, Korea, under contract number W912DY-21-F-0076 with APTIM Federal Services, LLC. The comprehensive document details maintenance requirements for multiple fuel storage and transfer facilities, including two 10,000-gallon JP-8 storage tanks, a bulk terminal with rail and truck receipt capabilities, gas station infrastructure with diesel and gasoline storage, and various operational areas with specific equipment like filter separators, pumps, valves, and containment systems.

The maintenance plan provides an exhaustive asset inventory with unique component identifiers, manufacturer details, maintenance frequencies, and specific UFC (Unified Facilities Criteria) section references for each piece of equipment. Key facilities include a fuel pump house (CSY-1565), tank car load/unload facility (CSY-1577), truck fill stand (CSY-1566), and multiple vehicle fueling stations. The document outlines maintenance schedules, special considerations, and operational requirements for filter separators, pre-filter vessels, and other critical fuel handling infrastructure, with maintenance intervals ranging from quarterly to annual inspections and component replacements.

View the file

Other files

File Type Posted
CDRL Set 17 - 65-67.pdf PDF
CDRL Set 3 - 9-12.pdf PDF
CDRL Set 13 - 49-52.pdf PDF
Attachment 4 - PPQ Sample.pdf PDF
FMP POF OSN_20251029.xlsx XLSX spreadsheet
FMP POF SUW_20251029.xlsx XLSX spreadsheet
FMP POF KUS_20251029.xlsx XLSX spreadsheet
Attachment 2 Sample Service Order (Appendix A - Attachment 1 Service Order Form).xlsx XLSX spreadsheet
CDRL Set 6 - 21-24.pdf PDF
CDRL Set 8 - 29-32.pdf PDF
CDRL Set 5 - 17-20.pdf PDF
CDRL Set 1 - 1-4.pdf PDF
CDRL Set 9 - 33-36.pdf PDF
Appendix K Real Property Data.xlsx XLSX spreadsheet
Attachment 3 Technical Eval Form - V1.pdf PDF
FMP POF YCH_20251029.xlsx XLSX spreadsheet
FMP POF TAE_20251029.xlsx XLSX spreadsheet
FMP POF YSG_20251029.xlsx XLSX spreadsheet
FMP POF CRL_20251029.xlsx XLSX spreadsheet
Attachment 1 PWS amd Appendices POF - V1.pdf PDF
CDRL Set 10 - 37-40.pdf PDF
CDRL Set 16 - 60-64.pdf PDF
CDRL Set 15 - 57-60.pdf PDF
CDRL Set 4 - 13-16..pdf PDF
CDRL Set 2 - 5-8.pdf PDF
CDRL Set 14 - 53-56.pdf PDF
FMP POF KJU_20251029.xlsx XLSX spreadsheet
FMP POF POH_20251029.xlsx XLSX spreadsheet
Attachment 0005 Instructions and Evaluation Factors DRAFT.docx DOCX document
FMP POF WAL_20251029.xlsx XLSX spreadsheet
CDRL Set 7 - 25-28.pdf PDF
CDRL Set 12 - 45-48.pdf PDF
CDRL Set 11 - 41-44.pdf PDF
FMP POF KUN_20251029.xlsx XLSX spreadsheet
FMP POF HUM_20251029.xlsx XLSX spreadsheet
FMP POF KIM_20251029.xlsx XLSX spreadsheet
FMP POF K-16_20251029.xlsx XLSX spreadsheet
Show all 37

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Administrative

ADMINISTRATIVE
LocationInstallation NameCamp Casey
DLA Site CodeCSY
RPSUID4239
Hours of Operation0800-1630
AddressDongducheon, Korea
ContractContractor
Contract #
Local POCsPrimary QAE
QAE Phone
QAE Email
Alternate QAE
Alt QAE Phone
Alt QAE Email
Contractor POCsContractor PM
Contractor PM Phone
Contractor PM Email
Contractor QC Manager
Contractor QC Phone
Contractor QC Email
Contractor SM
Contractor SM Phone
Contractor SM Email
USACE POCsUSACE PM/COR
USACE PM/COR Phone
USACE PM/COR Email
USACE PE
USACE PE Phone
USACE PE Email
USACE KO
USACE KO Phone
USACE KO Email
USACE Monthly Report Inbox

Pacific Ocean Division, POD-AF

W912DY-21-F-0076&"-,Bold"&16Camp Casey
CSYFacility Maintenance Plan

OY3 Q1

&A &P of &N APTIM Federal Services, LLC

Instructions:

This table shows the minimum information required. Additional details should be included based on site specific requirements. Additional POCs may be required.

General Facility Description

General Facility Description
Installation NameCamp Casey
DLA Site CodeCSY
LocationDongducheon, Korea
Bulk Terminal: rail header w/ receipt for 5 rail cars, truck receipt for 2 trucks, truck issue w/ 2 top-load racks and 4 bottom load pantographs, (2) 10,000-gallon BBL JP-8 storage tanks (1562, 1563), 3 receipt pumps, office building, pump house, filter separators, ATG system.

Gas Station: (2) 3,200-gallon diesel USTs in vaults, (1) 5,000-gallon Mogas AST, 3 dispensers for diesel (2 nozzles each), 2 Mogas dispensers (2 nozzles each).

Ahntech Corporation operates the system and performs routine maintenance, daily, weekly, quarterly and annually.

Pacific Ocean Division, POD-AF

W912DY-21-F-0076&"-,Bold"&16CAMP CASEY
CSYFacility Maintenance Plan

OY3 Q1

&A &P of &N APTIM Federal Services, LLC

Instructions:

Include a general facility overview and description of each fuel system for the sites in accordance with UFC 3-460-01. Examples include: Bulk Storage Facilities, Aircraft Fueling Facilities, Marine and Dispensing Facilities, Ground Products Fueling Facilities, Alternate POL Facilities, and Support Facilities. Also include facility #s, facility names, fuel type, photos, and any other pertinent information.

Include Site Specific Conditions and Restrictions in this tab.

Figure 2

Site Location Drawings
Figure 2 - POL Facilities

Map of each operational area - and perhase each facility # or groups of facility #s in close vacinity

Pacific Ocean Division, POD-AF

W912DY-21-F-0076&"-,Bold"&16Camp Casey
CSYFacility Maintenance Plan

Revision 1

&A &P of &N APTIM Federal Services, LLC

Figure 3

Site Location Drawings
Figure 3 - Fow Diagram

Flow diagraphs for each "area"....operational area or facility # or group of facilities.

W912DY-21-F-0076&"-,Bold"&16Camp Casey
CSYFacility Maintenance Plan

Revision 1

&A &P of &N APTIM Federal Services, LLC

Communication Plan

W912DY-21-F-0076&"-,Bold"&16Camp Casey
CSYFacility Maintenance Plan

OY3 Q1

&A &P of &N APTIM Federal Services, LLC

Instructions:

Communication plan shall address in/out briefs, lines of communication, coordination for access, etc.

Site Specific Safety Plan

Pacific Ocean Division, POD-AF

W912DY-21-F-0076&"-,Bold"&16&K000000Camp Casey
CSYFacility Maintenance Plan

OY3 Q1

&A &P of &N APTIM Federal Services, LLC

Instructions:

Site Specific Addendum and Activity Hazard Analysis, which are Attachments to the APP, specific to activities or tasks related to recurring maintenance for this site.

PM Schedule

Pacific Ocean Division, POD-AF

W912DY-21-F-0076&"-,Bold"&16&K000000Camp Casey
CSYFacility Maintenance Plan

OY3 Q1

&A &P of &N APTIM Federal Services, LLC

Instructions:

Link PM schedule here

Task Matrix

Applicable Facility AssetsUFC System Level Maintenance FrequencySpecial Considerations
RPUIDReal Property Facility #Facility NameOperational AreaComponent TypeBase Asset NameComponent Unique ID CUIDAPTIM Asset IDAsset DescriptionMakeModelCapacity / SizeQuarterlySemi AnnualAnnualUFC Section ReferenceAdditional Manufacturer RM RequirementsOperator/Equipment RequirementsSystem AvailabilityOther ContractComments
250223CSY-15621562-FUEL TANK #1BULK STORAGEMV-Double Block and Bleed Valves28CSY-1562-DBBVL-16341016071CSYLocated on the 8 inch receipt line before the control valveGeneral ValveXXXSection 6-6.2.5Notify Facility
250223CSY-15621562-FUEL TANK #1BULK STORAGEMV-Double Block and Bleed ValvesCSY-1562-DBBVL-16341116072CSYLocated on the 8 inch receipt line after the control valve (skin valve)GHATGE PATILOmniSeal DBB Expanding Plug ValveXXXSection 6-6.2.5Notify Facility
250223CSY-15621562-FUEL TANK #1BULK STORAGEMV-Double Block and Bleed Valves32CSY-1562-DBBVL-16341216073CSYLocated on the 16 inch Issue line from the tank (skin valve). (Valve 32)General ValveXXXSection 6-6.2.5Notify Facility
250223CSY-15621562-FUEL TANK #1BULK STORAGEMV-Double Block and Bleed Valves33CSY-1562-DBBVL-16341316074CSYLocated on the bypass line for the 16 inch issue DBB valve from the tank. (Valve 33)General ValveXXXSection 6-6.2.5Notify Facility
250224CSY-15631563-FUEL TANK #2 WALL LABEL S1563BULK STORAGEMV-Double Block and Bleed Valves30CSY-1563-DBBVL-16341416075CSYLocated on the 8 inch receipt line before the control valveGeneral ValveXXXSection 6-6.2.5Notify FacilityWCG 1810804CC
250224CSY-15631563-FUEL TANK #2 WALL LABEL S1563BULK STORAGEMV-Double Block and Bleed Valves29CSY-1563-DBBVL-16341516076CSYLocated on the 8 inch receipt line after the control valve (skin valve)GHATGE PATILOmniSeal DBB Expanding Plug ValveXXXSection 6-6.2.5Notify Facility
250224CSY-15631563-FUEL TANK #2 WALL LABEL S1563BULK STORAGEMV-Double Block and Bleed Valves34CSY-1563-DBBVL-16341616077CSYLocated on the 16 inch issue line from the tank (skin valve). (Valve 34)General ValveC811XXXSection 6-6.2.5Notify Facility
250224CSY-15631563-FUEL TANK #2 WALL LABEL S1563BULK STORAGEMV-Double Block and Bleed Valves35CSY-1563-DBBVL-16341716078CSYLocated on the bypass line for the 16 inch DBB issue valve from the tankGeneral ValveXXXSection 6-6.2.5Notify Facility
250223CSY-15621562-FUEL TANK #1BULK STORAGELA-Externally Mounted Level AlarmsCSY-1562-EMLA-169952CSY00140High Level located near tank roof top accessible by tank stairsXXSection 8-9.9.1Coordinate with Facility
250223CSY-15621562-FUEL TANK #1BULK STORAGELA-Externally Mounted Level AlarmsCSY-1562-EMLA-169953CSY00141High-High Level located near tank roof top accessible by tank stairsXXSection 8-9.9.1Coordinate with Facility
250223CSY-15621562-FUEL TANK #1BULK STORAGEMV-Ball ValvesCSY-1562-BLVL-169954CSY00142Located on the 1in line from the tank to the PRT (center)VelanCF8MXSection 6-6.2.4Notify Facility
250223CSY-15621562-FUEL TANK #1BULK STORAGEMV-Ball ValvesCSY-1562-BLVL-169868CSY00143Located on the 1inch line from tank to PRT (tank side)Flow-TekSeries F15XSection 6-6.2.4Notify Facility
250223CSY-15621562-FUEL TANK #1BULK STORAGEMV-Ball ValvesCSY-1562-BLVL-169870CSY00144Located on the 1in line from the tank to the PRT (PRT side)Flow-TekSeries F15XSection 6-6.2.4Notify Facility
250223CSY-15621562-FUEL TANK #1BULK STORAGEMV-Ball ValvesB-43CSY-1562-BLVL-176263CSY00145Located on the PRT Drain. (Valve B-43)HwaSung Co., Ltd.F304XSection 6-6.2.4Notify Facility
250223CSY-15621562-FUEL TANK #1BULK STORAGEMV-Ball ValvesCSY-1562-BLVL-169834CSY00146Located on the PRT drain line downstream of the sight flow indicatorFlow-TekCF8MXSection 6-6.2.4Notify Facility
250223CSY-15621562-FUEL TANK #1BULK STORAGEMV-Ball ValvesCSY-1562-BLVL-169871CSY00147Located on the PRT drain line near the PRT pumpFlow-TekSeries F15XSection 6-6.2.4Notify Facility
250223CSY-15621562-FUEL TANK #1BULK STORAGEMV-Ball ValvesCSY-1562-BLVL-169955CSY00148Located on the Low Level Alarm (upper valve)Flow-TekSeries F15XSection 6-6.2.4Notify Facility
250223CSY-15621562-FUEL TANK #1BULK STORAGEMV-Ball ValvesCSY-1562-BLVL-169956CSY00149Located on the Low Level Alarm (lower valve)Flow-TekSeries F15XSection 6-6.2.4Notify Facility
250223CSY-15621562-FUEL TANK #1BULK STORAGEMV-Ball ValvesCSY-1562-BLVL-176264CSY00150Located on the Low Level Alarm (drain valve)Flow-TekSeries F15XSection 6-6.2.4Notify Facility
250223CSY-15621562-FUEL TANK #1BULK STORAGEMV-Ball ValvesCSY-1562-BLVL-176265CSY00151Located on the High Level Alarm (upper valve)Flow-TekSeries F15XSection 6-6.2.4Notify Facility
250223CSY-15621562-FUEL TANK #1BULK STORAGEMV-Ball ValvesCSY-1562-BLVL-176266CSY00152Located on the High Level Alarm (lower valve)Flow-TekSeries F15XSection 6-6.2.4Notify Facility
250223CSY-15621562-FUEL TANK #1BULK STORAGEMV-Ball ValvesCSY-1562-BLVL-169835CSY00153Located on the High Level Alarm (drain valve)Flow-TekSeries F15XSection 6-6.2.4Notify Facility
250223CSY-15621562-FUEL TANK #1BULK STORAGEMV-Ball ValvesCSY-1562-BLVL-169836CSY00154Located on the Hi-Hi Level Alarm (upper valve)Flow-TekSeries F15XSection 6-6.2.4Notify Facility
250223CSY-15621562-FUEL TANK #1BULK STORAGEMV-Ball ValvesCSY-1562-BLVL-169957CSY00155Located on the Hi-Hi Level Alarm (lower valve)Flow-TekSeries F15XSection 6-6.2.4Notify Facility
250223CSY-15621562-FUEL TANK #1BULK STORAGEMV-Ball ValvesCSY-1562-BLVL-169872CSY00156Located on the Hi-Hi Level Alarm (drain valve)Flow-TekSeries F15XSection 6-6.2.4Notify Facility
250223CSY-15621562-FUEL TANK #1BULK STORAGEMV-Ball ValvesCSY-1562-BLVL-169837CSY00157Located on the PRT sight glass drainBAZERXSection 6-6.2.4Notify Facility
250223CSY-15621562-FUEL TANK #1BULK STORAGETA-External High Level Shutoff Valves (HLSO)CSY-1562-GSCVL-153049CSY00158Located on the 8 inch receipt line at the tank (HLSO control valve)Cla-ValXXSection 8-9.6.1Operate System to Test
250223CSY-15621562-FUEL TANK #1BULK STORAGEPC-Aboveground Piping and Equipment CoatingCSY-1562-AGPCT-169838CSY00164Exposed Piping: 16 inch issue pipingSection 6-10.1
250223CSY-15621562-FUEL TANK #1BULK STORAGEPC-Aboveground Piping and Equipment CoatingCSY-1562-AGPCT-169958CSY00165Exposed Piping: 8 inch receipt pipingSection 6-10.1
250223CSY-15621562-FUEL TANK #1BULK STORAGEPC-Aboveground Piping and Equipment CoatingCSY-1562-AGPCT-169873CSY00166Exposed Piping: 1inch product recovery pipingSection 6-10.1
250223CSY-15621562-FUEL TANK #1BULK STORAGETK-Aboveground Field-Erected TanksCSY-1562-AGFET-176267CSY00168Product Storage Tank (JP-8 Tank 1)XXSection 8-4
250223CSY-15621562-FUEL TANK #1BULK STORAGEPS-Product Saver TanksCSY-1562-PRDST-176268CSY00169Product recovery tank for tank #1. (Facility 1562)HAN SUNG VALVETYPE 1XSection 8-9.10Notify Facility
250223CSY-15621562-FUEL TANK #1BULK STORAGETA-Mechanical Tape Gauges (non-ATG)CSY-1562-MTGA-169874CSY00170Mechanical tape gauge for Tank #1 (Fac.1562) located near the tank stair entrance.Shand & Jurs92021-31450100 20481005XSection 8-9.7Notify Facility2 wire transmitter Model: 31440-EL117001 S/N: 03050002
250223CSY-15621562-FUEL TANK #1BULK STORAGELA-Externally Mounted Level AlarmsCSY-1562-EMLA-169875CSY00171Low Level Alarms located near the tank stair entranceXXSection 8-9.9.1Coordinate with Facility
250223CSY-15621562-FUEL TANK #1BULK STORAGEMV-Ball ValvesCSY-1562-BLVL-169876CSY00172Located on the bottom perimeter of the tank (telltale) PRT sideXSection 6-6.2.4Notify Facility
250223CSY-15621562-FUEL TANK #1BULK STORAGEMV-Ball ValvesCSY-1562-BLVL-176269CSY00173Located on the bottom perimeter of the tank (telltale)XSection 6-6.2.4Notify Facility
250223CSY-15621562-FUEL TANK #1BULK STORAGECS-Dike/Berm with Walls and FloorsCSY-1562-DKBW-167873CSY00174Containment/Dike for Tank # 1XSection 8-10.2 / 8-10.2.1
250224CSY-15631563-FUEL TANK #2 WALL LABEL S1563BULK STORAGELA-Externally Mounted Level AlarmsCSY-1563-EMLA-169840CSY00175High Level located near tank roof top accessible by tank stairsXXSection 8-9.9.1Coordinate with Facility
250224CSY-15631563-FUEL TANK #2 WALL LABEL S1563BULK STORAGELA-Externally Mounted Level AlarmsCSY-1563-EMLA-169959CSY00176High-High Level located near tank roof top accessible by tank stairsXXSection 8-9.9.1Coordinate with Facility
250224CSY-15631563-FUEL TANK #2 WALL LABEL S1563BULK STORAGEMV-Ball ValvesCSY-1563-BLVL-176270CSY00177Located on the 1 inch line from the tank to PRT (middle of the line)VelanCF8MXSection 6-6.2.4Notify Facility
250224CSY-15631563-FUEL TANK #2 WALL LABEL S1563BULK STORAGEMV-Ball ValvesB-32CSY-1563-BLVL-169877CSY00178Located on the 1in line from tank to PRT (tank side). (Valve B-32)Flow-TekSeries F15XSection 6-6.2.4Notify Facility
250224CSY-15631563-FUEL TANK #2 WALL LABEL S1563BULK STORAGEMV-Ball ValvesB-34CSY-1563-BLVL-169878CSY00179Located on the 1 inch line from the tank to the PRT (PRT side)Flow-TekSeries F15XSection 6-6.2.4Notify Facility
250224CSY-15631563-FUEL TANK #2 WALL LABEL S1563BULK STORAGEMV-Ball ValvesB-36CSY-1563-BLVL-176271CSY00180Located on the PRT DrainFlow-TekCF8MXSection 6-6.2.4Notify Facility
250224CSY-15631563-FUEL TANK #2 WALL LABEL S1563BULK STORAGEMV-Ball ValvesCSY-1563-BLVL-176272CSY00181Located on the PRT drain line downstream of the sight flow indicatorVelanSeries F15XSection 6-6.2.4Notify Facility
250224CSY-15631563-FUEL TANK #2 WALL LABEL S1563BULK STORAGEMV-Ball ValvesB-38CSY-1563-BLVL-176273CSY00182Located on the PRT drain line next to the PRT pump. (Valve B-38)Flow-TekCF8MXSection 6-6.2.4Notify Facility
250224CSY-15631563-FUEL TANK #2 WALL LABEL S1563BULK STORAGEMV-Ball ValvesCSY-1563-BLVL-169842CSY00183Located on the Low Level Alarm (upper valve)Flow-TekSeries F15XSection 6-6.2.4Notify Facility
250224CSY-15631563-FUEL TANK #2 WALL LABEL S1563BULK STORAGEMV-Ball ValvesCSY-1563-BLVL-169844CSY00184Located on the Low Level Alarm (lower valve)Flow-TekSeries F15XSection 6-6.2.4Notify Facility
250224CSY-15631563-FUEL TANK #2 WALL LABEL S1563BULK STORAGEMV-Ball ValvesCSY-1563-BLVL-169960CSY00185Located on the Low Level Alarm (drain valve)Flow-TekSeries F15XSection 6-6.2.4Notify Facility
250224CSY-15631563-FUEL TANK #2 WALL LABEL S1563BULK STORAGEMV-Ball ValvesCSY-1563-BLVL-169879CSY00186Located on the High Level Alarm (upper valve)Flow-TekSeries F15XSection 6-6.2.4Notify Facility
250224CSY-15631563-FUEL TANK #2 WALL LABEL S1563BULK STORAGEMV-Ball ValvesCSY-1563-BLVL-169845CSY00187Located on the High Level Alarm (drain valve)Flow-TekSeries F15XSection 6-6.2.4Notify Facility
250224CSY-15631563-FUEL TANK #2 WALL LABEL S1563BULK STORAGEMV-Ball ValvesCSY-1563-BLVL-176274CSY00188Located on the High Level Alarm (lower valve)Flow-TekSeries F15XSection 6-6.2.4Notify Facility
250224CSY-15631563-FUEL TANK #2 WALL LABEL S1563BULK STORAGEMV-Ball ValvesCSY-1563-BLVL-176275CSY00189Located on the Hi-Hi Level Alarm (upper valve)Flow-TekSeries F15XSection 6-6.2.4Notify Facility
250224CSY-15631563-FUEL TANK #2 WALL LABEL S1563BULK STORAGEMV-Ball ValvesCSY-1563-BLVL-169961CSY00190Located on the Hi-Hi Level Alarm (lower valve)Flow-TekSeries F15XSection 6-6.2.4Notify Facility
250224CSY-15631563-FUEL TANK #2 WALL LABEL S1563BULK STORAGEMV-Ball ValvesCSY-1563-BLVL-169979CSY00191Located on the Hi-Hi Level Alarm (drain valve)Flow-TekSeries F15XSection 6-6.2.4Notify Facility
250224CSY-15631563-FUEL TANK #2 WALL LABEL S1563BULK STORAGEMV-Ball ValvesCSY-1563-BLVL-169980CSY00192Located under the PRT sight glass drainBAZERXSection 6-6.2.4Notify Facility
250224CSY-15631563-FUEL TANK #2 WALL LABEL S1563BULK STORAGETA-External High Level Shutoff Valves (HLSO)CSY-1563-GSCVL-153050CSY00193Located on the 8 inch receipt line at the tank (HLSO control valve)Cla-ValXXSection 8-9.6.1Operate System to Test
250224CSY-15631563-FUEL TANK #2 WALL LABEL S1563BULK STORAGEPC-Aboveground Piping and Equipment CoatingCSY-1563-AGPCT-169939CSY00199Issue pipingSection 6-10.1
250224CSY-15631563-FUEL TANK #2 WALL LABEL S1563BULK STORAGEPC-Aboveground Piping and Equipment CoatingCSY-1563-AGPCT-169883CSY00200Receipt pipingSection 6-10.1
250224CSY-15631563-FUEL TANK #2 WALL LABEL S1563BULK STORAGEPC-Aboveground Piping and Equipment CoatingCSY-1563-AGPCT-169884CSY00201Product recovery pipingSection 6-10.1
250224CSY-15631563-FUEL TANK #2 WALL LABEL S1563BULK STORAGETK-Aboveground Field-Erected TanksCSY-1563-AGFET-176276CSY00203Product Storage Tank (JP-8 Tank 2)XXSection 8-4
250224CSY-15631563-FUEL TANK #2 WALL LABEL S1563BULK STORAGEPS-Product Saver TanksCSY-1563-PRDST-169880CSY00204Product recovery tank for tank #2. (Facility 1563)HAN SUNG VALVETYPE 1XSection 8-9.10Notify Facility
250224CSY-15631563-FUEL TANK #2 WALL LABEL S1563BULK STORAGETA-Mechanical Tape Gauges (non-ATG)CSY-1563-MTGA-169881CSY00205Mechanical tape gauge for Tank #2 (Fac. 1563) located near the tank stair entrance.Shand & Jurs92021-31450100 20481005XSection 8-9.7Notify Facility2 wire transmitter Model: 31440-EL117001 S/N: 03050001
250224CSY-15631563-FUEL TANK #2 WALL LABEL S1563BULK STORAGELA-Externally Mounted Level AlarmsCSY-1563-EMLA-169882CSY00206Low Level Alarms located near the tank stair entranceXXSection 8-9.9.1Coordinate with Facility
250224CSY-15631563-FUEL TANK #2 WALL LABEL S1563BULK STORAGEMV-Ball ValvesCSY-1563-BLVL-169885CSY00207Located on the bottom perimeter of the tank (telltale) - PRT sideFlow-TekTFM-1600XSection 6-6.2.4Notify FacilityReplaced per the RITM at BYQ4
250224CSY-15631563-FUEL TANK #2 WALL LABEL S1563BULK STORAGEMV-Ball ValvesCSY-1563-BLVL-169886CSY00208Located on the bottom perimeter of the tank (telltale) BMC office sideFlow-TekTFM-1600XSection 6-6.2.4Notify FacilityReplaced per RITM at BYQ4
250224CSY-15631563-FUEL TANK #2 WALL LABEL S1563BULK STORAGECS-Dike/Berm with Walls and FloorsCSY-1563-DKBW-167874CSY00209Containment/Dike for Tank # 2XSection 8-10.2 / 8-10.2.1
247830CSY-15641564-FUEL/POL BLDGBULK STORAGESF-Emergency Eyewash/ShowersCSY-1564-EMEWSH-169990CSY00282Located in front of facility S1564Haws CorporationXXXSection 11-3Notify Facility
PWS Appx K-3CSY-FOS-1589FOS-1589-FOS-GRAVITY OIL AND GREASE SEPARATORBULK STORAGESF-Oil/Water SeparatorsCSY-1578-OWS-170030CSY00570Located across from tank 1 S1562Containment Solutions, InPSC 6000 DWJXXSection 11-5Notify Facility
250224CSY-15631563-FUEL TANK #2 WALL LABEL S1563BULK STORAGEEC-EFSO-Elec EquipCSY-1563-EFSO-170061CSY00575Located behind tanks 1 and 2 next to the level alarm panel.XSection 9-1.2Operate System to Test
247830CSY-15641564-FUEL/POL BLDGBULK STORAGEEC-EFSO-Elec EquipCSY-1564-EFSO-176304CSY00576EFSO located next to the entrance door.XSection 9-1.2Operate System to Test
250224CSY-15631563-FUEL TANK #2 WALL LABEL S1563BULK STORAGETG-Servo GaugeCSY-1563-SRVGA-170062CSY1006211324ATG located on top of tank 2HoneywellXXXSection 8-9.8.3Another Contract
1344980CSY-15901590-POLLUTANT CATCH BASINBULK STORAGECS-Containment Drain ValvesCSY-1577-CSGEN-167775CSY2206101411Containment drain valve (PIV) located at the end of the truck and rail offloading areaKennedy2945AXSection 8-10.1Key Required
250223CSY-15621562-FUEL TANK #1BULK STORAGECS-Containment Drain ValvesCSY-1562-CSGEN-167776CSY2206101412Containment drain valve (PIV) located outside the containment for tank 1 facility S1562Kennedy2945AXSection 8-10.1Key Required
250224CSY-15631563-FUEL TANK #2 WALL LABEL S1563BULK STORAGECS-Containment Drain ValvesCSY-1563-CSGEN-167777CSY2206101413Containment drain valve (PIV) located outside the containment for tank 2 facility S1563Kennedy2945AXSection 8-10.1Key Required
250223CSY-15621562-FUEL TANK #1BULK STORAGETG-Servo GaugeCSY-1562-SRVGA-170029CSY2206171153ATG gauge located on top of tank 1HoneywellXXXSection 8-9.8.3Another Contract
250224CSY-15631563-FUEL TANK #2 WALL LABEL S1563BULK STORAGEEC-Lightning Protection SystemsCSY-1563-LPTS-176314CSY2206201005Lightning protection system located on top of tank 2XSection 9-4At Height-Manlift Required
250223CSY-15621562-FUEL TANK #1BULK STORAGEEC-Lightning Protection SystemsCSY-1562-LPTS-170031CSY2206201006Lightning protection system located on top of tank 1XSection 9-4At Height-Manlift Required
PWS Appx K-3CSY-1565XX1565XX-PUMP STA BLDG AGBULK STORAGE/ PUMPHOUSETV-Thermal and Pressure Relief ValvesCSY-1565-TPRVL-16496716019CSYPRV located next to ball valve (16047) on the inlet line for issue filter separator #41Taylor ValveT -8200-1XXSection 6-6.3Coordinate with FacilitySet pressure 225 psig
PWS Appx K-3CSY-1565XX1565XX-PUMP STA BLDG AGBULK STORAGE/ PUMPHOUSETV-Thermal and Pressure Relief ValvesCSY-1565-TPRVL-16496816020CSYLocated on top of issue filter separator #41Taylor ValveT -8200-1XXSection 6-6.3Coordinate with FacilitySet pressure 225 psig
PWS Appx K-3CSY-1565XX1565XX-PUMP STA BLDG AGBULK STORAGE/ PUMPHOUSETV-Thermal and Pressure Relief ValvesCSY-1565-TPRVL-16496916021CSYLocated on top of issue filter separator #45Taylor ValveT -8200-1XXSection 6-6.3Coordinate with FacilitySet pressure 225 psig
PWS Appx K-3CSY-1565XX1565XX-PUMP STA BLDG AGBULK STORAGE/ PUMPHOUSETV-Thermal and Pressure Relief ValvesCSY-1565-TPRVL-16497016022CSYPRV located next to ball valve 50 (16045) on the inlet line for issue filter separator #45Taylor ValveT -8200-1XXSection 6-6.3Coordinate with FacilitySet pressure 225 psig
PWS Appx K-3CSY-1565XX1565XX-PUMP STA BLDG AGBULK STORAGE/ PUMPHOUSETV-Thermal and Pressure Relief ValvesCSY-1565-TPRVL-16497116023CSYLocated on top of receipt filter separator #46Taylor ValveT -8200-1XXSection 6-6.3Coordinate with FacilitySet pressure 225 psig
PWS Appx K-3CSY-1565XX1565XX-PUMP STA BLDG AGBULK STORAGE/ PUMPHOUSETV-Thermal and Pressure Relief ValvesCSY-1565-TPRVL-16497216024CSYPRV located next to ball valve (16043) on the inlet line for receipt filter separator #46Taylor ValveT -8200-1XXSection 6-6.3Coordinate with FacilitySet pressure 225 psig
PWS Appx K-3CSY-1565XX1565XX-PUMP STA BLDG AGBULK STORAGE/ PUMPHOUSETV-Thermal and Pressure Relief ValvesCSY-1565-TPRVL-16497316025CSYPRV located next to ball valve (16041) on the inlet line for the micronic filter vesselTaylor ValveT -8200-1XXSection 6-6.3Coordinate with FacilitySet pressure 225 psig
PWS Appx K-3CSY-1565XX1565XX-PUMP STA BLDG AGBULK STORAGE/ PUMPHOUSETV-Thermal and Pressure Relief ValvesCSY-1565-TPRVL-16497416026CSYLocated on top of the micronic filter vesselTaylor ValveT -8200-1XXSection 6-6.3Coordinate with FacilitySet pressure 150 psig
PWS Appx K-3CSY-1565XX1565XX-PUMP STA BLDG AGBULK STORAGE/ PUMPHOUSETV-Thermal and Pressure Relief ValvesCSY-1565-TPRVL-16497516027CSYPRV located next to the control valve on the outlet side of issue filter separator #41Taylor ValveT -8200-1XXSection 6-6.3Coordinate with FacilitySet pressure 100 psig
250221CSY-15651565-FUEL PUMP HOUSE BLDGBULK STORAGE/ PUMPHOUSETV-Thermal and Pressure Relief ValvesCSY-1565-TPRVL-16497616028CSYLocated next to DBB valve 26Taylor ValveT -8200-1XXSection 6-6.3Coordinate with FacilitySet pressure 123 psig
250221CSY-15651565-FUEL PUMP HOUSE BLDGBULK STORAGE/ PUMPHOUSETV-Thermal and Pressure Relief ValvesCSY-1565-TPRVL-16497716029CSYLocated between DBB valves 25 & 45Taylor ValveT -8200-1XXSection 6-6.3Coordinate with FacilitySet pressure 123 psig
250221CSY-15651565-FUEL PUMP HOUSE BLDGBULK STORAGE/ PUMPHOUSETV-Thermal and Pressure Relief ValvesCSY-1565-TPRVL-16497816030CSYLocated next to DBB valve 24Taylor ValveT -8200-1XXSection 6-6.3Coordinate with FacilitySet pressure 123 psig
250221CSY-15651565-FUEL PUMP HOUSE BLDGBULK STORAGE/ PUMPHOUSETV-Thermal and Pressure Relief ValvesCSY-1565-TPRVL-16497916031CSYLocated next to the 16 inch butterfly valveTaylor ValveT -8200-1XXSection 6-6.3Coordinate with FacilitySet pressure 123 psig
PWS Appx K-3CSY-1565XX1565XX-PUMP STA BLDG AGBULK STORAGE/ PUMPHOUSEMV-Ball ValvesCSY-1565-BLVL-16671816035CSYLocated on the 2 inch line from issue filter separator #41Flow-TekXSection 6-6.2.4Notify Facility
PWS Appx K-3CSY-1565XX1565XX-PUMP STA BLDG AGBULK STORAGE/ PUMPHOUSEMV-Ball ValvesB-25CSY-1565-BLVL-16671916036CSYLocated on the 2 inch line from issue filter separator #45. (Valve B-25)Flow-TekXSection 6-6.2.4Notify Facility
PWS Appx K-3CSY-1565XX1565XX-PUMP STA BLDG AGBULK STORAGE/ PUMPHOUSEMV-Ball ValvesB-26CSY-1565-BLVL-16672016037CSYLocated on the 2 inch line from receipt filter separator #46. (Valve B-26)Flow-TekXSection 6-6.2.4Notify Facility
PWS Appx K-3CSY-1565XX1565XX-PUMP STA BLDG AGBULK STORAGE/ PUMPHOUSEMV-Ball ValvesB-26CSY-1565-BLVL-16672116038CSYLocated on the 2 inch line from the micronic filter vesselFlow-TekXSection 6-6.2.4Notify Facility
PWS Appx K-3CSY-1565XX1565XX-PUMP STA BLDG AGBULK STORAGE/ PUMPHOUSEMV-Ball ValvesB-22CSY-1565-BLVL-16672216039CSYLocated on the 2 inch line coming from the PRT to the receipt line (PRT side)Flow-TekXSection 6-6.2.4Notify Facility
PWS Appx K-3CSY-1565XX1565XX-PUMP STA BLDG AGBULK STORAGE/ PUMPHOUSEMV-Ball ValvesB-23CSY-1565-BLVL-16672316040CSYLocated on the 2 inch line coming from the PRT to the receipt line (receipt line side)Flow-TekXSection 6-6.2.4Notify Facility
PWS Appx K-3CSY-1565XX1565XX-PUMP STA BLDG AGBULK STORAGE/ PUMPHOUSEMV-Ball ValvesCSY-1565-BLVL-16672416041CSYInlet isolation ball valve for micronic filter vesselFlow-TekXSection 6-6.2.4Notify Facility
PWS Appx K-3CSY-1565XX1565XX-PUMP STA BLDG AGBULK STORAGE/ PUMPHOUSEMV-Ball ValvesCSY-1565-BLVL-16672516042CSYOutlet isolation ball valve for micronic filter vesselFlow-TekXSection 6-6.2.4Notify Facility
PWS Appx K-3CSY-1565XX1565XX-PUMP STA BLDG AGBULK STORAGE/ PUMPHOUSEMV-Ball ValvesCSY-1565-BLVL-16672616043CSYInlet isolation ball valve for receipt filter separator #46Flow-TekXSection 6-6.2.4Notify Facility
PWS Appx K-3CSY-1565XX1565XX-PUMP STA BLDG AGBULK STORAGE/ PUMPHOUSEMV-Ball ValvesCSY-1565-BLVL-16672716044CSYOutlet isolation ball valve for receipt filter separator #46Flow-TekXSection 6-6.2.4Notify Facility
PWS Appx K-3CSY-1565XX1565XX-PUMP STA BLDG AGBULK STORAGE/ PUMPHOUSEMV-Ball Valves50CSY-1565-BLVL-16672816045CSYInlet isolation ball valve for issue filter separator #45 (Valve 50)Flow-TekXSection 6-6.2.4Notify Facility
PWS Appx K-3CSY-1565XX1565XX-PUMP STA BLDG AGBULK STORAGE/ PUMPHOUSEMV-Ball ValvesCSY-1565-BLVL-16672916046CSYOutlet isolation ball valve for issue filter separator #45Flow-TekXSection 6-6.2.4Notify Facility
PWS Appx K-3CSY-1565XX1565XX-PUMP STA BLDG AGBULK STORAGE/ PUMPHOUSEMV-Ball ValvesCSY-1565-BLVL-16673016047CSYInlet isolation ball valve for issue filter separator #41Flow-TekXSection 6-6.2.4Notify Facility
PWS Appx K-3CSY-1565XX1565XX-PUMP STA BLDG AGBULK STORAGE/ PUMPHOUSEMV-Ball ValvesCSY-1565-BLVL-16673116048CSYOutlet isolation ball valve for issue filter separator #41Flow-TekXSection 6-6.2.4Notify Facility
PWS Appx K-3CSY-1565XX1565XX-PUMP STA BLDG AGBULK STORAGE/ PUMPHOUSEMV-Ball ValvesB-31CSY-1565-BLVL-16673216049CSYLocated on the 2in branch piping on 6in Receipt Piping (low point)Flow-TekXSection 6-6.2.4Notify Facility
PWS Appx K-3CSY-1565XX1565XX-PUMP STA BLDG AGBULK STORAGE/ PUMPHOUSEMV-Ball ValvesCSY-1565-BLVL-16673316050CSYLocated on the 2in branch piping on 6in Issue Piping (high point)Flow-TekXSection 6-6.2.4Notify Facility
250221CSY-15651565-FUEL PUMP HOUSE BLDGBULK STORAGE/ PUMPHOUSEMV-Ball Valves43CSY-1565-BLVL-16673416051CSYLocated on 6in inlet piping to Pump P-1. (Valve 43)Flow-TekXSection 6-6.2.4Notify FacilityWCB N882
250221CSY-15651565-FUEL PUMP HOUSE BLDGBULK STORAGE/ PUMPHOUSEMV-Ball Valves41CSY-1565-BLVL-16673516052CSYLocated on 6in inlet piping to Pump P-2. (Valve 41)Flow-TekXSection 6-6.2.4Notify FacilityWCB N851
250221CSY-15651565-FUEL PUMP HOUSE BLDGBULK STORAGE/ PUMPHOUSEMV-Ball Valves39CSY-1565-BLVL-16673616053CSYLocated on 6in inlet piping to Pump P-3. (Valve 39)Flow-TekXSection 6-6.2.4Notify FacilityWCB N834
250221CSY-15651565-FUEL PUMP HOUSE BLDGBULK STORAGE/ PUMPHOUSEMV-Ball Valves40CSY-1565-BLVL-16673716054CSYLocated on 6in inlet piping to Pump P-4. (Valve 40)Flow-TekXSection 6-6.2.4Notify FacilityWCB N882
250221CSY-15651565-FUEL PUMP HOUSE BLDGBULK STORAGE/ PUMPHOUSEMV-Butterfly Valves36CSY-1565-BFVL-16870516055CSYButterfly valve located on the 16in line between the strainer and the wall. (Valve 36)XSection 6-6.2.6Notify Facility
250221CSY-15651565-FUEL PUMP HOUSE BLDGBULK STORAGE/ PUMPHOUSEMV-Double Block and Bleed Valves26CSY-1565-DBBVL-16339516056CSYFirst valve located on the second 8in Tee off from the main 8in line. (Valve 26)General Valve8111-GXXXSection 6-6.2.5Notify Facility
250221CSY-15651565-FUEL PUMP HOUSE BLDGBULK STORAGE/ PUMPHOUSEMV-Double Block and Bleed Valves24CSY-1565-DBBVL-16339616057CSYLocated on the 8in line that enters the pump house and runs along the wall. (Valve 24)General Valve8111-GXXXSection 6-6.2.5Notify Facility
250221CSY-15651565-FUEL PUMP HOUSE BLDGBULK STORAGE/ PUMPHOUSEMV-Double Block and Bleed Valves25CSY-1565-DBBVL-16339716058CSYLocated on the first 8in Tee off from the main 8in line. (Valve 25)General Valve8111-GXXXSection 6-6.2.5Notify Facility
250221CSY-15651565-FUEL PUMP HOUSE BLDGBULK STORAGE/ PUMPHOUSEMV-Double Block and Bleed Valves45CSY-1565-DBBVL-16339816059CSYSecond valve located on the second 8in Tee off from the main 8in line. (Valve 45)General Valve8111-GXXXSection 6-6.2.5Notify Facility
250221CSY-15651565-FUEL PUMP HOUSE BLDGBULK STORAGE/ PUMPHOUSEMV-Double Block and Bleed Valves44CSY-1565-DBBVL-16339916060CSYLocated on the outlet side of Pump P-1. (Valve 44)General Valve8111-GXXXSection 6-6.2.5Notify Facility
250221CSY-15651565-FUEL PUMP HOUSE BLDGBULK STORAGE/ PUMPHOUSEMV-Double Block and Bleed Valves42CSY-1565-DBBVL-16340016061CSYLocated on the outlet side of Pump P-2. (Valve 42)General Valve8111-GXXXSection 6-6.2.5Notify Facility
250221CSY-15651565-FUEL PUMP HOUSE BLDGBULK STORAGE/ PUMPHOUSEMV-Double Block and Bleed Valves37CSY-1565-DBBVL-16340116062CSYLocated on the outlet side of Pump P-3. (Valve 37)General Valve8111-GXXXSection 6-6.2.5Notify Facility
250221CSY-15651565-FUEL PUMP HOUSE BLDGBULK STORAGE/ PUMPHOUSEMV-Double Block and Bleed Valves38CSY-1565-DBBVL-16340216063CSYLocated on the outlet side of Pump P-4. (Valve 38)General Valve8111-GXXXSection 6-6.2.5Notify Facility
PWS Appx K-3CSY-1565XX1565XX-PUMP STA BLDG AGBULK STORAGE/ PUMPHOUSEMV-Double Block and Bleed Valves19CSY-1565-DBBVL-16340316064CSYLocated behind the micronic filter vesselGeneral Valve8111XXXSection 6-6.2.5Notify Facility
PWS Appx K-3CSY-1565XX1565XX-PUMP STA BLDG AGBULK STORAGE/ PUMPHOUSEMV-Double Block and Bleed Valves22CSY-1565-DBBVL-16340416065CSYLocated behind receipt filter separator #46. (Valve 22)General Valve8111XXXSection 6-6.2.5Notify Facility
PWS Appx K-3CSY-1565XX1565XX-PUMP STA BLDG AGBULK STORAGE/ PUMPHOUSEMV-Double Block and Bleed ValvesCSY-1565-DBBVL-16340516066CSYLocated behind issue filter separator #41 on the issue line (crossover valve)GHATGE PATILOmniSeal DBB Expanding Plug ValveXXXSection 6-6.2.5Notify Facility
PWS Appx K-3CSY-1565XX1565XX-PUMP STA BLDG AGBULK STORAGE/ PUMPHOUSEMV-Ball ValvesB-47CSY-1565-BLVL-169887CSY00216Located before the OPW cam lock connection for the PRTFlow-TekXSection 6-6.2.4Notify Facility
PWS Appx K-3CSY-1565XX1565XX-PUMP STA BLDG AGBULK STORAGE/ PUMPHOUSEMV-Ball ValvesB-19CSY-1565-BLVL-169919CSY00217Located below the PRT (drain) (Valve B-19)Flow-TekXSection 6-6.2.4Notify Facility
PWS Appx K-3CSY-1565XX1565XX-PUMP STA BLDG AGBULK STORAGE/ PUMPHOUSEMV-Ball ValvesB-18CSY-1565-BLVL-169921CSY00218Located on the 1 inch PRT pump bypass line. (Valve B-18)Flow-TekXSection 6-6.2.4Notify Facility
PWS Appx K-3CSY-1565XX1565XX-PUMP STA BLDG AGBULK STORAGE/ PUMPHOUSEMV-Ball ValvesB-20CSY-1565-BLVL-169981CSY00219Located on the 1 inch line from the PRT to the PRT pump. (Valve B-20)Flow-TekXSection 6-6.2.4Notify Facility
PWS Appx K-3CSY-1565XX1565XX-PUMP STA BLDG AGBULK STORAGE/ PUMPHOUSEMV-Ball ValvesB-16CSY-1565-BLVL-176277CSY00223Located below the micronic filter vessel (drain) (Valve B-16)Flow-TekXSection 6-6.2.4Notify Facility
PWS Appx K-3CSY-1565XX1565XX-PUMP STA BLDG AGBULK STORAGE/ PUMPHOUSEMV-Ball ValvesB-15CSY-1565-BLVL-169922CSY00224Located below the micronic filter vessel (horizontal)Flow-TekXSection 6-6.2.4Notify Facility
PWS Appx K-3CSY-1565XX1565XX-PUMP STA BLDG AGBULK STORAGE/ PUMPHOUSEMV-Ball ValvesB-14CSY-1565-BLVL-169923CSY00225Upstream isolation ball valve for the air eliminator located on top of the micronic filter vesselFlow-TekXSection 6-6.2.4Notify Facility
PWS Appx K-3CSY-1565XX1565XX-PUMP STA BLDG AGBULK STORAGE/ PUMPHOUSEMV-Ball ValvesB-13CSY-1565-BLVL-169924CSY00226Located on top of the micronic filter vessel (high point drain) (Valve B-13)Flow-TekXSection 6-6.2.4Notify Facility
PWS Appx K-3CSY-1565XX1565XX-PUMP STA BLDG AGBULK STORAGE/ PUMPHOUSEMV-Ball ValvesCSY-1565-BLVL-169888CSY00227Upstream isolation ball valve for PRV (16025) located next to ball valve (16041) on the inlet line for the micronic filter vesselFlow-TekXSection 6-6.2.4Notify Facility
PWS Appx K-3CSY-1565XX1565XX-PUMP STA BLDG AGBULK STORAGE/ PUMPHOUSEMV-Ball ValvesCSY-1565-BLVL-176278CSY00231Located below Filter Separator #46 (drain)Flow-TekXSection 6-6.2.4Notify Facility
PWS Appx K-3CSY-1565XX1565XX-PUMP STA BLDG AGBULK STORAGE/ PUMPHOUSEMV-Ball ValvesCSY-1565-BLVL-169925CSY00232Located below Filter Separator #46 (horizontal)Flow-TekXSection 6-6.2.4Notify Facility
PWS Appx K-3CSY-1565XX1565XX-PUMP STA BLDG AGBULK STORAGE/ PUMPHOUSEMV-Ball ValvesCSY-1565-BLVL-169926CSY00233Upstream isolation ball valve for the air eliminator located on top of receipt filter separator #46Flow-TekXSection 6-6.2.4Notify Facility
PWS Appx K-3CSY-1565XX1565XX-PUMP STA BLDG AGBULK STORAGE/ PUMPHOUSEMV-Ball ValvesCSY-1565-BLVL-169982CSY00234Located on top of receipt filter separator #46 (high point drain)Flow-TekXSection 6-6.2.4Notify Facility
PWS Appx K-3CSY-1565XX1565XX-PUMP STA BLDG AGBULK STORAGE/ PUMPHOUSEMV-Ball ValvesCSY-1565-BLVL-169983CSY00235Upstream isolation ball valve for PRV (16024) located next to ball valve (16043) on the inlet line for receipt filter separator #46Flow-TekXSection 6-6.2.4Notify Facility
PWS Appx K-3CSY-1565XX1565XX-PUMP STA BLDG AGBULK STORAGE/ PUMPHOUSEMV-Ball ValvesCSY-1565-BLVL-176279CSY00239Located below Filter Separator #45 (drain)Flow-TekXSection 6-6.2.4Notify Facility
PWS Appx K-3CSY-1565XX1565XX-PUMP STA BLDG AGBULK STORAGE/ PUMPHOUSEMV-Ball ValvesCSY-1565-BLVL-176280CSY00240Located below Filter Separator #45 (horizontal)Flow-TekXSection 6-6.2.4Notify Facility
PWS Appx K-3CSY-1565XX1565XX-PUMP STA BLDG AGBULK STORAGE/ PUMPHOUSEMV-Ball ValvesCSY-1565-BLVL-176281CSY00241Upstream isolation ball valve for the air eliminator located on top of issue filter separator #45Flow-TekXSection 6-6.2.4Notify Facility
PWS Appx K-3CSY-1565XX1565XX-PUMP STA BLDG AGBULK STORAGE/ PUMPHOUSEMV-Ball ValvesCSY-1565-BLVL-176282CSY00242Located on top of issue filter separator #45 (high point drain)Flow-TekXSection 6-6.2.4Notify Facility
PWS Appx K-3CSY-1565XX1565XX-PUMP STA BLDG AGBULK STORAGE/ PUMPHOUSEMV-Ball ValvesCSY-1565-BLVL-169927CSY00243Upstream isolation ball valve for PRV (16022) located next to ball valve 50 (16045) on the inlet line for issue filter separator #45Flow-TekXSection 6-6.2.4Notify Facility
PWS Appx K-3CSY-1565XX1565XX-PUMP STA BLDG AGBULK STORAGE/ PUMPHOUSEMV-Ball ValvesCSY-1565-BLVL-176283CSY00249Located below Filter Separator #41 (drain)Flow-TekXSection 6-6.2.4Notify Facility
250221CSY-15651565-FUEL PUMP HOUSE BLDGBULK STORAGE/ PUMPHOUSEMV-Check ValvesCSY-1565-CKVL-169928CSY00250Located on the bypass line for ball valve 43 on Pump P-1 inlet lineILSHINXSection 6-6.2.8Operate System to Test
250221CSY-15651565-FUEL PUMP HOUSE BLDGBULK STORAGE/ PUMPHOUSEMV-Check ValvesCSY-1565-CKVL-169929CSY00251Located on the bypass line for ball valve 41 on Pump P-2 inlet lineILSHINXSection 6-6.2.8Operate System to Test
250221CSY-15651565-FUEL PUMP HOUSE BLDGBULK STORAGE/ PUMPHOUSEMV-Check ValvesCSY-1565-CKVL-169984CSY00252Located on the bypass line for ball valve 39 on Pump P-3 inlet lineILSHINXSection 6-6.2.8Operate System to Test
250221CSY-15651565-FUEL PUMP HOUSE BLDGBULK STORAGE/ PUMPHOUSEMV-Check ValvesCSY-1565-CKVL-169889CSY00253Located on the bypass line for ball valve 40 on Pump P-4 inlet lineILSHINXSection 6-6.2.8Operate System to Test
250221CSY-15651565-FUEL PUMP HOUSE BLDGBULK STORAGE/ PUMPHOUSEMV-Check ValvesCSY-1565-CKVL-169890CSY00254Located on the 6in discharge line of Pump P-1CROWNPN J-68-50WT3-BFXSection 6-6.2.8Operate System to Test
250221CSY-15651565-FUEL PUMP HOUSE BLDGBULK STORAGE/ PUMPHOUSEMV-Check ValvesCSY-1565-CKVL-169891CSY00255Located on the 6in discharge line of Pump P-2CROWNXSection 6-6.2.8Operate System to Test
250221CSY-15651565-FUEL PUMP HOUSE BLDGBULK STORAGE/ PUMPHOUSEMV-Check ValvesCSY-1565-CKVL-169892CSY00256Located on the 6in discharge line of Pump P-3CROWNPN J-68-50WT3-BFXSection 6-6.2.8Operate System to Test
250221CSY-15651565-FUEL PUMP HOUSE BLDGBULK STORAGE/ PUMPHOUSEMV-Check ValvesCSY-1565-CKVL-169930CSY00257Located on the 6in discharge line of Pump P-4CROWNPN J-68-50WT3-BFXSection 6-6.2.8Operate System to Test
250221CSY-15651565-FUEL PUMP HOUSE BLDGBULK STORAGE/ PUMPHOUSEMV-Check ValvesCSY-1565-CKVL-169931CSY00258Located next to DBB valve 26CROWNXSection 6-6.2.8Operate System to Test
250221CSY-15651565-FUEL PUMP HOUSE BLDGBULK STORAGE/ PUMPHOUSEMV-Check ValvesCSY-1565-CKVL-169985CSY00259Located between DBB valves 24 and 25CROWNXSection 6-6.2.8Operate System to Test
PWS Appx K-3CSY-1565XX1565XX-PUMP STA BLDG AGBULK STORAGE/ PUMPHOUSEMV-Check ValvesCSY-1565-CKVL-169986CSY00260Located on the 2 inch line from the PRT to the receipt lineVelanMODEL AXSection 6-6.2.8Operate System to Test
PWS Appx K-3CSY-1565XX1565XX-PUMP STA BLDG AGBULK STORAGE/ PUMPHOUSEMV-Check ValvesCSY-1565-CKVL-169987CSY00261Located on the 2 inch line to the PRTXSection 6-6.2.8Operate System to Test
PWS Appx K-3CSY-1565XX1565XX-PUMP STA BLDG AGBULK STORAGE/ PUMPHOUSECV-Filter Separator Control ValvesCSY-1565-FSCVL-165477CSY00263Located on the outlet side of issue filter separator 41Cla-ValXXXSection 4-4.2.2Operate System to TestStock NO. 7090906E
PWS Appx K-3CSY-1565XX1565XX-PUMP STA BLDG AGBULK STORAGE/ PUMPHOUSECV-Filter Separator Control ValvesCSY-1565-FSCVL-165478CSY00264Located on the outlet side of issue filter separator 45Cla-ValXXXSection 4-4.2.2Operate System to TestStock NO. 7090906E
PWS Appx K-3CSY-1565XX1565XX-PUMP STA BLDG AGBULK STORAGE/ PUMPHOUSECV-Filter Separator Control ValvesCSY-1565-FSCVL-165479CSY00265Located on the outlet side of receipt filter separator 46Cla-ValXXXSection 4-4.2.2Operate System to TestStock NO. 7090906E
PWS Appx K-3CSY-1565XX1565XX-PUMP STA BLDG AGBULK STORAGE/ PUMPHOUSEPV-Differential Pressure GaugesCSY-1565-DPGA-169988CSY00277Located on filter separator 41Gammon534-30XXSection 6-7.2Coordinate with Facility
PWS Appx K-3CSY-1565XX1565XX-PUMP STA BLDG AGBULK STORAGE/ PUMPHOUSEPV-Differential Pressure GaugesCSY-1565-DPGA-169989CSY00278Located on filter separator 45Gammon534-30XXSection 6-7.2Coordinate with Facility
PWS Appx K-3CSY-1565XX1565XX-PUMP STA BLDG AGBULK STORAGE/ PUMPHOUSEPV-Differential Pressure GaugesCSY-1565-DPGA-169893CSY00279Located on filter separator 46Gammon534-30XXSection 6-7.2Coordinate with Facility
PWS Appx K-3CSY-1565XX1565XX-PUMP STA BLDG AGBULK STORAGE/ PUMPHOUSEPV-Differential Pressure GaugesCSY-1565-DPGA-169932CSY00280Located on the micronic filters next to filter separator 46Gammon534-30XXSection 6-7.2Coordinate with Facility
250221CSY-15651565-FUEL PUMP HOUSE BLDGBULK STORAGE/ PUMPHOUSEPV-Differential Pressure GaugesCSY-1565-DPGA-169933CSY00281Located on the 16in strainer inside facility S1565Gammon534-30XXSection 6-7.2Coordinate with Facility
PWS Appx K-3CSY-1565XX1565XX-PUMP STA BLDG AGBULK STORAGE/ PUMPHOUSEFT-Filter SeparatorsCSY-1565-FLSP-169894CSY00283Issue filter separator #41 located under the canopy next to facility S1565M.E. Industries, Inc.CFCS-D-7K39SB-1-2636FMXXSection 3-6.2Base provides filter elements
PWS Appx K-3CSY-1565XX1565XX-PUMP STA BLDG AGBULK STORAGE/ PUMPHOUSEFT-Filter SeparatorsCSY-1565-FLSP-169895CSY00284Issue filter separator #45 located under the canopy next to facility S1565M.E. Industries, Inc.CFCS-D-7K39SB-1-2636FMXXSection 3-6.2Base provides filter elements
PWS Appx K-3CSY-1565XX1565XX-PUMP STA BLDG AGBULK STORAGE/ PUMPHOUSEFT-Filter SeparatorsCSY-1565-FLSP-169896CSY00285Receipt filter separator #46 located under the canopy next to facility S1565M.E. Industries, Inc.CFCS-D-7K39SB-1-2636FMXXSection 3-6.2Base provides filter elements
PWS Appx K-3CSY-1565XX1565XX-PUMP STA BLDG AGBULK STORAGE/ PUMPHOUSEFT-Pre-Filter VesselsCSY-1565-PFVSL-169899CSY00286Micronic vessel located next to receipt filter separator #46BROWN S MFG LLCHF1644150NXXSection 3-6.1Base provides filter elements
PWS Appx K-3CSY-1565XX1565XX-PUMP STA BLDG AGBULK STORAGE/ PUMPHOUSEFP-Sight Flow IndicatorsCSY-1565-SFND-169934CSY00287Located on filter separator 41OPW VISI-FLO1571RXSection 6-12.3
PWS Appx K-3CSY-1565XX1565XX-PUMP STA BLDG AGBULK STORAGE/ PUMPHOUSEFP-Sight Flow IndicatorsCSY-1565-SFND-169935CSY00288Located on filter separator 45OPW VISI-FLO1571RXSection 6-12.3
PWS Appx K-3CSY-1565XX1565XX-PUMP STA BLDG AGBULK STORAGE/ PUMPHOUSEFP-Sight Flow IndicatorsCSY-1565-SFND-170007CSY00289Located on filter separator 46OPW VISI-FLO1571RXSection 6-12.3
PWS Appx K-3CSY-1565XX1565XX-PUMP STA BLDG AGBULK STORAGE/ PUMPHOUSEFP-Sight Flow IndicatorsCSY-1565-SFND-169901CSY00290Located on the micronic filters next to filter separator 46OPW VISI-FLO1571RXSection 6-12.3
PWS Appx K-3CSY-1565XX1565XX-PUMP STA BLDG AGBULK STORAGE/ PUMPHOUSEFP-Sight Flow IndicatorsCSY-1565-SFND-169903CSY00291Located on the PRT piping under the filter the filter separator canopyOPW VISI-FLO1471RFXSection 6-12.3
250221CSY-15651565-FUEL PUMP HOUSE BLDGBULK STORAGE/ PUMPHOUSEPC-Aboveground Piping and Equipment CoatingCSY-1565-AGPCT-176284CSY0029216 inch piping located inside and outside of the pump houseSection 6-10.1
250221CSY-15651565-FUEL PUMP HOUSE BLDGBULK STORAGE/ PUMPHOUSEPV-Pressure GaugesCSY-1565-PVGA-176285CSY00293Located on the outlet of pump P-1HISCOXXXSection 6-7.1Coordinate with Facility
250221CSY-15651565-FUEL PUMP HOUSE BLDGBULK STORAGE/ PUMPHOUSEPV-Pressure GaugesCSY-1565-PVGA-169936CSY00294Located on the outlet of pump P-2HISCOXXXSection 6-7.1Coordinate with Facility
250221CSY-15651565-FUEL PUMP HOUSE BLDGBULK STORAGE/ PUMPHOUSEPV-Pressure GaugesCSY-1565-PVGA-169937CSY00295Located on the outlet of pump P-3HISCOXXXSection 6-7.1Coordinate with Facility
250221CSY-15651565-FUEL PUMP HOUSE BLDGBULK STORAGE/ PUMPHOUSEPV-Pressure GaugesCSY-1565-PVGA-169940CSY00296Located on the outlet of pump P-4HISCOXXXSection 6-7.1Coordinate with Facility
250221CSY-15651565-FUEL PUMP HOUSE BLDGBULK STORAGE/ PUMPHOUSEPV-Pressure GaugesCSY-1565-PVGA-169943CSY00297Located behind pump P-1 on the 8in fuel lineHISCOXXXSection 6-7.1Coordinate with Facility
250221CSY-15651565-FUEL PUMP HOUSE BLDGBULK STORAGE/ PUMPHOUSEPM-Centrifugal PumpsP-1CSY-1565-CENP-169938CSY00310Issue Pump P-1 inside facility 1565Union Pumps4X6X18 HHSXXXSection 3-8.1Operate System to Test
250221CSY-15651565-FUEL PUMP HOUSE BLDGBULK STORAGE/ PUMPHOUSEPM-Centrifugal PumpsP-2CSY-1565-CENP-169945CSY00311Issue Pump P-2 inside facility 1565Union Pumps4X6X18 HHSXXXSection 3-8.1
250221CSY-15651565-FUEL PUMP HOUSE BLDGBULK STORAGE/ PUMPHOUSEPM-Centrifugal PumpsP-3CSY-1565-CENP-169991CSY00312Issue Pump P-3 inside facility 1565Union Pumps4X6X18 HHSXXXSection 3-8.1
250221CSY-15651565-FUEL PUMP HOUSE BLDGBULK STORAGE/ PUMPHOUSEPM-Centrifugal PumpsP-4CSY-1565-CENP-170008CSY00313Issue Pump P-4 inside facility 1565Union Pumps4X6X18 HHSXXXSection 3-8.1Operate System to Test
250221CSY-15651565-FUEL PUMP HOUSE BLDGBULK STORAGE/ PUMPHOUSEFT-Basket StrainerCSY-1565-BSTR-176286CSY00315Located in facility S1565 on the 16in fuel lineKeckleyF8XXSection 3-6.4
250221CSY-15651565-FUEL PUMP HOUSE BLDGBULK STORAGE/ PUMPHOUSEEQ-Real PropertyCSY-1565-ASSET-153842CSY00316Pump P-1 Motor controlAppletonEDS-20036Non-Appx G Class
250221CSY-15651565-FUEL PUMP HOUSE BLDGBULK STORAGE/ PUMPHOUSEEQ-Real PropertyCSY-1565-ASSET-153843CSY00317Pump P-2 motor controlAppletonEDS-20036Non-Appx G Class
250221CSY-15651565-FUEL PUMP HOUSE BLDGBULK STORAGE/ PUMPHOUSEEQ-Real PropertyCSY-1565-ASSET-153844CSY00318Pump P-3 motor controlAppletonEDS-20036Non-Appx G Class
PWS Appx K-3CSY-1565XX1565XX-PUMP STA BLDG AGBULK STORAGE/ PUMPHOUSEPS-Product Saver TanksCSY-1565-PRDST-176287CSY00319PRT located under the filter separator canopy next to facility 1565HAN SUNG VALVEXSection 8-9.10Notify Facility
PWS Appx K-3CSY-1565XX1565XX-PUMP STA BLDG AGBULK STORAGE/ PUMPHOUSEMV-Ball ValvesCSY-1565-BLVL-170009CSY00320Located below Filter Separator #41 (horizontal)Flow-TekXSection 6-6.2.4Notify Facility
PWS Appx K-3CSY-1565XX1565XX-PUMP STA BLDG AGBULK STORAGE/ PUMPHOUSEMV-Ball ValvesCSY-1565-BLVL-169962CSY00321Upstream isolation ball valve for the air eliminator located on top of issue filter separator #41Flow-TekXSection 6-6.2.4Notify Facility
PWS Appx K-3CSY-1565XX1565XX-PUMP STA BLDG AGBULK STORAGE/ PUMPHOUSEMV-Ball ValvesCSY-1565-BLVL-169963CSY00322Located on top of issue filter separator #41 (high point drain)Flow-TekXSection 6-6.2.4Notify Facility
PWS Appx K-3CSY-1565XX1565XX-PUMP STA BLDG AGBULK STORAGE/ PUMPHOUSEMV-Ball ValvesCSY-1565-BLVL-176288CSY00323Upstream isolation ball valve for PRV (16019) located next to ball valve (16047) on the inlet line for issue filter separator #41YOUNG JINYJ-150XSection 6-6.2.4Notify Facility
PWS Appx K-3CSY-1565XX1565XX-PUMP STA BLDG AGBULK STORAGE/ PUMPHOUSEMV-Ball ValvesCSY-1565-BLVL-169992CSY00324Upstream isolation ball valve for PRV (16027) located next to the control valve on the outlet side of issue filter separator #41Flow-TekXSection 6-6.2.4Notify Facility
PWS Appx K-3CSY-1565XX1565XX-PUMP STA BLDG AGBULK STORAGE/ PUMPHOUSEPV-Pressure GaugesCSY-1565-PVGA-176289CSY00326Located on the DP gauge for issue filter separator 41WikaXXXSection 6-7.1Coordinate with Facility
PWS Appx K-3CSY-1565XX1565XX-PUMP STA BLDG AGBULK STORAGE/ PUMPHOUSEPV-Pressure GaugesCSY-1565-PVGA-169993CSY00327Located on the DP gauge for issue filter separator 45WikaXXXSection 6-7.1Coordinate with Facility
PWS Appx K-3CSY-1565XX1565XX-PUMP STA BLDG AGBULK STORAGE/ PUMPHOUSEPV-Pressure GaugesCSY-1565-PVGA-169994CSY00328Located on the DP gauge for receipt filter separator 46Valley InstrumentXXXSection 6-7.1Coordinate with Facility
250221CSY-15651565-FUEL PUMP HOUSE BLDGBULK STORAGE/ PUMPHOUSEPC-Aboveground Piping and Equipment CoatingCSY-1565-AGPCT-170010CSY0032910 inch piping located inside and outside of the pump houseSection 6-10.1