FMP POF YCH_20251029.xlsx
XLSX spreadsheet 192 KB Posted
- Solicitation number
- DRAFTW912DY26RA005
About this file
This is a Facility Maintenance Plan (FMP) for the DFSP Yecheon fuel storage facility located in Korea, prepared for the Pacific Ocean Division under contract W912DY-21-F-0076 by APTIM Federal Services, LLC. The document details comprehensive maintenance requirements for multiple fuel storage and transfer systems, including seven underground JP-8 aircraft fuel tanks (Y1-Y7), two slop tanks (ST1, ST2), two flightline service tanks (FL1, FL2), and various supporting infrastructure such as hydrant systems, pump houses, pipeline valve pits, truck fill stands, and rail offloading headers.
The maintenance plan provides extensive technical specifications for each asset, including component unique identifiers, manufacturer details, maintenance frequencies, UFC section references, and special considerations. Key systems include filter separators, pumps, valves, piping, control systems, and electrical equipment across facilities like the POL Pump House 355 and 356, with maintenance tasks ranging from quarterly to annual inspections. The document emphasizes precise tracking of equipment, manufacturer requirements, system availability impacts, and cross-referencing of asset identifications, demonstrating a comprehensive approach to maintaining critical fuel infrastructure at the Yecheon Defense Fuel Support Point.
View the file
Other files
Show all 37
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Administrative
| ADMINISTRATIVE | ||
| Location | Installation Name | DFSP Yecheon |
| DLA Site Code | YCH | |
| RPSUID | 601 | |
| Hours of Operation | 0800-1630 | |
| Address | Yecheon, Korea | |
| Contract | Contractor | |
| Contract # | ||
| Local POCs | Primary FMSR | |
| FMSR Phone | ||
| FMSR Email | ||
| Alternate FMSR | ||
| Alt FMSR Phone | ||
| Alt FMSR Email | ||
| Contractor POCs | Contractor PM | |
| Contractor PM Phone | ||
| Contractor PM Email | ||
| Contractor QC Manager | ||
| Contractor QC Phone | ||
| Contractor QC Email | ||
| Contractor SOE | ||
| Contractor SOE Phone | ||
| Contractor SOE Email | ||
| Contractor RM | ||
| Contractor RM Phone | ||
| Contractor RM Email | ||
| Contractor SM | ||
| Contractor SM Phone | ||
| Contractor SM Email | ||
| USACE POCs | USACE PM/COR | |
| USACE PM/COR Phone | ||
| USACE PM/COR Email | ||
| USACE PE | ||
| USACE PE Phone | ||
| USACE PE Email | ||
| USACE KO | ||
| USACE KO Phone | ||
| USACE KO Email | ||
| USACE Monthly Report Inbox |
Pacific Ocean Division, POD-AF
| W912DY-21-F-0076 | &"-,Bold"&16DFSP Yecheon |
| YCH | Facility Maintenance Plan |
OY3 Q3
&A &P of &N APTIM Federal Services, LLC
Instructions:
This table shows the minimum information required. Additional details should be included based on site specific requirements. Additional POCs may be required.
General Facility Description
| General Facility Description | |
| Installation Name | DFSP Yecheon |
| DLA Site Code | YCH |
| Location | Yecheon, Korea |
| Bulk Storage (fueling facility to support marine and aircraft operations): (7) JP-8 USTs connected to rail/truck receipts; (10) rail car receipts (majority of fuel received by rail); (4) JP-8 truck fill/issue stand - 1 fill stands (two issue lines are not operational because of underground line leak); (2) 50,000-gallon USTs for Type IV hydrant system with (4) issue pantographs; (3) Pump Rooms 355, 356 and Tanks FL1/2. | |
| Contractor maintained. Ahntech operates the fuel systems and performs routine general maintenance. |
DLA is responsible (COR) for Ahntech.
Pacific Ocean Division, POD-AF
| W912DY-21-F-0076 | &"-,Bold"&16DFSP Yecheon |
| YCH | Facility Maintenance Plan |
OY3 Q3
&A &P of &N APTIM Federal Services, LLC
Instructions:
Include a general facility overview and description of each fuel system for the sites in accordance with UFC 3-460-01. Examples include: Bulk Storage Facilities, Aircraft Fueling Facilities, Marine and Dispensing Facilities, Ground Products Fueling Facilities, Alternate POL Facilities, and Support Facilities. Also include facility #s, facility names, fuel type, photos, and any other pertinent information.
Include Site Specific Conditions and Restrictions in this tab.
Communication Plan
Pacific Ocean Division, POD-AF
| W912DY-21-F-0076 | &"-,Bold"&16DFSP Yecheon |
| YCH | Facility Maintenance Plan |
OY3 Q3
&A &P of &N APTIM Federal Services, LLC
Instructions:
Communication plan shall address in/out briefs, lines of communication, coordination for access, etc.
Site Specific APP
Pacific Ocean Division, POD-AF
| W912DY-21-F-0076 | &"-,Bold"&16DFSP Yecheon |
| YCH | Facility Maintenance Plan |
OY3 Q3
&A &P of &N APTIM Federal Services, LLC
Instructions:
Site Specific Addendum and Activity Hazard Analysis, which are Attachments to the APP, specific to activities or tasks related to recurring maintenance for this site.
Instructions:
Site Specific Addendum and Activity Hazard Analysis, which are Attachments to the APP, specific to activities or tasks related to recurring maintenance for this site.
PM Schedule
Pacific Ocean Division, POD-AF
| W912DY-21-F-0076 | &"-,Bold"&16DFSP Yecheon |
| YCH | Facility Maintenance Plan |
OY3 Q3
&A &P of &N APTIM Federal Services, LLC
Instructions:
Link PM schedule here
Task Matrix
| Applicable Facility Assets | UFC System Level Maintenance Frequency | Special Considerations | ||||||||||||||||||
| RPUID | Real Property Facility # | Facility Name | Operational Area | Component Type | Base Asset Name | Component Unique ID CUID | APTIM Asset ID | Asset Description | Make | Model | Capacity / Size | Quarterly | Semi Annual | Annual | UFC Section Reference | Additional Manufacturer RM Requirements | Operator/Equipment Requirements | System Availability | Other Contract | Comments |
| 11181 | YCH-Y2 | Y2-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | MV-Ball Valves | 129 | YCH-Y2-BLVL-168854 | 16463YCH | Located on the 8 inch receipt line | Jamesbury | MA030-01 | X | Section 6-6.2.4 | Notify Facility; Confined Space | Confined Space- | ||||||
| 11181 | YCH-Y2 | Y2-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | MV-Ball Valves | YCH-Y2-BLVL-168759 | 16464YCH | Located on the 6 inch line for issue pump M2A | HwaSung Co., Ltd. | X | Section 6-6.2.4 | Notify Facility; Confined Space | Confined Space- | ||||||||
| 11181 | YCH-Y2 | Y2-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | MV-Ball Valves | YCH-Y2-BLVL-175954 | 16465YCH | Located on the 6 inch line for issue pump M2B | HwaSung Co., Ltd. | X | Section 6-6.2.4 | Notify Facility; Confined Space | Confined Space- | ||||||||
| 11181 | YCH-Y2 | Y2-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | MV-Ball Valves | YCH-Y2-BLVL-168761 | 16466YCH | Located on the 6 inch return line | HwaSung Co., Ltd. | X | Section 6-6.2.4 | Notify Facility; Confined Space | Confined Space- | ||||||||
| 11182 | YCH-Y3 | Y3-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | MV-Ball Valves | 138 | YCH-Y3-BLVL-175955 | 16467YCH | Located on the 8 inch receipt line | X | Section 6-6.2.4 | Notify Facility; Confined Space | Confined Space- | ||||||||
| 11182 | YCH-Y3 | Y3-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | MV-Ball Valves | 131 | YCH-Y3-BLVL-175956 | 16468YCH | Ball valve located on the issue line for M3B | X | Section 6-6.2.4 | Notify Facility; Confined Space | Confined Space- | ||||||||
| 11182 | YCH-Y3 | Y3-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | MV-Ball Valves | 132 | YCH-Y3-BLVL-168856 | 16469YCH | Ball valve located on the issue line for M3A | X | Section 6-6.2.4 | Notify Facility; Confined Space | Confined Space- | ||||||||
| 11182 | YCH-Y3 | Y3-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | MV-Ball Valves | 133 | YCH-Y3-BLVL-168858 | 16470YCH | Ball valve located on the return line | X | Section 6-6.2.4 | Notify Facility; Confined Space | Confined Space- | ||||||||
| 11185 | YCH-Y6 | Y6-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | MV-Ball Valves | 304 | YCH-Y6-BLVL-168987 | 16471YCH | 6-inch ball valve located on the receipt line. (Valve 304) | X | Section 6-6.2.4 | Notify Facility; Confined Space | Confined Space- | ||||||||
| 11185 | YCH-Y6 | Y6-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | MV-Ball Valves | 301 | YCH-Y6-BLVL-168988 | 16472YCH | 8-inch ball valve located on the discharge line for issue pump MS6A. (Valve 301) | X | Section 6-6.2.4 | Notify Facility; Confined Space | Confined Space- | ||||||||
| 11185 | YCH-Y6 | Y6-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | MV-Ball Valves | YCH-Y6-BLVL-175957 | 16473YCH | 6-inch ball valve located on the return line. | X | Section 6-6.2.4 | Notify Facility; Confined Space | Confined Space- | |||||||||
| 11186 | YCH-Y7 | Y7-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | MV-Ball Valves | 314 | YCH-Y7-BLVL-168860 | 16476YCH | Located on the 6 inch receipt line | X | Section 6-6.2.4 | Notify Facility; Confined Space | Confined Space- | ||||||||
| 11186 | YCH-Y7 | Y7-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | MV-Ball Valves | 311 | YCH-Y7-BLVL-168861 | 16477YCH | Located on the 8 inch issue line | X | Section 6-6.2.4 | Notify Facility; Confined Space | Confined Space- | ||||||||
| 11186 | YCH-Y7 | Y7-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | MV-Ball Valves | 312 | YCH-Y7-BLVL-168763 | 16478YCH | Located on the 6 inch return line | X | Section 6-6.2.4 | Notify Facility; Confined Space | Confined Space- | ||||||||
| 11186 | YCH-Y7 | Y7-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | MV-Ball Valves | 315 | YCH-Y7-BLVL-168765 | 16479YCH | 2-inch ball valve located on the PRT return line inside the tank vault. (Valve 315) | X | Section 6-6.2.4 | Notify Facility; Confined Space | Confined Space- | ||||||||
| 11186 | YCH-Y7 | Y7-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | MV-Ball Valves | 313 | YCH-Y7-BLVL-168990 | 16480YCH | 2-inch Val valve located on the sump pump discharge line. (Valve 313) | X | Section 6-6.2.4 | Notify Facility; Confined Space | Confined Space- | ||||||||
| 11183 | YCH-Y4 | Y4-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | MV-Ball Valves | YCH-Y4-BLVL-168991 | 16481YCH | 6-inch ball valve located on the receipt line. | X | Section 6-6.2.4 | Notify Facility; Confined Space | Confined Space- | |||||||||
| 11183 | YCH-Y4 | Y4-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | MV-Ball Valves | 201 | YCH-Y4-BLVL-168768 | 16482YCH | 8-inch ball valve located on the discharge line for issue pump MS4A. (Valve 201) | X | Section 6-6.2.4 | Notify Facility; Confined Space | Confined Space- | ||||||||
| 11183 | YCH-Y4 | Y4-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | MV-Ball Valves | 202 | YCH-Y4-BLVL-168992 | 16483YCH | 6-inch ball valve located on the return line. (Valve 202) | X | Section 6-6.2.4 | Notify Facility; Confined Space | Confined Space- | ||||||||
| 11184 | YCH-Y5 | Y5-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | MV-Ball Valves | 214 | YCH-Y5-BLVL-175959 | 16484YCH | 6-inch bal valve located on the receipt line. (Valve 214) | X | Section 6-6.2.4 | Notify Facility; Confined Space | Confined Space- | ||||||||
| 11184 | YCH-Y5 | Y5-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | MV-Ball Valves | 210 | YCH-Y5-BLVL-168863 | 16485YCH | 8-inch ball valve located on the discharge line for issue pump M5B. (Valve 210) | X | Section 6-6.2.4 | Notify Facility; Confined Space | Confined Space- | ||||||||
| 11184 | YCH-Y5 | Y5-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | MV-Ball Valves | 211 | YCH-Y5-BLVL-175960 | 16486YCH | 8-inch ball valve located on the discharge line for issue pump M5A. (Valve 211) | X | Section 6-6.2.4 | Notify Facility; Confined Space | Confined Space- | ||||||||
| 11184 | YCH-Y5 | Y5-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | MV-Ball Valves | 212 | YCH-Y5-BLVL-175961 | 16487YCH | 6-inch ball valve located on the return line. (Valve 212) | X | Section 6-6.2.4 | Notify Facility; Confined Space | Confined Space- | ||||||||
| 1114225 | YCH-ST1 | ST1-SLOP TANK 1 | BULK STORAGE | MV-Ball Valves | YCH-ST1-BLVL-174917 | YCH00558 | Ball valve located on 2 inch piping for quick connect | X | Section 6-6.2.4 | Notify Facility | ||||||||||
| 1114225 | YCH-ST1 | ST1-SLOP TANK 1 | BULK STORAGE | MV-Check Valves | YCH-ST1-CKVL-174775 | YCH00559 | Check valve located on 2 inch piping for quick connect | X | Section 6-6.2.8 | Notify Facility | ||||||||||
| 1114225 | YCH-ST1 | ST1-SLOP TANK 1 | BULK STORAGE | TK-Underground Double-Walled Shop-Fabricated Tanks | ST 1 | YCH-ST1-UGDSFT-174918 | YCH00560 | Slop tank 1 located underground | X | Section 8-5.4.2 | ||||||||||
| 1114225 | YCH-ST1 | ST1-SLOP TANK 1 | BULK STORAGE | PC-Aboveground Piping and Equipment Coating | YCH-ST1-AGPCT-174776 | YCH00562 | 2-inch coated piping for slop tank ST1 | Section 6-10.1 | ||||||||||||
| 1114225 | YCH-ST1 | ST1-SLOP TANK 1 | BULK STORAGE | EC-Ground Reels - Static Grounding Systems | YCH-ST1-STGS-174919 | YCH00563 | Ground reel located at slop tank 1 | X | X | Section 9-1.6.2 | ||||||||||
| 1114225 | YCH-ST1 | ST1-SLOP TANK 1 | BULK STORAGE | EC-EFSO-Elec Equip | YCH-ST1-EFSO-175366 | YCH00564 | EFSO located at slop tank 1 | X | Section 9-1.2 | Operate System to Test | ||||||||||
| 1114226 | YCH-ST2 | ST2-SLOP TANK 2 | BULK STORAGE | MV-Ball Valves | 362 | YCH-ST2-BLVL-175367 | YCH00565 | Ball valve located inside the slop tank vault on the tank inlet. (Valve 362) | X | Section 6-6.2.4 | Notify Facility | |||||||||
| 1114226 | YCH-ST2 | ST2-SLOP TANK 2 | BULK STORAGE | MV-Ball Valves | YCH-ST2-BLVL-177815 | YCH00566 | Ball valve located inside the slop tank vault for the Camlock connection. | X | Section 6-6.2.4 | Notify Facility | ||||||||||
| 1114226 | YCH-ST2 | ST2-SLOP TANK 2 | BULK STORAGE | TK-Underground Double-Walled Shop-Fabricated Tanks | ST 2 | YCH-ST2-UGDSFT-174920 | YCH00567 | Slop tank 2 located inside the vault | X | Section 8-5.4.2 | ||||||||||
| 1114226 | YCH-ST2 | ST2-SLOP TANK 2 | BULK STORAGE | MV-Ball Valves | YCH-ST2-BLVL-175368 | YCH00568 | Sight glass drain valve bottom side | X | Section 6-6.2.4 | Notify Facility | ||||||||||
| 1114226 | YCH-ST2 | ST2-SLOP TANK 2 | BULK STORAGE | MV-Gate Valves | YCH-ST2-GTVL-177817 | YCH00569 | Sight glass isolation gate valve top side | X | X | Section 6-6.2.3 | Notify Facility | |||||||||
| 1114226 | YCH-ST2 | ST2-SLOP TANK 2 | BULK STORAGE | MV-Gate Valves | YCH-ST2-GTVL-177818 | YCH00570 | Sight glass isolation gate valve bottom side | X | X | Section 6-6.2.3 | Notify Facility | |||||||||
| 1114226 | YCH-ST2 | ST2-SLOP TANK 2 | BULK STORAGE | CS-Self-Diking or Vaulted Tank Containment | YCH-ST2-SDVTCS-174777 | YCH00571 | Vault for slop tank | Section 8-10.4 | ||||||||||||
| 1114226 | YCH-ST2 | ST2-SLOP TANK 2 | BULK STORAGE | PC-Aboveground Piping and Equipment Coating | YCH-ST2-AGPCT-174921 | YCH00574 | Coated piping 2 inch inside slop tank vault | Section 6-10.1 | ||||||||||||
| 1114226 | YCH-ST2 | ST2-SLOP TANK 2 | BULK STORAGE | PC-Aboveground Piping and Equipment Coating | YCH-ST2-AGPCT-174778 | YCH00576 | Coated piping 3 inch inside slop tank vault | Section 6-10.1 | ||||||||||||
| 1114226 | YCH-ST2 | ST2-SLOP TANK 2 | BULK STORAGE | EQ-Air Vent | YCH-ST2-ASSET-177820 | YCH00577 | Goose neck style air vent next to tank vault lid | Non-Appx G Class | ||||||||||||
| 11180 | YCH-Y1 | Y1-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | TD-Miscellaneous Deactivated Components | YCH-Y1-MDEAC-177847 | YCH00730 | Tank Y1 is out of service for an undetermined amount of time | X | Section 12-5 | |||||||||||
| 11181 | YCH-Y2 | Y2-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | MV-Ball Valves | YCH-Y2-BLVL-174811 | YCH00731 | Located on the 1/2 line for the tank high-level shut off | X | Section 6-6.2.4 | Notify Facility; Confined Space | Confined Space- | |||||||||
| 11181 | YCH-Y2 | Y2-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | MV-Ball Valves | YCH-Y2-BLVL-174813 | YCH00732 | 1/2-inch isolation ball valve for the pressure gauge located on the outlet side of pump M2A | X | Section 6-6.2.4 | Notify Facility; Confined Space | Confined Space- | |||||||||
| 11181 | YCH-Y2 | Y2-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | MV-Ball Valves | YCH-Y2-BLVL-177848 | YCH00733 | 1/2-inch isolation ball valve for the pressure gauge located on the outlet side of pump M2B | X | Section 6-6.2.4 | Notify Facility; Confined Space | Confined Space- | |||||||||
| 11181 | YCH-Y2 | Y2-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | MV-Ball Valves | 124 | YCH-Y2-BLVL-174970 | YCH00734 | Located on the 2 inch line for sump pump M2C. (Valve 124) | X | Section 6-6.2.4 | Notify Facility; Confined Space | Confined Space- | ||||||||
| 11181 | YCH-Y2 | Y2-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | MV-Ball Valves | 125 | YCH-Y2-BLVL-174816 | YCH00739 | Located on the PRT piping from sump (second in line). (Valve 125) | X | Section 6-6.2.4 | Notify Facility; Confined Space | Confined Space- | ||||||||
| 11181 | YCH-Y2 | Y2-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | CV-General System Control Valves | A 9 | YCH-Y2-GSCVL-168042 | YCH00740 | 2-inch control valve located on the discharge line for sump pump M2C. (Valve A-9) | Cla-Val | X | X | Section 4-3.2.1 | Operate System to Test; Confined Space | Confined Space- | ||||||
| 11181 | YCH-Y2 | Y2-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | CV-General System Control Valves | A 5 | YCH-Y2-GSCVL-168047 | YCH00742 | 6-inch control valve located on the discharge line for issue pump M2A. (Valve A-5) | Cla-Val | X | X | Section 4-3.2.1 | Operate System to Test; Confined Space | Confined Space- | ||||||
| 11181 | YCH-Y2 | Y2-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | CV-General System Control Valves | A 6 | YCH-Y2-GSCVL-168050 | YCH00743 | 6-inch control valve located on the discharge line for issue pump M2B. (Valve A-6) | Cla-Val | X | X | Section 4-3.2.1 | Operate System to Test; Confined Space | Confined Space- | ||||||
| 11181 | YCH-Y2 | Y2-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | CV-General System Control Valves | YCH-Y2-GSCVL-168052 | YCH00744 | 6-inch control valve located on the return line. | Cla-Val | X | X | Section 4-3.2.1 | Operate System to Test; Confined Space | Confined Space- | |||||||
| 11181 | YCH-Y2 | Y2-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | MV-Gate Valves | 126 | YCH-Y2-GTVL-175384 | YCH00745 | Located on the piping from the side of the PRT. (Valve 126) | X | X | Section 6-6.2.3 | Notify Facility; Confined Space | Confined Space- | |||||||
| 11181 | YCH-Y2 | Y2-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | TA-Tank Pressure/Vacuum Vents | YCH-Y2-TPVVT-174972 | YCH00749 | Located inside tank vault near the entrance | Varec | 202051 | X | Section 8-9.3 | Notify Facility | Confined Space- | |||||||
| 11181 | YCH-Y2 | Y2-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | TA-Tank Pressure/Vacuum Vents | YCH-Y2-TPVVT-175385 | YCH00750 | Located inside tank vault across from the entrance | Varec | 202051 | X | Section 8-9.3 | Notify Facility | Confined Space- | |||||||
| 11181 | YCH-Y2 | Y2-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | PM-Vertical Turbine/Sub-merged Turbine Pumps | M2A | YCH-Y2-VTSP-174973 | YCH00751 | Issue pump M2A located inside vault | Peabody Floway | Type DKH | X | X | X | Section 3-8.1.3 / 3-8.3 | Operate System to Test; Confined Space | Confined Space- | 600 gpm | |||
| 11181 | YCH-Y2 | Y2-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | PM-Vertical Turbine/Sub-merged Turbine Pumps | M2B | YCH-Y2-VTSP-174975 | YCH00752 | Issue pump M2B located inside vault | Peabody Floway | Type DKH | X | X | X | Section 3-8.1.3 / 3-8.3 | Operate System to Test; Confined Space | Confined Space- | 600 gpm | |||
| 11181 | YCH-Y2 | Y2-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | PM-Vertical Turbine/Sub-merged Turbine Pumps | M2C | YCH-Y2-VTSP-175386 | YCH00753 | Sump pump M2C located inside vault | Peabody Floway | Type XKL | X | X | X | Section 3-8.1.3 / 3-8.3 | Operate System to Test; Confined Space | Confined Space- | 50 gpm | |||
| 11181 | YCH-Y2 | Y2-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | TK-Underground Field-Constructed Tanks | Y2 | YCH-Y2-UGFET-177849 | YCH00754 | Tank Y2 | X | Section 8-6 | Confined Space- | |||||||||
| 11181 | YCH-Y2 | Y2-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | PS-Product Saver Tanks | YCH-Y2-PRDST-177850 | YCH00755 | PST located on top of the tank | X | Section 8-9.10 | Notify Facility | Confined Space- | |||||||||
| 11181 | YCH-Y2 | Y2-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | TA-Mechanical Tape Gauges (non-ATG) | YCH-Y2-MTGA-164486 | YCH00756 | Fuel tank gauge located inside vault | Varec | MODEL B | X | Section 8-9.7 | Confined Space- | ||||||||
| 11181 | YCH-Y2 | Y2-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | TA-Mechanical Tape Gauges (non-ATG) | YCH-Y2-MTGA-164487 | YCH00757 | Water tank gauge located inside vault | Varec | MODEL B | X | Section 8-9.7 | Confined Space- | ||||||||
| 11181 | YCH-Y2 | Y2-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | MV-Ball Valves | YCH-Y2-BLVL-177851 | YCH00758 | Ball valve located on the PRT piping from sump (first in line) | X | Section 6-6.2.4 | Notify Facility; Confined Space | Confined Space- | |||||||||
| 11181 | YCH-Y2 | Y2-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | MV-Gate Valves | 127 | YCH-Y2-GTVL-174977 | YCH00759 | Gate valve located at the bottom of the PRT to the slop tank. (Valve 127) | X | X | Section 6-6.2.3 | Notify Facility; Confined Space | Confined Space- | |||||||
| 11181 | YCH-Y2 | Y2-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | PC-Aboveground Piping and Equipment Coating | YCH-Y2-AGPCT-175387 | YCH00761 | Coated piping 10 inch | Section 6-10.1 | Confined Space- | |||||||||||
| 11181 | YCH-Y2 | Y2-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | PC-Aboveground Piping and Equipment Coating | YCH-Y2-AGPCT-174728 | YCH00762 | Coated piping 8 inch | Section 6-10.1 | Confined Space- | |||||||||||
| 11181 | YCH-Y2 | Y2-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | PC-Aboveground Piping and Equipment Coating | YCH-Y2-AGPCT-174983 | YCH00763 | Coated piping 6 inch | Section 6-10.1 | Confined Space- | |||||||||||
| 11181 | YCH-Y2 | Y2-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | PC-Aboveground Piping and Equipment Coating | YCH-Y2-AGPCT-174819 | YCH00764 | Coated piping 2 inch | Section 6-10.1 | Confined Space- | |||||||||||
| 11181 | YCH-Y2 | Y2-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | EC-EFSO-Elec Equip | YCH-Y2-EFSO-174822 | YCH00765 | EFSO located at the top of the tank stairs | X | Section 9-1.2 | Operate System to Test | Confined Space- | |||||||||
| 11181 | YCH-Y2 | Y2-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | TA-External High Level Shutoff Valves (HLSO) | YCH-Y2-EHLSVL-177852 | YCH00770 | High-level shut off valve | X | X | Section 8-9.6.1 | Notify Facility | Confined Space- | ||||||||
| 11181 | YCH-Y2 | Y2-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | PV-Pressure Gauges | YCH-Y2-PVGA-174984 | YCH00771 | Pressure gauge located on the outlet side of pump M2A | X | X | X | Section 6-7.1 | Notify Facility | Confined Space- | |||||||
| 11181 | YCH-Y2 | Y2-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | PV-Pressure Gauges | YCH-Y2-PVGA-174985 | YCH00772 | Pressure gauge located on the outlet side of pump M2B | Ashcroft | X | X | X | Section 6-7.1 | Notify Facility | Confined Space- | ||||||
| 11182 | YCH-Y3 | Y3-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | MV-Ball Valves | 134 | YCH-Y3-BLVL-177853 | YCH00773 | Located on the 2 inch PRT issue line. (Valve 134) | X | Section 6-6.2.4 | Notify Facility; Confined Space | Confined Space- | ||||||||
| 11182 | YCH-Y3 | Y3-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | MV-Ball Valves | 135 | YCH-Y3-BLVL-177854 | YCH00774 | Located on the 2 inch PRT return line to the tank. (Valve 135) | X | Section 6-6.2.4 | Notify Facility; Confined Space | Confined Space- | ||||||||
| 11182 | YCH-Y3 | Y3-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | MV-Ball Valves | 136 | YCH-Y3-BLVL-177855 | YCH00775 | Located on the 2 inch PRT line to the slop tank. (Valve 136) | X | Section 6-6.2.4 | Notify Facility; Confined Space | Confined Space- | ||||||||
| 11182 | YCH-Y3 | Y3-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | MV-Ball Valves | 137 | YCH-Y3-BLVL-177856 | YCH00776 | Located on the 2 inch PRT crossover line. (Valve 137) | X | Section 6-6.2.4 | Notify Facility; Confined Space | Confined Space- | ||||||||
| 11182 | YCH-Y3 | Y3-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | MV-Ball Valves | 139 | YCH-Y3-BLVL-174986 | YCH00778 | 3/4-inch ball valve located on top of the HLSO control valve. | X | Section 6-6.2.4 | Notify Facility; Confined Space | Confined Space- | ||||||||
| 11182 | YCH-Y3 | Y3-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | MV-Ball Valves | 140 | YCH-Y3-BLVL-174804 | YCH00779 | Located on the PRT return line inside the tank vault. (Valve 140) | X | Section 6-6.2.4 | Notify Facility; Confined Space | Confined Space- | ||||||||
| 11182 | YCH-Y3 | Y3-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | MV-Ball Valves | 141 | YCH-Y3-BLVL-177857 | YCH00780 | Located on the sump pump discharge line. (Valve 141) | X | Section 6-6.2.4 | Notify Facility; Confined Space | Confined Space- | ||||||||
| 11182 | YCH-Y3 | Y3-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | MV-Check Valves | YCH-Y3-CKVL-174806 | YCH00781 | Located on the sump pump line | X | Section 6-6.2.8 | Notify Facility; Confined Space | Confined Space- | |||||||||
| 11182 | YCH-Y3 | Y3-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | CV-General System Control Valves | YCH-Y3-GSCVL-168054 | YCH00782 | 6-inch control valve located on the return line. | X | X | Section 4-3.2.1 | Operate System to Test; Confined Space | Confined Space- | ||||||||
| 11182 | YCH-Y3 | Y3-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | TA-Tank Pressure/Vacuum Vents | YCH-Y3-TPVVT-177858 | YCH00785 | Located inside vault near the entrance | Shand & Jurs | X | Section 8-9.3 | Notify Facility | Confined Space- | ||||||||
| 11182 | YCH-Y3 | Y3-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | TA-Tank Pressure/Vacuum Vents | YCH-Y3-TPVVT-177859 | YCH00786 | Located inside vault across from the entrance | Shand & Jurs | X | Section 8-9.3 | Notify Facility | Confined Space- | ||||||||
| 11182 | YCH-Y3 | Y3-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | PM-Vertical Turbine/Sub-merged Turbine Pumps | M3A | YCH-Y3-VTSP-174987 | YCH00787 | Issue pump M3A located inside vault | Layne & Bowler | X | X | X | Section 3-8.1.3 / 3-8.3 | Operate System to Test; Confined Space | Confined Space- | 600 gpm | ||||
| 11182 | YCH-Y3 | Y3-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | PM-Vertical Turbine/Sub-merged Turbine Pumps | M3B | YCH-Y3-VTSP-174988 | YCH00788 | Issue pump M3B located inside vault | Layne & Bowler | X | X | X | Section 3-8.1.3 / 3-8.3 | Operate System to Test; Confined Space | Confined Space- | 600 gpm | ||||
| 11182 | YCH-Y3 | Y3-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | PM-Vertical Turbine/Sub-merged Turbine Pumps | M3C | YCH-Y3-VTSP-174808 | YCH00789 | Sump pump M3C located inside vault | Layne & Bowler | X | X | X | Section 3-8.1.3 / 3-8.3 | Operate System to Test; Confined Space | Confined Space- | |||||
| 11182 | YCH-Y3 | Y3-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | TK-Underground Field-Constructed Tanks | Y3 | YCH-Y3-UGFET-174729 | YCH00790 | Tank Y3 | X | Section 8-6 | Confined Space- | |||||||||
| 11182 | YCH-Y3 | Y3-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | PS-Product Saver Tanks | YCH-Y3-PRDST-177860 | YCH00791 | PRT located on top of the tank | X | Section 8-9.10 | Notify Facility | Confined Space- | |||||||||
| 11182 | YCH-Y3 | Y3-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | TA-Mechanical Tape Gauges (non-ATG) | YCH-Y3-MTGA-164488 | YCH00792 | Fuel tank gauge located inside vault | Shand & Jurs | X | Section 8-9.7 | Confined Space- | |||||||||
| 11182 | YCH-Y3 | Y3-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | TA-Mechanical Tape Gauges (non-ATG) | YCH-Y3-MTGA-164489 | YCH00793 | Water tank gauge located inside vault | Shand & Jurs | X | Section 8-9.7 | Confined Space- | |||||||||
| 11182 | YCH-Y3 | Y3-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | MV-Ball Valves | YCH-Y3-BLVL-177861 | YCH00797 | 3/8-inch Isolation ball valve for the pressure gauge located on the outlet side of pump M3B | X | Section 6-6.2.4 | Notify Facility; Confined Space | Confined Space- | |||||||||
| 11182 | YCH-Y3 | Y3-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | MV-Check Valves | YCH-Y3-CKVL-177862 | YCH00798 | Check valve located on M3A issue line | X | Section 6-6.2.8 | Notify Facility; Confined Space | Confined Space- | |||||||||
| 11182 | YCH-Y3 | Y3-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | MV-Check Valves | YCH-Y3-CKVL-177863 | YCH00799 | Check valve located on M3B issue line | X | Section 6-6.2.8 | Notify Facility; Confined Space | Confined Space- | |||||||||
| 11182 | YCH-Y3 | Y3-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | CV-General System Control Valves | YCH-Y3-GSCVL-168056 | YCH00800 | Control valve located on the receipt line | X | X | Section 4-3.2.1 | Operate System to Test; Confined Space | Confined Space- | ||||||||
| 11182 | YCH-Y3 | Y3-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | PC-Aboveground Piping and Equipment Coating | YCH-Y3-AGPCT-174730 | YCH00803 | Coated piping 10 in | Section 6-10.1 | Confined Space- | |||||||||||
| 11182 | YCH-Y3 | Y3-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | PC-Aboveground Piping and Equipment Coating | YCH-Y3-AGPCT-174810 | YCH00804 | Coated piping 8 in | Section 6-10.1 | Confined Space- | |||||||||||
| 11182 | YCH-Y3 | Y3-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | PC-Aboveground Piping and Equipment Coating | YCH-Y3-AGPCT-174812 | YCH00805 | Coated piping 6 in | Section 6-10.1 | Confined Space- | |||||||||||
| 11182 | YCH-Y3 | Y3-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | PC-Aboveground Piping and Equipment Coating | YCH-Y3-AGPCT-177864 | YCH00806 | Coated piping 2 in | Section 6-10.1 | Confined Space- | |||||||||||
| 11182 | YCH-Y3 | Y3-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | PV-Pressure Gauges | YCH-Y3-PVGA-177865 | YCH00810 | Pressure gauge located on the outlet side of pump M3A | Ashcroft | X | X | X | Section 6-7.1 | Notify Facility | Confined Space- | ||||||
| 11182 | YCH-Y3 | Y3-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | PV-Pressure Gauges | YCH-Y3-PVGA-174814 | YCH00811 | Pressure gauge located on the outlet side of pump M3B | Ashcroft | X | X | X | Section 6-7.1 | Notify Facility | Confined Space- | ||||||
| 11182 | YCH-Y3 | Y3-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | TA-External High Level Shutoff Valves (HLSO) | YCH-Y3-EHLSVL-174815 | YCH00812 | High-level shut off valve | X | X | Section 8-9.6.1 | Notify Facility | Confined Space- | ||||||||
| 11183 | YCH-Y4 | Y4-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | MV-Ball Valves | 207 | YCH-Y4-BLVL-174817 | YCH00813 | 2-inch ball valve located on the PRT issue line. (Valve 207) | X | Section 6-6.2.4 | Notify Facility; Confined Space | Confined Space- | ||||||||
| 11183 | YCH-Y4 | Y4-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | MV-Ball Valves | 208 | YCH-Y4-BLVL-174989 | YCH00814 | 2-inch ball valve located on the PRT return line. (Valve 208) | X | Section 6-6.2.4 | Notify Facility; Confined Space | Confined Space- | ||||||||
| 11183 | YCH-Y4 | Y4-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | MV-Ball Valves | 209 | YCH-Y4-BLVL-174990 | YCH00815 | 2-inch ball valve located on the PRT crossover line. (Valve 209) | X | Section 6-6.2.4 | Notify Facility; Confined Space | Confined Space- | ||||||||
| 11183 | YCH-Y4 | Y4-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | MV-Ball Valves | YCH-Y4-BLVL-174731 | YCH00816 | 2-inch ball valve located on the PRT line to the slop tank. | X | Section 6-6.2.4 | Notify Facility; Confined Space | Confined Space- | |||||||||
| 11183 | YCH-Y4 | Y4-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | MV-Ball Valves | 205 | YCH-Y4-BLVL-174991 | YCH00817 | 2-inch ball valve located on the PRT return line inside the tank vault. (Valve 205) | X | Section 6-6.2.4 | Notify Facility; Confined Space | Confined Space- | ||||||||
| 11183 | YCH-Y4 | Y4-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | MV-Ball Valves | 203 | YCH-Y4-BLVL-177866 | YCH00818 | 2-inc ball valve located on the sump pump discharge line. (Valve 203) | X | Section 6-6.2.4 | Notify Facility; Confined Space | Confined Space- | ||||||||
| 11183 | YCH-Y4 | Y4-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | MV-Ball Valves | 206 | YCH-Y4-BLVL-174818 | YCH00819 | 3/4-inch bal valve located on top of the HLSO control valve. | X | Section 6-6.2.4 | Notify Facility; Confined Space | Confined Space- | ||||||||
| 11183 | YCH-Y4 | Y4-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | MV-Check Valves | YCH-Y4-CKVL-174992 | YCH00822 | 8-inch check valve located on the discharge line for issue pump MS4A. | X | Section 6-6.2.8 | Notify Facility; Confined Space | Confined Space- | |||||||||
| 11183 | YCH-Y4 | Y4-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | MV-Check Valves | YCH-Y4-CKVL-174993 | YCH00823 | 2-inch check valve located on the sump pump discharge line. | X | Section 6-6.2.8 | Notify Facility; Confined Space | Confined Space- | |||||||||
| 11183 | YCH-Y4 | Y4-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | CV-General System Control Valves | YCH-Y4-GSCVL-168058 | YCH00824 | Located on the 6 inch receipt line | X | X | Section 4-3.2.1 | Operate System to Test; Confined Space | Confined Space- | ||||||||
| 11183 | YCH-Y4 | Y4-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | CV-General System Control Valves | YCH-Y4-GSCVL-168061 | YCH00825 | 6-inch control valve located on the return line. | X | X | Section 4-3.2.1 | Operate System to Test; Confined Space | Confined Space- | ||||||||
| 11183 | YCH-Y4 | Y4-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | TA-Tank Pressure/Vacuum Vents | YCH-Y4-TPVVT-174732 | YCH00828 | Located inside vault near the entrance | Shand & Jurs | X | Section 8-9.3 | Notify Facility | Confined Space- | ||||||||
| 11183 | YCH-Y4 | Y4-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | TA-Tank Pressure/Vacuum Vents | YCH-Y4-TPVVT-174994 | YCH00829 | Located inside vault across from the entrance | Shand & Jurs | X | Section 8-9.3 | Notify Facility | Confined Space- | ||||||||
| 11183 | YCH-Y4 | Y4-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | PM-Vertical Turbine/Sub-merged Turbine Pumps | M4A | YCH-Y4-VTSP-175045 | YCH00830 | Issue pump M4A located inside vault | Layne & Bowler | X | X | X | Section 3-8.1.3 / 3-8.3 | Operate System to Test; Confined Space | Confined Space- | 600 gpm | ||||
| 11183 | YCH-Y4 | Y4-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | PM-Vertical Turbine/Sub-merged Turbine Pumps | M4B | YCH-Y4-VTSP-177867 | YCH00831 | Sump pump M4B located inside vault | Layne & Bowler | X | X | X | Section 3-8.1.3 / 3-8.3 | Operate System to Test; Confined Space | Confined Space- | |||||
| 11183 | YCH-Y4 | Y4-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | TK-Underground Field-Constructed Tanks | Y4 | YCH-Y4-UGFET-174733 | YCH00832 | Tank Y4 | X | Section 8-6 | Confined Space- | |||||||||
| 11183 | YCH-Y4 | Y4-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | PS-Product Saver Tanks | YCH-Y4-PRDST-174734 | YCH00833 | PRT located on top of the tank | X | Section 8-9.10 | Notify Facility | Confined Space- | |||||||||
| 11183 | YCH-Y4 | Y4-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | TA-Mechanical Tape Gauges (non-ATG) | YCH-Y4-MTGA-164490 | YCH00834 | Fuel tank gauge located inside vault | Shand & Jurs | X | Section 8-9.7 | Confined Space- | |||||||||
| 11183 | YCH-Y4 | Y4-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | TA-Mechanical Tape Gauges (non-ATG) | YCH-Y4-MTGA-164491 | YCH00835 | Water tank gauge located inside vault | Shand & Jurs | X | Section 8-9.7 | Confined Space- | |||||||||
| 11183 | YCH-Y4 | Y4-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | TA-External High Level Shutoff Valves (HLSO) | YCH-Y4-EHLSVL-177868 | YCH00836 | High-level shut off valve | X | X | Section 8-9.6.1 | Notify Facility | Confined Space- | ||||||||
| 11183 | YCH-Y4 | Y4-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | PV-Pressure Gauges | YCH-Y4-PVGA-174820 | YCH00838 | Pressure gauge located on the outlet of pump M4A | Ashcroft | X | X | X | Section 6-7.1 | Notify Facility | Confined Space- | ||||||
| 11183 | YCH-Y4 | Y4-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | PC-Aboveground Piping and Equipment Coating | YCH-Y4-AGPCT-174735 | YCH00839 | Coated piping 10 in | Section 6-10.1 | Confined Space- | |||||||||||
| 11183 | YCH-Y4 | Y4-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | PC-Aboveground Piping and Equipment Coating | YCH-Y4-AGPCT-177869 | YCH00840 | Coated piping 6 in | Section 6-10.1 | Confined Space- | |||||||||||
| 11183 | YCH-Y4 | Y4-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | PC-Aboveground Piping and Equipment Coating | YCH-Y4-AGPCT-174821 | YCH00841 | Coated piping 2 inch | Section 6-10.1 | Confined Space- | |||||||||||
| 11184 | YCH-Y5 | Y5-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | MV-Ball Valves | 217 | YCH-Y5-BLVL-175049 | YCH00844 | 2-inch ball valve located on the PRT issue line. (Valve 217) | X | Section 6-6.2.4 | Notify Facility; Confined Space | Confined Space- | ||||||||
| 11184 | YCH-Y5 | Y5-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | MV-Ball Valves | 218 | YCH-Y5-BLVL-175052 | YCH00845 | 2-inch ball valve located on the PRT return line. (Valve 218) | X | Section 6-6.2.4 | Notify Facility; Confined Space | Confined Space- | ||||||||
| 11184 | YCH-Y5 | Y5-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | MV-Ball Valves | 219 | YCH-Y5-BLVL-174736 | YCH00846 | 2-inch ball valve located on the PRT crossover line. (Valve 219) | X | Section 6-6.2.4 | Notify Facility; Confined Space | Confined Space- | ||||||||
| 11184 | YCH-Y5 | Y5-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | MV-Ball Valves | 220 | YCH-Y5-BLVL-175055 | YCH00847 | 2-inch ball valve located on the PRT line to the slop tank. (Valve 220) | X | Section 6-6.2.4 | Notify Facility; Confined Space | Confined Space- | ||||||||
| 11184 | YCH-Y5 | Y5-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | MV-Ball Valves | 213 | YCH-Y5-BLVL-175059 | YCH00848 | 2-inch ball valve located on the sump pump discharge line. (Valve 213) | X | Section 6-6.2.4 | Notify Facility; Confined Space | Confined Space- | ||||||||
| 11184 | YCH-Y5 | Y5-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | MV-Ball Valves | 215 | YCH-Y5-BLVL-174823 | YCH00849 | 2-inch ball valve located on the PRT return line inside the tank vault. (Valve 215) | X | Section 6-6.2.4 | Notify Facility; Confined Space | Confined Space- | ||||||||
| 11184 | YCH-Y5 | Y5-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | MV-Ball Valves | 216 | YCH-Y5-BLVL-177870 | YCH00850 | 3/4-inch ball valve located on top of the HLSO control valve. | X | Section 6-6.2.4 | Notify Facility; Confined Space | Confined Space- | ||||||||
| 11184 | YCH-Y5 | Y5-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | MV-Check Valves | YCH-Y5-CKVL-175062 | YCH00854 | 2-inch check valve located on the sump pump discharge line. | X | Section 6-6.2.8 | Notify Facility; Confined Space | Confined Space- | |||||||||
| 11184 | YCH-Y5 | Y5-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | CV-General System Control Valves | YCH-Y5-GSCVL-168064 | YCH00855 | 6-inch control valve located on the return line. | X | X | Section 4-3.2.1 | Operate System to Test; Confined Space | Confined Space- | ||||||||
| 11184 | YCH-Y5 | Y5-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | CV-General System Control Valves | YCH-Y5-GSCVL-168066 | YCH00856 | Located on the 6 inch receipt line | X | X | Section 4-3.2.1 | Operate System to Test; Confined Space | Confined Space- | ||||||||
| 11184 | YCH-Y5 | Y5-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | TA-Tank Pressure/Vacuum Vents | YCH-Y5-TPVVT-174824 | YCH00859 | Located inside vault near the entrance | Shand & Jurs | X | Section 8-9.3 | Notify Facility | Confined Space- | ||||||||
| 11184 | YCH-Y5 | Y5-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | TA-Tank Pressure/Vacuum Vents | YCH-Y5-TPVVT-174860 | YCH00860 | Located inside vault across from the entrance | Shand & Jurs | X | Section 8-9.3 | Notify Facility | Confined Space- | ||||||||
| 11184 | YCH-Y5 | Y5-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | PM-Vertical Turbine/Sub-merged Turbine Pumps | M5A | YCH-Y5-VTSP-177871 | YCH00861 | Issue pump M5A located inside vault | Layne & Bowler | X | X | X | Section 3-8.1.3 / 3-8.3 | Operate System to Test; Confined Space | Confined Space- | 600 gpm | ||||
| 11184 | YCH-Y5 | Y5-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | PM-Vertical Turbine/Sub-merged Turbine Pumps | M5B | YCH-Y5-VTSP-177872 | YCH00862 | Issue pump M5B located inside vault | Layne & Bowler | X | X | X | Section 3-8.1.3 / 3-8.3 | Operate System to Test; Confined Space | Confined Space- | 600 gpm | ||||
| 11184 | YCH-Y5 | Y5-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | PM-Vertical Turbine/Sub-merged Turbine Pumps | M5C | YCH-Y5-VTSP-177873 | YCH00863 | Sump pump M5C located inside vault | Layne & Bowler | X | X | X | Section 3-8.1.3 / 3-8.3 | Operate System to Test; Confined Space | Confined Space- | |||||
| 11184 | YCH-Y5 | Y5-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | TK-Underground Field-Constructed Tanks | Y5 | YCH-Y5-UGFET-174737 | YCH00864 | Tank Y5 | X | Section 8-6 | Confined Space- | |||||||||
| 11184 | YCH-Y5 | Y5-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | PS-Product Saver Tanks | YCH-Y5-PRDST-174738 | YCH00865 | PRT located on top of the tank | X | Section 8-9.10 | Notify Facility | Confined Space- | |||||||||
| 11184 | YCH-Y5 | Y5-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | TA-Mechanical Tape Gauges (non-ATG) | YCH-Y5-MTGA-164492 | YCH00866 | Fuel tank gauge located inside vault | Shand & Jurs | X | Section 8-9.7 | Confined Space- | |||||||||
| 11184 | YCH-Y5 | Y5-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | TA-Mechanical Tape Gauges (non-ATG) | YCH-Y5-MTGA-164493 | YCH00867 | Water tank gauge located inside vault | Shand & Jurs | X | Section 8-9.7 | Confined Space- | |||||||||
| 11184 | YCH-Y5 | Y5-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | MV-Check Valves | YCH-Y5-CKVL-177874 | YCH00869 | 8-inch check valve located on the discharge line for issue pump M5A. | X | Section 6-6.2.8 | Notify Facility; Confined Space | Confined Space- | |||||||||
| 11184 | YCH-Y5 | Y5-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | MV-Check Valves | YCH-Y5-CKVL-175065 | YCH00870 | 8-inch check valve located on the discharge line for issue pump M5B. | X | Section 6-6.2.8 | Notify Facility; Confined Space | Confined Space- | |||||||||
| 11184 | YCH-Y5 | Y5-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | PC-Aboveground Piping and Equipment Coating | YCH-Y5-AGPCT-174739 | YCH00872 | Coated piping 10 in | Section 6-10.1 | Confined Space- | |||||||||||
| 11184 | YCH-Y5 | Y5-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | PC-Aboveground Piping and Equipment Coating | YCH-Y5-AGPCT-174740 | YCH00873 | Coated piping 6 in | Section 6-10.1 | Confined Space- | |||||||||||
| 11184 | YCH-Y5 | Y5-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | PC-Aboveground Piping and Equipment Coating | YCH-Y5-AGPCT-174861 | YCH00874 | Coated piping 2 inch | Section 6-10.1 | Confined Space- | |||||||||||
| 11184 | YCH-Y5 | Y5-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | PV-Pressure Gauges | YCH-Y5-PVGA-174862 | YCH00875 | Pressure gauge located on the outlet of pump M5A | Ashcroft | X | X | X | Section 6-7.1 | Notify Facility | Confined Space- | ||||||
| 11184 | YCH-Y5 | Y5-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | PV-Pressure Gauges | YCH-Y5-PVGA-177875 | YCH00876 | Pressure gauge located on the outlet side of pump M5B | Ashcroft | X | X | X | Section 6-7.1 | Notify Facility | Confined Space- | ||||||
| 11184 | YCH-Y5 | Y5-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | TA-External High Level Shutoff Valves (HLSO) | YCH-Y5-EHLSVL-174863 | YCH00877 | High-level shut off valve | X | X | Section 8-9.6.1 | Notify Facility | Confined Space- | ||||||||
| 11185 | YCH-Y6 | Y6-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | MV-Ball Valves | 307 | YCH-Y6-BLVL-174741 | YCH00881 | 2-inch ball valve located on the PRT issue line. (Valve 307) | X | Section 6-6.2.4 | Notify Facility; Confined Space | Confined Space- | ||||||||
| 11185 | YCH-Y6 | Y6-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | MV-Ball Valves | 308 | YCH-Y6-BLVL-174742 | YCH00882 | 2-inch ball valve located on the PRT return line. (Valve 308) | X | Section 6-6.2.4 | Notify Facility; Confined Space | Confined Space- | ||||||||
| 11185 | YCH-Y6 | Y6-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | MV-Ball Valves | 309 | YCH-Y6-BLVL-174743 | YCH00883 | 2-inch ball valve located on the PRT crossover line. (Valve 309) | X | Section 6-6.2.4 | Notify Facility; Confined Space | Confined Space- | ||||||||
| 11185 | YCH-Y6 | Y6-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | MV-Ball Valves | 310 | YCH-Y6-BLVL-174864 | YCH00884 | 2-inch ball valve located on the PRT line to the slop tank. (Valve 310) | X | Section 6-6.2.4 | Notify Facility; Confined Space | Confined Space- | ||||||||
| 11185 | YCH-Y6 | Y6-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | MV-Ball Valves | 305 | YCH-Y6-BLVL-174865 | YCH00885 | 2-inch ball valve located on the PRT return line inside the tank vault. (Valve 305) | X | Section 6-6.2.4 | Notify Facility; Confined Space | Confined Space- | ||||||||
| 11185 | YCH-Y6 | Y6-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | MV-Ball Valves | 303 | YCH-Y6-BLVL-177876 | YCH00886 | 2-inch ball valve located on the sump pump discharge line inside the tank vault. (Valve 303) | X | Section 6-6.2.4 | Notify Facility; Confined Space | Confined Space- | ||||||||
| 11185 | YCH-Y6 | Y6-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | MV-Ball Valves | 306 | YCH-Y6-BLVL-174866 | YCH00887 | 3/4-inch ball valve located on top of the HLSO control valve. | X | Section 6-6.2.4 | Notify Facility; Confined Space | Confined Space- | ||||||||
| 11185 | YCH-Y6 | Y6-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | MV-Check Valves | YCH-Y6-CKVL-174867 | YCH00891 | 8-inch check valve located on the discharge line for issue pump MS6A. | X | Section 6-6.2.8 | Notify Facility; Confined Space | Confined Space- | |||||||||
| 11185 | YCH-Y6 | Y6-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | CV-General System Control Valves | YCH-Y6-GSCVL-168069 | YCH00892 | Located on the 6 inch receipt line | X | X | Section 4-3.2.1 | Operate System to Test; Confined Space | Confined Space- | ||||||||
| 11185 | YCH-Y6 | Y6-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | CV-General System Control Valves | YCH-Y6-GSCVL-168071 | YCH00893 | 6-inch control valve located on the return line. | X | X | Section 4-3.2.1 | Operate System to Test; Confined Space | Confined Space- | ||||||||
| 11185 | YCH-Y6 | Y6-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | TA-Tank Pressure/Vacuum Vents | YCH-Y6-TPVVT-174744 | YCH00896 | Located inside vault near the entrance | Shand & Jurs | X | Section 8-9.3 | Notify Facility | Confined Space- | ||||||||
| 11185 | YCH-Y6 | Y6-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | TA-Tank Pressure/Vacuum Vents | YCH-Y6-TPVVT-175068 | YCH00897 | Located inside vault across from the entrance | Shand & Jurs | X | Section 8-9.3 | Notify Facility | Confined Space- | ||||||||
| 11185 | YCH-Y6 | Y6-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | PM-Vertical Turbine/Sub-merged Turbine Pumps | M6A | YCH-Y6-VTSP-177877 | YCH00898 | Issue pump M6A located inside vault | Layne & Bowler | X | X | X | Section 3-8.1.3 / 3-8.3 | Operate System to Test; Confined Space | Confined Space- | 600 gpm | ||||
| 11185 | YCH-Y6 | Y6-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | PM-Vertical Turbine/Sub-merged Turbine Pumps | M6B | YCH-Y6-VTSP-174868 | YCH00899 | Sump pump M6B located inside vault | Layne & Bowler | X | X | X | Section 3-8.1.3 / 3-8.3 | Operate System to Test; Confined Space | Confined Space- | |||||
| 11185 | YCH-Y6 | Y6-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | TK-Underground Field-Constructed Tanks | Y6 | YCH-Y6-UGFET-174869 | YCH00900 | Tank Y6 | X | Section 8-6 | Confined Space- | |||||||||
| 11185 | YCH-Y6 | Y6-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | PS-Product Saver Tanks | YCH-Y6-PRDST-175071 | YCH00901 | PRT located on top of the tank | X | Section 8-9.10 | Notify Facility | Confined Space- | |||||||||
| 11185 | YCH-Y6 | Y6-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | TA-Mechanical Tape Gauges (non-ATG) | YCH-Y6-MTGA-164494 | YCH00902 | Fuel tank gauge located inside vault | Shand & Jurs | X | Section 8-9.7 | Confined Space- | |||||||||
| 11185 | YCH-Y6 | Y6-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | TA-Mechanical Tape Gauges (non-ATG) | YCH-Y6-MTGA-164495 | YCH00903 | Water tank gauge located inside vault | Shand & Jurs | X | Section 8-9.7 | Confined Space- | |||||||||
| 11185 | YCH-Y6 | Y6-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | MV-Check Valves | YCH-Y6-CKVL-174870 | YCH00904 | 2-inch check valve located on the sump pump discharge line. | X | Section 6-6.2.8 | Notify Facility; Confined Space | Confined Space- | |||||||||
| 11185 | YCH-Y6 | Y6-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | TA-External High Level Shutoff Valves (HLSO) | YCH-Y6-EHLSVL-174745 | YCH00905 | High-level shut off valve | X | X | Section 8-9.6.1 | Notify Facility | Confined Space- | ||||||||
| 11185 | YCH-Y6 | Y6-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | PV-Pressure Gauges | YCH-Y6-PVGA-177878 | YCH00907 | Pressure gauge located on the outlet side of pump M6A | Ashcroft | X | X | X | Section 6-7.1 | Notify Facility | Confined Space- | ||||||
| 11185 | YCH-Y6 | Y6-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | PC-Aboveground Piping and Equipment Coating | YCH-Y6-AGPCT-174871 | YCH00908 | Coated piping 10 in | Section 6-10.1 | Confined Space- | |||||||||||
| 11185 | YCH-Y6 | Y6-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | PC-Aboveground Piping and Equipment Coating | YCH-Y6-AGPCT-174872 | YCH00909 | Coated piping 6 in | Section 6-10.1 | Confined Space- | |||||||||||
| 11185 | YCH-Y6 | Y6-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | PC-Aboveground Piping and Equipment Coating | YCH-Y6-AGPCT-175074 | YCH00910 | Coated piping 2 inch | Section 6-10.1 | Confined Space- | |||||||||||
| 11186 | YCH-Y7 | Y7-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | MV-Ball Valves | 320 | YCH-Y7-BLVL-175077 | YCH00913 | 2-inch ball valve located on the PRT issue line. (Valve 320) | X | Section 6-6.2.4 | Notify Facility; Confined Space | Confined Space- | ||||||||
| 11186 | YCH-Y7 | Y7-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | MV-Ball Valves | YCH-Y7-BLVL-175081 | YCH00914 | 2-inch ball valve located on the PRT return line. | X | Section 6-6.2.4 | Notify Facility; Confined Space | Confined Space- | |||||||||
| 11186 | YCH-Y7 | Y7-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | MV-Ball Valves | 309 | YCH-Y7-BLVL-174746 | YCH00915 | Located on the PRT crossover line | X | Section 6-6.2.4 | Notify Facility; Confined Space | Confined Space- | ||||||||
| 11186 | YCH-Y7 | Y7-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | MV-Ball Valves | YCH-Y7-BLVL-177879 | YCH00916 | 2-inch ball valve located on the PRT line to the slop tank. | X | Section 6-6.2.4 | Notify Facility; Confined Space | Confined Space- | |||||||||
| 11186 | YCH-Y7 | Y7-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | MV-Ball Valves | 316 | YCH-Y7-BLVL-175083 | YCH00919 | 3/4-inch ball valve located on top of the HLSO control valve. | X | Section 6-6.2.4 | Notify Facility; Confined Space | Confined Space- | ||||||||
| 11186 | YCH-Y7 | Y7-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | MV-Check Valves | YCH-Y7-CKVL-177880 | YCH00923 | 8-inch check valve located on the discharge line for issue pump MS7A. | X | Section 6-6.2.8 | Notify Facility; Confined Space | Confined Space- | |||||||||
| 11186 | YCH-Y7 | Y7-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | CV-General System Control Valves | YCH-Y7-GSCVL-168073 | YCH00924 | Located on the 6 inch receipt line | X | X | Section 4-3.2.1 | Operate System to Test; Confined Space | Confined Space- | ||||||||
| 11186 | YCH-Y7 | Y7-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | CV-General System Control Valves | YCH-Y7-GSCVL-168075 | YCH00925 | 6-inch control valve located on the return line. | X | X | Section 4-3.2.1 | Operate System to Test; Confined Space | Confined Space- | ||||||||
| 11186 | YCH-Y7 | Y7-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | TA-Tank Pressure/Vacuum Vents | YCH-Y7-TPVVT-177881 | YCH00928 | Located inside vault near the entrance | Shand & Jurs | X | Section 8-9.3 | Notify Facility | Confined Space- | ||||||||
| 11186 | YCH-Y7 | Y7-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | TA-Tank Pressure/Vacuum Vents | YCH-Y7-TPVVT-177882 | YCH00929 | Located inside vault across from the entrance | Shand & Jurs | X | Section 8-9.3 | Notify Facility | Confined Space- | ||||||||
| 11186 | YCH-Y7 | Y7-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | PM-Vertical Turbine/Sub-merged Turbine Pumps | M7A | YCH-Y7-VTSP-174873 | YCH00930 | Issue pump M7A located inside vault | Layne & Bowler | X | X | X | Section 3-8.1.3 / 3-8.3 | Operate System to Test; Confined Space | Confined Space- | 600 gpm | ||||
| 11186 | YCH-Y7 | Y7-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | PM-Vertical Turbine/Sub-merged Turbine Pumps | M7B | YCH-Y7-VTSP-175086 | YCH00931 | Sump pump M7B located inside vault | Layne & Bowler | X | X | X | Section 3-8.1.3 / 3-8.3 | Operate System to Test; Confined Space | Confined Space- | |||||
| 11186 | YCH-Y7 | Y7-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | TK-Underground Field-Constructed Tanks | Y7 | YCH-Y7-UGFET-175090 | YCH00932 | Tank Y7 | X | Section 8-6 | Confined Space- | |||||||||
| 11186 | YCH-Y7 | Y7-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | PS-Product Saver Tanks | YCH-Y7-PRDST-174874 | YCH00933 | PRT located on top of the tank | X | Section 8-9.10 | Notify Facility | Confined Space- | |||||||||
| 11186 | YCH-Y7 | Y7-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | TA-Mechanical Tape Gauges (non-ATG) | YCH-Y7-MTGA-164496 | YCH00934 | Fuel tank gauge located inside vault | Shand & Jurs | X | Section 8-9.7 | Confined Space- | |||||||||
| 11186 | YCH-Y7 | Y7-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | TA-Mechanical Tape Gauges (non-ATG) | YCH-Y7-MTGA-164497 | YCH00935 | Water tank gauge located inside vault | Shand & Jurs | X | Section 8-9.7 | Confined Space- | |||||||||
| 11186 | YCH-Y7 | Y7-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | MV-Check Valves | YCH-Y7-CKVL-175092 | YCH00936 | 2-inch check valve located on the sump pump discharge line. | X | Section 6-6.2.8 | Notify Facility; Confined Space | Confined Space- | |||||||||
| 11186 | YCH-Y7 | Y7-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | TA-External High Level Shutoff Valves (HLSO) | YCH-Y7-EHLSVL-177883 | YCH00937 | High-level shut off valve | X | X | Section 8-9.6.1 | Notify Facility | Confined Space- | ||||||||
| 11186 | YCH-Y7 | Y7-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | PV-Pressure Gauges | YCH-Y7-PVGA-174747 | YCH00939 | Pressure gauge located on the outlet side of pump M7A | Ashcroft | X | X | X | Section 6-7.1 | Notify Facility | Confined Space- | ||||||
| 11186 | YCH-Y7 | Y7-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | PC-Aboveground Piping and Equipment Coating | YCH-Y7-AGPCT-175095 | YCH00940 | Coated piping 10 in | Section 6-10.1 | Confined Space- | |||||||||||
| 11186 | YCH-Y7 | Y7-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | PC-Aboveground Piping and Equipment Coating | YCH-Y7-AGPCT-177884 | YCH00941 | Coated piping 6 in | Section 6-10.1 | Confined Space- | |||||||||||
| 11186 | YCH-Y7 | Y7-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | PC-Aboveground Piping and Equipment Coating | YCH-Y7-AGPCT-177885 | YCH00942 | Coated piping 2 inch | Section 6-10.1 | Confined Space- | |||||||||||
| 1114225 | YCH-ST1 | ST1-SLOP TANK 1 | BULK STORAGE | MV-Ball Valves | YCH-ST1-BLVL-174827 | YCH01014 | Located inside valve pit 20 for ST1 from tank Y2 | HwaSung Co., Ltd. | X | Section 6-6.2.4 | Notify Facility; Confined Space | |||||||||
| 1114225 | YCH-ST1 | ST1-SLOP TANK 1 | BULK STORAGE | MV-Ball Valves | YCH-ST1-BLVL-174828 | YCH01015 | Located in valve pit 20 for ST1 from tank Y3 | HwaSung Co., Ltd. | X | Section 6-6.2.4 | Notify Facility; Confined Space | |||||||||
| 1114225 | YCH-ST1 | ST1-SLOP TANK 1 | BULK STORAGE | MV-Ball Valves | YCH-ST1-BLVL-177891 | YCH01016 | Located in valve pit 20 for ST1 from tank Y1 | HwaSung Co., Ltd. | X | Section 6-6.2.4 | Notify Facility; Confined Space | |||||||||
| 1114225 | YCH-ST1 | ST1-SLOP TANK 1 | BULK STORAGE | MV-Ball Valves | YCH-ST1-BLVL-177892 | YCH01017 | Located in valve pit 20 to ST1 | HwaSung Co., Ltd. | X | Section 6-6.2.4 | Notify Facility; Confined Space | |||||||||
| 1114225 | YCH-ST1 | ST1-SLOP TANK 1 | BULK STORAGE | SF-Emergency Eyewash/Showers | YCH-ST1-EMEWSH-174829 | YCH01018 | Portable emergency eyewash located at ST1 | Haws Corporation | X | X | X | Section 11-3 | Notify Facility | |||||||
| 1114226 | YCH-ST2 | ST2-SLOP TANK 2 | BULK STORAGE | SF-Emergency Eyewash/Showers | YCH-ST2-EMEWSH-174936 | YCH01019 | Portable emergency eyewash located at ST2 | Haws Corporation | X | X | X | Section 11-3 | Notify Facility | |||||||
| 11182 | YCH-Y3 | Y3-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | CS-Containment Drain Valves | YCH-Y3-CSGEN-216374 | YCH01624529 | Containment drain valve for the PRT containment | X | Section 8-10.1 | Confined Space- | ||||||||||
| 11182 | YCH-Y3 | Y3-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | MV-Ball Valves | YCH-Y3-BLVL-177893 | YCH0428220909 | 1/4-inch Isolation ball valve for the pressure gauge located on the outlet side of pump M3A. (Needle valve) | X | Section 6-6.2.4 | Notify Facility; Confined Space | Confined Space- | |||||||||
| 11182 | YCH-Y3 | Y3-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | TG-Servo Gauge | YCH-Y3-SRVGA-177894 | YCH0428220910 | Automatic Tank Gauge (ATG) | Honeywell | X | X | X | Section 8-9.8.3 | Confined Space- | Another Contract | ||||||
| 11182 | YCH-Y3 | Y3-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | MV-Ball Valves | YCH-Y3-BLVL-174937 | YCH0428220911 | 1/2-inch ball valve located on the bottom of the PRT sight glass | X | Section 6-6.2.4 | Notify Facility; Confined Space | Confined Space- | |||||||||
| 11182 | YCH-Y3 | Y3-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | MV-Gate Valves | YCH-Y3-GTVL-174830 | YCH0428220912 | 1/4-inch gate valve located on the top of the PRT sight glass | X | X | Section 6-6.2.3 | Notify Facility; Confined Space | Confined Space- | ||||||||
| 11182 | YCH-Y3 | Y3-JP-8 AIRCRAFT FUEL TANK | BULK STORAGE | MV-Gate Valves | YCH-Y3-GTVL-174831 | YCH0428220913 | 3/4-inch gate valve located on the PRT vent piping | X | X | Section 6-6.2.3 | Notify Facility; Confined Space | Confined Space- |