This is a Facility Maintenance Plan (FMP) for the DFSP Yecheon fuel storage facility located in Korea, prepared for the Pacific Ocean Division under contract W912DY-21-F-0076 by APTIM Federal Services, LLC. The document details comprehensive maintenance requirements for multiple fuel storage and transfer systems, including seven underground JP-8 aircraft fuel tanks (Y1-Y7), two slop tanks (ST1, ST2), two flightline service tanks (FL1, FL2), and various supporting infrastructure such as hydrant systems, pump houses, pipeline valve pits, truck fill stands, and rail offloading headers.

The maintenance plan provides extensive technical specifications for each asset, including component unique identifiers, manufacturer details, maintenance frequencies, UFC section references, and special considerations. Key systems include filter separators, pumps, valves, piping, control systems, and electrical equipment across facilities like the POL Pump House 355 and 356, with maintenance tasks ranging from quarterly to annual inspections. The document emphasizes precise tracking of equipment, manufacturer requirements, system availability impacts, and cross-referencing of asset identifications, demonstrating a comprehensive approach to maintaining critical fuel infrastructure at the Yecheon Defense Fuel Support Point.

View the file

Other files

File Type Posted
CDRL Set 17 - 65-67.pdf PDF
CDRL Set 3 - 9-12.pdf PDF
CDRL Set 13 - 49-52.pdf PDF
Attachment 4 - PPQ Sample.pdf PDF
FMP POF OSN_20251029.xlsx XLSX spreadsheet
FMP POF SUW_20251029.xlsx XLSX spreadsheet
FMP POF KUS_20251029.xlsx XLSX spreadsheet
Attachment 2 Sample Service Order (Appendix A - Attachment 1 Service Order Form).xlsx XLSX spreadsheet
FMP POF CSY_20251029.xlsx XLSX spreadsheet
CDRL Set 7 - 25-28.pdf PDF
CDRL Set 12 - 45-48.pdf PDF
CDRL Set 11 - 41-44.pdf PDF
FMP POF KUN_20251029.xlsx XLSX spreadsheet
FMP POF HUM_20251029.xlsx XLSX spreadsheet
FMP POF KIM_20251029.xlsx XLSX spreadsheet
FMP POF K-16_20251029.xlsx XLSX spreadsheet
Attachment 1 PWS amd Appendices POF - V1.pdf PDF
CDRL Set 10 - 37-40.pdf PDF
CDRL Set 16 - 60-64.pdf PDF
CDRL Set 15 - 57-60.pdf PDF
CDRL Set 4 - 13-16..pdf PDF
CDRL Set 2 - 5-8.pdf PDF
CDRL Set 14 - 53-56.pdf PDF
FMP POF KJU_20251029.xlsx XLSX spreadsheet
FMP POF POH_20251029.xlsx XLSX spreadsheet
Attachment 0005 Instructions and Evaluation Factors DRAFT.docx DOCX document
FMP POF WAL_20251029.xlsx XLSX spreadsheet
CDRL Set 6 - 21-24.pdf PDF
CDRL Set 8 - 29-32.pdf PDF
CDRL Set 5 - 17-20.pdf PDF
CDRL Set 1 - 1-4.pdf PDF
CDRL Set 9 - 33-36.pdf PDF
Appendix K Real Property Data.xlsx XLSX spreadsheet
Attachment 3 Technical Eval Form - V1.pdf PDF
FMP POF TAE_20251029.xlsx XLSX spreadsheet
FMP POF YSG_20251029.xlsx XLSX spreadsheet
FMP POF CRL_20251029.xlsx XLSX spreadsheet
Show all 37

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Administrative

ADMINISTRATIVE
LocationInstallation NameDFSP Yecheon
DLA Site CodeYCH
RPSUID601
Hours of Operation0800-1630
AddressYecheon, Korea
ContractContractor
Contract #
Local POCsPrimary FMSR
FMSR Phone
FMSR Email
Alternate FMSR
Alt FMSR Phone
Alt FMSR Email
Contractor POCsContractor PM
Contractor PM Phone
Contractor PM Email
Contractor QC Manager
Contractor QC Phone
Contractor QC Email
Contractor SOE
Contractor SOE Phone
Contractor SOE Email
Contractor RM
Contractor RM Phone
Contractor RM Email
Contractor SM
Contractor SM Phone
Contractor SM Email
USACE POCsUSACE PM/COR
USACE PM/COR Phone
USACE PM/COR Email
USACE PE
USACE PE Phone
USACE PE Email
USACE KO
USACE KO Phone
USACE KO Email
USACE Monthly Report Inbox

Pacific Ocean Division, POD-AF

W912DY-21-F-0076&"-,Bold"&16DFSP Yecheon
YCHFacility Maintenance Plan

OY3 Q3

&A &P of &N APTIM Federal Services, LLC

Instructions:

This table shows the minimum information required. Additional details should be included based on site specific requirements. Additional POCs may be required.

General Facility Description

General Facility Description
Installation NameDFSP Yecheon
DLA Site CodeYCH
LocationYecheon, Korea
Bulk Storage (fueling facility to support marine and aircraft operations): (7) JP-8 USTs connected to rail/truck receipts; (10) rail car receipts (majority of fuel received by rail); (4) JP-8 truck fill/issue stand - 1 fill stands (two issue lines are not operational because of underground line leak); (2) 50,000-gallon USTs for Type IV hydrant system with (4) issue pantographs; (3) Pump Rooms 355, 356 and Tanks FL1/2.
Contractor maintained. Ahntech operates the fuel systems and performs routine general maintenance.

DLA is responsible (COR) for Ahntech.

Pacific Ocean Division, POD-AF

W912DY-21-F-0076&"-,Bold"&16DFSP Yecheon
YCHFacility Maintenance Plan

OY3 Q3

&A &P of &N APTIM Federal Services, LLC

Instructions:

Include a general facility overview and description of each fuel system for the sites in accordance with UFC 3-460-01. Examples include: Bulk Storage Facilities, Aircraft Fueling Facilities, Marine and Dispensing Facilities, Ground Products Fueling Facilities, Alternate POL Facilities, and Support Facilities. Also include facility #s, facility names, fuel type, photos, and any other pertinent information.

Include Site Specific Conditions and Restrictions in this tab.

Communication Plan

Pacific Ocean Division, POD-AF

W912DY-21-F-0076&"-,Bold"&16DFSP Yecheon
YCHFacility Maintenance Plan

OY3 Q3

&A &P of &N APTIM Federal Services, LLC

Instructions:

Communication plan shall address in/out briefs, lines of communication, coordination for access, etc.

Site Specific APP

Pacific Ocean Division, POD-AF

W912DY-21-F-0076&"-,Bold"&16DFSP Yecheon
YCHFacility Maintenance Plan

OY3 Q3

&A &P of &N APTIM Federal Services, LLC

Instructions:

Site Specific Addendum and Activity Hazard Analysis, which are Attachments to the APP, specific to activities or tasks related to recurring maintenance for this site.

Instructions:

Site Specific Addendum and Activity Hazard Analysis, which are Attachments to the APP, specific to activities or tasks related to recurring maintenance for this site.

PM Schedule

Pacific Ocean Division, POD-AF

W912DY-21-F-0076&"-,Bold"&16DFSP Yecheon
YCHFacility Maintenance Plan

OY3 Q3

&A &P of &N APTIM Federal Services, LLC

Instructions:

Link PM schedule here

Task Matrix

Applicable Facility AssetsUFC System Level Maintenance FrequencySpecial Considerations
RPUIDReal Property Facility #Facility NameOperational AreaComponent TypeBase Asset NameComponent Unique ID CUIDAPTIM Asset IDAsset DescriptionMakeModelCapacity / SizeQuarterlySemi AnnualAnnualUFC Section ReferenceAdditional Manufacturer RM RequirementsOperator/Equipment RequirementsSystem AvailabilityOther ContractComments
11181YCH-Y2Y2-JP-8 AIRCRAFT FUEL TANKBULK STORAGEMV-Ball Valves129YCH-Y2-BLVL-16885416463YCHLocated on the 8 inch receipt lineJamesburyMA030-01XSection 6-6.2.4Notify Facility; Confined SpaceConfined Space-
11181YCH-Y2Y2-JP-8 AIRCRAFT FUEL TANKBULK STORAGEMV-Ball ValvesYCH-Y2-BLVL-16875916464YCHLocated on the 6 inch line for issue pump M2AHwaSung Co., Ltd.XSection 6-6.2.4Notify Facility; Confined SpaceConfined Space-
11181YCH-Y2Y2-JP-8 AIRCRAFT FUEL TANKBULK STORAGEMV-Ball ValvesYCH-Y2-BLVL-17595416465YCHLocated on the 6 inch line for issue pump M2BHwaSung Co., Ltd.XSection 6-6.2.4Notify Facility; Confined SpaceConfined Space-
11181YCH-Y2Y2-JP-8 AIRCRAFT FUEL TANKBULK STORAGEMV-Ball ValvesYCH-Y2-BLVL-16876116466YCHLocated on the 6 inch return lineHwaSung Co., Ltd.XSection 6-6.2.4Notify Facility; Confined SpaceConfined Space-
11182YCH-Y3Y3-JP-8 AIRCRAFT FUEL TANKBULK STORAGEMV-Ball Valves138YCH-Y3-BLVL-17595516467YCHLocated on the 8 inch receipt lineXSection 6-6.2.4Notify Facility; Confined SpaceConfined Space-
11182YCH-Y3Y3-JP-8 AIRCRAFT FUEL TANKBULK STORAGEMV-Ball Valves131YCH-Y3-BLVL-17595616468YCHBall valve located on the issue line for M3BXSection 6-6.2.4Notify Facility; Confined SpaceConfined Space-
11182YCH-Y3Y3-JP-8 AIRCRAFT FUEL TANKBULK STORAGEMV-Ball Valves132YCH-Y3-BLVL-16885616469YCHBall valve located on the issue line for M3AXSection 6-6.2.4Notify Facility; Confined SpaceConfined Space-
11182YCH-Y3Y3-JP-8 AIRCRAFT FUEL TANKBULK STORAGEMV-Ball Valves133YCH-Y3-BLVL-16885816470YCHBall valve located on the return lineXSection 6-6.2.4Notify Facility; Confined SpaceConfined Space-
11185YCH-Y6Y6-JP-8 AIRCRAFT FUEL TANKBULK STORAGEMV-Ball Valves304YCH-Y6-BLVL-16898716471YCH6-inch ball valve located on the receipt line. (Valve 304)XSection 6-6.2.4Notify Facility; Confined SpaceConfined Space-
11185YCH-Y6Y6-JP-8 AIRCRAFT FUEL TANKBULK STORAGEMV-Ball Valves301YCH-Y6-BLVL-16898816472YCH8-inch ball valve located on the discharge line for issue pump MS6A. (Valve 301)XSection 6-6.2.4Notify Facility; Confined SpaceConfined Space-
11185YCH-Y6Y6-JP-8 AIRCRAFT FUEL TANKBULK STORAGEMV-Ball ValvesYCH-Y6-BLVL-17595716473YCH6-inch ball valve located on the return line.XSection 6-6.2.4Notify Facility; Confined SpaceConfined Space-
11186YCH-Y7Y7-JP-8 AIRCRAFT FUEL TANKBULK STORAGEMV-Ball Valves314YCH-Y7-BLVL-16886016476YCHLocated on the 6 inch receipt lineXSection 6-6.2.4Notify Facility; Confined SpaceConfined Space-
11186YCH-Y7Y7-JP-8 AIRCRAFT FUEL TANKBULK STORAGEMV-Ball Valves311YCH-Y7-BLVL-16886116477YCHLocated on the 8 inch issue lineXSection 6-6.2.4Notify Facility; Confined SpaceConfined Space-
11186YCH-Y7Y7-JP-8 AIRCRAFT FUEL TANKBULK STORAGEMV-Ball Valves312YCH-Y7-BLVL-16876316478YCHLocated on the 6 inch return lineXSection 6-6.2.4Notify Facility; Confined SpaceConfined Space-
11186YCH-Y7Y7-JP-8 AIRCRAFT FUEL TANKBULK STORAGEMV-Ball Valves315YCH-Y7-BLVL-16876516479YCH2-inch ball valve located on the PRT return line inside the tank vault. (Valve 315)XSection 6-6.2.4Notify Facility; Confined SpaceConfined Space-
11186YCH-Y7Y7-JP-8 AIRCRAFT FUEL TANKBULK STORAGEMV-Ball Valves313YCH-Y7-BLVL-16899016480YCH2-inch Val valve located on the sump pump discharge line. (Valve 313)XSection 6-6.2.4Notify Facility; Confined SpaceConfined Space-
11183YCH-Y4Y4-JP-8 AIRCRAFT FUEL TANKBULK STORAGEMV-Ball ValvesYCH-Y4-BLVL-16899116481YCH6-inch ball valve located on the receipt line.XSection 6-6.2.4Notify Facility; Confined SpaceConfined Space-
11183YCH-Y4Y4-JP-8 AIRCRAFT FUEL TANKBULK STORAGEMV-Ball Valves201YCH-Y4-BLVL-16876816482YCH8-inch ball valve located on the discharge line for issue pump MS4A. (Valve 201)XSection 6-6.2.4Notify Facility; Confined SpaceConfined Space-
11183YCH-Y4Y4-JP-8 AIRCRAFT FUEL TANKBULK STORAGEMV-Ball Valves202YCH-Y4-BLVL-16899216483YCH6-inch ball valve located on the return line. (Valve 202)XSection 6-6.2.4Notify Facility; Confined SpaceConfined Space-
11184YCH-Y5Y5-JP-8 AIRCRAFT FUEL TANKBULK STORAGEMV-Ball Valves214YCH-Y5-BLVL-17595916484YCH6-inch bal valve located on the receipt line. (Valve 214)XSection 6-6.2.4Notify Facility; Confined SpaceConfined Space-
11184YCH-Y5Y5-JP-8 AIRCRAFT FUEL TANKBULK STORAGEMV-Ball Valves210YCH-Y5-BLVL-16886316485YCH8-inch ball valve located on the discharge line for issue pump M5B. (Valve 210)XSection 6-6.2.4Notify Facility; Confined SpaceConfined Space-
11184YCH-Y5Y5-JP-8 AIRCRAFT FUEL TANKBULK STORAGEMV-Ball Valves211YCH-Y5-BLVL-17596016486YCH8-inch ball valve located on the discharge line for issue pump M5A. (Valve 211)XSection 6-6.2.4Notify Facility; Confined SpaceConfined Space-
11184YCH-Y5Y5-JP-8 AIRCRAFT FUEL TANKBULK STORAGEMV-Ball Valves212YCH-Y5-BLVL-17596116487YCH6-inch ball valve located on the return line. (Valve 212)XSection 6-6.2.4Notify Facility; Confined SpaceConfined Space-
1114225YCH-ST1ST1-SLOP TANK 1BULK STORAGEMV-Ball ValvesYCH-ST1-BLVL-174917YCH00558Ball valve located on 2 inch piping for quick connectXSection 6-6.2.4Notify Facility
1114225YCH-ST1ST1-SLOP TANK 1BULK STORAGEMV-Check ValvesYCH-ST1-CKVL-174775YCH00559Check valve located on 2 inch piping for quick connectXSection 6-6.2.8Notify Facility
1114225YCH-ST1ST1-SLOP TANK 1BULK STORAGETK-Underground Double-Walled Shop-Fabricated TanksST 1YCH-ST1-UGDSFT-174918YCH00560Slop tank 1 located undergroundXSection 8-5.4.2
1114225YCH-ST1ST1-SLOP TANK 1BULK STORAGEPC-Aboveground Piping and Equipment CoatingYCH-ST1-AGPCT-174776YCH005622-inch coated piping for slop tank ST1Section 6-10.1
1114225YCH-ST1ST1-SLOP TANK 1BULK STORAGEEC-Ground Reels - Static Grounding SystemsYCH-ST1-STGS-174919YCH00563Ground reel located at slop tank 1XXSection 9-1.6.2
1114225YCH-ST1ST1-SLOP TANK 1BULK STORAGEEC-EFSO-Elec EquipYCH-ST1-EFSO-175366YCH00564EFSO located at slop tank 1XSection 9-1.2Operate System to Test
1114226YCH-ST2ST2-SLOP TANK 2BULK STORAGEMV-Ball Valves362YCH-ST2-BLVL-175367YCH00565Ball valve located inside the slop tank vault on the tank inlet. (Valve 362)XSection 6-6.2.4Notify Facility
1114226YCH-ST2ST2-SLOP TANK 2BULK STORAGEMV-Ball ValvesYCH-ST2-BLVL-177815YCH00566Ball valve located inside the slop tank vault for the Camlock connection.XSection 6-6.2.4Notify Facility
1114226YCH-ST2ST2-SLOP TANK 2BULK STORAGETK-Underground Double-Walled Shop-Fabricated TanksST 2YCH-ST2-UGDSFT-174920YCH00567Slop tank 2 located inside the vaultXSection 8-5.4.2
1114226YCH-ST2ST2-SLOP TANK 2BULK STORAGEMV-Ball ValvesYCH-ST2-BLVL-175368YCH00568Sight glass drain valve bottom sideXSection 6-6.2.4Notify Facility
1114226YCH-ST2ST2-SLOP TANK 2BULK STORAGEMV-Gate ValvesYCH-ST2-GTVL-177817YCH00569Sight glass isolation gate valve top sideXXSection 6-6.2.3Notify Facility
1114226YCH-ST2ST2-SLOP TANK 2BULK STORAGEMV-Gate ValvesYCH-ST2-GTVL-177818YCH00570Sight glass isolation gate valve bottom sideXXSection 6-6.2.3Notify Facility
1114226YCH-ST2ST2-SLOP TANK 2BULK STORAGECS-Self-Diking or Vaulted Tank ContainmentYCH-ST2-SDVTCS-174777YCH00571Vault for slop tankSection 8-10.4
1114226YCH-ST2ST2-SLOP TANK 2BULK STORAGEPC-Aboveground Piping and Equipment CoatingYCH-ST2-AGPCT-174921YCH00574Coated piping 2 inch inside slop tank vaultSection 6-10.1
1114226YCH-ST2ST2-SLOP TANK 2BULK STORAGEPC-Aboveground Piping and Equipment CoatingYCH-ST2-AGPCT-174778YCH00576Coated piping 3 inch inside slop tank vaultSection 6-10.1
1114226YCH-ST2ST2-SLOP TANK 2BULK STORAGEEQ-Air VentYCH-ST2-ASSET-177820YCH00577Goose neck style air vent next to tank vault lidNon-Appx G Class
11180YCH-Y1Y1-JP-8 AIRCRAFT FUEL TANKBULK STORAGETD-Miscellaneous Deactivated ComponentsYCH-Y1-MDEAC-177847YCH00730Tank Y1 is out of service for an undetermined amount of timeXSection 12-5
11181YCH-Y2Y2-JP-8 AIRCRAFT FUEL TANKBULK STORAGEMV-Ball ValvesYCH-Y2-BLVL-174811YCH00731Located on the 1/2 line for the tank high-level shut offXSection 6-6.2.4Notify Facility; Confined SpaceConfined Space-
11181YCH-Y2Y2-JP-8 AIRCRAFT FUEL TANKBULK STORAGEMV-Ball ValvesYCH-Y2-BLVL-174813YCH007321/2-inch isolation ball valve for the pressure gauge located on the outlet side of pump M2AXSection 6-6.2.4Notify Facility; Confined SpaceConfined Space-
11181YCH-Y2Y2-JP-8 AIRCRAFT FUEL TANKBULK STORAGEMV-Ball ValvesYCH-Y2-BLVL-177848YCH007331/2-inch isolation ball valve for the pressure gauge located on the outlet side of pump M2BXSection 6-6.2.4Notify Facility; Confined SpaceConfined Space-
11181YCH-Y2Y2-JP-8 AIRCRAFT FUEL TANKBULK STORAGEMV-Ball Valves124YCH-Y2-BLVL-174970YCH00734Located on the 2 inch line for sump pump M2C. (Valve 124)XSection 6-6.2.4Notify Facility; Confined SpaceConfined Space-
11181YCH-Y2Y2-JP-8 AIRCRAFT FUEL TANKBULK STORAGEMV-Ball Valves125YCH-Y2-BLVL-174816YCH00739Located on the PRT piping from sump (second in line). (Valve 125)XSection 6-6.2.4Notify Facility; Confined SpaceConfined Space-
11181YCH-Y2Y2-JP-8 AIRCRAFT FUEL TANKBULK STORAGECV-General System Control ValvesA 9YCH-Y2-GSCVL-168042YCH007402-inch control valve located on the discharge line for sump pump M2C. (Valve A-9)Cla-ValXXSection 4-3.2.1Operate System to Test; Confined SpaceConfined Space-
11181YCH-Y2Y2-JP-8 AIRCRAFT FUEL TANKBULK STORAGECV-General System Control ValvesA 5YCH-Y2-GSCVL-168047YCH007426-inch control valve located on the discharge line for issue pump M2A. (Valve A-5)Cla-ValXXSection 4-3.2.1Operate System to Test; Confined SpaceConfined Space-
11181YCH-Y2Y2-JP-8 AIRCRAFT FUEL TANKBULK STORAGECV-General System Control ValvesA 6YCH-Y2-GSCVL-168050YCH007436-inch control valve located on the discharge line for issue pump M2B. (Valve A-6)Cla-ValXXSection 4-3.2.1Operate System to Test; Confined SpaceConfined Space-
11181YCH-Y2Y2-JP-8 AIRCRAFT FUEL TANKBULK STORAGECV-General System Control ValvesYCH-Y2-GSCVL-168052YCH007446-inch control valve located on the return line.Cla-ValXXSection 4-3.2.1Operate System to Test; Confined SpaceConfined Space-
11181YCH-Y2Y2-JP-8 AIRCRAFT FUEL TANKBULK STORAGEMV-Gate Valves126YCH-Y2-GTVL-175384YCH00745Located on the piping from the side of the PRT. (Valve 126)XXSection 6-6.2.3Notify Facility; Confined SpaceConfined Space-
11181YCH-Y2Y2-JP-8 AIRCRAFT FUEL TANKBULK STORAGETA-Tank Pressure/Vacuum VentsYCH-Y2-TPVVT-174972YCH00749Located inside tank vault near the entranceVarec202051XSection 8-9.3Notify FacilityConfined Space-
11181YCH-Y2Y2-JP-8 AIRCRAFT FUEL TANKBULK STORAGETA-Tank Pressure/Vacuum VentsYCH-Y2-TPVVT-175385YCH00750Located inside tank vault across from the entranceVarec202051XSection 8-9.3Notify FacilityConfined Space-
11181YCH-Y2Y2-JP-8 AIRCRAFT FUEL TANKBULK STORAGEPM-Vertical Turbine/Sub-merged Turbine PumpsM2AYCH-Y2-VTSP-174973YCH00751Issue pump M2A located inside vaultPeabody FlowayType DKHXXXSection 3-8.1.3 / 3-8.3Operate System to Test; Confined SpaceConfined Space-600 gpm
11181YCH-Y2Y2-JP-8 AIRCRAFT FUEL TANKBULK STORAGEPM-Vertical Turbine/Sub-merged Turbine PumpsM2BYCH-Y2-VTSP-174975YCH00752Issue pump M2B located inside vaultPeabody FlowayType DKHXXXSection 3-8.1.3 / 3-8.3Operate System to Test; Confined SpaceConfined Space-600 gpm
11181YCH-Y2Y2-JP-8 AIRCRAFT FUEL TANKBULK STORAGEPM-Vertical Turbine/Sub-merged Turbine PumpsM2CYCH-Y2-VTSP-175386YCH00753Sump pump M2C located inside vaultPeabody FlowayType XKLXXXSection 3-8.1.3 / 3-8.3Operate System to Test; Confined SpaceConfined Space-50 gpm
11181YCH-Y2Y2-JP-8 AIRCRAFT FUEL TANKBULK STORAGETK-Underground Field-Constructed TanksY2YCH-Y2-UGFET-177849YCH00754Tank Y2XSection 8-6Confined Space-
11181YCH-Y2Y2-JP-8 AIRCRAFT FUEL TANKBULK STORAGEPS-Product Saver TanksYCH-Y2-PRDST-177850YCH00755PST located on top of the tankXSection 8-9.10Notify FacilityConfined Space-
11181YCH-Y2Y2-JP-8 AIRCRAFT FUEL TANKBULK STORAGETA-Mechanical Tape Gauges (non-ATG)YCH-Y2-MTGA-164486YCH00756Fuel tank gauge located inside vaultVarecMODEL BXSection 8-9.7Confined Space-
11181YCH-Y2Y2-JP-8 AIRCRAFT FUEL TANKBULK STORAGETA-Mechanical Tape Gauges (non-ATG)YCH-Y2-MTGA-164487YCH00757Water tank gauge located inside vaultVarecMODEL BXSection 8-9.7Confined Space-
11181YCH-Y2Y2-JP-8 AIRCRAFT FUEL TANKBULK STORAGEMV-Ball ValvesYCH-Y2-BLVL-177851YCH00758Ball valve located on the PRT piping from sump (first in line)XSection 6-6.2.4Notify Facility; Confined SpaceConfined Space-
11181YCH-Y2Y2-JP-8 AIRCRAFT FUEL TANKBULK STORAGEMV-Gate Valves127YCH-Y2-GTVL-174977YCH00759Gate valve located at the bottom of the PRT to the slop tank. (Valve 127)XXSection 6-6.2.3Notify Facility; Confined SpaceConfined Space-
11181YCH-Y2Y2-JP-8 AIRCRAFT FUEL TANKBULK STORAGEPC-Aboveground Piping and Equipment CoatingYCH-Y2-AGPCT-175387YCH00761Coated piping 10 inchSection 6-10.1Confined Space-
11181YCH-Y2Y2-JP-8 AIRCRAFT FUEL TANKBULK STORAGEPC-Aboveground Piping and Equipment CoatingYCH-Y2-AGPCT-174728YCH00762Coated piping 8 inchSection 6-10.1Confined Space-
11181YCH-Y2Y2-JP-8 AIRCRAFT FUEL TANKBULK STORAGEPC-Aboveground Piping and Equipment CoatingYCH-Y2-AGPCT-174983YCH00763Coated piping 6 inchSection 6-10.1Confined Space-
11181YCH-Y2Y2-JP-8 AIRCRAFT FUEL TANKBULK STORAGEPC-Aboveground Piping and Equipment CoatingYCH-Y2-AGPCT-174819YCH00764Coated piping 2 inchSection 6-10.1Confined Space-
11181YCH-Y2Y2-JP-8 AIRCRAFT FUEL TANKBULK STORAGEEC-EFSO-Elec EquipYCH-Y2-EFSO-174822YCH00765EFSO located at the top of the tank stairsXSection 9-1.2Operate System to TestConfined Space-
11181YCH-Y2Y2-JP-8 AIRCRAFT FUEL TANKBULK STORAGETA-External High Level Shutoff Valves (HLSO)YCH-Y2-EHLSVL-177852YCH00770High-level shut off valveXXSection 8-9.6.1Notify FacilityConfined Space-
11181YCH-Y2Y2-JP-8 AIRCRAFT FUEL TANKBULK STORAGEPV-Pressure GaugesYCH-Y2-PVGA-174984YCH00771Pressure gauge located on the outlet side of pump M2AXXXSection 6-7.1Notify FacilityConfined Space-
11181YCH-Y2Y2-JP-8 AIRCRAFT FUEL TANKBULK STORAGEPV-Pressure GaugesYCH-Y2-PVGA-174985YCH00772Pressure gauge located on the outlet side of pump M2BAshcroftXXXSection 6-7.1Notify FacilityConfined Space-
11182YCH-Y3Y3-JP-8 AIRCRAFT FUEL TANKBULK STORAGEMV-Ball Valves134YCH-Y3-BLVL-177853YCH00773Located on the 2 inch PRT issue line. (Valve 134)XSection 6-6.2.4Notify Facility; Confined SpaceConfined Space-
11182YCH-Y3Y3-JP-8 AIRCRAFT FUEL TANKBULK STORAGEMV-Ball Valves135YCH-Y3-BLVL-177854YCH00774Located on the 2 inch PRT return line to the tank. (Valve 135)XSection 6-6.2.4Notify Facility; Confined SpaceConfined Space-
11182YCH-Y3Y3-JP-8 AIRCRAFT FUEL TANKBULK STORAGEMV-Ball Valves136YCH-Y3-BLVL-177855YCH00775Located on the 2 inch PRT line to the slop tank. (Valve 136)XSection 6-6.2.4Notify Facility; Confined SpaceConfined Space-
11182YCH-Y3Y3-JP-8 AIRCRAFT FUEL TANKBULK STORAGEMV-Ball Valves137YCH-Y3-BLVL-177856YCH00776Located on the 2 inch PRT crossover line. (Valve 137)XSection 6-6.2.4Notify Facility; Confined SpaceConfined Space-
11182YCH-Y3Y3-JP-8 AIRCRAFT FUEL TANKBULK STORAGEMV-Ball Valves139YCH-Y3-BLVL-174986YCH007783/4-inch ball valve located on top of the HLSO control valve.XSection 6-6.2.4Notify Facility; Confined SpaceConfined Space-
11182YCH-Y3Y3-JP-8 AIRCRAFT FUEL TANKBULK STORAGEMV-Ball Valves140YCH-Y3-BLVL-174804YCH00779Located on the PRT return line inside the tank vault. (Valve 140)XSection 6-6.2.4Notify Facility; Confined SpaceConfined Space-
11182YCH-Y3Y3-JP-8 AIRCRAFT FUEL TANKBULK STORAGEMV-Ball Valves141YCH-Y3-BLVL-177857YCH00780Located on the sump pump discharge line. (Valve 141)XSection 6-6.2.4Notify Facility; Confined SpaceConfined Space-
11182YCH-Y3Y3-JP-8 AIRCRAFT FUEL TANKBULK STORAGEMV-Check ValvesYCH-Y3-CKVL-174806YCH00781Located on the sump pump lineXSection 6-6.2.8Notify Facility; Confined SpaceConfined Space-
11182YCH-Y3Y3-JP-8 AIRCRAFT FUEL TANKBULK STORAGECV-General System Control ValvesYCH-Y3-GSCVL-168054YCH007826-inch control valve located on the return line.XXSection 4-3.2.1Operate System to Test; Confined SpaceConfined Space-
11182YCH-Y3Y3-JP-8 AIRCRAFT FUEL TANKBULK STORAGETA-Tank Pressure/Vacuum VentsYCH-Y3-TPVVT-177858YCH00785Located inside vault near the entranceShand & JursXSection 8-9.3Notify FacilityConfined Space-
11182YCH-Y3Y3-JP-8 AIRCRAFT FUEL TANKBULK STORAGETA-Tank Pressure/Vacuum VentsYCH-Y3-TPVVT-177859YCH00786Located inside vault across from the entranceShand & JursXSection 8-9.3Notify FacilityConfined Space-
11182YCH-Y3Y3-JP-8 AIRCRAFT FUEL TANKBULK STORAGEPM-Vertical Turbine/Sub-merged Turbine PumpsM3AYCH-Y3-VTSP-174987YCH00787Issue pump M3A located inside vaultLayne & BowlerXXXSection 3-8.1.3 / 3-8.3Operate System to Test; Confined SpaceConfined Space-600 gpm
11182YCH-Y3Y3-JP-8 AIRCRAFT FUEL TANKBULK STORAGEPM-Vertical Turbine/Sub-merged Turbine PumpsM3BYCH-Y3-VTSP-174988YCH00788Issue pump M3B located inside vaultLayne & BowlerXXXSection 3-8.1.3 / 3-8.3Operate System to Test; Confined SpaceConfined Space-600 gpm
11182YCH-Y3Y3-JP-8 AIRCRAFT FUEL TANKBULK STORAGEPM-Vertical Turbine/Sub-merged Turbine PumpsM3CYCH-Y3-VTSP-174808YCH00789Sump pump M3C located inside vaultLayne & BowlerXXXSection 3-8.1.3 / 3-8.3Operate System to Test; Confined SpaceConfined Space-
11182YCH-Y3Y3-JP-8 AIRCRAFT FUEL TANKBULK STORAGETK-Underground Field-Constructed TanksY3YCH-Y3-UGFET-174729YCH00790Tank Y3XSection 8-6Confined Space-
11182YCH-Y3Y3-JP-8 AIRCRAFT FUEL TANKBULK STORAGEPS-Product Saver TanksYCH-Y3-PRDST-177860YCH00791PRT located on top of the tankXSection 8-9.10Notify FacilityConfined Space-
11182YCH-Y3Y3-JP-8 AIRCRAFT FUEL TANKBULK STORAGETA-Mechanical Tape Gauges (non-ATG)YCH-Y3-MTGA-164488YCH00792Fuel tank gauge located inside vaultShand & JursXSection 8-9.7Confined Space-
11182YCH-Y3Y3-JP-8 AIRCRAFT FUEL TANKBULK STORAGETA-Mechanical Tape Gauges (non-ATG)YCH-Y3-MTGA-164489YCH00793Water tank gauge located inside vaultShand & JursXSection 8-9.7Confined Space-
11182YCH-Y3Y3-JP-8 AIRCRAFT FUEL TANKBULK STORAGEMV-Ball ValvesYCH-Y3-BLVL-177861YCH007973/8-inch Isolation ball valve for the pressure gauge located on the outlet side of pump M3BXSection 6-6.2.4Notify Facility; Confined SpaceConfined Space-
11182YCH-Y3Y3-JP-8 AIRCRAFT FUEL TANKBULK STORAGEMV-Check ValvesYCH-Y3-CKVL-177862YCH00798Check valve located on M3A issue lineXSection 6-6.2.8Notify Facility; Confined SpaceConfined Space-
11182YCH-Y3Y3-JP-8 AIRCRAFT FUEL TANKBULK STORAGEMV-Check ValvesYCH-Y3-CKVL-177863YCH00799Check valve located on M3B issue lineXSection 6-6.2.8Notify Facility; Confined SpaceConfined Space-
11182YCH-Y3Y3-JP-8 AIRCRAFT FUEL TANKBULK STORAGECV-General System Control ValvesYCH-Y3-GSCVL-168056YCH00800Control valve located on the receipt lineXXSection 4-3.2.1Operate System to Test; Confined SpaceConfined Space-
11182YCH-Y3Y3-JP-8 AIRCRAFT FUEL TANKBULK STORAGEPC-Aboveground Piping and Equipment CoatingYCH-Y3-AGPCT-174730YCH00803Coated piping 10 inSection 6-10.1Confined Space-
11182YCH-Y3Y3-JP-8 AIRCRAFT FUEL TANKBULK STORAGEPC-Aboveground Piping and Equipment CoatingYCH-Y3-AGPCT-174810YCH00804Coated piping 8 inSection 6-10.1Confined Space-
11182YCH-Y3Y3-JP-8 AIRCRAFT FUEL TANKBULK STORAGEPC-Aboveground Piping and Equipment CoatingYCH-Y3-AGPCT-174812YCH00805Coated piping 6 inSection 6-10.1Confined Space-
11182YCH-Y3Y3-JP-8 AIRCRAFT FUEL TANKBULK STORAGEPC-Aboveground Piping and Equipment CoatingYCH-Y3-AGPCT-177864YCH00806Coated piping 2 inSection 6-10.1Confined Space-
11182YCH-Y3Y3-JP-8 AIRCRAFT FUEL TANKBULK STORAGEPV-Pressure GaugesYCH-Y3-PVGA-177865YCH00810Pressure gauge located on the outlet side of pump M3AAshcroftXXXSection 6-7.1Notify FacilityConfined Space-
11182YCH-Y3Y3-JP-8 AIRCRAFT FUEL TANKBULK STORAGEPV-Pressure GaugesYCH-Y3-PVGA-174814YCH00811Pressure gauge located on the outlet side of pump M3BAshcroftXXXSection 6-7.1Notify FacilityConfined Space-
11182YCH-Y3Y3-JP-8 AIRCRAFT FUEL TANKBULK STORAGETA-External High Level Shutoff Valves (HLSO)YCH-Y3-EHLSVL-174815YCH00812High-level shut off valveXXSection 8-9.6.1Notify FacilityConfined Space-
11183YCH-Y4Y4-JP-8 AIRCRAFT FUEL TANKBULK STORAGEMV-Ball Valves207YCH-Y4-BLVL-174817YCH008132-inch ball valve located on the PRT issue line. (Valve 207)XSection 6-6.2.4Notify Facility; Confined SpaceConfined Space-
11183YCH-Y4Y4-JP-8 AIRCRAFT FUEL TANKBULK STORAGEMV-Ball Valves208YCH-Y4-BLVL-174989YCH008142-inch ball valve located on the PRT return line. (Valve 208)XSection 6-6.2.4Notify Facility; Confined SpaceConfined Space-
11183YCH-Y4Y4-JP-8 AIRCRAFT FUEL TANKBULK STORAGEMV-Ball Valves209YCH-Y4-BLVL-174990YCH008152-inch ball valve located on the PRT crossover line. (Valve 209)XSection 6-6.2.4Notify Facility; Confined SpaceConfined Space-
11183YCH-Y4Y4-JP-8 AIRCRAFT FUEL TANKBULK STORAGEMV-Ball ValvesYCH-Y4-BLVL-174731YCH008162-inch ball valve located on the PRT line to the slop tank.XSection 6-6.2.4Notify Facility; Confined SpaceConfined Space-
11183YCH-Y4Y4-JP-8 AIRCRAFT FUEL TANKBULK STORAGEMV-Ball Valves205YCH-Y4-BLVL-174991YCH008172-inch ball valve located on the PRT return line inside the tank vault. (Valve 205)XSection 6-6.2.4Notify Facility; Confined SpaceConfined Space-
11183YCH-Y4Y4-JP-8 AIRCRAFT FUEL TANKBULK STORAGEMV-Ball Valves203YCH-Y4-BLVL-177866YCH008182-inc ball valve located on the sump pump discharge line. (Valve 203)XSection 6-6.2.4Notify Facility; Confined SpaceConfined Space-
11183YCH-Y4Y4-JP-8 AIRCRAFT FUEL TANKBULK STORAGEMV-Ball Valves206YCH-Y4-BLVL-174818YCH008193/4-inch bal valve located on top of the HLSO control valve.XSection 6-6.2.4Notify Facility; Confined SpaceConfined Space-
11183YCH-Y4Y4-JP-8 AIRCRAFT FUEL TANKBULK STORAGEMV-Check ValvesYCH-Y4-CKVL-174992YCH008228-inch check valve located on the discharge line for issue pump MS4A.XSection 6-6.2.8Notify Facility; Confined SpaceConfined Space-
11183YCH-Y4Y4-JP-8 AIRCRAFT FUEL TANKBULK STORAGEMV-Check ValvesYCH-Y4-CKVL-174993YCH008232-inch check valve located on the sump pump discharge line.XSection 6-6.2.8Notify Facility; Confined SpaceConfined Space-
11183YCH-Y4Y4-JP-8 AIRCRAFT FUEL TANKBULK STORAGECV-General System Control ValvesYCH-Y4-GSCVL-168058YCH00824Located on the 6 inch receipt lineXXSection 4-3.2.1Operate System to Test; Confined SpaceConfined Space-
11183YCH-Y4Y4-JP-8 AIRCRAFT FUEL TANKBULK STORAGECV-General System Control ValvesYCH-Y4-GSCVL-168061YCH008256-inch control valve located on the return line.XXSection 4-3.2.1Operate System to Test; Confined SpaceConfined Space-
11183YCH-Y4Y4-JP-8 AIRCRAFT FUEL TANKBULK STORAGETA-Tank Pressure/Vacuum VentsYCH-Y4-TPVVT-174732YCH00828Located inside vault near the entranceShand & JursXSection 8-9.3Notify FacilityConfined Space-
11183YCH-Y4Y4-JP-8 AIRCRAFT FUEL TANKBULK STORAGETA-Tank Pressure/Vacuum VentsYCH-Y4-TPVVT-174994YCH00829Located inside vault across from the entranceShand & JursXSection 8-9.3Notify FacilityConfined Space-
11183YCH-Y4Y4-JP-8 AIRCRAFT FUEL TANKBULK STORAGEPM-Vertical Turbine/Sub-merged Turbine PumpsM4AYCH-Y4-VTSP-175045YCH00830Issue pump M4A located inside vaultLayne & BowlerXXXSection 3-8.1.3 / 3-8.3Operate System to Test; Confined SpaceConfined Space-600 gpm
11183YCH-Y4Y4-JP-8 AIRCRAFT FUEL TANKBULK STORAGEPM-Vertical Turbine/Sub-merged Turbine PumpsM4BYCH-Y4-VTSP-177867YCH00831Sump pump M4B located inside vaultLayne & BowlerXXXSection 3-8.1.3 / 3-8.3Operate System to Test; Confined SpaceConfined Space-
11183YCH-Y4Y4-JP-8 AIRCRAFT FUEL TANKBULK STORAGETK-Underground Field-Constructed TanksY4YCH-Y4-UGFET-174733YCH00832Tank Y4XSection 8-6Confined Space-
11183YCH-Y4Y4-JP-8 AIRCRAFT FUEL TANKBULK STORAGEPS-Product Saver TanksYCH-Y4-PRDST-174734YCH00833PRT located on top of the tankXSection 8-9.10Notify FacilityConfined Space-
11183YCH-Y4Y4-JP-8 AIRCRAFT FUEL TANKBULK STORAGETA-Mechanical Tape Gauges (non-ATG)YCH-Y4-MTGA-164490YCH00834Fuel tank gauge located inside vaultShand & JursXSection 8-9.7Confined Space-
11183YCH-Y4Y4-JP-8 AIRCRAFT FUEL TANKBULK STORAGETA-Mechanical Tape Gauges (non-ATG)YCH-Y4-MTGA-164491YCH00835Water tank gauge located inside vaultShand & JursXSection 8-9.7Confined Space-
11183YCH-Y4Y4-JP-8 AIRCRAFT FUEL TANKBULK STORAGETA-External High Level Shutoff Valves (HLSO)YCH-Y4-EHLSVL-177868YCH00836High-level shut off valveXXSection 8-9.6.1Notify FacilityConfined Space-
11183YCH-Y4Y4-JP-8 AIRCRAFT FUEL TANKBULK STORAGEPV-Pressure GaugesYCH-Y4-PVGA-174820YCH00838Pressure gauge located on the outlet of pump M4AAshcroftXXXSection 6-7.1Notify FacilityConfined Space-
11183YCH-Y4Y4-JP-8 AIRCRAFT FUEL TANKBULK STORAGEPC-Aboveground Piping and Equipment CoatingYCH-Y4-AGPCT-174735YCH00839Coated piping 10 inSection 6-10.1Confined Space-
11183YCH-Y4Y4-JP-8 AIRCRAFT FUEL TANKBULK STORAGEPC-Aboveground Piping and Equipment CoatingYCH-Y4-AGPCT-177869YCH00840Coated piping 6 inSection 6-10.1Confined Space-
11183YCH-Y4Y4-JP-8 AIRCRAFT FUEL TANKBULK STORAGEPC-Aboveground Piping and Equipment CoatingYCH-Y4-AGPCT-174821YCH00841Coated piping 2 inchSection 6-10.1Confined Space-
11184YCH-Y5Y5-JP-8 AIRCRAFT FUEL TANKBULK STORAGEMV-Ball Valves217YCH-Y5-BLVL-175049YCH008442-inch ball valve located on the PRT issue line. (Valve 217)XSection 6-6.2.4Notify Facility; Confined SpaceConfined Space-
11184YCH-Y5Y5-JP-8 AIRCRAFT FUEL TANKBULK STORAGEMV-Ball Valves218YCH-Y5-BLVL-175052YCH008452-inch ball valve located on the PRT return line. (Valve 218)XSection 6-6.2.4Notify Facility; Confined SpaceConfined Space-
11184YCH-Y5Y5-JP-8 AIRCRAFT FUEL TANKBULK STORAGEMV-Ball Valves219YCH-Y5-BLVL-174736YCH008462-inch ball valve located on the PRT crossover line. (Valve 219)XSection 6-6.2.4Notify Facility; Confined SpaceConfined Space-
11184YCH-Y5Y5-JP-8 AIRCRAFT FUEL TANKBULK STORAGEMV-Ball Valves220YCH-Y5-BLVL-175055YCH008472-inch ball valve located on the PRT line to the slop tank. (Valve 220)XSection 6-6.2.4Notify Facility; Confined SpaceConfined Space-
11184YCH-Y5Y5-JP-8 AIRCRAFT FUEL TANKBULK STORAGEMV-Ball Valves213YCH-Y5-BLVL-175059YCH008482-inch ball valve located on the sump pump discharge line. (Valve 213)XSection 6-6.2.4Notify Facility; Confined SpaceConfined Space-
11184YCH-Y5Y5-JP-8 AIRCRAFT FUEL TANKBULK STORAGEMV-Ball Valves215YCH-Y5-BLVL-174823YCH008492-inch ball valve located on the PRT return line inside the tank vault. (Valve 215)XSection 6-6.2.4Notify Facility; Confined SpaceConfined Space-
11184YCH-Y5Y5-JP-8 AIRCRAFT FUEL TANKBULK STORAGEMV-Ball Valves216YCH-Y5-BLVL-177870YCH008503/4-inch ball valve located on top of the HLSO control valve.XSection 6-6.2.4Notify Facility; Confined SpaceConfined Space-
11184YCH-Y5Y5-JP-8 AIRCRAFT FUEL TANKBULK STORAGEMV-Check ValvesYCH-Y5-CKVL-175062YCH008542-inch check valve located on the sump pump discharge line.XSection 6-6.2.8Notify Facility; Confined SpaceConfined Space-
11184YCH-Y5Y5-JP-8 AIRCRAFT FUEL TANKBULK STORAGECV-General System Control ValvesYCH-Y5-GSCVL-168064YCH008556-inch control valve located on the return line.XXSection 4-3.2.1Operate System to Test; Confined SpaceConfined Space-
11184YCH-Y5Y5-JP-8 AIRCRAFT FUEL TANKBULK STORAGECV-General System Control ValvesYCH-Y5-GSCVL-168066YCH00856Located on the 6 inch receipt lineXXSection 4-3.2.1Operate System to Test; Confined SpaceConfined Space-
11184YCH-Y5Y5-JP-8 AIRCRAFT FUEL TANKBULK STORAGETA-Tank Pressure/Vacuum VentsYCH-Y5-TPVVT-174824YCH00859Located inside vault near the entranceShand & JursXSection 8-9.3Notify FacilityConfined Space-
11184YCH-Y5Y5-JP-8 AIRCRAFT FUEL TANKBULK STORAGETA-Tank Pressure/Vacuum VentsYCH-Y5-TPVVT-174860YCH00860Located inside vault across from the entranceShand & JursXSection 8-9.3Notify FacilityConfined Space-
11184YCH-Y5Y5-JP-8 AIRCRAFT FUEL TANKBULK STORAGEPM-Vertical Turbine/Sub-merged Turbine PumpsM5AYCH-Y5-VTSP-177871YCH00861Issue pump M5A located inside vaultLayne & BowlerXXXSection 3-8.1.3 / 3-8.3Operate System to Test; Confined SpaceConfined Space-600 gpm
11184YCH-Y5Y5-JP-8 AIRCRAFT FUEL TANKBULK STORAGEPM-Vertical Turbine/Sub-merged Turbine PumpsM5BYCH-Y5-VTSP-177872YCH00862Issue pump M5B located inside vaultLayne & BowlerXXXSection 3-8.1.3 / 3-8.3Operate System to Test; Confined SpaceConfined Space-600 gpm
11184YCH-Y5Y5-JP-8 AIRCRAFT FUEL TANKBULK STORAGEPM-Vertical Turbine/Sub-merged Turbine PumpsM5CYCH-Y5-VTSP-177873YCH00863Sump pump M5C located inside vaultLayne & BowlerXXXSection 3-8.1.3 / 3-8.3Operate System to Test; Confined SpaceConfined Space-
11184YCH-Y5Y5-JP-8 AIRCRAFT FUEL TANKBULK STORAGETK-Underground Field-Constructed TanksY5YCH-Y5-UGFET-174737YCH00864Tank Y5XSection 8-6Confined Space-
11184YCH-Y5Y5-JP-8 AIRCRAFT FUEL TANKBULK STORAGEPS-Product Saver TanksYCH-Y5-PRDST-174738YCH00865PRT located on top of the tankXSection 8-9.10Notify FacilityConfined Space-
11184YCH-Y5Y5-JP-8 AIRCRAFT FUEL TANKBULK STORAGETA-Mechanical Tape Gauges (non-ATG)YCH-Y5-MTGA-164492YCH00866Fuel tank gauge located inside vaultShand & JursXSection 8-9.7Confined Space-
11184YCH-Y5Y5-JP-8 AIRCRAFT FUEL TANKBULK STORAGETA-Mechanical Tape Gauges (non-ATG)YCH-Y5-MTGA-164493YCH00867Water tank gauge located inside vaultShand & JursXSection 8-9.7Confined Space-
11184YCH-Y5Y5-JP-8 AIRCRAFT FUEL TANKBULK STORAGEMV-Check ValvesYCH-Y5-CKVL-177874YCH008698-inch check valve located on the discharge line for issue pump M5A.XSection 6-6.2.8Notify Facility; Confined SpaceConfined Space-
11184YCH-Y5Y5-JP-8 AIRCRAFT FUEL TANKBULK STORAGEMV-Check ValvesYCH-Y5-CKVL-175065YCH008708-inch check valve located on the discharge line for issue pump M5B.XSection 6-6.2.8Notify Facility; Confined SpaceConfined Space-
11184YCH-Y5Y5-JP-8 AIRCRAFT FUEL TANKBULK STORAGEPC-Aboveground Piping and Equipment CoatingYCH-Y5-AGPCT-174739YCH00872Coated piping 10 inSection 6-10.1Confined Space-
11184YCH-Y5Y5-JP-8 AIRCRAFT FUEL TANKBULK STORAGEPC-Aboveground Piping and Equipment CoatingYCH-Y5-AGPCT-174740YCH00873Coated piping 6 inSection 6-10.1Confined Space-
11184YCH-Y5Y5-JP-8 AIRCRAFT FUEL TANKBULK STORAGEPC-Aboveground Piping and Equipment CoatingYCH-Y5-AGPCT-174861YCH00874Coated piping 2 inchSection 6-10.1Confined Space-
11184YCH-Y5Y5-JP-8 AIRCRAFT FUEL TANKBULK STORAGEPV-Pressure GaugesYCH-Y5-PVGA-174862YCH00875Pressure gauge located on the outlet of pump M5AAshcroftXXXSection 6-7.1Notify FacilityConfined Space-
11184YCH-Y5Y5-JP-8 AIRCRAFT FUEL TANKBULK STORAGEPV-Pressure GaugesYCH-Y5-PVGA-177875YCH00876Pressure gauge located on the outlet side of pump M5BAshcroftXXXSection 6-7.1Notify FacilityConfined Space-
11184YCH-Y5Y5-JP-8 AIRCRAFT FUEL TANKBULK STORAGETA-External High Level Shutoff Valves (HLSO)YCH-Y5-EHLSVL-174863YCH00877High-level shut off valveXXSection 8-9.6.1Notify FacilityConfined Space-
11185YCH-Y6Y6-JP-8 AIRCRAFT FUEL TANKBULK STORAGEMV-Ball Valves307YCH-Y6-BLVL-174741YCH008812-inch ball valve located on the PRT issue line. (Valve 307)XSection 6-6.2.4Notify Facility; Confined SpaceConfined Space-
11185YCH-Y6Y6-JP-8 AIRCRAFT FUEL TANKBULK STORAGEMV-Ball Valves308YCH-Y6-BLVL-174742YCH008822-inch ball valve located on the PRT return line. (Valve 308)XSection 6-6.2.4Notify Facility; Confined SpaceConfined Space-
11185YCH-Y6Y6-JP-8 AIRCRAFT FUEL TANKBULK STORAGEMV-Ball Valves309YCH-Y6-BLVL-174743YCH008832-inch ball valve located on the PRT crossover line. (Valve 309)XSection 6-6.2.4Notify Facility; Confined SpaceConfined Space-
11185YCH-Y6Y6-JP-8 AIRCRAFT FUEL TANKBULK STORAGEMV-Ball Valves310YCH-Y6-BLVL-174864YCH008842-inch ball valve located on the PRT line to the slop tank. (Valve 310)XSection 6-6.2.4Notify Facility; Confined SpaceConfined Space-
11185YCH-Y6Y6-JP-8 AIRCRAFT FUEL TANKBULK STORAGEMV-Ball Valves305YCH-Y6-BLVL-174865YCH008852-inch ball valve located on the PRT return line inside the tank vault. (Valve 305)XSection 6-6.2.4Notify Facility; Confined SpaceConfined Space-
11185YCH-Y6Y6-JP-8 AIRCRAFT FUEL TANKBULK STORAGEMV-Ball Valves303YCH-Y6-BLVL-177876YCH008862-inch ball valve located on the sump pump discharge line inside the tank vault. (Valve 303)XSection 6-6.2.4Notify Facility; Confined SpaceConfined Space-
11185YCH-Y6Y6-JP-8 AIRCRAFT FUEL TANKBULK STORAGEMV-Ball Valves306YCH-Y6-BLVL-174866YCH008873/4-inch ball valve located on top of the HLSO control valve.XSection 6-6.2.4Notify Facility; Confined SpaceConfined Space-
11185YCH-Y6Y6-JP-8 AIRCRAFT FUEL TANKBULK STORAGEMV-Check ValvesYCH-Y6-CKVL-174867YCH008918-inch check valve located on the discharge line for issue pump MS6A.XSection 6-6.2.8Notify Facility; Confined SpaceConfined Space-
11185YCH-Y6Y6-JP-8 AIRCRAFT FUEL TANKBULK STORAGECV-General System Control ValvesYCH-Y6-GSCVL-168069YCH00892Located on the 6 inch receipt lineXXSection 4-3.2.1Operate System to Test; Confined SpaceConfined Space-
11185YCH-Y6Y6-JP-8 AIRCRAFT FUEL TANKBULK STORAGECV-General System Control ValvesYCH-Y6-GSCVL-168071YCH008936-inch control valve located on the return line.XXSection 4-3.2.1Operate System to Test; Confined SpaceConfined Space-
11185YCH-Y6Y6-JP-8 AIRCRAFT FUEL TANKBULK STORAGETA-Tank Pressure/Vacuum VentsYCH-Y6-TPVVT-174744YCH00896Located inside vault near the entranceShand & JursXSection 8-9.3Notify FacilityConfined Space-
11185YCH-Y6Y6-JP-8 AIRCRAFT FUEL TANKBULK STORAGETA-Tank Pressure/Vacuum VentsYCH-Y6-TPVVT-175068YCH00897Located inside vault across from the entranceShand & JursXSection 8-9.3Notify FacilityConfined Space-
11185YCH-Y6Y6-JP-8 AIRCRAFT FUEL TANKBULK STORAGEPM-Vertical Turbine/Sub-merged Turbine PumpsM6AYCH-Y6-VTSP-177877YCH00898Issue pump M6A located inside vaultLayne & BowlerXXXSection 3-8.1.3 / 3-8.3Operate System to Test; Confined SpaceConfined Space-600 gpm
11185YCH-Y6Y6-JP-8 AIRCRAFT FUEL TANKBULK STORAGEPM-Vertical Turbine/Sub-merged Turbine PumpsM6BYCH-Y6-VTSP-174868YCH00899Sump pump M6B located inside vaultLayne & BowlerXXXSection 3-8.1.3 / 3-8.3Operate System to Test; Confined SpaceConfined Space-
11185YCH-Y6Y6-JP-8 AIRCRAFT FUEL TANKBULK STORAGETK-Underground Field-Constructed TanksY6YCH-Y6-UGFET-174869YCH00900Tank Y6XSection 8-6Confined Space-
11185YCH-Y6Y6-JP-8 AIRCRAFT FUEL TANKBULK STORAGEPS-Product Saver TanksYCH-Y6-PRDST-175071YCH00901PRT located on top of the tankXSection 8-9.10Notify FacilityConfined Space-
11185YCH-Y6Y6-JP-8 AIRCRAFT FUEL TANKBULK STORAGETA-Mechanical Tape Gauges (non-ATG)YCH-Y6-MTGA-164494YCH00902Fuel tank gauge located inside vaultShand & JursXSection 8-9.7Confined Space-
11185YCH-Y6Y6-JP-8 AIRCRAFT FUEL TANKBULK STORAGETA-Mechanical Tape Gauges (non-ATG)YCH-Y6-MTGA-164495YCH00903Water tank gauge located inside vaultShand & JursXSection 8-9.7Confined Space-
11185YCH-Y6Y6-JP-8 AIRCRAFT FUEL TANKBULK STORAGEMV-Check ValvesYCH-Y6-CKVL-174870YCH009042-inch check valve located on the sump pump discharge line.XSection 6-6.2.8Notify Facility; Confined SpaceConfined Space-
11185YCH-Y6Y6-JP-8 AIRCRAFT FUEL TANKBULK STORAGETA-External High Level Shutoff Valves (HLSO)YCH-Y6-EHLSVL-174745YCH00905High-level shut off valveXXSection 8-9.6.1Notify FacilityConfined Space-
11185YCH-Y6Y6-JP-8 AIRCRAFT FUEL TANKBULK STORAGEPV-Pressure GaugesYCH-Y6-PVGA-177878YCH00907Pressure gauge located on the outlet side of pump M6AAshcroftXXXSection 6-7.1Notify FacilityConfined Space-
11185YCH-Y6Y6-JP-8 AIRCRAFT FUEL TANKBULK STORAGEPC-Aboveground Piping and Equipment CoatingYCH-Y6-AGPCT-174871YCH00908Coated piping 10 inSection 6-10.1Confined Space-
11185YCH-Y6Y6-JP-8 AIRCRAFT FUEL TANKBULK STORAGEPC-Aboveground Piping and Equipment CoatingYCH-Y6-AGPCT-174872YCH00909Coated piping 6 inSection 6-10.1Confined Space-
11185YCH-Y6Y6-JP-8 AIRCRAFT FUEL TANKBULK STORAGEPC-Aboveground Piping and Equipment CoatingYCH-Y6-AGPCT-175074YCH00910Coated piping 2 inchSection 6-10.1Confined Space-
11186YCH-Y7Y7-JP-8 AIRCRAFT FUEL TANKBULK STORAGEMV-Ball Valves320YCH-Y7-BLVL-175077YCH009132-inch ball valve located on the PRT issue line. (Valve 320)XSection 6-6.2.4Notify Facility; Confined SpaceConfined Space-
11186YCH-Y7Y7-JP-8 AIRCRAFT FUEL TANKBULK STORAGEMV-Ball ValvesYCH-Y7-BLVL-175081YCH009142-inch ball valve located on the PRT return line.XSection 6-6.2.4Notify Facility; Confined SpaceConfined Space-
11186YCH-Y7Y7-JP-8 AIRCRAFT FUEL TANKBULK STORAGEMV-Ball Valves309YCH-Y7-BLVL-174746YCH00915Located on the PRT crossover lineXSection 6-6.2.4Notify Facility; Confined SpaceConfined Space-
11186YCH-Y7Y7-JP-8 AIRCRAFT FUEL TANKBULK STORAGEMV-Ball ValvesYCH-Y7-BLVL-177879YCH009162-inch ball valve located on the PRT line to the slop tank.XSection 6-6.2.4Notify Facility; Confined SpaceConfined Space-
11186YCH-Y7Y7-JP-8 AIRCRAFT FUEL TANKBULK STORAGEMV-Ball Valves316YCH-Y7-BLVL-175083YCH009193/4-inch ball valve located on top of the HLSO control valve.XSection 6-6.2.4Notify Facility; Confined SpaceConfined Space-
11186YCH-Y7Y7-JP-8 AIRCRAFT FUEL TANKBULK STORAGEMV-Check ValvesYCH-Y7-CKVL-177880YCH009238-inch check valve located on the discharge line for issue pump MS7A.XSection 6-6.2.8Notify Facility; Confined SpaceConfined Space-
11186YCH-Y7Y7-JP-8 AIRCRAFT FUEL TANKBULK STORAGECV-General System Control ValvesYCH-Y7-GSCVL-168073YCH00924Located on the 6 inch receipt lineXXSection 4-3.2.1Operate System to Test; Confined SpaceConfined Space-
11186YCH-Y7Y7-JP-8 AIRCRAFT FUEL TANKBULK STORAGECV-General System Control ValvesYCH-Y7-GSCVL-168075YCH009256-inch control valve located on the return line.XXSection 4-3.2.1Operate System to Test; Confined SpaceConfined Space-
11186YCH-Y7Y7-JP-8 AIRCRAFT FUEL TANKBULK STORAGETA-Tank Pressure/Vacuum VentsYCH-Y7-TPVVT-177881YCH00928Located inside vault near the entranceShand & JursXSection 8-9.3Notify FacilityConfined Space-
11186YCH-Y7Y7-JP-8 AIRCRAFT FUEL TANKBULK STORAGETA-Tank Pressure/Vacuum VentsYCH-Y7-TPVVT-177882YCH00929Located inside vault across from the entranceShand & JursXSection 8-9.3Notify FacilityConfined Space-
11186YCH-Y7Y7-JP-8 AIRCRAFT FUEL TANKBULK STORAGEPM-Vertical Turbine/Sub-merged Turbine PumpsM7AYCH-Y7-VTSP-174873YCH00930Issue pump M7A located inside vaultLayne & BowlerXXXSection 3-8.1.3 / 3-8.3Operate System to Test; Confined SpaceConfined Space-600 gpm
11186YCH-Y7Y7-JP-8 AIRCRAFT FUEL TANKBULK STORAGEPM-Vertical Turbine/Sub-merged Turbine PumpsM7BYCH-Y7-VTSP-175086YCH00931Sump pump M7B located inside vaultLayne & BowlerXXXSection 3-8.1.3 / 3-8.3Operate System to Test; Confined SpaceConfined Space-
11186YCH-Y7Y7-JP-8 AIRCRAFT FUEL TANKBULK STORAGETK-Underground Field-Constructed TanksY7YCH-Y7-UGFET-175090YCH00932Tank Y7XSection 8-6Confined Space-
11186YCH-Y7Y7-JP-8 AIRCRAFT FUEL TANKBULK STORAGEPS-Product Saver TanksYCH-Y7-PRDST-174874YCH00933PRT located on top of the tankXSection 8-9.10Notify FacilityConfined Space-
11186YCH-Y7Y7-JP-8 AIRCRAFT FUEL TANKBULK STORAGETA-Mechanical Tape Gauges (non-ATG)YCH-Y7-MTGA-164496YCH00934Fuel tank gauge located inside vaultShand & JursXSection 8-9.7Confined Space-
11186YCH-Y7Y7-JP-8 AIRCRAFT FUEL TANKBULK STORAGETA-Mechanical Tape Gauges (non-ATG)YCH-Y7-MTGA-164497YCH00935Water tank gauge located inside vaultShand & JursXSection 8-9.7Confined Space-
11186YCH-Y7Y7-JP-8 AIRCRAFT FUEL TANKBULK STORAGEMV-Check ValvesYCH-Y7-CKVL-175092YCH009362-inch check valve located on the sump pump discharge line.XSection 6-6.2.8Notify Facility; Confined SpaceConfined Space-
11186YCH-Y7Y7-JP-8 AIRCRAFT FUEL TANKBULK STORAGETA-External High Level Shutoff Valves (HLSO)YCH-Y7-EHLSVL-177883YCH00937High-level shut off valveXXSection 8-9.6.1Notify FacilityConfined Space-
11186YCH-Y7Y7-JP-8 AIRCRAFT FUEL TANKBULK STORAGEPV-Pressure GaugesYCH-Y7-PVGA-174747YCH00939Pressure gauge located on the outlet side of pump M7AAshcroftXXXSection 6-7.1Notify FacilityConfined Space-
11186YCH-Y7Y7-JP-8 AIRCRAFT FUEL TANKBULK STORAGEPC-Aboveground Piping and Equipment CoatingYCH-Y7-AGPCT-175095YCH00940Coated piping 10 inSection 6-10.1Confined Space-
11186YCH-Y7Y7-JP-8 AIRCRAFT FUEL TANKBULK STORAGEPC-Aboveground Piping and Equipment CoatingYCH-Y7-AGPCT-177884YCH00941Coated piping 6 inSection 6-10.1Confined Space-
11186YCH-Y7Y7-JP-8 AIRCRAFT FUEL TANKBULK STORAGEPC-Aboveground Piping and Equipment CoatingYCH-Y7-AGPCT-177885YCH00942Coated piping 2 inchSection 6-10.1Confined Space-
1114225YCH-ST1ST1-SLOP TANK 1BULK STORAGEMV-Ball ValvesYCH-ST1-BLVL-174827YCH01014Located inside valve pit 20 for ST1 from tank Y2HwaSung Co., Ltd.XSection 6-6.2.4Notify Facility; Confined Space
1114225YCH-ST1ST1-SLOP TANK 1BULK STORAGEMV-Ball ValvesYCH-ST1-BLVL-174828YCH01015Located in valve pit 20 for ST1 from tank Y3HwaSung Co., Ltd.XSection 6-6.2.4Notify Facility; Confined Space
1114225YCH-ST1ST1-SLOP TANK 1BULK STORAGEMV-Ball ValvesYCH-ST1-BLVL-177891YCH01016Located in valve pit 20 for ST1 from tank Y1HwaSung Co., Ltd.XSection 6-6.2.4Notify Facility; Confined Space
1114225YCH-ST1ST1-SLOP TANK 1BULK STORAGEMV-Ball ValvesYCH-ST1-BLVL-177892YCH01017Located in valve pit 20 to ST1HwaSung Co., Ltd.XSection 6-6.2.4Notify Facility; Confined Space
1114225YCH-ST1ST1-SLOP TANK 1BULK STORAGESF-Emergency Eyewash/ShowersYCH-ST1-EMEWSH-174829YCH01018Portable emergency eyewash located at ST1Haws CorporationXXXSection 11-3Notify Facility
1114226YCH-ST2ST2-SLOP TANK 2BULK STORAGESF-Emergency Eyewash/ShowersYCH-ST2-EMEWSH-174936YCH01019Portable emergency eyewash located at ST2Haws CorporationXXXSection 11-3Notify Facility
11182YCH-Y3Y3-JP-8 AIRCRAFT FUEL TANKBULK STORAGECS-Containment Drain ValvesYCH-Y3-CSGEN-216374YCH01624529Containment drain valve for the PRT containmentXSection 8-10.1Confined Space-
11182YCH-Y3Y3-JP-8 AIRCRAFT FUEL TANKBULK STORAGEMV-Ball ValvesYCH-Y3-BLVL-177893YCH04282209091/4-inch Isolation ball valve for the pressure gauge located on the outlet side of pump M3A. (Needle valve)XSection 6-6.2.4Notify Facility; Confined SpaceConfined Space-
11182YCH-Y3Y3-JP-8 AIRCRAFT FUEL TANKBULK STORAGETG-Servo GaugeYCH-Y3-SRVGA-177894YCH0428220910Automatic Tank Gauge (ATG)HoneywellXXXSection 8-9.8.3Confined Space-Another Contract
11182YCH-Y3Y3-JP-8 AIRCRAFT FUEL TANKBULK STORAGEMV-Ball ValvesYCH-Y3-BLVL-174937YCH04282209111/2-inch ball valve located on the bottom of the PRT sight glassXSection 6-6.2.4Notify Facility; Confined SpaceConfined Space-
11182YCH-Y3Y3-JP-8 AIRCRAFT FUEL TANKBULK STORAGEMV-Gate ValvesYCH-Y3-GTVL-174830YCH04282209121/4-inch gate valve located on the top of the PRT sight glassXXSection 6-6.2.3Notify Facility; Confined SpaceConfined Space-
11182YCH-Y3Y3-JP-8 AIRCRAFT FUEL TANKBULK STORAGEMV-Gate ValvesYCH-Y3-GTVL-174831YCH04282209133/4-inch gate valve located on the PRT vent pipingXXSection 6-6.2.3Notify Facility; Confined SpaceConfined Space-