FMP POF POH_20251029.xlsx
XLSX spreadsheet 286 KB Posted
- Solicitation number
- DRAFTW912DY26RA005
About this file
This document is a Facility Maintenance Plan (FMP) for the Defense Supply Point (DFSP) Pohang, located in Korea, specifically focusing on a fuel storage and distribution facility. The facility contains (7) JP-8 fuel tanks with various capacities, including (3) 50M-barrel, (2) 7,500-barrel, and (2) 3,000-barrel tanks, along with supporting infrastructure such as (4) pump houses, (10) truck receipt points, (12) truck issue points, (4) pantographs, and fire suppression systems.
The maintenance plan, prepared by APTIM Federal Services, LLC under contract W912DY-21-F-0076, provides detailed maintenance instructions for the facility's components, including filter separators, valves, pumps, and piping systems. The document includes a comprehensive task matrix with maintenance frequencies, component details, and special considerations, covering quarterly, semi-annual, and annual maintenance requirements. The facility is operated by Ahntech Corporation, which performs routine maintenance across daily, weekly, quarterly, and annual schedules. The maintenance plan emphasizes the importance of confined space protocols and requires facility notification and escort for various maintenance activities.
View the file
Other files
Show all 37
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Administrative
| ADMINISTRATIVE | ||
| Location | Installation Name | DFSP Pohang |
| DLA Site Code | POH | |
| RPSUID | 603 | |
| Hours of Operation | 0800-1630 | |
| Address | Pohang, Korea | |
| Contract | Contractor | |
| Contract # | ||
| Local POCs | Primary QAE | |
| QAE Phone | ||
| QAE Email | ||
| Alternate QAE | ||
| Alt QAE Phone | ||
| Alt QAE Email | ||
| Contractor POCs | Contractor PM | |
| Contractor PM Phone | ||
| Contractor PM Email | ||
| Contractor QC Manager | ||
| Contractor QC Phone | ||
| Contractor QC Email | ||
| Contractor SOE | ||
| Contractor SOE Phone | ||
| Contractor SOE Email | ||
| Contractor RM | ||
| Contractor RM Phone | ||
| Contractor RM Email | ||
| Contractor SM | ||
| Contractor SM Phone | ||
| Contractor SM Email | ||
| USACE POCs | USACE PM/COR | |
| USACE PM/COR Phone | ||
| USACE PM/COR Email | ||
| USACE PE | ||
| USACE PE Phone | ||
| USACE PE Email | ||
| USACE KO | ||
| USACE KO Phone | ||
| USACE KO Email | ||
| USACE Monthly Report Inbox |
Pacific Ocean Division, POD-AF
| W912DY-21-F-0076 | &"-,Bold"&16DFSP Pohang |
| POH | Facility Maintenance Plan |
OY3 Q1
&A &P of &N APTIM Federal Services, LLC
Instructions:
This table shows the minimum information required. Additional details should be included based on site specific requirements. Additional POCs may be required.
General Facility Description
| General Facility Description | |
| Installation Name | DFSP Pohang |
| DLA Site Code | POH |
| Location | Pohang, Korea |
| Bulk Storage (fueling facility to support land and aircraft operations): (7) cut and cover JP-8 tanks - (3) 50Mbarrel, (2) 7,500-barrel, (2) 3,000-barrel; (4) pump houses, (10) truck receipt, (12) truck issue, (4) pantographs, (2) 50,000-gallon hydrant tanks, (2) hydrant loop type IV, fire suppression system. | |
| Operations Contractors Ahntech Corporation operates the system and performs routine maintenance, daily, weekly, quarterly and annually. |
Pacific Ocean Division, POD-AF
| W912DY-21-F-0076 | &"-,Bold"&16DFSP Pohang |
| POH | Facility Maintenance Plan |
OY3 Q1
&A &P of &N APTIM Federal Services, LLC
Instructions:
Include a general facility overview and description of each fuel system for the sites in accordance with UFC 3-460-01. Examples include: Bulk Storage Facilities, Aircraft Fueling Facilities, Marine and Dispensing Facilities, Ground Products Fueling Facilities, Alternate POL Facilities, and Support Facilities. Also include facility #s, facility names, fuel type, photos, and any other pertinent information.
Include Site Specific Conditions and Restrictions in this tab.
Figure 3
| Site Location Drawings |
| Figure 3 - Fow Diagram |
Flow diagraphs for each "area"....operational area or facility # or group of facilities.
Pacific Ocean Division, POD-AF
| W912DY-21-F-0076 | &"-,Bold"&16DFSP Pohang |
| POH | Facility Maintenance Plan |
Revision 1
&A &P of &N APTIM Federal Services, LLC
Communication Plan
| W912DY-21-F-0076 | &"-,Bold"&16DFSP Pohang |
| POH | Facility Maintenance Plan |
OY3 Q1
&A &P of &N APTIM Federal Services, LLC
Instructions:
Communication plan shall address in/out briefs, lines of communication, coordination for access, etc.
Site Specific Safety Plan
| W912DY-21-F-0076 | &"-,Bold"&16DFSP Pohang |
| POH | Facility Maintenance Plan |
OY3 Q1
&A &P of &N APTIM Federal Services, LLC
Instructions:
Site Specific Addendum and Activity Hazard Analysis, which are Attachments to the APP, specific to activities or tasks related to recurring maintenance for this site.
PM Schedule
Pacific Ocean Division, POD-AF
| W912DY-21-F-0076 | &"-,Bold"&16&K000000DFSP Pohang |
| POH | Facility Maintenance Plan |
OY3 Q1
&A &P of &N APTIM Federal Services, LLC
Instructions:
Link PM schedule here
Task Matrix
| Applicable Facility Assets | UFC System Level Maintenance Frequency | Special Considerations | ||||||||||||||||||
| RPUID | Real Property Facility # | Facility Name | Operational Area | Component Type | Base Asset Name | Component Unique ID CUID | APTIM Asset ID | Asset Description | Make | Model | Capacity / Size | Quarterly | Semi Annual | Annual | UFC Section Reference | Additional Manufacturer RM Requirements | Operator/Equipment Requirements | System Availability | Other Contract | Comments |
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | TV-Thermal and Pressure Relief Valves | POH-PPL1-TPRVL-175971 | 16612POH | 1-inch pressure relief valve located inside Valve Pit # 5 (right PRV) | Taylor | T-7700-1 | X | X | Section 6-6.3 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | 165 PSI - Set Pressure | |||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Double Block and Bleed Valves | POH-PPL1-DBBVL-163533 | 16613POH | 6-inch double block and bleed valve inside Valve Pit # 5 (right side) | SAMBO IND. CO., LTD. | SBWG01 | X | X | X | Section 6-6.2.5 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | |||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Double Block and Bleed Valves | POH-PPL1-DBBVL-163534 | 16614POH | 6-inch double block and bleed valve located inside Valve Pit # 5 (tee section) | SAMBO IND. CO., LTD. | SBWG01 | X | X | X | Section 6-6.2.5 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | |||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | TV-Thermal and Pressure Relief Valves | POH-PPL1-TPRVL-168815 | 16615POH | 1-inch pressure relief valve located inside Valve Pit # 5 (left PRV) | Taylor | T-7700-1 | X | X | Section 6-6.3 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | 165 PSI - Set Pressure | |||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Double Block and Bleed Valves | POH-PPL1-DBBVL-163535 | 16616POH | 6-inch double block and bleed valve inside Valve Pit # 5 (left side) | SAMBO IND. CO., LTD. | SBWG01 | X | X | X | Section 6-6.2.5 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | |||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | TV-Thermal and Pressure Relief Valves | POH-PPL1-TPRVL-168816 | 16617POH | 1-inch pressure relief valve located inside Valve Pit # 4 | Taylor | T-7700-1 | X | X | Section 6-6.3 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | 165 PSI - Set Pressure | |||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Double Block and Bleed Valves | POH-PPL1-DBBVL-163536 | 16618POH | 6-inch double block and bleed valve located inside Valve Pit # 4 | SAMBO IND. CO., LTD. | SBWG01 | X | X | X | Section 6-6.2.5 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | |||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | TV-Thermal and Pressure Relief Valves | POH-PPL1-TPRVL-169234 | 16619POH | 1-inch pressure relief valve located inside Valve Pit # 6 | Taylor | T-7700-1 | X | X | Section 6-6.3 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | 165 PSI - Set Pressure | |||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Double Block and Bleed Valves | POH-PPL1-DBBVL-163537 | 16620POH | 6-inch double block and bleed valve located inside Valve Pit # 6 | SAMBO IND. CO., LTD. | SBWG01 | X | X | X | Section 6-6.2.5 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | |||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | TV-Thermal and Pressure Relief Valves | POH-PPL1-TPRVL-168905 | 16621POH | 1-inch pressure relief valve located inside Valve Pit # 7 | Taylor | T-7700-1 | X | X | Section 6-6.3 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | 165 PSI - Set Pressure | |||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Double Block and Bleed Valves | POH-PPL1-DBBVL-163538 | 16622POH | 6-inch double block and bleed valve located inside Valve Pit # 7 | SAMBO IND. CO., LTD. | SBWG01 | X | X | X | Section 6-6.2.5 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | |||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | TV-Thermal and Pressure Relief Valves | POH-PPL1-TPRVL-169235 | 16623POH | 1-inch pressure relief valve located inside Valve Pit # 8 | Taylor | T-7700-1 | X | X | Section 6-6.3 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | 165 PSI - Set Pressure | |||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Double Block and Bleed Valves | POH-PPL1-DBBVL-163539 | 16624POH | 6-inch double block and bleed valve located inside Valve Pit # 8 | SAMBO IND. CO., LTD. | SBWG01 | X | X | X | Section 6-6.2.5 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | |||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Double Block and Bleed Valves | POH-PPL1-DBBVL-163558 | 16678POH | 6-inch double block and bleed valve located inside Valve Pit # 3 | SAMBO IND. CO., LTD. | SBWG01 | X | X | X | Section 6-6.2.5 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | |||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | TV-Thermal and Pressure Relief Valves | POH-PPL1-TPRVL-165017 | 16679POH | 1-inch pressure relief valve located inside Valve Pit # 3 | Taylor | T-7700-1 | X | X | Section 6-6.3 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | 165 PSI - Set Pressure | |||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Double Block and Bleed Valves | POH-PPL1-DBBVL-163739 | 30503POH | 6-inch double block and bleed valve located inside Valve Pit # 2 | SAMBO IND. CO., LTD. | SBWG01 | X | X | X | Section 6-6.2.5 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | |||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | TV-Thermal and Pressure Relief Valves | POH-PPL1-TPRVL-169661 | 30504POH | 1-inch pressure relief valve located inside Valve Pit # 2 | Taylor | T-7700-1 | X | X | Section 6-6.3 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | 165 PSI - Set Pressure | |||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | TV-Thermal and Pressure Relief Valves | POH-PPL1-TPRVL-176141 | 30511POH | 1-inch pressure relief valve (inlet to FL-2 Tanks pipeline) inside Valve Pit # 1 | Taylor | T-7700-1 | X | X | Section 6-6.3 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | 165 PSI - Set Pressure | |||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Double Block and Bleed Valves | POH-PPL1-DBBVL-163741 | 30512POH | 6-inch double block and bleed valve located on the FL-2 line inside Valve Pit # 1 | SAMBO IND. CO., LTD. | SBWG01 | X | X | X | Section 6-6.2.5 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | |||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | TV-Thermal and Pressure Relief Valves | POH-PPL1-TPRVL-176142 | 30513POH | 1-inch pressure relief valve (bulk to FL-1 and 2 Tanks pipeline) inside Valve Pit # 1 | Taylor | T-7700-1 | X | X | Section 6-6.3 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | 165 PSI - Set Pressure | |||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | TV-Thermal and Pressure Relief Valves | POH-PPL1-TPRVL-169662 | 30514POH | 1-inch pressure relief valve (return pipeline) inside Valve Pit # 1 | Taylor | T-7700-1 | X | X | Section 6-6.3 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | 165 PSI - Set Pressure | |||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | TV-Thermal and Pressure Relief Valves | POH-PPL1-TPRVL-169663 | 30515POH | 1-inch pressure relief valve (inlet to FL-1 Tanks pipeline) inside Valve Pit # 1 | Taylor | T-7700-1 | X | X | Section 6-6.3 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | 165 PSI - Set Pressure | |||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Double Block and Bleed Valves | POH-PPL1-DBBVL-163743 | 30516POH | 6-inch double block and bleed valve (outlet of Flow Meter) inside Valve Pit # 1 | SAMBO IND. CO., LTD. | SBWG01 | X | X | X | Section 6-6.2.5 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | |||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Double Block and Bleed Valves | POH-PPL1-DBBVL-163745 | 30517POH | 6-inch double block and bleed valve located on the FL-1 line inside Valve Pit # 1 | SAMBO IND. CO., LTD. | SBWG01 | X | X | X | Section 6-6.2.5 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | |||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | TV-Thermal and Pressure Relief Valves | POH-PPL1-TPRVL-176143 | 30518POH | 1-inch pressure relief valve (bulk to aboveground pipeline) inside Valve Pit # 1 | Taylor | T-7700-1 | X | X | Section 6-6.3 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | 165 PSI - Set Pressure | |||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Double Block and Bleed Valves | POH-PPL1-DBBVL-163747 | 30519POH | 6-inch double block and bleed valve (meter bypass line) inside Valve Pit # 1 | SAMBO IND. CO., LTD. | SBWG01 | X | X | X | Section 6-6.2.5 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | |||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Double Block and Bleed Valves | POH-PPL1-DBBVL-163749 | 30520POH | 6-inch double block and bleed valve (inlet to Pig Launcher pipeline) inside Valve Pit # 1 | SAMBO IND. CO., LTD. | SBWG01 | X | X | X | Section 6-6.2.5 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | |||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Double Block and Bleed Valves | POH-PPL1-DBBVL-163751 | 30521POH | 6-inch double block and bleed valve (inlet to Flow Meter) inside Valve Pit # 1 | SAMBO IND. CO., LTD. | SBWG01 | X | X | X | Section 6-6.2.5 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | |||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Double Block and Bleed Valves | POH-PPL1-DBBVL-163787 | 30618POH | 6-inch double block and bleed valve located inside Valve Pit # 15 | Cameron | Truseal 211 | X | X | X | Section 6-6.2.5 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | |||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Double Block and Bleed Valves | V-141 | POH-PPL1-DBBVL-163789 | 30619POH | 6-inch double block and bleed valve located inside Valve Pit # 16 | Cameron | Truseal 211 | X | X | X | Section 6-6.2.5 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | ||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | PC-Aboveground Piping and Equipment Coating | POH-PPL1-AGPCT-173679 | POH0111221448 | 6-inch coated carbon steel piping for the Pig Launcher behind pump house 1 | Section 6-10.1 | CONFINED SPACE; ESCORT REQUIRED- | |||||||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | PC-Aboveground Piping and Equipment Coating | POH-PPL1-AGPCT-173611 | POH0111221459 | 8-inch coated carbon steel piping for the Pig Launcher behind pump house 1 | Section 6-10.1 | CONFINED SPACE; ESCORT REQUIRED- | |||||||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Ball Valves | POH-PPL1-BLVL-166851 | POH01240 | 1-inch isolation ball valve for PRV (30515) located on FL-1 line inside Valve Pit # 1 (upstream) | Flo-Tite | F150 | X | Section 6-6.2.4 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | |||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Ball Valves | POH-PPL1-BLVL-166852 | POH01241 | 1-inch isolation ball valve for PRV (30515) located on FL-1 line inside Valve Pit # 1 (downstream) | Flo-Tite | F150 | X | Section 6-6.2.4 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | |||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Ball Valves | POH-PPL1-BLVL-166853 | POH01242 | 1/2-inch high point ball valve located on the 6-inch pig line inside Valve Pit # 1 | Flo-Tite | F150 | X | Section 6-6.2.4 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | |||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Ball Valves | POH-PPL1-BLVL-166854 | POH01243 | 1-inch isolation ball valve for PRV (30513) located on the metered line inside Valve Pit # 1 (upstream) | Flo-Tite | F150 | X | Section 6-6.2.4 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | |||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Ball Valves | POH-PPL1-BLVL-166855 | POH01244 | 1-inch isolation ball valve for PRV (30513) located on the metered line inside Valve Pit # 1 (downstream) | Flo-Tite | F150 | X | Section 6-6.2.4 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | |||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Ball Valves | POH-PPL1-BLVL-166856 | POH01245 | 1/2-inch high point ball valve located on the 6-inch metered line for FL-1 and FL-2 inside Valve Pit # 1 | Flo-Tite | F150 | X | Section 6-6.2.4 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | |||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Ball Valves | POH-PPL1-BLVL-166857 | POH01246 | 1-inch isolation ball valve for PRV (30514) located on the meter bypass line inside Valve Pit # 1 (upstream) | Flo-Tite | F150 | X | Section 6-6.2.4 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | |||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Ball Valves | POH-PPL1-BLVL-166858 | POH01247 | 1-inch isolation ball valve for PRV (30511) located on FL-2 line inside Valve Pit # 1 (upstream) | Flo-Tite | F150 | X | Section 6-6.2.4 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | |||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Ball Valves | POH-PPL1-BLVL-166859 | POH01248 | 1-inch isolation ball valve for PRV (30511) located on FL-2 line inside Valve Pit # 1 (downstream) | Flo-Tite | F150 | X | Section 6-6.2.4 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | |||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Ball Valves | POH-PPL1-BLVL-148692 | POH01249 | 1/2-inch isolation ball valve for the pressure gauge on the return line inside Valve Pit # 1 | Flo-Tite | F150 | X | Section 6-6.2.4 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | 2000 WOG | ||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Ball Valves | POH-PPL1-BLVL-148693 | POH01250 | 1/2-inch ball valve (pressure gauge tee) on the return line inside Valve Pit # 1 | Flo-Tite | F150 | X | Section 6-6.2.4 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | 2000 WOG | ||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Ball Valves | POH-PPL1-BLVL-148694 | POH01251 | 1-inch isolation ball valve for PRV (30514) located on the meter bypass line inside Valve Pit # 1 (downstream) | Flo-Tite | F150 | X | Section 6-6.2.4 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | |||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Ball Valves | POH-PPL1-BLVL-148695 | POH01252 | 1-inch isolation ball valve for PRV (30518) located on the pig line inside Valve Pit # 1 (upstream) | Flo-Tite | F150 | X | Section 6-6.2.4 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | |||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Ball Valves | POH-PPL1-BLVL-148696 | POH01253 | 1/2-inch isolation ball valve for the pressure gauge on the FL-1 line inside Valve Pit # 1 | Flo-Tite | F150 | X | Section 6-6.2.4 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | 2000 WOG | ||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Ball Valves | POH-PPL1-BLVL-148697 | POH01254 | 1/2-inch ball valve (pressure gauge tee) on FL-1 line inside Valve Pit # 1 | Flo-Tite | F150 | X | Section 6-6.2.4 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | 2000 WOG | ||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Ball Valves | POH-PPL1-BLVL-148698 | POH01255 | 1/2-inch high point ball valve located on the 6-inch meter bypass line inside Valve Pit # 1 | Flo-Tite | F150 | X | Section 6-6.2.4 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | |||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Ball Valves | POH-PPL1-BLVL-148699 | POH01256 | 1-inch isolation ball valve for PRV (30518) located on the pig line inside Valve Pit # 1 (downstream) | Flo-Tite | F150 | X | Section 6-6.2.4 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | |||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Ball Valves | POH-PPL1-BLVL-148700 | POH01257 | 1/2-inch isolation ball valve for the pressure gauge on the FL-2 line inside Valve Pit # 1 | Flo-Tite | F150 | X | Section 6-6.2.4 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | 2000 WOG | ||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Ball Valves | POH-PPL1-BLVL-148701 | POH01258 | 1/2-inch ball valve (pressure gauge tee) on the FL-2 line inside Valve Pit # 1 | Flo-Tite | F150 | X | Section 6-6.2.4 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | 2000 WOG | ||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Check Valves | POH-PPL1-CKVL-173738 | POH01265 | 1-inch check valve (bulk to Pig Launcher) inside Valve Pit # 1 | Powell Valves | X | Section 6-6.2.8 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | ||||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Check Valves | POH-PPL1-CKVL-173710 | POH01266 | 1-inch check valve (bulk to FL-1 and 2 Tanks pipeline) inside Valve Pit # 1 | Powell Valves | X | Section 6-6.2.8 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | ||||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Check Valves | POH-PPL1-CKVL-174078 | POH01267 | 1-inch check valve (return pipeline) inside Valve Pit # 1 | Powell Valves | X | Section 6-6.2.8 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | ||||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | EQ-Air Vent | POH-PPL1-ASSET-177504 | POH01273 | 2-inch air vent located inside Valve Pit # 1 | SPX Flow | MF | Non-Appx G Class | CONFINED SPACE; ESCORT REQUIRED- | STX Flow | ||||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MT-Positive Displacement Meters | POH-PPL1-PDMT-156734 | POH01274 | Flow Meter Tank inside Valve Pit # 1 | Liquid Controls | MSAA75-2 | X | X | Section 3-7.1 | Operate System to Test | CONFINED SPACE; ESCORT REQUIRED- | ||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | SS-Surge Suppressors | POH-PPL1-SRGSP-167455 | POH01275 | 25 Gallon surge suppressor inside Valve Pit # 1 | Young Engineering | 25BSA-27 | X | Section 4-7.5 / 4-7.4 | CONFINED SPACE; ESCORT REQUIRED- | ||||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | FT-Basket Strainer | POH-PPL1-BSTR-177507 | POH01276 | 6-inch strainer inside Valve Pit # 1 | Titan Flow Control, Inc. | X | X | Section 3-6.4 | CONFINED SPACE; ESCORT REQUIRED- | ||||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | PV-Differential Pressure Gauges | POH-PPL1-DPGA-164381 | POH01277 | Direct reading-differential pressure gauge located on the basket strainer inside Valve Pit # 1 | Schultz Engineered Produc | SC-5150-30 | X | X | Section 6-7.2 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | ||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | PC-Aboveground Piping and Equipment Coating | POH-PPL1-AGPCT-174079 | POH01278 | 6-inch coated carbon steel piping located inside all Valve Pits (total 60 lf) | Section 6-10.1 | CONFINED SPACE; ESCORT REQUIRED- | |||||||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | PV-Pressure Gauges | FLVB-2 | POH-PPL1-PVGA-173739 | POH01279 | Pressure gauge inside Valve Pit # 2 | Cole Parmer | X | X | X | Section 6-7.1 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | |||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Ball Valves | POH-PPL1-BLVL-148702 | POH01280 | 2-inch ball valve (low point drain with cam lock connection) located inside Valve Pit # 2 | Flo-Tite | F150 | X | Section 6-6.2.4 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | |||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Ball Valves | POH-PPL1-BLVL-148703 | POH01283 | 1-inch isolation ball valve for PRV located inside Valve Pit # 2 (upstream) | Flo-Tite | F150 | X | Section 6-6.2.4 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | |||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Ball Valves | POH-PPL1-BLVL-148704 | POH01284 | 1-inch isolation ball valve for PRV located inside Valve Pit # 2 (downstream) | Flo-Tite | F150 | X | Section 6-6.2.4 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | |||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Ball Valves | POH-PPL1-BLVL-148705 | POH01285 | 1/2-inch ball valve (high point vent) located inside Valve Pit # 2 | Flo-Tite | F150 | X | Section 6-6.2.4 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | |||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Ball Valves | POH-PPL1-BLVL-148706 | POH01286 | 1/2-inch isolation ball valve for pressure gauge located inside Valve Pit # 2 | Flo-Tite | F150 | X | Section 6-6.2.4 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | 2000 WOG | ||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Ball Valves | POH-PPL1-BLVL-148707 | POH01287 | 1/2-inch ball valve (pressure gauge tee) located inside Valve Pit # 2 | Flo-Tite | F150 | X | Section 6-6.2.4 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | 2000 WOG | ||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Check Valves | POH-PPL1-CKVL-173711 | POH01288 | 1-inch check valve inside Valve Pit # 2 | Powell Valves | X | Section 6-6.2.8 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | ||||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Ball Valves | POH-PPL1-BLVL-148708 | POH01290 | 1/2-inch ball valve (high point vent) located inside Valve Pit # 3 | Flo-Tite | F150 | X | Section 6-6.2.4 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | |||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Ball Valves | POH-PPL1-BLVL-148709 | POH01291 | 1-inch isolation ball valve for PRV located inside Valve Pit # 3 (upstream) | Flo-Tite | F150 | X | Section 6-6.2.4 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | |||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Ball Valves | POH-PPL1-BLVL-148710 | POH01292 | 1-inch isolation ball valve for PRV located inside Valve Pit # 3 (downstream) | Flo-Tite | F150 | X | Section 6-6.2.4 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | |||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Ball Valves | POH-PPL1-BLVL-148711 | POH01293 | 1/2-inch isolation ball valve for pressure gauge located inside Valve Pit # 3 | Flo-Tite | F150 | X | Section 6-6.2.4 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | 2000 WOG | ||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Ball Valves | POH-PPL1-BLVL-148712 | POH01294 | 1/2-inch ball valve (pressure gauge tee) located inside Valve Pit # 3 | Flo-Tite | F150 | X | Section 6-6.2.4 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | 2000 WOG | ||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Ball Valves | POH-PPL1-BLVL-148713 | POH01295 | 2-inch ball valve (high point with cam lock connection) located inside Valve Pit # 3 | Flo-Tite | F150 | X | Section 6-6.2.4 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | |||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | PV-Pressure Gauges | POH-PPL1-PVGA-173740 | POH01296 | Pressure gauge located inside Valve Pit # 3 | Cole Parmer | X | X | X | Section 6-7.1 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | ||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | PV-Pressure Gauges | FLVB 1-1 | POH-PPL1-PVGA-173712 | POH01298 | Pressure gauge located on FL-1 line inside Valve Pit # 1 | Wika | X | X | X | Section 6-7.1 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | |||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Ball Valves | POH-PPL1-BLVL-148714 | POH01300 | 1/2-inch ball valve (high point vent) located inside Valve Pit # 4 | Flo-Tite | F150 | X | Section 6-6.2.4 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | |||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Ball Valves | POH-PPL1-BLVL-148715 | POH01301 | 1-inch isolation ball valve for PRV located inside Valve Pit # 4 (upstream) | Flo-Tite | F150 | X | Section 6-6.2.4 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | |||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Ball Valves | POH-PPL1-BLVL-148716 | POH01302 | 1-inch isolation ball valve for PRV located inside Valve Pit # 4 (downstream) | Flo-Tite | F150 | X | Section 6-6.2.4 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | |||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Ball Valves | POH-PPL1-BLVL-148717 | POH01303 | 1/2-inch isolation ball valve for pressure gauge located inside Valve Pit # 4 | Flo-Tite | F150 | X | Section 6-6.2.4 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | 2000 WOG | ||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Ball Valves | POH-PPL1-BLVL-148718 | POH01304 | 1/2-inch ball valve (pressure gauge tee) located inside Valve Pit # 4 | Flo-Tite | F150 | X | Section 6-6.2.4 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | 2000 WOG | ||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Ball Valves | POH-PPL1-BLVL-148719 | POH01305 | 2-inch ball valve (low point drain with cam lock connection) located inside Valve Pit # 4 | Flo-Tite | F150 | X | Section 6-6.2.4 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | |||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | PV-Pressure Gauges | POH-PPL1-PVGA-177510 | POH01306 | Pressure gauge located inside Valve Pit # 4 | Palmer Instruments | X | X | X | Section 6-7.1 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | ||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | PV-Pressure Gauges | FLVB 1-2 | POH-PPL1-PVGA-174080 | POH01308 | Pressure gauge located on the strainer DP gauge inside Valve Pit # 1 | Wika | X | X | X | Section 6-7.1 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | |||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Ball Valves | POH-PPL1-BLVL-148720 | POH01312 | 2-inch ball valve (high point with cam lock connection) located inside Valve Pit # 5 | Flo-Tite | F150 | X | Section 6-6.2.4 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | |||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Ball Valves | POH-PPL1-BLVL-148721 | POH01314 | 1/2-inch ball valve (high point vent) located inside Valve Pit # 5 | Flo-Tite | F150 | X | Section 6-6.2.4 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | |||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Ball Valves | POH-PPL1-BLVL-148722 | POH01315 | 1-inch isolation ball valve for PRV 16615 located inside Valve Pit # 5 (upstream) | Flo-Tite | F150 | X | Section 6-6.2.4 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | |||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Ball Valves | POH-PPL1-BLVL-148723 | POH01316 | 1-inch isolation ball valve for PRV 16615 located inside Valve Pit # 5 (downstream) | Flo-Tite | F150 | X | Section 6-6.2.4 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | |||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Ball Valves | POH-PPL1-BLVL-148724 | POH01317 | 1-inch isolation ball valve for PRV 16612 located inside Valve Pit # 5 (upstream) | Flo-Tite | F150 | X | Section 6-6.2.4 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | |||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Ball Valves | POH-PPL1-BLVL-148725 | POH01318 | 1-inch isolation ball valve for PRV 16612 located inside Valve Pit # 5 (downstream) | Flo-Tite | F150 | X | Section 6-6.2.4 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | |||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Ball Valves | POH-PPL1-BLVL-148726 | POH01321 | 1/2-inch isolation ball valve for pressure gauge located inside Valve Pit # 5 | Flo-Tite | F150 | X | Section 6-6.2.4 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | 2000 WOG | ||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Ball Valves | POH-PPL1-BLVL-148727 | POH01322 | 1/2-inch ball valve (pressure gauge tee) located inside Valve Pit # 5 | Flo-Tite | F150 | X | Section 6-6.2.4 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | 2000 WOG | ||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Ball Valves | POH-PPL1-BLVL-148728 | POH01323 | 3/4-inch ball valve (high point vent) located on the pig launcher behind pump house 1 | Flo-Tite | F150 | X | Section 6-6.2.4 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | |||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | PV-Pressure Gauges | POH-PPL1-PVGA-173713 | POH01324 | Pressure gauge located inside Valve Pit # 5 | Palmer Instruments | X | X | X | Section 6-7.1 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | ||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | CS-Dike/Berm Floors (curbed) | POH-PPL1-ETHDW-167850 | POH01326 | 9 feet x 7 feet Containment for Valve Pit # 5 | X | Section 8-10.2.2 | CONFINED SPACE; ESCORT REQUIRED- | ||||||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Ball Valves | POH-PPL1-BLVL-148729 | POH01328 | 2-inch ball valve (low point drain with cam lock connection) located inside Valve Pit # 6 | Flo-Tite | F150 | X | Section 6-6.2.4 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | |||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Ball Valves | POH-PPL1-BLVL-148730 | POH01329 | 1-inch isolation ball valve for PRV located inside Valve Pit # 6 (upstream) | Flo-Tite | F150 | X | Section 6-6.2.4 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | |||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Ball Valves | POH-PPL1-BLVL-148731 | POH01330 | 1-inch isolation ball valve for PRV located inside Valve Pit # 6 (downstream) | Flo-Tite | F150 | X | Section 6-6.2.4 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | |||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Ball Valves | POH-PPL1-BLVL-148732 | POH01331 | 1/2-inch ball valve (high point vent) located inside Valve Pit # 6 | Flo-Tite | F150 | X | Section 6-6.2.4 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | |||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Ball Valves | POH-PPL1-BLVL-148733 | POH01332 | 1/2-inch isolation ball valve for pressure gauge located inside Valve Pit # 6 | Flo-Tite | F150 | X | Section 6-6.2.4 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | 2000 WOG | ||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Ball Valves | POH-PPL1-BLVL-148734 | POH01333 | 1/2-inch ball valve (pressure gauge tee) located inside Valve Pit # 6 | Flo-Tite | F150 | X | Section 6-6.2.4 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | 2000 WOG | ||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | PV-Pressure Gauges | POH-PPL1-PVGA-177512 | POH01334 | Pressure gauge located inside Valve Pit # 6 | Cole Parmer | X | X | X | Section 6-7.1 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | ||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | PV-Pressure Gauges | FLBV 1-3 | POH-PPL1-PVGA-177514 | POH01336 | Pressure gauge located on the return line inside Valve Pit # 1 | Palmer Instruments | X | X | X | Section 6-7.1 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | |||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Ball Valves | POH-PPL1-BLVL-148735 | POH01338 | 1/2-inch ball valve (high point vent) located inside Valve Pit # 7 | Flo-Tite | F150 | X | Section 6-6.2.4 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | |||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Ball Valves | POH-PPL1-BLVL-148736 | POH01339 | 1-inch isolation ball valve for PRV located inside Valve Pit # 7 (upstream) | Flo-Tite | F150 | X | Section 6-6.2.4 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | |||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Ball Valves | POH-PPL1-BLVL-148737 | POH01340 | 1-inch isolation ball valve for PRV located inside Valve Pit # 7 (downstream) | Flo-Tite | F150 | X | Section 6-6.2.4 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | |||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Ball Valves | POH-PPL1-BLVL-148738 | POH01341 | 2-inch ball valve (high point with cam lock connection) located inside Valve Pit # 7 | Flo-Tite | F150 | X | Section 6-6.2.4 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | |||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Ball Valves | POH-PPL1-BLVL-148739 | POH01342 | 1/2-inch isolation ball valve for pressure gauge located inside Valve Pit # 7 | Flo-Tite | F150 | X | Section 6-6.2.4 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | 2000 psi | ||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Ball Valves | POH-PPL1-BLVL-148740 | POH01343 | 1/2-inch ball valve (pressure gauge tee) located inside Valve Pit # 7 | Flo-Tite | F150 | X | Section 6-6.2.4 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | 2000 psi | ||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Ball Valves | POH-PPL1-BLVL-148741 | POH01344 | 3-inch ball valve located inside Valve Pit # 7 at the flight line | Rockwell Valves | X | Section 6-6.2.4 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | ||||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | PV-Pressure Gauges | VB 7-1 | POH-PPL1-PVGA-174088 | POH01345 | Pressure gauge located inside Valve Pit # 7 | Cole Parmer | X | X | X | Section 6-7.1 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | |||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | PV-Pressure Gauges | FLVB 1-4 | POH-PPL1-PVGA-174092 | POH01347 | Pressure gauge located on FL-2 line inside Valve Pit # 1 | Palmer Instruments | X | X | X | Section 6-7.1 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | |||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Ball Valves | POH-PPL1-BLVL-161064 | POH01349 | 1-inch isolation ball valve for PRV located inside Valve Pit # 8 (upstream) | Flo-Tite | F150 | X | Section 6-6.2.4 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | |||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Ball Valves | POH-PPL1-BLVL-177517 | POH01350 | 1-inch isolation ball valve for PRV located inside Valve Pit # 8 (downstream) | Flo-Tite | F150 | X | Section 6-6.2.4 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | |||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Ball Valves | POH-PPL1-BLVL-177519 | POH01351 | 1/2-inch ball valve (high point vent) located inside Valve Pit # 8 | Flo-Tite | F150 | X | Section 6-6.2.4 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | |||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Ball Valves | POH-PPL1-BLVL-173741 | POH01352 | 1/2-inch isolation ball valve for pressure gauge located inside Valve Pit # 8 | Flo-Tite | F150 | X | Section 6-6.2.4 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | 2000 psi | ||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Ball Valves | POH-PPL1-BLVL-177521 | POH01353 | 1/2-inch ball valve (pressure gauge tee) located inside Valve Pit # 8 | Flo-Tite | F150 | X | Section 6-6.2.4 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | 2000 psi | ||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Ball Valves | POH-PPL1-BLVL-177523 | POH01354 | 3-inch ball valve located inside Valve Pit # 8 at the flight line | Rockwell Valves | X | Section 6-6.2.4 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | ||||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | PV-Pressure Gauges | VB 8-1 | POH-PPL1-PVGA-173714 | POH01355 | Pressure gauge located inside Valve Pit # 8 | Wika | X | X | X | Section 6-7.1 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | |||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Ball Valves | POH-PPL1-BLVL-174095 | POH01358 | 3-inch ball valve located inside Valve Pit # 9 at the flight line | Rockwell Valves | X | Section 6-6.2.4 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | ||||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Ball Valves | V-142 | POH-PPL1-BLVL-174096 | POH01361 | 2-inch ball valve for low point drain on unloading line located inside Valve Pit # 16 | DC | X | Section 6-6.2.4 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | |||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Ball Valves | V-140 | POH-PPL1-BLVL-177526 | POH01362 | 2-inch ball valve low point drain on load station line located inside Valve Pit # 16 | DC | X | Section 6-6.2.4 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | |||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | EQ-Air Vent | POH-PPL1-ASSET-173742 | POH01363 | 2-inch air vent located inside Pig Launcher at Flightline Area | SPX Flow | MF | Non-Appx G Class | CONFINED SPACE; ESCORT REQUIRED- | STX Flow | ||||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Ball Valves | POH-PPL1-BLVL-173743 | POH01364 | 3/4-inch ball valve (high point vent) on the Pig Launcher at Flightline Area | Flo-Tite | F150 | X | Section 6-6.2.4 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | |||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Ball Valves | POH-PPL1-BLVL-177528 | POH01365 | 1/2-inch isolation ball valve for the pressure gauge located on the Pig Launcher at Flightline Area | Flo-Tite | F150 | X | Section 6-6.2.4 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | 2000 WOG | ||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Ball Valves | POH-PPL1-BLVL-174098 | POH01366 | 1/2-inch ball valve (pressure gauge tee) on the Pig Launcher at Flightline Area | Flo-Tite | F150 | X | Section 6-6.2.4 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | 2000 WOG | ||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Ball Valves | POH-PPL1-BLVL-177496 | POH01367 | 2-inch ball valve (low point drain) on the Pig Launcher at the Flightline Area | Flo-Tite | F150 | X | Section 6-6.2.4 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | |||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | PV-Pressure Gauges | POH-PPL1-PVGA-173715 | POH01368 | Pressure gauge located on the Pig Launcher at the Flightline Area | Palmer Instruments | X | X | X | Section 6-7.1 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | ||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | PV-Pressure Gauges | POH-PPL1-PVGA-174117 | POH01369 | Pressure gauge located on the Pig Launcher behind pump house 1 | Palmer Instruments | X | X | X | Section 6-7.1 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | 0-300 psi | |||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | PC-Aboveground Piping and Equipment Coating | POH-PPL1-AGPCT-173744 | POH01370 | 6-inch coated carbon steel piping for the Pig Launcher at the Flightline Area | Section 6-10.1 | CONFINED SPACE; ESCORT REQUIRED- | |||||||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | PC-Aboveground Piping and Equipment Coating | POH-PPL1-AGPCT-173745 | POH01371 | 8-inch coated carbon steel piping for the Pig Launcher at the Flightline Area | Section 6-10.1 | CONFINED SPACE; ESCORT REQUIRED- | |||||||||||
| PWS Appx K-3 | POH-TBD03 | TBD03-Lights | Blk Strg/Hydrant | EC-Lighting | POH-TBD03-LIGHT-174120 | POH01375 | Eight light poles each with 2 lights. 16 lights total. Located at TUS-1, TLS-2, and TLS-3. | X | X | Section 9-1.8 | At Height-Manlift Required | |||||||||
| PWS Appx K-3 | POH-TBD05 | TBD05-CENTRALIZED CATHODIC PROTECTION SYSTEM - Category Cd Archive | Blk Strg/Hydrant | CP-Cathodic Protection System | POH-TBD05-CP-165391 | POH01376 | Cathodic Protection Rectifier (POL / Fire Protection Pumphouse # 1) | Section 9-2.1 | Another Contract | |||||||||||
| PWS Appx K-3 | POH-TBD05 | TBD05-CENTRALIZED CATHODIC PROTECTION SYSTEM - Category Cd Archive | Blk Strg/Hydrant | CP-Cathodic Protection System | POH-TBD05-CP-165392 | POH01377 | Cathodic Protection Rectifier (POL Pumphouse # 2) | Section 9-2.1 | Another Contract | |||||||||||
| PWS Appx K-3 | POH-TBD05 | TBD05-CENTRALIZED CATHODIC PROTECTION SYSTEM - Category Cd Archive | Blk Strg/Hydrant | CP-Cathodic Protection System | POH-TBD05-CP-165393 | POH01378 | Cathodic Protection Rectifier (POL Pumphouse # 3) | Section 9-2.1 | Another Contract | |||||||||||
| PWS Appx K-3 | POH-TBD05 | TBD05-CENTRALIZED CATHODIC PROTECTION SYSTEM - Category Cd Archive | Blk Strg/Hydrant | CP-Cathodic Protection System | POH-TBD05-CP-165394 | POH01379 | Cathodic Protection Rectifier (POL Pumphouse # 4) | Section 9-2.1 | Another Contract | |||||||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Ball Valves | POH-PPL1-BLVL-174222 | POH01604 | 2-inch ball valve (low point drain) on the pig launcher behind pump house 1 | X | Section 6-6.2.4 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | |||||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Ball Valves | POH-PPL1-BLVL-173886 | POH01608 | 1/2-inch isolation ball valve for pressure gauge located on the pig launcher behind pump house 1 | X | Section 6-6.2.4 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | |||||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Ball Valves | POH-PPL1-BLVL-174224 | POH01612 | 1/2-inch ball valve (pressure gauge tee) located on the pig launcher behind pump house 1 | X | Section 6-6.2.4 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | |||||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Ball Valves | POH-PPL1-BLVL-173978 | POH0421221058 | 1-inch ball valve on top of the flow meter located inside Valve Pit # 1 | Velan | X | Section 6-6.2.4 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | ||||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | MV-Ball Valves | POH-PPL1-BLVL-173979 | POH0421221059 | 2-inch ball valve located on the pig line (high point) inside Valve Pit # 1 | Mars Valve Co. Ltd. | X | Section 6-6.2.4 | Notify Facility | CONFINED SPACE; ESCORT REQUIRED- | ||||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | CS-Pipe Penetrations | POH-PPL1-PPEN-200245 | POH442301 | Pipe Penetrations (Valve Pit #1) | X | X | Section 8-10.6 | Confined Space | CONFINED SPACE; ESCORT REQUIRED- | ||||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | CS-Pipe Penetrations | POH-PPL1-PPEN-200246 | POH442302 | Pipe Penetrations (Valve Pit #2) | X | X | Section 8-10.6 | Confined Space | CONFINED SPACE; ESCORT REQUIRED- | ||||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | CS-Pipe Penetrations | POH-PPL1-PPEN-200247 | POH442303 | Pipe Penetrations (Valve Pit #3) | X | X | Section 8-10.6 | Confined Space | CONFINED SPACE; ESCORT REQUIRED- | ||||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | CS-Pipe Penetrations | POH-PPL1-PPEN-200248 | POH442304 | Pipe Penetrations (Valve Pit #4) | X | X | Section 8-10.6 | Confined Space | CONFINED SPACE; ESCORT REQUIRED- | ||||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | CS-Pipe Penetrations | POH-PPL1-PPEN-200249 | POH442305 | Pipe Penetrations (Valve Pit #5) | X | X | Section 8-10.6 | Confined Space | CONFINED SPACE; ESCORT REQUIRED- | ||||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | CS-Pipe Penetrations | POH-PPL1-PPEN-200250 | POH442306 | Pipe Penetrations (Valve Pit #6) | X | X | Section 8-10.6 | Confined Space | CONFINED SPACE; ESCORT REQUIRED- | ||||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | CS-Pipe Penetrations | POH-PPL1-PPEN-200251 | POH442307 | Pipe Penetrations (Valve Pit #7) | X | X | Section 8-10.6 | Confined Space | CONFINED SPACE; ESCORT REQUIRED- | ||||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | CS-Pipe Penetrations | POH-PPL1-PPEN-200252 | POH442308 | Pipe Penetrations (Valve Pit #8) | X | X | Section 8-10.6 | Confined Space | CONFINED SPACE; ESCORT REQUIRED- | ||||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | CS-Pipe Penetrations | POH-PPL1-PPEN-200253 | POH442315 | Pipe Penetrations (Valve Pit #15) | X | X | Section 8-10.6 | Confined Space | CONFINED SPACE; ESCORT REQUIRED- | ||||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | CS-Pipe Penetrations | POH-PPL1-PPEN-200254 | POH442316 | Pipe Penetrations (Valve Pit #16) | X | X | Section 8-10.6 | Confined Space | CONFINED SPACE; ESCORT REQUIRED- | ||||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | CS-Pipe Penetrations | POH-PPL1-PPEN-200255 | POH442317 | Pipe Penetrations (Flightline Valve Pit #7) | X | X | Section 8-10.6 | Confined Space | CONFINED SPACE; ESCORT REQUIRED- | ||||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | CS-Pipe Penetrations | POH-PPL1-PPEN-200256 | POH442318 | Pipe Penetrations (Flightline Valve Pit #8) | X | X | Section 8-10.6 | Confined Space | CONFINED SPACE; ESCORT REQUIRED- | ||||||||
| 162315 | POH-PPL1 | PPL1-POL PIPELINE | Blk Strg/Hydrant | CS-Pipe Penetrations | POH-PPL1-PPEN-200257 | POH442319 | Pipe Penetrations (Flightline Valve Pit #9) | X | X | Section 8-10.6 | Confined Space | CONFINED SPACE; ESCORT REQUIRED- | ||||||||
| 1112406 | POH-2011-22 | 2011-22-POL PUMP HOUSE 2 | Bulk Storage | TV-Thermal and Pressure Relief Valves | POH-2011-22-TPRVL-169042 | 16547POH | 1-inch pressure relief valve on filter separator (FS-6) | Taylor | T8250-1 | X | X | Section 6-6.3 | Notify Facility | 225 PSI - Set Pressure | ||||||
| 1112406 | POH-2011-22 | 2011-22-POL PUMP HOUSE 2 | Bulk Storage | TV-Thermal and Pressure Relief Valves | POH-2011-22-TPRVL-169043 | 16552POH | 1-inch pressure relief valve on filter separator (FS-5) | Taylor | T8250-1 | X | X | Section 6-6.3 | Notify Facility | 225 PSI - Set Pressure | ||||||
| 1112406 | POH-2011-22 | 2011-22-POL PUMP HOUSE 2 | Bulk Storage | TV-Thermal and Pressure Relief Valves | POH-2011-22-TPRVL-175970 | 16553POH | 1-inch pressure relief valve on filter separator (FS-11) | Taylor | T8200-1 | X | X | Section 6-6.3 | Notify Facility | 225 PSI - Set Pressure | ||||||
| 1112406 | POH-2011-22 | 2011-22-POL PUMP HOUSE 2 | Bulk Storage | TV-Thermal and Pressure Relief Valves | POH-2011-22-TPRVL-169044 | 16554POH | 1-inch pressure relief valve on filter separator (FS-12) | Taylor | T8250-1 | X | X | Section 6-6.3 | Notify Facility | 275 PSI - Set Pressure | ||||||
| 1113656 | POH-TUS2 | TUS2-TRUCK UNLOADING STATION 2 | Bulk Storage | TV-Thermal and Pressure Relief Valves | POH-TUS2-TPRVL-168813 | 16555POH | 1-inch pressure relief valve located at TUS 2-1 | Taylor | T8250-1 | X | X | Section 6-6.3 | Notify Facility | 225 PSI - Set Pressure | ||||||
| 1113656 | POH-TUS2 | TUS2-TRUCK UNLOADING STATION 2 | Bulk Storage | TV-Thermal and Pressure Relief Valves | POH-TUS2-TPRVL-169045 | 16556POH | 1-inch pressure relief valve located at TUS 2-2 | Taylor | T8250-1 | X | X | Section 6-6.3 | Notify Facility | 225 PSI - Set Pressure | ||||||
| 1113656 | POH-TUS2 | TUS2-TRUCK UNLOADING STATION 2 | Bulk Storage | TV-Thermal and Pressure Relief Valves | POH-TUS2-TPRVL-169046 | 16557POH | 1-inch pressure relief valve located at TUS 2-3 | Taylor | T8250-1 | X | X | Section 6-6.3 | Notify Facility | 225 PSI - Set Pressure | ||||||
| 1113650 | POH-TUS3 | TUS3-TRUCK UNLOADING STATION 3 | Bulk Storage | TV-Thermal and Pressure Relief Valves | POH-TUS3-TPRVL-168899 | 16558POH | 1 inch pressure relief valve located at TUS 3-3 | Taylor Valve | T-8250-1 | X | X | Section 6-6.3 | Notify Facility | Set pressure 225 psig | ||||||
| 1113650 | POH-TUS3 | TUS3-TRUCK UNLOADING STATION 3 | Bulk Storage | TV-Thermal and Pressure Relief Valves | POH-TUS3-TPRVL-168814 | 16559POH | 1-inch pressure relief valve located at TUS 3-2 | Taylor Valve | T-8250-1 | X | X | Section 6-6.3 | Notify Facility | 225 PSI - Set Pressure | ||||||
| 1112404 | POH-2011-23 | 2011-23-POL PUMP HOUSE 3 | Bulk Storage | TV-Thermal and Pressure Relief Valves | POH-2011-23-TPRVL-168900 | 16560POH | 1-inch pressure relief valve on filter separator (FS-7) | Taylor Valve | T-8250-1 | X | X | Section 6-6.3 | Notify Facility | Set pressure 225 psig | ||||||
| 1113650 | POH-TUS3 | TUS3-TRUCK UNLOADING STATION 3 | Bulk Storage | TV-Thermal and Pressure Relief Valves | POH-TUS3-TPRVL-169047 | 16561POH | 1-inch pressure relief valve located at TUS 3-1 | Taylor | T8250-1 | X | X | Section 6-6.3 | Notify Facility | 225 PSI - Set Pressure | ||||||
| 1113648 | POH-TLS3 | TLS3-TRUCK LOADING STATION 3 | Bulk Storage | MV-Ball Valves | POH-TLS3-BLVL-157019 | 16562POH | 4-inch ball valve located at TLS-3A (meter M9 side) | Flow-Tek | RF 15 | X | Section 6-6.2.4 | Notify Facility | ||||||||
| 1113648 | POH-TLS3 | TLS3-TRUCK LOADING STATION 3 | Bulk Storage | MV-Double Block and Bleed Valves | POH-TLS3-DBBVL-163498 | 16563POH | 4-inch double block and bleed valve located on the return line for TLS-3A | General Valve | Truseal 211 | X | X | X | Section 6-6.2.5 | Notify Facility | ||||||
| 1113648 | POH-TLS3 | TLS3-TRUCK LOADING STATION 3 | Bulk Storage | MV-Ball Valves | POH-TLS3-BLVL-157020 | 16564POH | 4-inch ball valve located at TLS-3A (meter M10 side) | Flow-Tek | RF 15 | X | Section 6-6.2.4 | Notify Facility | ||||||||
| 1113648 | POH-TLS3 | TLS3-TRUCK LOADING STATION 3 | Bulk Storage | MV-Double Block and Bleed Valves | POH-TLS3-DBBVL-163499 | 16565POH | 4-inch double block and bleed valve located at TLS-3A for meter M10 | General Valve | Truseal 211 | X | X | X | Section 6-6.2.5 | Notify Facility | ||||||
| 1113648 | POH-TLS3 | TLS3-TRUCK LOADING STATION 3 | Bulk Storage | MV-Double Block and Bleed Valves | POH-TLS3-DBBVL-163500 | 16566POH | 4-inch double block and bleed valve located at TLS-3A for meter M9 | General Valve | Truseal 211 | X | X | X | Section 6-6.2.5 | Notify Facility | ||||||
| 1113648 | POH-TLS3 | TLS3-TRUCK LOADING STATION 3 | Bulk Storage | MV-Ball Valves | POH-TLS3-BLVL-157021 | 16567POH | 4-inch ball valve located at TLS-3B (meter M12 side) | Flow-Tek | RF 15 | X | Section 6-6.2.4 | Notify Facility | ||||||||
| 1113648 | POH-TLS3 | TLS3-TRUCK LOADING STATION 3 | Bulk Storage | MV-Double Block and Bleed Valves | POH-TLS3-DBBVL-163501 | 16568POH | 4-inch double block and bleed valve located on the return line for TLS-3B | General Valve | Truseal 211 | X | X | X | Section 6-6.2.5 | Notify Facility | ||||||
| 1113648 | POH-TLS3 | TLS3-TRUCK LOADING STATION 3 | Bulk Storage | MV-Ball Valves | POH-TLS3-BLVL-157022 | 16569POH | 4-inch ball valve located at TLS-3B (meter M11 side) | Flow-Tek | RF 15 | X | Section 6-6.2.4 | Notify Facility | ||||||||
| 1113648 | POH-TLS3 | TLS3-TRUCK LOADING STATION 3 | Bulk Storage | MV-Double Block and Bleed Valves | POH-TLS3-DBBVL-163502 | 16570POH | 4-inch double block and bleed valve located at TLS-3B for meter M11 | General Valve | Truseal 211 | X | X | X | Section 6-6.2.5 | Notify Facility | ||||||
| 1113648 | POH-TLS3 | TLS3-TRUCK LOADING STATION 3 | Bulk Storage | MV-Double Block and Bleed Valves | POH-TLS3-DBBVL-163503 | 16571POH | 4-inch double block and bleed valve located at TLS-3B for meter M12 | General Valve | Truseal 211 | X | X | X | Section 6-6.2.5 | Notify Facility | ||||||
| 1113648 | POH-TLS3 | TLS3-TRUCK LOADING STATION 3 | Bulk Storage | MV-Ball Valves | POH-TLS3-BLVL-157023 | 16572POH | 4-inch ball valve located at TLS-3C (meter M13 side) | Flow-Tek | RF 15 | X | Section 6-6.2.4 | Notify Facility |