FMP POF K-16_20251029.xlsx
XLSX spreadsheet 95 KB Posted
- Solicitation number
- DRAFTW912DY26RA005
About this file
This file is a Facility Maintenance Plan (FMP) for the K-16 Air Base located in Seongnam, Korea, developed for the U.S. Army Corps of Engineers Pacific Ocean Division under contract W912DY-21-F-0076. The document provides comprehensive details about the site's petroleum, oils, and lubricants (POL) facilities, including two JP-8 underground tanks (35,000-gallon), one Mogas underground tank (2,500-gallon), filter separators, dispensers, truck loading/unloading systems, and associated infrastructure.
The maintenance plan includes detailed asset inventories, maintenance schedules, and technical specifications for various components such as valves, pumps, filter separators, dispensers, and electrical systems. Key facilities include underground fuel storage tanks, truck loading areas with bottom and top loading capabilities, vehicle fuel dispensers for JP-8 and Mogas, and supporting infrastructure like canopies, static grounding systems, and containment areas. The document is meticulously organized with specific maintenance requirements, component unique identifiers (CUID), and references to Unified Facilities Criteria (UFC) sections, indicating a structured approach to facility maintenance and operational readiness.
View the file
Other files
Show all 37
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Administrative
| ADMINISTRATIVE | ||
| Location | Installation Name | K16 Air Base |
| DLA Site Code | K16 | |
| RPSUID | 5675 | |
| Hours of Operation | 0800-1630 | |
| Address | Seongnam, Korea | |
| Contract | Contractor | |
| Contract # | ||
| Local POCs | Primary QAE | |
| QAE Phone | ||
| QAE Email | ||
| Alternate QAE | ||
| Alt QAE Phone | ||
| Alt QAE Email | ||
| Contractor POCs | Contractor PM | |
| Contractor PM Phone | ||
| Contractor PM Email | ||
| Contractor QC Manager | ||
| Contractor QC Phone | ||
| Contractor QC Email | ||
| Contractor SOE | ||
| Contractor SOE Phone | ||
| Contractor SOE Email | ||
| Contractor RM | ||
| Contractor RM Phone | ||
| Contractor RM Email | ||
| Contractor SM | ||
| Contractor SM Phone | ||
| Contractor SM Email | ||
| USACE POCs | USACE PM/COR | |
| USACE PM/COR Phone | ||
| USACE PM/COR Email | ||
| USACE PE | ||
| USACE PE Phone | ||
| USACE PE Email | ||
| USACE KO | ||
| USACE KO Phone | ||
| USACE KO Email | ||
| USACE Monthly Report Inbox |
Pacific Ocean Division, POD-AF
| W912DY-21-F-0076 | &"-,Bold"&16K16 Air Base |
| K16 | Facility Maintenance Plan |
OY3 Q1
&A &P of &N APTIM Federal Services, LLC
Instructions:
This table shows the minimum information required. Additional details should be included based on site specific requirements. Additional POCs may be required.
General Facility Description
| General Facility Description | |
| Installation Name | K16 Air Base |
| DLA Site Code | K16 |
| Location | Seongnam, Korea |
| POL Facility: (2) JP-8 35,000-gallon USTs (330, FOS 1.6.42), (1) Mogas 2,500-gallon UST (331), truck receipt for Mogas and JP-8, filter separator on receipt prior to 35,000 gallon USTs, JP-8 issue is through filter separator to dispenser (Dispenser 3/4) or top loading arms (2) or bottom loading arm, Mogas issue is to (1) dispenser (Dispenser 1/2), issue pump to loading arms or dispenser, POL control room, truck receipt stand, (3) filter separators, slop tank (UST-in vault), OWS with PIV (all receipt and issue areas have a common drain). | |
| Contractor maintained. Ahntech Corporation operates the station and performs routine general maintenance. |
Pacific Ocean Division, POD-AF
| W912DY-21-F-0076 | &"-,Bold"&16K16 Air Base |
| K16 | Facility Maintenance Plan |
OY3 Q1
&A &P of &N APTIM Federal Services, LLC
Instructions:
Include a general facility overview and description of each fuel system for the sites in accordance with UFC 3-460-01. Examples include: Bulk Storage Facilities, Aircraft Fueling Facilities, Marine and Dispensing Facilities, Ground Products Fueling Facilities, Alternate POL Facilities, and Support Facilities. Also include facility #s, facility names, fuel type, photos, and any other pertinent information.
Include Site Specific Conditions and Restrictions in this tab.
Figure 2
| Site Location Drawings |
| Figure 2 - POL Facilities |
Map of each operational area - and perhase each facility # or groups of facility #s in close vacinity
Pacific Ocean Division, POD-AF
| W912DY-21-F-0076 | &"-,Bold"&16K16 Air Base |
| K16 | Facility Maintenance Plan |
Revision 1
&A &P of &N APTIM Federal Services, LLC
Figure 3
| Site Location Drawings |
| Figure 3 - Fow Diagram |
Flow diagraphs for each "area"....operational area or facility # or group of facilities.
| W912DY-21-F-0076 | &"-,Bold"&16K16 Air Base |
| K16 | Facility Maintenance Plan |
Revision 1
&A &P of &N APTIM Federal Services, LLC
Communication Plan
| W912DY-21-F-0076 | &"-,Bold"&16K16 Air Base |
| K16 | Facility Maintenance Plan |
OY3 Q1
&A &P of &N APTIM Federal Services, LLC
Instructions:
Communication plan shall address in/out briefs, lines of communication, coordination for access, etc.
Site Specific Safety Plan
| W912DY-21-F-0076 | &"-,Bold"&16K16 Air Base |
| K16 | Facility Maintenance Plan |
Instructions:
Site Specific Addendum and Activity Hazard Analysis, which are Attachments to the APP, specific to activities or tasks related to recurring maintenance for this site.
PM Schedule
Pacific Ocean Division, POD-AF
| W912DY-21-F-0076 | &"-,Bold"&16&K000000K16 Air Base |
| K16 | Facility Maintenance Plan |
OY3 Q1
&A &P of &N APTIM Federal Services, LLC
Instructions:
Link PM schedule here
FS-PF Schedule
| FILTER SEPARATOR/PRE-FILTER MAINTENANCE SCHEDULES | |||||||||||||||||||||
| Applicable Facility Assets | Coalescer/Separator Information | Special Considerations | |||||||||||||||||||
| Real Property Unique Identifier | |||||||||||||||||||||
| (RPUID) | Real Property Facility # | Real Property Facility Name | Operational Area | Component Type | Base Asset ID | Component Unique Identifier (CUID) | APTIM Asset ID* | Asset Description* | Make | Model | Capacity (GPM) | UFC Section Reference | Number of Coalescer Cartridges | Number of | |||||||
| Separator Cartridges | Coalescer Cartridges | ||||||||||||||||||||
| Model # | Separator Cartridge | ||||||||||||||||||||
| Model # | Clean or Replace | ||||||||||||||||||||
| Separator Cartridge | Gasket | ||||||||||||||||||||
| Model # | Date Last Replaced | Replacement Due Date | Operator/Equipment Requirements | System Availability | Site Self Performs | ||||||||||||||||
| (Y/N) | Comments | ||||||||||||||||||||
| 1208757 | K16-336 | 336-POL PIPELINE ABOVE GROUND | BULK STORAGE-FILTER SEP PAD | FT-Filter Separators | K16-336-FLSP-176424 | K1600161 | Issue filter separator (west) located under canopy T 329 | Facet USA Inc. | CFCS-D-3N39SB-1636FM | Section 3-6.2 | CFCS-D-3N39SB-1636FM | Replace | 7/6/23 | 7/6/26 | Base provides filter elements | NO | 300 gpm | ||||
| 1208757 | K16-336 | 336-POL PIPELINE ABOVE GROUND | BULK STORAGE-FILTER SEP PAD | FT-Filter Separators | K16-336-FLSP-170521 | K1600162 | Issue filter separator (middle) located under canopy T 329 | Facet USA Inc. | CFCS-D-3N39SB-1636FM | Section 3-6.2 | CFCS-D-3N39SB-1636FM | Replace | 7/6/23 | 7/6/26 | Base provides filter elements | NO | 300 gpm | ||||
| 1208757 | K16-336 | 336-POL PIPELINE ABOVE GROUND | BULK STORAGE-FILTER SEP PAD | FT-Filter Separators | K16-336-FLSP-170393 | K1600173 | Receipt filter separator (east) located next to canopy T 329 | Facet USA Inc. | CFCS-D-3N39SB-1636FM | Section 3-6.2 | CFCS-D-3N39SB-1636FM | Replace | 7/6/23 | 7/6/26 | Base provides filter elements | NO | 300 gpm |
| W912DY-21-F-0076 | &"-,Bold"&16K16 Air Base |
| K16&"Times New Roman,Bold"&14 | Facility Maintenance Plan |
OY3 Q1
&A &P of &N APTIM Federal Services, LLC
Instructions:
1. Input all data as indicated on the sheet.
2. Additional documents referred to in the Special Considerations column shall be included as an appendix to this FMP.
3. The contractor shall generate a Component Unique Identifier (CUID) for each component utilizing the Component Acronym Sheet within this Work Book. The unique identifier must use the following:
Three letter Site Code - Facility # - Component Acronym - Sequential number Example: AAD-00063A-RCVL-0001
If component acronym is not listed, the contractor shall request an acronym be established through the HNC Project Manager and Project Engineer via email. Contractors may utilize other means of tracking/labeling assets such as QR codes in addition to the required CUID however, tracking/labeling must correlate with the CUID. This CUID shall be the standard for all DLA capitalized equipment.
4. Utilize the UFC Section Reference Work Category as noted on the Component Acronym Sheet.
5. Enter any applicable manufacturer requirements not stated in the UFC. References are acceptable with attachments.
6. Enter any applicable operator support or government owned equipment required to complete the RM task.
7. Enter impact on system availability by performing the RM task. This could include shutdown, lockout, or similar impacts.
8. Filter Separators and Pre-Filters identified here shall also be provided in the Task Matrix Tab.
9. Print Hard Copies as 11x17.
Task Matrix
| Applicable Facility Assets | UFC System Level Maintenance Frequency | Special Considerations | ||||||||||||||||||
| Real Property Unique Identifier (RPUID) | Real Property Facility # | Facility Name | Operational Area | Component Type | Base Asset ID | Component Unique ID (CUID) | APTIM Asset ID | Asset Description | Make | Model | Capacity / Size | Quarterly | Semi Annual | Annual | UFC Section Reference | Additional Manufacturer RM Requirements | Operator/Equipment Requirements | System Availability | Other contract | Comments |
| 974501 | K16-330 | 330-JET FUEL U/G | BULK STORAGE | MV-Double Block and Bleed Valves | K16-330-DBBVL-163427 | 16113K16 | Located on the 4 inch receipt line to tank 1 | General Valve | X | X | X | Section 6-6.2.5 | Coordinate with Facility | |||||||
| 974501 | K16-330 | 330-JET FUEL U/G | BULK STORAGE | MV-Double Block and Bleed Valves | K16-330-DBBVL-163428 | 16114K16 | Located on the 4 inch issue line from tank 1 issue pump | General Valve | X | X | X | Section 6-6.2.5 | Coordinate with Facility | |||||||
| 974501 | K16-330 | 330-JET FUEL U/G | BULK STORAGE | MV-Double Block and Bleed Valves | K16-330-DBBVL-163429 | 16115K16 | Located on the 2 inch piping from tank 1 sump pump | General Valve | X | X | X | Section 6-6.2.5 | Coordinate with Facility | |||||||
| 974501 | K16-330 | 330-JET FUEL U/G | BULK STORAGE | MV-Double Block and Bleed Valves | K16-330-DBBVL-163430 | 16116K16 | Located on the 4 inch receipt line to tank 2 | General Valve | X | X | X | Section 6-6.2.5 | Coordinate with Facility | |||||||
| 974501 | K16-330 | 330-JET FUEL U/G | BULK STORAGE | MV-Double Block and Bleed Valves | K16-330-DBBVL-163431 | 16117K16 | Located on the 4 inch issue line from tank 2 issue pump | General Valve | X | X | X | Section 6-6.2.5 | Coordinate with Facility | |||||||
| 974501 | K16-330 | 330-JET FUEL U/G | BULK STORAGE | MV-Double Block and Bleed Valves | K16-330-DBBVL-163432 | 16118K16 | Located on the 2 inch piping from tank 2 sump pump | General Valve | X | X | X | Section 6-6.2.5 | Coordinate with Facility | |||||||
| 974501 | K16-330 | 330-JET FUEL U/G | BULK STORAGE | TV-Thermal and Pressure Relief Valves | K16-330-TPRVL-164991 | 16138K16 | PRV located on the 4 inch receipt line for tank 2 | JOKWANG | X | X | Section 6-6.3 | Coordinate with Facility to Test | Set point 60 psig | |||||||
| 974501 | K16-330 | 330-JET FUEL U/G | BULK STORAGE | TV-Thermal and Pressure Relief Valves | K16-330-TPRVL-164992 | 16139K16 | PRV located on the 4 inch issue line from tank 2 | JOKWANG | X | X | Section 6-6.3 | Coordinate with Facility to Test | Set pressure 115 psig | |||||||
| 1208760 | K16-337 | 337-PRODUCT RECOVERY TANK | BULK STORAGE | MV-Double Block and Bleed Valves | K16-337-DBBVL-163444 | 16141K16 | DBB valve located on top of the tank | General Valve | X | X | X | Section 6-6.2.5 | Coordinate with Facility; Confined Space | |||||||
| 1208760 | K16-337 | 337-PRODUCT RECOVERY TANK | BULK STORAGE | MV-Ball Valves | K16-337-BLVL-175924 | 16142K16 | Ball valve located at the front of the tank second from the bottom | X | Section 6-6.2.4 | Coordinate with Facility; Confined Space | ||||||||||
| 1208760 | K16-337 | 337-PRODUCT RECOVERY TANK | BULK STORAGE | MV-Ball Valves | K16-337-BLVL-168874 | 16143K16 | Ball valve located at the front of the tank first from the bottom | X | Section 6-6.2.4 | Coordinate with Facility; Confined Space | ||||||||||
| 973489 | K16-323 | 323-OIL/WATER SEPERATOR | BULK STORAGE | SF-Oil/Water Separators | T 323 | K16-323-OWS-170338 | K1600002 | Oil Water Separator located between truck offload and perimeter fence | X | X | Section 11-5 | Notify Facility to Test | 100 gpm | |||||||
| 974501 | K16-330 | 330-JET FUEL U/G | BULK STORAGE | TA-Tank Pressure/Vacuum Vents | K16-330-TPVVT-176414 | K1600004 | Located next to the issue pump for Tank 1 | Varec | X | Section 8-9.3 | At Height-Ladder Required; Notify Facility | |||||||||
| 974501 | K16-330 | 330-JET FUEL U/G | BULK STORAGE | TA-Tank Pressure/Vacuum Vents | K16-330-TPVVT-170339 | K1600005 | Located next to the sump pump for Tank 1 | Shand & Jurs | X | Section 8-9.3 | At Height-Ladder Required; Notify Facility | |||||||||
| 974501 | K16-330 | 330-JET FUEL U/G | BULK STORAGE | TA-Tank Pressure/Vacuum Vents | K16-330-TPVVT-170495 | K1600006 | Located next to the issue pump for Tank 2 | Shand & Jurs | X | Section 8-9.3 | At Height-Ladder Required; Notify Facility | |||||||||
| 974501 | K16-330 | 330-JET FUEL U/G | BULK STORAGE | TA-Tank Pressure/Vacuum Vents | K16-330-TPVVT-170446 | K1600007 | Located next to the sump pump for Tank 2 | Varec | X | Section 8-9.3 | At Height-Ladder Required; Notify Facility | |||||||||
| 974501 | K16-330 | 330-JET FUEL U/G | BULK STORAGE | MV-Ball Valves | K16-330-BLVL-157236 | K1600008 | Isolation ball valve for the pressure gauge located on the 4 inch issue line from tank 1 issue pump | Flow-Tek | X | Section 6-6.2.4 | Coordinate with Facility | |||||||||
| 974501 | K16-330 | 330-JET FUEL U/G | BULK STORAGE | MV-Ball Valves | K16-330-BLVL-157237 | K1600009 | Isolation ball valve for the pressure gauge located on the 2 inch line from tank 1 sump pump | Flow-Tek | X | Section 6-6.2.4 | Coordinate with Facility | |||||||||
| 974501 | K16-330 | 330-JET FUEL U/G | BULK STORAGE | MV-Ball Valves | K16-330-BLVL-157238 | K1600010 | Isolation ball valve for the pressure gauge located on the 4 inch issue line from tank 2 issue pump | Flow-Tek | X | Section 6-6.2.4 | Coordinate with Facility | |||||||||
| 974501 | K16-330 | 330-JET FUEL U/G | BULK STORAGE | MV-Ball Valves | K16-330-BLVL-157239 | K1600011 | Isolation ball valve for the pressure gauge located on the 2 inch line from tank 2 sump pump | Flow-Tek | X | Section 6-6.2.4 | Coordinate with Facility | |||||||||
| 974501 | K16-330 | 330-JET FUEL U/G | BULK STORAGE | MV-Ball Valves | K16-330-BLVL-157240 | K1600012 | Isolation ball valve for the pressure gauge located on the 4 inch receipt line to tank 1 | Flow-Tek | X | Section 6-6.2.4 | Coordinate with Facility | |||||||||
| 974501 | K16-330 | 330-JET FUEL U/G | BULK STORAGE | MV-Ball Valves | K16-330-BLVL-157241 | K1600013 | Isolation ball valve for the pressure gauge located on the 4 inch receipt line to tank 2 | Flow-Tek | X | Section 6-6.2.4 | Coordinate with Facility | |||||||||
| 974501 | K16-330 | 330-JET FUEL U/G | BULK STORAGE | MV-Ball Valves | K16-330-BLVL-157242 | K1600014 | Isolation ball valve for the pressure gauge located on the 2 inch issue line from tank 1 red jacket pump | Flow-Tek | X | Section 6-6.2.4 | Coordinate with Facility | |||||||||
| 974501 | K16-330 | 330-JET FUEL U/G | BULK STORAGE | MV-Ball Valves | K16-330-BLVL-157243 | K1600015 | Located on the 2in issue line from the Red Jacket Pump to the JP-8 dispenser | Flow-Tek | X | Section 6-6.2.4 | Coordinate with Facility | |||||||||
| 974501 | K16-330 | 330-JET FUEL U/G | BULK STORAGE | MV-Ball Valves | K16-330-BLVL-157244 | K1600016 | Located on the 3/4 inch relief line to tank 1 | Velan | X | Section 6-6.2.4 | Coordinate with Facility | |||||||||
| 974501 | K16-330 | 330-JET FUEL U/G | BULK STORAGE | MV-Ball Valves | K16-330-BLVL-157245 | K1600017 | Located on the 3/4 inch relief line to tank 2 | Velan | X | Section 6-6.2.4 | Coordinate with Facility | |||||||||
| 974501 | K16-330 | 330-JET FUEL U/G | BULK STORAGE | CV-General System Control Valves | K16-330-GSCVL-153063 | K1600018 | Located on the 4 inch issue line from tank 1 issue pump | Cla-Val | X | X | Section 4-3.2.1 | Operate System to Test | ||||||||
| 974501 | K16-330 | 330-JET FUEL U/G | BULK STORAGE | CV-General System Control Valves | K16-330-GSCVL-153064 | K1600019 | Located on the 2 inch piping from tank 1 sump pump | Cla-Val | X | X | Section 4-3.2.1 | Operate System to Test | ||||||||
| 974501 | K16-330 | 330-JET FUEL U/G | BULK STORAGE | CV-General System Control Valves | K16-330-GSCVL-153065 | K1600020 | Located on the 4 inch issue line from tank 2 issue pump | Cla-Val | X | X | Section 4-3.2.1 | Operate System to Test | ||||||||
| 974501 | K16-330 | 330-JET FUEL U/G | BULK STORAGE | CV-General System Control Valves | K16-330-GSCVL-153066 | K1600021 | Located on the 2 inch piping from tank 2 sump pump | Cla-Val | X | X | Section 4-3.2.1 | Operate System to Test | ||||||||
| 974501 | K16-330 | 330-JET FUEL U/G | BULK STORAGE | TA-Internal HLSO Valves | K16-330-GSCVL-153067 | K1600022 | Located on the 4 inch receipt line for tank 1 (HLSO control valve) | Cla-Val | X | Section 8-9.6.2 | Operate System to Test | |||||||||
| 974501 | K16-330 | 330-JET FUEL U/G | BULK STORAGE | TA-Internal HLSO Valves | K16-330-GSCVL-153068 | K1600023 | Located on the 4 inch receipt line for tank 2 (HLSO control valve) | Cla-Val | X | Section 8-9.6.2 | Operate System to Test | |||||||||
| 974501 | K16-330 | 330-JET FUEL U/G | BULK STORAGE | PC-Aboveground Piping and Equipment Coating | K16-330-AGPCT-170340 | K1600030 | Exposed piping: 6in JP-8 (Tank and filter pad area) | Section 6-10.1 | ||||||||||||
| 974501 | K16-330 | 330-JET FUEL U/G | BULK STORAGE | PC-Aboveground Piping and Equipment Coating | K16-330-AGPCT-170496 | K1600031 | Exposed piping: 4in JP-8 (Tank and filter pad area) | Section 6-10.1 | ||||||||||||
| 974501 | K16-330 | 330-JET FUEL U/G | BULK STORAGE | PC-Aboveground Piping and Equipment Coating | K16-330-AGPCT-170497 | K1600032 | 2 inch sump line to the waste tank | Section 6-10.1 | ||||||||||||
| 974501 | K16-330 | 330-JET FUEL U/G | BULK STORAGE | PV-Pressure Gauges | K16-330-PVGA-170447 | K1600033 | Pressure gauge located on the 4 inch issue line from tank 1 issue pump | HISCO | X | X | X | Section 6-7.1 | ||||||||
| 974501 | K16-330 | 330-JET FUEL U/G | BULK STORAGE | PV-Pressure Gauges | K16-330-PVGA-170341 | K1600034 | Pressure gauge located on the 2 inch line from tank 1 sump pump | HISCO | X | X | X | Section 6-7.1 | ||||||||
| 974501 | K16-330 | 330-JET FUEL U/G | BULK STORAGE | PV-Pressure Gauges | K16-330-PVGA-176415 | K1600035 | Pressure gauge located on the 4 inch issue line from tank 2 issue pump | HISCO | X | X | X | Section 6-7.1 | ||||||||
| 974501 | K16-330 | 330-JET FUEL U/G | BULK STORAGE | PV-Pressure Gauges | K16-330-PVGA-170506 | K1600036 | Pressure gauge located on the 2 inch line from tank 2 sump pump | HISCO | X | X | X | Section 6-7.1 | ||||||||
| 974501 | K16-330 | 330-JET FUEL U/G | BULK STORAGE | PV-Pressure Gauges | K16-330-PVGA-170342 | K1600037 | Pressure gauge located on the 4 inch receipt line to tank 1 | Ashcroft | DURGAUGE | X | X | X | Section 6-7.1 | |||||||
| 974501 | K16-330 | 330-JET FUEL U/G | BULK STORAGE | PV-Pressure Gauges | K16-330-PVGA-170507 | K1600038 | Pressure gauge located on the 4 inch receipt line to tank 2 | HISCO | X | X | X | Section 6-7.1 | ||||||||
| 974501 | K16-330 | 330-JET FUEL U/G | BULK STORAGE | PV-Pressure Gauges | K16-330-PVGA-170508 | K1600039 | Pressure gauge located on the 2 inch issue line from tank 1 red jacket pump | HISCO | X | X | X | Section 6-7.1 | ||||||||
| 974501 | K16-330 | 330-JET FUEL U/G | BULK STORAGE | PM-Vertical Turbine/Sub-merged Turbine Pumps | K16-330-VTSP-170343 | K1600042 | JP-8 tank 1 issue pump | Dempster Industries | 8BCAL3T | X | X | X | Section 3-8.1.3 / 3-8.3 | Operate System to Test | 302 gpm | |||||
| 974501 | K16-330 | 330-JET FUEL U/G | BULK STORAGE | PM-Vertical Turbine/Sub-merged Turbine Pumps | K16-330-VTSP-170498 | K1600043 | JP-8 tank 2 issue pump | Dempster Industries | 8BCAL3T | X | X | X | Section 3-8.1.3 / 3-8.3 | Operate System to Test | 302 gpm | |||||
| 974501 | K16-330 | 330-JET FUEL U/G | BULK STORAGE | PM-Vertical Turbine/Sub-merged Turbine Pumps | K16-330-VTSP-176417 | K1600044 | JP-8 tank 1 sump pump | Goulds Pumps | DWI- 6RAHC-4 | X | X | X | Section 3-8.1.3 / 3-8.3 | Operate System to Test | 24 gpm | |||||
| 974501 | K16-330 | 330-JET FUEL U/G | BULK STORAGE | PM-Vertical Turbine/Sub-merged Turbine Pumps | K16-330-VTSP-170344 | K1600045 | JP-8 tank 2 sump pump | Goulds Pumps | DWI- 6RAHC-4 | X | X | X | Section 3-8.1.3 / 3-8.3 | Operate System to Test | 24 gpm | |||||
| 974501 | K16-330 | 330-JET FUEL U/G | BULK STORAGE | GF-Remote Dispenser Pumps | K16-330-RDSP-170499 | K1600046 | Red Jacket pump for the JP-8 dispenser located at JP-8 tank 1 | FE Petro | X | X | X | Section 7-15.1 | Operate System to Test | |||||||
| 974501 | K16-330 | 330-JET FUEL U/G | BULK STORAGE | TK-Underground Field-Constructed Tanks | K16-330-UGFET-170509 | K1600047 | Underground JP-8 Tank 1 | X | Section 8-6 | |||||||||||
| 974501 | K16-330 | 330-JET FUEL U/G | BULK STORAGE | TK-Underground Field-Constructed Tanks | K16-330-UGFET-170500 | K1600048 | Underground JP-8 Tank 2 | X | Section 8-6 | |||||||||||
| 974501 | K16-330 | 330-JET FUEL U/G | BULK STORAGE | GF-Ground Vehicle Fuel Piping | K16-330-GVFP-170501 | K1600049 | Aboveground and underground issue piping for JP-8 dispenser 3 and 4 | X | X | Section 7-11 | Coordinate with Facility | |||||||||
| 1208760 | K16-337 | 337-PRODUCT RECOVERY TANK | BULK STORAGE | TK-Aboveground Shop-Fabricated Tanks | Tank-4 | K16-337-AGSFP-170530 | K1600190 | Waste tank located inside vault | X | X | Section 8-5.1 | Confined Space | ||||||||
| 1208760 | K16-337 | 337-PRODUCT RECOVERY TANK | BULK STORAGE | CS-Self-Diking or Vaulted Tank Containment | T 337 | K16-337-SDVTCS-170404 | K1600191 | Waste tank containment vault | Section 8-10.4 | Confined Space | ||||||||||
| 1208760 | K16-337 | 337-PRODUCT RECOVERY TANK | BULK STORAGE | TA-Tank Pressure/Vacuum Vents | K16-337-TPVVT-170531 | K1600192 | Vent located inside the waste tank vault | Shand & Jurs | X | Section 8-9.3 | At Height-Ladder Required; Notify Facility | |||||||||
| 1208760 | K16-337 | 337-PRODUCT RECOVERY TANK | BULK STORAGE | PC-Aboveground Piping and Equipment Coating | K16-337-AGPCT-170406 | K1600193 | 2 inch slop waste piping from the JP-8 tanks to the waste tank, and from the waste tank to the truck offloading area | Section 6-10.1 | ||||||||||||
| 1208760 | K16-337 | 337-PRODUCT RECOVERY TANK | BULK STORAGE | PM-Centrifugal Pumps | K16-337-CENP-176437 | K1600194 | Water draw off pump located between waste tank vault and filter pad | Gorman-Rupp | 02C3-X.75 1P | X | X | X | Section 3-8.1 | |||||||
| 1208760 | K16-337 | 337-PRODUCT RECOVERY TANK | BULK STORAGE | FP-Sight Flow Indicators | K16-337-SFND-176439 | K1600195 | Located next to the ball valve at the bottom front side of tank. (Upper) | OPW VISI-FLO | X | Section 6-12.3 | ||||||||||
| 1208760 | K16-337 | 337-PRODUCT RECOVERY TANK | BULK STORAGE | FP-Sight Flow Indicators | K16-337-SFND-176441 | K1600196 | Located next to the ball valve at the bottom front side of tank. (Lower) | OPW VISI-FLO | X | Section 6-12.3 | ||||||||||
| 1208760 | K16-337 | 337-PRODUCT RECOVERY TANK | BULK STORAGE | TA-Tank Pressure/Vacuum Vents | K16-337-TPVVT-170544 | K1600219 | Located next to the waste tank vault | Shand & Jurs | X | Section 8-9.3 | At Height-Ladder Required; Notify Facility | |||||||||
| 974501 | K16-330 | 330-JET FUEL U/G | BULK STORAGE | GF-Transition Sumps | K16-330-TRSMP-176457 | K162206240920 | Transition sump for the JP dispenser issue line located near the filter separator pad | X | Section 7-14 | Notify Facility | ||||||||||
| 974501 | K16-330 | 330-JET FUEL U/G | BULK STORAGE | EC-Control Panels - Elec Equip | K16-330-ELEQ-170545 | K162206270910 | Control panel located inside facility S-328 | X | Section 9-1.2 | Coordinate with Facility | ||||||||||
| 974501 | K16-330 | 330-JET FUEL U/G | BULK STORAGE | EC-Panelboards | K16-330-PNB-170546 | K162206270911 | Panelboard located inside facility S-328 | X | Section 9-1.5 | Notify Facility | ||||||||||
| 1208760 | K16-337 | 337-PRODUCT RECOVERY TANK | BULK STORAGE | EC-Static Grounding Systems | K16-337-STGS-170547 | K162206270912 | Static grounding wire connected to the rolling lid. | X | Section 9-1.6.2 | |||||||||||
| 1208760 | K16-337 | 337-PRODUCT RECOVERY TANK | BULK STORAGE | EQ-Real Property | K16-337-ASSET-170402 | K162206270913 | This is not a check valve but a port to insert water for priming pump. located on the inlet side of the water draw off pump | Non-Appx G Class | ||||||||||||
| 974501 | K16-330 | 330-JET FUEL U/G | BULK STORAGE | EC-Electronic Equipment | K16-330-ELTREQ-170535 | K162206270916 | Flow switch located next to the issue pump for tank 1 | X | Section 9-1.9 | Notify Facility of Inspection | ||||||||||
| 974501 | K16-330 | 330-JET FUEL U/G | BULK STORAGE | EC-Electronic Equipment | K16-330-ELTREQ-176464 | K162206270917 | Flow switch located next to the issue pump for tank 2 | X | Section 9-1.9 | Notify Facility of Inspection | ||||||||||
| 974501 | K16-330 | 330-JET FUEL U/G | BULK STORAGE | EC-Electronic Equipment | K16-330-ELTREQ-170405 | K162206270918 | Flow switch located next to the sump pump for tank 1 | X | Section 9-1.9 | Notify Facility of Inspection | ||||||||||
| 974501 | K16-330 | 330-JET FUEL U/G | BULK STORAGE | EC-Electronic Equipment | K16-330-ELTREQ-170407 | K162206270919 | Flow switch located next to the sump pump for tank 2 | X | Section 9-1.9 | Notify Facility of Inspection | ||||||||||
| PWS Appx K-3 | K16-343 | 343-EXTERIOR LIGHTING | BULK STORAGE | EC-Lighting | S343 | K16-343-LIGHT-170409 | K162206271011 | One light pole with two lights at heights, one switch, and photocell | X | X | Section 9-1.8 | At Height-Manlift Required | ||||||||
| 1208760 | K16-337 | 337-PRODUCT RECOVERY TANK | BULK STORAGE | MV-Ball Valves | K16-337-BLVL-170548 | K162206280950 | Ball valve located on the water draw off pump housing (drain) | HAK | X | Section 6-6.2.4 | Coordinate with Facility; Confined Space | |||||||||
| 974502 | K16-331 | 331-MOGAS STR U/G (TANK 3) | BULK STORAGE/ MOGAS TANK | MV-Double Block and Bleed Valves | K16-331-DBBVL-163433 | 16119K16 | Located on the MOGAS receipt line | General Valve | X | X | X | Section 6-6.2.5 | Coordinate with Facility | |||||||
| 974502 | K16-331 | 331-MOGAS STR U/G (TANK 3) | BULK STORAGE/ MOGAS TANK | TV-Thermal and Pressure Relief Valves | K16-331-TPRVL-164990 | 16137K16 | PRV located on the MOGAS receipt line near the DBB valve | JOKWANG | X | X | Section 6-6.3 | Coordinate with Facility to Test | Set pressure 60 psig | |||||||
| 974502 | K16-331 | 331-MOGAS STR U/G (TANK 3) | BULK STORAGE/ MOGAS TANK | TA-Internal HLSO Valves | K16-331-GSCVL-153069 | K1600050 | Located on the MOGAS receipt line. (HLSO control valve) | Cla-Val | X | Section 8-9.6.2 | Operate System to Test | |||||||||
| 974502 | K16-331 | 331-MOGAS STR U/G (TANK 3) | BULK STORAGE/ MOGAS TANK | PC-Aboveground Piping and Equipment Coating | K16-331-AGPCT-170502 | K1600052 | 3 inch receipt line from MOGAS TK-3 to the truck offloading area | Section 6-10.1 | ||||||||||||
| 974502 | K16-331 | 331-MOGAS STR U/G (TANK 3) | BULK STORAGE/ MOGAS TANK | TA-Tank Pressure/Vacuum Vents | K16-331-TPVVT-176419 | K1600053 | Located near the perimeter fence next to the MOGAS underground tank | Shand & Jurs | X | Section 8-9.3 | At Height-Ladder Required; Notify Facility | |||||||||
| 974502 | K16-331 | 331-MOGAS STR U/G (TANK 3) | BULK STORAGE/ MOGAS TANK | TK-Underground Field-Constructed Tanks | Tank-3 | K16-331-UGFET-170503 | K1600055 | Manway for MOGAS Tank-3 located next to waste tank rolling lid | TYPE DWFT | X | Section 8-6 | |||||||||
| 974502 | K16-331 | 331-MOGAS STR U/G (TANK 3) | BULK STORAGE/ MOGAS TANK | GF-Remote Dispenser Pumps | K16-331-RDSP-170511 | K1600056 | Red Jacket Pump located on top of MOGAS Tank-3. Remove manway lid to access pump | FE Petro | X | X | X | Section 7-15.1 | Operate System to Test | |||||||
| 974502 | K16-331 | 331-MOGAS STR U/G (TANK 3) | BULK STORAGE/ MOGAS TANK | GF-Ground Vehicle Fuel Piping | K16-331-GVFP-170394 | K1600218 | Underground issue piping for MOGAS dispenser 1 and 2 | X | X | Section 7-11 | Coordinate with Facility | |||||||||
| 974502 | K16-331 | 331-MOGAS STR U/G (TANK 3) | BULK STORAGE/ MOGAS TANK | MV-Ball Valves | K16-331-BLVL-170396 | K162203161355 | Ball valve located on the issue side of the red jacket pump. | X | Section 6-6.2.4 | Coordinate with Facility | ||||||||||
| 1227049 | K16-339 | 339-TK TRK LD/UNLD | BULK STORAGE/TRUCK UNLOAD | MV-Ball Valves | K16-339-BLVL-168873 | 16107K16 | Ball valve located on the outlet side of the MOGAS offloading pump | X | Section 6-6.2.4 | Coordinate with Facility | ||||||||||
| 1227049 | K16-339 | 339-TK TRK LD/UNLD | BULK STORAGE/TRUCK UNLOAD | MV-Ball Valves | K16-339-BLVL-175923 | 16108K16 | Ball valve located on the drain tank T-4 to vacuum truck piping | X | Section 6-6.2.4 | Coordinate with Facility | ||||||||||
| 1227049 | K16-339 | 339-TK TRK LD/UNLD | BULK STORAGE/TRUCK UNLOAD | MV-Double Block and Bleed Valves | K16-339-DBBVL-163423 | 16109K16 | DBB valve located on the MOGAS offload line at the truck connection | General Valve | X | X | X | Section 6-6.2.5 | Coordinate with Facility | |||||||
| 1227049 | K16-339 | 339-TK TRK LD/UNLD | BULK STORAGE/TRUCK UNLOAD | MV-Double Block and Bleed Valves | K16-339-DBBVL-163424 | 16110K16 | DBB valve located on the JP-8 offload pump bypass line | General Valve | X | X | X | Section 6-6.2.5 | Coordinate with Facility | |||||||
| 1227049 | K16-339 | 339-TK TRK LD/UNLD | BULK STORAGE/TRUCK UNLOAD | MV-Double Block and Bleed Valves | K16-339-DBBVL-163425 | 16111K16 | DBB valve located on the inlet side of the JP-8 offloading pump | General Valve | X | X | X | Section 6-6.2.5 | Coordinate with Facility | |||||||
| 1227049 | K16-339 | 339-TK TRK LD/UNLD | BULK STORAGE/TRUCK UNLOAD | MV-Double Block and Bleed Valves | K16-339-DBBVL-163426 | 16112K16 | DBB valve located on the outlet side of the JP-8 offloading pump | General Valve | X | X | X | Section 6-6.2.5 | Coordinate with Facility | |||||||
| 1227049 | K16-339 | 339-TK TRK LD/UNLD | BULK STORAGE/TRUCK UNLOAD | TV-Thermal and Pressure Relief Valves | K16-339-TPRVL-164993 | 16140K16 | PRV located on the drain tank T-4 to vacuum truck piping | Taylor Valve | X | X | Section 6-6.3 | Coordinate with Facility to Test | Set pressure 150 psig | |||||||
| 1227049 | K16-339 | 339-TK TRK LD/UNLD | BULK STORAGE/TRUCK UNLOAD | MV-Check Valves | K16-339-CKVL-170408 | K1600198 | Butterfly check valve located on the outlet side of the JP-8 offloading pump next to the strainer | X | Section 6-6.2.8 | Operate System to Test | ||||||||||
| 1227049 | K16-339 | 339-TK TRK LD/UNLD | BULK STORAGE/TRUCK UNLOAD | MV-Check Valves | K16-339-CKVL-170532 | K1600199 | Butterfly check valve 2in located on the outlet side of the MOGAS offload pump | X | Section 6-6.2.8 | Operate System to Test | ||||||||||
| 1227049 | K16-339 | 339-TK TRK LD/UNLD | BULK STORAGE/TRUCK UNLOAD | SF-Fuel Truck Containment Areas | K16-339-FTKRCC-170410 | K1600200 | Tank truck offloading containment area | X | X | Section 11-1.1 | ||||||||||
| 1227049 | K16-339 | 339-TK TRK LD/UNLD | BULK STORAGE/TRUCK UNLOAD | MV-Gate Valves | K16-339-GTVL-170543 | K1600205 | Gate valve located at the JP-8 offload truck connection (cam lock) | Milvaco | X | X | Section 6-6.2.3 | Notify Facility | ||||||||
| 1227049 | K16-339 | 339-TK TRK LD/UNLD | BULK STORAGE/TRUCK UNLOAD | EC-Ground Reels - Static Grounding Systems | K16-339-STGS-170533 | K1600206 | Grounding reel located next to pump offload switches | X | X | Section 9-1.6.2 | ||||||||||
| 1227049 | K16-339 | 339-TK TRK LD/UNLD | BULK STORAGE/TRUCK UNLOAD | PC-Aboveground Piping and Equipment Coating | K16-339-AGPCT-176443 | K1600207 | Piping for MOGAS offload | Section 6-10.1 | ||||||||||||
| 1227049 | K16-339 | 339-TK TRK LD/UNLD | BULK STORAGE/TRUCK UNLOAD | PC-Aboveground Piping and Equipment Coating | K16-339-AGPCT-170387 | K1600208 | Piping for JP-8 offload | Section 6-10.1 | ||||||||||||
| 1227049 | K16-339 | 339-TK TRK LD/UNLD | BULK STORAGE/TRUCK UNLOAD | PM-Centrifugal Pumps | K16-339-CENP-170534 | K1600210 | MOGAS offload pump | Gorman-Rupp | 02K3-X2 | X | X | X | Section 3-8.1 | Operate System to Test | ||||||
| 1227049 | K16-339 | 339-TK TRK LD/UNLD | BULK STORAGE/TRUCK UNLOAD | PM-Centrifugal Pumps | K16-339-CENP-170389 | K1600211 | JP-8 offload pump | X | X | X | Section 3-8.1 | Operate System to Test | ||||||||
| 1227049 | K16-339 | 339-TK TRK LD/UNLD | BULK STORAGE/TRUCK UNLOAD | FT-Basket Strainer | K16-339-BSTR-176449 | K1600212 | Strainer located on the MOGAS offload piping | Titan Flow Control, Inc. | X | X | Section 3-6.4 | |||||||||
| 1227049 | K16-339 | 339-TK TRK LD/UNLD | BULK STORAGE/TRUCK UNLOAD | FT-Basket Strainer | K16-339-BSTR-176452 | K1600213 | Strainer located on the JP-8 offload piping | Titan Flow Control, Inc. | X | X | Section 3-6.4 | |||||||||
| 1227049 | K16-339 | 339-TK TRK LD/UNLD | BULK STORAGE/TRUCK UNLOAD | EC-EFSO-Elec Equip | K16-339-EFSO-170391 | K1600214 | EFSO located in between the MOGAS and Diesel pump offload switches | X | Section 9-1.2 | Operate System to Test | ||||||||||
| 1227049 | K16-339 | 339-TK TRK LD/UNLD | BULK STORAGE/TRUCK UNLOAD | PC-Aboveground Piping and Equipment Coating | K16-339-AGPCT-176454 | K1600217 | 4 inch piping for JP-8 offload measured from under the grading to the receipt filter separator | Section 6-10.1 | ||||||||||||
| 1227049 | K16-339 | 339-TK TRK LD/UNLD | BULK STORAGE/TRUCK UNLOAD | EC-Static Grounding Systems | K16-339-STGS-170403 | K162206270914 | Static grounding system located at the truck unloading area, near the pump switch panel. | X | Section 9-1.6.2 | |||||||||||
| 1227049 | K16-339 | 339-TK TRK LD/UNLD | BULK STORAGE/TRUCK UNLOAD | CS-Containment Drain Valves | K16-339-CSGEN-167791 | K162206271014 | Containment drain valve for the truck unloading area and the dispenser/truck loading area | Soosung Valve | X | Section 8-10.1 | Key Required | |||||||||
| 1208757 | K16-336 | 336-POL PIPELINE ABOVE GROUND | BULK STORAGE-FILTER SEP PAD | MV-Double Block and Bleed Valves | K16-336-DBBVL-163434 | 16120K16 | Issue filter separator inlet isolation valve (middle filter separator under canopy T 329) | General Valve | C811 | X | X | X | Section 6-6.2.5 | Coordinate with Facility | ||||||
| 1208757 | K16-336 | 336-POL PIPELINE ABOVE GROUND | BULK STORAGE-FILTER SEP PAD | MV-Double Block and Bleed Valves | K16-336-DBBVL-163435 | 16121K16 | Issue filter separator outlet isolation valve (middle filter separator under canopy T 329) | General Valve | C811 | X | X | X | Section 6-6.2.5 | Coordinate with Facility | ||||||
| 1208757 | K16-336 | 336-POL PIPELINE ABOVE GROUND | BULK STORAGE-FILTER SEP PAD | MV-Double Block and Bleed Valves | K16-336-DBBVL-163436 | 16122K16 | Issue filter separator outlet isolation valve (west filter separator under canopy T 329) | General Valve | C811 | X | X | X | Section 6-6.2.5 | Coordinate with Facility | ||||||
| 1208757 | K16-336 | 336-POL PIPELINE ABOVE GROUND | BULK STORAGE-FILTER SEP PAD | MV-Double Block and Bleed Valves | K16-336-DBBVL-163437 | 16123K16 | Issue filter separator inlet isolation valve (west filter separator under canopy T 329) | General Valve | C811 | X | X | X | Section 6-6.2.5 | Coordinate with Facility | ||||||
| 1208757 | K16-336 | 336-POL PIPELINE ABOVE GROUND | BULK STORAGE-FILTER SEP PAD | MV-Double Block and Bleed Valves | K16-336-DBBVL-163438 | 16124K16 | Located on the discharge/recirculation line | General Valve | 1-847-WCB | X | X | X | Section 6-6.2.5 | Coordinate with Facility | ||||||
| 1208757 | K16-336 | 336-POL PIPELINE ABOVE GROUND | BULK STORAGE-FILTER SEP PAD | MV-Double Block and Bleed Valves | K16-336-DBBVL-163439 | 16125K16 | Located on the issue line to the pantographs | General Valve | 1-847-WCB | X | X | X | Section 6-6.2.5 | Coordinate with Facility | ||||||
| 1208757 | K16-336 | 336-POL PIPELINE ABOVE GROUND | BULK STORAGE-FILTER SEP PAD | TV-Thermal and Pressure Relief Valves | K16-336-TPRVL-164986 | 16133K16 | PRV located on top of the receipt filter separator (east) next to canopy T 329 | Taylor Valve | 82E4251311 | X | X | Section 6-6.3 | Coordinate with Facility to Test | Set pressure 150 psig | ||||||
| 1208757 | K16-336 | 336-POL PIPELINE ABOVE GROUND | BULK STORAGE-FILTER SEP PAD | TV-Thermal and Pressure Relief Valves | K16-336-TPRVL-164987 | 16134K16 | PRV located on top of the issue filter separator (middle) under canopy T 329 | Taylor Valve | 82E4251311 | X | X | Section 6-6.3 | Coordinate with Facility to Test | Set pressure 150 psig | ||||||
| 1208757 | K16-336 | 336-POL PIPELINE ABOVE GROUND | BULK STORAGE-FILTER SEP PAD | TV-Thermal and Pressure Relief Valves | K16-336-TPRVL-164988 | 16135K16 | PRV located on top of the issue filter separator (west) under canopy T 329 | Taylor Valve | 82E4251311 | X | X | Section 6-6.3 | Coordinate with Facility to Test | Set pressure 150 psig | ||||||
| 1208757 | K16-336 | 336-POL PIPELINE ABOVE GROUND | BULK STORAGE-FILTER SEP PAD | TV-Thermal and Pressure Relief Valves | K16-336-TPRVL-164989 | 16136K16 | PRV located on the 6 inch piping for truck loading | JOKWANG | X | X | Section 6-6.3 | Coordinate with Facility to Test | Set pressure 115 psig | |||||||
| 973742 | K16-329 | 329-OVERHEAD PROTECT @ FILTERS | BULK STORAGE-FILTER SEP PAD | SF-Canopies | T 329 | K16-329-CNPY-167406 | K1600003 | Filter separator pad canopy | X | Section 11-2.2 | ||||||||||
| 1208757 | K16-336 | 336-POL PIPELINE ABOVE GROUND | BULK STORAGE-FILTER SEP PAD | MV-Ball Valves | K16-336-BLVL-157252 | K1600139 | Downstream isolation ball valve for the PRV located on the issue filter separator (middle) under canopy T 329 | Flow-Tek | S20 | X | Section 6-6.2.4 | Coordinate with Facility | ||||||||
| 1208757 | K16-336 | 336-POL PIPELINE ABOVE GROUND | BULK STORAGE-FILTER SEP PAD | MV-Ball Valves | K16-336-BLVL-157253 | K1600140 | Located under the issue filter separator (middle) opposite of the 3/4 inch control valve component under canopy T 329 | Flow-Tek | S20 | X | Section 6-6.2.4 | Coordinate with Facility | ||||||||
| 1208757 | K16-336 | 336-POL PIPELINE ABOVE GROUND | BULK STORAGE-FILTER SEP PAD | MV-Ball Valves | K16-336-BLVL-157254 | K1600141 | Located on the sight glass drain for the issue filter separator (middle) under canopy T 329 | APOLLO | X | Section 6-6.2.4 | Coordinate with Facility | |||||||||
| 1208757 | K16-336 | 336-POL PIPELINE ABOVE GROUND | BULK STORAGE-FILTER SEP PAD | MV-Ball Valves | K16-336-BLVL-157255 | K1600142 | Located under the issue filter separator (middle) next to 3/4 inch control valve component under canopy T 329 | Flow-Tek | S20 | X | Section 6-6.2.4 | Coordinate with Facility | ||||||||
| 1208757 | K16-336 | 336-POL PIPELINE ABOVE GROUND | BULK STORAGE-FILTER SEP PAD | MV-Ball Valves | K16-336-BLVL-157256 | K1600143 | Bypass ball valve for the air eliminator located on top of the issue filter separator (middle) under canopy T 329 | Velan | X | Section 6-6.2.4 | Coordinate with Facility | |||||||||
| 1208757 | K16-336 | 336-POL PIPELINE ABOVE GROUND | BULK STORAGE-FILTER SEP PAD | MV-Ball Valves | K16-336-BLVL-157257 | K1600144 | Located on the issue filter separator drain (middle) under canopy T 329 | Velan | X | Section 6-6.2.4 | Coordinate with Facility | |||||||||
| 1208757 | K16-336 | 336-POL PIPELINE ABOVE GROUND | BULK STORAGE-FILTER SEP PAD | MV-Ball Valves | K16-336-BLVL-157258 | K1600145 | Downstream isolation ball valve for the PRV located on the issue filter separator (west) under canopy T 329 | Flow-Tek | S20 | X | Section 6-6.2.4 | Coordinate with Facility; Operate System to Test | ||||||||
| 1208757 | K16-336 | 336-POL PIPELINE ABOVE GROUND | BULK STORAGE-FILTER SEP PAD | MV-Ball Valves | K16-336-BLVL-157259 | K1600146 | Bypass ball valve for the air eliminator located on top of the issue filter separator (west) under canopy T 329 | Flow-Tek | S20 | X | Section 6-6.2.4 | Coordinate with Facility | ||||||||
| 1208757 | K16-336 | 336-POL PIPELINE ABOVE GROUND | BULK STORAGE-FILTER SEP PAD | MV-Ball Valves | K16-336-BLVL-157260 | K1600147 | Located on the sight glass drain for the issue filter separator (west) under canopy T 329 | APOLLO | X | Section 6-6.2.4 | Coordinate with Facility | |||||||||
| 1208757 | K16-336 | 336-POL PIPELINE ABOVE GROUND | BULK STORAGE-FILTER SEP PAD | MV-Ball Valves | K16-336-BLVL-157261 | K1600148 | Located under the issue filter separator (west) next to the 3/4 in control valve component under canopy T 329 | Flow-Tek | S20 | X | Section 6-6.2.4 | Coordinate with Facility | ||||||||
| 1208757 | K16-336 | 336-POL PIPELINE ABOVE GROUND | BULK STORAGE-FILTER SEP PAD | MV-Ball Valves | K16-336-BLVL-157262 | K1600149 | Located under the issue filter separator (west) opposite of the 3/4 inch control valve component under canopy T 329 | Velan | X | Section 6-6.2.4 | Coordinate with Facility | |||||||||
| 1208757 | K16-336 | 336-POL PIPELINE ABOVE GROUND | BULK STORAGE-FILTER SEP PAD | MV-Ball Valves | K16-336-BLVL-157263 | K1600150 | Located on the issue filter separator drain (west) under canopy T 329 | Velan | X | Section 6-6.2.4 | Coordinate with Facility | |||||||||
| 1208757 | K16-336 | 336-POL PIPELINE ABOVE GROUND | BULK STORAGE-FILTER SEP PAD | CV-Filter Separator Control Valves | K16-336-FSCVL-165484 | K1600151 | Located on issue filter separator (middle) under canopy T 329 | Cla-Val | X | X | X | Section 4-4.2.2 | Operate System to Test | |||||||
| 1208757 | K16-336 | 336-POL PIPELINE ABOVE GROUND | BULK STORAGE-FILTER SEP PAD | CV-Filter Separator Control Valves | K16-336-FSCVL-170384 | K1600152 | Located on issue filter separator (west) under canopy T 329 | Cla-Val | X | X | X | Section 4-4.2.2 | Operate System to Test | |||||||
| 1208757 | K16-336 | 336-POL PIPELINE ABOVE GROUND | BULK STORAGE-FILTER SEP PAD | FT-Filter Separators | K16-336-FLSP-176424 | K1600161 | Issue filter separator (west) located under canopy T 329 | Facet USA Inc. | CFCS-D-3N39SB-1636FM | X | X | Section 3-6.2 | Base provides filter elements | 300 gpm | ||||||
| 1208757 | K16-336 | 336-POL PIPELINE ABOVE GROUND | BULK STORAGE-FILTER SEP PAD | FT-Filter Separators | K16-336-FLSP-170521 | K1600162 | Issue filter separator (middle) located under canopy T 329 | Facet USA Inc. | CFCS-D-3N39SB-1636FM | X | X | Section 3-6.2 | Base provides filter elements | 300 gpm | ||||||
| 1208757 | K16-336 | 336-POL PIPELINE ABOVE GROUND | BULK STORAGE-FILTER SEP PAD | PV-Pressure Gauges | K16-336-PVGA-176427 | K1600163 | Pressure gauge located on the 6 inch issue line for truck loading | HISCO | X | X | X | Section 6-7.1 | Notify Facility | |||||||
| 1208757 | K16-336 | 336-POL PIPELINE ABOVE GROUND | BULK STORAGE-FILTER SEP PAD | PV-Pressure Gauges | K16-336-PVGA-170386 | K1600164 | Pressure gauge located on the 6 inch issue line between the issue filter separator inlets | HISCO | X | X | X | Section 6-7.1 | Notify Facility | |||||||
| 1208757 | K16-336 | 336-POL PIPELINE ABOVE GROUND | BULK STORAGE-FILTER SEP PAD | MV-Ball Valves | K16-336-BLVL-170388 | K1600167 | Isolation ball valve for the pressure gauge located on the 6 inch JP-8 top load issue line | Flow-Tek | X | Section 6-6.2.4 | Coordinate with Facility | |||||||||
| 1208757 | K16-336 | 336-POL PIPELINE ABOVE GROUND | BULK STORAGE-FILTER SEP PAD | MV-Ball Valves | K16-336-BLVL-176429 | K1600168 | Isolation ball valve for the pressure gauge located on the 6 inch issue line between the issue filter separator inlets | Flow-Tek | X | Section 6-6.2.4 | Coordinate with Facility | |||||||||
| 1208757 | K16-336 | 336-POL PIPELINE ABOVE GROUND | BULK STORAGE-FILTER SEP PAD | MV-Ball Valves | K16-336-BLVL-170390 | K1600169 | Downstream isolation ball valve for the PRV located on the receipt filter separator (east) next to canopy T 329 | Flow-Tek | S20 | X | Section 6-6.2.4 | Coordinate with Facility | ||||||||
| 1208757 | K16-336 | 336-POL PIPELINE ABOVE GROUND | BULK STORAGE-FILTER SEP PAD | MV-Ball Valves | K16-336-BLVL-176431 | K1600170 | Downstream isolation ball valve for the air eliminator located on top of the receipt filter separator (east) next to canopy T 329 | Flow-Tek | S20 | X | Section 6-6.2.4 | Coordinate with Facility | ||||||||
| 1208757 | K16-336 | 336-POL PIPELINE ABOVE GROUND | BULK STORAGE-FILTER SEP PAD | MV-Ball Valves | K16-336-BLVL-170392 | K1600171 | Located on the sight glass drain for the receipt filter separator (east) next to canopy T 329 | APOLLO | X | Section 6-6.2.4 | Coordinate with Facility | |||||||||
| 1208757 | K16-336 | 336-POL PIPELINE ABOVE GROUND | BULK STORAGE-FILTER SEP PAD | MV-Ball Valves | K16-336-BLVL-176433 | K1600172 | Located on the receipt filter separator drain (east) next to canopy T 329 | Velan | X | Section 6-6.2.4 | Coordinate with Facility | |||||||||
| 1208757 | K16-336 | 336-POL PIPELINE ABOVE GROUND | BULK STORAGE-FILTER SEP PAD | FT-Filter Separators | K16-336-FLSP-170393 | K1600173 | Receipt filter separator (east) located next to canopy T 329 | Facet USA Inc. | CFCS-D-3N39SB-1636FM | X | X | Section 3-6.2 | Base provides filter elements | 300 gpm | ||||||
| 1208757 | K16-336 | 336-POL PIPELINE ABOVE GROUND | BULK STORAGE-FILTER SEP PAD | AE-Automatic Air Vents | K16-336-AAVT-167638 | K1600174 | Located on top of the issue filter separator (west) under canopy T 329 | Facet USA Inc. | CFCS-D-3N39SB-1636FM | X | Section 3-10.2 | Coordinate with Facility; Small Ladder Required | 300 gpm | |||||||
| 1208757 | K16-336 | 336-POL PIPELINE ABOVE GROUND | BULK STORAGE-FILTER SEP PAD | AE-Automatic Air Vents | K16-336-AAVT-167640 | K1600175 | Located on top of the issue filter separator (middle) under canopy T 329 | Facet USA Inc. | CFCS-D-3N39SB-1636FM | X | Section 3-10.2 | Coordinate with Facility; Small Ladder Required | 300 gpm | |||||||
| 1208757 | K16-336 | 336-POL PIPELINE ABOVE GROUND | BULK STORAGE-FILTER SEP PAD | AE-Automatic Air Vents | K16-336-AAVT-167642 | K1600176 | Located on top of the receipt filter separator (east) next to canopy T 329 | Facet USA Inc. | CFCS-D-3N39SB-1636FM | X | Section 3-10.2 | Coordinate with Facility; Small Ladder Required | 300 gpm | |||||||
| 1208757 | K16-336 | 336-POL PIPELINE ABOVE GROUND | BULK STORAGE-FILTER SEP PAD | PV-Pressure Gauges | K16-336-PVGA-170522 | K1600177 | Pressure gauge located on the issue filter separator DP gauge (west side) under canopy T-329 | X | X | X | Section 6-7.1 | Notify Facility | ||||||||
| 1208757 | K16-336 | 336-POL PIPELINE ABOVE GROUND | BULK STORAGE-FILTER SEP PAD | PV-Pressure Gauges | K16-336-PVGA-170395 | K1600178 | Pressure gauge located on the issue filter separator DP gauge (middle) under canopy T 329 | Ashcroft | X | X | X | Section 6-7.1 | Notify Facility | |||||||
| 1208757 | K16-336 | 336-POL PIPELINE ABOVE GROUND | BULK STORAGE-FILTER SEP PAD | PV-Pressure and Pressure/Vacuum Gauges | K16-336-PVGA-176436 | K1600179 | Pressure gauge located on the receipt filter separator DP gauge (east side) next to canopy T-329 | X | X | X | Section 6-7.1 | Notify Facility | ||||||||
| 1208757 | K16-336 | 336-POL PIPELINE ABOVE GROUND | BULK STORAGE-FILTER SEP PAD | PV-Differential Pressure Gauges | K16-336-DPGA-170541 | K1600180 | Located on the issue filter separator (west) under canopy T 329 | Gammon | 534-30 | X | X | Section 6-7.2 | Notify Facility | |||||||
| 1208757 | K16-336 | 336-POL PIPELINE ABOVE GROUND | BULK STORAGE-FILTER SEP PAD | PV-Differential Pressure Gauges | K16-336-DPGA-170529 | K1600181 | Located on the issue filter separator (middle) under canopy T 329 | Gammon | 534-30 | X | X | Section 6-7.2 | Notify Facility | |||||||
| 1208757 | K16-336 | 336-POL PIPELINE ABOVE GROUND | BULK STORAGE-FILTER SEP PAD | PV-Differential Pressure Gauges | K16-336-DPGA-170542 | K1600182 | Located on the receipt filter separator (east) next to canopy T 329 | Gammon | 534-30 | X | X | Section 6-7.2 | Notify Facility | |||||||
| 1208757 | K16-336 | 336-POL PIPELINE ABOVE GROUND | BULK STORAGE-FILTER SEP PAD | FP-Sight Flow Indicators | K16-336-SFND-170398 | K1600185 | Located on the issue filter separator (middle) under canopy T 329 | OPW | 1471 (1400 Series) | X | Section 6-12.3 | |||||||||
| 1208757 | K16-336 | 336-POL PIPELINE ABOVE GROUND | BULK STORAGE-FILTER SEP PAD | FP-Sight Flow Indicators | K16-336-SFND-170401 | K1600186 | Located on the issue filter separator (west) under canopy T 329 | OPW | 1471 (1400 Series) | X | Section 6-12.3 | |||||||||
| 1208757 | K16-336 | 336-POL PIPELINE ABOVE GROUND | BULK STORAGE-FILTER SEP PAD | CS-Containment Drain Valves | K16-336-CSGEN-167790 | K162206240921 | Containment drain valve for the filter pad containment located near the light poll near the filter separator pad (valve is mostly buried) | X | Section 8-10.1 | Key Required | ||||||||||
| 1208757 | K16-336 | 336-POL PIPELINE ABOVE GROUND | BULK STORAGE-FILTER SEP PAD | EC-Static Grounding Systems | K16-336-STGS-170400 | K162206240922 | Static grounding system for the filter pad area located in front of the receipt filter separator | X | Section 9-1.6.2 | |||||||||||
| 1208757 | K16-336 | 336-POL PIPELINE ABOVE GROUND | BULK STORAGE-FILTER SEP PAD | CS-Dike/Berm Floors (curbed) | K16-336-ETHDW-167833 | K2206270914 | Containment for the issue and receipt filter separators | X | Section 8-10.2.2 | |||||||||||
| 974505 | K16-334 | 334-AC TRK FUEL LDG | DISPENSER ISLAND-TRUCK LOADING | MV-Double Block and Bleed Valves | K16-334-DBBVL-163440 | 16126K16 | DBB valve located on the bottom loading piping before the meter | General Valve | C811 | X | X | X | Section 6-6.2.5 | Coordinate with Facility | ||||||
| 974505 | K16-334 | 334-AC TRK FUEL LDG | DISPENSER ISLAND-TRUCK LOADING | MV-Double Block and Bleed Valves | K16-334-DBBVL-163441 | 16127K16 | DBB valve located on the bottom loading piping after the meter | General Valve | CA811 | X | X | X | Section 6-6.2.5 | Coordinate with Facility | ||||||
| 974505 | K16-334 | 334-AC TRK FUEL LDG | DISPENSER ISLAND-TRUCK LOADING | MV-Double Block and Bleed Valves | 11 | K16-334-DBBVL-163442 | 16128K16 | DBB valve located on the top loading piping before the meter | General Valve | 8110-H/G | X | X | X | Section 6-6.2.5 | Coordinate with Facility | |||||
| 974505 | K16-334 | 334-AC TRK FUEL LDG | DISPENSER ISLAND-TRUCK LOADING | MV-Double Block and Bleed Valves | 12 | K16-334-DBBVL-163443 | 16129K16 | DBB valve located on the top loading piping after the meter | General Valve | CA811 | X | X | X | Section 6-6.2.5 | Coordinate with Facility | |||||
| 974505 | K16-334 | 334-AC TRK FUEL LDG | DISPENSER ISLAND-TRUCK LOADING | TV-Thermal and Pressure Relief Valves | 1 | K16-334-TPRVL-164983 | 16130K16 | PRV located on the bottom loading control valve | JOKWANG | BSR-HP | X | X | Section 6-6.3 | Coordinate with Facility to Test | Set pressure 115 psig | |||||
| 974505 | K16-334 | 334-AC TRK FUEL LDG | DISPENSER ISLAND-TRUCK LOADING | TV-Thermal and Pressure Relief Valves | 2 | K16-334-TPRVL-164984 | 16131K16 | PRV located on the bottom loading pantograph DBB valve. | JOKWANG | BSR-HP | X | X | Section 6-6.3 | Coordinate with Facility to Test | Set pressure 60 psig | |||||
| 974505 | K16-334 | 334-AC TRK FUEL LDG | DISPENSER ISLAND-TRUCK LOADING | TV-Thermal and Pressure Relief Valves | 3 | K16-334-TPRVL-164985 | 16132K16 | PRV located on the top loading control valve. | JOKWANG | BSR-HP | X | X | Section 6-6.3 | Coordinate with Facility to Test | Set pressure 115 psig | |||||
| 974505 | K16-334 | 334-AC TRK FUEL LDG | DISPENSER ISLAND-TRUCK LOADING | MV-Ball Valves | K16-334-BLVL-157246 | K1600095 | Isolation ball valve for the pressure gauge located on the bottom load piping between the flow meter and the strainer | Flow-Tek | X | Section 6-6.2.4 | Coordinate with Facility | |||||||||
| 974505 | K16-334 | 334-AC TRK FUEL LDG | DISPENSER ISLAND-TRUCK LOADING | MV-Ball Valves | K16-334-BLVL-157247 | K1600096 | Isolation ball valve for the pressure gauge located on the top load piping between the flow meter and the strainer | Flow-Tek | X | Section 6-6.2.4 | Coordinate with Facility | |||||||||
| 974505 | K16-334 | 334-AC TRK FUEL LDG | DISPENSER ISLAND-TRUCK LOADING | MV-Ball Valves | K16-334-BLVL-157248 | K1600097 | Ball valve located on the side of the top load piping next to the pressure gauge (sampling connections) | Flow-Tek | X | Section 6-6.2.4 | Coordinate with Facility | |||||||||
| 974505 | K16-334 | 334-AC TRK FUEL LDG | DISPENSER ISLAND-TRUCK LOADING | MV-Ball Valves | K16-334-BLVL-157249 | K1600098 | Ball valve located on the bottom load piping (low point) | Flow-Tek | X | Section 6-6.2.4 | Coordinate with Facility | |||||||||
| 974505 | K16-334 | 334-AC TRK FUEL LDG | DISPENSER ISLAND-TRUCK LOADING | MV-Ball Valves | K16-334-BLVL-157250 | K1600099 | Ball valve located on the top load piping (low point) | Flow-Tek | X | Section 6-6.2.4 | Coordinate with Facility | |||||||||
| 974505 | K16-334 | 334-AC TRK FUEL LDG | DISPENSER ISLAND-TRUCK LOADING | MV-Ball Valves | K16-334-BLVL-157251 | K1600100 | Ball valve located on the top load piping relief line (top loading platform) | Flow-Tek | X | Section 6-6.2.4 | Coordinate with Facility | |||||||||
| 974505 | K16-334 | 334-AC TRK FUEL LDG | DISPENSER ISLAND-TRUCK LOADING | SF-Fuel Truck Containment Areas | K16-334-FTKRCC-170524 | K1600101 | Containment around truck loading/dispenser island | X | X | Section 11-1.1 | ||||||||||
| 974505 | K16-334 | 334-AC TRK FUEL LDG | DISPENSER ISLAND-TRUCK LOADING | CV-Truck Fill Valves | K16-334-PTCVL-166678 | K1600102 | Control valve located on top load piping for top load pantograph | Cla-Val | 3100 G | X | X | Section 6-6.5.1 | Operate System to Test | |||||||
| 974505 | K16-334 | 334-AC TRK FUEL LDG | DISPENSER ISLAND-TRUCK LOADING | CV-Truck Fill Valves | K16-334-PTCVL-166679 | K1600103 | Control valve located on bottom load piping for bottom load pantograph | Cla-Val | 3100 G | X | X | Section 6-6.5.1 | Operate System to Test | |||||||
| 974505 | K16-334 | 334-AC TRK FUEL LDG | DISPENSER ISLAND-TRUCK LOADING | MT-Positive Displacement Meters | K16-334-PDMT-156524 | K1600108 | Bottom loading meter | Liquid Controls | M-40-1 | X | X | Section 3-7.1 | Operate System to Test; Fuel Truck Required | 45-450 GPM | ||||||
| 974505 | K16-334 | 334-AC TRK FUEL LDG | DISPENSER ISLAND-TRUCK LOADING | MT-Positive Displacement Meters | K16-334-PDMT-156525 | K1600109 | Top loading meter | Liquid Controls | M-25-1 | X | X | Section 3-7.1 | Operate System to Test; Fuel Truck Required | 30-300 GPM | ||||||
| 974505 | K16-334 | 334-AC TRK FUEL LDG | DISPENSER ISLAND-TRUCK LOADING | EC-Ground Reels - Static Grounding Systems | K16-334-STGS-170512 | K1600110 | Ground reel located on the bottom loading pantograph side | X | X | Section 9-1.6.2 | ||||||||||
| 974505 | K16-334 | 334-AC TRK FUEL LDG | DISPENSER ISLAND-TRUCK LOADING | EC-Ground Reels - Static Grounding Systems | K16-334-STGS-170525 | K1600111 | Ground reel located on the top loading pantograph side | Hannay Reels | GR75 | X | X | Section 9-1.6.2 | ||||||||
| 974505 | K16-334 | 334-AC TRK FUEL LDG | DISPENSER ISLAND-TRUCK LOADING | HN-Fueling Nozzles | K16-334-FLNZ-155999 | K1600112 | Located on the bottom loading pantograph | Cla-Val | D-2 Nozzle | X | X | Section 4-7.3 | ||||||||
| 974505 | K16-334 | 334-AC TRK FUEL LDG | DISPENSER ISLAND-TRUCK LOADING | H3-Fixed Pantographs | K16-334-FXPNT-155614 | K1600113 | Bottom loading pantograph | Cla-Val | X | Section 4-7.1.1 | ||||||||||
| 974505 | K16-334 | 334-AC TRK FUEL LDG | DISPENSER ISLAND-TRUCK LOADING | H3-Fixed Pantographs | K16-334-FXPNT-155615 | K1600114 | Top loading pantograph | Emco Wheaton | X | Section 4-7.1.1 | ||||||||||
| 974505 | K16-334 | 334-AC TRK FUEL LDG | DISPENSER ISLAND-TRUCK LOADING | PC-Aboveground Piping and Equipment Coating | K16-334-AGPCT-170346 | K1600115 | Top loading piping (4 inch measured to filter pad) | Section 6-10.1 | ||||||||||||
| 974505 | K16-334 | 334-AC TRK FUEL LDG | DISPENSER ISLAND-TRUCK LOADING | PC-Aboveground Piping and Equipment Coating | K16-334-AGPCT-170513 | K1600116 | Bottom loading piping (4 inch measured to filter pad) | Section 6-10.1 |
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .