This document is a Facility Maintenance Plan (FMP) for the Camp Carroll fuel service station located in Waegwan, Korea, prepared by APTIM Federal Services, LLC under contract W912DY-21-F-0076 with the Pacific Ocean Division. The facility contains multiple fuel storage and dispensing systems, including diesel and motor gasoline (MOGAS) tanks with a total capacity of 25,000 gallons, multiple dispensers, truck offloading capabilities, and associated infrastructure such as containment areas, grounding systems, valves, pumps, and emergency safety equipment.

The maintenance plan provides a comprehensive inventory of facility assets, detailing specific maintenance requirements for each component according to Unified Facilities Criteria (UFC) standards. The document includes detailed tracking information like Component Unique Identifiers (CUID), manufacturer specifications, maintenance frequencies (quarterly, semi-annual, and annual), and special considerations for each asset. The facility is operated by Ahntech Corporation and maintained to ensure safe and efficient fuel storage, dispensing, and transfer operations for ground vehicles at Camp Carroll.

View the file

Other files

File Type Posted
Attachment 1 PWS amd Appendices POF - V1.pdf PDF
CDRL Set 10 - 37-40.pdf PDF
CDRL Set 16 - 60-64.pdf PDF
CDRL Set 15 - 57-60.pdf PDF
CDRL Set 4 - 13-16..pdf PDF
CDRL Set 2 - 5-8.pdf PDF
CDRL Set 14 - 53-56.pdf PDF
FMP POF KJU_20251029.xlsx XLSX spreadsheet
FMP POF POH_20251029.xlsx XLSX spreadsheet
Attachment 0005 Instructions and Evaluation Factors DRAFT.docx DOCX document
FMP POF WAL_20251029.xlsx XLSX spreadsheet
CDRL Set 17 - 65-67.pdf PDF
CDRL Set 3 - 9-12.pdf PDF
CDRL Set 13 - 49-52.pdf PDF
Attachment 4 - PPQ Sample.pdf PDF
FMP POF OSN_20251029.xlsx XLSX spreadsheet
FMP POF SUW_20251029.xlsx XLSX spreadsheet
FMP POF KUS_20251029.xlsx XLSX spreadsheet
Attachment 2 Sample Service Order (Appendix A - Attachment 1 Service Order Form).xlsx XLSX spreadsheet
FMP POF CSY_20251029.xlsx XLSX spreadsheet
CDRL Set 6 - 21-24.pdf PDF
CDRL Set 8 - 29-32.pdf PDF
CDRL Set 5 - 17-20.pdf PDF
CDRL Set 1 - 1-4.pdf PDF
CDRL Set 9 - 33-36.pdf PDF
Appendix K Real Property Data.xlsx XLSX spreadsheet
Attachment 3 Technical Eval Form - V1.pdf PDF
FMP POF YCH_20251029.xlsx XLSX spreadsheet
FMP POF TAE_20251029.xlsx XLSX spreadsheet
FMP POF YSG_20251029.xlsx XLSX spreadsheet
CDRL Set 7 - 25-28.pdf PDF
CDRL Set 12 - 45-48.pdf PDF
CDRL Set 11 - 41-44.pdf PDF
FMP POF KUN_20251029.xlsx XLSX spreadsheet
FMP POF HUM_20251029.xlsx XLSX spreadsheet
FMP POF KIM_20251029.xlsx XLSX spreadsheet
FMP POF K-16_20251029.xlsx XLSX spreadsheet
Show all 37

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Administrative

ADMINISTRATIVE
LocationInstallation NameCamp Carroll
DLA Site CodeCRL
RPSUID4238
Hours of Operation0800-1630
AddressWaegwan, Korea
ContractContractor
Contract #
Local POCsPrimary QAE
QAE Phone
QAE Email
Alternate QAE
Alt QAE Phone
Alt QAE Email
Contractor POCsContractor PM
Contractor PM Phone
Contractor PM Email
Contractor QC Manager
Contractor QC Phone
Contractor QC Email
Contractor SM
Contractor SM Phone
Contractor SM Email
USACE POCsUSACE PM/COR
USACE PM/COR Phone
USACE PM/COR Email
USACE PE
USACE PE Phone
USACE PE Email
USACE KO
USACE KO Phone
USACE KO Email
USACE Monthly Report Inbox

Pacific Ocean Division, POD-AF

W912DY-21-F-0076&"-,Bold"&16Camp Carroll
CRLFacility Maintenance Plan

OY3 Q1

&A &P of &N APTIM Federal Services, LLC

Instructions:

This table shows the minimum information required. Additional details should be included based on site specific requirements. Additional POCs may be required.

General Facility Description

General Facility Description
Installation NameCamp Carroll
DLA Site CodeCRL
LocationWaegwan, Korea
Service Station: (1) 5,000-gallon diesel AST (930); (1) 10,000-gallon diesel AST (962); (1) 10,000-gallon Mogas AST (963); (2) Mogas dispensers 1/2 and 3/4 (961); (2) diesel dispensers 5/6 and 7/8 (960); containment drains/trench around dispenser islands; truck receipt for diesel and Mogas; truck offload (964) and storage tanks drain to OWS; dispenser islands OWS; POL office/control room; temporary office trailer.
Contractor maintained. Ahntech Corporation operates the station and performs routine general maintenance.

Pacific Ocean Division, POD-AF

W912DY-21-F-0076&"-,Bold"&16Camp Carroll
CRLFacility Maintenance Plan

OY3 Q1

&A &P of &N APTIM Federal Services, LLC

Instructions:

Include a general facility overview and description of each fuel system for the sites in accordance with UFC 3-460-01. Examples include: Bulk Storage Facilities, Aircraft Fueling Facilities, Marine and Dispensing Facilities, Ground Products Fueling Facilities, Alternate POL Facilities, and Support Facilities. Also include facility #s, facility names, fuel type, photos, and any other pertinent information.

Include Site Specific Conditions and Restrictions in this tab.

Communication Plan

Pacific Ocean Division, POD-AF

W912DY-21-F-0076&"-,Bold"&16Camp Carroll
CRLFacility Maintenance Plan

OY3 Q1

&A &P of &N APTIM Federal Services, LLC

Instructions:

Communication plan shall address in/out briefs, lines of communication, coordination for access, etc.

Site Specific APP

Pacific Ocean Division, POD-AF

W912DY-21-F-0076&"-,Bold"&16Camp Carroll
CRLFacility Maintenance Plan

OY3 Q1

&A &P of &N APTIM Federal Services, LLC

Instructions:

Site Specific Addendum and Activity Hazard Analysis, which are Attachments to the APP, specific to activities or tasks related to recurring maintenance for this site.

PM Schedule

Pacific Ocean Division, POD-AF

W912DY-21-F-0076&"-,Bold"&16&K000000Camp Carroll
CRLFacility Maintenance Plan

OY3 Q1

&A &P of &N APTIM Federal Services, LLC

Instructions:

Link PM schedule here

FS-PF Schedule

FILTER SEPARATOR/PRE-FILTER MAINTENANCE SCHEDULES
Applicable Facility AssetsCoalescer/Separator InformationSpecial Considerations
Real Property Unique Identifier
(RPUID)Real Property Facility #Real Property Facility NameOperational AreaComponent TypeBase Asset IDComponent Unique Identifier (CUID)APTIM Asset ID*Asset DescriptionMakeModelCapacity (GPM)UFC Section ReferenceNumber of Coalescer CartridgesNumber of
Separator CartridgesCoalescer Cartridges
Model #Separator Cartridge
Model #Clean or Replace
Separator CartridgeGasket
Model #Date Last ReplacedReplacement Due DateOperator/ Equipment RequirementsSystem AvailabilitySite Self Performs
(Y/N)Comments
No FS/PF for CRL

Pacific Ocean Division, POD-AF

W912DY-21-F-0076&"-,Bold"&16Camp Carroll
CRLFacility Maintenance Plan

OY3 Q1

&A &P of &N APTIM Federal Services, LLC

Instructions:

1. Input all data as indicated on the sheet.

2. Additional documents referred to in the Special Considerations column shall be included as an appendix to this FMP.

3. The contractor shall generate a Component Unique Identifier (CUID) for each component utilizing the Component Acronym Sheet within this Work Book. The unique identifier must use the following:

Three letter Site Code - Facility # - Component Acronym - Sequential number Example: AAD-00063A-RCVL-0001

If component acronym is not listed, the contractor shall request an acronym be established through the HNC Project Manager and Project Engineer via email. Contractors may utilize other means of tracking/labeling assets such as QR codes in addition to the required CUID however, tracking/labeling must correlate with the CUID. This CUID shall be the standard for all DLA capitalized equipment.

4. Utilize the UFC Section Reference Work Category as noted on the Component Acronym Sheet.

5. Enter any applicable manufacturer requirements not stated in the UFC. References are acceptable with attachments.

6. Enter any applicable operator support or government owned equipment required to complete the RM task.

7. Enter impact on system availability by performing the RM task. This could include shutdown, lockout, or similar impacts.

8. Filter Separators and Pre-Filters identified here shall also be provided in the Task Matrix Tab.

9. Print Hard Copies as 11x17.

Task Matrix

Applicable Facility AssetsUFC System Level Maintenance FrequencySpecial Considerations
RPUIDReal Property Facility #Facility NameOperational AreaComponent TypeBase Asset NameComponent Unique ID CUIDAPTIM Asset IDAsset DescriptionMakeModelCapacity / SizeQuarterlySemi AnnualAnnualUFC Section ReferenceAdditional Manufacturer RM RequirementsOperator/Equipment RequirementsSystem AvailabilityOther ContractComments
974400CRL-929929-FUEL/POL BLDGSERVICE STATIONGF-Gov SS EFSO SystemsS 929CRL-929-EFSO-176215CRL00001EFSO located on the front of building 929 next to cashier windowEFDB175-UM1 1/02XSection 7-16Operate System to TestFacility S929 is the admin/cash sale office
974400CRL-929929-FUEL/POL BLDGSERVICE STATIONGF-Gov SS EFSO SystemsCRL-929-EFSO-176217CRL00002EFSO located at the exit gateEFDB175-UM1 1/02XSection 7-16Operate System to Test
974400CRL-929929-FUEL/POL BLDGSERVICE STATIONSF-Oil/Water SeparatorsCRL-929-OWS-169698CRL00003OWS located next to the above ground tanksTYPE DWXTCSI-15XXSection 11-5Notify Facility
974400CRL-929929-FUEL/POL BLDGSERVICE STATIONEQ-Air VentCRL-929-ASSET-169699CRL00004Goose neck style vent located at the OWSNon-Appx G Class
974400CRL-929929-FUEL/POL BLDGSERVICE STATIONEQ-Air VentCRL-929-ASSET-176219CRL00005Goose neck style vent located at the OWSNon-Appx G Class
974400CRL-929929-FUEL/POL BLDGSERVICE STATIONSF-Emergency Eyewash/ShowersCRL-929-EMEWSH-169700CRL00006Located next to facility S929SpeakmanXXXSection 11-3Notify Facility
1169748CRL-930930-DIESEL STORAGE TANK #2 AGSERVICE STATIONMV-Ball ValvesCRL-930-BLVL-169856CRL00007Located on top of the diesel tankJomar ValveXSection 6-6.2.4Notify Facility
1169748CRL-930930-DIESEL STORAGE TANK #2 AGSERVICE STATIONEC-Static Grounding SystemsCRL-930-STGS-169701CRL00008Tank grounding cablesXSection 9-1.6.2
1169748CRL-930930-DIESEL STORAGE TANK #2 AGSERVICE STATIONGF-Ground Vehicle Fuel PipingCRL-930-GVFP-169718CRL00009Diesel issue piping 2 inch aboveground and below ground from tank S-930 to Diesel dispensers 5,6,7, and 8.XXSection 7-11Coordinate with Facility
1169748CRL-930930-DIESEL STORAGE TANK #2 AGSERVICE STATIONTA-Emergency VentsCRL-930-EMGVT-167457CRL00010Emergency vent primary located on top of the diesel tankClay and BaileyXSection 8-9.4
1169748CRL-930930-DIESEL STORAGE TANK #2 AGSERVICE STATIONTA-Emergency VentsCRL-930-EMGVT-167458CRL00011Emergency vent annular located on top of the diesel tankClay and BaileyXSection 8-9.4
1169748CRL-930930-DIESEL STORAGE TANK #2 AGSERVICE STATIONEQ-Real PropertyCRL-930-ASSET-169719CRL00012Anti syphon valve located on top of diesel tank S-930OPWNon-Appx G Class
1169748CRL-930930-DIESEL STORAGE TANK #2 AGSERVICE STATIONTK-Aboveground Shop-Fabricated TanksS-930CRL-930-AGSFP-176221CRL00013Diesel tankContainment Solutions, InLDP5000XXSection 8-5.1
1169748CRL-930930-DIESEL STORAGE TANK #2 AGSERVICE STATIONEQ-Air VentCRL-930-ASSET-176222CRL00014Vent located on top of the diesel tankNon-Appx G Class
1169748CRL-930930-DIESEL STORAGE TANK #2 AGSERVICE STATIONTA-Mechanical Tape Gauges (non-ATG)CRL-930-MTGA-176223CRL00015Tank gauge located on top of the diesel tankMorrison Bros. Co.XSection 8-9.7
PWS Appx K-3CRL-929OHP929OHP-FOS - OVERHEAD PROTECT FOR VEH FILL STASERVICE STATIONSF-Fuel Truck Containment AreasCRL-929OHP-FTKRCC-169702CRL00017Diesel and MOGAS Dispenser containment systemXXSection 11-1.1
974111CRL-960960-LAND VEHICLE FUELING FACILITY, DIESEL/JP8SERVICE STATIONDS-Dispenser CabinetKDR 5 and 6CRL-960-DSCB-153283CRL00018Diesel Dispensers 5 and 6Gasboy9853KTW1MXSection 7-7Key Required
974111CRL-960960-LAND VEHICLE FUELING FACILITY, DIESEL/JP8SERVICE STATIONDS-BreakawaysCRL-960-DSBW-168089CRL00019Diesel Dispenser 5XSection 7-4
974111CRL-960960-LAND VEHICLE FUELING FACILITY, DIESEL/JP8SERVICE STATIONDS-BreakawaysCRL-960-DSBW-168090CRL00020Diesel Dispenser 6OPWXSection 7-4
974111CRL-960960-LAND VEHICLE FUELING FACILITY, DIESEL/JP8SERVICE STATIONDS-Dispenser FiltersCRL-960-DSFLR-165632CRL00021Diesel Dispenser 5Cim-Tek FiltrationXSection 7-9Key Required
974111CRL-960960-LAND VEHICLE FUELING FACILITY, DIESEL/JP8SERVICE STATIONDS-Dispenser FiltersCRL-960-DSFLR-165633CRL00022Diesel Dispenser 6Cim-Tek FiltrationXSection 7-9Key Required
974111CRL-960960-LAND VEHICLE FUELING FACILITY, DIESEL/JP8SERVICE STATIONDS-Dispenser HosesCRL-960-DSHS-169703CRL00023Diesel Dispenser 5 Short HoseXSection 7-3
974111CRL-960960-LAND VEHICLE FUELING FACILITY, DIESEL/JP8SERVICE STATIONDS-Dispenser HosesCRL-960-DSHS-169704CRL00024Diesel Dispenser 5 Long HoseParkerXSection 7-3
974111CRL-960960-LAND VEHICLE FUELING FACILITY, DIESEL/JP8SERVICE STATIONDS-Dispenser HosesCRL-960-DSHS-169705CRL00025Diesel Dispenser 6 Short HoseVapor Systems TechnologieXSection 7-3
974111CRL-960960-LAND VEHICLE FUELING FACILITY, DIESEL/JP8SERVICE STATIONDS-Dispenser HosesCRL-960-DSHS-169858CRL00026Diesel Dispenser 6 Long HoseVapor Systems TechnologieXSection 7-3
974111CRL-960960-LAND VEHICLE FUELING FACILITY, DIESEL/JP8SERVICE STATIONDS-Dispenser MetersCRL-960-DSMTR-165795CRL00027Diesel Dispenser 5Gilbarco Veeder-RootT20150XSection 7-8Key Required; OPERATE SYSTEM TO TEST
974111CRL-960960-LAND VEHICLE FUELING FACILITY, DIESEL/JP8SERVICE STATIONDS-Dispenser MetersCRL-960-DSMTR-165796CRL00028Diesel Dispenser 6Gilbarco Veeder-RootT20150XSection 7-8Key Required; OPERATE SYSTEM TO TEST
974111CRL-960960-LAND VEHICLE FUELING FACILITY, DIESEL/JP8SERVICE STATIONDS-Dispenser NozzlesCRL-960-DSNZ-165813CRL00029Diesel Dispenser 5TJXSection 7-2Operate System to Test
974111CRL-960960-LAND VEHICLE FUELING FACILITY, DIESEL/JP8SERVICE STATIONDS-Dispenser NozzlesCRL-960-DSNZ-165814CRL00030Diesel Dispenser 6CATLOWXSection 7-2Operate System to Test
974111CRL-960960-LAND VEHICLE FUELING FACILITY, DIESEL/JP8SERVICE STATIONDS-Dispenser SumpsCRL-960-DSSMP-169720CRL00031Diesel Dispensers 5 and 6XSection 7-13Key Required
974111CRL-960960-LAND VEHICLE FUELING FACILITY, DIESEL/JP8SERVICE STATIONDS-Emergency Shutoff Valves (Shear Valves)CRL-960-ESHVL-169721CRL00032Diesel Dispensers 5 and 6TokheimMODEL 52AXSection 7-12Key Required; OPERATE SYSTEM TO TEST
974111CRL-960960-LAND VEHICLE FUELING FACILITY, DIESEL/JP8SERVICE STATIONDS-Hose RetrieverCRL-960-HSRTV-176224CRL00033Diesel Dispenser 5XSection 7-6
974111CRL-960960-LAND VEHICLE FUELING FACILITY, DIESEL/JP8SERVICE STATIONDS-Hose RetrieverCRL-960-HSRTV-176225CRL00034Diesel Dispenser 6XSection 7-6
974111CRL-960960-LAND VEHICLE FUELING FACILITY, DIESEL/JP8SERVICE STATIONDS-SwivelsCRL-960-DSSW-176226CRL00035Diesel Dispenser 5XSection 7-5
974111CRL-960960-LAND VEHICLE FUELING FACILITY, DIESEL/JP8SERVICE STATIONDS-SwivelsCRL-960-DSSW-169706CRL00036Diesel Dispenser 6XSection 7-5
974111CRL-960960-LAND VEHICLE FUELING FACILITY, DIESEL/JP8SERVICE STATIONDS-Self-Contained Dispenser PumpsCRL-960-SCDSP-165862CRL00037Diesel Dispenser 5BennettXSection 7-15.2Key Required; OPERATE SYSTEM TO TEST
974111CRL-960960-LAND VEHICLE FUELING FACILITY, DIESEL/JP8SERVICE STATIONDS-Self-Contained Dispenser PumpsCRL-960-SCDSP-165863CRL00038Diesel Dispenser 6BennettXSection 7-15.2Key Required; OPERATE SYSTEM TO TEST
974111CRL-960960-LAND VEHICLE FUELING FACILITY, DIESEL/JP8SERVICE STATIONDS-Dispenser CabinetKDR 7 and 8CRL-960-DSCB-153284CRL00039Diesel Dispensers 7 and 8Gasboy9853KTW1MXSection 7-7Key Required
974111CRL-960960-LAND VEHICLE FUELING FACILITY, DIESEL/JP8SERVICE STATIONDS-BreakawaysCRL-960-DSBW-168091CRL00040Diesel Dispenser 7XSection 7-4
974111CRL-960960-LAND VEHICLE FUELING FACILITY, DIESEL/JP8SERVICE STATIONDS-BreakawaysCRL-960-DSBW-168092CRL00041Diesel Dispenser 8EBWXSection 7-4
974111CRL-960960-LAND VEHICLE FUELING FACILITY, DIESEL/JP8SERVICE STATIONDS-Dispenser FiltersCRL-960-DSFLR-165634CRL00042Diesel Dispenser 7Cim-Tek FiltrationXSection 7-9Key Required
974111CRL-960960-LAND VEHICLE FUELING FACILITY, DIESEL/JP8SERVICE STATIONDS-Dispenser FiltersCRL-960-DSFLR-165635CRL00043Diesel Dispenser 8Cim-Tek FiltrationXSection 7-9Key Required
974111CRL-960960-LAND VEHICLE FUELING FACILITY, DIESEL/JP8SERVICE STATIONDS-Dispenser HosesCRL-960-DSHS-169707CRL00044Diesel Dispenser 7 Short HoseIRPCOXSection 7-3
974111CRL-960960-LAND VEHICLE FUELING FACILITY, DIESEL/JP8SERVICE STATIONDS-Dispenser HosesCRL-960-DSHS-176227CRL00045Diesel Dispenser 7 Long HoseParkerXSection 7-3
974111CRL-960960-LAND VEHICLE FUELING FACILITY, DIESEL/JP8SERVICE STATIONDS-Dispenser HosesCRL-960-DSHS-169860CRL00046Diesel Dispenser 8 Short HoseXSection 7-3
974111CRL-960960-LAND VEHICLE FUELING FACILITY, DIESEL/JP8SERVICE STATIONDS-Dispenser HosesCRL-960-DSHS-169861CRL00047Diesel Dispenser 8 Long HoseParkerXSection 7-3
974111CRL-960960-LAND VEHICLE FUELING FACILITY, DIESEL/JP8SERVICE STATIONDS-Dispenser MetersCRL-960-DSMTR-165797CRL00048Diesel Dispenser 7Gilbarco Veeder-RootT20150XSection 7-8Key Required; OPERATE SYSTEM TO TEST
974111CRL-960960-LAND VEHICLE FUELING FACILITY, DIESEL/JP8SERVICE STATIONDS-Dispenser MetersCRL-960-DSMTR-165798CRL00049Diesel Dispenser 8Gilbarco Veeder-RootT20150XSection 7-8Key Required; OPERATE SYSTEM TO TEST
974111CRL-960960-LAND VEHICLE FUELING FACILITY, DIESEL/JP8SERVICE STATIONDS-Dispenser NozzlesCRL-960-DSNZ-165815CRL00050Diesel Dispenser 7OPWXSection 7-2Operate System to Test
974111CRL-960960-LAND VEHICLE FUELING FACILITY, DIESEL/JP8SERVICE STATIONDS-Dispenser NozzlesCRL-960-DSNZ-165816CRL00051Diesel Dispenser 8KTEXSection 7-2Operate System to Test
974111CRL-960960-LAND VEHICLE FUELING FACILITY, DIESEL/JP8SERVICE STATIONDS-Dispenser SumpsCRL-960-DSSMP-169708CRL00052Diesel Dispensers 7 and 8XSection 7-13Key Required
974111CRL-960960-LAND VEHICLE FUELING FACILITY, DIESEL/JP8SERVICE STATIONDS-Emergency Shutoff Valves (Shear Valves)CRL-960-ESHVL-169863CRL00053Diesel Dispensers 7 and 8TokheimMODEL 52AXSection 7-12Key Required; OPERATE SYSTEM TO TEST
974111CRL-960960-LAND VEHICLE FUELING FACILITY, DIESEL/JP8SERVICE STATIONDS-Hose RetrieverCRL-960-HSRTV-169864CRL00054Diesel Dispenser 7XSection 7-6
974111CRL-960960-LAND VEHICLE FUELING FACILITY, DIESEL/JP8SERVICE STATIONDS-Hose RetrieverCRL-960-HSRTV-169709CRL00055Diesel Dispenser 8XSection 7-6
974111CRL-960960-LAND VEHICLE FUELING FACILITY, DIESEL/JP8SERVICE STATIONDS-SwivelsCRL-960-DSSW-169722CRL00056Diesel Dispenser 7XSection 7-5
974111CRL-960960-LAND VEHICLE FUELING FACILITY, DIESEL/JP8SERVICE STATIONDS-SwivelsCRL-960-DSSW-169723CRL00057Diesel Dispenser 8XSection 7-5
974111CRL-960960-LAND VEHICLE FUELING FACILITY, DIESEL/JP8SERVICE STATIONDS-Self-Contained Dispenser PumpsCRL-960-SCDSP-165864CRL00058Diesel Dispenser 7BennettXSection 7-15.2Key Required; OPERATE SYSTEM TO TEST
974111CRL-960960-LAND VEHICLE FUELING FACILITY, DIESEL/JP8SERVICE STATIONDS-Self-Contained Dispenser PumpsCRL-960-SCDSP-165865CRL00059Diesel Dispenser 8BennettXSection 7-15.2Key Required; OPERATE SYSTEM TO TEST
974111CRL-960960-LAND VEHICLE FUELING FACILITY, DIESEL/JP8SERVICE STATIONSF-CanopiesCRL-960-CNPY-167398CRL00060MOGAS and Diesel Dispenser canopyXSection 11-2.2
974398CRL-961961-LAND VEHICLE FUELING FACILITY, MOGASSERVICE STATIONDS-Dispenser CabinetMOGAS 1 and 2CRL-961-DSCB-153285CRL00061MOGAS Dispensers 1 and 2Gasboy9853KXTW1XSection 7-7Key Required
974398CRL-961961-LAND VEHICLE FUELING FACILITY, MOGASSERVICE STATIONDS-Dispenser CabinetMOGAS 3 and 4CRL-961-DSCB-153286CRL00063MOGAS Dispensers 3 and 4Gasboy9853KXTW1XSection 7-7Key Required
974398CRL-961961-LAND VEHICLE FUELING FACILITY, MOGASSERVICE STATIONDS-BreakawaysCRL-961-DSBW-168093CRL00064MOGAS Dispenser 1XSection 7-4
974398CRL-961961-LAND VEHICLE FUELING FACILITY, MOGASSERVICE STATIONDS-BreakawaysCRL-961-DSBW-168094CRL00065MOGAS Dispenser 2OPWXSection 7-4
974398CRL-961961-LAND VEHICLE FUELING FACILITY, MOGASSERVICE STATIONDS-Dispenser FiltersCRL-961-DSFLR-165636CRL00066MOGAS Dispenser 1Cim-Tek FiltrationXSection 7-9Key Required
974398CRL-961961-LAND VEHICLE FUELING FACILITY, MOGASSERVICE STATIONDS-Dispenser FiltersCRL-961-DSFLR-165637CRL00067MOGAS Dispenser 2Cim-Tek FiltrationXSection 7-9Key Required
974398CRL-961961-LAND VEHICLE FUELING FACILITY, MOGASSERVICE STATIONDS-Dispenser HosesCRL-961-DSHS-169710CRL00068MOGAS Dispenser 1 Short HoseXSection 7-3
974398CRL-961961-LAND VEHICLE FUELING FACILITY, MOGASSERVICE STATIONDS-Dispenser HosesCRL-961-DSHS-176228CRL00069MOGAS Dispenser 1 Long HoseParkerXSection 7-3
974398CRL-961961-LAND VEHICLE FUELING FACILITY, MOGASSERVICE STATIONDS-Dispenser HosesCRL-961-DSHS-176229CRL00070MOGAS Dispenser 2 Short HoseXSection 7-3
974398CRL-961961-LAND VEHICLE FUELING FACILITY, MOGASSERVICE STATIONDS-Dispenser HosesCRL-961-DSHS-169866CRL00071MOGAS Dispenser 2 Long HoseParkerXSection 7-3
974398CRL-961961-LAND VEHICLE FUELING FACILITY, MOGASSERVICE STATIONDS-Dispenser MetersCRL-961-DSMTR-165799CRL00072MOGAS Dispenser 1Gilbarco Veeder-RootT20150XSection 7-8Key Required; OPERATE SYSTEM TO TEST
974398CRL-961961-LAND VEHICLE FUELING FACILITY, MOGASSERVICE STATIONDS-Dispenser MetersCRL-961-DSMTR-165800CRL00073MOGAS Dispenser 2Gilbarco Veeder-RootT20150XSection 7-8Key Required; OPERATE SYSTEM TO TEST
974398CRL-961961-LAND VEHICLE FUELING FACILITY, MOGASSERVICE STATIONDS-Dispenser NozzlesCRL-961-DSNZ-165817CRL00074MOGAS Dispenser 1OPWXSection 7-2Operate System to Test
974398CRL-961961-LAND VEHICLE FUELING FACILITY, MOGASSERVICE STATIONDS-Dispenser NozzlesCRL-961-DSNZ-165818CRL00075MOGAS Dispenser 2OPWXSection 7-2Operate System to Test
974398CRL-961961-LAND VEHICLE FUELING FACILITY, MOGASSERVICE STATIONDS-Dispenser SumpsCRL-961-DSSMP-176230CRL00076MOGAS Dispensers 1 and 2XSection 7-13Key Required
974398CRL-961961-LAND VEHICLE FUELING FACILITY, MOGASSERVICE STATIONDS-Emergency Shutoff Valves (Shear Valves)CRL-961-ESHVL-176231CRL00077MOGAS Dispensers 1 and 2EBWXSection 7-12Key Required; OPERATE SYSTEM TO TEST
974398CRL-961961-LAND VEHICLE FUELING FACILITY, MOGASSERVICE STATIONDS-Hose RetrieverCRL-961-HSRTV-169724CRL00078MOGAS Dispenser 1XSection 7-6
974398CRL-961961-LAND VEHICLE FUELING FACILITY, MOGASSERVICE STATIONDS-Hose RetrieverCRL-961-HSRTV-169867CRL00079MOGAS Dispenser 2XSection 7-6
974398CRL-961961-LAND VEHICLE FUELING FACILITY, MOGASSERVICE STATIONDS-SwivelsCRL-961-DSSW-169869CRL00080MOGAS Dispenser 1OPWXSection 7-5
974398CRL-961961-LAND VEHICLE FUELING FACILITY, MOGASSERVICE STATIONDS-SwivelsCRL-961-DSSW-169711CRL00081MOGAS Dispenser 2XSection 7-5
974398CRL-961961-LAND VEHICLE FUELING FACILITY, MOGASSERVICE STATIONDS-BreakawaysCRL-961-DSBW-168095CRL00082MOGAS Dispenser 3XSection 7-4
974398CRL-961961-LAND VEHICLE FUELING FACILITY, MOGASSERVICE STATIONDS-BreakawaysCRL-961-DSBW-168096CRL00083MOGAS Dispenser 4XSection 7-4
974398CRL-961961-LAND VEHICLE FUELING FACILITY, MOGASSERVICE STATIONDS-Dispenser FiltersCRL-961-DSFLR-165638CRL00084MOGAS Dispenser 3Cim-Tek FiltrationXSection 7-9Key Required
974398CRL-961961-LAND VEHICLE FUELING FACILITY, MOGASSERVICE STATIONDS-Dispenser FiltersCRL-961-DSFLR-165639CRL00085MOGAS Dispenser 4Cim-Tek FiltrationXSection 7-9Key Required
974398CRL-961961-LAND VEHICLE FUELING FACILITY, MOGASSERVICE STATIONDS-Dispenser HosesCRL-961-DSHS-169839CRL00086MOGAS Dispenser 3 Short HoseXSection 7-3
974398CRL-961961-LAND VEHICLE FUELING FACILITY, MOGASSERVICE STATIONDS-Dispenser HosesCRL-961-DSHS-169841CRL00087MOGAS Dispenser 3 Long HoseParkerXSection 7-3
974398CRL-961961-LAND VEHICLE FUELING FACILITY, MOGASSERVICE STATIONDS-Dispenser HosesCRL-961-DSHS-169843CRL00088MOGAS Dispenser 4 Short HoseXSection 7-3
974398CRL-961961-LAND VEHICLE FUELING FACILITY, MOGASSERVICE STATIONDS-Dispenser HosesCRL-961-DSHS-176232CRL00089MOGAS Dispenser 4 Long HoseParkerXSection 7-3
974398CRL-961961-LAND VEHICLE FUELING FACILITY, MOGASSERVICE STATIONDS-Dispenser MetersCRL-961-DSMTR-165801CRL00090MOGAS Dispenser 3Gilbarco Veeder-RootT20150XSection 7-8Key Required; OPERATE SYSTEM TO TEST
974398CRL-961961-LAND VEHICLE FUELING FACILITY, MOGASSERVICE STATIONDS-Dispenser MetersCRL-961-DSMTR-165802CRL00091MOGAS Dispenser 4Gilbarco Veeder-RootT20150XSection 7-8Key Required; OPERATE SYSTEM TO TEST
974398CRL-961961-LAND VEHICLE FUELING FACILITY, MOGASSERVICE STATIONDS-Dispenser NozzlesCRL-961-DSNZ-165819CRL00092MOGAS Dispenser 3OPWXSection 7-2Operate System to Test
974398CRL-961961-LAND VEHICLE FUELING FACILITY, MOGASSERVICE STATIONDS-Dispenser NozzlesCRL-961-DSNZ-165820CRL00093MOGAS Dispenser 4OPWXSection 7-2Operate System to Test
974398CRL-961961-LAND VEHICLE FUELING FACILITY, MOGASSERVICE STATIONDS-Dispenser SumpsCRL-961-DSSMP-169846CRL00094MOGAS Dispensers 3 and 4XSection 7-13Key Required
974398CRL-961961-LAND VEHICLE FUELING FACILITY, MOGASSERVICE STATIONDS-Emergency Shutoff Valves (Shear Valves)CRL-961-ESHVL-169712CRL00095MOGAS dispensers 3 and 4Emco WheatonXSection 7-12Key Required; OPERATE SYSTEM TO TEST
974398CRL-961961-LAND VEHICLE FUELING FACILITY, MOGASSERVICE STATIONDS-Hose RetrieverCRL-961-HSRTV-169725CRL00096MOGAS Dispenser 3XSection 7-6
974398CRL-961961-LAND VEHICLE FUELING FACILITY, MOGASSERVICE STATIONDS-Hose RetrieverCRL-961-HSRTV-169726CRL00097MOGAS Dispenser 4XSection 7-6
974398CRL-961961-LAND VEHICLE FUELING FACILITY, MOGASSERVICE STATIONDS-SwivelsCRL-961-DSSW-169848CRL00098MOGAS Dispenser 3CATLOWXSection 7-5
974398CRL-961961-LAND VEHICLE FUELING FACILITY, MOGASSERVICE STATIONDS-SwivelsCRL-961-DSSW-176233CRL00099MOGAS Dispenser 4CATLOWXSection 7-5
974112CRL-962962-DIESEL STORAGE TANK AGSERVICE STATIONMV-Ball ValvesCRL-962-BLVL-169727CRL00100Located on top of the diesel tankJomar ValveXSection 6-6.2.4Notify Facility
974112CRL-962962-DIESEL STORAGE TANK AGSERVICE STATIONCS-Dike/Berm with Walls and FloorsCRL-962-DKBW-167870CRL00101Containment for diesel tanks S962 and S930XSection 8-10.2 / 8-10.2.1
974112CRL-962962-DIESEL STORAGE TANK AGSERVICE STATIONCS-Containment Drain ValvesCRL-962-CSGEN-167769CRL00102Drain valve for containment systemNamsung ValveXSection 8-10.1Key Required
974112CRL-962962-DIESEL STORAGE TANK AGSERVICE STATIONEC-Static Grounding SystemsCRL-962-STGS-169850CRL00103Tank grounding cablesXSection 9-1.6.2
974112CRL-962962-DIESEL STORAGE TANK AGSERVICE STATIONGF-Ground Vehicle Fuel PipingCRL-962-GVFP-169728CRL00104Diesel issue piping 2 inch aboveground and below ground from tank S-962 to Diesel dispensers 5,6,7 and 8.XXSection 7-11Coordinate with Facility
974112CRL-962962-DIESEL STORAGE TANK AGSERVICE STATIONTA-Emergency VentsCRL-962-EMGVT-167459CRL00105Emergency vent primary located on top of the diesel tankClay and BaileyXSection 8-9.4
974112CRL-962962-DIESEL STORAGE TANK AGSERVICE STATIONTA-Emergency VentsCRL-962-EMGVT-167460CRL00106Emergency vent annular located on top of the diesel tankClay and BaileyXSection 8-9.4
974112CRL-962962-DIESEL STORAGE TANK AGSERVICE STATIONEQ-Real PropertyCRL-962-ASSET-169729CRL00107Anti syphon valve located on top of the diesel tank S-962OPWNon-Appx G Class
974112CRL-962962-DIESEL STORAGE TANK AGSERVICE STATIONTK-Aboveground Shop-Fabricated TanksS-962CRL-962-AGSFP-169730CRL00108Diesel tankContainment Solutions, InLDP10000XXSection 8-5.1
974112CRL-962962-DIESEL STORAGE TANK AGSERVICE STATIONEQ-Air VentCRL-962-ASSET-176234CRL00109Vent located on top of the diesel tankNon-Appx G Class
974112CRL-962962-DIESEL STORAGE TANK AGSERVICE STATIONTA-Mechanical Tape Gauges (non-ATG)CRL-962-MTGA-169852CRL00110Tank gauge located on top of the diesel tankMorrison Bros. Co.XSection 8-9.7
974399CRL-963963-MOGAS STORAGE TANK AGSERVICE STATIONTA-Mechanical Tape Gauges (non-ATG)CRL-963-MTGA-169855CRL00112Tank gauge located on top of the MOGAS tankMorrison Bros. Co.XSection 8-9.7
974399CRL-963963-MOGAS STORAGE TANK AGSERVICE STATIONMV-Ball ValvesCRL-963-BLVL-169905CRL00113Located on top of the MOGAS tankJomar ValveXSection 6-6.2.4Notify Facility
974399CRL-963963-MOGAS STORAGE TANK AGSERVICE STATIONCS-Dike/Berm with Walls and FloorsCRL-963-DKBW-167871CRL00114Containment for MOGAS tank S963XSection 8-10.2 / 8-10.2.1
974399CRL-963963-MOGAS STORAGE TANK AGSERVICE STATIONCS-Containment Drain ValvesCRL-963-CSGEN-167770CRL00115Drain valve for containment systemNamsung ValveXSection 8-10.1Key Required
974399CRL-963963-MOGAS STORAGE TANK AGSERVICE STATIONEC-Static Grounding SystemsCRL-963-STGS-169713CRL00116Tank grounding cablesXSection 9-1.6.2
974399CRL-963963-MOGAS STORAGE TANK AGSERVICE STATIONGF-Ground Vehicle Fuel PipingCRL-963-GVFP-169909CRL00117MOGAS issue piping 2 inch aboveground and below ground from tank S-963 to MOGAS dispensers 1,2,3, and 4.XXSection 7-11Coordinate with Facility
974399CRL-963963-MOGAS STORAGE TANK AGSERVICE STATIONTA-Emergency VentsCRL-963-EMGVT-167461CRL00118Emergency vent primary located on top of the MOGAS tankClay and BaileyXSection 8-9.4
974399CRL-963963-MOGAS STORAGE TANK AGSERVICE STATIONTA-Emergency VentsCRL-963-EMGVT-167462CRL00119Emergency vent annular located on top of the MOGAS tankClay and BaileyXSection 8-9.4
974399CRL-963963-MOGAS STORAGE TANK AGSERVICE STATIONEQ-Real PropertyCRL-963-ASSET-153833CRL00120Anti syphon valve located on top of the MOGAS tank S-963OPWNon-Appx G Class
974399CRL-963963-MOGAS STORAGE TANK AGSERVICE STATIONTK-Aboveground Shop-Fabricated TanksS-963CRL-963-AGSFP-169912CRL00121MOGAS tankContainment Solutions, InLDP10000XXSection 8-5.1
974399CRL-963963-MOGAS STORAGE TANK AGSERVICE STATIONTA-Tank Pressure/Vacuum VentsCRL-963-TPVVT-169731CRL00122Pressure vent located on top of the diesel tankXSection 8-9.3Notify Facility
974399CRL-963963-MOGAS STORAGE TANK AGSERVICE STATIONGF-Remote Dispenser PumpsCRL-963-RDSP-169732CRL00123Red jacket pump located on top of the MOGAS tankFE PetroXXXSection 7-15.1Operate System to Test
974111CRL-960960-LAND VEHICLE FUELING FACILITY, DIESEL/JP8SERVICE STATIONGF-Transition SumpsCRL-960-TRSMP-169765CRL2207201025Transition sump located on the dispenser island for diesel dispensers 5 & 6 and 7 & 8Franklin Fueling SystemsXSection 7-14Notify Facility
974398CRL-961961-LAND VEHICLE FUELING FACILITY, MOGASSERVICE STATIONGF-Transition SumpsCRL-961-TRSMP-176241CRL2207201026Transition sump located on the dispenser island for MOGAS dispensers 1 & 2 and 3 & 4Franklin Fueling SystemsXSection 7-14Notify Facility
974399CRL-963963-MOGAS STORAGE TANK AGSERVICE STATIONGF-Transition SumpsCRL-963-TRSMP-169900CRL2207201027Transition sump for MOGAS tank S-963Franklin Fueling SystemsXSection 7-14Notify Facility
974112CRL-962962-DIESEL STORAGE TANK AGSERVICE STATIONGF-Transition SumpsCRL-962-TRSMP-169902CRL2207201028Transition sump for diesel tanks S-963 and S-930Franklin Fueling SystemsXSection 7-14Notify Facility
974400CRL-929929-FUEL/POL BLDGSERVICE STATIONEC-LightingCRL-929-LIGHT-169904CRL2207201029Dispenser canopy lighting. 24 lights at heights and two manual switches inside facility S-929. No photocellsXXSection 9-1.8At Height-Manlift Required
974400CRL-929929-FUEL/POL BLDGSERVICE STATIONEC-PanelboardsLACRL-929-PNB-176242CRL2207201030Panelboard LA located inside facility S-929XSection 9-1.5Notify Facility
974400CRL-929929-FUEL/POL BLDGSERVICE STATIONEC-Static Grounding SystemsCRL-929-STGS-176243CRL2207201031Static grounding system for the dispenser canopyXSection 9-1.6.2
974400CRL-929929-FUEL/POL BLDGSERVICE STATIONEC-LightingCRL-929-LIGHT-176244CRL2207201032Outside lighting for facility S-929. One on the backside of the building. Photocell only. One over the entrance door. Manual switch only.XXSection 9-1.8At Height-Ladder Required
974400CRL-929929-FUEL/POL BLDGSERVICE STATIONCS-Containment Drain ValvesCRL-929-CSGEN-167772CRL2207201033Containment drain valve for the dispenser containment areaXSection 8-10.1Key Required
974586CRL-964964-TK TRK LD/UNLD MOGASSERVICE STATION/ TRUCK UNLOADTV-Thermal and Pressure Relief ValvesCRL-964-TPRVL-16898916474CRLLocated on the 1 inch piping for MOGASTaylor ValveXXSection 6-6.3Coordinate with FacilitySet pressure 100 psig
974586CRL-964964-TK TRK LD/UNLD MOGASSERVICE STATION/ TRUCK UNLOADTV-Thermal and Pressure Relief ValvesCRL-964-TPRVL-17595816475CRLLocated on the 1 inch piping for dieselTaylor ValveT-8200-1XXSection 6-6.3Coordinate with FacilitySet pressure 100 psig
974586CRL-964964-TK TRK LD/UNLD MOGASSERVICE STATION/ TRUCK UNLOADMV-Ball ValvesCRL-964-BLVL-176235CRL00125Located on the 2 inch receipt line for diesel tank S-930 (pump bypass)Jomar ValveXSection 6-6.2.4Notify Facility
974586CRL-964964-TK TRK LD/UNLD MOGASSERVICE STATION/ TRUCK UNLOADMV-Ball ValvesCRL-964-BLVL-169914CRL00126Located on the 2 inch receipt line for diesel tank S-962 (pump bypass)Jomar ValveXSection 6-6.2.4Notify Facility
974586CRL-964964-TK TRK LD/UNLD MOGASSERVICE STATION/ TRUCK UNLOADMV-Ball ValvesCRL-964-BLVL-176236CRL00127Located on the 2 inch receipt piping for diesel pump inletJomar ValveXSection 6-6.2.4Notify Facility
974586CRL-964964-TK TRK LD/UNLD MOGASSERVICE STATION/ TRUCK UNLOADMV-Ball ValvesCRL-964-BLVL-169733CRL00128Located inside diesel offload cabinetHammond Valve8500 SeriesXSection 6-6.2.4Notify Facility
974586CRL-964964-TK TRK LD/UNLD MOGASSERVICE STATION/ TRUCK UNLOADMV-Ball ValvesCRL-964-BLVL-176237CRL00129Isolation valve for diesel PRV (upstream)Flow-TekXSection 6-6.2.4Notify Facility
974586CRL-964964-TK TRK LD/UNLD MOGASSERVICE STATION/ TRUCK UNLOADMV-Ball ValvesCRL-964-BLVL-169916CRL00130Isolation valve for diesel PRV (downstream)Flow-TekXSection 6-6.2.4Notify Facility
974586CRL-964964-TK TRK LD/UNLD MOGASSERVICE STATION/ TRUCK UNLOADMV-Ball ValvesCRL-964-BLVL-169714CRL00131Located on the 2 inch receipt line for MOGAS tank S-963 (pump bypass)Jomar ValveXSection 6-6.2.4Notify Facility
974586CRL-964964-TK TRK LD/UNLD MOGASSERVICE STATION/ TRUCK UNLOADMV-Ball ValvesCRL-964-BLVL-169918CRL00132Located on the 2 inch receipt piping for MOGAS pump inletJomar ValveXSection 6-6.2.4Notify Facility
974586CRL-964964-TK TRK LD/UNLD MOGASSERVICE STATION/ TRUCK UNLOADMV-Ball ValvesCRL-964-BLVL-169920CRL00133Isolation valve for MOGAS PRV (upstream)Flow-TekXSection 6-6.2.4Notify Facility
974586CRL-964964-TK TRK LD/UNLD MOGASSERVICE STATION/ TRUCK UNLOADMV-Ball ValvesCRL-964-BLVL-169734CRL00134Isolation valve for MOGAS PRV (downstream)Flow-TekXSection 6-6.2.4Notify Facility
974586CRL-964964-TK TRK LD/UNLD MOGASSERVICE STATION/ TRUCK UNLOADMV-Ball ValvesCRL-964-BLVL-169735CRL00135Located inside MOGAS offload cabinetHammond Valve8500 SeriesXSection 6-6.2.4Notify Facility
974586CRL-964964-TK TRK LD/UNLD MOGASSERVICE STATION/ TRUCK UNLOADSF-Fuel Truck Containment AreasCRL-964-FTKRCC-169715CRL00136Containment for truck offloadXXSection 11-1.1
974586CRL-964964-TK TRK LD/UNLD MOGASSERVICE STATION/ TRUCK UNLOADEC-Ground Reels - Static Grounding SystemsCRL-964-STGS-169785CRL00137Located next to the MOGAS offloading pumpHannay ReelsGR7XXSection 9-1.6.2
974586CRL-964964-TK TRK LD/UNLD MOGASSERVICE STATION/ TRUCK UNLOADEC-Static Grounding SystemsCRL-964-STGS-169897CRL00138Grounding for diesel and MOGAS offload pumpsXSection 9-1.6.2
974586CRL-964964-TK TRK LD/UNLD MOGASSERVICE STATION/ TRUCK UNLOADPC-Aboveground Piping and Equipment CoatingCRL-964-AGPCT-169786CRL001392 inch diesel receipt pipingSection 6-10.1
974586CRL-964964-TK TRK LD/UNLD MOGASSERVICE STATION/ TRUCK UNLOADPC-Aboveground Piping and Equipment CoatingCRL-964-AGPCT-169787CRL001402 inch MOGAS receipt pipingSection 6-10.1
974586CRL-964964-TK TRK LD/UNLD MOGASSERVICE STATION/ TRUCK UNLOADPM-Centrifugal PumpsCRL-964-CENP-169898CRL00143Diesel offloading pumpXXXSection 3-8.1Operate System to Test
974586CRL-964964-TK TRK LD/UNLD MOGASSERVICE STATION/ TRUCK UNLOADPM-Centrifugal PumpsCRL-964-CENP-169788CRL00144MOGAS offloading pumpXXXSection 3-8.1Operate System to Test
974586CRL-964964-TK TRK LD/UNLD MOGASSERVICE STATION/ TRUCK UNLOADEQ-Real PropertyCRL-964-ASSET-153834CRL00145Y strainer located on the 2 inch diesel receipt piping for tank S-930Morrison Bros. Co.Non-Appx G Class
974586CRL-964964-TK TRK LD/UNLD MOGASSERVICE STATION/ TRUCK UNLOADEQ-Real PropertyCRL-964-ASSET-153835CRL00146Y strainer located on the 2 inch diesel receipt piping for tank S-962Morrison Bros. Co.Non-Appx G Class
974586CRL-964964-TK TRK LD/UNLD MOGASSERVICE STATION/ TRUCK UNLOADEQ-Real PropertyCRL-964-ASSET-153836CRL00147Y strainer located on the 2 inch MOGAS receipt piping for tank S-963Morrison Bros. Co.Non-Appx G Class
974586CRL-964964-TK TRK LD/UNLD MOGASSERVICE STATION/ TRUCK UNLOADMV-Check ValvesCRL-964-CKVL-169789CRL00148Check valve located on the 2 inch diesel receipt line for tank S-930Snap-titeXSection 6-6.2.8Notify Facility
974586CRL-964964-TK TRK LD/UNLD MOGASSERVICE STATION/ TRUCK UNLOADMV-Check ValvesCRL-964-CKVL-176238CRL00149Check valve located on the 2 inch diesel receipt line for tank S-962Snap-titeXSection 6-6.2.8Notify Facility
974586CRL-964964-TK TRK LD/UNLD MOGASSERVICE STATION/ TRUCK UNLOADMV-Check ValvesCRL-964-CKVL-176239CRL00150Check valve located on the 2 inch MOGAS receipt line for tank S-963Snap-titeXSection 6-6.2.8Notify Facility
974586CRL-964964-TK TRK LD/UNLD MOGASSERVICE STATION/ TRUCK UNLOADEQ-Real PropertyCRL-964-ASSET-153837CRL00151Pump controls for diesel offloadPhillips Pump LLCP/N: ISP-2G/2Non-Appx G Class
974586CRL-964964-TK TRK LD/UNLD MOGASSERVICE STATION/ TRUCK UNLOADEQ-Real PropertyCRL-964-ASSET-153838CRL00152Pump controls for MOGAS offloadPhillips Pump LLCP/N: ISP-2GNon-Appx G Class
974586CRL-964964-TK TRK LD/UNLD MOGASSERVICE STATION/ TRUCK UNLOADGF-Gov SS EFSO SystemsCRL-964-EFSO-176240CRL00153EFSO located next to the truck offloadXSection 7-16Operate System to Test
974586CRL-964964-TK TRK LD/UNLD MOGASSERVICE STATION/ TRUCK UNLOADCS-Containment Drain ValvesCRL-964-CSGEN-167771CRL2207200700Containment drain valve located under the grating at the truck offloading areaXSection 8-10.1Key Required

Pacific Ocean Division, POD-AF

W912DY-21-F-0076&"-,Bold"&16Camp Carroll
CRLFacility Maintenance Plan

OY3 Q1

&A &P of &N APTIM Federal Services, LLC

Instructions:

1. Input all data as indicated on the sheet.

2. Additional documents referred to in the Special Considerations column shall be included as an appendix to this FMP.

3. The contractor shall generate a Component Unique Identifier (CUID) for each component utilizing the Component Acronym Sheet within this Work Book. The unique identifier must use the following:

Three letter Site Code - Facility # - Component Acronym - Sequential number Example: AAD-00063A-RCVL-0001

If component acronym is not listed, the contractor shall request an acronym be established through the HNC Project Manager and Project Engineer via email. Contractors may utilize other means of tracking/labeling assets such as QR codes in addition to the required CUID however, tracking/labeling must correlate with the CUID. This CUID shall be the standard for all DLA capitalized equipment. Base Asset ID if used by site shall be cross referenced with CUID appropriately.

4. Utilize the UFC Section Reference Work Category as noted on the Component Acronym Sheet.

5. Enter any applicable manufacturer requirements not stated in the UFC. References are acceptable with attachments.

6. Enter any applicable operator support or government owned equipment required to complete the RM task.

7. Enter impact on system availability by performing the RM task. This could include shutdown, lockout, or similar impacts.

8. Enter contract information for any other contract, contractor, or government personnel performing the applicable task. This is applicable to other Centrally Managed Programs, SRM, MILCON, or Public Works/Civil Engineering projects.

9. Print Hard Copies as 11x17.

Component Acronyms

Component Unique Identifier:Site Code-Facility #-Component Acronym-Sequential #
Example:AAD-00063A-RCVL-0001
NOTE: If component acronym is not listed, the contractor shall request an acronym be established through the HNC Project Manager and Project Engineer via email. Contractors may utilize other means of tracking/labeling assets such as QR codes in addition to the required CUID however, tracking/labeling must correlate with the CUID. This CUID shall be the standard for all DLA capitalized equipment
DLA Work Type CategoryUFC Section Reference Work Category
(Revised per Change 1, 29 April 2021)Component Acronym
Air CompressorsAir CompressorsAIRC
AlarmsExternally Mounted Level Alarms (Section 8-9.9.1)EMLA
Internally Mounted Level Alarms (Section 8-9.9.3)IMLA
BollardBollardsBLRD
BuildingBuilding HVACBHVAC
Building Domestic Water SystemBWTR
Building Waste WaterBWSW
Building - LightingBLTG
Building - ArchitecturalBARCH
Building - Fire Sprinkler SystemBFIRE
Containment/JointsContainment Systems (General) (Section 8-10.1)CSGEN
Concrete and Cement Brick Dike/Berm Walls (Section 8-10.2.1)DKBW
Dike/Berm Floors (Section 8-10.2.2)DKBF
Earthen Dike Walls (Section 8-10.3)ETHDW
Self-Diking or Vaulted Tank Containment (Section 8-10.4)SDVTCS
Flexible Membrane Liners (Section 8-10.5)FXML
Fuel Truck and Rail Car Containment Areas (Section 11-1.1)FTKRCC
Remote Spill Containment (Section 11-1.2)RSCS
Piers and Wharves Fuel Containment Systems (Section 5-1.2) - TestingFPWCT
Fuel Pier/Wharf Containment (PWS Section 3)FPWC
Corrosion Control/CoatingsAboveground Piping and Equipment Coatings (Section 6-10.1)AGPCT
MiscellaneousMiscellaneous Deactivated Components (Section 12-5)MDEAC
Electrical/LightingLighting (Section 9-1.8)LIGHT
Electrical/PowerElectrical Equipment (Section 9-1.2)ELEQ
Power Cables (Section 9-1.3)PWRCBL
Motor Controls (Section 9-1.4)MTRCT
Panelboards (Section 9-1.5)PNLB
Electric Motors (Section 9-1.7)ELEMT
Electronic Equipment (9-1.9)ELTREQ
Card and Key Locks (Section 9-3)CKLK
Electrical/ProtectionPower Grounding Systems (Section 9-1.6.1)PWRGS
Static Grounding Systems (Section 9-1.6.2)STGS
Cathodic Protection (Section 9-2.1)CP
Lightning Surge Arresters (Section 9-2.2.1)LSAR
Lightning Protection Systems (Section 9-4)LPTS
Ground Verification System (Section 9-5)GRVS
Electronic Overfill Protection Systems (Section 9-6)EOPS
Eyewash/ShowerEmergency Eyewash/Showers (Section 11-3)EMEWSH
Fencing/
GatesFencingFENC
GatesGATE
FiltrationPre-Filters (Section 3-6.1)PFVSL
Filter Separators (Section 3-6.2)FLSP
Haypack Filters (Section 3-6.3)HPKF
Basket Strainers (Section 3-6.4)BSTR
Filter Separator Sump Heaters (Section 3-6.5)FSSH
Sidestream Filtration Systems (Section 8-9.11)SSFTS
Fire Suppression EquipmentFlame Arrestors (Section 8-9.5)FLMARR
Foam Fire Protection Systems (Section 8-9.15)FFPS
Fire Protection Systems - Wet PipeFPRS
Fuel LaboratoriesVentilation Hoods (Section 11-4.1)VENTHD
GaugesPressure and Pressure/Vacuum Gauges (Section 6-7.1)PVGA
Differential Pressure Gauges (Section 6-7.2)DPGA
Mechanical Tape Gauges (Section 8-9.7)MTGA
Mechanically Operated Tape Gauge (Section 8-9.8.1)MOTGA
Magnetostrictive Probes (Section 8-9.8.2)MRPRB
Servo Gauge (Section 8-9.8.3)SRVGA
GeneratorsBack-Up Power GeneratorsBGEN
Heating CoilsSteam Type Heating Coils (Section 8-9.16.1)STHC
Thermal Fluid Type Heating Coils (Section 8-9.16.2)TFTHC
Electric Rod Type Heating (Section 8-9.16.3)ERTH
HosesLoading Fuel Hoses (Section 3-9.1)LDHS
Offloading Fuel Hoses (Section 3-9.2)OLHS
Aircraft Fueling Hoses (Section 4-7.5)ACFHS
HydrazineHydrazine Charging Units (Section 10-3)HDZCU
InspectionsTrouble ShootTRBST
API 510 InspectionsAPI510
API 653 or STI InspectionAPI653
Coatings Condition SurveyCCS
Issue/Receive - GroundDispenser Nozzles (Section 7-2)DSNZ
Dispenser Hoses (Section 7-3)DSHS
Breakaways (Section 7-4)DSBW
Swivels (Section 7-5)DSSW
Hose Retriever (Section 7-6)HSRTV
Dispenser Cabinet (Section 7-7)DSCB
Dispenser Meters (Section 7-8)DSMTR
Dispenser Filters (Section 7-9)DSFLR
Dispenser Strainers (Section 7-10)DSSTR
Ground Vehicle Fuel Piping (Section 7-11)GVFP
Emergency Shutoff Valves (Shear Valves) (Section 7-12)ESHVL
Dispenser Sumps (Section 7-13)DSSMP
Transition Sumps (Section 7-14)TRSMP
Remote Dispenser Pumps (Section 7-15.1)RDSP
Self-Contained Dispenser Pumps (Section 7-15.2)SCDSP
EFSO Systems (Section 7-16)EFSO
Stage I Vapor Recovery (Section 7-17.1)SIVP
Stage II Vapor Recovery (Section 7-17.2)SIIVP
Vapor Burners (Section 7-17.3)VPBNR
Point Sensor - Dry (Section 7-19.1.1)PSDRY
Automatic Line Leak Detector (Section 7-19.1.2)ALLD
Visual Monitoring (Section 7-20.1)VSLM
Issue/Receive - MarineMarine Receipt (Section 5-2)MRNRCP
Marine Issue (Section 5-3)MRNISU
Marine Loading Arms (Section 5-4)MRNLA
Marine Transfer Hoses (Section 5-5.1)MBTHS
Underwater Hoses (Section 5-5.2)UWHS
Single Point Mooring Systems (Section 5-7.1)SPMSS
Multi Point Mooring Systems (Section 5-7.2)MPMSS
Submerged Piping Systems (Section 5-8)SMPS
Boom Reels (Section 5-9)BMRL
Liquefied PetroleumLiquefied Petroleum Tanks (Section 10-1.1)LPTANK
Liquefied Petroleum Pipelines (Section 10-1.2)LPPIPE
Liquefied Petroleum Vapor Lines (Section 10-1.3)LPVPL
LPG Vaporizers (Section 10-1.4)LPGVPZ
Petroleum Gas Regulators (Section 10-1.5)PGREG
Liquefied Petroleum Gas Hoses (Section 10-1.6)LPGHS
Meter/
calibrationsPositive Displacement Meters (Section 3-7.1)PDMT
Turbine Flow Meters (Section 3-7.2)TBFMT
Orifice Flow Meters (Section 3-7.3)OFMT
Natural DisasterNatural Disaster
Natural GasCNG Piping (Section 10-2.1)NGPIPE
CNG Compressors (Section 10-2.2)NGCOMP
CNG Storage (Section 10-2.3)NGSTOR
CNG Dispensers (Section 10-2.4)NGDS
CNG Dispenser Hoses (Section 10-2.5)NGDSHS
NozzleHydrant Adapters (Section 4-7.2)HADP
Fueling Nozzles (Section 4-7.3)FLNZ
OtherFuel Additive Injectors (Section 3-11)FAIJ
PantographFixed Pantographs (Section 4-7.1.1)FXPNT
Detachable Pantographs (Section 4-7.1.2)DTPNT
PipingOn-Base Pipelines (Section 6-1.1)OBPL
Non-DOT Regulated (Section 6-1.2.1)NDPL
Aboveground Piping (Section 6-1.3)AGPL
Double-Wall Piping (Section 6-1.4)DWPL
Low Point Drains (Section 6-12.1)LPDN
High Point Vents (Section 6-12.2)HPVT
Sight Flow Indicators (Section 6-12.3)SFND
Rope Sensor Systems (Section 6-13.1.1)RPSS
Point Sensor - Dry (Section 6-13.1.2)PSDRY
Visual Monitoring (Section 6-14.1)VSLM
Pipe Penetrations (Section 8-10.6)PPEN
Deactivated Petroleum Fuel Pipelines (Section 12-3)DEACPL
Pressure/Temperature ControlAir Eliminator Tanks (Section 3-10.1)AELT
Automatic Air Vents (Section 3-10.2)AAVT
Surge Suppressors (Section 4-7.4)SRGSP
Thermal and Pressure Relief Valves (Section 6-6.3)TPRVL
Pressure Transmitters (Section 6-7.3)PRTR
Differential Pressure Transmitters (Section 6-7.4)DPTR
Flexible Ball Joints (Section 6-8)FBLJT
Dial Thermometer (Section 6-9.1)DTHMR
Emergency Vents (Section 8-9.4)EMGVT
PumpCentrifugal Pumps (Section 3-8.1)CENP
Vertical Inline Pumps (Section 3-8.2)VILP
Vertical Turbine/Submerged Turbine Pumps (Section 3-8.3)VTSP
Sliding Vane Pumps (Section 3-8.5)SLVP
Gear Pumps (Section 3-8.6)GERP
Diaphragm Pumps (Section 3-8.7)DIAP
Internal Combustion Drives (Section 3-8.8)ICDR
Gearboxes (Section 3-8.9)GRBX
Deactivated Petroleum Fuel Pumps (Section 12-4)DEACP
Signage/MarkingsSignage and Markings (Section 2-7)SIGN
StructuresPumphouse/Filter Buildings (Section 11-2.1)PFBLDG
Canopies (Section 11-2.2)CNPY
Cranes and Hoists (Section 11-6)CRNHST
TankAboveground Field-Erected Tanks (Section 8-4)AGFET
Geodesic Dome Roofs (Section 8-4.2)GEODR
Foundations (Section 8-4.3)FOUND
Aboveground Shop Fabricated Tanks (Section 8-5.1)AGSFP
Self-Diking or Vaulted Tanks (Section 8-5.2)SDVT
Rectangular Concrete-Encased Tanks (Section 8-5.3)RCET
Single-Walled Underground Shop-Fabricated Tanks (Section 8-5.4.1)UGSSFT
Double-Walled Underground Shop-Fabricated Tanks (Section 8-5.4.2)UGDSFT
Underground Field-Constructed Tanks (Cut and Cover Tanks) (Section 8-6)UGFET
Tank Cleaning (Section 8-7)TCLEAN
Aluminum Honeycomb Floating Pans (Section 8-9.1.1)AHFP
Steel Floating Pans (Section 8-9.1.2)STLFP
Pontoon Floating Pans (Section 8-9.1.3)PTNFP
Floating Roofs (Section 8-9.1.4)FLTRF
Floating Roof and Pan Pressure/Vacuum Vents (Section 8-9.1.5)FPPVV
Floating Roof and Pan Legs (Section 8-9.1.6)FRPLG
Secondary Tank Bottoms (Section 8-9.2)SNDTB
Tank Pressure/Vacuum Vents (Section 8-9.3)TPVVT
Product Saver Tanks (Section 8-9.10)PRDST
Fill Ports (Section 8-9.12)FPRT
Point Sensor - Dry (Section 8-9.13.1)PSDRY
Point Sensor - Wet (Section 8-9.13.2)PSWET
Point Sensor - Pressure/Vacuum (Section 8-9.13.3)PSPV
Visual Leak Detection (Section 8-9.13.4)VSLLD
Floating Suction Lines (Section 8-9.14)FLTSL
Stilling Wells (Section 8-9.17)STGW
Deactivated Petroleum Fuel Tanks (Section 12-2)DEACT
TestingPressure Testing
Underground PitsIsolation Valve Pits (Section 6-11.1)ISVLP
Hydrant Fuel Pits (Section 6-11.2)HDFP
High Point Vent Pits (Section 6-11.3)HPVP
Low Point Drain Pits (Section 6-11.4)LPDP
Lateral Control Pits (Section 6-11.5)LTCP
ValvesGeneral System Control Valves (Section 4-3.2.1)GSCVL
Refuel Control Valves (Section 4-3.2.5)RCVL
Pressure Relief Valves (Section 4-3.2.6)PRCVL
Defuel Control Valve (Section 4-3.2.7)DFCVL
Dual Rate-of-Flow Control Valves (Section 4-3.2.8)DRFCVL
Combination Dual Rate-of-Flow Control and Solenoid Valves (Section 4-3.3.1)CFSCVL
Dual Pressure Relief, Solenoid Shutoff, and Check Valves (Section 4-3.3.2)DPSCVL
Non-Surge Check Valves (Section 4-4.2.1)NSCKVL
Filter Separator Control Valves (Section 4-4.2.2)FSCVL
Defuel/Flush Valves (Section 4-4.2.3)DFFCVL
Issue Venturi (Section 4-4.2.4)ISVTR
Return Venturi (Section 4-4.2.5)RTVTR
Back Pressure Control Valves (Section 4-4.2.6)BPCVL
Pressure Control Valves (Section 4-4.2.7)PCVL

This is the start of the file's text. The full file is on GovTribe.