This is a Fire Protection System specification document for the Volusia County Tax Collector's office renovation project located at 123 W. Indiana Avenue in DeLand, Florida. The document establishes comprehensive technical requirements for the design, installation, inspection, and testing of a wet pipe automatic sprinkler fire protection system serving approximately 6,766 square feet of renovated interior space. The fire protection contractor must comply with all applicable state and local codes, obtain necessary permits and government approvals, and coordinate the system installation with existing conditions and other trades. The system design follows NFPA 13 (2019 Edition) and the 2023 Florida Fire Prevention Code with local amendments. Key deliverables include preparing detailed shop drawings, conducting field verification of architectural and structural conditions, installing UL-listed and FM-approved components, performing hydrostatic testing at 200 PSI minimum for two hours, and obtaining final inspection and acceptance from the local fire department, building department, and project architect/engineer. The project incorporates both upright and pendent sprinkler head types with specific temperature ratings of 155 degrees Fahrenheit and 5.6 K-factor, with precise placement requirements relative to ceiling tiles, structural members, and other building systems.

The specification requires the fire sprinkler contractor to provide product data sheets, coordinate sprinkler placement with HVAC diffusers, electrical lighting, ceiling systems, and structural elements, and install all piping absolutely rust-free with proper hangers sized according to pipe diameter. All grooved fittings must be Victaulic brand or approved equal, with screwed piping in Schedule 40 black steel pipe per ASTM A120 specifications. The building has an existing water supply from the public water main with existing backflow prevention and metering; a fire pump and water storage tank are not required. The system includes tamper switches and flow switches connected to the building fire alarm panel, with flow switches set to alarm when a single sprinkler head operates. All materials and components must be rated for maximum system working pressure and must be either UL-listed or Factory Mutual-approved for automatic sprinkler system use. The project funding is through Volusia County appropriations with potential tax savings through the Consumer's Certificate of Exemption for direct material purchases without sales tax.

View the file

Other files

File Type Posted
Tax_Collector_Interior_Renovations_and_Restoration_(Addendum_#3_Revision).pdf PDF
M1.101_-_FIRST_LEVEL_PLAN_AND_SCHEDULES_MECHANICAL.pdf PDF
E1.102_-_FIRST_LEVEL_PLAN_LIGHTING.pdf PDF
E1.101_-_FIRST_LEVEL_PLAN_POWER.pdf PDF
E0.001_-_ELECTRICAL_LEGEND_NOTES_ABBREVIATIONS.pdf PDF
Attachment_E_-_Additional_Renderings.pdf PDF
Attachment_D_-_Fire_Alarm_Panel.pdf PDF
Tax_Collector_Interior_Renovations_and_Restoration.pdf PDF
MASTER_Construction_Contract.pdf PDF
Attachment_C_-_Staging_2.png PNG image
Attachment_B_-_Staging_1.png PNG image
Attachment_A_-_Parking.png PNG image
COV_Division_27,_IT_Systems_Design_and_Installation_Guidelines_for_A-E.pdf PDF
Sales_Tax_Exemption_Procedure.pdf PDF
PRIME-SUB_FORM.xls XLS spreadsheet
VC_Tax_Collector_DeLand_Office_Project_Manuals_5.15.2025.pdf PDF
VC_Tax_Collector_DeLand_Office_Renovation_Bid_Set_5.15.2025.pdf PDF
Payment_and_Performance_Bond.pdf PDF
Basic_Insurance_Requirements.pdf PDF
Special_Conditions.pdf PDF
Bid_Documents.pdf PDF
VCTCO_Architectural.pdf PDF
VCTCO_Volume_2_specs.pdf PDF
Mechanical.pdf PDF
VCTCO_Volume_1_specs.pdf PDF
Fire_Protection.pdf PDF
Electrical.pdf PDF
2025-05-15_-_BID_&_PERMIT_SET_-_Telecommunications.pdf PDF
VOLUSIA_COUNTY_TC_Form_C402.pdf PDF
Plumbing.pdf PDF
staging_(1).png PNG image
Pre-Bid_Meeting_Invitee_Listing.docx DOCX document
Staging.png PNG image
Parking.png PNG image
PRIME-SUB_FORM_for_Contractors_rev._01.15.2025_(lock_before_publishing)_(1).xls XLS spreadsheet
SPECIAL_CONDITIONS_FOR_BIDDERS.docx DOCX document
Show all 36

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1. FIRE PROTECTION SYSTEM TO COMPLY WITH ALL APPLICABLE STATE, LOCAL CODES & AHJ REQUIREMENTS. ALSO

SHALL OBTAIN ALL PERMITS, LICENSES AND ALL GOVERNMENT/MILITARY REQUIREMENTS.

2. FINAL INSPECTION AND APPROVAL BY LOCAL FIRE DEPARTMENT, BLDG. DEPT. AND ARCHITECT/ENGINEER.

3. VISIT THE SITE TO CHECK AND VERIFY ALL EXISTING CONDITIONS PRIOR TO BIDDING TO INSURE THE

COORDINATION OF THE FIRE SERVICES WITH EXISTING CONDITIONS.

4. CUTTING OF STRUCTURAL AND/OR ARCHITECTURAL MEMBERS TO BE DONE ONLY WITH THE WRITTEN APPROVAL OF

THE ARCHITECT AND STRUCTURAL ENGINEER.

5. FITTINGS REQUIRED FOR PROPER INSTALLATION, COORDINATION WITH OTHER EXISTING TRADES, AND/OR TO

MAINTAIN PROPER CLEARANCES SHALL BE PROVIDED. VERIFY STRUCTURAL, MECHANICAL, ELECTRICAL

INSTALLATIONS AND AVOID AN/ALL OBSTRUCTIONS OR INTERFERENCES WITH FIRE PROTECTION PIPE ROUTING.

6. CONTRACTOR SHALL MAKE A FIELD VISIT TO VERIFY ARCHITECTURAL REFLECTED CEILING CONDITIONS AND

ELECTRICAL LIGHTING, CEILING CONFIGURATIONS AND HEIGHTS.

7. FIRE STOP ALL PENETRATIONS OF SMOKE/FIRE WALLS, CEILINGS, FLOORS, ROOFS, ETC., FLASH AND

COUNTERFLASH ROOF PENETRATIONS. (SEE FIRE RATED PIPE PENETRATION DETAILS ON ARCHITECTURAL

SHEETS).

8. PROVIDE ACCESS PANELS TO ALL VALVES ABOVE NON-ACCESSIBLE CEILINGS AND CHASES.

9. SPRINKLER HEADS ARE TO BE COORDINATED WITH ALL LOCATIONS OF DIFFUSERS, SPEAKERS, LIGHTING FIXTURES, CEILING SYSTEMS AND STRUCTURAL SYSTEM.

10. INDICATE CENTER TO CENTER DIMENSIONS AND/OR PIPE CUT LENGTHS AND NOMINAL PIPE DIAMETERS ON ALL

PIPING. INDICATE PIPE TYPE, SCHEDULE OF WALL THICKNESS AND METHOD OF JOINING ON SHOP DRAWING.

11. PROVIDE STOCK OF EXTRA SPRINKLERS IN ACCORDANCE WITH N.F.P.A. # 13.

12. PROVIDE DETAIL AND INDICATE TYPE OF HANGERS TO BE INSTALLED FOR SPRINKLER PIPING. METHODS OF

HANGING PIPES, HEADERS AND BRANCHES SHALL BE IN ACCORDANCE WITH N.F.P.A. 13. ALL HANGERS ON 4" PIPE

AND LARGER SHALL BE CLEVIS-TYPE HANGERS. HANGERS SHALL NOT INTERFERE WITH ANY OTHER TRADE.

POWDER DRIVEN STUDS SHALL NOT BE USED.

13. ALL GROOVED & SCREWED FITTING SHALL BE UL/FM APPROVED PRIOR TO ANY INSTALLATION BY ENGINEER WHO

RESERVES THE RIGHT TO DISAPPROVE ANY FITTING. ALL SCREWED PIPING SHALL BE SCHEDULE 40 BLACK STEEL

PIPE IN ACCORDANCE WITH SPECIFICATIONS ASTM A120 AND SHALL BE JOINED BY SCREWED JOINTS IN

ACCORDANCE WITH SPECIFICATION ANSI B2.1. ALL GROOVED PIPING 2-1/2" OR LARGER SHALL BE SCHEDULE 10

BLACK STEEL.

14. WELD-O-LETS SHALL BE TWO SIZES SMALLER THAN CROSSMAIN, NO LENGTH OF CROSSMAIN SHALL BE GREATER

THAN 10'-0". ALL SPRINKLER PIPING & FITTINGS SHALL BE INSTALLED ABSOLUTELY RUST-FREE.

15. AUTOMATIC SPRINKLER TEMPERATURE RATINGS OF FUSIBLE ELEMENTS TO BE IN ACCORDANCE WITH N.F.P.A. 13.

ALL SPRINKLERS SHALL HAVE CORROSIVE RESISTANT COATING WHERE EXPOSED TO ELEMENTS.

16. SPRINKLERS SHALL COVER THE ENTIRE AREA OF ALL STRUCTURAL MEMBERS. THE SPRAY PATTERN ON ANY

SPRINKLER SHALL NOT BE BLOCKED BY WALL, PARTITIONS OR STRUCTURAL COMPONENTS.

17. IMMEDIATELY NOTIFY THE ARCHITECT/ENGINEER OF ANY DISCREPANCIES FOUND BETWEEN THESE PLANS, OTHER

ENGINEERING PLANS, THE ARCHITECTURAL PLANS AND/OR FIELD CONDITIONS PRIOR TO FINAL BID PRICE OR FINAL

PERMITTING.

18. IN CASE OF DISPUTE OR DOUBT AS TO INTENT OF DRAWINGS OR SPECIFICATIONS, OBTAIN ARCHITECT/ENGINEER'S

WRITTEN DECISION BEFORE PROCEEDING WITH BID OR WORK INVOLVED.

19. BEFORE SUBMITTING PROPOSAL OR BID, EXAMINE ALL DRAWINGS AND SPECIFICATIONS RELATING TO THIS

PROJECT, THE AMOUNT OF SPACE AVAILABLE FOR PIPING, EQUIPMENT AND CONNECTING SERVICES, THE SCOPE

OF SITE OF THE WORK, THE REQUIREMENTS TO CORRELATE THE FIRE PROTECTION WORK WITH THAT OF OTHER

TRADES AND THE TIME SCHEDULE NECESSARY TO PERFORM THAT WORK.

20. PIPE SHALL BE REAMED AND CLEANED BEFORE ASSEMBLY, AND AFTER ASSEMBLY THE ENTIRE PIPING SYSTEM

SHALL BE FLUSHED CLEAN.

21. ADJUST NEW SPRINKLER PIPING AND SPRINKLER HEAD PLACEMENT TO ACCOMMODATE EXISTING CEILING HEIGHTS

AND STRUCTURAL CONFIGURATIONS.

22. PROVIDE SYSTEM(S) WITH FLUSHING CONNECTION(S).

23. PROVIDE SPRINKLERS ABOVE AND BELOW EXPOSED DUCTWORK 4 FEET OR WIDER.

24. PROVIDE HAZARD COVERAGE FOR THE FUNCTIONS FOR EACH AREA.

25. INDICATE THE TOTAL SQUARE FOOT AREA PROTECTED BY SYSTEM(S) ON EACH FLOOR(S).

26. ALL PENDENT SPRINKLERS SHALL BE CENTER OF TILE, UNLESS MAXIMUM DISTANCES FROM WALLS OR BETWEEN

HEADS IS EXCEEDED. IF NOT POSSIBLE ALL SPRINKLER HEADS MOUNTED IN CEILING SHALL BE LOCATED A MINIMUM

OF 4" AWAY FROM ANY WALLS, CEILING GRID MEMBERS, CEILING HEIGHT CHANGES OR ANY OTHER VERTICAL

INTERSECTING STRUCTURAL SURFACE.

27. FIRE PROTECTION CONTRACTOR SHALL ASSIST IN PREPARATION OF COORDINATION DRAWINGS FOR ALL LEVELS

WHICH INDICATE ALL THE ENGINEERING DISCIPLINES & FIRE PROTECTION PIPING. THESE DRAWINGS SHALL BE

PREPARED & APPROVED BY THE ENGINEER PRIOR TO ANY INSTALLATION.

28. REFER TO ARCHITECTURAL DRAWINGS FOR CEILING HEIGHTS IN EACH AREA.

29. ALL MATERIALS, WHERE APPLICABLE, SHALL BE U.L. LISTED AND FACTORY MUTUAL APPROVED FOR USE IN

AUTOMATIC SPRINKLER SYSTEMS. ALL NEW PIPING SHALL BE HYDROSTATICALLY TESTED FOR TWO HOURS IN

ACCORDANCE WITH NFPA #13, 2019 ED. MINIMUM HYDROSTATIC TEST PRESSURE SHALL BE 200 PSI.

30. WET SYSTEM PIPING SHALL BE INSTALLED LEVEL TO DRAIN BACK TO THE SYSTEM RISER, IN ACCORDANCE WITH

NFPA #13. TRAPPED SECTIONS OF PIPING SHALL HAVE AUXILIARY DRAIN CONNECTIONS IN ACCORDANCE WITH NFPA

#13.

THESE PLANS REQUIRE THAT A SEPARATE FIRE SPRINKLER SHOP DRAWING BE PROVIDED AND PERMITS BE OBTAINED BY THE LICENSED AND CERTIFIED FIRE SPRINKLER CONTRACTOR FOR THE INSTALLATION OF THESE SYSTEMS.

THESE PLANS REQUIRE THAT A SEPARATE FIRE ALARM SHOP DRAWING BE PROVIDED AND PERMITS BE OBTAINED BY THE LICENSED AND CERTIFIED FIRE ALARM CONTRACTOR FOR THE INSTALLATION OF THIS SYSTEM.

THE FIRE SPRINKLER CONTRACTOR SHALL OBTAIN THE ACCEPTANCE TESTS FROM THE LOCAL

AUTHORITY. THE ACCEPTANCE TEST FOR THE OVERHEAD SPRINKLER SYSTEM PIPING SHALL BE IN

ACCORDANCE WITH NFPA 13. USING THE MATERIAL AND TEST CERTIFICATE FOR ABOVEGROUND.

THE FIRE SPRINKLER CONTRACTOR SHALL PREPARE DETAILED WORKING PLANS IN

ACCORDANCE WITH NFPA 13,2019 EDITION. THE FIRE PROTECTION SYSTEM LAYOUT SHALL

FOLLOW THE DESIGN GUIDELINES SET FORTH IN THESE FIRE PROTECTION SYSTEM

ENGINEERING DOCUMENTS.

THIS IS AN EXISTING STRUCTURE WITH AN EXISTING SPRINKLER SYSTEM; THEREFORE, THE POINT OF

SERVICE IS NOT SHOWN.

THE FOLLOWING ARE APPLICABLE STANDARDS: NFPA 13 2019 EDITION.

CLASSIFICATIONS OF HAZARD OCCUPANCIES FOR THE AREAS OF DESIGN SHALL BE AS INDICATED ON THE

FLOOR PLANS.

WATER SUPPLY: THIS BUILDING HAS AN EXISTING SUPPLY COMING OFF THE EXISTING WATER MAIN.

THIS IS AN EXISTING STRUCTURE WITH AN EXISTING SPRINKLER SYSTEM. SEE THIS SHEET FOR EXISTING

HYDRAULIC SPECIFICATIONS.

VALVE AND ALARM REQUIREMENTS: ALL CONTROL VALVES ON SPRINKLER RISERS & FIRE PROTECTION BACKFLOW PREVENTERS SHALL HAVE A TAMPER SWITCH. THE FLOW SWITCH SHALL BE SET TO NOT ALARM WITH MINOR CITY WATER PRESSURE FLUCTUATIONS. HOWEVER, THE FLOW OF ONE SPRINKLER HEAD SHALL PRODUCE AN ALARM CONDITION BY TRIPPING THE FLOW SWITCH. ALL FLOW & TAMPER SWITCHES SHALL BE CONNECTED TO THE BUILDING FIRE ALARM PANEL. FLOW SWITCHES SHALL ALSO SOUND THE ELECTRIC ALARM BELL ON THE OUTSIDE WALL. FIRE SPRINKLER CONTRACTOR SHALL VERIFY & TEST PER NFPA 13.

THE LOCAL WATER PURVEYOR IS REQUESTED TO ADVISE THE ENGINEER OF RECORD IF CONDITIONS EXIST IN THEIR WATER SUPPLY THAT COULD LEAD TO MIC, SO THAT THE ENGINEER CAN DESIGN CORRECTIVE MEASURES. THERE ARE NO KNOWN MIC CONDITIONS IN THE PUBLIC UTILITY'S WATER SYSTEMS.

SEE CIVIL DRAWINGS FOR BACKFLOW AND METER. BACKFLOW PREVENTER AND METERING SPECIFICATIONS

SHALL MEET OR EXCEED REQUIREMENTS OF THE PUBLIC UTILITY.

INTERIOR FIRE PROTECTION COMPONENTS: PRODUCT DATA SHEETS SHALL BE SUBMITTED BY THE SPRINKLER CONTRACTOR ALONG WITH THEIR SHOP DRAWINGS. ALL FIRE PROTECTION DEVICES AND

COMPONENTS SHALL BE UL LISTED AND FM APPROVED.

THE SPRINKLER SYSTEM SHALL BE WET PIPE WITH SPRINKLERS THAT HAVE A TEMPERATURE RATING OF 155

DEGREES AND THE SPACING SHALL BE PER MANUFACTURERS LISTING.

A FIRE PUMP IS NOT REQUIRED FOR THIS RENOVATION.

A FIRE WATER STORAGE TANK IS NOT REQUIRED BASED UPON WATER SUPPLY INFORMATION, BUILDING

HEIGHT AND HAZARD CLASSIFICATION.

THIS IS NOT A STORAGE OCCUPANCY AND AN OWNER'S CERTIFICATE IS NOT REQUIRED.

31. WET PIPE SPRINKLER SYSTEM DESIGNED PER NFPA 13.

32. PIPE TO HANG TIGHT TO BOTTOM OF DECK WHERE POSSIBLE. IN ALL OTHER AREAS, PIPE TO HANG AS HIGH AS

POSSIBLE.

33. THE CONSTRUCTION MANAGER SHALL PROVIDE, OR HAVE PROVIDED, A SET OF COORDINATION DWGS. FOR ALL

SYSTEMS & FEATURES THAT OCCUR ABOVE THE CEILING PLANE. THE COORDINATION DWGS. SHALL INCLUDE, BUT

NOT BE LIMITED TO, STRUCTURAL MEMBERS, HVAC DUCTWORK, HYDRONIC PIPING, PLUMBING SUPPLY & WASTE

PIPING, FIRE PROTECTION PIPING, ELECTRICAL POWER CONDUITS & RACEWAYS & ELECTRICAL LOW VOLTAGE

CONDUITS & RACEWAYS. THE COORDINATION DWGS. SHALL PROVIDE, APPORTION & COORDINATE SPACE FOR ALL

SYSTEMS, HORIZONTALLY & VERTICALLY ABOVE THE CEILING PLANE TO THE STRUCTURAL DECK ABOVE ALLOWING

EACH TRADE CONTRACTOR THE SPACE TO PROPERLY EXECUTE HIS PORTION OF THE WORK.

34. ALL GROOVED FITTINGS TO BE "VICTAULIC" FITTINGS OR APPROVED EQUAL.

35. ALL DIMENSIONS TO BE VERIFIED DURING FIELD CHECK OF SPRINKLER SYSTEM.

36. ALL UPRIGHT TYPE SPRINKLERS ARE TO BE BRASS w/NO ESCUTCHEON 1/2" ORIFICE, 155°F WITH A 5.6 K-FACTOR.

QUICK RESPONSE EQUAL TO THE VIKING MICROFAST MODEL M QUICK RESPONSE IDENTIFICATION #VK300.

37. RECESSED PENDENT TYPE SPRINKLERS (PUBLIC AND COMMON AREAS) ARE TO BE WHITE w/RECESSED WHITE

ESCUTCHEON, 1/2" ORIFICE, 155° WITH A 5.6 K-FACTOR. QUICK RESPONSE. EQUAL TO THE VIKING QR RECESSED

PENDENT SPRINKLER IDENTIFICATION #VK302.

38. SEMI-RECESSED PENDENT TYPE SPRINKLERS (BACK OF HOUSE AREAS) ARE TO BE WHITE w/WHITE ESCUTCHEON, 1/2" ORIFICE, 155° WITH A 5.6 K-FACTOR. QUICK RESPONSE. EQUAL TO THE VIKING QR RECESSED PENDENT

SPRINKLER IDENTIFICATION #VK302.

39. ALL FIRE SPRINKLER COMPONENTS ARE TO BE RATED FOR THE MAXIMUM SYSTEM WORKING PRESSURE TO WHICH

THEY ARE EXPOSED IN ACCORDANCE WITH NFPA 13.

40. ALL PENDENT TYPE FIRE SPRINKLERS IN PUBLIC AREAS SHALL BE CENTERED IN CEILING TILES

SYMBOL HAZARD DENSITY

HOSE

DEMAND

(GPM)

DURATION

(MIN)

MAX.

STORAGE

HEIGHT

DESIGN AREA

(SQ. FT.)

MAX SQ. FT.

/ SPRINKLER

ORDINARY

HAZARD

GROUP I

.15GPM/

SQ.FT.

130 1500 250 60 8'-0"

LIGHT

HAZARD

.1GPM/

SQ.FT.

225 1500 100 30 NONE

LH

SPRINKLER HEAD IN CEILING TILE DETAIL

SPRINKLER HEAD DETAIL

TYPICAL SPRINKLER HEAD RELOCATION

6"

6"

6"

6"

12"12"

12" 12" 12" 12"

12"

12"

32.003(1)

32.003(2)

32.004(2)(a)

32.004(2)(b)

32.004(2)(c)

32.004(2)(d)

32.004(2)(e)

32.004(2)(f)

32.004(2)(g)

32.004(2)(h)

32.004(2)(i)

32.004(2)(j)

32.004(2)(k)

32.004(2)(l)

32.004(2)(m)

QUARTER TILE IS ACCEPTABLE

QUARTER TILE IS ACCEPTABLE

Acceptable Locations for Sprinkler in 2'x2' Ceiling Tile

Sprinkler in 4'x2' Ceiling Tile Acceptable Locations for

APPLICABLE CODES/STANDARDS

FIRE PROTECTION GENERAL NOTES

NOTE:

ALL REFERENCES TO "CONTRACTOR" SHALL MEAN THE SUB-CONTRACTOR PERFORMING THE SPECIFIC WORK.

HVAC SUBCONTRACTOR SHALL BE RESPONSIBLE FOR ALL MECHANICAL WORK. ELECTRICIAN SHALL BE

RESPONSIBLE FOR ALL ELECTRICAL WORK. PLUMBING SUBCONTRACTOR SHALL BE RESPONSIBLE FOR ALL

PLUMBING WORK. FIRE ALARM SUBCONTRACTOR SHALL BE RESPONSIBLE FOR ALL FIRE ALARM WORK, AND

FIRE SPRINKLER CONTRACTOR SHALL BE RESPONSIBLE FOR ALL FIRE SPRINKLER WORK.

FAC 61G15-32.003 NOTES

FAC 61G15-32.004 NOTES

FIRE PROTECTION GENERAL NOTES (CONT.)

MAXIMUM DISTANCE BETWEEN HANGERS

- 2019 NFPA 13

- 2023 FLORIDA FIRE PREVENTION CODE WITH LOCAL AMENDMENTS

- 2023 FLORIDA BUILDING CODE WITH LOCAL AMENDMENTS

DESIGN CRITERIA

1" 1-1/4" 1-1/2" 2" 2-1/2" 3" 4"-6"

NOMINAL

PIPE SIZE

STEEL PIPE - 12'-0" 15'-0" 15'-0" 15'-0" 15'-0" 15'-0"

CPVC 5'-6" 6'-0" 6'-6" 7'-0" 8'-0" 9'-0" 10'-0" -

3/4"

12'-0"

NTS

1" DROP NIPPLE

NEW SPRINKLER HEAD

BRANCH LINE

EXISTING

CEILING PLATE

SUSPENDED CEILING

REMOVE EXISTING

SPRINKLER HEAD AND

REPIPE AS SHOWN

NOT TO SCALE

(TYPE & COLOR BY ARCH.)

SUSPENDED CEILING TILE

REPIPE AS SHOWN

AND EXIST. SPRINKLER.

REMOVE DROP NIPPLE

BRANCH PIPE

CL

NEW SPRINKLER HEAD

CEILING PLATE

OH-I

.20GPM/

SQ.FT.

ORDINARY

HAZARD

GROUP II

130 1500 250 90 12'-0"

OH-II

DRAWING NUMBER

SEAL

S

RACH ITECTS

TITLE

DATE

LOCATION

OWNER

PROJECT

605 E. Robinson Street Suite 630

Orlando, Florida 32801 Office 321.296.8100 silling.com

CA# 26308 I24027.00

5/16/2025 8:44:08 AMAutodesk Docs://VOLUSIA-TC Office Deland/VCTCO-Fire.rvt

FIRE PROTECTION

LEGEND, NOTES &

ABBREVIATIONS

F0.001

Volusia County Tax Collector

Thomas C Kelley Administration Center 123 W. Indiana Avenue Deland, Florida 32720

Volusia County Tax Collector - Deland Office Renovation

Eric S Cepull PE 64750

05.15.2025

IE - FIRE PROTECTION SHEET LIST

Sheet Number Sheet Name Project Issue Date Project Status Current Revision Current Revision Date Current Revision Description Sheet Discipline

F0.001 FIRE PROTECTION LEGEND, NOTES & ABBREVIATIONS 05.15.2025 ISSUE FOR PERMIT FIRE PROTECTION

F1.101 FIRST LEVEL PLAN FIRE PROTECTION 05.15.2025 ISSUE FOR PERMIT FIRE PROTECTION

Grand total: 2

REVISIONS

A A

B B

G G

H H

J J

D D

E E

F F

BREAK ROOM

OFFICE

CASH

IT

MECHANICAL

STAIR

HALL

STORAGE

HALL

ELEC

IT

STORAGE

PERMITTING

HALL

TOILET

TOILET

CHECK-IN

STAFF

CHECK-IN

ENTRY

WAITING A

WAITING B

SERVICE

TESTING

CUSTOMER

SERVICE

HALL

HALL

HALL

ALIGN NEW WALL

W/ CORNER

ALIGN

LIMITS OF WORK

L

IM

IT

S

O F

W O

R K

L

IM

IT

S

O F

W O

R K

ALIGN

A L

IG

N

W O

O D

B E

N C

H

OH-I

OH-I

NIC

OH-I

OH-I

OH-I

OH-I

FLOOR

PLAN

NORTH

DRAWING NUMBER

SEAL

S

RACH ITECTS

TITLE

DATE

LOCATION

OWNER

PROJECT

605 E. Robinson Street Suite 630

Orlando, Florida 32801 Office 321.296.8100 silling.com

CA# 26308 I24027.00

5/16/2025 8:44:12 AMAutodesk Docs://VOLUSIA-TC Office Deland/VCTCO-Fire.rvt

FIRST LEVEL PLAN FIRE

PROTECTION

F1.101

Volusia County Tax Collector

Thomas C Kelley Administration Center 123 W. Indiana Avenue Deland, Florida 32720

Volusia County Tax Collector - Deland Office Renovation

Eric S Cepull PE 64750

05.15.2025

1/8" = 1'-0"F1.101

1 1ST LEVEL - New Work Fire Protection

1. DETERMINE EXACT LOCATION OF ALL EXISTING FIRE PROTECTION COMPONENTS

AND WIRING BEFORE COMMENCING WORK.

2. LOCATE AND PRESERVE ALL PORTIONS OF THE EXISTING FIRE PROTECTION

SYSTEMS WHICH SHALL REMAIN.

3. EXISTING PIPING AND SPRINKLERS MAY BE REUSED WHERE THEY ARE OF THE TYPE

SPECIFIED, MEET THE REQUIREMENTS OF THE NEW WORK AS DEFINED BY THE

CONTRACT DOCUMENTS, AND REMAIN IN GOOD CONDITION.

4. ALL SPACES SHOWN ARE CONSIDERED TO BE NFPA 13 LIGHT HAZARD OCCUPANCY

UNLESS NOTED OTHERWISE.

GENERAL NOTES

REVISIONS

F0.001 - FIRE PROTECTION LEGEND, NOTES & ABBREVIATIONS
F1.101 - FIRST LEVEL PLAN FIRE PROTECTION