FI23-013-VA-Walla-Walla-Bldg-76-FA.pdf
PDF 3 MB Posted
- Attached to
- H212 Fire Alarm Inspections, Testing, Maintenance & Repairs - Walla Walla VA - Dept of Veterans Affairs
- Solicitation number
- 36C26025Q0599
About this file
This document is a Fire Alarm System Replacement technical drawing set for Building 76 at the VA Walla Walla Medical Center located at 77 Wainwright Drive in Walla Walla, Washington. The project involves a comprehensive fire alarm system upgrade, including replacing the existing campus fire alarm system with a new addressable system, replacing copper cabling with fiber optic infrastructure, and installing new fire alarm control panels.
The scope of work includes installing voice evacuation notification appliances throughout the building, monitoring fire sprinkler systems, adding smoke and heat detectors in code-required locations, installing new manual pull stations at building exits, and implementing a campus-wide computer monitoring and control system in Building 78. The project follows 2018 IBC, IFC, NFPA 101, and VA Fire Protection Manual standards. The system will be a Notifier fire alarm system with features like synchronized voice evacuation, central station monitoring, and addressable intelligent devices. The drawings were prepared by Vulcan Fire and are dated 05/16/2024, with the project involving a 5,950 square foot facility.
View the file
Other files
Show all 27
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SYSTEM INPUTS
PANEL FUNCTIONS
ALARM DEVICES
SYSTEM RESET
SYSTEM SILENCE
"ALL SYSTEMS NORMAL"
SMOKE DETECTORS
SUPERVISORY DEVICES
TROUBLE FUNCTIONS
ABNORMAL CIRCUIT OR DEVICE
FIRE ALARM SYSTEM AC POWER FAILURE
FIRE ALARM SYSTEM LOW BATTERY
SP
EA
KE
RS
A
ND
S
TR
OB
ES
S
TO
P
YE
LL
OW
LE
D W
IL
L F
LA
SH
A
ND
YE
LL
OW
LE
D W
IL
L F
LA
SH
A
ND
W
IL
L T
UR
N
ON
, U
NT
IL
S
IL
EN
CE
D.
RE
D
LE
D
AN
D
AU
IB
LE
S
OU
ND
ER
HI
ST
OR
Y
LO
G:
SYSTEM OUTPUTS
(S
YN
CH
RO
NI
ZE
D
AN
D
VO
IC
E
EV
AC
TE
MP
OR
AL
P
AT
TE
RN
AC
TI
VA
TE
S
BU
IL
DI
NG
S
IN
TE
RI
OR
N
OT
IF
IC
AT
IO
N
DE
VI
CE
S
FACP FUNCTION
AC
TU
AT
ES
T
RO
UB
LE
C
ON
DI
TI
ON
A
T
CO
NT
RO
L P
AN
EL
PU
LS
IN
G
SO
UN
DE
R
W
IL
L T
UR
N
ON
, U
NT
IL
A
CK
NO
W
LE
DG
ED
AC
TU
AT
ES
S
UP
ER
VI
SO
RY
C
ON
DI
TI
ON
A
T
CO
NT
RO
L P
AN
EL
GR
EE
N
AC
P
OW
ER
IN
DI
CA
TO
R
IS
LI
T
ST
EA
DI
LY
ON
C
ON
TR
OL
P
AN
EL
CH
AR
AC
TE
R
LC
D
DI
SA
PL
Y
DI
SP
LA
Y
TH
E
CU
ST
OM
M
ES
SA
GE
"A
LL
S
YS
TE
MS
N
OR
MA
L"
AC
TU
AT
ES
A
LA
RM
C
ON
DI
TI
ON
A T
CO
NT
RO
L P
AN
EL
RE
CO
RD
IN
G
OF
T
HE
E
VE
NT
IN
S
YS
TE
MS
M
EM
OR
Y
PU
LS
IN
G
SO
UN
DE
R
W
IL
L T
UR
N
ON
, U
NT
IL
A
CK
NO
W
LE
DG
ED
FI
RE
A
LA
RM
C
ON
TR
OL
P
AN
EL
R
ET
UR
NS
T O
NO
RM
AL
NOTIFICATION
MANUAL PULL STATION
A B C D E F G H I J K L M
FIRE SPRINKLER SYSTEM - MAIN WATERFLOW SWITCH (LATCHING)
Fire Alarm System Matrix
FIRE SPRINKLER SYSTEM - VALVE TAMPER SWITCH
MICROPHONE ACTIVATION WITH CIRCUIT SELECTION SWITCH
(V
OI
CE
E
VA
CU
AT
IO
N
SP
EA
KE
RS
AC
TI
VA
TE
S
BU
IL
DI
NG
S
IN
TE
RI
OR
N
OT
IF
IC
AT
IO
N
DE
VI
CE
S
(C
ON
TA
CT
ID
) T
O U.
L.
CL
AS
S
CE
NT
RA
L S
TA
TI
ON
(C
ON
TA
CT
ID
) T
O U.
L.
CL
AS
S
CE
NT
RA
L S
TA
TI
ON
(C
ON
TA
CT
ID
) T
O U.
L.
CL
AS
S
CE
NT
RA
L S
TA
TI
ON
(C
ON
TA
CT
ID
) T
O U.
L.
CL
AS
S
CE
NT
RA
L S
TA
TI
ON
TR
AN
SM
IT
S W
AT
ER
FL
OW
C
ON
DI
TI
ON
V
IA
C
EL
LU
LA
R
CO
MM
UN
IC
AT
OR
TR
AN
SM
IT
S
TR
OU
BL
E
CO
ND
IT
IO
N
VI
A
CE
LL
UL
AR
C
OM
MU
NI
CA
TO
R
TR
AN
SM
IT
S
SU
PE
RV
IS
OR
Y
CO
ND
IT
IO
N
VI
A
CE
LL
UL
AR
C
OM
MU
NI
CA
TO
R
TR
AN
SM
IT
S
AL
AR
M
CO
ND
IT
IO
N
VI
A
CE
LL
UL
AR
C
OM
MU
NI
CA
TO
R
AN
NU
NC
IA
TO
RS
(B
OT
H
SP
EA
KE
RS
A
ND
S
TR
OB
ES
W
IL
L S
TO
P)
NO
TI
FI
CA
TI
ON
A
PP
LI
AN
CE
S
SH
AL
L B E
SI
LE
NC
EA
BL
E
AT
T
HE
FA
CP
O
R
ON
YX
W
OR
KS
S
TA
TI
ON
IN
B
UI
LD
IN
G
SE
CU
RI
TY
O
FF
IC
E
TR
AN
SM
IT
S
SY
ST
EM
C
ON
DI
TI
ON
V
IA
FI
BE
R
NE
TW
OR
K
NE
TW
OR
K
AN
NU
NC
IA
TO
R
IN
B
UI
LD
IN
G
P
OL
IC
E
ST
AT
IO
N
TR
AN
SM
IT
S
SY
ST
EM
C
ON
DI
TI
ON
V
IA
FI
BE
R
NE
TW
OR
K
N O
Number of Sheets:
By
Installing Fire Alarm System Contractor:
Date
Drawn By:
Drawn Date:
Scale:
Drawing No.
Revisions Description
Authority Having Jurisdiction:
Project Contacts
DHL
05/16/2024
VA
W al la
W al la
B ui ld in g
W ai nw rig ht
D riv e W al la
W al la , W
A
Li fe
S af et y
(F ire
A la rm S ys te m ) D ra w in gs
COPYRIGHT NOTICE
ALL DRAWINGS AND WRITTEN MATERIAL APPEARING HEREIN
CONSTITUTE THE ORIGINAL AND UNPUBLISHED WORK OF
VULCAN FIRE, AND THE SAME MAY NOT BE DUPLICATED, USED
OR DISCLOSED WITHOUT THE EXPRESS WRITTEN CONSENT OF
VULCAN FIRE
Reviewed by:
ENGINEERED SYSTEM DISTRIBUTION
by Honeywell
TM
Vulcan Project #: FI23-013
Todd Wagner
NICET #106447
Fire Alarm Systems Level IV Expiration: 11/1/26 Reviewed: 05/16/24
Signature:____________________________
U .S
.D ep ar tm en t o f V et er an s A ffa irs
Fi re
A la rm S ys te m R ep la ce m en t -
P ha se B
Walla Walla Fire Department 2251 S. Howard St., Walla Walla, WA 99362
(509) 524-4603
Vulcan Fire 112 East Hazel Ave., Ste#1, Coeur d'Alene, ID 83814
(208) 277-0171
GC
L ice ns e:
V
UL
CA
F*
0M
El ec
L ice ns e:
V
UL
CA
F*
W
EB
SI
TE
: w w w
.v ul ca nf ire us
.c om
PH
ON
E
(2
) 2
-0
Ea st H az el
A ve nu e, S ui te
1, C oe ur d 'A le ne
, I da ho
N/A
FA-0.0
Site Plan
General Notes:
Drawing Notes:
Fire Alarm Control Panel Terminations:
Scope of Work:
All wiring runs shown on the fire alarm shop drawings are conceptual only. They do not and are not intended to be actual wire runs or conduit runs. Device interconnect is intended to show only sequence of device connections and type of wire.
Please review both the floor plans and the riser diagram drawings to resolve any conflicts or questions that may come up. If the drawings do not answer your questions, please call Vulcan Fire for help to answer your questions.
Electrical Contractor is advised not to complete terminations at the Fire Alarm Control Panel. Terminations will be completed by a qualified Vulcan Fire Technician.
Code Analysis:
Edition of Codes:
Number of Stories:
Edition of Standards:
Occupancy Type: B, Business (Office, Maintenance/Shop) S-1 Storage (Storage Rooms, Boilers)
2018 IBC, IFC, IMC
2018 NFPA 101
City of Walla Walla Amendments 2009 ANSI 117.1 Guidelines for Accessible & Useable
Yes, Fully Fire Sprinklered
1 w/ Mezzanine
Visual Notification: Public Mode
Wire runs are indicated by AlphaNumeric designations.
power run of "2#__ " cable. A designation of "P3" would indicate another individual run of "2#__ " cable.
"2#__Twisted AND a run of 2#__ " cable.
A designation of "A,P2", would refer to a run of
The wire Gauge of any wire run is determined by the
A designation of "P2", would refer to a individual pair, 2#__ Twisted" cable.
A designation of "2A", would refer to a run of "2 length of the wire run and the power load on that run.
A typical wire run designated as "A", would refer to a single run of "2 #__ Twisted" cable.
For example:
A,P2
P2,P3
A
2A
Wire Chart:
Audible Notification: Voice Evac - Temporal 3 Pattern / Synchronized
Type of FA System: New Fire Alarm Addressable System
Index of Drawings Drawing Name
Drawing Number
Cover SheetCover SheetFA-0.0 FA-1.1 First Floor - Fire Alarm Plan / Mezzanine -
Fire Alarm Plan / Riser Diagram / Details / Load Calculations / Speaker Calculations
Temporal Pattern Notification Device Numbering:
(IE: HORN/STROBE)
AUDIBLE/VISUAL DEVICE
(IE: STROBE ONLY)
AUDIBLE DEVICE
(IE: HORN ONLY)
WITH THE REQUIREMENTS FOR VISUAL DEVICES.
1. ADA ACCESSIBILITY GUIDELINES HAVE ACCEPTED NFPA 72 GUIDELINES AS "EQUIVALENT FACILITATION".
3. MEASUREMENT IS TO THE BOTTOM OF THE DEVICE.
2. NFPA 72 STATES THAT COMBINATION AUDIBLE/VISUAL DEVICES SHALL BE MOUNTED IN ACCORDANCE
NOTES:
AFF = ABOVE FINISHED FLOOR0" (FLOOR)
NFPA 72
A
90" A.F.F.
A/V
96" A.F.F.
80" A.F.F.
NFPA 72
MAX.
MIN.
V
VISUAL DEVICE
CEILING
6" BELOW
CEILING
Example of Proper Mounting for Audible/Visual Devices:
Example of Junction Box Detail (FA):
If Applicable (Use for eample only)
Sheet Number
Walla Walla, WA 99362
U.S. Department Of Veterans Affairs VA Medical Center
77 Wainwright Drive
Owner
Fire Protection System:
Square Footage:
FA System Required: Code-Required
Project Manager: Dave Clem
GDM of Oregon 1584 McNeil Street, Suite 200
DuPont, WA 98327
Architect / Engineer
5,950 GSF
Protected Premises Fire Alarm Systems (Wiring):
Mounted Candela Rating:
S150 = 150 Candela S177 = 177 Candela S185 = 185 Candela
S135 = 135 Candela
S115 = 115 Candela S110 = 110 Candela S95 = 95 Candela S75 = 75 Candela S30 = 30 Candela S15 = 15 Candela
Ceiling S15C S15
Wattage Speaker 1W Tap
Guard WireWG WeatherproofWP
VOICE CIRCUIT
V 2
2S
POWER SUPPLY NUMBER
STROBE CIRCUIT
CIRCUIT NUMBER
AMPLIFIER NUMBER
CIRCUIT NUMBER
("T" Tap) Class B
Class B
P
F P
VS VSAIM
Class B
IDC - Initiating Device Circuit Manual Pull Stations, Fire Sprinkler System, Etc.
NAC - Notification Appliance Circuit Horns, Bells, Strobes, Etc.
SLC - Signaling Line Circuit Intelligent (Addressable) Devices
Only in J-Box (per Owner)
FS
S
Where used, End-Of-Line Resistors shall be labeled "EOL" on the Device (per Owner)
Building 76 77 Wainwright Drive, Walla Walla, WA 99362
Fire Alarm System Replacement
The scope of work for this project is to replace the existing campus fire alarm system with a new fire alarm system throughout. The existing copper cabling backbone infrastructure will be replaced with new fiber optic cabling. Each building will be provided with new fire alarm control panels connected to the campus network. A new campus wide computer monitoring and control system will be provided in Building 78.
Existing fire alarm devices such as pull stations, detectors, relay modules, monitor modules, flow and tamper switch interfaces, and associated conduit, boxes and cabling shall be demolished and replaced with new devices.
Building 76 Fire Alarm System:
The new Notifier fire alarm system in Building 76 will be replacing the existing fire alarm system. Voice evacuation notification appliances will be installed throughout the entire building, which will alert the occupants in the event of a fire. The FACP will provide monitoring of the fire sprinkler system. Smoke and Heat Detectors will be installed where required per codes. New manual pull station will be installed at building exits.
The fire sprinkler tamper switches will cause a supervisory signal when activated. These devices will report as a supervisory signal.
The fire alarm system shall be monitored through a central monitoring company of the owners choosing prior to the final inspection.
N
All intelligent and or addressable Fire Alarm Devices must be placed in protected areas with ambient temperature ranging from 32° to 120°. Weatherproof Fire Alarm Devices have temperature rating from -40° to 151° in wet or dry applications.
Do not place smoke detectors within 3 feet of air supply registers and diffusers.
All intelligent devices shall be interconnected as shown on the riser on-line diagram. Each intelligent device is designed with an address. T-Tapping is permitted on SLC Loop (Class "B") only.
Wire runs show interconnected of fire alarm devices only. Wiring does not represent conduit runs.
Electrical Contractor is responsible for proper connection of equipment provided by others.
(RL) Indicates Existing Device to be relocated to new location.
(R) Indicates Device to be removed and returned to Owner.
(E) Indicates Device existing to remain (shown in gray scale).
(N) Indicates New Device.
(RR) Indicates Remove Existing Device and replace with new Device. Return any removed equipment to Owner.
Typical Device Mounting Height:
NFPA 2016
Wall Mounted AUDIBLE device.
Top of Individual Device
MAX
4'-0"
"ADA"
(48")
Top of Device of the Same Lens
Top of Unit
Top of Cabinet
To Handle of Device Per NFPA 72 from (AFF) Above All heights measured
NOT TO SCALE
Finished Floor
BOTTOM
OF
6'-0"
80" TO
MIN* (72")
LENS
See Note #5
7'-0"
TO TOP
OF
Approx.96"
MAX*
(84")LENS
(6")
THAN
BELOW
CEILING
(90")
AND
LESS
THAN
NOT
LESS
NOT
(64") 5'-4" or 80" MIN. to Bottom A/V or Visual Only Devices
MAX 96" to Top of Lens for all
#1) HEIGHTS SHOWN ARE LISTED IN NFPA STANDARDS 2016.
#2) MOUNTING HEIGHTS LISTED IN SPECIFICATIONS OR SHOWN ON THE
ARCHITECTURAL ELEVATIONS SHALL GOVERN. ANY DISCREPANCY SHALL BE
BROUGHT TO THE ATTENTION OF THE AHJ AND THE ENGINEER OF RECORD.
#3) WALL MOUNTED ADA STROBES & HORN/STROBES ARE TO BE PLACED
A MINIMUM OF 80" ABOVE FINISHED FLOOR MEASURED AT THE BOTTOM OF
THE LENS OR 6" BELOW THE CEILING TO THE TOP OF THE LENS,
WHICHEVER IS LOWEST. THE MAXIMUM HEIGHT MEASURED AT THE TOP OF
THE LENS SHALL NOT EXCEED 96".
#4) IN SLEEPING ROOMS A STROBE MOUNTED LESS THAN 24" FROM THE
CEILING SHALL BE AT LEAST 177CD. STROBES MOUNTED 24" OR BELOW
SHALL BE AT LEAST 110 CD. A STROBE SHALL BE MOUNTED WITHIN 16FT
OF THE PILLOW.
#5) REMOTE LIGHTS, TEST STATIONS AND MODULES SHOULD BE MOUNTED
SO AS TO BE ACCESSIBLE, YET ABOVE EASY REACH TO PREVENT
VANDALISM.
#6) CEILING MOUNT VISIBLE DEVICES SHALL BE SPACED ACCORDING TO
2016 NFPA 72.
FSA
FACFACP RPS
AIM AOM
F
RL
S15H15 15MC15
RT
J DM
MAP FTR
C
AOM
R
S
(48") 4'-0"
*MAX
(42") 3'-6"
*MIN
U.S. Department of Veterans Affairs
VA WALLA WALLA - FIRE LIFE SAFETY - PHASE B Fire Alarm Systems Interconnect Drawings
X
X X
X X
X
X
X
X
XX X
X
X
X
X
X
X
STATE NURSING HOME
STATE NURSING HOME
STATE NURSING HOME
STATE NURSING HOME
N U
R
SIN
G H
O M
E
FU
TU
R E
BL
D
G
7 49 48
66T-7
77T-1
T-2
756968
116119
121126125124
109CM
147 146
W
SITE
Setting Initiating Device Addresses:
D:L1: 501
ONESTENS
7 8 9
00 15
D = Detector M = Monitor
Device AddressData Loop Number
DIALS ARE
LOCATED ON THE
BACK OF EACH
DEVICE
N1:
Node Number
2016 NFPA 72, 2020 NFPA 70 (NEC), VA Fire Protection Manual
FSA
MAP
BATT
S P
FACP
EVAC
F
AIM
VS
WF
SS
FARC
Indicates Circuit Continuation Indicates Home Run to FACP
S30
S75
F190°
S15
S95
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text PRV Vault
AutoCAD SHX Text F/A
AutoCAD SHX Text 8"
AutoCAD SHX Text Caps
AutoCAD SHX Text Tank
AutoCAD SHX Text Fuel
AutoCAD SHX Text F/A
AutoCAD SHX Text Valves
AutoCAD SHX Text
PRV
AutoCAD SHX Text F/A
General Note:
Addressing Legend:
D = Detector M = Module
Module/Device Number M01L01
Loop Number
* All addressable devices require SLC Loop (A-wire) from the FACP to operate. For help, please refer to riser diagram for reference.
* Do not route conduit into the bottom of any fire alarm system component cabinets.
* Tap all speakers at 1/2 watt - 25 volts unless otherwise indicated at individual device.
* Contractor may reuse existing pathways where available. Verify with system designer prior to adding additional devices or extending circuits to ensure voltage drop calculations are within acceptable limits.
1) Section of NFPA 72, National Fire Alarm Code requires units to be provided with smoke detection in areas that are not continuously occupied.
2) Provide Dedicated 120VAC circuit to the FACP label the Dedicated circuit breaker "Fire Alarm." In red with lockout. Location of breaker shall be noted at FACP.
3) Fiber Network routing to be field coordinated.
4) Visual Notification omitted in areas without existing devices or ADA requirements to comply with VA Fire Protection Manual Section 7.3.F.l.4.
Field verify single person offices with hearing-impaired occupants.
Flag Notes: (Some flag notes may not appear on every sheet)
Dedicated
120VAC
SS
FACP FARC
MAP
EP
GUTTER
CPU2-640
HS-NCM-MF
NCA-2
DVC / CMIC-1
DAA2-7525
EVAC
BATT
Battery Battery
Addressable Pull Station
321(-)
A ANBG-12LX
Strobe S0-1
Speaker V0-1 V
S
B300-6
From
Device SLC Loop previous
Device SLC Loop To next
A
A
Addressable Smoke or Heat Detector
RA
P
SF F
V
S75
4.7k
20k
Speaker/Strobe
Speaker
Strobe
VV
S S
Strobe
Strobe
S_ S_
S
1W S75
A
First Floor
SL
C
Lo op
A
P
SA
Backflow Preventer
VS
47k
Main - Fire Sprinkler System
WF 47k
VS
Main
AIM D
DD
T1
T2
T4 T5
LOOP
T6 T7 T8
T9 T10
ADDRESS
T3
T11
FMM-1
Fire Sprinkler Valve Tamper
D 0 15 14
6 7 8 9 9876
1 0
TENS ONES
A
A
Fire Sprinkler System - Valve Tamper with FMM-1 Monitor Module
T1
T2
T4 T5
LOOP
T6 T7 T8
T9 T10
ADDRESS
T3
T11
FMM-1
Fire Sprinkler Valve Tamper
D 0 15 14
6 7 8 9 9876
1 0
TENS ONES
A
A
Fire Sprinkler System - Valve Tamper with FMM-1 Monitor Module
Mezzanine
F190°
HF
F
To Fiber Network Bldg. 82
FTo Fiber Network Bldg. 80 FSA2AD,AP
MAP
F
1W S110
First Floor
AIM
1W S75
1W S75
1W S75
1W S75 S15
Mezzanine
1W S75
1W S3015
Dedicated
120VAC
SS
FARC
MAP
EP
To Bldg. Devices (SLC Loop) A
CPU2-640
HS-NCM-MF
NCA-2
DVC / CMIC-1
DAA2-7525 FACP
Spkr Crkts V0-1, V0-2, V0-3, V0-4BATT
NAC Crkts S0-1, S0-2, S0-3, S0-4, To Fiber Network Patch Panel2F
Components located inside of
FACP
EVAC
S P
N55:L1:D001
FN55:L1:M001
INCINERATOR
101A
FOYER/STORAGE
CONTROL/MAINT.
SHOP
101B
OFFICE
101D
RESTROOM
/ SHOWER
101C
BOILER
ROOM
101E
PUMP
ROOM
101F
EMERGENCY
GENERATOR
101G
To FACP
MAP
FSA 2AD,AP
S P N55:L1:D002
S75 1W
S0-1 V0-1
S75 1W
S0-1 V0-1
VS
Backflow Preventer
Main - Fire Sprinkler System
D WF
N55:L1:M011
N55:L1:M012
VS D
AIM
DAIM
Field verify Fire Sprinkler connections.
F N55:L1:M002
S110 1W
S0-1 V0-1
S75
S0-1 V0-1
S0-1
S0-1
S75 1W
S0-1 V0-1
S75 1W
S0-1 V0-1
S75 1W
S0-1 V0-1
S15
S0-1 V0-1
F
F190° H
F
S30 1W
S0-1 V0-1
To
FACP
S,V
From Mezz.
To Mezz.
N55:L1:M003
N55:L1:M004
N55:L1:D003
S0-1
S,V
S,V
S,V
S,V
S,V S,V
S,V
S,V
S,V S,V
DA ROOM/
MEZZANINE
S75 1W
S0-1 V0-1
To/From 1st Flr
S,V
Number of Sheets:
By
Installing Fire Alarm System Contractor:
Date
Drawn By:
Drawn Date:
Scale:
Drawing No.
Revisions Description
Authority Having Jurisdiction:
Project Contacts
DHL
05/16/2024
VA
W al la
W al la
B ui ld in g
W ai nw rig ht
D riv e W al la
W al la , W
A
Li fe
S af et y
(F ire
A la rm S ys te m ) D ra w in gs
COPYRIGHT NOTICE
ALL DRAWINGS AND WRITTEN MATERIAL APPEARING HEREIN
CONSTITUTE THE ORIGINAL AND UNPUBLISHED WORK OF
VULCAN FIRE, AND THE SAME MAY NOT BE DUPLICATED, USED
OR DISCLOSED WITHOUT THE EXPRESS WRITTEN CONSENT OF
VULCAN FIRE
Reviewed by:
ENGINEERED SYSTEM DISTRIBUTION
by Honeywell
TM
Vulcan Project #: FI23-013
Todd Wagner
NICET #106447
Fire Alarm Systems Level IV Expiration: 11/1/26 Reviewed: 05/16/24
Signature:____________________________
U .S
.D ep ar tm en t o f V et er an s A ffa irs
Fi re
A la rm S ys te m R ep la ce m en t -
P ha se B
Walla Walla Fire Department 2251 S. Howard St., Walla Walla, WA 99362
(509) 524-4603
Vulcan Fire 112 East Hazel Ave., Ste#1, Coeur d'Alene, ID 83814
(208) 277-0171
GC
L ice ns e:
V
UL
CA
F*
0M
El ec
L ice ns e:
V
UL
CA
F*
W
EB
SI
TE
: w w w
.v ul ca nf ire us
.c om
PH
ON
E
(2
) 2
-0
Ea st H az el
A ve nu e, S ui te
1, C oe ur d 'A le ne
, I da ho
1/8" = 1'-0"
FA-1.1
Riser Diagram / Details - Fire Alarm System
VOLTAGE DROPS ARE CALCULATED AT 16VDC.
L= ONE WAY LENGTH OF CIRCUIT(FEET)
WHERE VD= VOLTAGE DROP
R= 3.19 OHMS PER THOUSAND
I= LOAD CURRENT(AMPERES)
AFTER DETERMINING THE LENGTH OF THE HORN/STROBE CIRCUIT, USE
THE FOLLOWING FORMULA TO CALCULATE THE VOLTAGE DROP.
2xLxRxIVD=
LUMP SUM METHOD WAS USED TO CALCULATE ALLOWABLE VOLTAGE DROP. THIS METHOD
ALLOWS FOR A SMALL MARGIN OF SAFETY, TAKING INTO CONSIDERATION THE ACTUAL
CIRCUIT ROUTING MAY DIFFER FROM WHAT IS SHOWN ON THE SHOP SUBMITTAL
DRAWINGS. IF ACTUAL CIRCUIT LENGTH IS GOING TO EXCEED THE MAXIMUM ALLOWABLE
CIRCUIT LENGTH, CONTACT VULCAN FIRE.
VOLTAGE-DROP CALCULATION NOTE:
** STARTING VOLTAGE-DROP CALCULATIONS IS 20.4 PER UL 864, 9TH EDITION STANDARDS FOR FIRE ALARM
CONTROL PANELS.
Scale: 1/4'' = 1'-0''
10 2 4 8 16
First Floor - Fire Alarm System Plan
Scale: 1/4'' = 1'-0''
10 2 4 8 16
Mezzanine - Fire Alarm System Plan
AutoCAD SHX Text 47k
AutoCAD SHX Text
EOL
AutoCAD SHX Text Resistor
AutoCAD SHX Text 47k
AutoCAD SHX Text
EOL
AutoCAD SHX Text Resistor
AutoCAD SHX Text
UP
AutoCAD SHX Text
DN
AutoCAD SHX Text
DN
AutoCAD SHX Text
DN
| Sheets and Views |
| FI23-013 VA Walla Walla Bldg-76 FA-FA-0.0 (1) |
| FI23-013 VA Walla Walla Bldg-76 FA-FA-1.1 (2) |
File details come from the government source that posted it. Updated .