FI23-013-VA-Walla-Walla-Bldg-82-FA_Record.pdf

PDF 3 MB Posted

Attached to
H212 Fire Alarm Inspections, Testing, Maintenance & Repairs - Walla Walla VA - Dept of Veterans Affairs
Solicitation number
36C26025Q0599
Issued by

About this file

These are fire alarm system replacement drawings for Building 82 at the VA Walla Walla Medical Center, prepared by Vulcan Fire. The project involves replacing the existing campus fire alarm system with a new addressable Notifier system throughout the building, including installation of voice evacuation notification appliances, smoke and heat detectors, manual pull stations, and fire sprinkler system monitoring. The new system will use fiber optic cabling for the backbone infrastructure and will be connected to a campus-wide computer monitoring and control system in Building 78.

The drawings (FA-0.0 and FA-1.1) provide detailed plans for the first and second floors, including device locations, wiring diagrams, and system matrix. Key specifications include a new Fire Alarm Control Panel (FACP), Class B wiring, addressable devices, elevator recall functions, and central station monitoring. The project is designed to comply with 2018 IBC, IFC, NFPA 101, and VA Fire Protection Manual standards, with the building classified as Business (B) and Storage (S-1) occupancy types.

View the file

Other files

File Type Posted
S06 Amendment 36C26025Q0599 0002.pdf PDF
S02 RFQ 36C26025Q0599_1 Rev 7-31-2025.pdf PDF
S06 Amendment 36C26025Q0599 0001.pdf PDF
FI23-013-VA-Walla-Walla-Bldg-135-FA_Record.pdf PDF
FI23-013-VA-Walla-Walla-Bldg-65-FA_Record.pdf PDF
FI23-013-VA-Walla-Walla-Bldg-69-FA_Record.pdf PDF
FI23-013-VA-Walla-Walla-Bldg-140-FA_RECORD.pdf PDF
FI23-013-VA-Walla-Walla-Bldg-143-FA_Record.pdf PDF
FI23-013-VA-Walla-Walla-Bldg-66-FA_Record.pdf PDF
FI23-013-VA-Walla-Walla-Bldg-31-FA_Record.pdf PDF
FI23-013-VA-Walla-Walla-Bldg-49-FA_Record.pdf PDF
FI23-013-VA-Walla-Walla-Bldg-81-FA_Record.pdf PDF
FI23-013-VA-Walla-Walla-Bldg-75-FA_Record.pdf PDF
FI23-013-VA-Walla-Walla-Bldg-T1-and-T2-FA_Record.pdf PDF
FI23-013-VA-Walla-Walla-Bldg-T-7-FA_Record.pdf PDF
FI23-013-VA-Walla-Walla-Bldg-80-FA_Record.pdf PDF
FI23-013-VA-Walla-Walla-Bldg-145-FA_Record.pdf PDF
S02 RFQ 36C26025Q0599_1.pdf PDF
FI23-013-VA-Walla-Walla-Bldg-76-FA.pdf PDF
PP_Questionnaire.pdf PDF
FI23-013-VA-Walla-Walla-Bldg-41-FA_Record.pdf PDF
FI23-013-VA-Walla-Walla-Bldg-74-FA_Record.pdf PDF
FI23-013-VA-Walla-Walla-Bldg-77-FA_Record.pdf PDF
FI23-013-VA-Walla-Walla-Bldg-78-FA_Record.pdf PDF
FI23-013-VA-Walla-Walla-Bldg-48-FA_Record.pdf PDF
FI23-013-VA-Walla-Walla-Bldg-68-_Record.pdf PDF
FI23-013-VA-Walla-Walla-Bldg-63-FA_Record.pdf PDF
Show all 27

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SYSTEM INPUTS

PANEL FUNCTIONS

ALARM DEVICES

SYSTEM RESET

SYSTEM SILENCE

"ALL SYSTEMS NORMAL"

SMOKE DETECTORS

SUPERVISORY DEVICES

TROUBLE FUNCTIONS

ABNORMAL CIRCUIT OR DEVICE

FIRE ALARM SYSTEM AC POWER FAILURE

FIRE ALARM SYSTEM LOW BATTERY

SP

EA

KE

RS

A

ND

S

TR

OB

ES

S

TO

P

YE

LL

OW

LE

D W

IL

L F

LA

SH

A

ND

YE

LL

OW

LE

D W

IL

L F

LA

SH

A

ND

W

IL

L T

UR

N

ON

, U

NT

IL

S

IL

EN

CE

D.

RE

D

LE

D

AN

D

AU

IB

LE

S

OU

ND

ER

HI

ST

OR

Y

LO

G:

SYSTEM OUTPUTS

(S

YN

CH

RO

NI

ZE

D

AN

D

VO

IC

E

EV

AC

TE

MP

OR

AL

P

AT

TE

RN

AC

TI

VA

TE

S

BU

IL

DI

NG

S

IN

TE

RI

OR

N

OT

IF

IC

AT

IO

N

DE

VI

CE

S

REQUIRED FA CONTROLFACP FUNCTION

AC

TU

AT

ES

T

RO

UB

LE

C

ON

DI

TI

ON

A

T

CO

NT

RO

L P

AN

EL

PU

LS

IN

G

SO

UN

DE

R

W

IL

L T

UR

N

ON

, U

NT

IL

A

CK

NO

W

LE

DG

ED

AC

TU

AT

ES

S

UP

ER

VI

SO

RY

C

ON

DI

TI

ON

A

T

CO

NT

RO

L P

AN

EL

GR

EE

N

AC

P

OW

ER

IN

DI

CA

TO

R

IS

LI

T

ST

EA

DI

LY

ON

C

ON

TR

OL

P

AN

EL

CH

AR

AC

TE

R

LC

D

DI

SA

PL

Y

DI

SP

LA

Y

TH

E

CU

ST

OM

M

ES

SA

GE

"A

LL

S

YS

TE

MS

N

OR

MA

L"

AC

TU

AT

ES

A

LA

RM

C

ON

DI

TI

ON

A T

CO

NT

RO

L P

AN

EL

RE

CO

RD

IN

G

OF

T

HE

E

VE

NT

IN

S

YS

TE

MS

M

EM

OR

Y

PU

LS

IN

G

SO

UN

DE

R

W

IL

L T

UR

N

ON

, U

NT

IL

A

CK

NO

W

LE

DG

ED

FI

RE

A

LA

RM

C

ON

TR

OL

P

AN

EL

R

ET

UR

NS

T O

NO

RM

AL

NOTIFICATION

MANUAL PULL STATION

A B C D E F G H I J K L M N O P Q R

* FIRE SPRINKLER SYSTEM - ZONED WATERFLOW SWITCH (LATCHING)

FIRE SPRINKLER SYSTEM - MAIN WATERFLOW SWITCH (LATCHING)

Fire Alarm System Matrix

FIRE SPRINKLER SYSTEM - VALVE TAMPER SWITCH

MICROPHONE ACTIVATION WITH CIRCUIT SELECTION SWITCH

(C

ON

TA

CT

ID

) T

O U.

L.

CL

AS

S

CE

NT

RA

L S

TA

TI

ON

(C

ON

TA

CT

ID

) T

O U.

L.

CL

AS

S

CE

NT

RA

L S

TA

TI

ON

(C

ON

TA

CT

ID

) T

O U.

L.

CL

AS

S

CE

NT

RA

L S

TA

TI

ON

(C

ON

TA

CT

ID

) T

O U.

L.

CL

AS

S

CE

NT

RA

L S

TA

TI

ON

TR

AN

SM

IT

S W

AT

ER

FL

OW

C

ON

DI

TI

ON

V

IA

C

EL

LU

LA

R

CO

MM

UN

IC

AT

OR

TR

AN

SM

IT

S

TR

OU

BL

E

CO

ND

IT

IO

N

VI

A

CE

LL

UL

AR

C

OM

MU

NI

CA

TO

R

TR

AN

SM

IT

S

SU

PE

RV

IS

OR

Y

CO

ND

IT

IO

N

VI

A

CE

LL

UL

AR

C

OM

MU

NI

CA

TO

R

TR

AN

SM

IT

S

AL

AR

M

CO

ND

IT

IO

N

VI

A

CE

LL

UL

AR

C

OM

MU

NI

CA

TO

R

AN

NU

NC

IA

TO

RS

(B

OT

H

SP

EA

KE

RS

A

ND

S

TR

OB

ES

W

IL

L S

TO

P)

NO

TI

FI

CA

TI

ON

A

PP

LI

AN

CE

S

SH

AL

L B E

SI

LE

NC

EA

BL

E

AT

T

HE

FA

CP

O

R

- ELEVATOR LOBBY - (First Floor)

- SPOT TYPE DETECTORS, (All, except as specifically noted below)

- ELEVATOR LOBBY - (Second Floor)

- ELEVATOR MACHINE ROOM (First Floor)

- TOP OF ELEVATOR SHAFT

EL

EV

AT

OR

R

EC

AL

L (

PR

IM

AR

Y)

EL

EV

AT

OR

R

EC

AL

L T

O

SE

CO

ND

FL

OO

R

EL

EV

AT

OR

R

EC

AL

L (

AL

TE

RN

AT

E)

EL

EV

AT

OR

R

EC

AL

L T

O

FI

RS

T

FL

OO

R

AC

TI

VA

TE

E

LE

VA

TO

R

FI

RE

D

EP

AR

TM

EN

T

(F

LA

SH

IN

G) L

IG

HT

AC

TI

VA

TE

E

LE

VA

TO

R

FI

RE

D

EP

AR

TM

EN

T (S

TE

AD

Y) L

IG

HT

PR

IO

R

TO

S

PR

IN

KL

ER

H

EA

D

AC

TI

VA

TI

ON

SH

UT

DO

W

N

PO

W

ER

T O

AF

FE

CT

ED

E

LE

VA

TO

R

S

HEAT DETECTORS

- ELEVATOR MACHINE ROOM (First Floor)

- TOP OF ELEVATOR SHAFT

- BOTTOM OF ELEVATOR SHAFT

ON

YX

W

OR

KS

S

TA

TI

ON

IN

B

UI

LD

IN

G

SE

CU

RI

TY

O

FF

IC

E

TR

AN

SM

IT

S

SY

ST

EM

C

ON

DI

TI

ON

V

IA

FI

BE

R

NE

TW

OR

K

NE

TW

OR

K

AN

NU

NC

IA

TO

R

IN

B

UI

LD

IN

G

P

OL

IC

E

ST

AT

IO

N

TR

AN

SM

IT

S

SY

ST

EM

C

ON

DI

TI

ON

V

IA

FI

BE

R

NE

TW

OR

K

T

Number of Sheets:

By

Installing Fire Alarm System Contractor:

Date

Drawn By:

Drawn Date:

Scale:

Drawing No.

Revisions Description

Authority Having Jurisdiction:

Project Contacts

DHL

05/14/2024

VA

W al la

W al la

B ui ld in g

W ai nw rig ht

D riv e W al la

W al la , W

A

Li fe

S af et y

(F ire

A la rm S ys te m ) D ra w in gs

COPYRIGHT NOTICE

ALL DRAWINGS AND WRITTEN MATERIAL APPEARING HEREIN

CONSTITUTE THE ORIGINAL AND UNPUBLISHED WORK OF

VULCAN FIRE, AND THE SAME MAY NOT BE DUPLICATED, USED

OR DISCLOSED WITHOUT THE EXPRESS WRITTEN CONSENT OF

VULCAN FIRE

Reviewed by:

ENGINEERED SYSTEM DISTRIBUTION

by Honeywell

TM

Vulcan Project #: FI23-013

U .S

.D ep ar tm en t o f V et er an s A ffa irs

Fi re

A la rm S ys te m R ep la ce m en t -

P ha se B

Walla Walla Fire Department 2251 S. Howard St., Walla Walla, WA 99362

(509) 524-4603

Vulcan Fire 112 East Hazel Ave., Ste#1, Coeur d'Alene, ID 83814

(208) 277-0171

GC

L ice ns e:

V

UL

CA

F*

0M

El ec

L ice ns e:

V

UL

CA

F*

W

EB

SI

TE

: w w w

.v ul ca nf ire us

.c om

PH

ON

E

(2

) 2

-0

Ea st H az el

A ve nu e, S ui te

1, C oe ur d 'A le ne

, I da ho

N/A

FA-0.0

Site Plan

General Notes:

Drawing Notes:

Fire Alarm Control Panel Terminations:

Scope of Work:

All wiring runs shown on the fire alarm shop drawings are conceptual only. They do not and are not intended to be actual wire runs or conduit runs. Device interconnect is intended to show only sequence of device connections and type of wire.

Please review both the floor plans and the riser diagram drawings to resolve any conflicts or questions that may come up. If the drawings do not answer your questions, please call Vulcan Fire for help to answer your questions.

Electrical Contractor is advised not to complete terminations at the Fire Alarm Control Panel. Terminations will be completed by a qualified Vulcan Fire Technician.

Code Analysis:

Edition of Codes:

Number of Stories:

Edition of Standards:

Occupancy Type: B, Business (Offices, Work Rooms) S-1 Storage (Storage Closets, Storage Bay)

2018 IBC, IFC, IMC

2018 NFPA 101

City of Walla Walla Amendments 2009 ANSI 117.1 Guidelines for Accessible & Useable

Yes, Fully Fire Sprinklered

1 w/ Unoccupied Basement

Visual Notification: Public Mode

Wire runs are indicated by AlphaNumeric designations.

power run of "2#__ " cable. A designation of "P3" would indicate another individual run of "2#__ " cable.

"2#__Twisted AND a run of 2#__ " cable.

A designation of "A,P2", would refer to a run of

The wire Gauge of any wire run is determined by the

A designation of "P2", would refer to a individual pair, 2#__ Twisted" cable.

A designation of "2A", would refer to a run of "2 length of the wire run and the power load on that run.

A typical wire run designated as "A", would refer to a single run of "2 #__ Twisted" cable.

For example:

A,P2

P2,P3

A

2A

Wire Chart:

Audible Notification: Voice Evac - Temporal 3 Pattern / Synchronized

Type of FA System: New Fire Alarm Addressable System

Index of Drawings Drawing Name

Drawing Number

Cover SheetCover SheetFA-0.0 FA-1.1 First Floor - Fire Alarm Plan / Basement -

Fire Alarm Plan / Riser Diagram / Details / Load Calculations / Speaker Calculations

Temporal Pattern Notification Device Numbering:

(IE: HORN/STROBE)

AUDIBLE/VISUAL DEVICE

(IE: STROBE ONLY)

AUDIBLE DEVICE

(IE: HORN ONLY)

WITH THE REQUIREMENTS FOR VISUAL DEVICES.

1. ADA ACCESSIBILITY GUIDELINES HAVE ACCEPTED NFPA 72 GUIDELINES AS "EQUIVALENT FACILITATION".

3. MEASUREMENT IS TO THE BOTTOM OF THE DEVICE.

2. NFPA 72 STATES THAT COMBINATION AUDIBLE/VISUAL DEVICES SHALL BE MOUNTED IN ACCORDANCE

NOTES:

AFF = ABOVE FINISHED FLOOR0" (FLOOR)

NFPA 72

A

90" A.F.F.

A/V

96" A.F.F.

80" A.F.F.

NFPA 72

MAX.

MIN.

V

VISUAL DEVICE

CEILING

6" BELOW

CEILING

Example of Proper Mounting for Audible/Visual Devices:

Example of Junction Box Detail (FA):

If Applicable (Use for eample only)

Sheet Number

Walla Walla, WA 99362

U.S. Department Of Veterans Affairs VA Medical Center

77 Wainwright Drive

Owner

Fire Protection System:

Square Footage:

FA System Required: Code-Required

Project Manager: Dave Clem

GDM of Oregon 1584 McNeil Street, Suite 200

DuPont, WA 98327

Architect / Engineer

7,663 GSF

Protected Premises Fire Alarm Systems (Wiring):

Mounted Candela Rating:

S150 = 150 Candela S177 = 177 Candela S185 = 185 Candela

S135 = 135 Candela

S115 = 115 Candela S110 = 110 Candela S95 = 95 Candela S75 = 75 Candela S30 = 30 Candela S15 = 15 Candela

Ceiling S15C S15

Wattage Speaker 1W Tap

Guard WireWG WeatherproofWP

VOICE CIRCUIT

V 2

2S

POWER SUPPLY NUMBER

STROBE CIRCUIT

CIRCUIT NUMBER

AMPLIFIER NUMBER

CIRCUIT NUMBER

("T" Tap) Class B

Class B

P

F P

VS VSAIM

Class B

IDC - Initiating Device Circuit Manual Pull Stations, Fire Sprinkler System, Etc.

NAC - Notification Appliance Circuit Horns, Bells, Strobes, Etc.

SLC - Signaling Line Circuit Intelligent (Addressable) Devices

Only in J-Box (per Owner)

FS

S

Where used, End-Of-Line Resistors shall be labeled "EOL" on the Device (per Owner)

Building 82 77 Wainwright Drive, Walla Walla, WA 99362

Fire Alarm System Replacement

The scope of work for this project is to replace the existing campus fire alarm system with a new fire alarm system throughout. The existing copper cabling backbone infrastructure will be replaced with new fiber optic cabling. Each building will be provided with new fire alarm control panels connected to the campus network. A new campus wide computer monitoring and control system will be provided in Building 78.

Existing fire alarm devices such as pull stations, detectors, relay modules, monitor modules, flow and tamper switch interfaces, and associated conduit, boxes and cabling shall be demolished and replaced with new devices.

Building 82 Fire Alarm System:

The new Notifier fire alarm system in Building 82 will be replacing the existing fire alarm system. Voice evacuation notification appliances will be installed throughout the entire building, which will alert the occupants in the event of a fire. The FACP will provide monitoring of the fire sprinkler system. Smoke and Heat Detectors will be installed where required per codes. New manual pull station will be installed at building exits.

The fire sprinkler tamper switches will cause a supervisory signal when activated. These devices will report as a supervisory signal.

The fire alarm system shall be monitored through a central monitoring company of the owners choosing prior to the final inspection.

N

All intelligent and or addressable Fire Alarm Devices must be placed in protected areas with ambient temperature ranging from 32° to 120°. Weatherproof Fire Alarm Devices have temperature rating from -40° to 151° in wet or dry applications.

Do not place smoke detectors within 3 feet of air supply registers and diffusers.

All intelligent devices shall be interconnected as shown on the riser on-line diagram. Each intelligent device is designed with an address. T-Tapping is permitted on SLC Loop (Class "B") only.

Wire runs show interconnected of fire alarm devices only. Wiring does not represent conduit runs.

Electrical Contractor is responsible for proper connection of equipment provided by others.

(RL) Indicates Existing Device to be relocated to new location.

(R) Indicates Device to be removed and returned to Owner.

(E) Indicates Device existing to remain (shown in gray scale).

(N) Indicates New Device.

(RR) Indicates Remove Existing Device and replace with new Device. Return any removed equipment to Owner.

Typical Device Mounting Height:

NFPA 2016

Wall Mounted AUDIBLE device.

Top of Individual Device

MAX

4'-0"

"ADA"

(48")

Top of Device of the Same Lens

Top of Unit

Top of Cabinet

To Handle of Device Per NFPA 72 from (AFF) Above All heights measured

NOT TO SCALE

Finished Floor

BOTTOM

OF

6'-0"

80" TO

MIN* (72")

LENS

See Note #5

7'-0"

TO TOP

OF

Approx.96"

MAX*

(84")LENS

(6")

THAN

BELOW

CEILING

(90")

AND

LESS

THAN

NOT

LESS

NOT

(64") 5'-4" or 80" MIN. to Bottom A/V or Visual Only Devices

MAX 96" to Top of Lens for all

#1) HEIGHTS SHOWN ARE LISTED IN NFPA STANDARDS 2016.

#2) MOUNTING HEIGHTS LISTED IN SPECIFICATIONS OR SHOWN ON THE

ARCHITECTURAL ELEVATIONS SHALL GOVERN. ANY DISCREPANCY SHALL BE

BROUGHT TO THE ATTENTION OF THE AHJ AND THE ENGINEER OF RECORD.

#3) WALL MOUNTED ADA STROBES & HORN/STROBES ARE TO BE PLACED

A MINIMUM OF 80" ABOVE FINISHED FLOOR MEASURED AT THE BOTTOM OF

THE LENS OR 6" BELOW THE CEILING TO THE TOP OF THE LENS,

WHICHEVER IS LOWEST. THE MAXIMUM HEIGHT MEASURED AT THE TOP OF

THE LENS SHALL NOT EXCEED 96".

#4) IN SLEEPING ROOMS A STROBE MOUNTED LESS THAN 24" FROM THE

CEILING SHALL BE AT LEAST 177CD. STROBES MOUNTED 24" OR BELOW

SHALL BE AT LEAST 110 CD. A STROBE SHALL BE MOUNTED WITHIN 16FT

OF THE PILLOW.

#5) REMOTE LIGHTS, TEST STATIONS AND MODULES SHOULD BE MOUNTED

SO AS TO BE ACCESSIBLE, YET ABOVE EASY REACH TO PREVENT

VANDALISM.

#6) CEILING MOUNT VISIBLE DEVICES SHALL BE SPACED ACCORDING TO

2016 NFPA 72.

FSA

FACFACP RPS

AIM AOM

F

RL

S15H15 15MC15

RT

J DM

MAP FTR

C

AOM

R

S

(48") 4'-0"

*MAX

(42") 3'-6"

*MIN

U.S. Department of Veterans Affairs

VA WALLA WALLA - FIRE LIFE SAFETY - PHASE B Fire Alarm Systems Interconnect Drawings

X

X X

X X

X

X

X

X

XX X

X

X

X

X

X

X

STATE NURSING HOME

STATE NURSING HOME

STATE NURSING HOME

STATE NURSING HOME

N U

R

SIN

G H

O M

E

FU

TU

R E

BL

D

G

7 49 48

66T-7

77T-1

T-2

756968

116119

121126125124

109CM

147 146

W

SITE

Setting Initiating Device Addresses:

D:L1: 501

ONESTENS

7 8 9

00 15

D = Detector M = Monitor

Device AddressData Loop Number

DIALS ARE

LOCATED ON THE

BACK OF EACH

DEVICE

N1:

Node Number

2016 NFPA 72, 2020 NFPA 70 (NEC), VA Fire Protection Manual

FSA

MAP

BATT

S P

FACP

EVAC

F

AIM

VS

WF

SS

FARC

Indicates Circuit Continuation Indicates Home Run to FACP

S15C

S15

S95

R

FATC

F135° S

C

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text PRV Vault

AutoCAD SHX Text F/A

AutoCAD SHX Text 8"

AutoCAD SHX Text Caps

AutoCAD SHX Text Tank

AutoCAD SHX Text Fuel

AutoCAD SHX Text F/A

AutoCAD SHX Text Valves

AutoCAD SHX Text

PRV

AutoCAD SHX Text F/A

General Note:

* All addressable devices require SLC Loop (A-wire) from the FACP to operate. For help, please refer to riser diagram for reference.

* Do not route conduit into the bottom of any fire alarm system component cabinets.

* After each duct smoke detector has been installed use a Megnehelic

Test Instrument to verify adequate air flow, show the results on the Shop Drawings for the AHJ's review.

* Tap all speakers at 1/2 watt - 25 volts unless otherwise indicated at individual device.

* Contractor may reuse existing pathways where available. Verify with system designer prior to adding additional devices or extending circuits to ensure voltage drop calculations are within acceptable limits.

1) Section of NFPA 72, National Fire Alarm Code requires units to be provided with smoke detection in areas that are not continuously occupied.

2) Provide Dedicated 120VAC circuit to the FACP label the Dedicated circuit breaker "Fire Alarm." In red with lockout. Location of breaker shall be noted at FACP.

3) Fiber Network routing to be field coordinated.

4) Detector is to activate Elevator Recall Functions.

5) Detector is to activate Elevator Shunt Trip. Mount within 24" of Sprinkler

Head.

6) Visual Notification omitted in areas without existing devices or ADA requirements to comply with VA Fire Protection Manual Section 7.3.F.l.4.

Field verify single person offices with hearing-impaired occupants.

Flag Notes: (Some flag notes may not appear on every sheet)

Addressing Legend:

D = Detector M = Module

Module/Device Number M01L01

Loop Number N01Node Number

C1W

Dedicated

120VAC

SS

FACP FARC

MAP

GUTTER

CPU2-640

HS-NCM-MF

NCA-2

DVC / CMIC-1

DAA2-7525

EVAC

BATT

Battery Battery

Addressable Pull Station

321(-)

A ANBG-12LX

B300-6

From

Device SLC Loop previous

Device SLC Loop To next

A

A

Addressable Smoke or Heat Detector

RA

P F F

S15 2W S95

4.7k

20k

Speaker/Strobe

Speaker

Strobe

VV

S S

Strobe

Strobe

S_ S_

S15

1W S15C 30 15 15 15

4.7k

20k

First Floor

P

Elevator Controls (Field Verify Location)

120VAC Shunt Trip Power Source

Primary Recall (Steady) Alternate Recall (Steady)

Shunt Trip Breaker

Fire Light Indicator (Flashing)

R

FATCXP6-R

Sp ar e Sp ar e

47k

R

F135° H

PP

AIM

S

Backflow Preventer

VS

47k

Main - Fire Sprinkler System

WF 47k

VS

Main

WF

VS

VS

47k

47k

47k

AIM

AIM

AIM

AIM

AIM

WF

VS

47k

47k

AIM

AIM

WF

VS

47k

47k

AIM

AIM

T1

T2

T4 T5

LOOP

T6 T7 T8

T9 T10

ADDRESS

T3

T11

FMM-1

Fire Sprinkler Valve Tamper

D 0 15 14

6 7 8 9 9876

1 0

TENS ONES

A

A

Fire Sprinkler System - Valve Tamper with FMM-1 Monitor Module

T1

T2

T4 T5

LOOP

T6 T7 T8

T9 T10

ADDRESS

T3

T11

FMM-1

Fire Sprinkler Valve Tamper

D 0 15 14

6 7 8 9 9876

1 0

TENS ONES

A

A

Fire Sprinkler System - Valve Tamper with FMM-1 Monitor Module

Second Floor Second Floor

F135° H

F135°

HF

To Fiber Network Bldg. 41

To Fiber Network Bldg. 66 FSA

MAP

F

2W S95

1W S15

S15 1W

S15C 15

First Floor

S15

P S S

SS

S

EP

Strobe S0-1

Speaker V0-1 V

S

V S

A

S V

Strobe S0-2

Speaker V0-2 V

S

A

SL

C

Lo op

A

A

D

A

A

D

DD

D

D

D

D

D

D

D

A

A

F

F

2AD,AP

A

S15

Dedicated

120VAC

SS

FARC

MAP

To Bldg. Devices (SLC Loop)

CPU2-640

HS-NCM-MF

NCA-2

DVC / CMIC-1

DAA2-7525 FACP

Spkr Crkts V0-1, V0-2, V0-3, V0-4BATT

NAC Crkts S0-1, S0-2, S0-3, S0-4, To Fiber Network Patch Panel

Components located inside of

FACP

EVAC

P N52:L1:D001

F N52:L1:M001

VS

Main - Fire Sprinkler System

WF

N52:L1:M011

N52:L1:M012

VS

AIM

AIMField Verify Fire Sprinkler Connections

AIM

AIM

AIM

N52:L1:M013

N52:L1:M014

N52:L1:M015

WF

VS

VS

PF135°

Elevator #1 Control

120VAC Shunt Trip Power Source

Primary Recall (Steady) Alternate Recall (Steady)

Shunt Trip Breaker

Fire Light Indicator (Flashing)

R

FATCXP6-R

Sp ar e Sp ar e

47k

R

N5 2:

L1 :M

N5 2:

L1 :M

N5 2:

L1 :M

N5 2:

L1 :M

N5 2:

L1 :M

N52:L1:M031

N5 2:

L1 :M

Elevator Controls (Field Verify Location)

N52:L1:D010 N52:L1:D011

AIM

WF

N52:L1:M016

AIM

AIM

AIM

N52:L1:M018

N52:L1:M019

WF

VS

AIM

N52:L1:M017

VS

F

F135°

N52:L1:D011

H

N52:L1:M002

N52:L1:M003

F

N52:L1:M004

S95 2W

S95 2W

WORK

BAY

STORAGE

BAY

STORAGE

RESTROOM

STORAGE

C1-1

C1-2

ELEV.

EQUIP.

STORAGE

S15 1W

To FACPFSAS15

To 2nd Floor

S0-1 V0-1

S0-1 V0-1

S0-1 V0-1

S0-1 V0-1

S0-1 V0-1

S0-1

S15 S0-1 V0-1

P

N52:L1:D003

To 2nd Floor

S

S S

EP

A 2F

Backflow Preventer

D

DD

D

D

D

D

D

D

D

D

2AD,AP

S,V

S,V

S,V

S,V

S,V

AD,AP

F

S,V

J J J J J

J

J

J

MAP

S,V

S,V S,V S,V S,V

AD,AP

AD,AP

A

A

A A

A

A

A

A

A

A

F

HAD,AP

AA

P N52:L1:D002

S15C 1W

S0-2 V0-2

S15C 1W

S0-2 V0-2

C1W

6 6 6 6

HSKP

212B

MEN'S

RESTROOM

WOMEN'S

RESTROOM

111A

OFFICE

BREAK

ROOM

207A

OFFICE

208 207 206

C2-2

STORAGE

205A

OFFICE

OFFICE

202 OFFICE

STOR.

212A

HSKP

211B

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

S15S0-2 V0-2

S

S0-2

V0-2

S0-2

S0-2 S0-2

P

F135°

N52:L1:D012

N52:L1:D013

H

15C

15C

S0-2

30C

S0-2

15C

S

S,V

S,V

S,V S,V

S,VS,V

S,V S,V

J J

J J J J

J J

J J J

To 1st Floor

S

A A

Number of Sheets:

By

Installing Fire Alarm System Contractor:

Date

Drawn By:

Drawn Date:

Scale:

Drawing No.

Revisions Description

Authority Having Jurisdiction:

Project Contacts

DHL

05/14/2024

VA

W al la

W al la

B ui ld in g

W ai nw rig ht

D riv e W al la

W al la , W

A

Li fe

S af et y

(F ire

A la rm S ys te m ) D ra w in gs

COPYRIGHT NOTICE

ALL DRAWINGS AND WRITTEN MATERIAL APPEARING HEREIN

CONSTITUTE THE ORIGINAL AND UNPUBLISHED WORK OF

VULCAN FIRE, AND THE SAME MAY NOT BE DUPLICATED, USED

OR DISCLOSED WITHOUT THE EXPRESS WRITTEN CONSENT OF

VULCAN FIRE

Reviewed by:

ENGINEERED SYSTEM DISTRIBUTION

by Honeywell

TM

Vulcan Project #: FI23-013

U .S

.D ep ar tm en t o f V et er an s A ffa irs

Fi re

A la rm S ys te m R ep la ce m en t -

P ha se B

Walla Walla Fire Department 2251 S. Howard St., Walla Walla, WA 99362

(509) 524-4603

Vulcan Fire 112 East Hazel Ave., Ste#1, Coeur d'Alene, ID 83814

(208) 277-0171

GC

L ice ns e:

V

UL

CA

F*

0M

El ec

L ice ns e:

V

UL

CA

F*

W

EB

SI

TE

: w w w

.v ul ca nf ire us

.c om

PH

ON

E

(2

) 2

-0

Ea st H az el

A ve nu e, S ui te

1, C oe ur d 'A le ne

, I da ho

1/8" = 1'-0"

FA-1.1

Riser Diagram / Details - Fire Alarm System

VOLTAGE DROPS ARE CALCULATED AT 16VDC.

L= ONE WAY LENGTH OF CIRCUIT(FEET)

WHERE VD= VOLTAGE DROP

R= 3.19 OHMS PER THOUSAND

I= LOAD CURRENT(AMPERES)

AFTER DETERMINING THE LENGTH OF THE HORN/STROBE CIRCUIT, USE

THE FOLLOWING FORMULA TO CALCULATE THE VOLTAGE DROP.

2xLxRxIVD=

LUMP SUM METHOD WAS USED TO CALCULATE ALLOWABLE VOLTAGE DROP. THIS METHOD

ALLOWS FOR A SMALL MARGIN OF SAFETY, TAKING INTO CONSIDERATION THE ACTUAL

CIRCUIT ROUTING MAY DIFFER FROM WHAT IS SHOWN ON THE SHOP SUBMITTAL

DRAWINGS. IF ACTUAL CIRCUIT LENGTH IS GOING TO EXCEED THE MAXIMUM ALLOWABLE

CIRCUIT LENGTH, CONTACT VULCAN FIRE.

VOLTAGE-DROP CALCULATION NOTE:

** STARTING VOLTAGE-DROP CALCULATIONS IS 20.4 PER UL 864, 9TH EDITION STANDARDS FOR FIRE ALARM

CONTROL PANELS.

Scale: 1/8'' = 1'-0''

20 4 8 16 32

First Floor - Fire Alarm System Plan

Scale: 1/8'' = 1'-0''

20 4 8 16 32

Second Floor - Fire Alarm System Plan

AutoCAD SHX Text 47k

AutoCAD SHX Text

EOL

AutoCAD SHX Text Resistor

AutoCAD SHX Text 47k

AutoCAD SHX Text

EOL

AutoCAD SHX Text Resistor

Sheets and Views
FI23-013 VA Walla Walla Bldg-82 FA_Record-FA-0.0 (1)
FI23-013 VA Walla Walla Bldg-82 FA_Record-FA-1.1 (2)

File details come from the government source that posted it. Updated .