FI23-013-VA-Walla-Walla-Bldg-49-FA_Record.pdf

PDF 3 MB Posted

Attached to
H212 Fire Alarm Inspections, Testing, Maintenance & Repairs - Walla Walla VA - Dept of Veterans Affairs
Solicitation number
36C26025Q0599
Issued by

About this file

These are record drawings for a fire alarm system replacement project at the VA Walla Walla Medical Center, specifically for Building 49. The project involves replacing the existing campus fire alarm system with a new Notifier addressable fire alarm system, including new fiber optic cabling infrastructure, fire alarm control panels, and campus-wide monitoring capabilities. The system will include voice evacuation notification appliances, HVAC unit control, elevator recall functions, sprinkler system monitoring, smoke and heat detectors, manual pull stations, and central station monitoring. The drawings detail the fire alarm system components for the building's basement, first floor, and second floor, with specific device placement, wiring diagrams, and technical specifications for a comprehensive fire safety upgrade.

View the file

Other files

File Type Posted
S06 Amendment 36C26025Q0599 0002.pdf PDF
S02 RFQ 36C26025Q0599_1 Rev 7-31-2025.pdf PDF
S06 Amendment 36C26025Q0599 0001.pdf PDF
FI23-013-VA-Walla-Walla-Bldg-135-FA_Record.pdf PDF
FI23-013-VA-Walla-Walla-Bldg-65-FA_Record.pdf PDF
FI23-013-VA-Walla-Walla-Bldg-69-FA_Record.pdf PDF
FI23-013-VA-Walla-Walla-Bldg-140-FA_RECORD.pdf PDF
FI23-013-VA-Walla-Walla-Bldg-143-FA_Record.pdf PDF
FI23-013-VA-Walla-Walla-Bldg-66-FA_Record.pdf PDF
FI23-013-VA-Walla-Walla-Bldg-31-FA_Record.pdf PDF
FI23-013-VA-Walla-Walla-Bldg-82-FA_Record.pdf PDF
FI23-013-VA-Walla-Walla-Bldg-81-FA_Record.pdf PDF
FI23-013-VA-Walla-Walla-Bldg-75-FA_Record.pdf PDF
FI23-013-VA-Walla-Walla-Bldg-T1-and-T2-FA_Record.pdf PDF
FI23-013-VA-Walla-Walla-Bldg-T-7-FA_Record.pdf PDF
FI23-013-VA-Walla-Walla-Bldg-80-FA_Record.pdf PDF
FI23-013-VA-Walla-Walla-Bldg-145-FA_Record.pdf PDF
S02 RFQ 36C26025Q0599_1.pdf PDF
FI23-013-VA-Walla-Walla-Bldg-76-FA.pdf PDF
PP_Questionnaire.pdf PDF
FI23-013-VA-Walla-Walla-Bldg-41-FA_Record.pdf PDF
FI23-013-VA-Walla-Walla-Bldg-74-FA_Record.pdf PDF
FI23-013-VA-Walla-Walla-Bldg-77-FA_Record.pdf PDF
FI23-013-VA-Walla-Walla-Bldg-78-FA_Record.pdf PDF
FI23-013-VA-Walla-Walla-Bldg-48-FA_Record.pdf PDF
FI23-013-VA-Walla-Walla-Bldg-68-_Record.pdf PDF
FI23-013-VA-Walla-Walla-Bldg-63-FA_Record.pdf PDF
Show all 27

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SYSTEM INPUTS

PANEL FUNCTIONS

ALARM DEVICES

SYSTEM RESET

SYSTEM SILENCE

"ALL SYSTEMS NORMAL"

SMOKE DETECTORS

SUPERVISORY DEVICES

TROUBLE FUNCTIONS

ABNORMAL CIRCUIT OR DEVICE

FIRE ALARM SYSTEM AC POWER FAILURE

FIRE ALARM SYSTEM LOW BATTERY

SP

EA

KE

RS

A

ND

S

TR

OB

ES

S

TO

P

YE

LL

OW

LE

D W

IL

L F

LA

SH

A

ND

YE

LL

OW

LE

D W

IL

L F

LA

SH

A

ND

W

IL

L T

UR

N

ON

, U

NT

IL

S

IL

EN

CE

D.

RE

D

LE

D

AN

D

AU

IB

LE

S

OU

ND

ER

HI

ST

OR

Y

LO

G:

SYSTEM OUTPUTS

(S

YN

CH

RO

NI

ZE

D

AN

D

VO

IC

E

EV

AC

TE

MP

OR

AL

P

AT

TE

RN

AC

TI

VA

TE

S

BU

IL

DI

NG

S

IN

TE

RI

OR

N

OT

IF

IC

AT

IO

N

DE

VI

CE

S

REQUIRED FA CONTROLFACP FUNCTION

AC

TU

AT

ES

T

RO

UB

LE

C

ON

DI

TI

ON

A

T

CO

NT

RO

L P

AN

EL

PU

LS

IN

G

SO

UN

DE

R

W

IL

L T

UR

N

ON

, U

NT

IL

A

CK

NO

W

LE

DG

ED

AC

TU

AT

ES

S

UP

ER

VI

SO

RY

C

ON

DI

TI

ON

A

T

CO

NT

RO

L P

AN

EL

GR

EE

N

AC

P

OW

ER

IN

DI

CA

TO

R

IS

LI

T

ST

EA

DI

LY

ON

C

ON

TR

OL

P

AN

EL

CH

AR

AC

TE

R

LC

D

DI

SA

PL

Y

DI

SP

LA

Y

TH

E

CU

ST

OM

M

ES

SA

GE

"A

LL

S

YS

TE

MS

N

OR

MA

L"

AC

TU

AT

ES

A

LA

RM

C

ON

DI

TI

ON

A T

CO

NT

RO

L P

AN

EL

RE

CO

RD

IN

G

OF

T

HE

E

VE

NT

IN

S

YS

TE

MS

M

EM

OR

Y

PU

LS

IN

G

SO

UN

DE

R

W

IL

L T

UR

N

ON

, U

NT

IL

A

CK

NO

W

LE

DG

ED

FI

RE

A

LA

RM

C

ON

TR

OL

P

AN

EL

R

ET

UR

NS

T O

NO

RM

AL

NOTIFICATION

MANUAL PULL STATION

SH

UT

D

OW

N

OF

R

ES

PE

CT

IV

E

HV

AC

U

NI

T

A B C D E F G H I J K L M N O P Q R

* FIRE SPRINKLER SYSTEM - ZONED WATERFLOW SWITCH (LATCHING)

FIRE SPRINKLER SYSTEM - MAIN WATERFLOW SWITCH (LATCHING)

Fire Alarm System Matrix

FIRE SPRINKLER SYSTEM - VALVE TAMPER SWITCH

MICROPHONE ACTIVATION WITH CIRCUIT SELECTION SWITCH

(C

ON

TA

CT

ID

) T

O U.

L.

CL

AS

S

CE

NT

RA

L S

TA

TI

ON

(C

ON

TA

CT

ID

) T

O U.

L.

CL

AS

S

CE

NT

RA

L S

TA

TI

ON

(C

ON

TA

CT

ID

) T

O U.

L.

CL

AS

S

CE

NT

RA

L S

TA

TI

ON

(C

ON

TA

CT

ID

) T

O U.

L.

CL

AS

S

CE

NT

RA

L S

TA

TI

ON

TR

AN

SM

IT

S W

AT

ER

FL

OW

C

ON

DI

TI

ON

V

IA

C

EL

LU

LA

R

CO

MM

UN

IC

AT

OR

TR

AN

SM

IT

S

TR

OU

BL

E

CO

ND

IT

IO

N

VI

A

CE

LL

UL

AR

C

OM

MU

NI

CA

TO

R

TR

AN

SM

IT

S

SU

PE

RV

IS

OR

Y

CO

ND

IT

IO

N

VI

A

CE

LL

UL

AR

C

OM

MU

NI

CA

TO

R

TR

AN

SM

IT

S

AL

AR

M

CO

ND

IT

IO

N

VI

A

CE

LL

UL

AR

C

OM

MU

NI

CA

TO

R

AN

NU

NC

IA

TO

RS

(B

OT

H

SP

EA

KE

RS

A

ND

S

TR

OB

ES

W

IL

L S

TO

P)

NO

TI

FI

CA

TI

ON

A

PP

LI

AN

CE

S

SH

AL

L B E

SI

LE

NC

EA

BL

E

AT

T

HE

FA

CP

O

R

DUCT (SMOKE) DETECTOR (Associated with AHU)

- ELEVATOR LOBBY - (First Floor)

- SPOT TYPE DETECTORS, (All, except as specifically noted below)

- ELEVATOR LOBBY - (Second Floor)

- ELEVATOR MACHINE ROOM (First Floor)

EL

EV

AT

OR

R

EC

AL

L (

PR

IM

AR

Y)

EL

EV

AT

OR

R

EC

AL

L T

O

SE

CO

ND

FL

OO

R

EL

EV

AT

OR

R

EC

AL

L (

AL

TE

RN

AT

E)

EL

EV

AT

OR

R

EC

AL

L T

O

FI

RS

T

FL

OO

R

AC

TI

VA

TE

E

LE

VA

TO

R

FI

RE

D

EP

AR

TM

EN

T

(F

LA

SH

IN

G) L

IG

HT

AC

TI

VA

TE

E

LE

VA

TO

R

FI

RE

D

EP

AR

TM

EN

T (S

TE

AD

Y) L

IG

HT

PR

IO

R

TO

S

PR

IN

KL

ER

H

EA

D

AC

TI

VA

TI

ON

SH

UT

DO

W

N

PO

W

ER

T O

AF

FE

CT

ED

E

LE

VA

TO

R

S

HEAT DETECTORS

- ELEVATOR MACHINE ROOM (First Floor)

- TOP OF ELEVATOR SHAFT

ON

YX

W

OR

KS

S

TA

TI

ON

IN

B

UI

LD

IN

G

SE

CU

RI

TY

O

FF

IC

E

TR

AN

SM

IT

S

SY

ST

EM

C

ON

DI

TI

ON

V

IA

FI

BE

R

NE

TW

OR

K

NE

TW

OR

K

AN

NU

NC

IA

TO

R

IN

B

UI

LD

IN

G

P

OL

IC

E

ST

AT

IO

N

TR

AN

SM

IT

S

SY

ST

EM

C

ON

DI

TI

ON

V

IA

FI

BE

R

NE

TW

OR

K

T U

Number of Sheets:

By

Installing Fire Alarm System Contractor:

Date

Drawn By:

Drawn Date:

Scale:

Drawing No.

Revisions Description

Authority Having Jurisdiction:

Project Contacts

DHL

03/19/2024

VA

W al la

W al la

B ui ld in g

W ai nw rig ht

D riv e W al la

W al la , W

A

Li fe

S af et y

(F ire

A la rm S ys te m ) D ra w in gs

COPYRIGHT NOTICE

ALL DRAWINGS AND WRITTEN MATERIAL APPEARING HEREIN

CONSTITUTE THE ORIGINAL AND UNPUBLISHED WORK OF

VULCAN FIRE, AND THE SAME MAY NOT BE DUPLICATED, USED

OR DISCLOSED WITHOUT THE EXPRESS WRITTEN CONSENT OF

VULCAN FIRE

ENGINEERED SYSTEM DISTRIBUTION

by Honeywell

TM

Vulcan Project #: FI23-013

U .S

.D ep ar tm en t o f V et er an s A ffa irs

Fi re

A la rm S ys te m R ep la ce m en t -

P ha se B

Walla Walla Fire Department 2251 S. Howard St., Walla Walla, WA 99362

(509) 524-4603

Vulcan Fire 112 East Hazel Ave., Ste#1, Coeur d'Alene, ID 83814

(208) 277-0171

GC

L ice ns e:

V

UL

CA

F*

0M

El ec

L ice ns e:

V

UL

CA

F*

W

EB

SI

TE

: w w w

.v ul ca nf ire us

.c om

PH

ON

E

(2

) 2

-0

Ea st H az el

A ve nu e, S ui te

1, C oe ur d 'A le ne

, I da ho

Record Drawings (11/01/2024)

N/A

FA-0.0

Site Plan

General Notes:

Drawing Notes:

Fire Alarm Control Panel Terminations:

All wiring runs shown on the fire alarm shop drawings are conceptual only. They do not and are not intended to be actual wire runs or conduit runs. Device interconnect is intended to show only sequence of device connections and type of wire.

Please review both the floor plans and the riser diagram drawings to resolve any conflicts or questions that may come up. If the drawings do not answer your questions, please call Vulcan Fire for help to answer your questions.

Electrical Contractor is advised not to complete terminations at the Fire Alarm Control Panel. Terminations will be completed by a qualified Vulcan Fire Technician.

Code Analysis:

Edition of Codes:

Number of Stories:

Edition of Standards:

Occupancy Type: B, Business (Clinic, Exam, Offices) S-1 Storage (Storage Closets)

2018 IBC, IFC, IMC

2018 NFPA 101

City of Walla Walla Amendments 2009 ANSI 117.1 Guidelines for Accessible & Useable

Yes, Fully Fire Sprinklered

Visual Notification: Public Mode

Wire runs are indicated by AlphaNumeric designations.

power run of "2#__ " cable. A designation of "P3" would indicate another individual run of "2#__ " cable.

"2#__Twisted AND a run of 2#__ " cable.

A designation of "A,P2", would refer to a run of

The wire Gauge of any wire run is determined by the

A designation of "P2", would refer to a individual pair, 2#__ Twisted" cable.

A designation of "2A", would refer to a run of "2 length of the wire run and the power load on that run.

A typical wire run designated as "A", would refer to a single run of "2 #__ Twisted" cable.

For example:

A,P2

P2,P3

A

2A

Wire Chart:

Audible Notification: Voice Evac - Temporal 3 Pattern / Synchronized

Type of FA System: New Fire Alarm Addressable System

Temporal Pattern Notification Device Numbering:

(IE: HORN/STROBE)

AUDIBLE/VISUAL DEVICE

(IE: STROBE ONLY)

AUDIBLE DEVICE

(IE: HORN ONLY)

WITH THE REQUIREMENTS FOR VISUAL DEVICES.

1. ADA ACCESSIBILITY GUIDELINES HAVE ACCEPTED NFPA 72 GUIDELINES AS "EQUIVALENT FACILITATION".

3. MEASUREMENT IS TO THE BOTTOM OF THE DEVICE.

2. NFPA 72 STATES THAT COMBINATION AUDIBLE/VISUAL DEVICES SHALL BE MOUNTED IN ACCORDANCE

NOTES:

AFF = ABOVE FINISHED FLOOR0" (FLOOR)

NFPA 72

A

90" A.F.F.

A/V

96" A.F.F.

80" A.F.F.

NFPA 72

MAX.

MIN.

V

VISUAL DEVICE

CEILING

6" BELOW

CEILING

Example of Proper Mounting for Audible/Visual Devices:

Fire Protection System:

Square Footage:

FA System Required: Code-Required

3,245 GSF

Protected Premises Fire Alarm Systems (Wiring):

Mounted Candela Rating:

S150 = 150 Candela S177 = 177 Candela S185 = 185 Candela

S135 = 135 Candela

S115 = 115 Candela S110 = 110 Candela S95 = 95 Candela S75 = 75 Candela S30 = 30 Candela S15 = 15 Candela

Ceiling S15C S15

Wattage Speaker 1W Tap

Guard WireWG WeatherproofWP

VOICE CIRCUIT

V 2

2S

POWER SUPPLY NUMBER

STROBE CIRCUIT

CIRCUIT NUMBER

AMPLIFIER NUMBER

CIRCUIT NUMBER

("T" Tap) Class B

Class B

P

F P

VS VSAIM

Class B

IDC - Initiating Device Circuit Manual Pull Stations, Fire Sprinkler System, Etc.

NAC - Notification Appliance Circuit Horns, Bells, Strobes, Etc.

SLC - Signaling Line Circuit Intelligent (Addressable) Devices

Only in J-Box (per Owner)

FS

S

Where used, End-Of-Line Resistors shall be labeled "EOL" on the Device (per Owner)

Building 49 77 Wainwright Drive, Walla Walla, WA 99362

Fire Alarm System Replacement

N

All intelligent and or addressable Fire Alarm Devices must be placed in protected areas with ambient temperature ranging from 32° to 120°. Weatherproof Fire Alarm Devices have temperature rating from -40° to 151° in wet or dry applications.

Do not place smoke detectors within 3 feet of air supply registers and diffusers.

All intelligent devices shall be interconnected as shown on the riser on-line diagram. Each intelligent device is designed with an address. T-Tapping is permitted on SLC Loop (Class "B") only.

Wire runs show interconnected of fire alarm devices only. Wiring does not represent conduit runs.

Electrical Contractor is responsible for proper connection of equipment provided by others.

(RL) Indicates Existing Device to be relocated to new location.

(R) Indicates Device to be removed and returned to Owner.

(E) Indicates Device existing to remain (shown in gray scale).

(N) Indicates New Device.

(RR) Indicates Remove Existing Device and replace with new Device. Return any removed equipment to Owner.

Typical Device Mounting Height:

NFPA 2016

Wall Mounted AUDIBLE device.

Top of Individual Device

MAX

4'-0"

"ADA"

(48")

Top of Device of the Same Lens

Top of Unit

Top of Cabinet

To Handle of Device Per NFPA 72 from (AFF) Above All heights measured

NOT TO SCALE

Finished Floor

BOTTOM

OF

6'-0"

80" TO

MIN* (72")

LENS

See Note #5

7'-0"

TO TOP

OF

Approx.96"

MAX*

(84")LENS

(6")

THAN

BELOW

CEILING

(90")

AND

LESS

THAN

NOT

LESS

NOT

(64") 5'-4" or 80" MIN. to Bottom A/V or Visual Only Devices

MAX 96" to Top of Lens for all

#1) HEIGHTS SHOWN ARE LISTED IN NFPA STANDARDS 2016.

#2) MOUNTING HEIGHTS LISTED IN SPECIFICATIONS OR SHOWN ON THE

ARCHITECTURAL ELEVATIONS SHALL GOVERN. ANY DISCREPANCY SHALL BE

BROUGHT TO THE ATTENTION OF THE AHJ AND THE ENGINEER OF RECORD.

#3) WALL MOUNTED ADA STROBES & HORN/STROBES ARE TO BE PLACED

A MINIMUM OF 80" ABOVE FINISHED FLOOR MEASURED AT THE BOTTOM OF

THE LENS OR 6" BELOW THE CEILING TO THE TOP OF THE LENS,

WHICHEVER IS LOWEST. THE MAXIMUM HEIGHT MEASURED AT THE TOP OF

THE LENS SHALL NOT EXCEED 96".

#4) IN SLEEPING ROOMS A STROBE MOUNTED LESS THAN 24" FROM THE

CEILING SHALL BE AT LEAST 177CD. STROBES MOUNTED 24" OR BELOW

SHALL BE AT LEAST 110 CD. A STROBE SHALL BE MOUNTED WITHIN 16FT

OF THE PILLOW.

#5) REMOTE LIGHTS, TEST STATIONS AND MODULES SHOULD BE MOUNTED

SO AS TO BE ACCESSIBLE, YET ABOVE EASY REACH TO PREVENT

VANDALISM.

#6) CEILING MOUNT VISIBLE DEVICES SHALL BE SPACED ACCORDING TO

2016 NFPA 72.

FSA

FACFACP RPS

AIM AOM

F

RL

S15H15 15MC15

RT

J DM

MAP FTR

C

AOM

R

S

(48") 4'-0"

*MAX

(42") 3'-6"

*MIN

Obstructions or other Bends, 3 Feet x 6 = 18 Feet Duct Width = 3 Feet Example:

as far as possible Widths Maximum, or Minimum, 10 Duct Six Duct Widths

Inlet Return Air

Duct Smoke Detector Placement

Width

Width

The recommended location of Smoke Detectors mounted in or Duct Smoke Detectors mounted on air ducts should be between six duct widths and ten duct widths up stream from any duct openings, deflection plates, sharp bends, or branch connections. Refer to NFPA 72, 90A, 92A, OR 92B for further guidelines.

Duct Detectors shall be located:

A. At the Return Air Duct Side of AHU's above 2,000 CFM

Openings, as far as possible Widths Maximum, or Minimum, 10 Duct Six Duct Widths

Up to 1 ft.

Width

Outside Duct Recommended * Sampling Tube for different duct widths:

Sampling Tubes recommended

DST1

2/3 the duct width

* Must extend a minimum of

2 to 4 ft. DST3 4 to 8 ft. DST5 8 to 12 ft. DST10

1 to 2 ft. DST1.5

12" 1/4"

Detector

Duct

Sampling Tube 2"

The Sampling Tube should be angled at least 1/4" down for every 12" of duct width.

3/4" Hole

DST5

Sampling Tube Part Number

DST5

Downstream from Sampling Tube Exhaust Tube must be Mounted

Air Flow

Air Flow

Holes must Face into Air Flow

Detector

Detector

U.S. Department of Veterans Affairs

VA WALLA WALLA - FIRE LIFE SAFETY - PHASE B Fire Alarm Systems Interconnect Drawings

Setting Initiating Device Addresses:

D:L1: 501

ONESTENS

7 8 9

00 15

D = Detector M = Monitor

Device AddressData Loop Number

DIALS ARE

LOCATED ON THE

BACK OF EACH

DEVICE

N1:

Node Number

X

X X

X X

X

X

X

X

XX X

X

X

X

X

X

X

STATE NURSING HOME

STATE NURSING HOME

STATE NURSING HOME

STATE NURSING HOME

N U

R

SIN

G H

O M

E

FU

TU

R E

BL

D

G

7 49 48

66T-7

77T-1

T-2

756968

116119

121126125124

109CM

147 146

W

SITE

Scope of Work:

The scope of work for this project is to replace the existing campus fire alarm system with a new fire alarm system throughout. The existing copper cabling backbone infrastructure will be replaced with new fiber optic cabling. Each building will be provided with new fire alarm control panels connected to the campus network. A new campus wide computer monitoring and control system will be provided in Building 78.

Existing fire alarm devices such as pull stations, detectors, relay modules, monitor modules, flow and tamper switch interfaces, and associated conduit, boxes and cabling shall be demolished and replaced with new devices.

Building 48 Fire Alarm System:

The new Notifier fire alarm system in Building 48 will be replacing the existing fire alarm system. Voice evacuation notification appliances will be installed throughout the entire building, which will alert the occupants in the event of a fire. The FACP will provide control over the HVAC units and elevator recall function. The FACP will provide monitoring of the fire sprinkler system. Smoke and Heat Detectors will be installed where required per codes.

New manual pull station will be installed at building exits.

The fire sprinkler tamper switches will cause a supervisory signal when activated. These devices will report as a supervisory signal.

The fire alarm system shall be monitored through a central monitoring company of the owners choosing prior to the final inspection.

Scope of Work:

Example of Junction Box Detail (FA):

If Applicable (Use for eample only)

Walla Walla, WA 99362

U.S. Department Of Veterans Affairs VA Medical Center

77 Wainwright Drive

Owner

Project Manager: Dave Clem

GDM of Oregon 1584 McNeil Street, Suite 200

DuPont, WA 98327

Architect / Engineer The scope of work for this project is to replace the existing campus fire alarm system with a new fire alarm system throughout. The existing copper cabling backbone infrastructure will be replaced with new fiber optic cabling. Each building will be provided with new fire alarm control panels connected to the campus network. A new campus wide computer monitoring and control system will be provided in Building 78.

Existing fire alarm devices such as pull stations, detectors, relay modules, monitor modules, flow and tamper switch interfaces, and associated conduit, boxes and cabling shall be demolished and replaced with new devices.

Building 49 Fire Alarm System:

The new Notifier fire alarm system in Building 49 will be replacing the existing fire alarm system. Voice evacuation notification appliances will be installed throughout the entire building, which will alert the occupants in the event of a fire. The FACP will provide control over the HVAC units and elevator recall function. The FACP will provide monitoring of the fire sprinkler system. Smoke and Heat Detectors will be installed where required per codes.

New manual pull station will be installed at building exits.

The fire sprinkler tamper switches will cause a supervisory signal when activated. These devices will report as a supervisory signal.

The fire alarm system shall be monitored through a central monitoring company of the owners choosing prior to the final inspection.

Index of Drawings Drawing Name

Drawing Number

Cover Sheet / Fire Alarm MatrixFA-0.0 FA-1.1 Basement - Fire Alarm Plan /

First Floor - Fire Alarm Plan / Second Floor - Fire Alarm Plan / Riser Diagram / Details / Load Calculations / Speaker Calculations

Sheet Number

2016 NFPA 72, 2020 NFPA 70 (NEC), VA Fire Protection Manual

MAP

BATT

S P

FACP

EVAC

F

AIM

S30

S15C

VS

WF

SS

FARC

Indicates Circuit Continuation Indicates Home Run to FACP

AOM

R

RTS

S

F135°

R

F135°

CONV.

AIM

D

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text PRV Vault

AutoCAD SHX Text F/A

AutoCAD SHX Text 8"

AutoCAD SHX Text Caps

AutoCAD SHX Text Tank

AutoCAD SHX Text Fuel

AutoCAD SHX Text F/A

AutoCAD SHX Text Valves

AutoCAD SHX Text

PRV

AutoCAD SHX Text F/A

8'-7" AFF

8'-7" AFF8'-7" AFF

8'-7" AFF

8'-7" AFF

8'-10" AFF

8'-1" AFF

KITCHEN

DIRECTOR

OFFICE

CONFERENCE

COPIER

OFFICE

STAIR

HSKP

WAITING

RECEPT.

RESTROOM

CORR.

ELEVATOR

Dedicated

120VAC

SS

FARC

MAP

To Bldg. Devices (SLC Loop)

CPU2-640

HS-NCM-SF

NCA-2

DVC / CMIC-1

DAA2-7525 FACP

Spkr Crkts V0-1, V0-2, V0-3, V0-4BATT

NAC Crkts S0-1, S0-2, S0-3, S0-4, To Fiber Network Patch Panel

S P

Components located inside of

FACP

N7:L1:D001

EVAC

F N7:L1:M001

S15C

S0-1 V0-1

S0-1

S15C

S0-1 V0-1

S15C

S0-1 V0-1

S15CS0-1

V0-1

S15C

S0-1 V0-1

S15C

S0-1 V0-1

S15C S0-1 V0-1

RTS

AOM

R

N7:L1:M022

To AHU Shutdown

FN7:L1:M002

15C S0-1

S P

N7:L1:D002

P N7:L1:D003

F135° H N7:L1:D004

N7:L1:M016

N7:L1:M017

N7:L1:M015

N7:L1:M013

Elevator Control

120VAC

Shunt Trip Power Source

Primary Recall (Steady)

Alternate Recall (Steady)

AOM

R

AOM

R

Fire Light Indicator (Flashing)AOM

R

R

EP

A 2F

2S,2V

A,S,V

2S,2V

D

2S,2V

2S,2V

J

J J

J

J

J

J

J

J

J

2A

2A,2S,2V

2A

A,S,V

2S,2V

2S,2V

A

A,V

AIM

DTo Top of Shaft

A,D

N7:L1:M014

D

To Top of Shaft Heat Detector

Up to Fiber LIU

F

F

A,S,V

A,S,V

A,S,V

2S,2V

2S,2VRT

RT

To Basement Duct Detector

A

A

A A

S

General Note:

Addressing Legend:

D = Detector M = Module

Module/Device Number M01L01

Loop Number

* All addressable devices require SLC Loop (A-wire) from the FACP to operate. For help, please refer to riser diagram for reference.

* Do not route conduit into the bottom of any fire alarm system component cabinets.

* After each duct smoke detector has been installed use a Megnehelic Test Instrument to verify adequate air flow, show the results on the Shop Drawings for the AHJ's review.

* Tap all speakers at 1/2 watt - 25 volts unless otherwise indicated at individual device.

* Contractor may reuse existing pathways where available. Verify with system designer prior to adding additional devices or extending circuits to ensure voltage drop calculations are within acceptable limits.

1) Section of NFPA 72, National Fire Alarm Code requires units to be provided with smoke detection in areas that are not continuously occupied.

2) Provide Dedicated 120VAC circuit to the FACP label the Dedicated circuit breaker "Fire Alarm." In red with lockout. Location of breaker shall be noted at FACP.

3) Fiber Network routing to be field coordinated.

4) Detector is to activate Elevator Recall Functions.

5) Detector is to activate Elevator Shunt Trip. Mount within 24" of Sprinkler

Head.

6) Visual Notification omitted in areas without existing devices or ADA requirements to comply with VA Fire Protection Manual Section 7.3.F.l.4.

Field verify single person offices with hearing-impaired occupants.

7) Building basement is a confined entry, non-occupied space.

Flag Notes: (Some flag notes may not appear on every sheet)

Dedicated

120VAC

SS

FACP

FARC

MAP

GUTTER

CPU2-640

HS-NCM-SF

NCA-2

DVC / CMIC-1

DAA2-7525

EVAC

BATT

Battery Battery

Addressable Pull Station

321(-)

A ANBG-12LX

B300-6

From

Device SLC Loop previous

Device SLC Loop To next

A

A

Addressable Smoke or Heat Detector

RA

P

SF F

S15C S15C S15C

Speaker/Strobe

Speaker

Strobe

V

S

Strobe

Strobe

S_ S_

S15C S15C

RTS

To RTU Shutdown

AOM

R

Shutdown To Fan

0 15

6 7 8 9 9876

1 0

T1

T2

T4 T5

LOOP

T6 T7 T8

T9 T10

TENS ONES

ADDRESS

T3

T11

FRM-1

*Verify Connection with Mech. HVAC Contractor

A

A

Fan Shutdown Controlled by FRM-1 Control Relay Module

1W S30 15 15 15C 15C

F

Second Floor Second Floor

First Floor First Floor

Basement Basement

15C

F135° H

P S

P S

F135° H

P S

5.6K

TEST COIL (+)

TEST COIL (-)

COMM(+)

OUT CONV ONLY (+)

COMM (-)

RA/RTS (-)

RA (+)

RTS (+)

From previous SLC Loop

Devices

To next SLC Loop Devices(+)

RTS-151KEY

REMOTE

TEST

STATION

JUMPER

Duct Smoke Detector with Remote Test Station RTS-151

A

RT

5 S

EP

Strobe S0-1

Speaker V0-1 V

S

V S

A

RT

A

S V

Strobe S0-2

Speaker V0-2 V

S

SL

C

Lo op

A A

A

A

A

A

VS

D

D

WFD

WFD

Glycol System

PIV

Wet System

VSAIM

AIM

A

AA

Elevator Control

120VAC

Shunt Trip Power Source

Primary Recall (Steady)

Alternate Recall (Steady)

AOM

R

AOM

R

Fire Light Indicator (Flashing)AOM

R

R

DAIM

D

A,D

CONV.

A

47k

47k

47k

47k

47k

47k

F

To Fiber Network Bldg. 48

FTo Fiber Network Bldg. 68

15C

A

AIM

D

8'-9" AFF

8'-9" AFF

8'-9" AFF

8'-9" AFF

8'-9" AFF

8'-9" AFF

8'-10 12" AFF

OFFICE

EXEC. ASSISTANT

TO DIRECTOR

OFFICE

OFFICE

OFFICE

ASSOCIATE

DIRECTOR

OFFICE

HSKP

IT/

COMM

STAFF

RESTROOM

SHAFT

ELEVATOR

F N7:L1:M004 S30

1W

S0-2 V0-2

S0-2

S15C

S0-2 V0-2

S0-2

To FACP

S0-2

P

N7:L1:D006

F135°

A,S,V

J

S0-2

S0-2

J J

H

To Bottom of Shaft

A,D

CONV.

A,D

A

2S

2S

2S

2S

A,S,V

A,S,V

S A

A,S,V

A,S,V

Fiber LIU

BASEMENT

B101

VS

Main - Fire Sprinkler System

N7:L1:M011

N7:L1:M012

S

Located in Basement Duct

N7:L1:D021

D

D

WFN7:L1:M010 D

WFN7:L1:M009 D

Glycol System

PIV

Wet System

VS

To First Floor

A

AIM

AIM

A

A

A

RT

To

CONF.

RTS

AIM

D

Number of Sheets:

By

Installing Fire Alarm System Contractor:

Date

Drawn By:

Drawn Date:

Scale:

Drawing No.

Revisions Description

Authority Having Jurisdiction:

Project Contacts

DHL

03/19/2024

VA

W al la

W al la

B ui ld in g

W ai nw rig ht

D riv e W al la

W al la , W

A

Li fe

S af et y

(F ire

A la rm S ys te m ) D ra w in gs

COPYRIGHT NOTICE

ALL DRAWINGS AND WRITTEN MATERIAL APPEARING HEREIN

CONSTITUTE THE ORIGINAL AND UNPUBLISHED WORK OF

VULCAN FIRE, AND THE SAME MAY NOT BE DUPLICATED, USED

OR DISCLOSED WITHOUT THE EXPRESS WRITTEN CONSENT OF

VULCAN FIRE

ENGINEERED SYSTEM DISTRIBUTION

by Honeywell

TM

Vulcan Project #: FI23-013

U .S

.D ep ar tm en t o f V et er an s A ffa irs

Fi re

A la rm S ys te m R ep la ce m en t -

P ha se B

Walla Walla Fire Department 2251 S. Howard St., Walla Walla, WA 99362

(509) 524-4603

Vulcan Fire 112 East Hazel Ave., Ste#1, Coeur d'Alene, ID 83814

(208) 277-0171

GC

L ice ns e:

V

UL

CA

F*

0M

El ec

L ice ns e:

V

UL

CA

F*

W

EB

SI

TE

: w w w

.v ul ca nf ire us

.c om

PH

ON

E

(2

) 2

-0

Ea st H az el

A ve nu e, S ui te

1, C oe ur d 'A le ne

, I da ho

Record Drawings (11/01/2024)

1/8" = 1'-0"

FA-1.1

Scale: 1/4'' = 1'-0''

10 2 4 8 16

First Floor - Fire Alarm System Plan

Riser Diagram / Details - Fire Alarm System

Scale: 1/4'' = 1'-0''

10 2 4 8 16

Second Floor - Fire Alarm System Plan Scale: 1/4'' = 1'-0''

10 2 4 8 16

Basement - Fire Alarm System Plan

VOLTAGE DROPS ARE CALCULATED AT 16VDC.

L= ONE WAY LENGTH OF CIRCUIT(FEET)

WHERE VD= VOLTAGE DROP

R= 3.19 OHMS PER THOUSAND

I= LOAD CURRENT(AMPERES)

AFTER DETERMINING THE LENGTH OF THE HORN/STROBE CIRCUIT, USE

THE FOLLOWING FORMULA TO CALCULATE THE VOLTAGE DROP.

2xLxRxIVD=

LUMP SUM METHOD WAS USED TO CALCULATE ALLOWABLE VOLTAGE DROP. THIS METHOD

ALLOWS FOR A SMALL MARGIN OF SAFETY, TAKING INTO CONSIDERATION THE ACTUAL

CIRCUIT ROUTING MAY DIFFER FROM WHAT IS SHOWN ON THE SHOP SUBMITTAL

DRAWINGS. IF ACTUAL CIRCUIT LENGTH IS GOING TO EXCEED THE MAXIMUM ALLOWABLE

CIRCUIT LENGTH, CONTACT VULCAN FIRE.

VOLTAGE-DROP CALCULATION NOTE:

** STARTING VOLTAGE-DROP CALCULATIONS IS 20.4 PER UL 864, 9TH EDITION STANDARDS FOR FIRE ALARM

CONTROL PANELS.

Sheets and Views
FI23-013 VA Walla Walla Bldg-49 FA-FA-0.0 (1)
FI23-013 VA Walla Walla Bldg-49 FA-FA-1.1 (2)

File details come from the government source that posted it. Updated .