These are record drawings for a fire alarm system replacement project at the VA Walla Walla Medical Center, specifically for Building 49. The project involves replacing the existing campus fire alarm system with a new Notifier addressable fire alarm system, including new fiber optic cabling infrastructure, fire alarm control panels, and campus-wide monitoring capabilities. The system will include voice evacuation notification appliances, HVAC unit control, elevator recall functions, sprinkler system monitoring, smoke and heat detectors, manual pull stations, and central station monitoring. The drawings detail the fire alarm system components for the building's basement, first floor, and second floor, with specific device placement, wiring diagrams, and technical specifications for a comprehensive fire safety upgrade.
View the file
Other files
Show all 27
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SYSTEM INPUTS
PANEL FUNCTIONS
ALARM DEVICES
SYSTEM RESET
SYSTEM SILENCE
"ALL SYSTEMS NORMAL"
SMOKE DETECTORS
SUPERVISORY DEVICES
TROUBLE FUNCTIONS
ABNORMAL CIRCUIT OR DEVICE
FIRE ALARM SYSTEM AC POWER FAILURE
FIRE ALARM SYSTEM LOW BATTERY
SP
EA
KE
RS
A
ND
S
TR
OB
ES
S
TO
P
YE
LL
OW
LE
D W
IL
L F
LA
SH
A
ND
YE
LL
OW
LE
D W
IL
L F
LA
SH
A
ND
W
IL
L T
UR
N
ON
, U
NT
IL
S
IL
EN
CE
D.
RE
D
LE
D
AN
D
AU
IB
LE
S
OU
ND
ER
HI
ST
OR
Y
LO
G:
SYSTEM OUTPUTS
(S
YN
CH
RO
NI
ZE
D
AN
D
VO
IC
E
EV
AC
TE
MP
OR
AL
P
AT
TE
RN
AC
TI
VA
TE
S
BU
IL
DI
NG
S
IN
TE
RI
OR
N
OT
IF
IC
AT
IO
N
DE
VI
CE
S
REQUIRED FA CONTROLFACP FUNCTION
AC
TU
AT
ES
T
RO
UB
LE
C
ON
DI
TI
ON
A
T
CO
NT
RO
L P
AN
EL
PU
LS
IN
G
SO
UN
DE
R
W
IL
L T
UR
N
ON
, U
NT
IL
A
CK
NO
W
LE
DG
ED
AC
TU
AT
ES
S
UP
ER
VI
SO
RY
C
ON
DI
TI
ON
A
T
CO
NT
RO
L P
AN
EL
GR
EE
N
AC
P
OW
ER
IN
DI
CA
TO
R
IS
LI
T
ST
EA
DI
LY
ON
C
ON
TR
OL
P
AN
EL
CH
AR
AC
TE
R
LC
D
DI
SA
PL
Y
DI
SP
LA
Y
TH
E
CU
ST
OM
M
ES
SA
GE
"A
LL
S
YS
TE
MS
N
OR
MA
L"
AC
TU
AT
ES
A
LA
RM
C
ON
DI
TI
ON
A T
CO
NT
RO
L P
AN
EL
RE
CO
RD
IN
G
OF
T
HE
E
VE
NT
IN
S
YS
TE
MS
M
EM
OR
Y
PU
LS
IN
G
SO
UN
DE
R
W
IL
L T
UR
N
ON
, U
NT
IL
A
CK
NO
W
LE
DG
ED
FI
RE
A
LA
RM
C
ON
TR
OL
P
AN
EL
R
ET
UR
NS
T O
NO
RM
AL
NOTIFICATION
MANUAL PULL STATION
SH
UT
D
OW
N
OF
R
ES
PE
CT
IV
E
HV
AC
U
NI
T
A B C D E F G H I J K L M N O P Q R
* FIRE SPRINKLER SYSTEM - ZONED WATERFLOW SWITCH (LATCHING)
FIRE SPRINKLER SYSTEM - MAIN WATERFLOW SWITCH (LATCHING)
Fire Alarm System Matrix
FIRE SPRINKLER SYSTEM - VALVE TAMPER SWITCH
MICROPHONE ACTIVATION WITH CIRCUIT SELECTION SWITCH
(C
ON
TA
CT
ID
) T
O U.
L.
CL
AS
S
CE
NT
RA
L S
TA
TI
ON
(C
ON
TA
CT
ID
) T
O U.
L.
CL
AS
S
CE
NT
RA
L S
TA
TI
ON
(C
ON
TA
CT
ID
) T
O U.
L.
CL
AS
S
CE
NT
RA
L S
TA
TI
ON
(C
ON
TA
CT
ID
) T
O U.
L.
CL
AS
S
CE
NT
RA
L S
TA
TI
ON
TR
AN
SM
IT
S W
AT
ER
FL
OW
C
ON
DI
TI
ON
V
IA
C
EL
LU
LA
R
CO
MM
UN
IC
AT
OR
TR
AN
SM
IT
S
TR
OU
BL
E
CO
ND
IT
IO
N
VI
A
CE
LL
UL
AR
C
OM
MU
NI
CA
TO
R
TR
AN
SM
IT
S
SU
PE
RV
IS
OR
Y
CO
ND
IT
IO
N
VI
A
CE
LL
UL
AR
C
OM
MU
NI
CA
TO
R
TR
AN
SM
IT
S
AL
AR
M
CO
ND
IT
IO
N
VI
A
CE
LL
UL
AR
C
OM
MU
NI
CA
TO
R
AN
NU
NC
IA
TO
RS
(B
OT
H
SP
EA
KE
RS
A
ND
S
TR
OB
ES
W
IL
L S
TO
P)
NO
TI
FI
CA
TI
ON
A
PP
LI
AN
CE
S
SH
AL
L B E
SI
LE
NC
EA
BL
E
AT
T
HE
FA
CP
O
R
DUCT (SMOKE) DETECTOR (Associated with AHU)
- ELEVATOR LOBBY - (First Floor)
- SPOT TYPE DETECTORS, (All, except as specifically noted below)
- ELEVATOR LOBBY - (Second Floor)
- ELEVATOR MACHINE ROOM (First Floor)
EL
EV
AT
OR
R
EC
AL
L (
PR
IM
AR
Y)
EL
EV
AT
OR
R
EC
AL
L T
O
SE
CO
ND
FL
OO
R
EL
EV
AT
OR
R
EC
AL
L (
AL
TE
RN
AT
E)
EL
EV
AT
OR
R
EC
AL
L T
O
FI
RS
T
FL
OO
R
AC
TI
VA
TE
E
LE
VA
TO
R
FI
RE
D
EP
AR
TM
EN
T
(F
LA
SH
IN
G) L
IG
HT
AC
TI
VA
TE
E
LE
VA
TO
R
FI
RE
D
EP
AR
TM
EN
T (S
TE
AD
Y) L
IG
HT
PR
IO
R
TO
S
PR
IN
KL
ER
H
EA
D
AC
TI
VA
TI
ON
SH
UT
DO
W
N
PO
W
ER
T O
AF
FE
CT
ED
E
LE
VA
TO
R
S
HEAT DETECTORS
- ELEVATOR MACHINE ROOM (First Floor)
- TOP OF ELEVATOR SHAFT
ON
YX
W
OR
KS
S
TA
TI
ON
IN
B
UI
LD
IN
G
SE
CU
RI
TY
O
FF
IC
E
TR
AN
SM
IT
S
SY
ST
EM
C
ON
DI
TI
ON
V
IA
FI
BE
R
NE
TW
OR
K
NE
TW
OR
K
AN
NU
NC
IA
TO
R
IN
B
UI
LD
IN
G
P
OL
IC
E
ST
AT
IO
N
TR
AN
SM
IT
S
SY
ST
EM
C
ON
DI
TI
ON
V
IA
FI
BE
R
NE
TW
OR
K
T U
Number of Sheets:
By
Installing Fire Alarm System Contractor:
Date
Drawn By:
Drawn Date:
Scale:
Drawing No.
Revisions Description
Authority Having Jurisdiction:
Project Contacts
DHL
03/19/2024
VA
W al la
W al la
B ui ld in g
W ai nw rig ht
D riv e W al la
W al la , W
A
Li fe
S af et y
(F ire
A la rm S ys te m ) D ra w in gs
COPYRIGHT NOTICE
ALL DRAWINGS AND WRITTEN MATERIAL APPEARING HEREIN
CONSTITUTE THE ORIGINAL AND UNPUBLISHED WORK OF
VULCAN FIRE, AND THE SAME MAY NOT BE DUPLICATED, USED
OR DISCLOSED WITHOUT THE EXPRESS WRITTEN CONSENT OF
VULCAN FIRE
ENGINEERED SYSTEM DISTRIBUTION
by Honeywell
TM
Vulcan Project #: FI23-013
U .S
.D ep ar tm en t o f V et er an s A ffa irs
Fi re
A la rm S ys te m R ep la ce m en t -
P ha se B
Walla Walla Fire Department 2251 S. Howard St., Walla Walla, WA 99362
(509) 524-4603
Vulcan Fire 112 East Hazel Ave., Ste#1, Coeur d'Alene, ID 83814
(208) 277-0171
GC
L ice ns e:
V
UL
CA
F*
0M
El ec
L ice ns e:
V
UL
CA
F*
W
EB
SI
TE
: w w w
.v ul ca nf ire us
.c om
PH
ON
E
(2
) 2
-0
Ea st H az el
A ve nu e, S ui te
1, C oe ur d 'A le ne
, I da ho
Record Drawings (11/01/2024)
N/A
FA-0.0
Site Plan
General Notes:
Drawing Notes:
Fire Alarm Control Panel Terminations:
All wiring runs shown on the fire alarm shop drawings are conceptual only. They do not and are not intended to be actual wire runs or conduit runs. Device interconnect is intended to show only sequence of device connections and type of wire.
Please review both the floor plans and the riser diagram drawings to resolve any conflicts or questions that may come up. If the drawings do not answer your questions, please call Vulcan Fire for help to answer your questions.
Electrical Contractor is advised not to complete terminations at the Fire Alarm Control Panel. Terminations will be completed by a qualified Vulcan Fire Technician.
Code Analysis:
Edition of Codes:
Number of Stories:
Edition of Standards:
Occupancy Type: B, Business (Clinic, Exam, Offices) S-1 Storage (Storage Closets)
2018 IBC, IFC, IMC
2018 NFPA 101
City of Walla Walla Amendments 2009 ANSI 117.1 Guidelines for Accessible & Useable
Yes, Fully Fire Sprinklered
Visual Notification: Public Mode
Wire runs are indicated by AlphaNumeric designations.
power run of "2#__ " cable. A designation of "P3" would indicate another individual run of "2#__ " cable.
"2#__Twisted AND a run of 2#__ " cable.
A designation of "A,P2", would refer to a run of
The wire Gauge of any wire run is determined by the
A designation of "P2", would refer to a individual pair, 2#__ Twisted" cable.
A designation of "2A", would refer to a run of "2 length of the wire run and the power load on that run.
A typical wire run designated as "A", would refer to a single run of "2 #__ Twisted" cable.
For example:
A,P2
P2,P3
A
2A
Wire Chart:
Audible Notification: Voice Evac - Temporal 3 Pattern / Synchronized
Type of FA System: New Fire Alarm Addressable System
Temporal Pattern Notification Device Numbering:
(IE: HORN/STROBE)
AUDIBLE/VISUAL DEVICE
(IE: STROBE ONLY)
AUDIBLE DEVICE
(IE: HORN ONLY)
WITH THE REQUIREMENTS FOR VISUAL DEVICES.
1. ADA ACCESSIBILITY GUIDELINES HAVE ACCEPTED NFPA 72 GUIDELINES AS "EQUIVALENT FACILITATION".
3. MEASUREMENT IS TO THE BOTTOM OF THE DEVICE.
2. NFPA 72 STATES THAT COMBINATION AUDIBLE/VISUAL DEVICES SHALL BE MOUNTED IN ACCORDANCE
NOTES:
AFF = ABOVE FINISHED FLOOR0" (FLOOR)
NFPA 72
A
90" A.F.F.
A/V
96" A.F.F.
80" A.F.F.
NFPA 72
MAX.
MIN.
V
VISUAL DEVICE
CEILING
6" BELOW
CEILING
Example of Proper Mounting for Audible/Visual Devices:
Fire Protection System:
Square Footage:
FA System Required: Code-Required
3,245 GSF
Protected Premises Fire Alarm Systems (Wiring):
Mounted Candela Rating:
S150 = 150 Candela S177 = 177 Candela S185 = 185 Candela
S135 = 135 Candela
S115 = 115 Candela S110 = 110 Candela S95 = 95 Candela S75 = 75 Candela S30 = 30 Candela S15 = 15 Candela
Ceiling S15C S15
Wattage Speaker 1W Tap
Guard WireWG WeatherproofWP
VOICE CIRCUIT
V 2
2S
POWER SUPPLY NUMBER
STROBE CIRCUIT
CIRCUIT NUMBER
AMPLIFIER NUMBER
CIRCUIT NUMBER
("T" Tap) Class B
Class B
P
F P
VS VSAIM
Class B
IDC - Initiating Device Circuit Manual Pull Stations, Fire Sprinkler System, Etc.
NAC - Notification Appliance Circuit Horns, Bells, Strobes, Etc.
SLC - Signaling Line Circuit Intelligent (Addressable) Devices
Only in J-Box (per Owner)
FS
S
Where used, End-Of-Line Resistors shall be labeled "EOL" on the Device (per Owner)
Building 49 77 Wainwright Drive, Walla Walla, WA 99362
Fire Alarm System Replacement
N
All intelligent and or addressable Fire Alarm Devices must be placed in protected areas with ambient temperature ranging from 32° to 120°. Weatherproof Fire Alarm Devices have temperature rating from -40° to 151° in wet or dry applications.
Do not place smoke detectors within 3 feet of air supply registers and diffusers.
All intelligent devices shall be interconnected as shown on the riser on-line diagram. Each intelligent device is designed with an address. T-Tapping is permitted on SLC Loop (Class "B") only.
Wire runs show interconnected of fire alarm devices only. Wiring does not represent conduit runs.
Electrical Contractor is responsible for proper connection of equipment provided by others.
(RL) Indicates Existing Device to be relocated to new location.
(R) Indicates Device to be removed and returned to Owner.
(E) Indicates Device existing to remain (shown in gray scale).
(N) Indicates New Device.
(RR) Indicates Remove Existing Device and replace with new Device. Return any removed equipment to Owner.
Typical Device Mounting Height:
NFPA 2016
Wall Mounted AUDIBLE device.
Top of Individual Device
MAX
4'-0"
"ADA"
(48")
Top of Device of the Same Lens
Top of Unit
Top of Cabinet
To Handle of Device Per NFPA 72 from (AFF) Above All heights measured
NOT TO SCALE
Finished Floor
BOTTOM
OF
6'-0"
80" TO
MIN* (72")
LENS
See Note #5
7'-0"
TO TOP
OF
Approx.96"
MAX*
(84")LENS
(6")
THAN
BELOW
CEILING
(90")
AND
LESS
THAN
NOT
LESS
NOT
(64") 5'-4" or 80" MIN. to Bottom A/V or Visual Only Devices
MAX 96" to Top of Lens for all
#1) HEIGHTS SHOWN ARE LISTED IN NFPA STANDARDS 2016.
#2) MOUNTING HEIGHTS LISTED IN SPECIFICATIONS OR SHOWN ON THE
ARCHITECTURAL ELEVATIONS SHALL GOVERN. ANY DISCREPANCY SHALL BE
BROUGHT TO THE ATTENTION OF THE AHJ AND THE ENGINEER OF RECORD.
#3) WALL MOUNTED ADA STROBES & HORN/STROBES ARE TO BE PLACED
A MINIMUM OF 80" ABOVE FINISHED FLOOR MEASURED AT THE BOTTOM OF
THE LENS OR 6" BELOW THE CEILING TO THE TOP OF THE LENS,
WHICHEVER IS LOWEST. THE MAXIMUM HEIGHT MEASURED AT THE TOP OF
THE LENS SHALL NOT EXCEED 96".
#4) IN SLEEPING ROOMS A STROBE MOUNTED LESS THAN 24" FROM THE
CEILING SHALL BE AT LEAST 177CD. STROBES MOUNTED 24" OR BELOW
SHALL BE AT LEAST 110 CD. A STROBE SHALL BE MOUNTED WITHIN 16FT
OF THE PILLOW.
#5) REMOTE LIGHTS, TEST STATIONS AND MODULES SHOULD BE MOUNTED
SO AS TO BE ACCESSIBLE, YET ABOVE EASY REACH TO PREVENT
VANDALISM.
#6) CEILING MOUNT VISIBLE DEVICES SHALL BE SPACED ACCORDING TO
2016 NFPA 72.
FSA
FACFACP RPS
AIM AOM
F
RL
S15H15 15MC15
RT
J DM
MAP FTR
C
AOM
R
S
(48") 4'-0"
*MAX
(42") 3'-6"
*MIN
Obstructions or other Bends, 3 Feet x 6 = 18 Feet Duct Width = 3 Feet Example:
as far as possible Widths Maximum, or Minimum, 10 Duct Six Duct Widths
Inlet Return Air
Duct Smoke Detector Placement
Width
Width
The recommended location of Smoke Detectors mounted in or Duct Smoke Detectors mounted on air ducts should be between six duct widths and ten duct widths up stream from any duct openings, deflection plates, sharp bends, or branch connections. Refer to NFPA 72, 90A, 92A, OR 92B for further guidelines.
Duct Detectors shall be located:
A. At the Return Air Duct Side of AHU's above 2,000 CFM
Openings, as far as possible Widths Maximum, or Minimum, 10 Duct Six Duct Widths
Up to 1 ft.
Width
Outside Duct Recommended * Sampling Tube for different duct widths:
Sampling Tubes recommended
DST1
2/3 the duct width
* Must extend a minimum of
2 to 4 ft. DST3 4 to 8 ft. DST5 8 to 12 ft. DST10
1 to 2 ft. DST1.5
12" 1/4"
Detector
Duct
Sampling Tube 2"
The Sampling Tube should be angled at least 1/4" down for every 12" of duct width.
3/4" Hole
DST5
Sampling Tube Part Number
DST5
Downstream from Sampling Tube Exhaust Tube must be Mounted
Air Flow
Air Flow
Holes must Face into Air Flow
Detector
Detector
U.S. Department of Veterans Affairs
VA WALLA WALLA - FIRE LIFE SAFETY - PHASE B Fire Alarm Systems Interconnect Drawings
Setting Initiating Device Addresses:
D:L1: 501
ONESTENS
7 8 9
00 15
D = Detector M = Monitor
Device AddressData Loop Number
DIALS ARE
LOCATED ON THE
BACK OF EACH
DEVICE
N1:
Node Number
X
X X
X X
X
X
X
X
XX X
X
X
X
X
X
X
STATE NURSING HOME
STATE NURSING HOME
STATE NURSING HOME
STATE NURSING HOME
N U
R
SIN
G H
O M
E
FU
TU
R E
BL
D
G
7 49 48
66T-7
77T-1
T-2
756968
116119
121126125124
109CM
147 146
W
SITE
Scope of Work:
The scope of work for this project is to replace the existing campus fire alarm system with a new fire alarm system throughout. The existing copper cabling backbone infrastructure will be replaced with new fiber optic cabling. Each building will be provided with new fire alarm control panels connected to the campus network. A new campus wide computer monitoring and control system will be provided in Building 78.
Existing fire alarm devices such as pull stations, detectors, relay modules, monitor modules, flow and tamper switch interfaces, and associated conduit, boxes and cabling shall be demolished and replaced with new devices.
Building 48 Fire Alarm System:
The new Notifier fire alarm system in Building 48 will be replacing the existing fire alarm system. Voice evacuation notification appliances will be installed throughout the entire building, which will alert the occupants in the event of a fire. The FACP will provide control over the HVAC units and elevator recall function. The FACP will provide monitoring of the fire sprinkler system. Smoke and Heat Detectors will be installed where required per codes.
New manual pull station will be installed at building exits.
The fire sprinkler tamper switches will cause a supervisory signal when activated. These devices will report as a supervisory signal.
The fire alarm system shall be monitored through a central monitoring company of the owners choosing prior to the final inspection.
Scope of Work:
Example of Junction Box Detail (FA):
If Applicable (Use for eample only)
Walla Walla, WA 99362
U.S. Department Of Veterans Affairs VA Medical Center
77 Wainwright Drive
Owner
Project Manager: Dave Clem
GDM of Oregon 1584 McNeil Street, Suite 200
DuPont, WA 98327
Architect / Engineer The scope of work for this project is to replace the existing campus fire alarm system with a new fire alarm system throughout. The existing copper cabling backbone infrastructure will be replaced with new fiber optic cabling. Each building will be provided with new fire alarm control panels connected to the campus network. A new campus wide computer monitoring and control system will be provided in Building 78.
Existing fire alarm devices such as pull stations, detectors, relay modules, monitor modules, flow and tamper switch interfaces, and associated conduit, boxes and cabling shall be demolished and replaced with new devices.
Building 49 Fire Alarm System:
The new Notifier fire alarm system in Building 49 will be replacing the existing fire alarm system. Voice evacuation notification appliances will be installed throughout the entire building, which will alert the occupants in the event of a fire. The FACP will provide control over the HVAC units and elevator recall function. The FACP will provide monitoring of the fire sprinkler system. Smoke and Heat Detectors will be installed where required per codes.
New manual pull station will be installed at building exits.
The fire sprinkler tamper switches will cause a supervisory signal when activated. These devices will report as a supervisory signal.
The fire alarm system shall be monitored through a central monitoring company of the owners choosing prior to the final inspection.
Index of Drawings Drawing Name
Drawing Number
Cover Sheet / Fire Alarm MatrixFA-0.0 FA-1.1 Basement - Fire Alarm Plan /
First Floor - Fire Alarm Plan / Second Floor - Fire Alarm Plan / Riser Diagram / Details / Load Calculations / Speaker Calculations
Sheet Number
2016 NFPA 72, 2020 NFPA 70 (NEC), VA Fire Protection Manual
MAP
BATT
S P
FACP
EVAC
F
AIM
S30
S15C
VS
WF
SS
FARC
Indicates Circuit Continuation Indicates Home Run to FACP
AOM
R
RTS
S
F135°
R
F135°
CONV.
AIM
D
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text PRV Vault
AutoCAD SHX Text F/A
AutoCAD SHX Text 8"
AutoCAD SHX Text Caps
AutoCAD SHX Text Tank
AutoCAD SHX Text Fuel
AutoCAD SHX Text F/A
AutoCAD SHX Text Valves
AutoCAD SHX Text
PRV
AutoCAD SHX Text F/A
8'-7" AFF
8'-7" AFF8'-7" AFF
8'-7" AFF
8'-7" AFF
8'-10" AFF
8'-1" AFF
KITCHEN
DIRECTOR
OFFICE
CONFERENCE
COPIER
OFFICE
STAIR
HSKP
WAITING
RECEPT.
RESTROOM
CORR.
ELEVATOR
Dedicated
120VAC
SS
FARC
MAP
To Bldg. Devices (SLC Loop)
CPU2-640
HS-NCM-SF
NCA-2
DVC / CMIC-1
DAA2-7525 FACP
Spkr Crkts V0-1, V0-2, V0-3, V0-4BATT
NAC Crkts S0-1, S0-2, S0-3, S0-4, To Fiber Network Patch Panel
S P
Components located inside of
FACP
N7:L1:D001
EVAC
F N7:L1:M001
S15C
S0-1 V0-1
S0-1
S15C
S0-1 V0-1
S15C
S0-1 V0-1
S15CS0-1
V0-1
S15C
S0-1 V0-1
S15C
S0-1 V0-1
S15C S0-1 V0-1
RTS
AOM
R
N7:L1:M022
To AHU Shutdown
FN7:L1:M002
15C S0-1
S P
N7:L1:D002
P N7:L1:D003
F135° H N7:L1:D004
N7:L1:M016
N7:L1:M017
N7:L1:M015
N7:L1:M013
Elevator Control
120VAC
Shunt Trip Power Source
Primary Recall (Steady)
Alternate Recall (Steady)
AOM
R
AOM
R
Fire Light Indicator (Flashing)AOM
R
R
EP
A 2F
2S,2V
A,S,V
2S,2V
D
2S,2V
2S,2V
J
J J
J
J
J
J
J
J
J
2A
2A,2S,2V
2A
A,S,V
2S,2V
2S,2V
A
A,V
AIM
DTo Top of Shaft
A,D
N7:L1:M014
D
To Top of Shaft Heat Detector
Up to Fiber LIU
F
F
A,S,V
A,S,V
A,S,V
2S,2V
2S,2VRT
RT
To Basement Duct Detector
A
A
A A
S
General Note:
Addressing Legend:
D = Detector M = Module
Module/Device Number M01L01
Loop Number
* All addressable devices require SLC Loop (A-wire) from the FACP to operate. For help, please refer to riser diagram for reference.
* Do not route conduit into the bottom of any fire alarm system component cabinets.
* After each duct smoke detector has been installed use a Megnehelic Test Instrument to verify adequate air flow, show the results on the Shop Drawings for the AHJ's review.
* Tap all speakers at 1/2 watt - 25 volts unless otherwise indicated at individual device.
* Contractor may reuse existing pathways where available. Verify with system designer prior to adding additional devices or extending circuits to ensure voltage drop calculations are within acceptable limits.
1) Section of NFPA 72, National Fire Alarm Code requires units to be provided with smoke detection in areas that are not continuously occupied.
2) Provide Dedicated 120VAC circuit to the FACP label the Dedicated circuit breaker "Fire Alarm." In red with lockout. Location of breaker shall be noted at FACP.
3) Fiber Network routing to be field coordinated.
4) Detector is to activate Elevator Recall Functions.
5) Detector is to activate Elevator Shunt Trip. Mount within 24" of Sprinkler
Head.
6) Visual Notification omitted in areas without existing devices or ADA requirements to comply with VA Fire Protection Manual Section 7.3.F.l.4.
Field verify single person offices with hearing-impaired occupants.
7) Building basement is a confined entry, non-occupied space.
Flag Notes: (Some flag notes may not appear on every sheet)
Dedicated
120VAC
SS
FACP
FARC
MAP
GUTTER
CPU2-640
HS-NCM-SF
NCA-2
DVC / CMIC-1
DAA2-7525
EVAC
BATT
Battery Battery
Addressable Pull Station
321(-)
A ANBG-12LX
B300-6
From
Device SLC Loop previous
Device SLC Loop To next
A
A
Addressable Smoke or Heat Detector
RA
P
SF F
S15C S15C S15C
Speaker/Strobe
Speaker
Strobe
V
S
Strobe
Strobe
S_ S_
S15C S15C
RTS
To RTU Shutdown
AOM
R
Shutdown To Fan
0 15
6 7 8 9 9876
1 0
T1
T2
T4 T5
LOOP
T6 T7 T8
T9 T10
TENS ONES
ADDRESS
T3
T11
FRM-1
*Verify Connection with Mech. HVAC Contractor
A
A
Fan Shutdown Controlled by FRM-1 Control Relay Module
1W S30 15 15 15C 15C
F
Second Floor Second Floor
First Floor First Floor
Basement Basement
15C
F135° H
P S
P S
F135° H
P S
5.6K
TEST COIL (+)
TEST COIL (-)
COMM(+)
OUT CONV ONLY (+)
COMM (-)
RA/RTS (-)
RA (+)
RTS (+)
From previous SLC Loop
Devices
To next SLC Loop Devices(+)
RTS-151KEY
REMOTE
TEST
STATION
JUMPER
Duct Smoke Detector with Remote Test Station RTS-151
A
RT
5 S
EP
Strobe S0-1
Speaker V0-1 V
S
V S
A
RT
A
S V
Strobe S0-2
Speaker V0-2 V
S
SL
C
Lo op
A A
A
A
A
A
VS
D
D
WFD
WFD
Glycol System
PIV
Wet System
VSAIM
AIM
A
AA
Elevator Control
120VAC
Shunt Trip Power Source
Primary Recall (Steady)
Alternate Recall (Steady)
AOM
R
AOM
R
Fire Light Indicator (Flashing)AOM
R
R
DAIM
D
A,D
CONV.
A
47k
47k
47k
47k
47k
47k
F
To Fiber Network Bldg. 48
FTo Fiber Network Bldg. 68
15C
A
AIM
D
8'-9" AFF
8'-9" AFF
8'-9" AFF
8'-9" AFF
8'-9" AFF
8'-9" AFF
8'-10 12" AFF
OFFICE
EXEC. ASSISTANT
TO DIRECTOR
OFFICE
OFFICE
OFFICE
ASSOCIATE
DIRECTOR
OFFICE
HSKP
IT/
COMM
STAFF
RESTROOM
SHAFT
ELEVATOR
F N7:L1:M004 S30
1W
S0-2 V0-2
S0-2
S15C
S0-2 V0-2
S0-2
To FACP
S0-2
P
N7:L1:D006
F135°
A,S,V
J
S0-2
S0-2
J J
H
To Bottom of Shaft
A,D
CONV.
A,D
A
2S
2S
2S
2S
A,S,V
A,S,V
S A
A,S,V
A,S,V
Fiber LIU
BASEMENT
B101
VS
Main - Fire Sprinkler System
N7:L1:M011
N7:L1:M012
S
Located in Basement Duct
N7:L1:D021
D
D
WFN7:L1:M010 D
WFN7:L1:M009 D
Glycol System
PIV
Wet System
VS
To First Floor
A
AIM
AIM
A
A
A
RT
To
CONF.
RTS
AIM
D
Number of Sheets:
By
Installing Fire Alarm System Contractor:
Date
Drawn By:
Drawn Date:
Scale:
Drawing No.
Revisions Description
Authority Having Jurisdiction:
Project Contacts
DHL
03/19/2024
VA
W al la
W al la
B ui ld in g
W ai nw rig ht
D riv e W al la
W al la , W
A
Li fe
S af et y
(F ire
A la rm S ys te m ) D ra w in gs
COPYRIGHT NOTICE
ALL DRAWINGS AND WRITTEN MATERIAL APPEARING HEREIN
CONSTITUTE THE ORIGINAL AND UNPUBLISHED WORK OF
VULCAN FIRE, AND THE SAME MAY NOT BE DUPLICATED, USED
OR DISCLOSED WITHOUT THE EXPRESS WRITTEN CONSENT OF
VULCAN FIRE
ENGINEERED SYSTEM DISTRIBUTION
by Honeywell
TM
Vulcan Project #: FI23-013
U .S
.D ep ar tm en t o f V et er an s A ffa irs
Fi re
A la rm S ys te m R ep la ce m en t -
P ha se B
Walla Walla Fire Department 2251 S. Howard St., Walla Walla, WA 99362
(509) 524-4603
Vulcan Fire 112 East Hazel Ave., Ste#1, Coeur d'Alene, ID 83814
(208) 277-0171
GC
L ice ns e:
V
UL
CA
F*
0M
El ec
L ice ns e:
V
UL
CA
F*
W
EB
SI
TE
: w w w
.v ul ca nf ire us
.c om
PH
ON
E
(2
) 2
-0
Ea st H az el
A ve nu e, S ui te
1, C oe ur d 'A le ne
, I da ho
Record Drawings (11/01/2024)
1/8" = 1'-0"
FA-1.1
Scale: 1/4'' = 1'-0''
10 2 4 8 16
First Floor - Fire Alarm System Plan
Riser Diagram / Details - Fire Alarm System
Scale: 1/4'' = 1'-0''
10 2 4 8 16
Second Floor - Fire Alarm System Plan Scale: 1/4'' = 1'-0''
10 2 4 8 16
Basement - Fire Alarm System Plan
VOLTAGE DROPS ARE CALCULATED AT 16VDC.
L= ONE WAY LENGTH OF CIRCUIT(FEET)
WHERE VD= VOLTAGE DROP
R= 3.19 OHMS PER THOUSAND
I= LOAD CURRENT(AMPERES)
AFTER DETERMINING THE LENGTH OF THE HORN/STROBE CIRCUIT, USE
THE FOLLOWING FORMULA TO CALCULATE THE VOLTAGE DROP.
2xLxRxIVD=
LUMP SUM METHOD WAS USED TO CALCULATE ALLOWABLE VOLTAGE DROP. THIS METHOD
ALLOWS FOR A SMALL MARGIN OF SAFETY, TAKING INTO CONSIDERATION THE ACTUAL
CIRCUIT ROUTING MAY DIFFER FROM WHAT IS SHOWN ON THE SHOP SUBMITTAL
DRAWINGS. IF ACTUAL CIRCUIT LENGTH IS GOING TO EXCEED THE MAXIMUM ALLOWABLE
CIRCUIT LENGTH, CONTACT VULCAN FIRE.
VOLTAGE-DROP CALCULATION NOTE:
** STARTING VOLTAGE-DROP CALCULATIONS IS 20.4 PER UL 864, 9TH EDITION STANDARDS FOR FIRE ALARM
CONTROL PANELS.