26 08 00.pdf

PDF 13 KB Posted

Attached to
TINKER AFB MAC BOA WWYK190023 Renovate Restrooms B117
Solicitation number
FA813726R0030
Issued by

About this file

This document is a Technical Specifications section (26 08 00) for Apparatus Inspection and Testing at Tinker Air Force Base, Oklahoma, effective April 2019.

The specification establishes requirements for independent third-party acceptance testing and inspection of electrical distribution systems and generation equipment. The contractor must engage a qualified testing organization that has been regularly engaged in electrical testing for a minimum of 5 years, maintains a calibration program, and uses instruments calibrated in accordance with NETA ATS (2013) Standard. The testing organization must be a first-tier subcontractor independent of equipment suppliers, manufacturers, and installers, with no work performed by second-tier subcontractors. The lead engineering technician performing testing must be certified by NETA or NICET with a minimum of 5 years' experience inspecting, testing, and calibrating electrical distribution and generation equipment, and must provide three references with specific contact information.

Required submittals include government-approved test reports documenting acceptance tests and inspections, and certificates verifying organization qualifications and lead technician credentials, submitted within 10 days of test completion. Test procedures for each equipment item must be submitted at least 45 days prior to the planned testing date and approved before testing begins. The Contracting Officer must receive at least 14 days' notice before tests are conducted. Testing applies to diesel-generator sets (15-300 KW standby), underground medium voltage cables and grounding systems, automatic transfer switches, and low voltage switchgear. Functional engine shutdown tests, vibration baseline tests, and load bank tests for generators are excluded and performed by the start-up engineer. Final system acceptance is contingent upon satisfactory completion of acceptance tests, and a testing organization representative must be present when tested equipment is initially energized.

View the file

Other files

File Type Posted
03 39 00.00 10.pdf PDF
03 62 16.pdf PDF
04 20 00.pdf PDF
05 21 00.pdf PDF
06 20 00.pdf PDF
06 61 16.pdf PDF
07 60 00.pdf PDF
07 61 14.00 20.pdf PDF
07 84 00.pdf PDF
07 92 00.pdf PDF
08 11 16.pdf PDF
08 36 13.pdf PDF
08 71 00.pdf PDF
09 68 00.pdf PDF
10 28 13.pdf PDF
13 48 00.pdf PDF
21 13 17.pdf PDF
22 00 00.pdf PDF
23 00 00.pdf PDF
23 08 00.pdf PDF
23 11 25.pdf PDF
23 35 00.pdf PDF
23 64 26.pdf PDF
23 82 16.00 40.pdf PDF
23 82 43.00 40.pdf PDF
26 56 00.pdf PDF
31 23 06.pdf PDF
32 01 14.pdf PDF
32 13 74.pdf PDF
02 41 00.pdf PDF
06 10 00.pdf PDF
07 12 00.pdf PDF
07 42 13.pdf PDF
07 42 63.pdf PDF
07 53 23.pdf PDF
07 54 19.pdf PDF
07 62 13.pdf PDF
08 41 13.pdf PDF
08 51 13.pdf PDF
08 51 23.pdf PDF
09 51 00.pdf PDF
00 71 00.pdf PDF
01 78 23.pdf PDF
00 72 00.pdf PDF
00 80 00.pdf PDF
Solicitation - FA813726R0030.pdf PDF
Att10_190023_SOW.pdf PDF
EAL List - BLANK to Contractors WWYK190023.xlsx XLSX spreadsheet
Att11_190023_Submittal Register_Final.pdf PDF
Wage Determination.pdf PDF
Show 40 more

50 files listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Ti nker AFB, OK TAFB Techni cal Spr ci f i cat i ons 2019

SECTI ON 26 08 00

APPARATUS I NSPECTI ON AND TESTI NG

04/17

PART 1 GENERAL

1. 1 REFERENCES

The publ i cat i ons l i s t ed bel ow f or m a par t of t hi s speci f i cat i on t o t he ext ent r ef er enced. The publ i cat i ons ar e r ef er r ed t o wi t hi n t he t ext by t he basi c desi gnat i on onl y.

I NTERNATI ONAL ELECTRI CAL TESTI NG ASSOCI ATI ON ( NETA)

NETA ATS ( 2013) St andar d f or Accept ance Test i ng Speci f i cat i ons f or El ect r i cal Power Equi pment and Syst ems

1. 2 RELATED REQUI REMENTS

Sect i on 26 00 00. 00 20 BASI C ELECTRI CAL MATERI ALS AND METHODS appl i es t o t hi s sect i on wi t h addi t i ons and modi f i cat i ons speci f i ed her ei n.

1. 3 SUBMITTALS

Gover nment appr oval i s r equi r ed al l submi t t al s. Submi t t he f ol l owi ng i n accor dance wi t h Sect i on 01 33 00 SUBMI TTAL PROCEDURES:

SD- 06 Test Repor t s

Accept ance t est s and i nspect i ons

SD- 07 Cer t i f i cat es

Qual i f i cat i ons of or gani zat i on, and l ead engi neer i ng t echni c i an

Accept ance t est and i nspect i ons pr ocedur e

1. 4 QUALI TY ASSURANCE

1. 4. 1 Qualifications

Cont r act or shal l engage t he ser vi ces of a qual i f i ed t est i ng or gani zat i on t o pr ovi de i nspect i on, t est i ng, cal i br at i on, and adj ust ment of t he el ect r i cal di st r i but i on syst em and gener at i on equi pment l i s t ed i n par agr aph ent i t l ed " Accept ance Test s and I nspect i ons" her ei n.

Or gani zat i on shal l be i ndependent of t he suppl i er , manuf act ur er , and i nst al l er of t he equi pment . The or gani zat i on shal l be a f i r st t i er subcont r act or . No wor k r equi r ed by t hi s sect i on of t he speci f i cat i on shal l be per f or med by a second t i er subcont r act or .

a. Submi t name and qual i f i cat i ons of or gani zat i on. Or gani zat i on shal l have been r egul ar l y engaged i n t he t est i ng of el ect r i cal mat er i al s, devi ces, i nst al l at i ons, and syst ems f or a mi ni mum of 5 year s. The or gani zat i on shal l have a cal i br at i on pr ogr am, and t est i nst r ument s used shal l be cal i br at ed i n accor dance wi t h NETA ATS.

Apr i l 2019 Page 1 SECTI ON 26 08 00

b. Submi t name and qual i f i cat i ons of t he l ead engi neer i ng t echni c i an per f or mi ng t he r equi r ed t est i ng ser vi ces. I ncl ude a l i s t of t hr ee compar abl e j obs per f or med by t he t echni c i an wi t h speci f i c names and t el ephone number s f or r ef er ence. Test i ng, i nspect i on, cal i br at i on, and adj ust ment s shal l be per f or med by an engi neer i ng t echni c i an, cer t i f i ed by NETA or t he Nat i onal I nst i t ut e f or Cer t i f i cat i on i n Engi neer i ng Technol ogi es ( NI CET) wi t h a mi ni mum of 5 year s ' exper i ence i nspect i ng, t est i ng, and cal i br at i ng el ect r i cal di st r i but i on and gener at i on equi pment , syst ems, and devi ces.

1. 4. 2 Accept ance Test s and I nspect i ons Repor t s

Submi t cer t i f i ed copi es of i nspect i on r epor t s and t est r epor t s. Repor t s shal l i ncl ude cer t i f i cat i on of compl i ance wi t h speci f i ed r equi r ement s, i dent i f y def i c i enci es, and r ecommend cor r ect i ve act i on when appr opr i at e.

Type and neat l y bi nd t est r epor t s t o f or m a par t of t he f i nal r ecor d.

Submi t t est r epor t s document i ng t he r esul t s of each t est not mor e t han 10 days af t er t est i s compl et ed.

1. 4. 3 Accept ance Test and I nspect i ons Pr ocedur e

Submi t t est pr ocedur e r epor t s f or each i t em of equi pment t o be f i el d t est ed at l east 45 days pr i or t o pl anned t est i ng dat e. Do not per f or m t est i ng unt i l af t er t est pr ocedur e has been appr oved.

PART 2 PRODUCTS

Not used.

PART 3 EXECUTI ON

3. 1 ACCEPTANCE TESTS AND I NSPECTI ONS

Test i ng or gani zat i on shal l per f or m accept ance t est s and i nspect i ons. Test met hods, pr ocedur es, and t est val ues shal l be per f or med and eval uat ed i n accor dance wi t h NETA ATS, t he manuf act ur er ' s r ecommendat i ons, and par agr aph ent i t l ed " Fi el d Qual i t y Cont r ol " of each appl i cabl e speci f i cat i on sect i on. Test s i dent i f i ed as opt i onal i n NETA ATS ar e not r equi r ed unl ess ot her wi se speci f i ed. Equi pment shal l be pl aced i n ser vi ce onl y af t er compl et i on of r equi r ed t est s and eval uat i on of t he t est r esul t s have been compl et ed. Cont r act or shal l suppl y t o t he t est i ng or gani zat i on compl et e set s of shop dr awi ngs, set t i ngs of adj ust abl e devi ces, and ot her i nf or mat i on necessar y f or an accur at e t est and i nspect i on of t he syst em pr i or t o t he per f or mance of any f i nal t est i ng. Cont r act i ng Of f i cer shal l be not i f i ed at l east 14 days i n advance of when t est s wi l l be conduct ed by t he t est i ng or gani zat i on. Per f or m accept ance t est s and i nspect i ons on appl i cabl e equi pment and syst ems speci f i ed i n t he f ol l owi ng sect i ons:

a. Sect i on 26 32 14. 00 10 DI ESEL- GENERATOR SET, STATI ONARY 15- 300 KW, STANDBY APPLI CATI ONS. Funct i onal engi ne shut down t est s, v i br at i on base- l i ne t est , and l oad bank t est shal l not be per f or med by t he t est i ng or gani zat i on. These t est s shal l be per f or med by t he st ar t - up engineer.

b. Sect i on 33 71 02 UNDERGROUND ELECTRI CAL DI STRI BUTI ON. Medi um vol t age cabl es and gr oundi ng syst ems onl y.

Apr i l 2019 Page 2 SECTI ON 26 08 00

c. Sect i on 26 36 00. 00 10 AUTOMATI C TRANSFER SWI TCHES

d. Sect i on 26 23 00 LOW VOLTAGE SWI TCHGEAR

3. 2 SYSTEM ACCEPTANCE

Fi nal accept ance of t he syst em i s cont i ngent upon sat i sf act or y compl et i on of accept ance t est s and i nspect i ons.

3. 3 PLACI NG EQUI PMENT I N SERVI CE

A r epr esent at i ve of t he appr oved t est i ng or gani zat i on shal l be pr esent when equi pment t est ed by t he or gani zat i on i s i ni t i al l y ener gi zed and pl aced i n ser vi ce.

- - End of Sect i on - -