RFI - Light Fixtures in Joist Ceiling RFI 26 COR.pdf

PDF 249 KB Posted

Attached to
TINKER AFB MAC BOA WWYK190068 REPAIR FIRE SUPPRESSION SYSTEM, B2280
Solicitation number
FA813725R0035
Issued by

About this file

This Request for Information (RFI) concerns the Repair Fire Suppression System project at Maintenance Hanger B2280 located at Tinker Air Force Base. The RFI addresses a technical issue with light fixture placement in the Fire Alarm Room, specifically regarding three 1'x4' light fixtures added by Amendment #04 that would clash with structural CFMF joists. The contractor requested clarification on whether the light fixture layout could be revised to parallel with the joists and fit between them to reduce structural modification costs.

The government's response, provided by Edward Cardona from HDR, recommends that the contractor provide a Lithonia ZL1D-L48-5000LM-FLTMVOLT-40K-8CRI-E10W-WH-WGZ48 lighting fixture and surface mount it to the gyp board ceiling, as indicated in an attached sketch. The RFI was submitted on 08/18/2025 by Chris Brezny from Nemecek Interior Construction and received a response on 09/12/2025, with the primary goal of resolving the lighting fixture installation challenge while minimizing additional structural work.

View the file

Other files

File Type Posted
Solicitation Amendment FA813725R00350009 SF 30.pdf PDF
Solicitation Amendment FA813725R00350008 SF 30.pdf PDF
Solicitation Amendment FA813725R00350009 SF 30.pdf PDF
190068_GOVT RESPONSE TO RFI 25A AND REDATED RESPONSE COR.pdf PDF
Solicitation Amendment FA813725R00350007 SF 30.pdf PDF
Solicitation Amendment FA813725R00350006 SF 30.pdf PDF
GOVERNMENT RESPONSE TO RFI 25_25A COR.pdf PDF
Capsol LED Text Displays - Capsol.pdf PDF
WWYK190068_RFI_23-24-25 SEP24.pdf PDF
CAPSOL-EXP-LEDM-Text-Display-Data-Sheet-V1.4.pdf_safe.pdf PDF
CAPSOL-LEDM-Text-Display-Data-Sheet_1.6.pdf PDF
Capsol Mini LED Text Displays - Capsol.pdf PDF
RFI 26 WWYK190068_Rev_1_26 51 00.pdf PDF
RFI 26 Fixture with Joist.pdf PDF
RFI 26 zl1d.pdf_safe.pdf PDF
Solicitation Amendment FA813725R00350005 SF 30.pdf PDF
Solicitation Amendment FA813725R00350004 SF 30.pdf PDF
190068_Attch04_Revised_Design_Analysis.pdf PDF
190068_Attch01_DRWG.pdf PDF
190068_Attch02_Revised_Submittal_Register.pdf PDF
Solicitation Amendment FA813725R00350003 SF 30.pdf PDF
Solicitation Amendment FA813725R00350002 SF 30.pdf PDF
000111_F1.pdf PDF
190068_DD100_Appendix A.pdf PDF
fire prot-01.pdf PDF
190068_DD100_Appendix B.pdf PDF
190068_PreBid RFI GOVT RESPONSE.pdf PDF
190068_IFC_Design Analysis_Final.pdf PDF
FP from DACA63-76-C-0111.pdf PDF
190068_TAFB_IFC_FINAL_SPECIFICATIONS.pdf PDF
UFGS 28 31 76.pdf_safe.pdf PDF
Solicitation Amendment FA813725R00350001 SF 30.pdf PDF
01 78 00.pdf PDF
Recovered Materials Determination Form.pdf PDF
01 78 23.pdf PDF
ufc_3_260_04_2018.pdf PDF
tinkerafb_INRMP_App E.pdf PDF
dafi91-202.pdf PDF
dafi13-213_tinkerafbsup.pdf PDF
EM_385-1-1.pdf PDF
007200_Attch7b_Monthly Hazardous Usage Report.pdf PDF
000_TABLE OF CONTENTS.pdf PDF
afman40-201.pdf PDF
007200_Attch14_Information for New Boilers.pdf PDF
Solicitation - FA813725R0035 for WWYK190068.pdf PDF
ufc_3_600_01_2016_c6.pdf PDF
afman32-7003.pdf PDF
dafi13-213.pdf PDF
00 80 00.pdf PDF
01 32 16.00 20.pdf PDF
Show 40 more

Latest 50 of 96 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

09/12/2025 Date

Response Desired

C:

File:

Attachments

Request for Information Project: Repair Fire Suppression System, Maintenance Hanger B2280 No.: 01 Date: 08/18/2025

Location:

From:

_Tinker Air Force Base

Nemecek Interior Construction

PM:

Chris Brezny

Phone No.: (405) 819-0309 Fax No.:

To: Action Requested: Clarification Direction

Approval Alternate Proposal

05 40 00 &

Reference: Drawing No.: A-401 & S-401 & E-401 Detail No.: Spec. Section: 26 51 00 Article:

RFI

Information Needed: Amendment #04 added (3) 1’x4’ Light Fixtures to the Fire Alarm Room per 1/E-401 & 1/A-401. These fixtures are recessed in the Fire Rated Ceiling and would clash with the structural CFMF Joists. Can the lights fixture layout be revised so they parallel with the joists and fit between the joists? These would eliminate significant structural changes to the joist ceiling, which would reduce costs. If the light fixtures cannot be relocated, please provide updated structural detail for blockout.

Submitted By: Chris Brezny

Proceed With Recommended Solution Additional Instructions to Follow

Recommendation: GOVERNMENT RESPOSE:

Contractor shall provide lighting fixture equal to Lithonia ZL1D-L48-5000LM-FLTMVOLT- 40K-8CRI-E10W-WH-WGZ48 and surface mount to gyp board ceiling as noted in the attached sketch.

Please also see attached cut sheet for the surface mounted lighting fixture.

Edward Cardona - HDR By

Attn:

Probable Effect:

Other:

Increase/Decrease Cost Increase/Decrease Time

No Change

1155531637C Highlight

1155531637C Highlight

1155531637C Text Box

RFI -026

1155531637C Text Box

05 40 00 &
Proceed With Recommended Solution Additional Instructions to Follow
2025-09-17T14:18:49-0500
MORRIS.MATTHEW.K.1385757456

File details come from the government source that posted it. Updated .