Elmendorf foam test graph bay 1-8.pdf
PDF 18 KB Posted
- Attached to
- FXSB 19-4014 Radiant Bay Heating 10682 9684
- Solicitation number
- FA500021R0038
About this file
This document contains results from foam testing conducted at Elmendorf Air Force Base. Foam testing was performed on eight separate aircraft hangar bays protected by Jet-X foam generators. Tests measured refractive index, pressure, flow rate and pattern for each hangar bay. Refractive index readings ranged from 1.3343 to 1.3344, within specifications. The tests were observed by representatives from Ansul and the Air Force to verify system operation and foam concentration levels.
The related federal contract opportunity is a solicitation from the Department of the Air Force Pacific Air Forces for radiant bay heating. No further details are provided on required products or services, response dates, or other salient information.
View the file
Other files
Show all 36
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FOAM TEST RESULTS
ELMENDORF AFB HANGAR 26
Date: Tuesday, June 29, 2010 TEST Bay Proportioner Nozzle Piezomtr/Pitot Actual *Refractive Test Discharge
Customer: Elmendorf AFB # Size Dia Pressure Flow Index Percent Duration
Location: Hangar 26 1 1 4" 1.3344 3-1/4% 60 seconds
Anchorage, AK 2 2 4" 1.3343 3% 60 seconds
Description: Aircraft hangar bays 1 - 8. Each 3 3 4" 1.3343 3% 60 seconds separately protected by (3) Jet-X 4 4 4" 1.3344 3-1/4% 60 seconds generators. 5 5 4" 1.3344 3-1/4% 60 seconds
Certification: Steve Frere 6 6 4" 1.3344 3-1/4% 60 seconds
Ansul Rep: Thomas Wolff 7 7 4" 1.3344 3-1/4% 60 seconds
8 8 4" 1.3344 3-1/4% 60 seconds
Refractive Samples:
Water 1.3330
0.50%
1%
1.50%
2% 1.3339
2.50%
3% 1.3343
3.50%
4%
4.50%
5% 1.3352
5.50%
6%
6.50%
7%
7.50%
8%
8.50%
9%
Concentrate: 2-3/4%
Ansul Jet-X
TEST DESCRIPTION: Each system was separately manually activated. Duration, operation of valves, flow and pattern were established through-out each hangar bay area. Foam percents were verified with a refractometer.
1.3326
1.3328
1.3330
1.3332
1.3334
1.3336
1.3338
1.3340
1.3342
1.3344
1.3346
1.3348
1.3350
1.3352
1.3354
Water 1% 2% 3% 4% 5% 6% 7% 8% 9%
R e fr a c ti v e I n d e x