This document contains the results of a field test of a fire pump. The field test was conducted on a AC Pump 1580 with a 125 HP motor at Blue Scope Constructon's 8 Bay Weather Shelter project in EAFB, AK. The pump was tested at various flows and pressures, including 750 GPM at 110 PSI, 1500 GPM at 102 PSI, and 2250 GPM at 74 PSI. The test results were compared to the manufacturer's certified curve and theoretical performance values. The document also lists settings for the pump's control panel, including jockey pressure points, timer settings, and alarm points. Additionally, the attached federal contract opportunity is a solicitation from the Department of the Air Force Pacific Air Forces for heating a radiant bay at FXSB. The solicitation includes attachments but provides no further description of the required products or services.
View the file
Other files
Show all 36
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Fire Pump Field Test
Fire Pump Equipment Information Customer Blue Scope Constructon
Pump AC Pump 1580 09-056124-01-01 1775 CW Project 8 Bay Weather Shelter,EAFB,AK
Motor Emerson P118699445 125 HP 1780 RPM 480vac 3 PHASE Theoretical points Certified/Shop Curve DATE 6/29/2010
Control Cutler-Hammer FD-90 LMR Plus 125 16B1917E 480vac GPM PSI GPM PSI TDH
0 111 0 120 50
PUMP TEST READINGS FOR PUMP No. 1 750 110 750 118 75 GMW Fire Protection
Manual Input 1500 102 1500 105 120 6108 Mckay
Pump Rating 1500 gpm @ 100 psi. Rated RPM= 1775 2250 74 130 Anchorage, AK 99518
Flow Orifice in. 1.75 1.75 1.75 Phone 336-5000 Fax 336-5050 Applied Coefficient 100 100 100
Hose Monster 100.00 Manual Input
PRESSURE READINGS
P it o t
N o
P it o t
N o
P it o t
N o
P it o t
N o
P it o t
N o
P it o t
N o
RPM % of Rated % of Rated Adjusted Adjusted V o lt s /2
V o lt s /3
V o lt s /3
A m p s
A m p s
A m p s
Suction Discharge Pitot Readings Reading Flow Net Head Capacity Net Head Flow Net Head
55 psi. 179 psi. 0 1793 0 124 0% 124% 0 124 467 469 468 67 59 70 Churn
50 psi. 174 psi. 33 1788 760 124 50% 121% 766 121 466 468 467 104 104 106 50%
40 psi. 147 psi. 34 34 1782 1552 107 103% 107% 1558 107 465 467 467 134 135 137 100%
41 psi. 138 psi. 34 34 35 1783 2333 97 155% 97% 2342 97 465 468 467 142 144 145 150%
Per NFPA# 20
Settings PSI
Jockey off 170
Jockey on 160
Timer 10 Mins
Main on 150
Main off 140
Sequential 10 Sec
Min run 10 Mins
Check List
Alignment GOOD
Voltage OK
Manual Starts x6 YES OK
Auto Starts x10x6 YES OK
Flow Test Hose Monste
Alarms Yes OK
Pump Running YES OK
Power YES OK
Common YES OK
Special
0 500 1000 1500 2000 2500
N e t A d ju s te d H e a d P
S I
Net Adjusted Flow GPM
Mfg. Curve
Test results
Theoretical