This document contains the results of a fire pump field test and information on a related federal contract opportunity. The field test results are for Pump 2 at the 7 Bay Weather Shelter project at Eielson Air Force Base in Alaska. Key details include the pump manufacturer and model, motor information, theoretical and test flow rates at various pressures, control panel information, and test readings showing the pump performing as expected per the manufacturer's rating of 1500 gpm at 100 psi.
The related federal contract opportunity is solicitation number FA500021R0038 for heating a radiant bay at Eielson Air Force Base. The opportunity is being issued by the Department of the Air Force Pacific Air Forces for an unspecified description as the opportunity details are provided in attachments. No further information is included in the document regarding the requirements, response date, or award date.
View the file
Other files
Show all 36
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Fire Pump Field Test
Fire Pump Equipment Information Customer Blue Scope Constructon
Pump AC Pump 1580 09-056-125-01-01 1775 CW Project 7 Bay Weather Shelter,EAFB,AK
Motor Emerson P1186994445 125 HP 1780 RPM 480vac 3 PHASE Theoretical points Certified/Shop Curve DATE 6/29/2010
Control Cutler-Hammer FD-90 LMR Plus 125 16B-1915E 480vac GPM PSI GPM PSI TDH
0 111 0 118 50
PUMP TEST READINGS FOR PUMP No. 2 750 110 750 118 85 GMW Fire Protection
Manual Input 1500 102 1500 104 120 6108 Mckay
Pump Rating 1500 gpm @ 100 psi. Rated RPM= 1775 2250 78 130 Anchorage, AK 99518
Flow Orifice in. 1.75 1.75 1.75 Phone 336-5000 Fax 336-5050 Applied Coefficient 100 100 100
Hose Monster 100.00 Manual Input
PRESSURE READINGS
P it o t
N o
P it o t
N o
P it o t
N o
P it o t
N o
P it o t
N o
P it o t
N o
RPM % of Rated % of Rated Adjusted Adjusted V o lt s /2
V o lt s /3
V o lt s /3
A m p s
A m p s
A m p s
Suction Discharge Pitot Readings Reading Flow Net Head Capacity Net Head Flow Net Head
50 psi. 174 psi. 0 1794 0 124 0% 124% 0 124 469 471 471 66 68 70 Churn
48 psi. 169 psi. 33 1787 760 121 50% 121% 765 121 468 470 471 99 100 102 50%
42 psi. 153 psi. 34 34 1784 1552 111 104% 111% 1562 111 468 470 470 131 133 135 100%
36 psi. 130 psi. 34 34 35 1783 2333 94 155% 94% 2325 94 468 469 470 144 146 149 150%
Per NFPA# 20
Settings PSI
Jockey off 170
Jockey on 160
Timer 10 Mins
Main on 150
Main off 140
Sequential 10 Sec
Min run 10 Mins
Check List
Alignment GOOD
Voltage OK
Manual Starts x6 YES OK
Auto Starts x10x6 YES OK
Flow Test Hose Monste
Alarms Yes OK
Pump Running YES OK
Power YES OK
Common YES OK
Special
0 500 1000 1500 2000 2500
N e t A d ju s te d H e a d P
S I
Net Adjusted Flow GPM
Mfg. Curve
Test results
Theoretical