This document contains a fill report for an Ansul fire suppression system at Elmendorf Air Force Base and information on a related federal contract opportunity. The fill report details the refilling of a 200 gallon Ansul Jet-X foam system protecting aircraft hangar bays 9 through 15 at Elmendorf AFB. Each bay is protected by three Jet-X-15A high-expansion generators, with the controller located approximately 15 to 20 feet from the top concentrate discharge of the foam tank. The system was tested by GMW Fire Protection and found to meet 3% foam quality standards. Additionally, the report provides the solicitation number and name for an opportunity with the Department of the Air Force Pacific Air Forces to provide radiant bay heating at facilities 10682 and 9684, though no further details are included on products or services required under this contract.
View the file
Other files
Show all 36
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FILLING SERVICE REPORT
ANSUL REP: Thomas Wolff DATE: Tuesday, June 29, 2010
SOLD TO: Ansul, Inc. JOB NO: #2253
One Stanton Street CONTACT: Troy Wiltbank
Marinette, WI 54143-2542 PHONE: 253-306-4296
INSTALLATION CONTRACTOR: GMW Fire Protection CONTACT: Clayton Johnson
6108 McKay Street PHONE: 907-336-5000
Anchorage, AK 99501 EMAIL:
SIZE: 200 HA/VA VA SERIAL# 107268 CONTROLLER: (7) 4"
CONCENTRATE: Ansul Jet X TYPE: Hi-ex %: 2-3/4% FILL AUTHORIZATION Troy Wiltbank COMPANY Tyco Fire Suppression & Building Products
FILL LOCATION:
NAME OF USER: Elmendorf AFB
ADDRESS: Hangar 24 CONTACT: Steve Frere
Anchorage, AK PHONE: 907-552-9955
DESCRIPTION OF SYSTEM: Aircraft hangar bays: 9 - 15. Each protected by (3) Jet-X-15A hi-ex generators.
CONTROLLER LOCATED: Approximate 15 to 20' away from top concentrate discharge of foam tank.
FILL PROCEDURE: GALLONS FILLED: Filled by GMW Fire Protection
SYSTEM: PRESSURIZED: XX NON-PRESSURIZED RELIEF VALVE:
ISOLATION VALVE Hydraulic actuator DELUGE VALVE:
TEST DESCRIPTION See attached foam test results.
TEST RESULTS: 3% XX 6% OTHER
UNIT TOPPED OFF: YES XX NO # OF GALLONS Refilled by GMW Fire Protection
CUSTOMER CERTIFICATION: FILL/TEST BY: Steve Frere DATE: 6/29/10
ANSUL CERTIFICATION: FILL/TEST BY: Thomas Wolff DATE: 6/29/10
OPERATION MANUAL RECEIVED BY: DATE:
COMPANY:
NOTES: 1. Actual estimated capacity of the tank is approx. 220 gallons.
2. In accordance with NFPA 11, chapter 7 and NFPA 25, table 8-2: an annual inspection of the system is required.