8 Bay Pump 2 field test.pdf
PDF 36 KB Posted
- Attached to
- FXSB 19-4014 Radiant Bay Heating 10682 9684
- Solicitation number
- FA500021R0038
About this file
This document contains the results of a field test of a fire pump. The field test was conducted on a AC Pump 1580 with a 125 HP motor at Blue Scope Constructon's 8 Bay Weather Shelter project in EAFB, AK. The pump was tested at various flows and pressures, including 750 GPM at 110 PSI, 1500 GPM at 102 PSI, and 2250 GPM at 74 PSI. Readings were taken from six pitot tubes and the results were recorded on a chart showing net adjusted head versus net adjusted flow. The test confirmed the pump meets its rated capacity of 1500 GPM at 100 PSI at 1775 RPM, as specified in the McKay Pump rating. The test results indicate the pump is performing as expected according to its theoretical and manufacturer curves.
The related federal contract opportunity is a solicitation from the Department of the Air Force Pacific Air Forces for FXSB 19-4014 Radiant Bay Heating 10682 9684. No further details are provided in the document about the products or services required under the solicitation.
View the file
Other files
Show all 36
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Fire Pump Field Test
Fire Pump Equipment Information Customer Blue Scope Constructon
Pump AC Pump 1580 09-056124-01-02 1775 CW Project 8 Bay Weather Shelter,EAFB,AK
Motor Emerson P118699446 125 HP 1780 RPM 480vac 3 PHASE Theoretical points Certified/Shop Curve DATE 6/29/2010
Control Cutler-Hammer FD-90 LMR Plus 125 16B1917E 480vac GPM PSI GPM PSI TDH
0 111 0 122 50
PUMP TEST READINGS FOR PUMP No. 2 750 110 750 118 90 GMW Fire Protection
Manual Input 1500 102 1500 104 110 6108 Mckay
Pump Rating 1500 gpm @ 100 psi. Rated RPM= 1775 2250 74 125 Anchorage, AK 99518
Flow Orifice in. 1.75 1.75 1.75 Phone 336-5000 Fax 336-5050 Applied Coefficient 100 100 100
Hose Monster 100.00 Manual Input
PRESSURE READINGS
P it o t
N o
P it o t
N o
P it o t
N o
P it o t
N o
P it o t
N o
P it o t
N o
RPM % of Rated % of Rated Adjusted Adjusted V o lt s /2
V o lt s /3
V o lt s /3
A m p s
A m p s
A m p s
Suction Discharge Pitot Readings Reading Flow Net Head Capacity Net Head Flow Net Head
55 psi. 173 psi. 0 1793 0 118 0% 118% 0 118 467 470 469 66 67 70 Churn
50 psi. 173 psi. 33 1788 760 123 50% 123% 766 123 467 469 469 104 106 106 50%
39 psi. 145 psi. 34 34 1782 1552 106 103% 106% 1558 103 466 469 469 131 134 135 100%
38 psi. 130 psi. 34 34 35 1783 2333 92 155% 92% 2342 92 466 469 468 141 143 144 150%
Per NFPA# 20
Settings PSI
Jockey off 170
Jockey on 160
Timer 10 Mins
Main on 150
Main off 140
Sequential 10 Sec
Min run 10 Mins
Check List
Alignment GOOD
Voltage OK
Manual Starts x6 YES OK
Auto Starts x10x6 YES OK
Flow Test Hose Monste
Alarms Yes OK
Pump Running YES OK
Power YES OK
Common YES OK
Special
0 500 1000 1500 2000 2500
N e t A d ju s te d H e a d P
S I
Net Adjusted Flow GPM
Mfg. Curve
Test results
Theoretical
File details come from the government source that posted it. Updated .