8_Nellis-Creech Lighting Req 2019-01-22.pdf

PDF 31 KB Posted

Attached to
SABER IDIQ
Solicitation number
FA486125R0003
Issued by

About this file

This document is an Installation Facilities Standards (IFS) appendix for lighting requirements at Nellis and Creech Air Force Bases, dated 22 Jan 2019. The comprehensive guidelines specify detailed technical requirements for all interior and exterior lighting fixtures, mandating solid-state LED luminaires with specific performance characteristics, including color temperature between 4000K-4500K, minimum 10-year luminaire warranty, 50,000-hour rated life, and integrated motion/photocell controls for energy efficiency.

Key technical specifications include requirements for different lighting environments such as interior fixtures (20 feet or less above floor), high bay fixtures (over 20 feet), exterior street/parking lot fixtures, wall pack and walkway fixtures, area/security lighting, and airfield/apron lighting. All fixtures must be compatible with CCTV and night vision equipment, meet security and force protection standards, and incorporate energy-saving features like automatic dimming, motion sensors, and photocell controls. Prohibited are T-8, T-5, induction, and high-intensity discharge fixtures, with a strong emphasis on LED technology and adaptive lighting management across various operational spaces.

View the file

Other files

File Type Posted
51_RFI Log_ SABER Seed RKMF 2400010 Reno Honor Guard 99 FSS B10250.xlsx XLSX spreadsheet
45 - Attachment Contract Information Sheet.pdf PDF
44 - SABER SOO RKMF240010 Renovate Honor Guard 99 FSS B10250_14Feb2025.pdf PDF
36 - AF 3000 Material Approval Submittal - 01 Sep 2003.pdf PDF
33 - AF Form 3065 Progress Report Template - 01 Apr 1996.pdf PDF
30 - AF Form 103 Base Civil Engineering Work Clearance Request - 01 Aug 1994.pdf PDF
28 - Nuclear Gauge Form 1.xlsx XLSX spreadsheet
22_RUS Bulletin 1728F-806 UG Main VEA Standard - 18 October 2018.pdf PDF
20_UT1-UT5 Modified Trenching Drawing - Aug 2016.pdf PDF
15 - Hazardous Material Management Guidance Document 2023-06-03.pdf PDF
14_ACC Sole Source EMCS Letter.pdf PDF
10_Nellis-Creech Utility Meter Req 2019-09-13.pdf PDF
2 - Price Schedule 23 September 25.pdf PDF
49 - As-Builts.pdf PDF
48 - Example SABER Design Intent Drawing Sets_28 Nov.pdf PDF
47 - Example SABER Design Intent Drawing Set Level 2_20 Nov.pdf PDF
41 - General Decision Number_NV20240038 Building Clark County.pdf PDF
39 - Form SS-PER-007-003 Internal Combustion Engine Worksheet.pdf PDF
37 - BUILDER Inventory Sheet.xlsx XLSX spreadsheet
35 - AF 66 Schedule of Material Submittals.xlsx XLSX spreadsheet
32 - AF 3064 Progress Schedule Template - 01 Apr 1996.xlsx XLSX spreadsheet
27 - NTTR Visit Request - 27 Jan 2023.pdf PDF
25 - UH1.2 - Grounding Assembly for Pad-mounted Transformers and Enclosures 2 Rods - Aug 2016.pdf PDF
19_UF3.PC Concrete Pad for Three Phase Requirement - Aug 2016.pdf PDF
13 - Work Clearance Triggers.pdf PDF
6 - Nellis-Creech Comm Req NC 2710 - Jun 2023.pdf PDF
3 - Self Score Worksheet SABER_23 Sept 2025.xlsx XLSX spreadsheet
34 - Schedule of Values Template.xlsx XLSX spreadsheet
1 - SABER SOW 25 Sep 25.pdf PDF
23_Power Trench Sand and Backfill Requirements - Apr 2013.pdf PDF
52 - 99 SFS - Mass Pass Request Template.xlsx XLSX spreadsheet
Atch 50_RFI Log_General Solicitation and Non-SABER Seed Related Questions.xlsx XLSX spreadsheet
42 - General Decision Number NV20240001 Bldg NTTR.pdf PDF
40 - General Decision Number NV20240058 Highway Clark County.pdf PDF
31 - AF Form 3052 Cost Estimate Template.xlsx XLSX spreadsheet
24_UG3.3 Three Phase Six Bushing Pad-mounted Transformer - Aug 2016.pdf PDF
18 - Nellis Supplement to DAFI 31-218 Motor Vehicle Traffic Supervision - 23 Mar 2023.pdf PDF
17 - Installation Plan 12 - Hazardous Waste Management Plan 27 Sep 23.pdf PDF
16_USAF Integrated Cultural Resources Mgmt Plan 32-7065 ICRMP - 06 Nov 2019.pdf PDF
9_Nellis-Creech Mech-Plumb Req 2020-07-07.pdf PDF
Solicitation - FA486125R0003.pdf PDF
46 - Example SABER Design Intent Drawing Set Level 1_20 Nov.pdf PDF
43 - General Decision Number_NV20250024 Heavy Clark County.pdf PDF
38_NTTR Automated Information System _AIS_ Equipment Form.pdf PDF
29 - Nuclear Gauge Form 2.docx DOCX document
26 - Connection Charge Agreement - 22 Feb 23.pdf PDF
21_US3.PJ Single and Three Phase Primary Junctions - Aug 2016.pdf PDF
12 - Env Permit-ATP Guidance 2023.pdf PDF
11_Nellis-Creech Plant List.pdf PDF
7 - Nellis-Creech Electrical Req 2023-10-17.pdf PDF
Show 40 more

50 files listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

NELLIS AND CREECH AFB

INSTALLATION FACILITIES STANDARDS (IFS)

LIGHTING REQUIREMENTS

22 JAN 2019

This document is an appendix to Nellis & Creech Air Force Bases IFS which is located here:

https://www.wbdg.org/ffc/af-afcec/installation-facilities-standards-ifs/nellis-creech-afb-ifs

1. Codes and Standards: All design and construction shall be in compliance with the most recent versions of the following:

Nellis & Creech Air Force Bases Installation Facilities Standards (IFS) Unified Facilities Criteria (UFC) 3-530-01 Design: Interior, Exterior Lighting and

Controls Unified Facilities Guide Specification (UFGS) 26 51 00.00 40 for interior lighting UFGS 26 56 00 for exterior lighting UFGS 26 56 19.00 40 for roadway lighting UFGS 26 56 23.00 40 for area lighting UFGS 26 56 36 00 40 for flood lighting UFGS 26 56 20.00 10 for airfield and heliport lighting AFI 31-101 Integrated Defense for security applications

2. All interior and exterior lighting fixtures shall comply with the following:

2.1 Fixtures shall be solid-state LED luminaires designed specifically for LED technologies (typically flat to compliment the directional characteristics of LEDs) with integrated controls and remote lighting level adjustment/dimming capabilities.

2.2 Fixtures shall have a color temperature in KELVIN of between 4000K and 4500K.

Fixtures shall have appropriate illumination volume (foot candle/lumen) output to meet work surface UFC guidelines per fixture/space photometric analysis (using typical manufacturer software).

2.3 LED Luminaires shall have a minimum warranty of 10 years.

2.4 LED Drivers shall have a minimum warranty of 5 years.

2.5 Ballasts and lamps shall have a minimum rated life of 50,000 hours.

2.6 Fixtures shall be rated to operate at ambient temperatures between 0 degrees F and

120 degrees F or higher. This requirement does not apply to Interior Recessed, Downlight, and Wall Wash Fixtures.

2.7 T-8, T-5, Induction, and High Intensity Discharge fixtures are prohibited.

https://www.wbdg.org/ffc/af-afcec/installation-facilities-standards-ifs/nellis-creech-afb-ifs

2.8 All interior (and all practicable exterior) facility lighting fixtures shall be controlled by motion detectors. Any exceptions shall be requested by Contractor for approval by the Contracting Officer. No exceptions will be made for restroom and conference room fixtures. Wall switches shall be installed to turn sensors/lights on and off as needed (i.e. lights off in a conference room in order to view wall screens). Sensors shall be placed in a location not affected by movement outside of open doorways.

Daylighting wall switches shall be installed to allow dimming/turn-off of fixtures located nearest to windows, hangar/truck doors or similar daylighting sources. This may also be accomplished with photocell controls for automatic dimming/turn-off.

3. Interior Fixtures located 20 feet or less above finished floor:

3.1 Luminaires shall be solid-state LED Luminaires (preferably flat plate as opposed to

Silver Bowl, recessed, or light scattering fixtures) with full remote dimming controls.

3.2 LED linear replacements for existing fluorescent fixtures may be used provided that the following conditions are met:

3.2.1 The existing ballast shall be replaced with LED Driver or electronic ballast specifically for LED applications.

3.2.2 Fixtures shall have a color temperature as indicated in 2.2. Other color temperatures may be considered in housing applications, hospitality applications, and in maintenance facilities. See UFC 3-530-01 for additional information.

3.3 Provide wire guards for all open LED linear replacements.

4. Interior High Bay Fixtures located higher than 20 feet above work surface:

Each fixture shall have on/off motion sensors (with partial shutoff delay before full off), and be remotely adjustable (infrared or Bluetooth) light output/on-off control.

5. Exterior Street and Parking Lot Fixtures:

5.1 All street and parking lot light fixtures shall include appropriate controls for dusk till dawn photocells (one photocell per fixture). Parking area fixtures shall have automatic dimming for late-night to dawn operation to increase energy savings when parking lots are typically vacant.

5.2 Glass fixture lens are preferred.

6. Exterior Wall Pack and Walkway Fixtures:

6.1 All wall pack lighting fixtures shall include dusk till dawn photocells; wall-packs away from ingress/egress points and not illuminating Air Force assets (mechanical and electrical equipment, trash enclosures, etc.) shall also have motion sensor controls to eliminate energy waste and night sky pollution.

6.2 All walkway lighting fixtures shall include dusk till dawn photocells.

6.3 Glass fixture lens are preferred.

6.4 Light bollards shall be full cutoff type and vandal resistant. Bollards shall not have exposed vertical plastic/acrylic lens. Electrical service shall be 208v maximum with 120v to ground.

7. Exterior Area, Flood, Canopy, and Security Lighting Fixtures:

7.1 As appropriate, Contractor shall obtain lighting design approval from base Security

Forces and/or base Antiterrorism Force Protection (ATFP) office.

7.2 Fixtures shall be compatible with CCTV, and night vision goggles.

7.3 Fixtures shall meet appropriate illumination requirements for security and ATFP.

7.4 Certain large area security lighting applications may employ individual fixture motion sensor on-controls to identify intrusion points with lighting where otherwise fixtures remain off, saving energy.

7.5 Automatic dimming/on-off and motion sensors shall be used to allow energy savings during low use times while maintaining some illumination for adequate security when dimmed.

8. Exterior Airfield / Apron Lighting Fixtures:

8.1 As appropriate, Contractor shall obtain lighting design approval from Airfield

Operations office, base Security Forces, and/or base ATFP office.

8.1.1 Fixtures shall be compatible with CCTV, and night vision goggles.

8.1.2 Fixtures shall meet appropriate illumination requirements for aircraft and equipment operations and ATFP/security.

8.2 Glass fixture lens are preferred.

8.3 Automatic Bi-level dimming with occupancy sensors shall be explored to allow energy savings when lights are used infrequently, or when instant-on LED capabilities enhance security achievement. Certain locations (i.e. personnel/vehicle doors or gates) shall have motion sensors that only dim lighting to maintain access point illumination.

9. Reference separate Nellis-Creech IFS appendix document for non-lighting Electrical

Requirements.

END OF LIGHTING REQUIREMENTS