19_UF3.PC Concrete Pad for Three Phase Requirement - Aug 2016.pdf
PDF 29 KB Posted
- Attached to
- SABER IDIQ
- Solicitation number
- FA486125R0003
About this file
This document is a technical drawing specification for a concrete pad design for three-phase electrical equipment. The drawing provides detailed dimensions and reinforcement requirements for two pad sizes (#1 and #2) accommodating transformers ranging from 75 to 2500 kVA.
Key specifications include: concrete testing requirements of 3000 pounds minimum per square inch with 4-6% entrained air, reinforcing steel (ATSM-A615 Grade 60) placed approximately 6" on center, and a minimum 2-inch concrete cover over reinforcing steel. The pad dimensions and rebar spacing are designed to be adjustable based on specific transformer size and weight. The drawing includes precise measurements for pad length (A), width (B), and other critical dimensions, along with specific reinforcing bar configurations for each pad size (MK1-MK5 locations). The technical drawing is dated August 2016 and coded as UF3.PC for three-phase primary equipment installation.