FNWZ 99-0013
PROJECT TITLE
BUILDING 7232 (425 3RD ST.) & 7233 (417 3RD ST.)
PROJECT LOCATION
Bldg. 7232
SECURITY POLICE
Bldg. 6117
CONTRACTOR'S ACCESS
(TYE GATE)
HAUL ROAD ROUTE
MAIN GATE
PROJECT NUMBER
Bldg. 7233
DESIGN REPAIR FOR HVAC SYSTEM
SIGNATURE OFFICE
COORDINATION
APPROVED
Jacobs Engineering Group Inc.
Texas Registered Engineering Firm F-2966 777 Main Street P.O. Box 901058 Fort Worth, TX 76102
REVISION BY/DATE
FNWZ 99-0013
S.MITCHELL
04/08/15
R E
G I S
TERED ARCH
I T E
C T
S
T A T E O F T EXA
S
W
IL
L IAM R . PETERSON
1 7 4 0 3
S.LINDQUIST
W. PETERSON
SHEET INDEX
SEQ SHEET NO. SHEET TITLE
COVER SHEET
SEQUENCE OF BUILDING CONSTRUCTION
LIFE SAFETY PLANS
GENERAL NOTES SYMBOLS AND ABBREVIATIONS
1ST AND 2ND FLOOR PLANS
3RD FLOOR PLAN AND DETAILS
EXTERIOR ELEVATIONS AND DETAILS
INTAKE PILASTER DETAILS
FIRE PROTECTION GENERAL NOTES
1ST AND 2ND FLOOR FIRE PROTECTION PLANS
3RD FLOOR FIRE PROTECTION PLAN
MECHANICAL SITE PLAN
CENTRAL PLANT PLAN
1ST FLOOR DEMOLITION PLAN
2ND FLOOR DEMOLITION PLAN
3RD FLOOR DEMOLITIONPLAN
1ST FLOOR HVAC PLAN
2ND FLOOR HVAC PLAN
3RD FLOOR HVAC PLAN
ATTIC HVAC PLAN
MECHANICAL DETAILS
MECHANICAL DETAILS
MECHANICAL DETAILS
MECHANICAL SCHEDULES
PIPING FLOW DIAGRAM
PIPING FLOW DIAGRAM
CONTROLS
CONTROLS
1ST FLOOR ELECTRICAL PLAN
2ND FLOOR ELECTRICAL PLAN
3RD FLOOR ELECTRICAL PLAN
ELECTRICAL SCHEDULES
ELECTRICAL SCHEDULES
G-001 01
PROJECT COVER
SHEET
FACILITY
7232 & 7233
OF
01 PROJECT COVER SHEETG-000
G-000 03 723202 G-001 03 723203 G-002 03 723204 A-001 05
A-101 A-102 A-201 A-301
03723209 F-001 03723210 F-101 03723211 F-102
GENERAL NOTES SYMBOLS AND ABBREVIATIONS
GENERAL NOTES SYMBOLS AND ABBREVIATIONS
18723212 M-001 187232 187232 187232 187232 187232 187232 187232 187232 187232 187232 187232 187232 187232 187232 187232 187232 187232
MPE-101
MPE-102
MD-101
MD-102
MD-103
MH-101
MH-102
MH-103
MH-104
M-501 M-502 M-503 M-601 M-701 M-702 M-801 M-802 E-001 E-101 E-102 E-103 E-601 E-602
7233 COVER SHEET
SEQUENCE OF BUILDING CONSTRUCTION
LIFE SAFETY PLANS
GENERAL NOTES SYMBOLS AND ABBREVIATIONS
1ST AND 2ND FLOOR PLANS
3RD FLOOR PLAN AND DETAILS
EXTERIOR ELEVATIONS AND DETAILS
INTAKE PILASTER DETAILS
FIRE PROTECTION GENERAL NOTES
1ST AND 2ND FLOOR FIRE PROTECTION PLANS
3RD FLOOR FIRE PROTECTION PLAN
MECHANICAL SITE PLAN
CENTRAL PLANT PLAN
1ST FLOOR DEMOLITION PLAN
2ND FLOOR DEMOLITION PLAN
3RD FLOOR DEMOLITIONPLAN
1ST FLOOR HVAC PLAN
2ND FLOOR HVAC PLAN
3RD FLOOR HVAC PLAN
ATTIC HVAC PLAN
MECHANICAL DETAILS
MECHANICAL DETAILS
MECHANICAL DETAILS
MECHANICAL SCHEDULES
PIPING FLOW DIAGRAM
PIPING FLOW DIAGRAM
CONTROLS
CONTROLS
1ST FLOOR ELECTRICAL PLAN
2ND FLOOR ELECTRICAL PLAN
3RD FLOOR ELECTRICAL PLAN
ELECTRICAL SCHEDULES
ELECTRICAL SCHEDULES
G-000 03 G-001 03 G-002 03 A-001 05
A-101 A-102 A-201 A-301
03F-001 03F-101 03F-102
GENERAL NOTES SYMBOLS AND ABBREVIATIONS
GENERAL NOTES SYMBOLS AND ABBREVIATIONS
18M-001
MPE-101
MPE-102
MD-101
MD-102
MD-103
MH-101
MH-102
MH-103
MH-104
M-501 M-502 M-503 M-601 M-701 M-702 M-801 M-802 E-001 E-101 E-102 E-103 E-601 E-602
1392454892C Typewritten Text Bldg 7223
1392454892C Oval
1392454892C Polygonal Line
AREA MAP
FNWZ 99-0013
PROJECT TITLE
BUILDING 7232 (425 3RD ST.)
L
DYESS AFB
ABILENE
PROJECT LOCATION
Bldg. 7232
SECURITY POLICE
Bldg. 6117
CONTRACTOR'S ACCESS
(TYE GATE)
HAUL ROAD ROUTE
MAIN GATE
PROJECT NUMBER
I-20 I-20
LO
OP
Bldg. 7233
DESIGN REPAIR FOR HVAC SYSTEM
APPROVED
Jacobs Engineering Group Inc.
Texas Registered Engineering Firm F-2966 777 Main Street P.O. Box 901058 Fort Worth, TX 76102
REVISION BY/DATE
FNWZ 99-0013
S.MITCHELL
04/08/15
R E
G I S
TERED ARCH
I T E
C T
S
T A T E O F T EXA
S
W
IL
L IAM R . PETERSON
1 7 4 0 3
S.LINDQUIST
W. PETERSON
SHEET INDEX
SEQ SHEET NO. SHEET TITLE
GENERAL
01 G-000 COVER SHEET
02 G-001 SEQUENCE OF BUILDING CONSTRUCTION
03 G-002 LIFE SAFETY PLANS
ARCHITECTURAL
04 A-001 GENERAL NOTES SYMBOLS AND ABBREVIATIONS
05 A-101 1ST AND 2ND FLOOR PLANS
06 A-102 3RD FLOOR PLAN AND DETAILS
07 A-201 EXTERIOR ELEVATIONS AND DETAILS
08 A-301 INTAKE PILASTER DETAILS
FIRE PROTECTION
09 F-001 FIRE PROTECTION GENERAL NOTES
10 F-101 1ST AND 2ND FLOOR FIRE PROTECTION PLANS
11 F-102 3RD FLOOR FIRE PROTECTION PLAN
MECHANICAL
12 M-001 GENERAL NOTES
13 MPE-101 MECHANICAL SITE PLAN
14 MPE-102 CENTRAL PLANT PLAN
15 MD-101 1ST FLOOR DEMOLITION PLAN
16 MD-102 2ND FLOOR DEMOLITION PLAN
17 MD-103 3RD FLOOR DEMOLITIONPLAN
18 MH-101 1ST FLOOR HVAC PLAN
19 MH-102 2ND FLOOR HVAC PLAN
20 MH-103 3RD FLOOR HVAC PLAN
21 MH-104 ATTIC HVAC PLAN
22 M-501 MECHANICAL DETAILS
23 M-502 MECHANICAL DETAILS
24 M-503 MECHANICAL DETAILS
25 M-601 MECHANICAL SCHEDULES
26 M-701 PIPING FLOW DIAGRAM
27 M-702 PIPING FLOW DIAGRAM
28 M-801 CONTROLS
29 M-802 CONTROLS
ELECTRICAL
30 E-001 GENERAL NOTES
31 E-101 1ST FLOOR ELECTRICAL PLAN
32 E-102 2ND FLOOR ELECTRICAL PLAN
33 E-103 3RD FLOOR ELECTRICAL PLAN
34 E-601 ELECTRICAL SCHEDULES
35 E-602 ELECTRICAL SCHEDULES
10. PAINT ALL EXPOSED NEW FIRE SUPPRESSION SYSTEM PIPING, VALVES, AND EQUIPMENT EXCEPT IN THE CONCEALED SPACE ABOVE THE CEILING. PAINT ALL NEW EXPOSED INTERIOR AND EXTERIOR MASONRY, GALVANIZED SHEET METAL DUCTWORK, PIPING, CONDUIT, EQUIPMENT, AND SUPPORTS WITH EXCEPTION TO FACTORY PAINTED EQUIPMENT AND ENCLOSURES.
11. DEMOLISH ALL EXISTING MECHANICAL AND ELECTRICAL DEVICES, CONDUIT, AND WIRING RENDERED UNUSABLE BY CONSTRUCTION WORK PERFORMED IN THIS PROJECT. DEMOLITION SHALL
EXTEND BACK TO THE SOURCE THAT SERVES THE LOAD.
12. REPLACE ALL CEILINGS INDICATED TO BE DEMOLISHED WITH NEW LAY-IN OR FINISHED GYP BOARD CEILING OF SIMILAR TYPE AS THE EXISTING OR AS OTHERWISE INDICATED OR SCHEDULED. REPLACE THE CEILING IN DAMP AREAS WITH MOISTURE RESISTANT GYP BOARD AND FINISHED WITH EPOXY PAINT. CONTRACTOR SHALL PATCH, PAINT, AND FINISH THE ENTIRE WALL OR PORTION OF THE WALL IN THE RESPECTIVE ROOM AS NECESSARY TO MATCH EXISTING PAINT AND FINISH IN AREAS WHERE NEW CEILING HEIGHT DIFFERS FROM THE EXISTING.
13. MEASURE THE EXISTING FULL LOAD CURRENT FOR EACH CIRCUIT BREAKER IN EXISTING DISTRIBUTION PANEL WHERE EXISTING LOADS ARE NOT SHOWN. SHOW MEASURED VALUES ON THE AS-BUILT DRAWING PANEL SCHEDULE. NOTIFY THE GOVERNMENT FOR FURTHER ACTION IF THE TOTAL MEASURED LOAD EXCEEDS THE ALLOWABLE LOAD FOR THE PANEL RATING.
14. AN ASBESTOS SURVEY HAS BEEN CONDUCTED AND IS INCLUDED IN THE APPENDIX TO THE SPECIFICATIONS. THE CONTRACTOR SHALL SUBMIT A PRICE PROPOSAL WITH QUANTITY OF ACM THE IS ANTICIPATED TO BE ABATED. SECTION 01560 ENVIRONMENTAL PROTECTION STATES THE REQUIREMENTS FOR SAFE HANDLING AND DISPOSAL OF ACM. ALL ABATEMENT, TRANSPORTATION, DISPOSAL, AND FEES ARE TO BE INCLUDED AS PART OF THIS CONSTRUCTION PACKAGE.
GENERAL SCOPE AND WORKING CONDITIONS NOTES:
1. GENERAL SCOPE OF WORK IN THIS PROJECT CONSIST OF REPAIRING, REMOVING AND REPLACING
THE BUILDING HVAC SYSTEM.
2. BUILDING IS TO REMAIN OCCUPIED DURING CONSTRUCTION, WORK PHASING IS REQUIRED.
CONTRACTOR IS TO COORDINATE WORK WITH BCE TO DETERMINE RELEASE OF BUILDING AREAS
FOR CONSTRUCTION.
3. GENERAL CONTRACTOR TO PROVIDE TEMPORARY DUST PROTECTION BETWEEN AREAS UNDER
CONSTRUCTION DURING WORK.
4. CONTRACTOR IS TO NOT INHIBIT NORMAL BASE OPERATIONS. THIS INCLUDES TRAFFIC FLOW.
CONTRACTOR TO SUBMIT A TRAFFIC CONTROL PLAN PRIOR TO ANY REPAIRS THAT WILL CAUSE
CONGESTION.
5. CONTRACTOR IS TO OBTAIN A DIG PERMIT AT ALL LOCATIONS PRIOR TO DIGGING FROM DYESS AFB
COMMUNICATIONS SQUADRON.
GENERAL NOTES:
1. CONTRACTOR MAY CONTACT ONLY THE BASE CONTRACTING OFFICE - 7 CONS/LGCA, DYESS AFB, TX 79607-1581; (325)
696-3685 FOR ANY AND ALL INFORMATION WITH REGARDS TO THIS CONTRACT.
2. ALL WORK IS NEW UNLESS OTHERWISE INDICATED TO BE "EXISTING" OR "REUSED" OR "RELOCATED".
3. CONTRACTOR SHALL OBTAIN A COMPLETED AF FORM 103 "WORK CLEARANCE REQUEST" FROM THE CONTRACTING
OFFICER PRIOR TO PERFORMANCE OF ON-SITE WORK.
4. EXISTING UNDERGROUND UTILITY LOCATIONS SHOWN ARE APPROXIMATE. CONTRACTOR SHALL FIELD VERIFY EXACT
LOCATIONS PRIOR TO EXCAVATION OR TRENCHING.
5. CONTRACTOR SHALL HAND DIG WITHIN 5 FEET EITHER SIDE OF UTILITY CROSSINGS UNTIL THE UTILITY IS PHYSICALLY
EXPOSED PRIOR TO PERFORMING MECHANICAL TRENCHING OR EXCAVATING.
6. CONTRACTOR IS HIGHLY ENCOURAGED TO PERFORM A SITE VISIT TO THOROUGHLY FAMILIARIZE THEMSELVES WITH ANY AND ALL EXISTING SITE AND PROJECT LOCATION CONDITIONS WHICH MAY AFFECT THE WORK UNDER THIS CONTRACT.
THE GOVERNMENT WILL NOT BE RESPONSIBLE FOR CONTRACTOR ERRORS OR OMISSIONS WHICH COULD BE MADE
KNOWN BY ATTENDING A SITE VISIT.
7. PROVIDE PROTECTION AND/OR TEMPORARY RELOCATION FOR THE EXISTING GOVERNMENT OWNED FURNITURE AND EQUIPMENT IN THE FACILITY AS NECESSARY TO INSTALL ALL REQUIRED NEW EQUIPMENT. REPLACE ALL CARPET THAT IS STAINED OR SOILED BEYOND CLEANING OF ALL TRACE OF CONSTRUCTION DAMAGE WITH NEW SIMILAR CARPET. THE GOVERNMENT WILL TEMPORARILY MOVE ALL DESKTOP COMPUTERS AND RELATED ELECTRONIC EQUIPMENT, ALL COMMUNICATIONS DEVICES, AND ALL LOOSE AND STORE MATERIALS FROM THE DESKTOPS, TABLES, BOOKSHELVES, CABINETS, AND WALLS AS NECESSARY FOR THEIR PROTECTION.
8. PROVIDE ALL TEMPORARY WORK AS REQUIRED TO SUPPORT EXISTING HVAC GRILLES AND DIFFUSERS, LIGHTING FIXTURES, COMMUNICATIONS AND SIGNAL WIRING, CONDUITS. ETC. WHERE THE EXISTING CEILING GRID IS REMOVED.
PROVIDE SPLIT SLEEVES FOR ALL COMMUNICATION CABLES (NOT IN CONDUIT) THAT PENETRATE NEW FIRE RATED WALL
CONSTRUCTION.
9. KEEP THE EXISTING HVAC, FIRE ALARM, FIRE SUPPRESSION, ELECTRICAL DISTRIBUTION, AND OTHER ALL OTHER UTILITIES IN THE FACILITY OPERATIONAL WHILE PERFORMING THE WORK REQUIRED BY THE CONTRACT DOCUMENTS.
G-000
COVER SHEET
PHASE 3PHASE 4
PHASE 2PHASE 5
PHASE 1
PHASE 3PHASE 4
PHASE 2PHASE 5
PHASE 3PHASE 4
PHASE 2PHASE 5
APPROVED
Jacobs Engineering Group Inc.
Texas Registered Engineering Firm F-2966 777 Main Street P.O. Box 901058 Fort Worth, TX 76102
REVISION BY/DATE
FNWZ 99-0013
S.MITCHELL
04/08/15
R E
G I S
TERED ARCH
I T E
C T
S
T A T E O F T EXA
S
W
IL
L IAM R . PETERSON
1 7 4 0 3
S.LINDQUIST
W. PETERSON
SCALE:
G-001 NOT TO SCALE
SCALE:
G-001 NOT TO SCALE
SCALE:
G-001 NOT TO SCALE
SCALE:
G-001 NOT TO SCALE
PHASE 1
PHASE 2
GENERAL SEQUENCE
1. CONSTRUCTION SHALL BE PERFORMED ON ONE BUILDING (7232 OR 7233) AT A TIME.
2. WORK IN CENTRAL PLANT.
3. INSTALLATION OF BURRIED CHILLED WATER LINES.
4. INSTALLATION OF CHILLED AND HEATING WATER LINES IN ATTIC.
5. REPLACEMENT OF FAN COIL UNITS AND CONNECTION TO BOTH HEATING AND
CHILLED LINES.
GENERAL COMMENTS
A. CONTRACTOR SHALL SUBMIT AN OVERALL SCHEDULE TO CONTRACTING OFFICER
FOR APPROVAL WITHIN 3 WEEKS OF AWARD.
B. CONTRACTOR SHALL SUBMIT DETAILED SCHEDULE TO CONTRACTING OFFICER ON A
WEEKLY BASIS .
C. BUILDING MAY REMAIN OCCUPIED DURING CONSTRUCTION (EXCEPT FOR ACTUAL
ROOM OF WORK) AND CONTRACTOR SHALL ARRANGE FOR AND PROVIDE
TEMPORARY HEAT/VENTILATION AND/OR CHILLED/HEATING WATER FOR THE
NON-CONSTRUCTION, OCCUPIED AREAS.
D. CONTRACTOR SHALL MOVE/PROTECT/STORE DESKS, CHAIRS, AND OTHER OFFICE
FURNITURE WHILE PERFORMING WORK IN EACH ROOM. UPON COMPLETION,
CONTRACTOR SHALL MOVE FURNITURE BACK TO ORIGINAL LOCATION.
E. BASED ON SEASON, THE EXISTING PIPING FROM THE CENTRAL PLANT WILL BE IN
EITHER COOLING OR HEATING MODE. CONTRACTOR SHALL CONSIDER SEASON,
SCHEDULE AND TEMPORARY CONNECTIONS IN SUBMITTAL.
F. ALL WORK MUST BE COMPLETED IN A PHASE BEFORE STARTING THE NEXT.
WORK IN CENTRAL PLANT AND UNDERGROUND PIPING. EXTERIOR PIPE CHASE AND PIPING
INTO ATTIC. PROVIDE TEMPORARY VALVES IN CHILLED/HOT WATER SUPPLY AND RETURN
PIPING TO ALLOW BUILDING NOT UNDER CONSTRUCTION TO FUNCTION WITH EXISTING
2-PIPE COOLING/HEATING SYSTEM. UPON CONSTRUCTION COMPLETION, REMOVE ALL
TEMPORARY VALVES. DISCONNECT EXISTING PIPING TO BE ABANDONED IN PLACE FROM
NEW PIPING CONNECTION POINT AND CAP PIPING ABANDONED IN PLACE.
SOUTHEAST QUADRANT, ALL 3 FLOORS. INSTALL VERTICAL PIPING AND REPLACE FAN
COIL UNITS. PERFORM ARCHITECTURAL AND ELECTRICAL SUPPORT WORK. RECOMMEND
WORKING EAST TO WEST.
PHASE 3
NORTHEAST QUADRANT, ALL 3 FLOORS. INSTALL VERTICAL PIPING AND REPLACE FAN
COIL UNITS. PERFORM ARCHITECTURAL AND ELECTRICAL SUPPORT WORK. RECOMMEND
WORKING EAST TO WEST.
PHASE 4
NORTHWEST QUADRANT, ALL 3 FLOORS. INSTALL VERTICAL PIPING AND REPLACE FAN
COIL UNITS. PERFORM ARCHITECTURAL AND ELECTRICAL SUPPORT WORK. RECOMMEND
WORKING EAST TO WEST.
PHASE 5
SOUTHWEST QUADRANT, ALL 3 FLOORS. INSTALL VERTICAL PIPING AND REPLACE FAN
COIL UNITS. PERFORM ARCHITECTURAL AND ELECTRICAL SUPPORT WORK. RECOMMEND
WORKING EAST TO WEST.
G-001
SEQUENCE OF BUILDING
CONSTRUCTION
APPROVED
Jacobs Engineering Group Inc.
Texas Registered Engineering Firm F-2966 777 Main Street P.O. Box 901058 Fort Worth, TX 76102
REVISION BY/DATE
FNWZ 99-0013
S.MITCHELL
04/08/15
R E
G I S
TERED ARCH
I T E
C T
S
T A T E O F T EXA
S
W
IL
L IAM R . PETERSON
1 7 4 0 3
S.LINDQUIST
W. PETERSON
SCALE:
G-002 NOT TO SCALE
SCALE:
G-002 NOT TO SCALE
SCALE:
G-002 NOT TO SCALE
PATH OF EXIT TRAVEL WITH
DISTANCES FROM SELECTED
REMOTE LOCATIONS TO
NEAREST EXIT. DISTANCES
INCLUDE TOTAL TRAVEL
DISTANCE AND COMMON PATH
OF EXIT TRAVEL.
FIRE EXTINGUISHER; 10 LB
ABC FIRE EXTINGUISHER CFGI.
CALCULATED ROOM/AREA
OCCUPANCY LOAD.
BUILDING CODE ANALYSIS
G-002
LIFE SAFETY PLANS
ABBREVIATIONS
A/C A/E
AB
ABAN
ACC
ACS FLR
ACST
ACT
AD
ADA
ADC
ADJ
ADS
AFF
AHU
ALNMT
ALT
ALUM
ANOD
APPROX
AR
ARCH
ASKLR
ASR
ASSY
ASTM
ASYM
AUTO
AUX
B/B
BAT
BC
BD
BEV
BF
BFF
BKBD
BL
BL
BLD
BLDG
BLKT
BLST
BLW
BM
BN
BOS
BOT
BP
BPRF
BRDG
BRG
BRKT
BRZ
BS
BSMT
BT WLD
BWTN
BUR
C
C TO C
C&G
CAB
CB
CBB
CD
CEM
CEM FIN
CER
CFCI
CFGI
CFLG
CG
CHBD
CHFR
CI
CIP
AND
AT
A
AIR CONDITION
ARCHITECT/ENGINEER
ANCHOR BOLT
ABANDON
ACCESSIBLE
ACCESS FLOOR
ACOUSTIC
ACOUSTICAL CEILING TILE
AREA DRAIN
AMERICANS WITH DISABILITIES ACT
AUTOMATIC DOOR CLOSER
ADJUSTABLE
AUTOMATIC DOOR SEAL
ABOVE FINISH FLOOR
AIR HANDLING UNIT
ALIGNMENT
ALTERNATE
ALUMINUM
ANODIZE
APPROXIMATE
AS REQUIRED
ARCHITECT
AUTOMATIC SPRINKLER
AUTOMATIC SPRINKLER RISER
ASSEMBLY
AMERICAN SOCIETY FOR TESTING
AND MATERIALS
ASYMMETRICAL
AUTOMATIC
AUXILIARY
B
BACK TO BACK
BATTEN
BACK OF CURB
BOARD
BEVEL
BOTH FACES
BELOW FINISH FLOOR
BACKBOARD
BASE LINE
BUILDING LINE
BUILD
BUILDING
BLANKET
BALLAST
BELOW
BEAM
BULLNOSE
BOTTOM OF STEEL
BOTTOM
BUILDING PAPER
BULLETPROOF (BULLET-RESISTANT)
BRIDGING
BEARING
BRACKET
BRONZE
BOTH SIDES
BASEMENT
BUTT WELD
BETWEEN
BUILT-UP ROOFING
C
CHANNEL
CENTER TO CENTER
CURB AND GUTTER
CABINET
CERAMIC BASE
CEMENTITIOUS (BACKER) BOARD
CONSTRUCTION DOCUMENTS
CEMENT
CEMENT FINISH
CERAMIC
CONTRACTOR FURNISHED
CONTRACTOR INSTALLED
CONTRACTOR FURNISHED
GOVERNMENT INSTALLED
COUNTERFLASHING
CORNER GUARD
CHALKBOARD
CHAMFER
CAST IRON
CAST-IN-PLACE
CIP
CJ
CL
CLDG
CLG
CLL
CLO
CLR
CLR
CLT
CM
CMPST
CMU
CND
CNR
CNTOR
CNTR
COL
COMM
COMPR
CONN
CONSTR
CONT
CORR
COV
CPRS
CPT
CRS
CSB
CSMT
CSWK
CT
CTR
CTRL
CU
D
DBL
DEG
DEMO
DIM
DIST
DMPF
DR
DR FR
DR OPNG
DS
DT DR
DW
DW
DWH
DX OUT
EA
EE
EF
EGSB
EHD
EIFS
EJ
EL
ELAST
ELEC
ELEV
EM
EMER
ENAM
ENCL
ENGR
ENTR
ENVIR
EPRF
EQ
EQUIP
ESCAL
ESMT
EST
EW
EWC
EWH
CAST IRON PIPE
CONTROL JOINT
CENTER LINE
CLADDING
CEILING
COLUMN LINE
CLOSET
CLEAR
COLOR
CLEAT
CENTIMETER
COMPOSITE
CONCRETE MASONRY UNIT
CONDUIT
CORNER
CONTACTOR
COUNTER
COLUMN
COMMUNICATION
COMPRESSOR
CONNECT
CONSTRUCTION
CONTINUE
CORRIDOR
COVER
COMPRESSIBLE
CARPET
COLD ROLLED STEEL
CONCRETE SPLASH BLOCK
CASEMENT
CASEWORK
CERAMIC TILE
CENTER
CONTROL
CUBIC
D
DEPTH
DOUBLE
DEGREE
DEMOLITION
DIMENSION
DISTANCE
DAMPPROOFING
DOOR
DOOR FRAME
DOOR OPENING
DOWNSPOUT
DUTCH DOOR
DISHWASHER
DOMESTIC WATER
DOMESTIC WATER HEATER
DUPLEX OUTLET
E
EACH
EACH END
EACH FACE
EXTERIOR GYPSUM
SHEATHING BOARD
ELECTRIC HAND DRYER
EXTERIOR INSULATION
AND FINISH SYSTEM
EXPANSION JOINT
ELEVATION
ELASTOMERIC
ELECTRIC
ELEVATOR
EXPANDED METAL
EMERGENCY
ENAMEL
ENCLOSURE
ENGINEER
ENTRANCE
ENVIRONMENT
EXPLOSION PROOF
EQUAL
EQUIPMENT
ESCALATOR
EASEMENT
ESTIMATE
EACH WAY
ELECTRIC WATER COOLER
ELECTRIC WATER HEATER
EWS
EXH FN
EXH HD
EXHV
EXIST
EXP
EXP
EXT
EXT LT
F
FACIL
FAS
FB
FC BRK
FD
FDTN
FE
FEC
FF EL
FHC
FIN
FIN FL
FIN GR
FIXT
FLASH
FLR
FLUOR
FM
FN
FO
FOM
FOW
FP
FPM
FR
FSTNR
FT
FTG
FURG
FURN
FUT
FW
FWC
GA
GAL
GALV
GB
GDR
GEN
GFCI
GFGI
GLZ
GRAN
GRTG
GSB
GT
GUT
GWH
GYP BD
HB
HC
HDBD
HDW
HID
HM
HMD
HMF
HNDRL
HORIZ
HPLAM
HST
HT
HVAC
HW
ID
ID
INSUL
INT
EYE WASH SYSTEM
EXHAUST FAN
EXHAUST HOOD
EXHAUST VENT
EXISTING
EXPOSED
EXPANSION
EXTINGUISHER
EXIT LIGHT
F
FEMALE
FACILITY
FIRE ALARM STATION
FIRE BLANKET
FACE BRICK
FLOOR DRAIN
FOUNDATION
FIRE EXTINGUISHER
FIRE EXTINGUISHER CABINET
FINISH FLOOR ELEVATION
FIRE HOSE CABINET
FINISH
FINISH FLOOR
FINISH GRADE
FIXTURE
FLASHING
FLOOR
FLUORESCENT
FACTORY MUTUAL
FENCE
FINISHED OPENING
FACE OF MASONRY
FACE OF WALL
FIRE PROTECTION
FEET PER MINUTE
FIRE RATING
FASTENER
FEET
FOOTING
FURRING
FURNITURE
FUTURE
FIRE WALL
FABRIC WALLCOVERING
G
GAGE
GALLON
GALVANIZED
GRAB BAR
GUARDRAIL
GENERAL
GOVERNMENT FURNISHED
CONTRACTOR INSTALLED
GOVERNMENT FURNISHED
GOVERNMENT INSTALLED
GLAZING
GRANITE
GRATING
GYPSUM SHEATHING BOARD
GROUT
GUTTER
GAS FIRED WATER HEATER
GYPSUM BOARD
H
HOSE BIBB
HANDICAP
HARDBOARD
HARDWARE
HIGH INTENSITY DISCHARGE
HOLLOW METAL
HOLLOW METAL DOOR
HOLLOW METAL FRAME
HANDRAIL
HORIZONTAL
HIGH PRESSURE PLASTIC
LAMINATE
HOIST
HEIGHT
HEATING, VENTILATION,
AND AIR CONDITIONING
HOT WATER
I
IDENTIFICATION
INSIDE DIAMETER
INSULATION
INTERIOR
IP
IS
JAN
J-BOX
K
KOP
L
LAB
LAD
LAM
LAM GL
LAV
LB
LBR
LDG
LH
LHR
LKR
LNDSCP
LVR
LWC
LYR
M
MACH RM
MAINT
MATL
MAX
MECH
MECH RM
MEMB
MEZZ
MFD
MFR
MID
MIN
MIRR
MISC
MLWK
MM
MO
MOT
MRT
MS
MSB
MTD
MTL
MULL
MVBL
MW
MWP
N
NIC
NM
NO
NOM
NS
NTS
OA
OCC
OFF
OH DR
OPH
OPNG
OPP
OPR
P
PBD
PC
PCC
PEJ
PERIM
PERP
PIL
PL
PL
PLAM
PLAS
PLAS
IRON PIPE
INSECT SCREEN
J
JANITOR
JUNCTION BOX
K
THOUSAND
KNOCK OUT PANEL
L
ANGLE
LABORATORY
LADDER
LAMINATE
LAMINATED GLASS
LAVATORY
POUND
LUMBER
LANDING
LEFT HAND
LEFT HAND REVERSE
LOCKER
LANDSCAPE
LOUVER
LIGHTWEIGHT CONCRETE
LAYER
M
METER
MACHINE ROOM
MAINTENANCE
MATERIAL
MAXIMUM
MECHANICAL
MECHANICAL ROOM
MEMBRANE
MEZZANINE
MANUFACTURED
MANUFACTURER
MIDDLE
MINIMUM
MIRROR
MISCELLANEOUS
MILLWORK
MILLIMETER
MASONRY OPENING
MOTOR
MARBLE THRESHOLD
MOP SINK
MOP SERVICE BASIN
MOUNTED
METAL
MULLION
MOVABLE
MICROWAVE
MEMBRANE WATERPROOFING
N
NORTH
NOT IN CONTRACT
NON-METALLIC
NUMBER
NOMINAL
NARROW STILE
NOT TO SCALE
O
OVERALL
OCCUPY
OFFICE
OVERHEAD (COILING) DOOR
OPPOSITE HAND
OPENING
OPPOSITE
OPERABLE
P
PUMP
PARTICLEBOARD
PORTLAND CEMENT
PRECAST CONCRETE
PREMOLDED EXPANSION JOINT
PERIMETER
PERPENDICULAR
PILASTER
PLATE
PROPERTY LINE
PLASTIC LAMINATE
PLASTER
PLASTIC
PLB
PLYWD
PNEU
PNL
PNT
POLY
PORT
PR
PR
PRCST
PREFAB
PREFIN
PROJ
PT
PTD
PTDR
PTN
PUR
PVC
PVG
R
R
RB
RB
RB HK
RBR
RC
RCP
RCVR
RD
RDC
REBAR
REC
RECD
RECPT
RECT
RE:
REF
REG
REINF
REM
REP
REPL
REQD
RESIL
REST
RF
RH
RH
RHR
RLG
RM
RND
RO
ROW
RT
RVL
S
SAN
SAT
SB
SC
SCD
SCHED
SCP
SCWD
SDBL
SDL
SECT
SEG
SEP
SF
SHFT
SHT
SHTHG
SIM
SLNT
SLV
SM
SND
SND INS
PLUMB
PLYWOOD
PNEUMATIC
PANEL
PAINT
POLYETHYLENE (PLASTIC)
PORTABLE
PAIR
PIPE RAIL
PRECAST
PREFABRICATE
PREFINISH
PROJECT
PORCELAIN TILE
PAPER TOWEL DISPENSER
PAPER TOWEL DISPENSER
AND RECEPTACLE
PARTITION
PURLINS
POLYVINYL CHLORIDE (PLASTIC)
PAVING
R
RADIUS
THERMAL RESISTANCE
RESILIENT BASE
RUBBER BASE
ROBE HOOK
RUBBER
REINFORCED CONCRETE
REFLECTED CEILING PLAN
RECEIVER
ROOF DRAIN
REDUCER
REINFORCING STEEL BARS
RECESSED
RECEIVED
RECEPTACLE
RECTANGLE
REFERENCE
REFRIGERATOR
REGULATION
REINFORCE
REMOVABLE
REPAIR
REPLACE
REQUIRED
RESILIENT
RESTROOM
RESILIENT FLOORING
RIGHT HAND
ROOF HATCH
RIGHT HAND REVERSE
RAILING
ROOM
ROUND
ROUGH OPENING
RIGHT OF WAY
RIGHT
REVEAL
S
SOUTH
SANITARY
SUSPENDED ACOUSTICAL TILE
SPLASH BLOCK
SEALED CONCRETE
SEAT COVER DISPENSER
SCHEDULE
SCUPPER
SOLID CORE WOOD DOOR
SANDBLAST
SADDLE
SECTION
SEGMENT
SEPARATE
SQUARE FOOT (FEET)
SHAFT (ELEVATOR)
SHEET
SHEATHING
SIMILAR
SEALANT
SLEEVE
SHEET METAL
SANITARY NAPKIN DISPENSER
SOUND INSULATION
SND
SP
SQ
SS
SS
SST
ST
STC
STD
STL JST
STL PL
STL TR
STOR
STR
STRM
STRUCT
STRUCT STL
SUSP
SUSP CLG
SYM
SYMM
SYS
T
TB
TEL
TEMP
TER
THERM
THK
THRES
TOC
TOM
TOS
TOW
TPD
TRANS
TS
TSTAT
TTB
TYP
UON
UPS
UR
VAC
VB
VCT
VERT
VIF
VIS
VNR
VOL
VR
VRFY
VWF
W
W CAB
W/
W/O
WBL
WC
WD
WDW
WF
WF BM
WFAB
WH
WPM
WSCT
WT
WTR
WW
WWF
X BRACE
XFMR
YD
SANITARY NAPKIN DISPOSAL
SUMP PIT
SQUARE
SANITARY SEWER
SERVICE SINK
STAINLESS STEEL
STAIRS
SOUND TRANSMISSION CLASS
STANDARD
STEEL JOIST
STEEL PLATE
STEEL TRUSS
STORAGE
STRINGER
STOREROOM
STRUCTURAL
STRUCTURAL STEEL
SUSPEND
SUSPENDED CEILING
SYMBOL
SYMMETRICAL
SYSTEM
T
TREAD
TOWEL BAR
TELEPHONE
TEMPORARY
TERRAZZO
THERMAL
THICKNESS
THRESHOLD
TABLE OF CONTENT
TOP OF MASONRY
TOP OF STEEL
TOP OF WALL
TOILET PAPER DISPENSER
TRANSPARENT
TUBE STEEL
THERMOSTAT
TELEPHONE TERMINAL BOARD
TYPICAL
U
UNLESS OTHERWISE NOTED
UNINTERRUPTIBLE POWER SUPPLY
URINAL
V
VACUUM
VINYL BASE
VINYL COMPOSITION TILE
VERTICAL
VERIFY IN FIELD
VISUAL
VENEER
VOLUME
VAPOR RETARDER
VERIFY
VINYL WALL FABRIC
W
WIDE
WALL CABINETS
WITH
WITHOUT
WOOD BLOCKING
WATER CLOSET
WOOD
WINDOW
WIDE FLANGE
BEAM, WIDE FLANGE
WALL FABRIC
WALL HUNG
WATERPROOF MEMBRANE
WAINSCOT
WEIGHT
WATER
WIREWAY
WELDED WIRE FABRIC
X
CROSS BRACE
TRANSFORMER
Y
YARD
FRTD FIRE RETARDENT TREATED
LGS LIGHT GAGE STEEL
SSMR STANDING SEAM METAL ROOF
ACP ACOUSTIC PANEL
PWDR POWDER
MB MARKER BOARD
MATERIAL INDICATIONS
A. VERIFY AND DOCUMENT CONDITIONS AND DIMENSIONS ON THE JOB SITE
BEFORE BEGINNING CONSTRUCTION.
B. DO NOT SCALE THE DRAWINGS FOR CONSTRUCTION PURPOSES.
C. VERIFY SIZE AND LOCATION OF ALL OPENINGS FOR EQUIPMENT AND
RELATED WORK.
D. ALL PLAN DIMENSIONS ARE TO FACE OF CONCRETE MASONRY UNITS OR
CENTERLINE OF COLUMNS UNLESS OTHERWISE NOTED.
E. REFER TO MECHANICAL, PLUMBING AND ELECTRICAL DRAWINGS FOR
ADDITIONAL LOCATIONS OF PENETRATIONS OCCURING WITHIN FLOOR,
WALL, CEILING AND ROOF SYSTEMS.
F. REFER TO MECHANICAL AND ELECTRICAL DRAWINGS FOR
LOCATIONS OF EQUIPMENT NOT SHOWN ON ARCHITECTURAL DRAWINGS.
G. FINISH FLOOR ELEVATION OF 0'-0" IS A RELATIVE ELEVATION USED FOR
DESIGN COORDINATION.
GENERAL NOTES
WOOD, ROUGH
FRAME THROUGH
MEMBER
BATT INSULATION
RIGID INSULATION
STEEL
CONCRETE
MASONRY UNITS
CONCRETE
ARCHITECTURAL SYMBOLS
COMPACTED
EARTH
L-1
A-501
A-501
A-501
A-501
A-501
APPROVED
Jacobs Engineering Group Inc.
Texas Registered Engineering Firm F-2966 777 Main Street P.O. Box 901058 Fort Worth, TX 76102
REVISION BY/DATE
FNWZ 99-0013
S.MITCHELL
04/08/15
R E
G I S
TERED ARCH
I T E
C T
S
T A T E O F T EXA
S
W
IL
L IAM R . PETERSON
1 7 4 0 3
S.LINDQUIST
W. PETERSON
A-001
GENERAL NOTES
SYMBOLS AND
APPROVED
Jacobs Engineering Group Inc.
Texas Registered Engineering Firm F-2966 777 Main Street P.O. Box 901058 Fort Worth, TX 76102
REVISION BY/DATE
FNWZ 99-0013
S.MITCHELL
04/08/15
R E
G I S
TERED ARCH
I T
EC
T
S
T A T E O F T EXA
S
W I L
L IAM R . PETERSON
1 7 4 0 3
SCALE:
A-101 1/8"=1'-0"
4/A-301 2/A-301 1/A-301
S.LINDQUIST
W. PETERSON
GRAPHIC SCALE: 1/8"=1'-0"
122 4 6 8 16 FT.
SCALE:
A-101 1/8"=1'-0"
A-201
A-201
A-201
A-201
4/A-301 2/A-301 1/A-301
NEW INTAKE PILASTER, TYPICAL
NEW CORNER HVAC UNITS, TYPICAL. REF: MECHANICAL
NEW INTAKE PILASTER, TYPICAL
EDGE OF EXISTING SUNSHADE LEDGE
PIPE SHROUD.
PIPE SHROUD.
EXISTING INTAKE LOUVER TO REMAIN. INFILL OPENING FROM
THE INSIDE WITH 4" THICK SOLID CONCRETE MASONRY UNIT.
PROVIDE GYPSUM BOARD INTERIOR FINISH.
EXISTING INTAKE LOUVER TO
REMAIN. INFILL OPENING FROM
THE INSIDE WITH 4" THICK SOLID
CONCRETE MASONRY UNIT.
PROVIDE GYPSUM BOARD
INTERIOR FINISH.
EXISTING GUTTERS
EXISTING ROOF BELOW
HVAC UNIT ON PRECAST CONCRETE PAD. REF: MECHANICAL, 3/A-102
GENERAL NOTES:
1. BUILDING ELEMENTS THAT ARE EXISTING AND ARE TO
REMAIN ARE SHOWN AS SCREENED LINES.
2. BUILDING ELEMENTS THAT ARE NEW CONSTRUCTION
ARE SHOWN AS SOLID BOLD LINES.
3. PATCH AND PAINT ALL AREAS DAMAGED DURING THE
REPLACEMENT OF HVAC UNITS.
4. FINISH ALL EXPOSED AREAS THAT WERE PREVIOUSLY
CONCEALED BY THE HVAC UNITS TO MATCH
SURROUNDING FINISHES.
5. PROVIDE CLEAR WORK SPACE BY MOVING OR
PROTECTING OFFICE FURNITURE. RETURN TO
ORIGINAL LOCATION AFTER CONSTRUCTION.
6. WHERE PAINT IS TO BE APPLIED TO AN INTERIOR
WALL SURFACE, THE ENTIRE WALL IS TO BE PAINTED.
HVAC UNIT ABOVE DOOR. REF: MECHANICAL
1/A-102
1/A-102
EXISTING HVAC UNIT TO BE
REMOVED. PATCH FLOOR, WALL,
AND CEILING. PROVIDE FINISHES
TO MATCH SURROUNDING
FLOORING , WALL BASE, WALL
PAINT, AND CEILING
NEW CORNER HVAC UNITS, TYPICAL. REF: MECHANICAL
EDGE OF EXISTING SUNSHADE LEDGE
SAW CUT AND REMOVE FLOOR AS REQUIRED TO
INSTALL OUTSIDE AIR DUCT AND PIPING FROM ATTIC.
FLASH AROUND DUCT AND PIPING TO OPENING WITH
SHEET METAL CLOSURE AT BOTH SIDES.NEW REPLACEMENT WALL MOUNTED
EXHAUST FAN. REF: MECHANICAL
BLANK OFF EXISTING WALL LOUVER
WITH SHEET METAL AND INSULATE
WITH 1" POLYISO RIGID INSULATION
BLANK OFF EXISTING WALL LOUVER
WITH SHEET METAL AS REQUIRED.
PAINT EXPOSED METAL FLAT BLACK
TYPICAL AT
CORNERS
TYPICAL AT
DOWNSPOUT
TYPICAL
TYPICAL AT
CORNERS
TYPICAL AT
DOWNSPOUT
TYPICAL
2/A-301
TYPICAL AT
DOWNSPOUT
2/A-301
TYPICAL AT
DOWNSPOUT
BLANK OFF EXISTING WALL LOUVER
WITH SHEET METAL AS REQUIRED.
PAINT EXPOSED METAL FLAT BLACK
EXISTING INTAKE LOUVER TO REMAIN. INFILL
OPENING FROM THE INSIDE WITH 4" THICK
SOLID CONCRETE MASONRY UNIT. PROVIDE
GYPSUM BOARD INTERIOR FINISH.
ROOF MOUNTED HVAC
UNIT. REF: MECHANICAL
EXISTING HVAC UNIT TO BE REMOVED.
PATCH FLOOR, WALL, AND CEILING.
PROVIDE FINISHES TO MATCH
SURROUNDING FLOORING , WALL
BASE, WALL PAINT, AND CEILING
EXISTING HVAC UNIT TO BE REMOVED. PATCH
FLOOR, WALL, AND CEILING. PROVIDE FINISHES
TO MATCH SURROUNDING FLOORING , WALL
BASE, WALL PAINT, AND CEILING
2/A-301
TYPICAL AT
DOWNSPOUT
2/A-301
TYPICAL AT
DOWNSPOUT
NEW REPLACEMENT WALL MOUNTED
EXHAUST FAN. REF: MECHANICAL
NEW DOOR IN EXISTING DOOR FRAME
EXISTING DOWNSPOUT;
TYPICAL
VENTILATION HOOD
REF: 4/A102
A-101
1ST AND 2ND FLOOR
PLANS
APPROVED
Jacobs Engineering Group Inc.
Texas Registered Engineering Firm F-2966 777 Main Street P.O. Box 901058 Fort Worth, TX 76102
REVISION BY/DATE
FNWZ 99-0013
S.MITCHELL
04/08/15
R E
G I S
TERED ARCH
I T E
C T
S
T A T E O F T EXA
S
W
IL
L IAM R . PETERSON
1 7 4 0 3
SCALE:
A-102 1/8"=1'-0"
S.LINDQUIST
W. PETERSON
GRAPHIC SCALE: 1"=1'-0"
2 FT.
6 1842 8 10
24 IN.
SCALE:
A-102 1-1/2"=1'-0"
DOOR
A-201
A-201
NEW CORNER HVAC UNITS, TYPICAL. REF: MECHANICAL
EDGE OF EXISTING SUNSHADE LEDGE
EDGE OF EXISTING SUNSHADE LEDGE
GRAPHIC SCALE: 1-1/2"=1'-0"
2 FT.1
2 4 6 8 10 1812 24 IN.
3'-0"
7' -0
THICKNESS 1 3/4"
MATERIAL HM - INSULATED
FINISH PAINT
FIRE RATING NONE
FRAME EXISTING
HARDWARE HW-1
GENERAL NOTES:
1. BUILDING ELEMENTS THAT ARE EXISTING AND
ARE TO REMAIN ARE SHOWN AS SCREENED LINES.
2. BUILDING ELEMENTS THAT ARE NEW
CONSTRUCTION ARE SHOWN AS SOLID BOLD
LINES.
3. PATCH AND PAINT ALL AREAS DAMAGED DURING
THE REPLACEMENT OF HVAC UNITS.
4. FINISH ALL EXPOSED AREAS THAT WERE
PREVIOUSLY CONCEALED BY THE HVAC UNITS TO
MATCH SURROUNDING FINISHES.
5. PROVIDE CLEAR WORK SPACE BY MOVING OR
PROTECTING OFFICE FURNITURE. RETURN TO
ORIGINAL LOCATION AFTER CONSTRUCTION.
6. WHERE PAINT IS TO BE APPLIED TO AN INTERIOR
WALL SURFACE, THE ENTIRE WALL IS TO BE
PAINTED.
1'-4"
4' -0
HVAC PIPING. REFER TO MECHANICAL
PROVIDE SEALANT JOINTS AT THE
INTERSECTION OF FIBER CEMENT
BOARD AND MASONRY. TYPICAL
5/16" FIBER CEMENT PANEL
3 5/8" METAL STUD
FRAMING
1/2" PLYWOOD
FIBER CEMENT TRIM;
3/4"X3 1/2"
ISOLATE PIPES FROM CONCRETE
SLAB WITH 1/2" PREFOARMED
EXPANSION JOINT
PIPE SHROUD.
1/A-102
ALIGN WITH EXISTING
RAFTER ABOVE
A-301
SIM
SAW CUT AND REMOVE FLOOR AND CEILING AS
REQUIRED TO INSTALL OUTSIDE AIR DUCT AND PIPING
FROM ATTIC. FLASH AROUND DUCT AND PIPING TO
OPENING WITH SHEET METAL CLOSURE AT BOTH SIDES.
NEW REPLACEMENT WALL MOUNTED
EXHAUST FAN. REF: MECHANICAL
BLANK OFF EXISTING WALL LOUVER
WITH SHEET METAL AND INSULATE
WITH 1" POLYISO RIGID INSULATION
EXISTING INTAKE LOUVERS TO REMAIN. INFILL OPENING FROM
THE INSIDE WITH 4" THICK SOLID CONCRETE MASONRY UNIT.
PROVIDE GYPSUM BOARD INTERIOR FINISH.
EXISTING HVAC UNIT TO BE REMOVED. PATCH FLOOR, WALL,
AND CEILING. PROVIDE FINISHES TO MATCH SURROUNDING
FLOORING , WALL BASE, WALL PAINT, AND CEILING
BLANK OFF EXISTING WALL LOUVER
WITH SHEET METAL AS REQUIRED.
PAINT EXPOSED METAL FLAT BLACK
PROVIDE NEW OPENING THRU EXISTING SHINGLE ROOF
FOR NEW VENTILATION OPENING. REF: 2/A-102 MECHANICAL.
EXISTING
DOWNSPOUT; TYPICAL
GRAPHIC SCALE: 1/8"=1'-0"
122 4 6 8 16 FT.
1'-0"
1' -0
3"
(2) #6 CONT
#5 @ 12" OC TOP AND BOTTOM
8"
BARS TO MATCH SIZE AND
SPACING OF SLAB
REINFORCING
FINISHED GRADE
OR PAVING
SCALE: 1"=1'-0"
PERIMETER SECTION DETAIL AT EQUIPMENT PAD
A-102
6"
EDGE OF EQUIPMENT,
TYPICAL.
SCALE: 1-1/2"=1'-0"
VENTILATOR HOOD SECTION DETAIL
A-102
1'-0"
ALUMINUM VENTILATOR HOOD EXISTING HVAC INTAKE VENT.
DO NOT BLOCK
EXISTING BUILDING HATCHED
6" DIA. CORE DRILL THROUGH
EXISTING CONCRETE SLAB
MOUNTING FRAME. 1-1/2" X
1-1/2" STAINLESS STEEL
ANGLES, MITERED TO FIT
AT CORNERS
EXISTING CONC SLAB
FOAM INSULATION TAPE
GASKETED SS FASTNER
3 PER SIDE
ALUMINUM VENTILATOR
HOOD
SS EPOXY ANCHOR 3 PER
SIDE
FOAM INSULATION TAPE
DO NOT BLOCK OPENING;
NOTCH TOP TRACK AS
REQUIRED
A-102
3RD FLOOR PLAN AND
DETAILS
1392454892C Typewritten Text
PREFINISHED
1392454892C Typewritten Text
PREFINISHED
1392454892C Typewritten Text
NOTE: COMPLETED CONSTRUCTION SHALL BE PAINTED.
APPROVED
Jacobs Engineering Group Inc.
Texas Registered Engineering Firm F-2966 777 Main Street P.O. Box 901058 Fort Worth, TX 76102
REVISION BY/DATE
FNWZ 99-0013
S.MITCHELL
04/08/15
R E
G I S
TERED ARCH
I T E
C T
S
T A T E O F T EXA
S
W
IL
L IAM R . PETERSON
1 7 4 0 3
S.LINDQUIST
W. PETERSON
5'-2"±
2"x6" WOOD RAFTERS
EXISTING WOOD RAFTERS BEYOND
1/2" PLYWOOD DECKING
2"X4" DOUBLE BASE PLATES
1/2" PLYWOOD DECKING
GENERAL NOTES:
A. REMOVE EXISTING SHINGLES AND DECKING AS
REQUIRED.
B. NEW ASPHALT SHINGLES TO MATCH EXISTING
SHINGLES. NO EXISTING SHINGLES ARE TO BE
REUSED.
SLOPE
EXISTING DOWNSPOUT
A-201
A-201
7/A-201
6/A-201
1/2" PLYWOOD DECKING
UNDERLAYMENT SHEET
ASPHALT SHINGLES
3/4"X5 1/2" FIBER CEMENT BOARD TRIM
DRIP EDGE FLASHING
5/16" THICK FIBER CEMENT LAP SIDING
1/2" PLYWOOD WITH SHEET
WEATHER BARRIER
2"X6" WOOD RAFTER
1/2" PLYWOOD WITH SHEET
WEATHER BARRIER
5/16" THICK FIBER CEMENT SIDING
METAL FLASHING
EXISTING METAL TRIM
EXISTING METAL GUTTER
EXISTING FACIA BOARD
EXISTING DECKING
EXISTING WOOD RAFTERS
2"x6" WOOD RAFTERS AT 2'-0"
ON CENTER. NOTCH OUT FOR
BASE PLATES. RE:8/A-201
ASPHALT SHINGLES ON 15# FELT UNDERLAYMENT
5/
8"
2"X4" BASE PLATES 2"X6" RAFTER
3 1/2"
2"X6" WOOD RAFTER
PIPE SHROUD 1'-4"4'-0"PIPE SHROUD
3' -6
16'-9"
FIBER CEMENT LAP SIDING; 5/16" THICK X 5 1/2" WIDE
SHEET VALLEY
FLASHING,
REF: 9/A-201
EXISTING WOOD
RAFTERS AND KICKERS
EXISTING WOOD RAFTERS
2"X6" WOOD RAFTERS
HVAC PIPES
2"X4" DOUBLE BASE PLATES
EXISTING FACIA. GUTTER NOT SHOWN FOR CLARITY
2"X4" BASE PLATE
FIBER CEMENT BOARD TRIM; 3/4" THICK X 5 1/2" WIDE
AS REQUIRED TO ALIGN WITH THE EXISTING RAFTERS
EXISTING DECKING.
REMOVE AS REQUIRED.
2"x4" DOUBLE BASE PLATES2"x4" DOUBLE BASE PLATES
2"X4" WOOD BASE PLATE
2"X6" WOOD RAFTER, SHOWN
DASHED FOR CLARITY
(2) 2"X4" WOOD BASE PLATES
BEYOND
2"X4" CENTER POST
SHROUD NOT SHOWN FOR CLARITY
FIBER CEMENT BOARD TRIM; 3/4" THICK
X 3 1/2" WIDE AT ALL PANEL SEAMS
SHEET VALLEY
FLASHING.
REF: 9/A-201
8/A-201
GRAPHIC SCALE: 3"=1'-0"
1 3 5 92 4 6 12" IN.
1 FT.
GRAPHIC SCALE: 1/2"=1'-0"
2 4 FT.
6 6
24 36 48 IN.
GRAPHIC SCALE: 1/4"=1'-0"
61 2 3 4 8 FT.
CLIP, ATTACH WITH TWO NAILS,
BEND OVER NAIL HEADS
FELT UNDERLAYMENT
TRIMMED VALLEY SHINGLE
SHEET METAL
VALLEY FLASHING
1" TALL "W" RIB
ROOF DECK /
SHEATHING
SCALE:
A-201 1/4"=1'-0"
SCALE:
A-201 1/4"=1'-0"
SCALE:
A-201 3"=1'-0"
SCALE:
A-201 3"=1'-0"
SCALE:
A-201 3"=1'-0"
SCALE:
A-201 N.T.S.
SCALE:
A-201 1/2"=1'-0"
SCALE:
A-201 N.T.S.
SCALE:
A-201 1/2"=1'-0"
1/
2"
A-201
EXTERIOR ELEVATIONS
AND DETAILS
1392454892C Line
1392454892C Typewritten Text
NOTE: ALL UNDERLAYMENT SHALL BE 240 DEGREE, MIN 40-MIL THICK, COLD APPLIED,
SELF-ADHERING, POLYMER-MODIFIED, BITUMINOUS SHEET MEMBRANE WITH AN
EMBOSSED, SLIP RESITANT EXPOSED SURFACE COMPLYING WITH ASTM D 1970.
UNDERLAYMENT SHALL BE CONTINUOUS ON NEW WOOD DECK. TUCK BELOW EXISTING
SHINGLES TO REMAIN.
1392454892C Rectangle
1392454892C Line
1392454892C Typewritten Text
(PREFINISHED)
1392454892C Typewritten Text
PREFINISHED
1392454892C Typewritten Text
PREFINISHED
1392454892C Typewritten Text
UNDERLAYMENT CONTINUOUS
ON NEW ROOF DECK
1392454892C Line
1392454892C Typewritten Text
PREFINISHED
1392454892C Line
1392454892C Typewritten Text 3/4"
1392454892C Line
1392454892C
(3/4" CDX)
APPROVED
Jacobs Engineering Group Inc.
Texas Registered Engineering Firm F-2966 777 Main Street P.O. Box 901058 Fort Worth, TX 76102
REVISION BY/DATE
FNWZ 99-0013
S.MITCHELL
04/08/15
R E
G I S
TERED ARCH
I T E
C T
S
T A T E O F T EXA
S
W
IL
L IAM R . PETERSON
1 7 4 0 3
5/A-301
S.LINDQUIST
W. PETERSON
EXISTING
DOWNSPOUT
3/A-301
CONCRETE PAD
TO HAVE A 1/4"
PER 1'-0" SLOPE
AWAY FROM
BUILDING
1'-6" CONCRETE PAD
1'-4" AT PIPE SHROUD
3/8" X 12" SMOOTH DOWEL TO
BE DRILLED INTO EXISTING
SLAB, ONE END GREASED,
MINIMUM 2 PER SLAB, 18" O.C.
MAX
6"
1/2" THICK PREFORMED
JOINT
NEW SLAB TO BE A
MINIMUM OF A 1/2"
LOWER THAN
EXISTING SLAB
3 5/8" METAL
STUD FRAMING
BEYOND
EXISTING BUILDING
HATCHED
EXISTING HVAC INTAKE VENT.
DO NOT BLOCK.
EXISTING
BUILDING,
HATCHED
EXISTING
OPENING
THROUGH
OVERHANG
EPDM FLASHING; UV RESISTANT,
RETRO FIT CONFIGURATION WITH
SPLINE ON HIGH SIDE, STAINLESS
STEEL CLAMP AT DOWNSPOUT, SOFT
METAL FLANGE TO MOLD TO PILASTER
TOP, COLOR: BLACK
EXISTING ROUND ,
METAL DOWNSPOUT
TO REMAIN
BRONZE
DOWNSPOUT
NOZZLE
PROVIDE WALL PIPE CLAMPS
EXISTING CONCRETE
OVERHANG
EXISTING CONCRETE
OVERHANG HATCHED
3 5/8" METAL
STUD FRAMING
1' -6
2"
1/2" PLYWOOD
2ND FLOOR
GROUND FLOOR
5" P
A D
EXISTING
CONCRETE
SPLASH BLOCK
2'-8" ±
4'-8" ±
4'-8" ±
#3 REBAR,
CENTERED IN
SLAB, 15" O.C.
EACH WAY
9"
PROVIDE SEALANT
JOINTS AT THE
INTERSECTIONS OF
FIBER CEMENT BOTH
PANELS AND TRIM AT
CONCRETE. TYPICAL
6" DIA. CORE DRILL THROUGH
EXISTING CONC. SLAB, 1 PER
EACH VENT OPENING ON 1ST
FLOOR. CENTER ON EXISTING
VENT OPENING
EXISTING BUILDING
HATCHED
EXISTING HVAC INTAKE VENT.
DO NOT BLOCK
SQUARE VENT; 12"X12" SINGLE
UNIT, BAFFLE FOR WEATHER
RESISTANCE, FULL INSECT
SCREEN, UV STABILIZED
COPOLYMER, COLOR TO MATCH
PAINT, 35% FREE AREA MINIMUM,
PROVIDE 1 VENT PER HVAC
INTAKE AT 1ST FLOOR
5/16" FIBER CEMENT
PANEL WITH SHEET
WEATHER BARRIER
3 5/8" METAL STUD
FRAMING
FIBER CEMENT TRIM;
3/4"X3 1/2"
FIBER CEMENT TRIM AT
ALL PANEL JOINTS
EQUALLY SPACED
8"
REMOVE
EXISTING CAST
IRON BOOT AND
METAL
TRANSITION
PROVIDE NEW
METAL ROUND
DOWNSPOUT
SECTION TO
MATCH EXISTING
SHEET METAL TOP; PREFINISHED, 24
GAGE, SINGLE PIECE, CRIMPED TO
RECEIVE DECKING ON THE SIDES
AND BOTTOM OF SLOPE
3/4" EXTERIOR
GRADE PLYWOOD
SHEET METAL TOP
FLASHING MOUNTED IN
MORTAR JOINT WITH SOFT
METAL WEDGE SET IN BED
OF SEALANT
1/4" DIAMETER STAINLESS
STEEL FASTNER AND
EXPANSION SLEEVE
ANCHOR AT 8" O.C.
FASTEN AT 8" O.C.
SHEET METAL TOP
3/4" EXTERIOR
GRADE PLYWOOD
TRIM
SHEET METAL TOP
CONDENSATION
LINE. REF:
MECHANICAL.
GRAPHIC SCALE: 3"=1'-0"
1 3 5 92 4 6 12" IN.
1 FT.0
GRAPHIC SCALE: 1-1/2"=1'-0"
2 FT.1
2 4 6 8 10 1812 24 IN.
GRAPHIC SCALE: 1"=1'-0"
2 FT.
6 1842 8 10
24 IN.
A-301
SIM
SEALANT JOINT AT
ALL PENETRATIONS
SCALE:
A-301 1"=1'-0" SCALE:
A-301 3"=1'-0"
SCALE:
A-301 1"=1'-0"
SCALE:
A-301 1"=1'-0"
SCALE:
A-301 1 1/2"=1'-0"
SCALE:
A-301 1"=1'-0"
SHEET METAL
COUNTER
FLASHING
1' -6
5/16" FIBER CEMENT
PANEL WITH SHEET
WEATHER BARRIER
3 5/8" METAL STUD
FRAMING
EXISTING BUILDING
HATCHED
1' -6
EXISTING BUILDING
HATCHED
EXISTING
DOWNSPOUT
1' -6
EXISTING BUILDING
HATCHED
EXISTING HVAC
INTAKE. DO NOT
BLOCK
PROVIDE SEALANT JOINTS
AT THE INTERSECTION OF
FIBER CEMENT BOARD
AND MASONRY. TYPICAL
1/2" PLYWOOD
EXISTING HVAC
INTAKE. DO NOT
BLOCK
PROVIDE SEALANT
JOINTS AT THE
INTERSECTION OF
FIBER CEMENT
BOARD AND
MASONRY. TYPICAL
5/16" FIBER CEMENT
PANEL WITH SHEET
WEATHER BARRIER
3 5/8" METAL STUD
FRAMING
1/2" PLYWOOD
5/16" FIBER CEMENT
PANEL WITH SHEET
WEATHER BARRIER
3 5/8" METAL STUD
FRAMING
1/2" PLYWOOD
EXISTING HVAC
INTAKE. DO NOT
BLOCK
EXISTING HVAC
INTAKE. DO NOT
BLOCK
FIBER CEMENT TRIM;
3/4"X3 1/2" AT ALL PANEL
SEAMS, HORIZONTAL AND
VERTICAL TRIM SHALL BE
EQUALLY SPACED
PROVIDE SEALANT JOINTS
AT THE INTERSECTION OF
FIBER CEMENT BOARD
AND MASONRY. TYPICAL
BRONZE DOWN
SPOUT NOZZLE
FIBER CEMENT TRIM;
3/4"X3 1/2" AT ALL PANEL
SEAMS, HORIZONTAL AND
VERTICAL TRIM SHALL BE
EQUALLY SPACED
FIBER CEMENT TRIM;
3/4"X3 1/2" AT ALL PANEL
SEAMS, HORIZONTAL AND
VERTICAL TRIM SHALL BE
EQUALLY SPACED
SET METAL STUD IN
A BEAD OF SEALANT
1/2" PLYWOOD
FIBER CEMENT TRIM
FIBER CEMENT
PANEL
SEALANT
DRIP EDGE
CONDENSATION LINE.
REF: MECHANICAL
PROVIDE SEALANT
JOINT AT ALL
PENETRATIONS
CONDENSATION LINE.
REF: MECHANICAL
PROVIDE SEALANT
JOINT AT ALL
PENETRATIONS
WEEPHOLE; 3/8" DIAMETER
PLASTIC TUBE, 4" LONG
WITH WICK AND BRASS
SCREEN, SET UNDER
METAL TRACK, 1'-6" ON
CENTER OR MINIMUM 1 PER
SIDE
WEEPHOLE; 3/8"
DIAMETER PLASTIC
TUBE, 4" LONG WITH
WICK AND BRASS
SCREEN, SET UNDER
METAL TRACK, 1'-6" ON
CENTER OR MINIMUM 1
PER SIDE
WEEPHOLE; 3/8"
DIAMETER PLASTIC
TUBE, 4" LONG WITH
WICK AND BRASS
SCREEN, SET UNDER
METAL TRACK, 1'-6" ON
CENTER OR MINIMUM 1
PER SIDE
A-301
INTAKE PILASTER
DETAILS
1392454892C Typewritten Text
PREFINISHED
1392454892C Typewritten Text
PREFINISHED
1392454892C
PREFINISHED
A. PROVIDE MINOR ADDITIONS AND MODIFICATIONS TO THE EXISTING FIRE DETECTION
AND ALARM SYSTEM IN THE BUILDING AS INDICATED ON THE DRAWINGS. PERFORM ALL
DESIGN AND INSTALLATION WORK IN ACCORDANCE WITH 2010 NFPA 72, UFC 3-600-01,
UFC 4-021-01, AND SPECIFICATION 283111. HEAT DETECTION IS ALSO PROVIDED
THROUGHOUT ATTIC LEVEL (NOT SHOWN ON DRAWINGS). NO MODIFICATIONS OF ATTIC
LEVEL DETECTION ARE REQUIRED. THERE IS NO VISUAL NOTIFICATION PROVIDED IN THE
BUILDING.
B. RUN ALL WIRING IN MINIMUM 3/4" CONDUIT.
C.
D.
MOUNT THE OPERABLE PART OF MANUAL PULL STATIONS AT 48" AFF.
E.
PROVIDE POWER LIMITED CIRCUITS.
F.
DO NOT LOCATE DETECTORS IN DIRECT AIR OR CLOSER THAN 3
FEET FROM AN AIR SUPPLY OR RETURN DIFFUSER.
G.
PROVIDE CONNECTIONS TO THE LIGHT AND POWER SERVICE IN
ACCORDANCE WITH 2010 NFPA 72.
H.
PROVIDE 16 AWG MINIMUM INITIATING DEVICE AND SIGNALING LINE
CIRCUITS.
I.
PROVIDE 16 AWG MINIMUM NOTIFICATION DEVICE CIRCUITS.
J.
PROVIDE CLASS "B", SIGNALING LINE CIRCUITS. PROVIDE
CLASS "B" INITIATING DEVICE CIRCUITS. PROVIDE CLASS "B"
NOTIFICATION APPLIANCE CIRCUITS.
K.
THESE DOCUMENTS DEPICT PERFORMANCE DESIGN ONLY.
PROVIDE COMPLETE DOCUMENTS FOR APPROVAL FROM THE
AUTHORITY HAVING JURISDICTION, INCLUDE IN THE DRAWINGS ANY
ADDITIONAL EQUIPMENT NECESSARY TO COMPLETE THE
INSTALLATION AND COMPLY WITH LOCAL CODES AND AMENDMENTS.
PROVIDE ELECTRIC BELLS THROUGHOUT THE BUILDING. PROVIDE ADDITIONAL
ELECTRIC BELLS AS NECESSARY TO MEET THE AUDIBILITY REQUIREMENTS OF
NFPA 72 SECTION 18.4.
NOTIFY BASE FIRE DEPARTMENT UPON ANY IMPAIRMENT OF FIRE DETECTION SYSTEM.
FIRE WATCH SHALL BE INPLEMENTED PER UFC 3-600-01 AND BASE FIRE DEPARTMENT
REQUIREMENTS.
APPROVED
Jacobs Engineering Group Inc.
Texas Registered Engineering Firm F-2966 777 Main Street P.O. Box 901058 Fort Worth, TX 76102
REVISION BY/DATE
FNWZ 99-0013
S.MITCHELL
04/08/15
B. BOONE
R. PARK
F-001
FIRE PROTECTION
GENERAL NOTES
P
PP
A N
N
FA
T
FA
C
P
P
3 1
OFFICE
OFFICE
HOLDING
BREAK
STOR.
OFFICE
MENS
WOMENS
STAIRS
VEST.
MECH.
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
CLASS RM.
OFFICE
LOUNGE
CONF.
125STOR.
AUDITORIUM
STOR.
OFFICE
VEST.
CORR.
CLASS RM.
CONF.
111OFFICE
OFFICE
P PP
CLASS RM.
CLASS RM.
CLASS RM.
CLASS RM.
CLASS RM.
CLASS RM.
CORR.
OFFICE
OFFICE
LAN OFF.
MENS
WOMENS
STAIRS
STOR.
MECH.
OFFICE
OFFICE
OFFICE
OFFICE
CONF.
LOUNGE
OFFICE
CORR.
GENERAL NOTES:
KEYED NOTES:
1. MONACO FIRE ALARM RADIO TRANSMITTER
2. FIRE DETECTION / ALARM SYSTEM PANEL.
3. FIRE DETECTION / ALARM ANNUNCIATOR PANEL.
A. REFER TO SHEET F-001 FOR GENERAL NOTES AND SYMBOLS.
B. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR
COORDINATION WITH LIGHTS, MECHANICAL DIFFUSERS, AND
CEILING GRID.
C. ALL DEVICES AND COMPONENTS SHOWN ON PLANS ARE
EXISTING TO REMAIN UNLESS NOTED OTHERWISE.
X
APPROVED
Jacobs Engineering Group Inc.
Texas Registered Engineering Firm F-2966 777 Main Street P.O. Box 901058 Fort Worth, TX 76102
REVISION BY/DATE
FNWZ 99-0013
S.MITCHELL
04/08/15
B. BOONE
R. PARK
SCALE:
F-101 1/8"=1'-0"
GRAPHIC SCALE: 1/8"=1'-0"
122 4 6 8 16 FT.
SCALE:
F-101 1/8"=1'-0"
F-101
1ST AND 2ND FLOOR
FIRE PROTECTION
PLANS
P P
CLASS RM.
COMP. LAB
SCIENCE LAB
308B
CLASS RM.
COMP. LAB
CLASS RM.
SCIENCE LAB
CORR.
MENS
WOMENS
PROCTOR
ED. OFFICE
STAIRS
STOR.
314 MECH.
OFFICE
318 OFFICE
OFFICE
CONF.
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
CORR.
TESTING
APPROVED
Jacobs Engineering Group Inc.
Texas Registered Engineering Firm F-2966 777 Main Street P.O. Box 901058 Fort Worth, TX 76102
REVISION BY/DATE
FNWZ 99-0013
S.MITCHELL
04/08/15
B. BOONE
R. PARK
SCALE:
F-102 1/8"=1'-0"
GRAPHIC SCALE: 1/8"=1'-0"
122 4 6 8 16 FT.
GENERAL NOTES:
KEYED NOTES:
1. OMNI-DIRECTIONAL RADIO ANTENNA.
A. REFER TO SHEET F-001 FOR GENERAL NOTES AND SYMBOLS.
B. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR
COORDINATION WITH LIGHTS, MECHANICAL DIFFUSERS, AND
CEILING GRID.
C. ALL DEVICES AND COMPONENTS SHOWN ON PLANS ARE
EXISTING TO REMAIN UNLESS NOTED OTHERWISE.
X
F-102
3RD FLOOR FIRE
PROTECTION PLAN
CT
T
AQ
DUCT AVERAGING TEMPERATURE ELEMENT
RECEIVER PRESSURE GAUGE (PANEL MTD.)
CURRENT SENSING RELAY
LIQUID FLOW METER
AQUASTAT
DIFFERENTIAL PRESSURE SWITCH (DIGITAL)
DIFFERENTIAL PRESSURE SENSOR/TRANSMITTERDT
SP
DP
PT
HT
LT
PRESSURE TRANSMITTER
MOTOR STARTER (LOCAL OR MCC)
STATIC PRESSURE SENSOR/TRANSMITTER
DUCT HUMIDITY SENSOR/TRANSMITTER
LEVEL TRANSMITTER
VIBRATION SWITCH
ANGLE VALVE
PLUG VALVE
BALL VALVE
3-WAY VALVE
NEEDLE VALVE/INSTRUMENT VALVE
BUTTERFLY VALVE
GLOBE VALVE
VALVE W/ REDUCERS (GATE VALVE SHOWN)
GATE VALVE
NORMAL
OPEN
NORMAL
CLOSED
CONTROL VALVE SYMBOLS:
M
P
ELECTRIC ACTUATOR
PNEUMATIC ACTUATOR
S SOLENOID ACTUATOR
F FIRESTAT
CARBON DIOXIDE (C02) SENSORCD
ELECTRIC DAMPER ACTUATORDA
CARBON MONOXIDE (C0) SENSORCM
R REFRIGERANT DETECTOR/SENSOR
MANUALLY ACTIVED SWITCHHS
T
FR
H
H
TEMPERATURE SENSOR/TRANSMITTER
HUMIDITY SENSOR/TRANSMITTER
DUCT SMOKE DETECTOR
FREEZESTAT
ROOM THERMOSTAT OR SENSOR
ROOM HUMIDISTAT
S
F FLOW SENSOR
(PULL STAT., PUSH STAT., ETC)
R
M ELECTRIC MOTOR
RELAY
FS FLOW SWITCH
T
DUCT SECURITY BARSSB
S
GATE VALVE W/ 3/4" HOSE THREAD ADAPTER
SAFETY VALVE OR PRESSURE RELIEF VALVE
TEMPERATURE WELL
TWO-WAY CONTROL VALVE
THREE-WAY CONTROL VALVE
VENTURI FLOW METER
PRESSURE REDUCING VALVE (PRV)
AUTOMATIC AIR VENT
PRESSURE GAGE WITH COCK
MANUAL AIR VENT
PIPE ANCHOR
PITCH DOWN IN DIRECTION OF ARROW
DIRECTION OF FLOW
PIPE GUIDE
BRANCH - TOP CONNECTION
ECCENTRIC REDUCER
BRANCH - SIDE CONNECTION
CONCENTRIC REDUCER
RISER UP (ELBOW)
CAPPED PIPE
UNION (SCREWED)
BRANCH - BOTTOM CONNECTION
RISE OR DROP IN PIPE
ORIFICE UNION
FLANGED CONNECTION
STRAINER WITH BLOWDOWN VALVE
TEMPERATURE & PRESSURE PORT
THERMOMETER
MANUAL BALANCING VALVE
SOLENOID VALVE
BALL VALVE
BUTTERFLY VALVE
NEEDLE VALVE
FLOW SWITCH
HOSE BIBB
RISER DOWN (ELBOW)
FLEX CONNECTION
BELLOWS CONNECTION
FLEX PIPE ANGLE GATE VALVE
ANGLE GLOBE VALVE
DIAPHRAGM VALVE
QUICK ACTION VALVE
OS&Y VALVE
OS&Y VALVE WITH SUPERVISORY SWITCH
FLANGED VALVE (GATE VALVE SHOWN)
FLOAT VALVE
ORIFICE FLOW PLATE
PS
FS
(ALL SYMBOLS SHOWN ARE NOT NECESSARILY USED ON THE DRAWINGS)
PRESSURE SWITCH
BLIND FLANGE
WELDED CONNECTION
FLANGED CONNECTION
SOLDERED CONNECTION
THREADED OR "PRESS" CONNECTION
BELL & SPIGOT CONNECTION
SOLVENT CONNECTION
AUTOMATIC BALANCING VALVE
EXISTING EQUIPMENT TO BE REMOVED
EXISTING EQUIPMENT TO REMAIN
NEW EQUIPMENT
VALVE IN RISE
VALVE IN CENTER DROP
VALVE IN DROP
PUMP
(DOUBLE SPHERE NEOPRENE TYPE)
CHECK VALVE (NON SLAM)
PLUG VALVE
GLOBE VALVE
GATE VALVE
VACUUM BREAKER
PROJECT: DYESS BUILDING 7232 & 7233
INDOOR DESIGN CONDITIONS
WINTER: 68°F ± 2°F; (OCCUPIED AREAS)
SUMMER: 75°F ± 2°F; 50% RH ± 10% RH (OCCUPIED AREAS)
MAKE-UP WATERMU
CONDENSER WATER RETURN
CONDENSER WATER SUPPLY
CWR
CWS
HEATING WATER RETURN
HEATING WATER SUPPLY
HWR
HWS
PIPE TO BE REMOVED, "AAA" DENOTES TYPE
AAA
AHU CONDENSATE DRAINCD
DRAIND
REFRIGERANT LIQUIDRL
REFRIGERANT SUCTIONRS
EXISTING PIPE, "AAA" DENOTES TYPEAAA
UNDERGROUND PIPE, "AAA" DENOTES TYPE
AAA
X X X X
CHILLED WATER RETURN
CHILLED WATER SUPPLY
CHR
CHS
CEILING RETURN AIR GRILLE OR RETURN REGISTER
SIDEWALL SUPPLY OR RETURN REGISTER OR GRILLE
STANDARD ECCENTRIC DUCT TRANSITION
STANDARD CONCENTRIC DUCT TRANSITION
STANDARD ROUND BRANCH DUCT (SPIN-IN)
SECTION THROUGH RECTANGULAR SUPPLY DUCT
DUCT ACCESS DOOR
TYPICAL SUPPY AIR TEE WITH SPLITTER DAMPER
VERTICAL DAMPER IN DUCT (OR OPENING)
HORIZONTAL FIRE DAMPER AT FLOOR PENETRATION
CONNECT NEW DUCT TO EXISTING
DUCT WITH ACOUSTICAL LINING
MANUAL VOLUME DAMPER
OR RECTANGULAR ELBOWS, UNLESS NOTED OTHERWISE)
VANED RADIUS ELBOW
VANED ELBOW (PROVIDE VANES IN ALL SQUARE
SECTION THROUGH ROUND DUCT, SUPPLY OR
EXHAUST AS NOTED
SECTION THROUGH RECTANGULAR RETURN DUCT
XX/XX
ACCESS DOOR IN CEILING
A.D.
FLEXIBLE DUCT, SIZE AS SHOWN
RECTANGULAR-TO-ROUND DUCT TRANSITION
A.D.
DAMPER TYPE:
SECTION THROUGH RECTANGULAR RETURN DUCT
CEILING EXHAUST AIR GRILLE OR EXHAUST REGISTER
PATTERN. NO PATTERN SHOWN EQUALS
CEILING SUPPLY AIR DIFFUSER - ARROWS INDICATE
4-WAY
STANDARD RECTANGULAR BRANCH DUCT (45° TAKE-OFF)
STANDARD ROUND BRANCH DUCT (CONICAL)
DN
UP
RELIEF OR EXHAUST AIR DUCT UP
RELIEF OR EXHAUST AIR DUCT DOWN
IN-LINE 90 DEGREE DROP (RISE) IN DUCT
INCLINED DROP IN DUCT
INCLINED RISE IN DUCT
SUPPLY OR OUTSIDE AIR DUCT DOWN
SUPPLY OR OUTSIDE AIR DUCT UP
RETURN AIR DUCT DOWN
RETURN AIR DUCT UP
1 2
POINT OF CHANGE IN DUCT CONSTRUCTION
FLEXIBLE DUCT CONNECTION
DUCT PRESSURE CLASS.
FD - FIRE DAMPER
SD - SMOKE DAMPER
FSD - COMBINATION FIRE/SMOKE DAMPER
BD - GRAVITY BACKDRAFT DAMPER
CD - CONTROL DAMPER
*NO MARK INDICATES MANUAL VOLUME DAMPER
AT FIRE-RATED PARTITION
(SEE BELOW FOR OTHER TYPES)
POINT OF CONNECTION - NEW TO EXISTING
DRAWING NOTE REFERENCE1
72°F ± 2°F; (COMMUNICATION AND MECHANICAL ROOMS)
72°F ± 2°F; (COMMUNICATION AND MECHANICAL ROOMS)
SHEET NUMBER ON WHICH
DETAIL IS DRAWN
RE : 2 / M-201
REFER TO
DRAWING/DETAIL NUMBER
M-201
POINT OF CONNECTION - DEMOLITION TO EXISTING
FAN COIL UNIT(S)FCU(S)
ABOVE FINISHED FLOORAFF
UNLESS OTHERWISE
NOTED
UON
TYPICALTYP
OUTSIDE AIROA
SUPPLY AIRSA
RETURN AIRRA
EXHAUST AIREA
DEDICATED OUTDOOR
AIR UNIT
DOAU
M RISER TYPE IDENTIFIER
RISER NUMBER
WINTER:
SUMMER: 98°F DRY BULB (1.0%)
72°F MEAN COINCIDENT WET BULB (1.0%)
22°F DRY BULB (99.0%)
WEATHER STATION - DYESS AFB/ABILENE, TX
STATION #: 690190
ELEVATION: 1788 FEET; LATITUDE: 32.43°N; LONGITUDE: 99.85°W
DESIGN CONDITIONS FROM ASHRAE FUNDAMENTALS 2009
SUMMER
DEHUMIDIFICATION:
90°F DRY BULB (1.0%)
75°F MEAN COINCIDENT WET BULB (1.0%)
A. REFER TO SPECIFICATIONS FOR MATERIALS AND METHODS FOR CONSTRUCTION.
B. COORDINATE LOCATION OF ALL PENETRATIONS WITH THE BUILDING STRUCTURE.
C. COORDINATE ALL SLAB PENETRATIONS AND SLEEVES PRIOR TO EACH CONCRETE POUR.
D. FURNISH ACCESS DOORS FOR INSTALLATION IN WALLS AND CEILINGS WHERE ACCESS IS REQUIRED TO
CONCEALED MECHANICAL EQUIPMENT, VALVES, CONTROLS, AND OTHER DEVICES.
E. PERFORM WORK IN ACCORDANCE WITH THE LATEST EDITIONS, REVISIONS, AMENDMENTS OR
SUPPLEMENTS OF APPLICABLE STATUTES, ORDINANCES, CODES, OR REGULATIONS OF FEDERAL, STATE AND LOCAL AUTHORITIES HAVING JURISDICTION IN EFFECT ON THE DATE BIDS ARE RECEIVED.
F. WHERE APPROVAL CODES HAVE BEEN ESTABLISHED BY OSHA, UNDERWRITERS LABORATORY, AMERICAN CODES, ANSI, ASME, ASA, ASHRAE, ASTM, ARI, NEC, NFPA, SMACNA, OR THE STATE FIRE INSURANCE REGULATORY BODY, FOLLOW THESE STANDARDS WHETHER OR NOT INDICATED ON THE DRAWINGS.
G. ARRANGE WITH AUTHORITIES AND UTILITY COMPANIES FOR PERMITS, FEES, AND SERVICE CONNECTIONS.
VERIFYING LOCATIONS AND ARRANGEMENTS AND PAYING ALL CHARGES, INCLUDING INSPECTIONS.
H. COORDINATE WORK WITH ARCHITECTURAL FEATURES AND COORDINATE WORK SUCH THAT
INTERFERENCES BETWEEN PIPING, DUCTWORK, EQUIPMENT, PLUMBING WORK, ELECTRICAL WORK, AND
BUILDING STRUCTURE WILL BE AVOIDED.
I. PROVIDE THE ENTIRE SYSTEM AND ITS COMPONENT ITEMS OF EQUIPMENT IN OPERATING CONDITION
WITHOUT OBJECTIONABLE VIBRATION OR NOISE.
J. PROVIDE ALL WIRING AND ELECTRICAL CONTROLS IN ACCORDANCE WITH NFPA 70 (NEC).
K. VERIFY AND DOCUMENT EXISTING CONDITIONS AND DIMENSIONS ON THE JOB SITE PRIOR TO STARTING ANY
WORK.
L. DO NOT SCALE THESE DRAWINGS FOR CONSTRUCTION PURPOSES.
M. ALL DUCTWORK SIZES ARE FREE AIR STREAM DIMENSIONS.
N. INSTALL DUCTWORK AND PIPING TO PROVIDE THE MAXIMUM CLEAR HEIGHT UNDERNEATH.
O. REFER TO ARCHITECTURAL DRAWINGS FOR FRAMING REQUIRED AROUND PIPES AND DUCTS PENETRATING
ROOFS, WALLS, AND FLOORS.
P. REFER TO ARCHITECTURAL ELEVATION DRAWINGS, WHERE THE ARCHITECT HAS DRAWN SUCH ELEVATIONS, FOR THE LOCATION OF ALL WALL MOUNTED DEVICES.
Q. ALL TAPS TO DIFFUSERS SHALL BE SAME SIZE AS DIFFUSER NECK OPENING UNLESS OTHERWISE NOTED.
R. PAINT ANY ABOVE CEILING ITEMS, WHICH CAN BE SEEN THROUGH AIR SLOTS OR GRILLES, FLAT BLACK.
S. PROVIDE PLENUM RATED CABLE, DEVICES, PIPING, ETC. IN PLENUM SPACE.
T. PROVIDE TEMPORARY 30% EFFICIENT, 2" THICK FILTERS OVER RETURN AIR OPENINGS OF ANY AHU'S WHICH ARE PLACED IN SERVICE PRIOR TO COMPLETION OF CONSTRUCTION. REMOVE FILTERS FOR TEST &
BALANCE.
U. ALL HARDWARE AND SOFTWARE FOR THE HVAC DDCS SHALL BE INSTALLED, WIRED, PROGRAMMED, BE MADE OPERATIONAL, AND MAINTAIN SPACE TEMPERATURE CONTROL OF THE HEATING AND COOLING SYSTEM TO COINCIDE WITH COMPLETION OF INSTALLATION OF THE HVAC AIR HANDLING, REFRIGERATION, HEATING, AND PIPING EQUIPMENT; AND PRIOR TO BENEFICIAL OCCUPANCY. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE COORDINATION OF EFFORT BETWEEN THE USING ORGANIZATION, 7CES, AND 7COMM TO INSURE CONNECTIVITY IS AVAILABLE AT BOTH THE FACILITY AND AT THE 7CES HOST WORKSTATION SUCH THAT THERE IS NO DELAY IN MEETING THE ABOVE OPERATIONAL REQUIREMENT TIMELINE. SHOULD, FOR ANY REASON, CONNECTIVITY NOT BE AVAILABLE AT THE FACILITY OR AT 7CES TO
MEET THE ABOVE OPERATIONAL REQUIREMENT TIMELINE, THE CONTRACTOR SHALL UPLOAD THE
CONTROL SOFTWARE BY LAPTOP DIRECTLY TO THE DDCS CONTROL PANEL; AND ADJUST THE
PROGRAMMING SUCH THAT THE HVAC CONTROL SYSTEM BE OPERATIONAL AT THE FACILITY TO MAINTAIN SPACE TEMPERATURE CONTROL. THE GRAPHICAL INTERFACE SOFTWARE SHALL SUBSEQUENTLY BE UPLOADED BY THE CONTRACTOR AT NO COST TO THE GOVERNMENT AT THE 7CES HOST WORKSTATION
WHEN THE CONNECTIVITY BECOMES AVAILABLE.
V. PROVIDE ALL TEMPORARY WORK AS REQUIRED TO SUPPORT EXISTING HVAC GRILLES, DIFFUSERS, ETC.
WHERE THE EXISTING CEILING GRID IS REMOVED.
W. KEEP OPERATIONAL AS MUCH AS POSSIBLE THE EXISTING HVAC SYSTEMS IN THE FACILITY OPERATIONAL
WHILE PERFORMING THE WORK REQUIRED BY THE CONTRACT DOCUMENTS.
X. PAINT ALL EXPOSED INTERIOR AND EXTERIOR GALVANIZED SHEET METAL DUCTWORK, PIPING, EQUIPMENT, AND SUPPORTS WITH EXCEPTION TO FACTORY PAINTED EQUIPMENT AND ENCLOSURES.
Y. DEMOLISH ALL EXISTING MECHANICAL DEVICES RENDERED UNUSABLE BY CONSTRUCTION WORK PERFORMED IN THIS PROJECT. DEMOLITIONS SHALL EXTEND BACK TO THE SOURCE THAT SERVES THE
LOAD.
A. ENERGY CODE - ASHRAE 90.1-2007 - ZONE 3B
VENTILATION - ASHRAE 62.1-2007B.
TAG
AIR DEVICE TAG ON HVAC PLANS:
MAXIMUM AIRFLOW (CFM)
INDICATES A 46" / 30" DIA OVAL DUCT
(NET FREE AREA)
INDICATES A 20" ROUND DUCT (NET
FREE AREA)
INDICATES A 24"x12" RECTANGULAR
DUCT (NET FREE AREA)
24"X12"
20"ø
46/30 Ө
CFM
TYP
SIZE
MARK
AIR DEVICE NECK SIZE
APPROVED
Jacobs Engineering Group Inc.
Texas Registered Engineering Firm F-2966 777 Main Street P.O. Box 901058 Fort Worth, TX 76102
REVISION BY/DATE
FNWZ 99-0013
S.MITCHELL
04/08/15
C.SOLARI
C.SOLARI
M-001
GENERAL NOTES,
SYMBOLS AND
7-38
7-37
W x
W x
W x
W x
W x
W x
W x
W x
W x
W x
W x
Wx
Wx
Wx
Wx
W x
W x
W x
W x
W x
W x
W x
W x
W x
W x
W x
W x
W x
W x
W x
W x
W x
W x
W x
W x
W x
W x
W x
W x
W x
W x
W
Wx
Wx
Wx
Wx
Wx
Wx
Wx
Wx
Wx
Wx
W x
Wx
Wx
Wx
Wx
Wx
Wx
Wx
W x
Wx
Wx
Wx
Wx
Wx
Wx
Wx
Wx
W x
W x
W x
W x
W x
W x
W x
W x
Wx
Wx
Wx
Wx
Wx
Wx
Wx
Wx
Wx
Wx
Wx
Wx
Wx
Wx
Wx
Wx
Wx
Wx
Wx
Wx
Wx
Wx
Wx
Wx
W x
W x
W x
W x
W x
W x
W x
W x
W x W x
W x
W x
W x
W x
W x
W x
W x
W x
CU
x
C U x
CUx
CUx
CUx
CUx
CU
x
CU x
CUx
CU
x
CUx
CUx
CUx
CUx
CUx
CUx
CUx
CUx
CUx
CUx
CU x
C U x
C U x
C U x
C U x
C U x
C U x
C U x
C U x
C U x
C U x
C U x
SSx
SSx
SS
x
SS
x
SS
x
SS
x
SS
x
SS
x
SS
x
SS
x
SSx
SSx
SSx
SSx
SSx
SSx
SSx
SS
x
SS
x
SS
x
SS
x
SS
x
SS
x
SSx
SSx
SSx
SSx
SSx
SSx
SS
x
SS
x
SS
x
SS
x
SS
x
SS
x
SS
x
SS
x
SS
x
SS
x
SS
x
SS
x
SS
x
SSx
SSx
SSx
SSx
SSx
SSx
SSx
SDx
SDx
SDx
SDx
SDx
SDx
SDx
SD
x
SD
x
SD
x
SD
x
SDx
SDx
SDx
SDx
SDx
SDx
SDx
SD
x
SD
x
SD
x
SDx
SDx
SDx
SDx
SDx
EUx
EUx
EUx
EU
x
EU
x
EU
x
EU
x
EU
x
EU
x
EUx
EUx
EUx
EU
x
EU
x
EU
x
EU
x
EU
x
EU
x
EU
x
EU
x x
EUx
EUx
EUx
EUx
EUx
EU
x
EU
x
EU
x
EU
x
EU
x
EU
x
EU
x
EU
x
EU
x
EU
x
EU
x
EU
x
APPROVED
Jacobs Engineering Group Inc.
Texas Registered Engineering Firm F-2966 777 Main Street P.O. Box 901058 Fort Worth, TX 76102
REVISION BY/DATE
FNWZ 99-0013
S.MITCHELL
04/08/15
C.SOLARI
C.SOLARI
KEYED NOTES:
1. EXISTING HOT/CHILLED WATER SUPPLY AND RETURN
PIPING TO BE CAPPED AND ABANDONED IN PLACE.
2. EXISTING HOT/CHILLED WATER SUPPLY AND RETURN
PIPING TO REMAIN. CONVERT TO HOT WATER SERVICE
ONLY.
3. TAP NEW 4" HOT WATER SUPPLY AND RETURN INTO
EXISTING LINES.
4. ROUTE NEW CHILLED AND HOT WATER SUPPLY AND
RETURN PIPING FROM BELOW GRADE UP TO ATTIC. MOUNT
PIPING IN A PIPING ENCLOSURE ALONG SIDE EXTERIOR
WALL. REFER TO ARCHITECTURAL PLANS FOR ENCLOSURE
DETAIL.
5. REFER TO MPE-102 FOR PIPING CONTINUATION IN
CENTRAL PLANT.
6. PROVIDE 7'x7'x3' THRUST BLOCK.
7. PROVIDE 3'x6'x3' THRUST BLOCK.
X
SCALE:
MPE-101 1/32"=1'-0"
GENERAL NOTES:
A. SEE M-001 FOR MECHANICAL…