_3 _Sample_Project_Drawings.pdf

PDF 15 MB Posted

Attached to
Dyess AFB MACC Federal contract opportunity
Solicitation number
FA4661-15-R-0002
Issued by
Department of the Air Force Air Combat Command

About this file

Attachment 3 - Sample Project Drawings

View the file

Other files for this federal contract opportunity

Other files attached to Dyess AFB MACC, newest first.
File Type Posted
Amendment_3.pdf PDF
Attachment__8 _Fan_Coil_Unit_Spec_for_Sample.pdf PDF
FA4661-15-R-0002-0002.pdf PDF
1-Prototypical_3_Story_Dorm_(Bldgs_7232_ _7233)_-_Initial_Construction_-_1954.pdf PDF
3-Bldg_7233_-_Available_As-Built_Drawings_after_Initial_Construction.pdf PDF
4-Bldg_7223_-_Available_As-Built_Drawings.pdf PDF
2-Bldg_7232_-_Available_As-Built_Drawings_after_Initial_Construction.pdf PDF
Response_to_Questions_29_June_15.pdf PDF
_7 _Sample_Project_Bid_Schedule.docx DOCX document
Slides.pdf PDF
Q A_Post_18_June_15.pdf PDF
SignIn_Sheet.pdf PDF
FA466116R0002_Amendment_1.pdf PDF
Site_Visit_Minutes.pdf PDF
_4 _Past_Performance_Questionaire.pdf PDF
_5 _Site_Visit_Registration.doc DOC document
_6 _Question_Submission.doc DOC document
_2 _Sample_Project_Specifications.pdf PDF
Dyess_AFB_MACC_FY15_Solicitation.pdf PDF
_1 _General_MACC_Specifications.pdf PDF
_6 _Question_Submission.doc DOC document
_2 _Sample_Project_Specifications.pdf PDF
_1 _General_MACC_Specifications.pdf PDF
_4 _Past_Performance_Questionaire.pdf PDF
_3 _Sample_Project_Drawings.pdf PDF
_5 _Site_Visit_Registration.doc DOC document
Dyess_AFB_MACC_FY15_Solicitation.pdf PDF
Clarification_on_Draft_Documents_6_May_15.pdf PDF
MACC_FY15_Draft_RFP.doc DOC document
_8 _Question_Submission.doc DOC document
_1 _General_MACC_Specifications.pdf PDF
_4 _Seed_Project_3.pdf PDF
_7 _Site_Visit_Registration.doc DOC document
_2 _Seed_Project_1.pdf PDF
_5 _Seed_Project_4.pdf PDF
_6 _Past_Performance_Questionaire.docx DOCX document
_3 _Seed_Project_2.pdf PDF
Show all 37

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FNWZ 99-0013

PROJECT TITLE

BUILDING 7232 (425 3RD ST.) & 7233 (417 3RD ST.)

PROJECT LOCATION

Bldg. 7232

SECURITY POLICE

Bldg. 6117

CONTRACTOR'S ACCESS

(TYE GATE)

HAUL ROAD ROUTE

MAIN GATE

PROJECT NUMBER

Bldg. 7233

DESIGN REPAIR FOR HVAC SYSTEM

SIGNATURE OFFICE

COORDINATION

APPROVED

Jacobs Engineering Group Inc.

Texas Registered Engineering Firm F-2966 777 Main Street P.O. Box 901058 Fort Worth, TX 76102

REVISION BY/DATE

FNWZ 99-0013

S.MITCHELL

04/08/15

R E

G I S

TERED ARCH

I T E

C T

S

T A T E O F T EXA

S

W

IL

L IAM R . PETERSON

1 7 4 0 3

S.LINDQUIST

W. PETERSON

SHEET INDEX

SEQ SHEET NO. SHEET TITLE

COVER SHEET

SEQUENCE OF BUILDING CONSTRUCTION

LIFE SAFETY PLANS

GENERAL NOTES SYMBOLS AND ABBREVIATIONS

1ST AND 2ND FLOOR PLANS

3RD FLOOR PLAN AND DETAILS

EXTERIOR ELEVATIONS AND DETAILS

INTAKE PILASTER DETAILS

FIRE PROTECTION GENERAL NOTES

1ST AND 2ND FLOOR FIRE PROTECTION PLANS

3RD FLOOR FIRE PROTECTION PLAN

MECHANICAL SITE PLAN

CENTRAL PLANT PLAN

1ST FLOOR DEMOLITION PLAN

2ND FLOOR DEMOLITION PLAN

3RD FLOOR DEMOLITIONPLAN

1ST FLOOR HVAC PLAN

2ND FLOOR HVAC PLAN

3RD FLOOR HVAC PLAN

ATTIC HVAC PLAN

MECHANICAL DETAILS

MECHANICAL DETAILS

MECHANICAL DETAILS

MECHANICAL SCHEDULES

PIPING FLOW DIAGRAM

PIPING FLOW DIAGRAM

CONTROLS

CONTROLS

1ST FLOOR ELECTRICAL PLAN

2ND FLOOR ELECTRICAL PLAN

3RD FLOOR ELECTRICAL PLAN

ELECTRICAL SCHEDULES

ELECTRICAL SCHEDULES

G-001 01

PROJECT COVER

SHEET

FACILITY

7232 & 7233

OF

01 PROJECT COVER SHEETG-000

G-000 03 723202 G-001 03 723203 G-002 03 723204 A-001 05

A-101 A-102 A-201 A-301

03723209 F-001 03723210 F-101 03723211 F-102

GENERAL NOTES SYMBOLS AND ABBREVIATIONS

GENERAL NOTES SYMBOLS AND ABBREVIATIONS

18723212 M-001 187232 187232 187232 187232 187232 187232 187232 187232 187232 187232 187232 187232 187232 187232 187232 187232 187232

MPE-101

MPE-102

MD-101

MD-102

MD-103

MH-101

MH-102

MH-103

MH-104

M-501 M-502 M-503 M-601 M-701 M-702 M-801 M-802 E-001 E-101 E-102 E-103 E-601 E-602

7233 COVER SHEET

SEQUENCE OF BUILDING CONSTRUCTION

LIFE SAFETY PLANS

GENERAL NOTES SYMBOLS AND ABBREVIATIONS

1ST AND 2ND FLOOR PLANS

3RD FLOOR PLAN AND DETAILS

EXTERIOR ELEVATIONS AND DETAILS

INTAKE PILASTER DETAILS

FIRE PROTECTION GENERAL NOTES

1ST AND 2ND FLOOR FIRE PROTECTION PLANS

3RD FLOOR FIRE PROTECTION PLAN

MECHANICAL SITE PLAN

CENTRAL PLANT PLAN

1ST FLOOR DEMOLITION PLAN

2ND FLOOR DEMOLITION PLAN

3RD FLOOR DEMOLITIONPLAN

1ST FLOOR HVAC PLAN

2ND FLOOR HVAC PLAN

3RD FLOOR HVAC PLAN

ATTIC HVAC PLAN

MECHANICAL DETAILS

MECHANICAL DETAILS

MECHANICAL DETAILS

MECHANICAL SCHEDULES

PIPING FLOW DIAGRAM

PIPING FLOW DIAGRAM

CONTROLS

CONTROLS

1ST FLOOR ELECTRICAL PLAN

2ND FLOOR ELECTRICAL PLAN

3RD FLOOR ELECTRICAL PLAN

ELECTRICAL SCHEDULES

ELECTRICAL SCHEDULES

G-000 03 G-001 03 G-002 03 A-001 05

A-101 A-102 A-201 A-301

03F-001 03F-101 03F-102

GENERAL NOTES SYMBOLS AND ABBREVIATIONS

GENERAL NOTES SYMBOLS AND ABBREVIATIONS

18M-001

MPE-101

MPE-102

MD-101

MD-102

MD-103

MH-101

MH-102

MH-103

MH-104

M-501 M-502 M-503 M-601 M-701 M-702 M-801 M-802 E-001 E-101 E-102 E-103 E-601 E-602

1392454892C Typewritten Text Bldg 7223

1392454892C Oval

1392454892C Polygonal Line

AREA MAP

FNWZ 99-0013

PROJECT TITLE

BUILDING 7232 (425 3RD ST.)

L

DYESS AFB

ABILENE

PROJECT LOCATION

Bldg. 7232

SECURITY POLICE

Bldg. 6117

CONTRACTOR'S ACCESS

(TYE GATE)

HAUL ROAD ROUTE

MAIN GATE

PROJECT NUMBER

I-20 I-20

LO

OP

Bldg. 7233

DESIGN REPAIR FOR HVAC SYSTEM

APPROVED

Jacobs Engineering Group Inc.

Texas Registered Engineering Firm F-2966 777 Main Street P.O. Box 901058 Fort Worth, TX 76102

REVISION BY/DATE

FNWZ 99-0013

S.MITCHELL

04/08/15

R E

G I S

TERED ARCH

I T E

C T

S

T A T E O F T EXA

S

W

IL

L IAM R . PETERSON

1 7 4 0 3

S.LINDQUIST

W. PETERSON

SHEET INDEX

SEQ SHEET NO. SHEET TITLE

GENERAL

01 G-000 COVER SHEET

02 G-001 SEQUENCE OF BUILDING CONSTRUCTION

03 G-002 LIFE SAFETY PLANS

ARCHITECTURAL

04 A-001 GENERAL NOTES SYMBOLS AND ABBREVIATIONS

05 A-101 1ST AND 2ND FLOOR PLANS

06 A-102 3RD FLOOR PLAN AND DETAILS

07 A-201 EXTERIOR ELEVATIONS AND DETAILS

08 A-301 INTAKE PILASTER DETAILS

FIRE PROTECTION

09 F-001 FIRE PROTECTION GENERAL NOTES

10 F-101 1ST AND 2ND FLOOR FIRE PROTECTION PLANS

11 F-102 3RD FLOOR FIRE PROTECTION PLAN

MECHANICAL

12 M-001 GENERAL NOTES

13 MPE-101 MECHANICAL SITE PLAN

14 MPE-102 CENTRAL PLANT PLAN

15 MD-101 1ST FLOOR DEMOLITION PLAN

16 MD-102 2ND FLOOR DEMOLITION PLAN

17 MD-103 3RD FLOOR DEMOLITIONPLAN

18 MH-101 1ST FLOOR HVAC PLAN

19 MH-102 2ND FLOOR HVAC PLAN

20 MH-103 3RD FLOOR HVAC PLAN

21 MH-104 ATTIC HVAC PLAN

22 M-501 MECHANICAL DETAILS

23 M-502 MECHANICAL DETAILS

24 M-503 MECHANICAL DETAILS

25 M-601 MECHANICAL SCHEDULES

26 M-701 PIPING FLOW DIAGRAM

27 M-702 PIPING FLOW DIAGRAM

28 M-801 CONTROLS

29 M-802 CONTROLS

ELECTRICAL

30 E-001 GENERAL NOTES

31 E-101 1ST FLOOR ELECTRICAL PLAN

32 E-102 2ND FLOOR ELECTRICAL PLAN

33 E-103 3RD FLOOR ELECTRICAL PLAN

34 E-601 ELECTRICAL SCHEDULES

35 E-602 ELECTRICAL SCHEDULES

10. PAINT ALL EXPOSED NEW FIRE SUPPRESSION SYSTEM PIPING, VALVES, AND EQUIPMENT EXCEPT IN THE CONCEALED SPACE ABOVE THE CEILING. PAINT ALL NEW EXPOSED INTERIOR AND EXTERIOR MASONRY, GALVANIZED SHEET METAL DUCTWORK, PIPING, CONDUIT, EQUIPMENT, AND SUPPORTS WITH EXCEPTION TO FACTORY PAINTED EQUIPMENT AND ENCLOSURES.

11. DEMOLISH ALL EXISTING MECHANICAL AND ELECTRICAL DEVICES, CONDUIT, AND WIRING RENDERED UNUSABLE BY CONSTRUCTION WORK PERFORMED IN THIS PROJECT. DEMOLITION SHALL

EXTEND BACK TO THE SOURCE THAT SERVES THE LOAD.

12. REPLACE ALL CEILINGS INDICATED TO BE DEMOLISHED WITH NEW LAY-IN OR FINISHED GYP BOARD CEILING OF SIMILAR TYPE AS THE EXISTING OR AS OTHERWISE INDICATED OR SCHEDULED. REPLACE THE CEILING IN DAMP AREAS WITH MOISTURE RESISTANT GYP BOARD AND FINISHED WITH EPOXY PAINT. CONTRACTOR SHALL PATCH, PAINT, AND FINISH THE ENTIRE WALL OR PORTION OF THE WALL IN THE RESPECTIVE ROOM AS NECESSARY TO MATCH EXISTING PAINT AND FINISH IN AREAS WHERE NEW CEILING HEIGHT DIFFERS FROM THE EXISTING.

13. MEASURE THE EXISTING FULL LOAD CURRENT FOR EACH CIRCUIT BREAKER IN EXISTING DISTRIBUTION PANEL WHERE EXISTING LOADS ARE NOT SHOWN. SHOW MEASURED VALUES ON THE AS-BUILT DRAWING PANEL SCHEDULE. NOTIFY THE GOVERNMENT FOR FURTHER ACTION IF THE TOTAL MEASURED LOAD EXCEEDS THE ALLOWABLE LOAD FOR THE PANEL RATING.

14. AN ASBESTOS SURVEY HAS BEEN CONDUCTED AND IS INCLUDED IN THE APPENDIX TO THE SPECIFICATIONS. THE CONTRACTOR SHALL SUBMIT A PRICE PROPOSAL WITH QUANTITY OF ACM THE IS ANTICIPATED TO BE ABATED. SECTION 01560 ENVIRONMENTAL PROTECTION STATES THE REQUIREMENTS FOR SAFE HANDLING AND DISPOSAL OF ACM. ALL ABATEMENT, TRANSPORTATION, DISPOSAL, AND FEES ARE TO BE INCLUDED AS PART OF THIS CONSTRUCTION PACKAGE.

GENERAL SCOPE AND WORKING CONDITIONS NOTES:

1. GENERAL SCOPE OF WORK IN THIS PROJECT CONSIST OF REPAIRING, REMOVING AND REPLACING

THE BUILDING HVAC SYSTEM.

2. BUILDING IS TO REMAIN OCCUPIED DURING CONSTRUCTION, WORK PHASING IS REQUIRED.

CONTRACTOR IS TO COORDINATE WORK WITH BCE TO DETERMINE RELEASE OF BUILDING AREAS

FOR CONSTRUCTION.

3. GENERAL CONTRACTOR TO PROVIDE TEMPORARY DUST PROTECTION BETWEEN AREAS UNDER

CONSTRUCTION DURING WORK.

4. CONTRACTOR IS TO NOT INHIBIT NORMAL BASE OPERATIONS. THIS INCLUDES TRAFFIC FLOW.

CONTRACTOR TO SUBMIT A TRAFFIC CONTROL PLAN PRIOR TO ANY REPAIRS THAT WILL CAUSE

CONGESTION.

5. CONTRACTOR IS TO OBTAIN A DIG PERMIT AT ALL LOCATIONS PRIOR TO DIGGING FROM DYESS AFB

COMMUNICATIONS SQUADRON.

GENERAL NOTES:

1. CONTRACTOR MAY CONTACT ONLY THE BASE CONTRACTING OFFICE - 7 CONS/LGCA, DYESS AFB, TX 79607-1581; (325)

696-3685 FOR ANY AND ALL INFORMATION WITH REGARDS TO THIS CONTRACT.

2. ALL WORK IS NEW UNLESS OTHERWISE INDICATED TO BE "EXISTING" OR "REUSED" OR "RELOCATED".

3. CONTRACTOR SHALL OBTAIN A COMPLETED AF FORM 103 "WORK CLEARANCE REQUEST" FROM THE CONTRACTING

OFFICER PRIOR TO PERFORMANCE OF ON-SITE WORK.

4. EXISTING UNDERGROUND UTILITY LOCATIONS SHOWN ARE APPROXIMATE. CONTRACTOR SHALL FIELD VERIFY EXACT

LOCATIONS PRIOR TO EXCAVATION OR TRENCHING.

5. CONTRACTOR SHALL HAND DIG WITHIN 5 FEET EITHER SIDE OF UTILITY CROSSINGS UNTIL THE UTILITY IS PHYSICALLY

EXPOSED PRIOR TO PERFORMING MECHANICAL TRENCHING OR EXCAVATING.

6. CONTRACTOR IS HIGHLY ENCOURAGED TO PERFORM A SITE VISIT TO THOROUGHLY FAMILIARIZE THEMSELVES WITH ANY AND ALL EXISTING SITE AND PROJECT LOCATION CONDITIONS WHICH MAY AFFECT THE WORK UNDER THIS CONTRACT.

THE GOVERNMENT WILL NOT BE RESPONSIBLE FOR CONTRACTOR ERRORS OR OMISSIONS WHICH COULD BE MADE

KNOWN BY ATTENDING A SITE VISIT.

7. PROVIDE PROTECTION AND/OR TEMPORARY RELOCATION FOR THE EXISTING GOVERNMENT OWNED FURNITURE AND EQUIPMENT IN THE FACILITY AS NECESSARY TO INSTALL ALL REQUIRED NEW EQUIPMENT. REPLACE ALL CARPET THAT IS STAINED OR SOILED BEYOND CLEANING OF ALL TRACE OF CONSTRUCTION DAMAGE WITH NEW SIMILAR CARPET. THE GOVERNMENT WILL TEMPORARILY MOVE ALL DESKTOP COMPUTERS AND RELATED ELECTRONIC EQUIPMENT, ALL COMMUNICATIONS DEVICES, AND ALL LOOSE AND STORE MATERIALS FROM THE DESKTOPS, TABLES, BOOKSHELVES, CABINETS, AND WALLS AS NECESSARY FOR THEIR PROTECTION.

8. PROVIDE ALL TEMPORARY WORK AS REQUIRED TO SUPPORT EXISTING HVAC GRILLES AND DIFFUSERS, LIGHTING FIXTURES, COMMUNICATIONS AND SIGNAL WIRING, CONDUITS. ETC. WHERE THE EXISTING CEILING GRID IS REMOVED.

PROVIDE SPLIT SLEEVES FOR ALL COMMUNICATION CABLES (NOT IN CONDUIT) THAT PENETRATE NEW FIRE RATED WALL

CONSTRUCTION.

9. KEEP THE EXISTING HVAC, FIRE ALARM, FIRE SUPPRESSION, ELECTRICAL DISTRIBUTION, AND OTHER ALL OTHER UTILITIES IN THE FACILITY OPERATIONAL WHILE PERFORMING THE WORK REQUIRED BY THE CONTRACT DOCUMENTS.

G-000

COVER SHEET

PHASE 3PHASE 4

PHASE 2PHASE 5

PHASE 1

PHASE 3PHASE 4

PHASE 2PHASE 5

PHASE 3PHASE 4

PHASE 2PHASE 5

APPROVED

Jacobs Engineering Group Inc.

Texas Registered Engineering Firm F-2966 777 Main Street P.O. Box 901058 Fort Worth, TX 76102

REVISION BY/DATE

FNWZ 99-0013

S.MITCHELL

04/08/15

R E

G I S

TERED ARCH

I T E

C T

S

T A T E O F T EXA

S

W

IL

L IAM R . PETERSON

1 7 4 0 3

S.LINDQUIST

W. PETERSON

SCALE:

G-001 NOT TO SCALE

SCALE:

G-001 NOT TO SCALE

SCALE:

G-001 NOT TO SCALE

SCALE:

G-001 NOT TO SCALE

PHASE 1

PHASE 2

GENERAL SEQUENCE

1. CONSTRUCTION SHALL BE PERFORMED ON ONE BUILDING (7232 OR 7233) AT A TIME.

2. WORK IN CENTRAL PLANT.

3. INSTALLATION OF BURRIED CHILLED WATER LINES.

4. INSTALLATION OF CHILLED AND HEATING WATER LINES IN ATTIC.

5. REPLACEMENT OF FAN COIL UNITS AND CONNECTION TO BOTH HEATING AND

CHILLED LINES.

GENERAL COMMENTS

A. CONTRACTOR SHALL SUBMIT AN OVERALL SCHEDULE TO CONTRACTING OFFICER

FOR APPROVAL WITHIN 3 WEEKS OF AWARD.

B. CONTRACTOR SHALL SUBMIT DETAILED SCHEDULE TO CONTRACTING OFFICER ON A

WEEKLY BASIS .

C. BUILDING MAY REMAIN OCCUPIED DURING CONSTRUCTION (EXCEPT FOR ACTUAL

ROOM OF WORK) AND CONTRACTOR SHALL ARRANGE FOR AND PROVIDE

TEMPORARY HEAT/VENTILATION AND/OR CHILLED/HEATING WATER FOR THE

NON-CONSTRUCTION, OCCUPIED AREAS.

D. CONTRACTOR SHALL MOVE/PROTECT/STORE DESKS, CHAIRS, AND OTHER OFFICE

FURNITURE WHILE PERFORMING WORK IN EACH ROOM. UPON COMPLETION,

CONTRACTOR SHALL MOVE FURNITURE BACK TO ORIGINAL LOCATION.

E. BASED ON SEASON, THE EXISTING PIPING FROM THE CENTRAL PLANT WILL BE IN

EITHER COOLING OR HEATING MODE. CONTRACTOR SHALL CONSIDER SEASON,

SCHEDULE AND TEMPORARY CONNECTIONS IN SUBMITTAL.

F. ALL WORK MUST BE COMPLETED IN A PHASE BEFORE STARTING THE NEXT.

WORK IN CENTRAL PLANT AND UNDERGROUND PIPING. EXTERIOR PIPE CHASE AND PIPING

INTO ATTIC. PROVIDE TEMPORARY VALVES IN CHILLED/HOT WATER SUPPLY AND RETURN

PIPING TO ALLOW BUILDING NOT UNDER CONSTRUCTION TO FUNCTION WITH EXISTING

2-PIPE COOLING/HEATING SYSTEM. UPON CONSTRUCTION COMPLETION, REMOVE ALL

TEMPORARY VALVES. DISCONNECT EXISTING PIPING TO BE ABANDONED IN PLACE FROM

NEW PIPING CONNECTION POINT AND CAP PIPING ABANDONED IN PLACE.

SOUTHEAST QUADRANT, ALL 3 FLOORS. INSTALL VERTICAL PIPING AND REPLACE FAN

COIL UNITS. PERFORM ARCHITECTURAL AND ELECTRICAL SUPPORT WORK. RECOMMEND

WORKING EAST TO WEST.

PHASE 3

NORTHEAST QUADRANT, ALL 3 FLOORS. INSTALL VERTICAL PIPING AND REPLACE FAN

COIL UNITS. PERFORM ARCHITECTURAL AND ELECTRICAL SUPPORT WORK. RECOMMEND

WORKING EAST TO WEST.

PHASE 4

NORTHWEST QUADRANT, ALL 3 FLOORS. INSTALL VERTICAL PIPING AND REPLACE FAN

COIL UNITS. PERFORM ARCHITECTURAL AND ELECTRICAL SUPPORT WORK. RECOMMEND

WORKING EAST TO WEST.

PHASE 5

SOUTHWEST QUADRANT, ALL 3 FLOORS. INSTALL VERTICAL PIPING AND REPLACE FAN

COIL UNITS. PERFORM ARCHITECTURAL AND ELECTRICAL SUPPORT WORK. RECOMMEND

WORKING EAST TO WEST.

G-001

SEQUENCE OF BUILDING

CONSTRUCTION

APPROVED

Jacobs Engineering Group Inc.

Texas Registered Engineering Firm F-2966 777 Main Street P.O. Box 901058 Fort Worth, TX 76102

REVISION BY/DATE

FNWZ 99-0013

S.MITCHELL

04/08/15

R E

G I S

TERED ARCH

I T E

C T

S

T A T E O F T EXA

S

W

IL

L IAM R . PETERSON

1 7 4 0 3

S.LINDQUIST

W. PETERSON

SCALE:

G-002 NOT TO SCALE

SCALE:

G-002 NOT TO SCALE

SCALE:

G-002 NOT TO SCALE

PATH OF EXIT TRAVEL WITH

DISTANCES FROM SELECTED

REMOTE LOCATIONS TO

NEAREST EXIT. DISTANCES

INCLUDE TOTAL TRAVEL

DISTANCE AND COMMON PATH

OF EXIT TRAVEL.

FIRE EXTINGUISHER; 10 LB

ABC FIRE EXTINGUISHER CFGI.

CALCULATED ROOM/AREA

OCCUPANCY LOAD.

BUILDING CODE ANALYSIS

G-002

LIFE SAFETY PLANS

ABBREVIATIONS

A/C A/E

AB

ABAN

ACC

ACS FLR

ACST

ACT

AD

ADA

ADC

ADJ

ADS

AFF

AHU

ALNMT

ALT

ALUM

ANOD

APPROX

AR

ARCH

ASKLR

ASR

ASSY

ASTM

ASYM

AUTO

AUX

B/B

BAT

BC

BD

BEV

BF

BFF

BKBD

BL

BL

BLD

BLDG

BLKT

BLST

BLW

BM

BN

BOS

BOT

BP

BPRF

BRDG

BRG

BRKT

BRZ

BS

BSMT

BT WLD

BWTN

BUR

C

C TO C

C&G

CAB

CB

CBB

CD

CEM

CEM FIN

CER

CFCI

CFGI

CFLG

CG

CHBD

CHFR

CI

CIP

AND

AT

A

AIR CONDITION

ARCHITECT/ENGINEER

ANCHOR BOLT

ABANDON

ACCESSIBLE

ACCESS FLOOR

ACOUSTIC

ACOUSTICAL CEILING TILE

AREA DRAIN

AMERICANS WITH DISABILITIES ACT

AUTOMATIC DOOR CLOSER

ADJUSTABLE

AUTOMATIC DOOR SEAL

ABOVE FINISH FLOOR

AIR HANDLING UNIT

ALIGNMENT

ALTERNATE

ALUMINUM

ANODIZE

APPROXIMATE

AS REQUIRED

ARCHITECT

AUTOMATIC SPRINKLER

AUTOMATIC SPRINKLER RISER

ASSEMBLY

AMERICAN SOCIETY FOR TESTING

AND MATERIALS

ASYMMETRICAL

AUTOMATIC

AUXILIARY

B

BACK TO BACK

BATTEN

BACK OF CURB

BOARD

BEVEL

BOTH FACES

BELOW FINISH FLOOR

BACKBOARD

BASE LINE

BUILDING LINE

BUILD

BUILDING

BLANKET

BALLAST

BELOW

BEAM

BULLNOSE

BOTTOM OF STEEL

BOTTOM

BUILDING PAPER

BULLETPROOF (BULLET-RESISTANT)

BRIDGING

BEARING

BRACKET

BRONZE

BOTH SIDES

BASEMENT

BUTT WELD

BETWEEN

BUILT-UP ROOFING

C

CHANNEL

CENTER TO CENTER

CURB AND GUTTER

CABINET

CERAMIC BASE

CEMENTITIOUS (BACKER) BOARD

CONSTRUCTION DOCUMENTS

CEMENT

CEMENT FINISH

CERAMIC

CONTRACTOR FURNISHED

CONTRACTOR INSTALLED

CONTRACTOR FURNISHED

GOVERNMENT INSTALLED

COUNTERFLASHING

CORNER GUARD

CHALKBOARD

CHAMFER

CAST IRON

CAST-IN-PLACE

CIP

CJ

CL

CLDG

CLG

CLL

CLO

CLR

CLR

CLT

CM

CMPST

CMU

CND

CNR

CNTOR

CNTR

COL

COMM

COMPR

CONN

CONSTR

CONT

CORR

COV

CPRS

CPT

CRS

CSB

CSMT

CSWK

CT

CTR

CTRL

CU

D

DBL

DEG

DEMO

DIM

DIST

DMPF

DR

DR FR

DR OPNG

DS

DT DR

DW

DW

DWH

DX OUT

EA

EE

EF

EGSB

EHD

EIFS

EJ

EL

ELAST

ELEC

ELEV

EM

EMER

ENAM

ENCL

ENGR

ENTR

ENVIR

EPRF

EQ

EQUIP

ESCAL

ESMT

EST

EW

EWC

EWH

CAST IRON PIPE

CONTROL JOINT

CENTER LINE

CLADDING

CEILING

COLUMN LINE

CLOSET

CLEAR

COLOR

CLEAT

CENTIMETER

COMPOSITE

CONCRETE MASONRY UNIT

CONDUIT

CORNER

CONTACTOR

COUNTER

COLUMN

COMMUNICATION

COMPRESSOR

CONNECT

CONSTRUCTION

CONTINUE

CORRIDOR

COVER

COMPRESSIBLE

CARPET

COLD ROLLED STEEL

CONCRETE SPLASH BLOCK

CASEMENT

CASEWORK

CERAMIC TILE

CENTER

CONTROL

CUBIC

D

DEPTH

DOUBLE

DEGREE

DEMOLITION

DIMENSION

DISTANCE

DAMPPROOFING

DOOR

DOOR FRAME

DOOR OPENING

DOWNSPOUT

DUTCH DOOR

DISHWASHER

DOMESTIC WATER

DOMESTIC WATER HEATER

DUPLEX OUTLET

E

EACH

EACH END

EACH FACE

EXTERIOR GYPSUM

SHEATHING BOARD

ELECTRIC HAND DRYER

EXTERIOR INSULATION

AND FINISH SYSTEM

EXPANSION JOINT

ELEVATION

ELASTOMERIC

ELECTRIC

ELEVATOR

EXPANDED METAL

EMERGENCY

ENAMEL

ENCLOSURE

ENGINEER

ENTRANCE

ENVIRONMENT

EXPLOSION PROOF

EQUAL

EQUIPMENT

ESCALATOR

EASEMENT

ESTIMATE

EACH WAY

ELECTRIC WATER COOLER

ELECTRIC WATER HEATER

EWS

EXH FN

EXH HD

EXHV

EXIST

EXP

EXP

EXT

EXT LT

F

FACIL

FAS

FB

FC BRK

FD

FDTN

FE

FEC

FF EL

FHC

FIN

FIN FL

FIN GR

FIXT

FLASH

FLR

FLUOR

FM

FN

FO

FOM

FOW

FP

FPM

FR

FSTNR

FT

FTG

FURG

FURN

FUT

FW

FWC

GA

GAL

GALV

GB

GDR

GEN

GFCI

GFGI

GLZ

GRAN

GRTG

GSB

GT

GUT

GWH

GYP BD

HB

HC

HDBD

HDW

HID

HM

HMD

HMF

HNDRL

HORIZ

HPLAM

HST

HT

HVAC

HW

ID

ID

INSUL

INT

EYE WASH SYSTEM

EXHAUST FAN

EXHAUST HOOD

EXHAUST VENT

EXISTING

EXPOSED

EXPANSION

EXTINGUISHER

EXIT LIGHT

F

FEMALE

FACILITY

FIRE ALARM STATION

FIRE BLANKET

FACE BRICK

FLOOR DRAIN

FOUNDATION

FIRE EXTINGUISHER

FIRE EXTINGUISHER CABINET

FINISH FLOOR ELEVATION

FIRE HOSE CABINET

FINISH

FINISH FLOOR

FINISH GRADE

FIXTURE

FLASHING

FLOOR

FLUORESCENT

FACTORY MUTUAL

FENCE

FINISHED OPENING

FACE OF MASONRY

FACE OF WALL

FIRE PROTECTION

FEET PER MINUTE

FIRE RATING

FASTENER

FEET

FOOTING

FURRING

FURNITURE

FUTURE

FIRE WALL

FABRIC WALLCOVERING

G

GAGE

GALLON

GALVANIZED

GRAB BAR

GUARDRAIL

GENERAL

GOVERNMENT FURNISHED

CONTRACTOR INSTALLED

GOVERNMENT FURNISHED

GOVERNMENT INSTALLED

GLAZING

GRANITE

GRATING

GYPSUM SHEATHING BOARD

GROUT

GUTTER

GAS FIRED WATER HEATER

GYPSUM BOARD

H

HOSE BIBB

HANDICAP

HARDBOARD

HARDWARE

HIGH INTENSITY DISCHARGE

HOLLOW METAL

HOLLOW METAL DOOR

HOLLOW METAL FRAME

HANDRAIL

HORIZONTAL

HIGH PRESSURE PLASTIC

LAMINATE

HOIST

HEIGHT

HEATING, VENTILATION,

AND AIR CONDITIONING

HOT WATER

I

IDENTIFICATION

INSIDE DIAMETER

INSULATION

INTERIOR

IP

IS

JAN

J-BOX

K

KOP

L

LAB

LAD

LAM

LAM GL

LAV

LB

LBR

LDG

LH

LHR

LKR

LNDSCP

LVR

LWC

LYR

M

MACH RM

MAINT

MATL

MAX

MECH

MECH RM

MEMB

MEZZ

MFD

MFR

MID

MIN

MIRR

MISC

MLWK

MM

MO

MOT

MRT

MS

MSB

MTD

MTL

MULL

MVBL

MW

MWP

N

NIC

NM

NO

NOM

NS

NTS

OA

OCC

OFF

OH DR

OPH

OPNG

OPP

OPR

P

PBD

PC

PCC

PEJ

PERIM

PERP

PIL

PL

PL

PLAM

PLAS

PLAS

IRON PIPE

INSECT SCREEN

J

JANITOR

JUNCTION BOX

K

THOUSAND

KNOCK OUT PANEL

L

ANGLE

LABORATORY

LADDER

LAMINATE

LAMINATED GLASS

LAVATORY

POUND

LUMBER

LANDING

LEFT HAND

LEFT HAND REVERSE

LOCKER

LANDSCAPE

LOUVER

LIGHTWEIGHT CONCRETE

LAYER

M

METER

MACHINE ROOM

MAINTENANCE

MATERIAL

MAXIMUM

MECHANICAL

MECHANICAL ROOM

MEMBRANE

MEZZANINE

MANUFACTURED

MANUFACTURER

MIDDLE

MINIMUM

MIRROR

MISCELLANEOUS

MILLWORK

MILLIMETER

MASONRY OPENING

MOTOR

MARBLE THRESHOLD

MOP SINK

MOP SERVICE BASIN

MOUNTED

METAL

MULLION

MOVABLE

MICROWAVE

MEMBRANE WATERPROOFING

N

NORTH

NOT IN CONTRACT

NON-METALLIC

NUMBER

NOMINAL

NARROW STILE

NOT TO SCALE

O

OVERALL

OCCUPY

OFFICE

OVERHEAD (COILING) DOOR

OPPOSITE HAND

OPENING

OPPOSITE

OPERABLE

P

PUMP

PARTICLEBOARD

PORTLAND CEMENT

PRECAST CONCRETE

PREMOLDED EXPANSION JOINT

PERIMETER

PERPENDICULAR

PILASTER

PLATE

PROPERTY LINE

PLASTIC LAMINATE

PLASTER

PLASTIC

PLB

PLYWD

PNEU

PNL

PNT

POLY

PORT

PR

PR

PRCST

PREFAB

PREFIN

PROJ

PT

PTD

PTDR

PTN

PUR

PVC

PVG

R

R

RB

RB

RB HK

RBR

RC

RCP

RCVR

RD

RDC

REBAR

REC

RECD

RECPT

RECT

RE:

REF

REG

REINF

REM

REP

REPL

REQD

RESIL

REST

RF

RH

RH

RHR

RLG

RM

RND

RO

ROW

RT

RVL

S

SAN

SAT

SB

SC

SCD

SCHED

SCP

SCWD

SDBL

SDL

SECT

SEG

SEP

SF

SHFT

SHT

SHTHG

SIM

SLNT

SLV

SM

SND

SND INS

PLUMB

PLYWOOD

PNEUMATIC

PANEL

PAINT

POLYETHYLENE (PLASTIC)

PORTABLE

PAIR

PIPE RAIL

PRECAST

PREFABRICATE

PREFINISH

PROJECT

PORCELAIN TILE

PAPER TOWEL DISPENSER

PAPER TOWEL DISPENSER

AND RECEPTACLE

PARTITION

PURLINS

POLYVINYL CHLORIDE (PLASTIC)

PAVING

R

RADIUS

THERMAL RESISTANCE

RESILIENT BASE

RUBBER BASE

ROBE HOOK

RUBBER

REINFORCED CONCRETE

REFLECTED CEILING PLAN

RECEIVER

ROOF DRAIN

REDUCER

REINFORCING STEEL BARS

RECESSED

RECEIVED

RECEPTACLE

RECTANGLE

REFERENCE

REFRIGERATOR

REGULATION

REINFORCE

REMOVABLE

REPAIR

REPLACE

REQUIRED

RESILIENT

RESTROOM

RESILIENT FLOORING

RIGHT HAND

ROOF HATCH

RIGHT HAND REVERSE

RAILING

ROOM

ROUND

ROUGH OPENING

RIGHT OF WAY

RIGHT

REVEAL

S

SOUTH

SANITARY

SUSPENDED ACOUSTICAL TILE

SPLASH BLOCK

SEALED CONCRETE

SEAT COVER DISPENSER

SCHEDULE

SCUPPER

SOLID CORE WOOD DOOR

SANDBLAST

SADDLE

SECTION

SEGMENT

SEPARATE

SQUARE FOOT (FEET)

SHAFT (ELEVATOR)

SHEET

SHEATHING

SIMILAR

SEALANT

SLEEVE

SHEET METAL

SANITARY NAPKIN DISPENSER

SOUND INSULATION

SND

SP

SQ

SS

SS

SST

ST

STC

STD

STL JST

STL PL

STL TR

STOR

STR

STRM

STRUCT

STRUCT STL

SUSP

SUSP CLG

SYM

SYMM

SYS

T

TB

TEL

TEMP

TER

THERM

THK

THRES

TOC

TOM

TOS

TOW

TPD

TRANS

TS

TSTAT

TTB

TYP

UON

UPS

UR

VAC

VB

VCT

VERT

VIF

VIS

VNR

VOL

VR

VRFY

VWF

W

W CAB

W/

W/O

WBL

WC

WD

WDW

WF

WF BM

WFAB

WH

WPM

WSCT

WT

WTR

WW

WWF

X BRACE

XFMR

YD

SANITARY NAPKIN DISPOSAL

SUMP PIT

SQUARE

SANITARY SEWER

SERVICE SINK

STAINLESS STEEL

STAIRS

SOUND TRANSMISSION CLASS

STANDARD

STEEL JOIST

STEEL PLATE

STEEL TRUSS

STORAGE

STRINGER

STOREROOM

STRUCTURAL

STRUCTURAL STEEL

SUSPEND

SUSPENDED CEILING

SYMBOL

SYMMETRICAL

SYSTEM

T

TREAD

TOWEL BAR

TELEPHONE

TEMPORARY

TERRAZZO

THERMAL

THICKNESS

THRESHOLD

TABLE OF CONTENT

TOP OF MASONRY

TOP OF STEEL

TOP OF WALL

TOILET PAPER DISPENSER

TRANSPARENT

TUBE STEEL

THERMOSTAT

TELEPHONE TERMINAL BOARD

TYPICAL

U

UNLESS OTHERWISE NOTED

UNINTERRUPTIBLE POWER SUPPLY

URINAL

V

VACUUM

VINYL BASE

VINYL COMPOSITION TILE

VERTICAL

VERIFY IN FIELD

VISUAL

VENEER

VOLUME

VAPOR RETARDER

VERIFY

VINYL WALL FABRIC

W

WIDE

WALL CABINETS

WITH

WITHOUT

WOOD BLOCKING

WATER CLOSET

WOOD

WINDOW

WIDE FLANGE

BEAM, WIDE FLANGE

WALL FABRIC

WALL HUNG

WATERPROOF MEMBRANE

WAINSCOT

WEIGHT

WATER

WIREWAY

WELDED WIRE FABRIC

X

CROSS BRACE

TRANSFORMER

Y

YARD

FRTD FIRE RETARDENT TREATED

LGS LIGHT GAGE STEEL

SSMR STANDING SEAM METAL ROOF

ACP ACOUSTIC PANEL

PWDR POWDER

MB MARKER BOARD

MATERIAL INDICATIONS

A. VERIFY AND DOCUMENT CONDITIONS AND DIMENSIONS ON THE JOB SITE

BEFORE BEGINNING CONSTRUCTION.

B. DO NOT SCALE THE DRAWINGS FOR CONSTRUCTION PURPOSES.

C. VERIFY SIZE AND LOCATION OF ALL OPENINGS FOR EQUIPMENT AND

RELATED WORK.

D. ALL PLAN DIMENSIONS ARE TO FACE OF CONCRETE MASONRY UNITS OR

CENTERLINE OF COLUMNS UNLESS OTHERWISE NOTED.

E. REFER TO MECHANICAL, PLUMBING AND ELECTRICAL DRAWINGS FOR

ADDITIONAL LOCATIONS OF PENETRATIONS OCCURING WITHIN FLOOR,

WALL, CEILING AND ROOF SYSTEMS.

F. REFER TO MECHANICAL AND ELECTRICAL DRAWINGS FOR

LOCATIONS OF EQUIPMENT NOT SHOWN ON ARCHITECTURAL DRAWINGS.

G. FINISH FLOOR ELEVATION OF 0'-0" IS A RELATIVE ELEVATION USED FOR

DESIGN COORDINATION.

GENERAL NOTES

WOOD, ROUGH

FRAME THROUGH

MEMBER

BATT INSULATION

RIGID INSULATION

STEEL

CONCRETE

MASONRY UNITS

CONCRETE

ARCHITECTURAL SYMBOLS

COMPACTED

EARTH

L-1

A-501

A-501

A-501

A-501

A-501

APPROVED

Jacobs Engineering Group Inc.

Texas Registered Engineering Firm F-2966 777 Main Street P.O. Box 901058 Fort Worth, TX 76102

REVISION BY/DATE

FNWZ 99-0013

S.MITCHELL

04/08/15

R E

G I S

TERED ARCH

I T E

C T

S

T A T E O F T EXA

S

W

IL

L IAM R . PETERSON

1 7 4 0 3

S.LINDQUIST

W. PETERSON

A-001

GENERAL NOTES

SYMBOLS AND

APPROVED

Jacobs Engineering Group Inc.

Texas Registered Engineering Firm F-2966 777 Main Street P.O. Box 901058 Fort Worth, TX 76102

REVISION BY/DATE

FNWZ 99-0013

S.MITCHELL

04/08/15

R E

G I S

TERED ARCH

I T

EC

T

S

T A T E O F T EXA

S

W I L

L IAM R . PETERSON

1 7 4 0 3

SCALE:

A-101 1/8"=1'-0"

4/A-301 2/A-301 1/A-301

S.LINDQUIST

W. PETERSON

GRAPHIC SCALE: 1/8"=1'-0"

122 4 6 8 16 FT.

SCALE:

A-101 1/8"=1'-0"

A-201

A-201

A-201

A-201

4/A-301 2/A-301 1/A-301

NEW INTAKE PILASTER, TYPICAL

NEW CORNER HVAC UNITS, TYPICAL. REF: MECHANICAL

NEW INTAKE PILASTER, TYPICAL

EDGE OF EXISTING SUNSHADE LEDGE

PIPE SHROUD.

PIPE SHROUD.

EXISTING INTAKE LOUVER TO REMAIN. INFILL OPENING FROM

THE INSIDE WITH 4" THICK SOLID CONCRETE MASONRY UNIT.

PROVIDE GYPSUM BOARD INTERIOR FINISH.

EXISTING INTAKE LOUVER TO

REMAIN. INFILL OPENING FROM

THE INSIDE WITH 4" THICK SOLID

CONCRETE MASONRY UNIT.

PROVIDE GYPSUM BOARD

INTERIOR FINISH.

EXISTING GUTTERS

EXISTING ROOF BELOW

HVAC UNIT ON PRECAST CONCRETE PAD. REF: MECHANICAL, 3/A-102

GENERAL NOTES:

1. BUILDING ELEMENTS THAT ARE EXISTING AND ARE TO

REMAIN ARE SHOWN AS SCREENED LINES.

2. BUILDING ELEMENTS THAT ARE NEW CONSTRUCTION

ARE SHOWN AS SOLID BOLD LINES.

3. PATCH AND PAINT ALL AREAS DAMAGED DURING THE

REPLACEMENT OF HVAC UNITS.

4. FINISH ALL EXPOSED AREAS THAT WERE PREVIOUSLY

CONCEALED BY THE HVAC UNITS TO MATCH

SURROUNDING FINISHES.

5. PROVIDE CLEAR WORK SPACE BY MOVING OR

PROTECTING OFFICE FURNITURE. RETURN TO

ORIGINAL LOCATION AFTER CONSTRUCTION.

6. WHERE PAINT IS TO BE APPLIED TO AN INTERIOR

WALL SURFACE, THE ENTIRE WALL IS TO BE PAINTED.

HVAC UNIT ABOVE DOOR. REF: MECHANICAL

1/A-102

1/A-102

EXISTING HVAC UNIT TO BE

REMOVED. PATCH FLOOR, WALL,

AND CEILING. PROVIDE FINISHES

TO MATCH SURROUNDING

FLOORING , WALL BASE, WALL

PAINT, AND CEILING

NEW CORNER HVAC UNITS, TYPICAL. REF: MECHANICAL

EDGE OF EXISTING SUNSHADE LEDGE

SAW CUT AND REMOVE FLOOR AS REQUIRED TO

INSTALL OUTSIDE AIR DUCT AND PIPING FROM ATTIC.

FLASH AROUND DUCT AND PIPING TO OPENING WITH

SHEET METAL CLOSURE AT BOTH SIDES.NEW REPLACEMENT WALL MOUNTED

EXHAUST FAN. REF: MECHANICAL

BLANK OFF EXISTING WALL LOUVER

WITH SHEET METAL AND INSULATE

WITH 1" POLYISO RIGID INSULATION

BLANK OFF EXISTING WALL LOUVER

WITH SHEET METAL AS REQUIRED.

PAINT EXPOSED METAL FLAT BLACK

TYPICAL AT

CORNERS

TYPICAL AT

DOWNSPOUT

TYPICAL

TYPICAL AT

CORNERS

TYPICAL AT

DOWNSPOUT

TYPICAL

2/A-301

TYPICAL AT

DOWNSPOUT

2/A-301

TYPICAL AT

DOWNSPOUT

BLANK OFF EXISTING WALL LOUVER

WITH SHEET METAL AS REQUIRED.

PAINT EXPOSED METAL FLAT BLACK

EXISTING INTAKE LOUVER TO REMAIN. INFILL

OPENING FROM THE INSIDE WITH 4" THICK

SOLID CONCRETE MASONRY UNIT. PROVIDE

GYPSUM BOARD INTERIOR FINISH.

ROOF MOUNTED HVAC

UNIT. REF: MECHANICAL

EXISTING HVAC UNIT TO BE REMOVED.

PATCH FLOOR, WALL, AND CEILING.

PROVIDE FINISHES TO MATCH

SURROUNDING FLOORING , WALL

BASE, WALL PAINT, AND CEILING

EXISTING HVAC UNIT TO BE REMOVED. PATCH

FLOOR, WALL, AND CEILING. PROVIDE FINISHES

TO MATCH SURROUNDING FLOORING , WALL

BASE, WALL PAINT, AND CEILING

2/A-301

TYPICAL AT

DOWNSPOUT

2/A-301

TYPICAL AT

DOWNSPOUT

NEW REPLACEMENT WALL MOUNTED

EXHAUST FAN. REF: MECHANICAL

NEW DOOR IN EXISTING DOOR FRAME

EXISTING DOWNSPOUT;

TYPICAL

VENTILATION HOOD

REF: 4/A102

A-101

1ST AND 2ND FLOOR

PLANS

APPROVED

Jacobs Engineering Group Inc.

Texas Registered Engineering Firm F-2966 777 Main Street P.O. Box 901058 Fort Worth, TX 76102

REVISION BY/DATE

FNWZ 99-0013

S.MITCHELL

04/08/15

R E

G I S

TERED ARCH

I T E

C T

S

T A T E O F T EXA

S

W

IL

L IAM R . PETERSON

1 7 4 0 3

SCALE:

A-102 1/8"=1'-0"

S.LINDQUIST

W. PETERSON

GRAPHIC SCALE: 1"=1'-0"

2 FT.

6 1842 8 10

24 IN.

SCALE:

A-102 1-1/2"=1'-0"

DOOR

A-201

A-201

NEW CORNER HVAC UNITS, TYPICAL. REF: MECHANICAL

EDGE OF EXISTING SUNSHADE LEDGE

EDGE OF EXISTING SUNSHADE LEDGE

GRAPHIC SCALE: 1-1/2"=1'-0"

2 FT.1

2 4 6 8 10 1812 24 IN.

3'-0"

7' -0

THICKNESS 1 3/4"

MATERIAL HM - INSULATED

FINISH PAINT

FIRE RATING NONE

FRAME EXISTING

HARDWARE HW-1

GENERAL NOTES:

1. BUILDING ELEMENTS THAT ARE EXISTING AND

ARE TO REMAIN ARE SHOWN AS SCREENED LINES.

2. BUILDING ELEMENTS THAT ARE NEW

CONSTRUCTION ARE SHOWN AS SOLID BOLD

LINES.

3. PATCH AND PAINT ALL AREAS DAMAGED DURING

THE REPLACEMENT OF HVAC UNITS.

4. FINISH ALL EXPOSED AREAS THAT WERE

PREVIOUSLY CONCEALED BY THE HVAC UNITS TO

MATCH SURROUNDING FINISHES.

5. PROVIDE CLEAR WORK SPACE BY MOVING OR

PROTECTING OFFICE FURNITURE. RETURN TO

ORIGINAL LOCATION AFTER CONSTRUCTION.

6. WHERE PAINT IS TO BE APPLIED TO AN INTERIOR

WALL SURFACE, THE ENTIRE WALL IS TO BE

PAINTED.

1'-4"

4' -0

HVAC PIPING. REFER TO MECHANICAL

PROVIDE SEALANT JOINTS AT THE

INTERSECTION OF FIBER CEMENT

BOARD AND MASONRY. TYPICAL

5/16" FIBER CEMENT PANEL

3 5/8" METAL STUD

FRAMING

1/2" PLYWOOD

FIBER CEMENT TRIM;

3/4"X3 1/2"

ISOLATE PIPES FROM CONCRETE

SLAB WITH 1/2" PREFOARMED

EXPANSION JOINT

PIPE SHROUD.

1/A-102

ALIGN WITH EXISTING

RAFTER ABOVE

A-301

SIM

SAW CUT AND REMOVE FLOOR AND CEILING AS

REQUIRED TO INSTALL OUTSIDE AIR DUCT AND PIPING

FROM ATTIC. FLASH AROUND DUCT AND PIPING TO

OPENING WITH SHEET METAL CLOSURE AT BOTH SIDES.

NEW REPLACEMENT WALL MOUNTED

EXHAUST FAN. REF: MECHANICAL

BLANK OFF EXISTING WALL LOUVER

WITH SHEET METAL AND INSULATE

WITH 1" POLYISO RIGID INSULATION

EXISTING INTAKE LOUVERS TO REMAIN. INFILL OPENING FROM

THE INSIDE WITH 4" THICK SOLID CONCRETE MASONRY UNIT.

PROVIDE GYPSUM BOARD INTERIOR FINISH.

EXISTING HVAC UNIT TO BE REMOVED. PATCH FLOOR, WALL,

AND CEILING. PROVIDE FINISHES TO MATCH SURROUNDING

FLOORING , WALL BASE, WALL PAINT, AND CEILING

BLANK OFF EXISTING WALL LOUVER

WITH SHEET METAL AS REQUIRED.

PAINT EXPOSED METAL FLAT BLACK

PROVIDE NEW OPENING THRU EXISTING SHINGLE ROOF

FOR NEW VENTILATION OPENING. REF: 2/A-102 MECHANICAL.

EXISTING

DOWNSPOUT; TYPICAL

GRAPHIC SCALE: 1/8"=1'-0"

122 4 6 8 16 FT.

1'-0"

1' -0

3"

(2) #6 CONT

#5 @ 12" OC TOP AND BOTTOM

8"

BARS TO MATCH SIZE AND

SPACING OF SLAB

REINFORCING

FINISHED GRADE

OR PAVING

SCALE: 1"=1'-0"

PERIMETER SECTION DETAIL AT EQUIPMENT PAD

A-102

6"

EDGE OF EQUIPMENT,

TYPICAL.

SCALE: 1-1/2"=1'-0"

VENTILATOR HOOD SECTION DETAIL

A-102

1'-0"

ALUMINUM VENTILATOR HOOD EXISTING HVAC INTAKE VENT.

DO NOT BLOCK

EXISTING BUILDING HATCHED

6" DIA. CORE DRILL THROUGH

EXISTING CONCRETE SLAB

MOUNTING FRAME. 1-1/2" X

1-1/2" STAINLESS STEEL

ANGLES, MITERED TO FIT

AT CORNERS

EXISTING CONC SLAB

FOAM INSULATION TAPE

GASKETED SS FASTNER

3 PER SIDE

ALUMINUM VENTILATOR

HOOD

SS EPOXY ANCHOR 3 PER

SIDE

FOAM INSULATION TAPE

DO NOT BLOCK OPENING;

NOTCH TOP TRACK AS

REQUIRED

A-102

3RD FLOOR PLAN AND

DETAILS

1392454892C Typewritten Text

PREFINISHED

1392454892C Typewritten Text

PREFINISHED

1392454892C Typewritten Text

NOTE: COMPLETED CONSTRUCTION SHALL BE PAINTED.

APPROVED

Jacobs Engineering Group Inc.

Texas Registered Engineering Firm F-2966 777 Main Street P.O. Box 901058 Fort Worth, TX 76102

REVISION BY/DATE

FNWZ 99-0013

S.MITCHELL

04/08/15

R E

G I S

TERED ARCH

I T E

C T

S

T A T E O F T EXA

S

W

IL

L IAM R . PETERSON

1 7 4 0 3

S.LINDQUIST

W. PETERSON

5'-2"±

2"x6" WOOD RAFTERS

EXISTING WOOD RAFTERS BEYOND

1/2" PLYWOOD DECKING

2"X4" DOUBLE BASE PLATES

1/2" PLYWOOD DECKING

GENERAL NOTES:

A. REMOVE EXISTING SHINGLES AND DECKING AS

REQUIRED.

B. NEW ASPHALT SHINGLES TO MATCH EXISTING

SHINGLES. NO EXISTING SHINGLES ARE TO BE

REUSED.

SLOPE

EXISTING DOWNSPOUT

A-201

A-201

7/A-201

6/A-201

1/2" PLYWOOD DECKING

UNDERLAYMENT SHEET

ASPHALT SHINGLES

3/4"X5 1/2" FIBER CEMENT BOARD TRIM

DRIP EDGE FLASHING

5/16" THICK FIBER CEMENT LAP SIDING

1/2" PLYWOOD WITH SHEET

WEATHER BARRIER

2"X6" WOOD RAFTER

1/2" PLYWOOD WITH SHEET

WEATHER BARRIER

5/16" THICK FIBER CEMENT SIDING

METAL FLASHING

EXISTING METAL TRIM

EXISTING METAL GUTTER

EXISTING FACIA BOARD

EXISTING DECKING

EXISTING WOOD RAFTERS

2"x6" WOOD RAFTERS AT 2'-0"

ON CENTER. NOTCH OUT FOR

BASE PLATES. RE:8/A-201

ASPHALT SHINGLES ON 15# FELT UNDERLAYMENT

5/

8"

2"X4" BASE PLATES 2"X6" RAFTER

3 1/2"

2"X6" WOOD RAFTER

PIPE SHROUD 1'-4"4'-0"PIPE SHROUD

3' -6

16'-9"

FIBER CEMENT LAP SIDING; 5/16" THICK X 5 1/2" WIDE

SHEET VALLEY

FLASHING,

REF: 9/A-201

EXISTING WOOD

RAFTERS AND KICKERS

EXISTING WOOD RAFTERS

2"X6" WOOD RAFTERS

HVAC PIPES

2"X4" DOUBLE BASE PLATES

EXISTING FACIA. GUTTER NOT SHOWN FOR CLARITY

2"X4" BASE PLATE

FIBER CEMENT BOARD TRIM; 3/4" THICK X 5 1/2" WIDE

AS REQUIRED TO ALIGN WITH THE EXISTING RAFTERS

EXISTING DECKING.

REMOVE AS REQUIRED.

2"x4" DOUBLE BASE PLATES2"x4" DOUBLE BASE PLATES

2"X4" WOOD BASE PLATE

2"X6" WOOD RAFTER, SHOWN

DASHED FOR CLARITY

(2) 2"X4" WOOD BASE PLATES

BEYOND

2"X4" CENTER POST

SHROUD NOT SHOWN FOR CLARITY

FIBER CEMENT BOARD TRIM; 3/4" THICK

X 3 1/2" WIDE AT ALL PANEL SEAMS

SHEET VALLEY

FLASHING.

REF: 9/A-201

8/A-201

GRAPHIC SCALE: 3"=1'-0"

1 3 5 92 4 6 12" IN.

1 FT.

GRAPHIC SCALE: 1/2"=1'-0"

2 4 FT.

6 6

24 36 48 IN.

GRAPHIC SCALE: 1/4"=1'-0"

61 2 3 4 8 FT.

CLIP, ATTACH WITH TWO NAILS,

BEND OVER NAIL HEADS

FELT UNDERLAYMENT

TRIMMED VALLEY SHINGLE

SHEET METAL

VALLEY FLASHING

1" TALL "W" RIB

ROOF DECK /

SHEATHING

SCALE:

A-201 1/4"=1'-0"

SCALE:

A-201 1/4"=1'-0"

SCALE:

A-201 3"=1'-0"

SCALE:

A-201 3"=1'-0"

SCALE:

A-201 3"=1'-0"

SCALE:

A-201 N.T.S.

SCALE:

A-201 1/2"=1'-0"

SCALE:

A-201 N.T.S.

SCALE:

A-201 1/2"=1'-0"

1/

2"

A-201

EXTERIOR ELEVATIONS

AND DETAILS

1392454892C Line

1392454892C Typewritten Text

NOTE: ALL UNDERLAYMENT SHALL BE 240 DEGREE, MIN 40-MIL THICK, COLD APPLIED,

SELF-ADHERING, POLYMER-MODIFIED, BITUMINOUS SHEET MEMBRANE WITH AN

EMBOSSED, SLIP RESITANT EXPOSED SURFACE COMPLYING WITH ASTM D 1970.

UNDERLAYMENT SHALL BE CONTINUOUS ON NEW WOOD DECK. TUCK BELOW EXISTING

SHINGLES TO REMAIN.

1392454892C Rectangle

1392454892C Line

1392454892C Typewritten Text

(PREFINISHED)

1392454892C Typewritten Text

PREFINISHED

1392454892C Typewritten Text

PREFINISHED

1392454892C Typewritten Text

UNDERLAYMENT CONTINUOUS

ON NEW ROOF DECK

1392454892C Line

1392454892C Typewritten Text

PREFINISHED

1392454892C Line

1392454892C Typewritten Text 3/4"

1392454892C Line

1392454892C

(3/4" CDX)

APPROVED

Jacobs Engineering Group Inc.

Texas Registered Engineering Firm F-2966 777 Main Street P.O. Box 901058 Fort Worth, TX 76102

REVISION BY/DATE

FNWZ 99-0013

S.MITCHELL

04/08/15

R E

G I S

TERED ARCH

I T E

C T

S

T A T E O F T EXA

S

W

IL

L IAM R . PETERSON

1 7 4 0 3

5/A-301

S.LINDQUIST

W. PETERSON

EXISTING

DOWNSPOUT

3/A-301

CONCRETE PAD

TO HAVE A 1/4"

PER 1'-0" SLOPE

AWAY FROM

BUILDING

1'-6" CONCRETE PAD

1'-4" AT PIPE SHROUD

3/8" X 12" SMOOTH DOWEL TO

BE DRILLED INTO EXISTING

SLAB, ONE END GREASED,

MINIMUM 2 PER SLAB, 18" O.C.

MAX

6"

1/2" THICK PREFORMED

JOINT

NEW SLAB TO BE A

MINIMUM OF A 1/2"

LOWER THAN

EXISTING SLAB

3 5/8" METAL

STUD FRAMING

BEYOND

EXISTING BUILDING

HATCHED

EXISTING HVAC INTAKE VENT.

DO NOT BLOCK.

EXISTING

BUILDING,

HATCHED

EXISTING

OPENING

THROUGH

OVERHANG

EPDM FLASHING; UV RESISTANT,

RETRO FIT CONFIGURATION WITH

SPLINE ON HIGH SIDE, STAINLESS

STEEL CLAMP AT DOWNSPOUT, SOFT

METAL FLANGE TO MOLD TO PILASTER

TOP, COLOR: BLACK

EXISTING ROUND ,

METAL DOWNSPOUT

TO REMAIN

BRONZE

DOWNSPOUT

NOZZLE

PROVIDE WALL PIPE CLAMPS

EXISTING CONCRETE

OVERHANG

EXISTING CONCRETE

OVERHANG HATCHED

3 5/8" METAL

STUD FRAMING

1' -6

2"

1/2" PLYWOOD

2ND FLOOR

GROUND FLOOR

5" P

A D

EXISTING

CONCRETE

SPLASH BLOCK

2'-8" ±

4'-8" ±

4'-8" ±

#3 REBAR,

CENTERED IN

SLAB, 15" O.C.

EACH WAY

9"

PROVIDE SEALANT

JOINTS AT THE

INTERSECTIONS OF

FIBER CEMENT BOTH

PANELS AND TRIM AT

CONCRETE. TYPICAL

6" DIA. CORE DRILL THROUGH

EXISTING CONC. SLAB, 1 PER

EACH VENT OPENING ON 1ST

FLOOR. CENTER ON EXISTING

VENT OPENING

EXISTING BUILDING

HATCHED

EXISTING HVAC INTAKE VENT.

DO NOT BLOCK

SQUARE VENT; 12"X12" SINGLE

UNIT, BAFFLE FOR WEATHER

RESISTANCE, FULL INSECT

SCREEN, UV STABILIZED

COPOLYMER, COLOR TO MATCH

PAINT, 35% FREE AREA MINIMUM,

PROVIDE 1 VENT PER HVAC

INTAKE AT 1ST FLOOR

5/16" FIBER CEMENT

PANEL WITH SHEET

WEATHER BARRIER

3 5/8" METAL STUD

FRAMING

FIBER CEMENT TRIM;

3/4"X3 1/2"

FIBER CEMENT TRIM AT

ALL PANEL JOINTS

EQUALLY SPACED

8"

REMOVE

EXISTING CAST

IRON BOOT AND

METAL

TRANSITION

PROVIDE NEW

METAL ROUND

DOWNSPOUT

SECTION TO

MATCH EXISTING

SHEET METAL TOP; PREFINISHED, 24

GAGE, SINGLE PIECE, CRIMPED TO

RECEIVE DECKING ON THE SIDES

AND BOTTOM OF SLOPE

3/4" EXTERIOR

GRADE PLYWOOD

SHEET METAL TOP

FLASHING MOUNTED IN

MORTAR JOINT WITH SOFT

METAL WEDGE SET IN BED

OF SEALANT

1/4" DIAMETER STAINLESS

STEEL FASTNER AND

EXPANSION SLEEVE

ANCHOR AT 8" O.C.

FASTEN AT 8" O.C.

SHEET METAL TOP

3/4" EXTERIOR

GRADE PLYWOOD

TRIM

SHEET METAL TOP

CONDENSATION

LINE. REF:

MECHANICAL.

GRAPHIC SCALE: 3"=1'-0"

1 3 5 92 4 6 12" IN.

1 FT.0

GRAPHIC SCALE: 1-1/2"=1'-0"

2 FT.1

2 4 6 8 10 1812 24 IN.

GRAPHIC SCALE: 1"=1'-0"

2 FT.

6 1842 8 10

24 IN.

A-301

SIM

SEALANT JOINT AT

ALL PENETRATIONS

SCALE:

A-301 1"=1'-0" SCALE:

A-301 3"=1'-0"

SCALE:

A-301 1"=1'-0"

SCALE:

A-301 1"=1'-0"

SCALE:

A-301 1 1/2"=1'-0"

SCALE:

A-301 1"=1'-0"

SHEET METAL

COUNTER

FLASHING

1' -6

5/16" FIBER CEMENT

PANEL WITH SHEET

WEATHER BARRIER

3 5/8" METAL STUD

FRAMING

EXISTING BUILDING

HATCHED

1' -6

EXISTING BUILDING

HATCHED

EXISTING

DOWNSPOUT

1' -6

EXISTING BUILDING

HATCHED

EXISTING HVAC

INTAKE. DO NOT

BLOCK

PROVIDE SEALANT JOINTS

AT THE INTERSECTION OF

FIBER CEMENT BOARD

AND MASONRY. TYPICAL

1/2" PLYWOOD

EXISTING HVAC

INTAKE. DO NOT

BLOCK

PROVIDE SEALANT

JOINTS AT THE

INTERSECTION OF

FIBER CEMENT

BOARD AND

MASONRY. TYPICAL

5/16" FIBER CEMENT

PANEL WITH SHEET

WEATHER BARRIER

3 5/8" METAL STUD

FRAMING

1/2" PLYWOOD

5/16" FIBER CEMENT

PANEL WITH SHEET

WEATHER BARRIER

3 5/8" METAL STUD

FRAMING

1/2" PLYWOOD

EXISTING HVAC

INTAKE. DO NOT

BLOCK

EXISTING HVAC

INTAKE. DO NOT

BLOCK

FIBER CEMENT TRIM;

3/4"X3 1/2" AT ALL PANEL

SEAMS, HORIZONTAL AND

VERTICAL TRIM SHALL BE

EQUALLY SPACED

PROVIDE SEALANT JOINTS

AT THE INTERSECTION OF

FIBER CEMENT BOARD

AND MASONRY. TYPICAL

BRONZE DOWN

SPOUT NOZZLE

FIBER CEMENT TRIM;

3/4"X3 1/2" AT ALL PANEL

SEAMS, HORIZONTAL AND

VERTICAL TRIM SHALL BE

EQUALLY SPACED

FIBER CEMENT TRIM;

3/4"X3 1/2" AT ALL PANEL

SEAMS, HORIZONTAL AND

VERTICAL TRIM SHALL BE

EQUALLY SPACED

SET METAL STUD IN

A BEAD OF SEALANT

1/2" PLYWOOD

FIBER CEMENT TRIM

FIBER CEMENT

PANEL

SEALANT

DRIP EDGE

CONDENSATION LINE.

REF: MECHANICAL

PROVIDE SEALANT

JOINT AT ALL

PENETRATIONS

CONDENSATION LINE.

REF: MECHANICAL

PROVIDE SEALANT

JOINT AT ALL

PENETRATIONS

WEEPHOLE; 3/8" DIAMETER

PLASTIC TUBE, 4" LONG

WITH WICK AND BRASS

SCREEN, SET UNDER

METAL TRACK, 1'-6" ON

CENTER OR MINIMUM 1 PER

SIDE

WEEPHOLE; 3/8"

DIAMETER PLASTIC

TUBE, 4" LONG WITH

WICK AND BRASS

SCREEN, SET UNDER

METAL TRACK, 1'-6" ON

CENTER OR MINIMUM 1

PER SIDE

WEEPHOLE; 3/8"

DIAMETER PLASTIC

TUBE, 4" LONG WITH

WICK AND BRASS

SCREEN, SET UNDER

METAL TRACK, 1'-6" ON

CENTER OR MINIMUM 1

PER SIDE

A-301

INTAKE PILASTER

DETAILS

1392454892C Typewritten Text

PREFINISHED

1392454892C Typewritten Text

PREFINISHED

1392454892C

PREFINISHED

A. PROVIDE MINOR ADDITIONS AND MODIFICATIONS TO THE EXISTING FIRE DETECTION

AND ALARM SYSTEM IN THE BUILDING AS INDICATED ON THE DRAWINGS. PERFORM ALL

DESIGN AND INSTALLATION WORK IN ACCORDANCE WITH 2010 NFPA 72, UFC 3-600-01,

UFC 4-021-01, AND SPECIFICATION 283111. HEAT DETECTION IS ALSO PROVIDED

THROUGHOUT ATTIC LEVEL (NOT SHOWN ON DRAWINGS). NO MODIFICATIONS OF ATTIC

LEVEL DETECTION ARE REQUIRED. THERE IS NO VISUAL NOTIFICATION PROVIDED IN THE

BUILDING.

B. RUN ALL WIRING IN MINIMUM 3/4" CONDUIT.

C.

D.

MOUNT THE OPERABLE PART OF MANUAL PULL STATIONS AT 48" AFF.

E.

PROVIDE POWER LIMITED CIRCUITS.

F.

DO NOT LOCATE DETECTORS IN DIRECT AIR OR CLOSER THAN 3

FEET FROM AN AIR SUPPLY OR RETURN DIFFUSER.

G.

PROVIDE CONNECTIONS TO THE LIGHT AND POWER SERVICE IN

ACCORDANCE WITH 2010 NFPA 72.

H.

PROVIDE 16 AWG MINIMUM INITIATING DEVICE AND SIGNALING LINE

CIRCUITS.

I.

PROVIDE 16 AWG MINIMUM NOTIFICATION DEVICE CIRCUITS.

J.

PROVIDE CLASS "B", SIGNALING LINE CIRCUITS. PROVIDE

CLASS "B" INITIATING DEVICE CIRCUITS. PROVIDE CLASS "B"

NOTIFICATION APPLIANCE CIRCUITS.

K.

THESE DOCUMENTS DEPICT PERFORMANCE DESIGN ONLY.

PROVIDE COMPLETE DOCUMENTS FOR APPROVAL FROM THE

AUTHORITY HAVING JURISDICTION, INCLUDE IN THE DRAWINGS ANY

ADDITIONAL EQUIPMENT NECESSARY TO COMPLETE THE

INSTALLATION AND COMPLY WITH LOCAL CODES AND AMENDMENTS.

PROVIDE ELECTRIC BELLS THROUGHOUT THE BUILDING. PROVIDE ADDITIONAL

ELECTRIC BELLS AS NECESSARY TO MEET THE AUDIBILITY REQUIREMENTS OF

NFPA 72 SECTION 18.4.

NOTIFY BASE FIRE DEPARTMENT UPON ANY IMPAIRMENT OF FIRE DETECTION SYSTEM.

FIRE WATCH SHALL BE INPLEMENTED PER UFC 3-600-01 AND BASE FIRE DEPARTMENT

REQUIREMENTS.

APPROVED

Jacobs Engineering Group Inc.

Texas Registered Engineering Firm F-2966 777 Main Street P.O. Box 901058 Fort Worth, TX 76102

REVISION BY/DATE

FNWZ 99-0013

S.MITCHELL

04/08/15

B. BOONE

R. PARK

F-001

FIRE PROTECTION

GENERAL NOTES

P

PP

A N

N

FA

T

FA

C

P

P

3 1

OFFICE

OFFICE

HOLDING

BREAK

STOR.

OFFICE

MENS

WOMENS

STAIRS

VEST.

MECH.

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

CLASS RM.

OFFICE

LOUNGE

CONF.

125STOR.

AUDITORIUM

STOR.

OFFICE

VEST.

CORR.

CLASS RM.

CONF.

111OFFICE

OFFICE

P PP

CLASS RM.

CLASS RM.

CLASS RM.

CLASS RM.

CLASS RM.

CLASS RM.

CORR.

OFFICE

OFFICE

LAN OFF.

MENS

WOMENS

STAIRS

STOR.

MECH.

OFFICE

OFFICE

OFFICE

OFFICE

CONF.

LOUNGE

OFFICE

CORR.

GENERAL NOTES:

KEYED NOTES:

1. MONACO FIRE ALARM RADIO TRANSMITTER

2. FIRE DETECTION / ALARM SYSTEM PANEL.

3. FIRE DETECTION / ALARM ANNUNCIATOR PANEL.

A. REFER TO SHEET F-001 FOR GENERAL NOTES AND SYMBOLS.

B. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR

COORDINATION WITH LIGHTS, MECHANICAL DIFFUSERS, AND

CEILING GRID.

C. ALL DEVICES AND COMPONENTS SHOWN ON PLANS ARE

EXISTING TO REMAIN UNLESS NOTED OTHERWISE.

X

APPROVED

Jacobs Engineering Group Inc.

Texas Registered Engineering Firm F-2966 777 Main Street P.O. Box 901058 Fort Worth, TX 76102

REVISION BY/DATE

FNWZ 99-0013

S.MITCHELL

04/08/15

B. BOONE

R. PARK

SCALE:

F-101 1/8"=1'-0"

GRAPHIC SCALE: 1/8"=1'-0"

122 4 6 8 16 FT.

SCALE:

F-101 1/8"=1'-0"

F-101

1ST AND 2ND FLOOR

FIRE PROTECTION

PLANS

P P

CLASS RM.

COMP. LAB

SCIENCE LAB

308B

CLASS RM.

COMP. LAB

CLASS RM.

SCIENCE LAB

CORR.

MENS

WOMENS

PROCTOR

ED. OFFICE

STAIRS

STOR.

314 MECH.

OFFICE

318 OFFICE

OFFICE

CONF.

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

CORR.

TESTING

APPROVED

Jacobs Engineering Group Inc.

Texas Registered Engineering Firm F-2966 777 Main Street P.O. Box 901058 Fort Worth, TX 76102

REVISION BY/DATE

FNWZ 99-0013

S.MITCHELL

04/08/15

B. BOONE

R. PARK

SCALE:

F-102 1/8"=1'-0"

GRAPHIC SCALE: 1/8"=1'-0"

122 4 6 8 16 FT.

GENERAL NOTES:

KEYED NOTES:

1. OMNI-DIRECTIONAL RADIO ANTENNA.

A. REFER TO SHEET F-001 FOR GENERAL NOTES AND SYMBOLS.

B. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR

COORDINATION WITH LIGHTS, MECHANICAL DIFFUSERS, AND

CEILING GRID.

C. ALL DEVICES AND COMPONENTS SHOWN ON PLANS ARE

EXISTING TO REMAIN UNLESS NOTED OTHERWISE.

X

F-102

3RD FLOOR FIRE

PROTECTION PLAN

CT

T

AQ

DUCT AVERAGING TEMPERATURE ELEMENT

RECEIVER PRESSURE GAUGE (PANEL MTD.)

CURRENT SENSING RELAY

LIQUID FLOW METER

AQUASTAT

DIFFERENTIAL PRESSURE SWITCH (DIGITAL)

DIFFERENTIAL PRESSURE SENSOR/TRANSMITTERDT

SP

DP

PT

HT

LT

PRESSURE TRANSMITTER

MOTOR STARTER (LOCAL OR MCC)

STATIC PRESSURE SENSOR/TRANSMITTER

DUCT HUMIDITY SENSOR/TRANSMITTER

LEVEL TRANSMITTER

VIBRATION SWITCH

ANGLE VALVE

PLUG VALVE

BALL VALVE

3-WAY VALVE

NEEDLE VALVE/INSTRUMENT VALVE

BUTTERFLY VALVE

GLOBE VALVE

VALVE W/ REDUCERS (GATE VALVE SHOWN)

GATE VALVE

NORMAL

OPEN

NORMAL

CLOSED

CONTROL VALVE SYMBOLS:

M

P

ELECTRIC ACTUATOR

PNEUMATIC ACTUATOR

S SOLENOID ACTUATOR

F FIRESTAT

CARBON DIOXIDE (C02) SENSORCD

ELECTRIC DAMPER ACTUATORDA

CARBON MONOXIDE (C0) SENSORCM

R REFRIGERANT DETECTOR/SENSOR

MANUALLY ACTIVED SWITCHHS

T

FR

H

H

TEMPERATURE SENSOR/TRANSMITTER

HUMIDITY SENSOR/TRANSMITTER

DUCT SMOKE DETECTOR

FREEZESTAT

ROOM THERMOSTAT OR SENSOR

ROOM HUMIDISTAT

S

F FLOW SENSOR

(PULL STAT., PUSH STAT., ETC)

R

M ELECTRIC MOTOR

RELAY

FS FLOW SWITCH

T

DUCT SECURITY BARSSB

S

GATE VALVE W/ 3/4" HOSE THREAD ADAPTER

SAFETY VALVE OR PRESSURE RELIEF VALVE

TEMPERATURE WELL

TWO-WAY CONTROL VALVE

THREE-WAY CONTROL VALVE

VENTURI FLOW METER

PRESSURE REDUCING VALVE (PRV)

AUTOMATIC AIR VENT

PRESSURE GAGE WITH COCK

MANUAL AIR VENT

PIPE ANCHOR

PITCH DOWN IN DIRECTION OF ARROW

DIRECTION OF FLOW

PIPE GUIDE

BRANCH - TOP CONNECTION

ECCENTRIC REDUCER

BRANCH - SIDE CONNECTION

CONCENTRIC REDUCER

RISER UP (ELBOW)

CAPPED PIPE

UNION (SCREWED)

BRANCH - BOTTOM CONNECTION

RISE OR DROP IN PIPE

ORIFICE UNION

FLANGED CONNECTION

STRAINER WITH BLOWDOWN VALVE

TEMPERATURE & PRESSURE PORT

THERMOMETER

MANUAL BALANCING VALVE

SOLENOID VALVE

BALL VALVE

BUTTERFLY VALVE

NEEDLE VALVE

FLOW SWITCH

HOSE BIBB

RISER DOWN (ELBOW)

FLEX CONNECTION

BELLOWS CONNECTION

FLEX PIPE ANGLE GATE VALVE

ANGLE GLOBE VALVE

DIAPHRAGM VALVE

QUICK ACTION VALVE

OS&Y VALVE

OS&Y VALVE WITH SUPERVISORY SWITCH

FLANGED VALVE (GATE VALVE SHOWN)

FLOAT VALVE

ORIFICE FLOW PLATE

PS

FS

(ALL SYMBOLS SHOWN ARE NOT NECESSARILY USED ON THE DRAWINGS)

PRESSURE SWITCH

BLIND FLANGE

WELDED CONNECTION

FLANGED CONNECTION

SOLDERED CONNECTION

THREADED OR "PRESS" CONNECTION

BELL & SPIGOT CONNECTION

SOLVENT CONNECTION

AUTOMATIC BALANCING VALVE

EXISTING EQUIPMENT TO BE REMOVED

EXISTING EQUIPMENT TO REMAIN

NEW EQUIPMENT

VALVE IN RISE

VALVE IN CENTER DROP

VALVE IN DROP

PUMP

(DOUBLE SPHERE NEOPRENE TYPE)

CHECK VALVE (NON SLAM)

PLUG VALVE

GLOBE VALVE

GATE VALVE

VACUUM BREAKER

PROJECT: DYESS BUILDING 7232 & 7233

INDOOR DESIGN CONDITIONS

WINTER: 68°F ± 2°F; (OCCUPIED AREAS)

SUMMER: 75°F ± 2°F; 50% RH ± 10% RH (OCCUPIED AREAS)

MAKE-UP WATERMU

CONDENSER WATER RETURN

CONDENSER WATER SUPPLY

CWR

CWS

HEATING WATER RETURN

HEATING WATER SUPPLY

HWR

HWS

PIPE TO BE REMOVED, "AAA" DENOTES TYPE

AAA

AHU CONDENSATE DRAINCD

DRAIND

REFRIGERANT LIQUIDRL

REFRIGERANT SUCTIONRS

EXISTING PIPE, "AAA" DENOTES TYPEAAA

UNDERGROUND PIPE, "AAA" DENOTES TYPE

AAA

X X X X

CHILLED WATER RETURN

CHILLED WATER SUPPLY

CHR

CHS

CEILING RETURN AIR GRILLE OR RETURN REGISTER

SIDEWALL SUPPLY OR RETURN REGISTER OR GRILLE

STANDARD ECCENTRIC DUCT TRANSITION

STANDARD CONCENTRIC DUCT TRANSITION

STANDARD ROUND BRANCH DUCT (SPIN-IN)

SECTION THROUGH RECTANGULAR SUPPLY DUCT

DUCT ACCESS DOOR

TYPICAL SUPPY AIR TEE WITH SPLITTER DAMPER

VERTICAL DAMPER IN DUCT (OR OPENING)

HORIZONTAL FIRE DAMPER AT FLOOR PENETRATION

CONNECT NEW DUCT TO EXISTING

DUCT WITH ACOUSTICAL LINING

MANUAL VOLUME DAMPER

OR RECTANGULAR ELBOWS, UNLESS NOTED OTHERWISE)

VANED RADIUS ELBOW

VANED ELBOW (PROVIDE VANES IN ALL SQUARE

SECTION THROUGH ROUND DUCT, SUPPLY OR

EXHAUST AS NOTED

SECTION THROUGH RECTANGULAR RETURN DUCT

XX/XX

ACCESS DOOR IN CEILING

A.D.

FLEXIBLE DUCT, SIZE AS SHOWN

RECTANGULAR-TO-ROUND DUCT TRANSITION

A.D.

DAMPER TYPE:

SECTION THROUGH RECTANGULAR RETURN DUCT

CEILING EXHAUST AIR GRILLE OR EXHAUST REGISTER

PATTERN. NO PATTERN SHOWN EQUALS

CEILING SUPPLY AIR DIFFUSER - ARROWS INDICATE

4-WAY

STANDARD RECTANGULAR BRANCH DUCT (45° TAKE-OFF)

STANDARD ROUND BRANCH DUCT (CONICAL)

DN

UP

RELIEF OR EXHAUST AIR DUCT UP

RELIEF OR EXHAUST AIR DUCT DOWN

IN-LINE 90 DEGREE DROP (RISE) IN DUCT

INCLINED DROP IN DUCT

INCLINED RISE IN DUCT

SUPPLY OR OUTSIDE AIR DUCT DOWN

SUPPLY OR OUTSIDE AIR DUCT UP

RETURN AIR DUCT DOWN

RETURN AIR DUCT UP

1 2

POINT OF CHANGE IN DUCT CONSTRUCTION

FLEXIBLE DUCT CONNECTION

DUCT PRESSURE CLASS.

FD - FIRE DAMPER

SD - SMOKE DAMPER

FSD - COMBINATION FIRE/SMOKE DAMPER

BD - GRAVITY BACKDRAFT DAMPER

CD - CONTROL DAMPER

*NO MARK INDICATES MANUAL VOLUME DAMPER

AT FIRE-RATED PARTITION

(SEE BELOW FOR OTHER TYPES)

POINT OF CONNECTION - NEW TO EXISTING

DRAWING NOTE REFERENCE1

72°F ± 2°F; (COMMUNICATION AND MECHANICAL ROOMS)

72°F ± 2°F; (COMMUNICATION AND MECHANICAL ROOMS)

SHEET NUMBER ON WHICH

DETAIL IS DRAWN

RE : 2 / M-201

REFER TO

DRAWING/DETAIL NUMBER

M-201

POINT OF CONNECTION - DEMOLITION TO EXISTING

FAN COIL UNIT(S)FCU(S)

ABOVE FINISHED FLOORAFF

UNLESS OTHERWISE

NOTED

UON

TYPICALTYP

OUTSIDE AIROA

SUPPLY AIRSA

RETURN AIRRA

EXHAUST AIREA

DEDICATED OUTDOOR

AIR UNIT

DOAU

M RISER TYPE IDENTIFIER

RISER NUMBER

WINTER:

SUMMER: 98°F DRY BULB (1.0%)

72°F MEAN COINCIDENT WET BULB (1.0%)

22°F DRY BULB (99.0%)

WEATHER STATION - DYESS AFB/ABILENE, TX

STATION #: 690190

ELEVATION: 1788 FEET; LATITUDE: 32.43°N; LONGITUDE: 99.85°W

DESIGN CONDITIONS FROM ASHRAE FUNDAMENTALS 2009

SUMMER

DEHUMIDIFICATION:

90°F DRY BULB (1.0%)

75°F MEAN COINCIDENT WET BULB (1.0%)

A. REFER TO SPECIFICATIONS FOR MATERIALS AND METHODS FOR CONSTRUCTION.

B. COORDINATE LOCATION OF ALL PENETRATIONS WITH THE BUILDING STRUCTURE.

C. COORDINATE ALL SLAB PENETRATIONS AND SLEEVES PRIOR TO EACH CONCRETE POUR.

D. FURNISH ACCESS DOORS FOR INSTALLATION IN WALLS AND CEILINGS WHERE ACCESS IS REQUIRED TO

CONCEALED MECHANICAL EQUIPMENT, VALVES, CONTROLS, AND OTHER DEVICES.

E. PERFORM WORK IN ACCORDANCE WITH THE LATEST EDITIONS, REVISIONS, AMENDMENTS OR

SUPPLEMENTS OF APPLICABLE STATUTES, ORDINANCES, CODES, OR REGULATIONS OF FEDERAL, STATE AND LOCAL AUTHORITIES HAVING JURISDICTION IN EFFECT ON THE DATE BIDS ARE RECEIVED.

F. WHERE APPROVAL CODES HAVE BEEN ESTABLISHED BY OSHA, UNDERWRITERS LABORATORY, AMERICAN CODES, ANSI, ASME, ASA, ASHRAE, ASTM, ARI, NEC, NFPA, SMACNA, OR THE STATE FIRE INSURANCE REGULATORY BODY, FOLLOW THESE STANDARDS WHETHER OR NOT INDICATED ON THE DRAWINGS.

G. ARRANGE WITH AUTHORITIES AND UTILITY COMPANIES FOR PERMITS, FEES, AND SERVICE CONNECTIONS.

VERIFYING LOCATIONS AND ARRANGEMENTS AND PAYING ALL CHARGES, INCLUDING INSPECTIONS.

H. COORDINATE WORK WITH ARCHITECTURAL FEATURES AND COORDINATE WORK SUCH THAT

INTERFERENCES BETWEEN PIPING, DUCTWORK, EQUIPMENT, PLUMBING WORK, ELECTRICAL WORK, AND

BUILDING STRUCTURE WILL BE AVOIDED.

I. PROVIDE THE ENTIRE SYSTEM AND ITS COMPONENT ITEMS OF EQUIPMENT IN OPERATING CONDITION

WITHOUT OBJECTIONABLE VIBRATION OR NOISE.

J. PROVIDE ALL WIRING AND ELECTRICAL CONTROLS IN ACCORDANCE WITH NFPA 70 (NEC).

K. VERIFY AND DOCUMENT EXISTING CONDITIONS AND DIMENSIONS ON THE JOB SITE PRIOR TO STARTING ANY

WORK.

L. DO NOT SCALE THESE DRAWINGS FOR CONSTRUCTION PURPOSES.

M. ALL DUCTWORK SIZES ARE FREE AIR STREAM DIMENSIONS.

N. INSTALL DUCTWORK AND PIPING TO PROVIDE THE MAXIMUM CLEAR HEIGHT UNDERNEATH.

O. REFER TO ARCHITECTURAL DRAWINGS FOR FRAMING REQUIRED AROUND PIPES AND DUCTS PENETRATING

ROOFS, WALLS, AND FLOORS.

P. REFER TO ARCHITECTURAL ELEVATION DRAWINGS, WHERE THE ARCHITECT HAS DRAWN SUCH ELEVATIONS, FOR THE LOCATION OF ALL WALL MOUNTED DEVICES.

Q. ALL TAPS TO DIFFUSERS SHALL BE SAME SIZE AS DIFFUSER NECK OPENING UNLESS OTHERWISE NOTED.

R. PAINT ANY ABOVE CEILING ITEMS, WHICH CAN BE SEEN THROUGH AIR SLOTS OR GRILLES, FLAT BLACK.

S. PROVIDE PLENUM RATED CABLE, DEVICES, PIPING, ETC. IN PLENUM SPACE.

T. PROVIDE TEMPORARY 30% EFFICIENT, 2" THICK FILTERS OVER RETURN AIR OPENINGS OF ANY AHU'S WHICH ARE PLACED IN SERVICE PRIOR TO COMPLETION OF CONSTRUCTION. REMOVE FILTERS FOR TEST &

BALANCE.

U. ALL HARDWARE AND SOFTWARE FOR THE HVAC DDCS SHALL BE INSTALLED, WIRED, PROGRAMMED, BE MADE OPERATIONAL, AND MAINTAIN SPACE TEMPERATURE CONTROL OF THE HEATING AND COOLING SYSTEM TO COINCIDE WITH COMPLETION OF INSTALLATION OF THE HVAC AIR HANDLING, REFRIGERATION, HEATING, AND PIPING EQUIPMENT; AND PRIOR TO BENEFICIAL OCCUPANCY. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE COORDINATION OF EFFORT BETWEEN THE USING ORGANIZATION, 7CES, AND 7COMM TO INSURE CONNECTIVITY IS AVAILABLE AT BOTH THE FACILITY AND AT THE 7CES HOST WORKSTATION SUCH THAT THERE IS NO DELAY IN MEETING THE ABOVE OPERATIONAL REQUIREMENT TIMELINE. SHOULD, FOR ANY REASON, CONNECTIVITY NOT BE AVAILABLE AT THE FACILITY OR AT 7CES TO

MEET THE ABOVE OPERATIONAL REQUIREMENT TIMELINE, THE CONTRACTOR SHALL UPLOAD THE

CONTROL SOFTWARE BY LAPTOP DIRECTLY TO THE DDCS CONTROL PANEL; AND ADJUST THE

PROGRAMMING SUCH THAT THE HVAC CONTROL SYSTEM BE OPERATIONAL AT THE FACILITY TO MAINTAIN SPACE TEMPERATURE CONTROL. THE GRAPHICAL INTERFACE SOFTWARE SHALL SUBSEQUENTLY BE UPLOADED BY THE CONTRACTOR AT NO COST TO THE GOVERNMENT AT THE 7CES HOST WORKSTATION

WHEN THE CONNECTIVITY BECOMES AVAILABLE.

V. PROVIDE ALL TEMPORARY WORK AS REQUIRED TO SUPPORT EXISTING HVAC GRILLES, DIFFUSERS, ETC.

WHERE THE EXISTING CEILING GRID IS REMOVED.

W. KEEP OPERATIONAL AS MUCH AS POSSIBLE THE EXISTING HVAC SYSTEMS IN THE FACILITY OPERATIONAL

WHILE PERFORMING THE WORK REQUIRED BY THE CONTRACT DOCUMENTS.

X. PAINT ALL EXPOSED INTERIOR AND EXTERIOR GALVANIZED SHEET METAL DUCTWORK, PIPING, EQUIPMENT, AND SUPPORTS WITH EXCEPTION TO FACTORY PAINTED EQUIPMENT AND ENCLOSURES.

Y. DEMOLISH ALL EXISTING MECHANICAL DEVICES RENDERED UNUSABLE BY CONSTRUCTION WORK PERFORMED IN THIS PROJECT. DEMOLITIONS SHALL EXTEND BACK TO THE SOURCE THAT SERVES THE

LOAD.

A. ENERGY CODE - ASHRAE 90.1-2007 - ZONE 3B

VENTILATION - ASHRAE 62.1-2007B.

TAG

AIR DEVICE TAG ON HVAC PLANS:

MAXIMUM AIRFLOW (CFM)

INDICATES A 46" / 30" DIA OVAL DUCT

(NET FREE AREA)

INDICATES A 20" ROUND DUCT (NET

FREE AREA)

INDICATES A 24"x12" RECTANGULAR

DUCT (NET FREE AREA)

24"X12"

20"ø

46/30 Ө

CFM

TYP

SIZE

MARK

AIR DEVICE NECK SIZE

APPROVED

Jacobs Engineering Group Inc.

Texas Registered Engineering Firm F-2966 777 Main Street P.O. Box 901058 Fort Worth, TX 76102

REVISION BY/DATE

FNWZ 99-0013

S.MITCHELL

04/08/15

C.SOLARI

C.SOLARI

M-001

GENERAL NOTES,

SYMBOLS AND

7-38

7-37

W x

W x

W x

W x

W x

W x

W x

W x

W x

W x

W x

Wx

Wx

Wx

Wx

W x

W x

W x

W x

W x

W x

W x

W x

W x

W x

W x

W x

W x

W x

W x

W x

W x

W x

W x

W x

W x

W x

W x

W x

W x

W x

W

Wx

Wx

Wx

Wx

Wx

Wx

Wx

Wx

Wx

Wx

W x

Wx

Wx

Wx

Wx

Wx

Wx

Wx

W x

Wx

Wx

Wx

Wx

Wx

Wx

Wx

Wx

W x

W x

W x

W x

W x

W x

W x

W x

Wx

Wx

Wx

Wx

Wx

Wx

Wx

Wx

Wx

Wx

Wx

Wx

Wx

Wx

Wx

Wx

Wx

Wx

Wx

Wx

Wx

Wx

Wx

Wx

W x

W x

W x

W x

W x

W x

W x

W x

W x W x

W x

W x

W x

W x

W x

W x

W x

W x

CU

x

C U x

CUx

CUx

CUx

CUx

CU

x

CU x

CUx

CU

x

CUx

CUx

CUx

CUx

CUx

CUx

CUx

CUx

CUx

CUx

CU x

C U x

C U x

C U x

C U x

C U x

C U x

C U x

C U x

C U x

C U x

C U x

SSx

SSx

SS

x

SS

x

SS

x

SS

x

SS

x

SS

x

SS

x

SS

x

SSx

SSx

SSx

SSx

SSx

SSx

SSx

SS

x

SS

x

SS

x

SS

x

SS

x

SS

x

SSx

SSx

SSx

SSx

SSx

SSx

SS

x

SS

x

SS

x

SS

x

SS

x

SS

x

SS

x

SS

x

SS

x

SS

x

SS

x

SS

x

SS

x

SSx

SSx

SSx

SSx

SSx

SSx

SSx

SDx

SDx

SDx

SDx

SDx

SDx

SDx

SD

x

SD

x

SD

x

SD

x

SDx

SDx

SDx

SDx

SDx

SDx

SDx

SD

x

SD

x

SD

x

SDx

SDx

SDx

SDx

SDx

EUx

EUx

EUx

EU

x

EU

x

EU

x

EU

x

EU

x

EU

x

EUx

EUx

EUx

EU

x

EU

x

EU

x

EU

x

EU

x

EU

x

EU

x

EU

x x

EUx

EUx

EUx

EUx

EUx

EU

x

EU

x

EU

x

EU

x

EU

x

EU

x

EU

x

EU

x

EU

x

EU

x

EU

x

EU

x

APPROVED

Jacobs Engineering Group Inc.

Texas Registered Engineering Firm F-2966 777 Main Street P.O. Box 901058 Fort Worth, TX 76102

REVISION BY/DATE

FNWZ 99-0013

S.MITCHELL

04/08/15

C.SOLARI

C.SOLARI

KEYED NOTES:

1. EXISTING HOT/CHILLED WATER SUPPLY AND RETURN

PIPING TO BE CAPPED AND ABANDONED IN PLACE.

2. EXISTING HOT/CHILLED WATER SUPPLY AND RETURN

PIPING TO REMAIN. CONVERT TO HOT WATER SERVICE

ONLY.

3. TAP NEW 4" HOT WATER SUPPLY AND RETURN INTO

EXISTING LINES.

4. ROUTE NEW CHILLED AND HOT WATER SUPPLY AND

RETURN PIPING FROM BELOW GRADE UP TO ATTIC. MOUNT

PIPING IN A PIPING ENCLOSURE ALONG SIDE EXTERIOR

WALL. REFER TO ARCHITECTURAL PLANS FOR ENCLOSURE

DETAIL.

5. REFER TO MPE-102 FOR PIPING CONTINUATION IN

CENTRAL PLANT.

6. PROVIDE 7'x7'x3' THRUST BLOCK.

7. PROVIDE 3'x6'x3' THRUST BLOCK.

X

SCALE:

MPE-101 1/32"=1'-0"

GENERAL NOTES:

A. SEE M-001 FOR MECHANICAL…

This is the start of the file's text. The full file is on GovTribe.