OFFUTT AIR FORCE BASE
(092036) 26 27 26-1 (Repair AHU O-Club, B462)
2010 by FEI
SECTION 26 27 26
WIRING DEVICES
PART 1 - GENERAL
1.1 SUMMARY
A. The extent of wiring device work is indicated by drawings. Wiring devices are defined as single discrete units of electrical distribution systems, which are intended to carry but not utilize electric energy.
B. Types of electrical wiring devices in this section include the following:
1. Receptacles.
2. Ground-fault circuit interrupters.
3. Switches.
4. Wallplates.
5. Plugs and connectors.
PART 2 - PRODUCTS
2.1 ACCEPTABLE MANUFACTURERS
A. Manufacturers: Subject to compliance with requirements, provide wiring devices of one (1) of the following:
1. Arrow Hart
2. Bryant Electric Co.
3. Cooper Wiring Devices
4. Daniel Woodhead Co.
5. Hubbell Inc.
6. Leviton Mfg Co.
7. Pass and Seymour Inc.
2.2 FABRICATED WIRING DEVICES
A. General: Provide factory-fabricated wiring devices, in types, colors and electrical ratings for applications indicated and which comply with NEMA Standards Pub/No. WD 1. Provide ivory color devices except as otherwise indicated; color selection to be verified by Contractor with Owner’s
Representative. All devices shall be specification grade.
B. Receptacles:
1. Heavy-Duty Duplex: Provide heavy-duty self-grounding type duplex receptacles, 2-pole, 3-wire, 20-amperes, triple-wipe contacts, 125-volts, with green hexagonal equipment ground screw, metal plaster ears, designed for side and back wiring with spring loaded, screw activated pressure plate, with NEMA configuration 5-20R unless otherwise indicated.
a. P & S Plug Tail receptacles with connector built into back of device and separate polycarbonate connector housing with connector leads are acceptable.
(092036) 26 27 26-2 (Repair AHU O-Club, B462)
2. Ground-Fault Interrupters: Provide "feed-thru" type ground-fault circuit interrupters, with heavy-duty duplex receptacles, capable of protecting connected downstream receptacles on single circuit, and of being installed in a 2-3/4-inch deep outlet box without adapter, grounding type UL Rated Class A, Group 1, rated 20-amperes, 120-volts, 60 Hz; with solid-state ground-fault sensing and signaling; with 5-milliamperes ground-fault trip level; equip with
NEMA configuration 5-20R.
C. Plugs and Connectors:
1. Plugs and Connectors: Provide plugs and connectors with required amperage ratings, voltage ratings and NEMA configurations, which are designed to suit the atmospheric conditions of the equipment surroundings. All plugs and connectors shall be manufactured by Daniel
Woodhead Company or approved equal by one (1) of the following manufacturers:
a. Hubbell Inc.
b. Pass and Seymour Inc.
D. Switches:
1. General: Switches shall be provided as specified in this section. Additional features such as key operator, rocker, and lighted toggle shall be provided where indicated on the drawings.
2. Single-Pole: Provide heavy-duty flush single-pole AC quiet, self-grounding type switches, 20-amperes, 120/277-volts, with mounting yoke insulated from mechanism, equip with plaster ears, toggle switch handle, and side-wired screw terminals.
3. Three-Way: Provide heavy-duty flush 3-way AC quiet, self-grounding type switches, 20-amperes, 120/277-volts, with mounting yoke insulated from mechanism, equip with plaster ears, toggle switch handles and side-wired screw terminals.
2.3 WIRING DEVICE ACCESSORIES
A. Wallplates: Provide wallplates for single and combination wiring devices, of types, sizes and with ganging and cutouts as indicated. Select plates which mate and match wiring devices to which attached. Construct with metal screws for securing plates to devices; screw heads colored to match finish of plates.
1. Finished Areas:
Material and Finish: 0.04-inch thick, type 302 satin finished stainless steel
2. Unfinished Areas:
Material and Finish: Steel plate, galvanized.
3. Surface-mounted boxes in unfinished areas shall be furnished with 4-inch square raised covers, with openings to fit device or devices to be installed.
B. Furnish cast metallic weatherproof covers for receptacle installed outdoors, in wet locations or shown as weatherproof. Provide in-use weatherproof covers where required per NEC.
(092036) 26 27 26-3 (Repair AHU O-Club, B462)
PART 3 - EXECUTION
3.1 INSTALLATION OF WIRING DEVICES
A. Install wiring devices as indicated, in accordance with manufacturer's written instructions, applicable requirements of NEC and NECA's "Standard of Installation" and in accordance with recognized industry practices to fulfill project requirements.
B. Coordinate with other work, including painting, electrical boxes and wiring work, as necessary to interface installation of wiring devices with other work.
C. Install wiring devices only in electrical boxes, which are clean; free from excess building materials, dirt and debris.
D. Install wallplates after painting work is completed.
E. The continuity of branch circuit conductors shall not depend on device connections such as lampholders, receptacles, etc. where the removal of the device would interrupt the continuity. Branch circuit conductors shall be spliced with jumpers to connect the device.
F. Connections of wire to devices shall be screw tightened (except devices with built-in connector/leads).
Connections using only spring pressure are not acceptable.
G. Tighten connectors and terminals, including screws and bolts, in accordance with equipment manufacturer's published torque tightening values for wiring devices. Where manufacturer's torquing requirements are not indicated, tighten connectors and terminals to comply with tightening torques specified in UL Standards 486A and B. Use properly scaled torque indicating hand tool.
H. All switches and receptacles with exposed terminals shall be wrapped with insulating tape equal to
Scotch No. 33 such that no live parts are left exposed.
3.2 PROTECTION OF WALLPLATES AND RECEPTACLES
A. Upon installation of wallplates and receptacles, advise Contractor regarding proper and cautious use of convenience outlets. At time of Substantial Completion, replace those items, which have been damaged, including those burned and scored by faulty plugs and those, which are not clean and free from paint, dirt and debris.
3.3 GROUNDING
A. Provide equipment grounding connections for wiring devices, unless otherwise indicated. Tighten connections to comply with tightening torques specified in UL Standard 486A to assure permanent and effective grounds.
3.4 TESTING
A. Prior to energizing circuitry, test wiring for electrical continuity, and for short-circuits. Ensure proper polarity of connections is maintained. Subsequent to energization, test wiring devices to demonstrate compliance with requirements.
END OF SECTION