OFFUTT AIR FORCE BASE
(092036) 26 05 26-1 (Repair AHU O-Club, B462)
2010 by FEI
SECTION 26 05 26
GROUNDING
PART 1 - GENERAL
1.1 SUMMARY
A. Extent of grounding work is indicated by drawings, schedules and as specified herein.
B. Types of grounding specified in this section include the following:
1. Solid grounding.
C. Requirements of this section apply to electrical grounding work specified elsewhere in these specifications.
PART 2 - PRODUCTS
2.1 GROUNDING SYSTEMS
A. Materials and Components:
1. General: Except as otherwise indicated, provide electrical grounding systems indicated; with assembly of materials, including, but not limited to, cables/wires, connectors, terminals
(solderless lugs), grounding rods/electrodes, bonding jumper braid and additional accessories needed for complete installation. Where more than one type unit meets indicated requirements, selection is Installer's option. Where materials or components are not indicated, provide products complying with NEC, UL, IEEE and established industry standards for applications indicated.
B. Conductors: Provide copper electrical grounding conductors for grounding connections matching power supply wiring materials and sized according to NEC. All conduits shall contain a minimum of one (1) separate equipment grounding conductor identified and sized according to NEC.
C. Bonding Jumper Braid: Copper braided tape, constructed of 30-gage bare copper wires and properly sized for indicated applications.
D. Flexible Jumper Strap: Flexible flat conductor, 480 strands of 30-gage bare copper wire; 3/4-inch wide, 9-1/2-inches long; 48,250cm. Protect braid with copper bolt hole ends with holes sized for 3/8-inch dia.
bolts.
E. Bonding Plates, Connectors, Terminals and Clamps: Provide electrical bonding plates, connectors, terminals, lugs and clamps as recommended by bonding plate, connector, terminal and clamp manufacturers for indicated applications.
F. Ground Rods:
1. Sectional Ground Rods: Steel with copper welded exterior, 3/4-inch diameter.
G. Electrical Grounding Connection Accessories: Provide electrical insulating tape, heat-shrinkable insulating tubing, welding materials, bonding straps, as recommended by accessories manufacturers for type services indicated.
OFFUTT AIR FORCE BASE
(092036) 26 05 26-2 (Repair AHU O-Club, B462)
2010 by FEI
H. Exothermic Welded Connections: Comply with AWS Code for procedures, appearance, and quality of welds; and methods used in correcting welding work. Provide welded connections where grounding conductors connect to underground grounding rods/electrodes.
PART 3 - EXECUTION
3.1 INSPECTION
A. Installer must examine areas and conditions under which electrical grounding connections are to be made and notify Contractor in writing of conditions detrimental to proper completion of work. Do not proceed with work until unsatisfactory conditions have been corrected in a manner acceptable to
Installer.
3.2 INSTALLATION OF ELECTRICAL GROUNDING
A. General: Install electrical grounding systems where shown, in accordance with applicable portions of
NEC, with NECA's "Standard of Installation" and in accordance with recognized industry practices to ensure that products comply with requirements and serve intended functions.
B. The equipment grounding conductor shall be connected directly to the equipment grounding screw provided on receptacles.
C. At switch outlets, where self-grounding type switches are installed in metal boxes, the equipment grounding conductor shall be connected directly to the metal box.
D. Coordinate with other electrical work as necessary to interface installation of electrical grounding system with other work.
E. Weld grounding conductors to underground grounding rods/electrodes. Welds that are puffed up or that show convex surfaces indicating improper cleaning are not acceptable.
F. Install bonding jumpers with ground clamps on water meter piping to electrically bypass water meters.
G. Install clamp-on connectors only on thoroughly cleaned metal contact surfaces, to ensure electrical conductivity and circuit integrity.
3.3 FIELD QUALITY CONTROL
A. Upon completion of installation of electrical grounding systems, test ground resistance with ground resistance tester. Where tests show resistance to ground is over 5 ohms, take appropriate action to reduce resistance to 5 ohms or less, by driving additional ground rods and/or by chemically treating soil encircling ground rod; then retest to demonstrate compliance.
END OF SECTION