Exhibit D 36C2506R0006- Conceptual Floor Plan and Finishes Revised 3.26.2026.pdf
PDF 2 MB Posted
- Attached to
- X1DB--Kalamazoo Clinic RFI Response #4
- Solicitation number
- 36C25026R0006
About this file
This document is Exhibit D to a lease solicitation (RLP 36C25026R0006) for a Community Based Outpatient Clinic (CBOC) facility in Kalamazoo, containing comprehensive conceptual floor plans, room requirements, and interior finishes specifications.
The exhibit specifies 67 individual rooms totaling 9,438 square feet, including clinical spaces (six general exam rooms, specialty exam rooms for women's health, telehealth, and tele-retinal imaging, procedure and exam rooms), patient support areas (toilets, blood draw stations, laboratory processing), administrative spaces (staff workstations, conference rooms, offices), and support functions (storage, telecommunications, HVAC, janitorial). The lessor is responsible for adapting the provided schematic layout to their actual space while meeting all functional requirements. Key clinical specifications include exam rooms with 120 square feet, procedure rooms with specialized equipment zones, bariatric accommodations, and accessible design features. Interior finishes requirements detail specific flooring materials (porcelain tile, carpet tile, luxury vinyl tile, rubber flooring), wall treatments, paint colors (Sherwin Williams and Benjamin Moore specifications provided), and ceiling finishes. The document mandates specific equipment and systems including nurse call systems, physical access control using Hirsch Velocity FICAM with PIV cards, security surveillance with NVR streaming capability, video teleconferencing infrastructure, public address systems, and two-way radio systems. Special requirements include HVAC temperature control at 70±5°F with humidity not exceeding 50±5%, IT room specifications with dedicated climate control and security measures, emergency generator capability, privacy curtains (Architex DRx6001), door hardware per Grand Master Key System specifications, and telecommunications cabling per CAT 6A standards. The procurement responsibility matrix designates the lessor for most finishes, signage, hardware, and installations, with the government providing furniture, biohazard bins, feminine hygiene dispensers, artwork, and televisions.
View the file
Other files
Show all 32
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DESIGN SCHEMATIC
The schematic above is representative of the layout required for this space. The Lessor is responsible for using the room schedule below and this layout to adapt the Government’s requirements to the space. Specific questions regarding the layout should be directed to the Lease Contracting Officer for resolution. The Government is not responsible for errors, omissions, or assumptions made by the Lessor in the adaption of the Government’s requirements to the Lessor’s space.
RLP 36C25026R0006 - Exhibit D- Conceptual Floor Plan, Room Requirements , and Finishes
VA Typical Room Layouts:
Section 3
KALAMAZOO VA CLINIC ROOM LISTING
Space Description: ROOMS Sq. Ftg. (ea)* Cum. Area Vestibule / Indoor Buffer 1 120 120 Public Heath Kiosk 1 20 20 Lactation Room 2 80 160 Interview Patient Care Room 1 140 140 Information / Welcome Area Alcove 1 20 20 Veteran and Guest Seating 1 260 260 Family Seating 1 60 60 General Storage 1 30 30 Bariatric Patient Toilet 1 75 75 Universal Single Occupant Toilet 3 75 225 Housekeeping Aides Closet (HAC) 2 60 120 PACT Teamwork Shared Office 1 100 100 Veteran Video Connect Station 1 80 80 Refreshment Station 1 80 80 Vending Area 1 30 30 Shared Group Room 1 240 240 Shared Group Storage Room 1 60 60 General Exam Room 6 120 720 PACT Storage 1 56 56 Blood Draw Station 1 80 80 Bariatric Blood Draw Station 1 100 100 Laboratory Specimen Processing 1 125 125 Laboratory Clean Supply Room 1 60 60 Specimen Collection Toilet 1 65 65 Tele-Retinal Imaging Exam Room 1 140 140 Women Veteran Exam Room 1 140 140 Women Veteran Exam Room Toilet 1 75 75 Multi-Use Bariatric Exam Room 1 210 210 Podiatry Exam Room 1 140 140 Counseling Patient Care Consult 1 125 125 Patient Height and Weight Alcove 1 60 60 Telehealth Exam Room 1 150 150 Equipment Alcove 1 50 50 Supply Alcove 1 50 50 Hoteling Workstation 1 96 96 Clinical Staff Workstation 1 224 224 Copy/Supply Alcove 1 50 50 CBOC Huddle Space 1 180 180 Medication Alcove 1 50 50 Full Gas Cylinder Storage 1 40 40 Empty Gas Cylinder Storage 1 40 40 Medical Equipment Storage Room 1 80 80 Clinical Supplies Storage Room 1 60 60 Telecommunications Room (OIT) 1 100 100 Staff Workroom/ Storage Room 1 140 140 Staff Conference Room 1 240 240 Share Leadership Office 1 140 140 ID/Photo Alcove 1 56 56 HAS Storage 1 85 85 Staff Locker Alcove 1 40 40 Clinical Neighborhood Staff Room 1 125 125 Staff Wellness/Fitness Room 1 160 160 PACT Pharmacist Office 1 120 120 Admin/Flex Office 1 100 100 Logistice Entrance/Drop-Off 1 0 0 Covered Drop-Off/Pickup 1 0 0 Veteran Outdoor Seating Area 1 0 0 Staff Outdoor Eating Area 1 0 0 Subtotal 67 6292 *Allowance for Corridors, Common areas. (50%) 3146 Total 9438 *Space requirements and Sq. Ftg. Estimates, according to VA CO Clinical Standa rds.
A. SPACE DETAILS:
A.1 Entry Vestibule
A.1.1 Forty-two inches (42”) minimum entrance door with air lock and automatic push button door opener.
A.1.2 Sensors shall be motioned detector type with self-contained units mounted on the headers. If sliding doors are utilized and accepted as required exits, the doors shall be designed to open manually in the event of a power failure.
A.1.3 Walk-off entry mats shall be provided and maintained by lessor.
A.1.4 Hand sanitizer dispenser, wall mounted.
A.2 Reception A.2.1 Thirty-two inches (42”) minimum clearance entrance door, entry lock set.
A.2.2 Space and utilities for two (2) staff workstations with opening and countertop for wheelchair access.
A.2.3 Panic button to be mounted to VA-provided furniture in locations determined by the VA. Main panic alarm station console to be in reception.
A.2.4 Main nurse call station console.
A.2.5 Space and utilities for one (1) multi-function printer.
A.2.6 Clock.
A.2.7 Coat hooks.
A.2.8 Full size step-on opener trashcan.
A.2.9 Hand sanitizer dispenser, wall mounted.
A.3 Wheelchair Alcove A.3.1 Space for three (3) VA provided wheelchairs.
A.3.2 Location should be near entry vestibule and/or reception.
A.4 Waiting Room A.4.1 All doors to waiting room to have forty-twoinches(42”) minimum door. Doors from waiting area to clinical care spaces to have card reader access and automatic push button door opener.
A.4.2 Television.
A.4.3 Full size step-on opener trashcan.
A.4.4 Hand sanitizer dispenser, wall mounted.
A.5 Drinking Fountain Alcove A.5.1 Alcove sized to minimum one (1) drinking fountain with water bottle fill dispenser.
A.6 Lab with blood specimen collection A.6.1 Entry doors to be forty-two inches (42”) minimum with privacy lock set.
A.6.2 A minimum of ten (10’0”) lineal feet of both upper and lower casework with under mounted stainless-steel sink.
A.6.3 Handheld eye wash station with temperature control mixing valve at sink.
A.6.4 Ceiling mounted cubical curtain track sized to fit around blood specimen chair.
A.6.5 Clock.
A.6.6 Coat hooks.
A.6.7 Trashcan, twelve (12) gallons, hands free.
A.6.8 Biohazard collection bin, six (6) gallons, hands free, red.
A.6.9 Sharps container, lockable, three (3) gallons, wall mounted.
A.6.10 Glove box holder, wall mounted.
A.6.11 Hand sanitizer dispenser, wall mounted.
A.6.12 Lab Toilet with Keyed Water Shutoff A.6.13 Lab to be provided independent HVAC temperature controls to adjust temperature within due to increased electrical heat producing equipment present.
A.7 Alcove, Height/Weight Accessible Station
A.7.1 Scale.
A.7.2 Stadiometer, wall mounted.
A.7.3 Coat hook.
A.7.4 Hand sanitizer dispenser, wall mounted.
A.8 Alcove, Equipment A.8.1 Hand sanitizer dispenser, wall mounted.
A.9 Alcove, Supply A.9.1 Lockable cabinets.
A.9.2 Hand sanitizer dispenser, wall mounted.
A.10 Alcove, Medication A.10.1 Lockable cabinets.
A.10.2 Hand sanitizer dispenser, wall mounted.
A.11 Alcove, Team Copy/Supply A.11.1 Lockable cabinets.
A.11.2 Hand sanitizer dispenser, wall mounted.
A.12 Alcove, Staff Personal Property Locker A.12.1 Lockable lockers.
A.12.2 Clock.
A.12.3 Coat hooks.
A.12.4 Trashcan, twelve (12) gallons, hands free.
A.12.5 Hand sanitizer dispenser, wall mounted.
A.13 Refreshment Station A.13.1 Lockable cabinets.
A.13.2 Space available in reception area to support refreshment station.
A.13.3 Hand sanitizer dispenser, wall mounted.
A.14 Exam Room A.14.1 Entry doors to be forty-two inches (42”) minimum with privacy lock set.
A.14.2 Room pressure: Neutral.
A.14.3 Panic button mounted to VA-provided furniture.
A.14.4 Sink, wall mounted.
A.14.5 Paper towel dispenser.
A.14.6 Soap dispenser.
A.14.7 Hand sanitizer dispenser.
A.14.8 Clock.
A.14.9 Coat hooks.
A.14.10 Trashcan, twelve (12) gallons, hands free.
A.14.11 Biohazard collection bin, six (6) gallons, hands free, red.
A.14.12 Sharps container, lockable, three (3) gallons, wall mounted.
A.14.13 Glove box holder, wall mounted.
A.14.14 A.14.15 Ceiling mounted track for cubicle curtain, sized to fit around exam bed.
A.14.16 Diagnostic set, wall mounted.
A.14.17 Privacy Curtain, Architex DRx6001
A.15 Consult Room A.15.1 Entry doors to be forty-two inches (42”) minimum with privacy lock set.
A.15.2 Room pressure: Neutral.
A.15.3 Panic Button mounted to VA-provided furniture.
A.15.4 Hand sanitizer dispenser.
A.15.5 Clock.
A.15.6 Coat hooks.
A.15.7 Trashcan, twelve (12) gallons, hands free.
A.16 Conference Room/Group Therapy A.16.1 Entry doors to be forty-two inches (42”) minimum with privacy lock set.
A.16.2 Television, wall mounted.
A.16.3 Eight (8) coat hooks, wall mounted.
A.16.4 Clock.
A.16.5 Trashcan, twelve (12) gallons, hands free.
A.16.6 Hand sanitizer dispenser.
A.17 Storage Room A.17.1 Entry door to be thirty-six inches (36”) minimum clearance, storage room lock set.
A.17.2 Room pressure: Positive.
A.17.3 Space cannot have a water source or window.
A.18 Staff Lounge A.18.1 Entry door to be thirty-two inches (32”) minimum clearance, entry lock set.
A.18.2 A minimum of six (6’-0”) lineal feet of both upper and lower casework with under mounted stainless-steel sink and countertop surface to accommodate a microwave and coffee pot.
A.18.3 Panic button to be mounted on wall.
A.18.4 Ten (10) coat hooks.
A.18.5 Clock.
A.18.6 Hand sanitizer dispenser.
A.19 Open Administrative Space A.19.1 Entry door to be forty-two inches (42”) minimum, entry lock set.
A.19.2 Space and utilities for eight (8) staff workstations.
A.19.3 Sink, wall mounted.
A.19.4 Panic button per staff workstation to be mounted to VA provided furniture.
A.19.5 Ten (10) coat hooks.
A.19.6 Clock.
A.19.7 Hand sanitizer dispenser.
A.19.8 Trashcan, twelve (12) gallons, hands free.
A.20 IT Room A.20.1 The size of this room shall be a minimum of ten feet (10’) x thirteen feet (13’).
A.20.2 No windows are allowed.
A.20.3 No floor drains are allowed.
A.20.4 Four feet (4’) x eight feet (8’) sheets of three-quarter inch (¾”) fire retardant plywood mounted on the wall and painted.
A.20.5 Four (4) 208VAC/60 HZ/30 AMPS, single phase electrical outlets on dedicated circuits.
A.20.6 Four (4) 120VAC/60 HZ/20 AMPS, single phase electrical outlets on dedicated circuits.
A.20.7 Data rack, Hubbell model HPW96RR19 or equal, eight (8’) feet high. Minimum one (1) required.
A.20.8 Include data punch down panels per the data requirements listed throughout the functional room listing to accommodate approximately forty-eight (48) data outlets with two (2) jacks each and an additional forty-eight (48) spares.
A.20.9 Exterior walls of brick and masonry construction are acceptable. Exterior walls which are composed of wood frame and siding require an interior backing of steel security screen mesh or sheet partition.
A.20.10 Doors must be fitted with a mortise lock with a deadlock feature with interior hinges and swing outward from the IT room.
A.20.11 A.20.12 No glass doors or doors with glass panes.
A.20.13 All perimeter room walls, including drywall, must extend from floor slab to structure above to ensure physical security, in which case no ceiling is required. Interstitial overhead areas which enable entry into a secure room from an unsecured room must be barricaded by the installation of a suitable partition in the interstitial space with prevents “up and over” access. Ventilation grills on doors and air circulation ducts which exceed 0.06 m2 (100 square inches) in areas must be reinforced to prevent their removal from outside of the room. Other possible access means such as dumbwaiter shafts, roof or wall ventilator housing, trapdoors, etc., must be secured by appropriate means.
A.20.14 A motion intrusion detection alarm system shall be installed which detects entry into the room.
Equipment which operates on the principle of narrow beam interception, door contacts, microwave, or photoelectric eye are unacceptable. Intrusion detectors must have the following essential features:
A.20.15 An internal, automatic charging direct current (DC) standby power supply and a primary alternating current (AC) power operation.
A.20.16 A remote, key operated activation/deactivation switch installed outside the room and adjacent to the room entrance door frame.
A.20.17 An automatic reset capability following an intrusion detection.
A.20.18 A local alarm level of eighty decibels (80 dB) minimum to ninety decibels (90 dB) maximum within the configuration of the protected area.
A.20.19 Dedicated heating, ventilation, and air conditioning (HVAC) unit for IT closet that maintains temperature and humidity levels within the facility where information system resides at acceptable levels (per information system manufacturer requirements) and consistently monitors temperature and humidity. Designed to accommodate the telecommunications system: the temperature of this room shall be maintained at 70° ±5° F, with humidity control not to exceed 50% ±5% relative humidity, regardless of outside temperature or seasonal changes, seven (7) days a week, in order to minimize damage to government-owned-equipment (GOE) delicate electronic circuits for computerized systems only.
A.20.20 Install a dedicated split air conditioning unit with thermostat located in the room. Condensate must be pumped from the room to a drain in another area and not have a floor drain in this room.
A.20.21 Emergency power off (EPO) for all power to IT closets which are on a separate panel than main circuit board. Switch shall be clearly labeled, easily accessible and protected from unauthorized activation.
A.20.22 Automatic emergency lighting on separate circuit for information systems that activates in the event of a power outage or disruption and that covers emergency exits and evacuation routes within the facility.
A.20.23 Provide master shutoff valve(s) for water source(s) within proximity to information systems that are accessible to VA staff. Shutoff valves should be located outside of the IT closet.
A.20.24 Fire suppression and detection devices/systems for the information system that are supported by an independent energy source, activate automatically, and notify the organization and emergency responders in the event of a fire, provide automatic notification of any activation to the organization and emergency responders, and provides automatic fire suppression capability for the information system when the facility is not staffed on a continuous basis. (Can include but not limited to sprinkler systems, handheld fire extinguishers, fixed fire hoses, and smoke detectors)
A.20.25 The room shall not be located directly below laboratories, kitchens, laundries, toilets, showers, or other areas where water service is provided.
A.20.26 The door requires multifactor security (deadbolt and another form of electronic security), to permit two (2) form identification and data collection twenty-four (24) hour per day seven (7) days per week, of entrance, exit, and duration within room (Example forms of identification are badge, key card, electronic cipher pin, and biometrics).
A.20.27 Doors and frames shall be two (2) hour fire resistive construction. Provided intrusion detection will provide door and lock status sensors and motion detectors.
B. PROCUREMENT/INSTALLATION REQUIREMENTS
These requirements are not inclusive to all items required by the Lessor for a full and acceptable product.
Interior Finishes Notes
General Notes
A. Hollow metal frames and doors to be painted.
B. Window sills to be solid surface fabrication.
C. Resilient base to be 4", unless otherwise noted.
D. Provide painted finishes only on inside of exterior walls (no wall covering).
E. Floor material transitions to occur at centerline of door, unless otherwise noted.
F. Wall brackets, grills, fire extinguisher cabinets, fin tube radiation, etc. to be painted to match adjacent wall color G. Interior stairwell treads to be concrete with rubber nosings and RFT, LVT or RF landings. Stair nosings to be a contrasting color for safety.
H. Coordinate height o f wall protection with wall-mounted devices.
I. Gypsum board soffits may be substituted for ACT above locations such as nurse stations, patient transaction/consultation desks reception desks and lobby/waiting areas.
J. Soffit above upper cabinets to be gypsum board.
K. Refer to FGI recommendations regarding indoor air quality, sustainability and life cycle of materials.
L. Solid surface countertops to have sides and backsplash at walls.
Schedule Notes
1. CT tile to 7'-0" on plumbing and adjacent wall(s) with paint above to ceiling.
2. Tile base to be coved.
3. Integral coved base 6" high tightly sealed to walls.
4. If sink is present, use hard suface flooring as noted.
5. Lead lined walls and control area view window.
6. Flooring and base to match adjacent area flooring material and base.
7. Use gasketed, clip down ACT/grid system
8. Use slip-retardant finish on floor material
9. Public and exposed open stairways to be treated similar to adjacent spaces using CT/PT/RF on treads.
Stair nosings to be a contrasting color for safety
10. Note that if wall saver designed chairs are used, no wall protection is required.
11. Extend all room partitions to structural deck.
12. CT above countertop on wall.
13. Ceiling height as required to acommodate equipment.
14. Cove QT base, 6" high.
15. No separate trim at top of base, use alternate method to seal to wall.
16. Ceiling suspension system should be fabricated from nonferromagnetic material.
17. Aesthetic specialty materials may be used as accents where the design and budget permits.
18. Ceiling tile to meet USDA regulations.
19. Floors to be slip-resistant and meet ANSI 326.3 for measuring dynamic coefficient of friction for hard surfaces
20. Wall base on gyp board but not needed on any exterior materials such as brick, metal, or stone walls.
21. Wall CT and ceiling to meet building code light reflectancy standards.
22. Space may be room or area within a room. Coordinate finishes with adjacent spaces.
23. Provide 3/4" painted plywood where required by Telecommunications.
24 Window(s) required to have blackout glazing; installation tight to the window gasket
Acrovyn mechanically mtd, flush corner guards floor to finished ceiling; to be determined by VA ID
CPT1 Carpet Tile FOH CPT Tile FOH: Mannington Canapy II Cedar (82122) Brick Ashlar
24x24
CPT2 Carpet Tile Offices CPT Tile Offices: Mannington ALA Mode Cedar (82122) Lertical
Ashlar 24x24
PT Porcelain Floor Tile Dal Tile Marble Attache MA86, Matte 24x48, Brick Lay
CG Corner Guard
Kalamazoo Community Based Outpatient Clinic (CBOC) RLP #
Abbreviation Description All finishes to be equal to or better than the
ACCENT Aesthetic Specialty Materials 3 Form, Reception and waiting area dividers, Digital Print White
Oak + Vade, Varia 3/8, Vellum F04
AF Access Flooring To be determined by VA ID
AT Acoustical Ceiling Tile (Not Used) Ceiling Attenuation Class (CAC) ASTM E413, 40-44 range & NRD
(Noise Reduction Coefficient) ASTM C423, Min 0.55
AT-SP To be determined by VA IDAcoustical Scrubbable Ceiling Tile (with sprayed plastic finish)
BG Bumper Guard Acrovyn Chameleon mechanically mtd Crash Rails; to be determined by VA ID
MAT Carpet Walk Off mat Tandus Centiva, Assertive Series, Walk Off; to be determined by
VA ID
LVT2 Luxury Vinyl Tile FOH Manningtion: LVT FOH Vintage Walnut Hawkshaw (MSC118)
5x36
GWB Gypsum Wallboard Systems 5/8" drywall, level 5 finish
LVT1 Luxury Vinyl Tile BOH Mannington; LVT BOH Vintage Walnut Hayworth (MSC124)
5x36
RF Rubber Flooring Johnsonite Metallurgy Series; style, color, and location to be determined by VA ID
RWC Rigid Vinyl Wall Covering (wall protection) Acrovyn Chameleon Series: sytle and color to be determined by
VA ID
PRB Profile Rubber Base ( height may vary) Johnsonite Millwork Attache, Profile 6 Inches, MW XX E 66
Either Ore
RB Resilient Base Johnsonite Traditional Resilient 1/8" Base 4" high Either Ore;
locations to be determined by VA ID
GRT
Grout Floor and Wall; Bathrooms, Breakroom backsplash and behind drinking fountains TEC 973 Warm Taupe
SS
Corian Counters: Bathrooms, Reception (Waterfall), and
Breakroom Silver Linear
SC High Build Glazed Coating (special coating) Sherwin Williams, commercial interior Low/no VOC
TRNS Transition Schluter Quadec Brushed Antique Bronze, NOTE: all metal transitions and trim to match Schluter bruched antique
Bronze.
WSV Exam Rm & Lab; Mannington, Burlap, HullWelded Sheet vinyl
Special Faced Acoustical TileSP CAC 40-44 to be determined by VA ID
DR Doors / Stain for Reception and in Bathrooms (Sinks) Architectural Wood Doors, White Maple Ravine RA18
WT2 Wall tile for Drinking Fountains floor to ceiling Herringbone pattern, Virginia Tile, Marazzi Treverksoul Brown
MRZ TR8R 4x21x3/8
Casework Exam Rooms Herman Miller Compass (Color to be specified by VA ID)
WT1
Wall Tile for Bathrooms (4 feet high on walls) and backsplash for Breakroom (under cabinets to countertop)
Brick lay / backsplash for breakroom; brick lay dal tile color wheel
4x12 matte arctic white
P3 Paint Accent Office SW 7046 Anonymous;
P4 Paint Nutral BOH: SW 7638 Jogging Path;
P1 Paint Main Area: SW 9165 Gossamer Veil
P2 Paint Accent Reception: Benjamin Moore HC-133 Yourktowne Green;
P5 Paint Accent Exams SW 6207 Retreat
P6 Paint Bathroom Walls: SW 7024 Functional Gray
ROW NO. DEPARTMENT PRIMARY
ROOM CODE ROOM NAMES (VA) QTY ALTERNATE ROOM
CODES (VA)
A
LT
R O
O M
C O
D E
A
LT
R O
O M
C O
D E
A
LT
R O
O M
C O
D E
A
LT
R O
O M
C O
D E
A
LT
R O
O M
C O
D E
A
LT
R O
O M
C O
D E
A
LT
R O
O M
C O
D E
A
LT
R O
O M
C O
D E
A
LT
R O
O M
C O
D E
A
LT
R O
O M
C O
D E
A
LT
R O
O M
C O
D E
A
LT
R O
O M
C O
D E
A
LT
R O
O M
C O
D E
A
LT
R O
O M
C O
D E
14 ROOM NAME FGI EQUIVALENT FOR
ASHRAE 170
FGI EQUIVALENT FOR
TABLE 1.2-6
1 - COMMUNITY
BASED OUTPATIENT
CLINIC (CBOC) (265)
LOB02 CBOC Vestibule / Indoor Buffer, Bldg Sprt
1 LOB02 VESTIBULE
1 - COMMUNITY
BASED OUTPATIENT
CLINIC (CBOC) (265)
NCWD4 CBOC Public Health Kiosk, Clncl Sprt
NCWD4, SRLW1, CLSC1,
RCHK2, RECP4, CSWH1,
RCHK1
NCWD4 SRLW1 CLSC1 RCHK2 RECP4 CSWH1 RCHK1 ALCOVE PATIENT CORRIDOR
1 - COMMUNITY
BASED OUTPATIENT
CLINIC (CBOC) (265)
LACO1 CBOC Lactation Room, Wm Vet Svc
1 LACO1 LACO1 LACTATION ROOM
1 - COMMUNITY
BASED OUTPATIENT
CLINIC (CBOC) (265)
OFDC1 CBOC Interview Patient Care Room
1 OFDC1, CLCEX, OFDC2,
CMP01 OFDC1 CLCEX OFDC2 CMP01 CONSULT CONSULTATION
1 - COMMUNITY
BASED OUTPATIENT
CLINIC (CBOC) (265)
NCWD4
Veteran Information / Welcome Area Storage Alcove, CBOC
NCWD4, SRLW1, CLSC1,
RCHK2, RECP4, CSWH1,
RCHK1
NCWD4 SRLW1 CLSC1 RCHK2 RECP4 CSWH1 RCHK1 ALCOVE PATIENT CORRIDOR
1 - COMMUNITY
BASED OUTPATIENT
CLINIC (CBOC) (265)
WRO1 CBOC Veteran / Guest Seating, Bldg Sprt
WRO1, WRF01, WRC06,
WTG20, WTG10, WTF03,
WTPC3, WRC05,
WTG06, LOB06, WTF01,
WTG21, WTG07, WTG28,
WTG27
WRO1 /
WRF01 WRC06 WTG20 WTG10 WTF03 WTPC3 WRC05 WTG06 LOB06 WTF01 WTG21 WTG07 WTG28 WTG27 WAITING PUBLIC SPACE
1 - COMMUNITY
BASED OUTPATIENT
CLINIC (CBOC) (265)
WRO1 CBOC Family Seating, Bldg Sprt
WRO1, WRF01, WRC06,
WTG20, WTG10, WTF03,
WTPC3, WRC05,
WTG06, LOB06, WTF01,
WTG21, WTG07, WTG28,
WTG27
WRO1 /
WRF01 WRC06 WTG20 WTG10 WTF03 WTPC3 WRC05 WTG06 LOB06 WTF01 WTG21 WTG07 WTG28 WTG27 WAITING PUBLIC SPACE
1 - COMMUNITY
BASED OUTPATIENT
CLINIC (CBOC) (265)
SRE01 CBOC General Storage, Bldg Sprt
SRE01, SRS01, SRS02,
SRSE1, CLHS4, STSP4,
CLCS1, SRCS1, FILE1,
CLHS3, SRPB1, PRC03,
SRE01 SRS01 SRS02 SRSE1 STSP4 CLCS1 SRCS1 FILE1 CLHS3 SRPB1 PRC03 CLHS2 FSCS1 STORAGE CLEAN STORAGE
1 - COMMUNITY
BASED OUTPATIENT
CLINIC (CBOC) (265)
TNPG1 CBOC Bariatric Patient Toilet, Bldg Sprt
TNPG1, TLTF2, TLTF3,
TLTM2, TLTF1, TNPM2,
TLTB1, TPG01, TNPFM,
TPB01, TNPM3, TNPF3,
TLTU1 TNPG1 TLTF2 TLTF3 TLTM2 TLTF1 TNPM2 TLTB1 TPG01 TNPFM TPB01 TNPM3 TNPF3 TLTM1 TOILET TOILET ROOM TOILET ROOM
1 - COMMUNITY
BASED OUTPATIENT
CLINIC (CBOC) (265)
TNPG1 CBOC Universal Single Occupant Toilet, Bldg Sprt
TNPG1, TLTF2, TLTF3,
TLTM2, TLTF1, TNPM2,
TLTB1, TPG01, TNPFM,
TPB01, TNPM3, TNPF3,
TLTU1 TNPG1 TLTF2 TLTF3 TLTM2 TLTF1 TNPM2 TLTB1 TPG01 TNPFM TPB01 TNPM3 TNPF3 TLTM1 TOILET TOILET ROOM TOILET ROOM
1 - COMMUNITY
BASED OUTPATIENT
CLINIC (CBOC) (265)
JANC1 CBOC Housekeeping Aides Closet (HAC), Bldg Sprt
1 JANC1, BSHC1, BGSH1,
JANC2 JANC1 BSHC1 BGSH1 JANC2 JANITOR'S CLOSET JANITOR'S CLOSET
1 - COMMUNITY
BASED OUTPATIENT
CLINIC (CBOC) (265)
WRTM1 PACT Teamwork Shared Office, Stff Sprt
1 WRTM1, WKTM3, NSTA1,
WRCH1 WRTM1 WKTM3 NSTA1 WRCH1 PACT TEAM WORK
SPACE
1 - COMMUNITY
BASED OUTPATIENT
CLINIC (CBOC) (265)
OFDC1 CBOC Veteran Video Connect Station, Clncl Sprt
1 OFDC1, CLCEX, OFDC2,
CMP01 OFDC1 CLCEX OFDC2 CMP01 CONSULT CONSULTATION
1 - COMMUNITY
BASED OUTPATIENT
CLINIC (CBOC) (265)
SB207 CBOC Outdoor Seating, Bldg Sprt
1 ZK100 ZK100 RECREATION SPACE -
OUTDOOR
1 - COMMUNITY
BASED OUTPATIENT
CLINIC (CBOC) (265)
SV381 CBOC Refreshment Station, Bldg Sprt
1 SV381 SV381 VOLUNTEER COFFEE
STATION
1 - COMMUNITY
BASED OUTPATIENT
CLINIC (CBOC) (265)
BX002 CBOC Vending Area, VC Svc 1 BX002 BX002 VENDING
1 - COMMUNITY
BASED OUTPATIENT
CLINIC (CBOC) (265)
CLSC4 Shared Group / Multifunction Room, CBOC
1 CLSC4 CLSC4 MEDICAL
APPOINTMENT CONSULTATION
1 - COMMUNITY
BASED OUTPATIENT
CLINIC (CBOC) (265)
SRE01 Shared Group / Multifunction Storage Room, CBOC
SRE01, SRS01, SRS02,
SRSE1, CLHS4, STSP4,
CLCS1, SRCS1, FILE1,
CLHS3, SRPB1, PRC03,
SRE01 SRS01 SRS02 SRSE1 STSP4 CLCS1 SRCS1 FILE1 CLHS3 SRPB1 PRC03 CLHS2 FSCS1 STORAGE CLEAN STORAGE
1 - COMMUNITY
BASED OUTPATIENT
CLINIC (CBOC) (265)
EXPA1 General Exam Room, CBOC 1
EXPA1, EXBH1, EXEB1,
EXRG0, EXRG3, EXRG4,
EXP01, EXRG1, EXR10,
EXRE2, EXRC1
EXPA1 EXBH1 EXEB1 EXRG0 EXRG4 EXP01 EXRG1 EXR10 EXRE2 EXRC1 EXAM ROOM EXAM EXAMINATION
1 - COMMUNITY
BASED OUTPATIENT
CLINIC (CBOC) (265)
SRE01 PACT Storage, Lgstcs Svc 1
SRE01, SRS01, SRS02,
SRSE1, CLHS4, STSP4,
CLCS1, SRCS1, FILE1,
CLHS3, SRPB1, PRC03,
SRE01 SRS01 SRS02 SRSE1 STSP4 CLCS1 SRCS1 FILE1 CLHS3 SRPB1 PRC03 CLHS2 FSCS1 STORAGE CLEAN STORAGE
1 - COMMUNITY
BASED OUTPATIENT
CLINIC (CBOC) (265)
LBVP1 CBOC Blood Draw Station, Path Svc
1 LBVP1, RCA07, LBBD1,
RCA97, LBSP1, LBBD2 LBVP1 RCA07 LBBD1 RCA97 LBSP1 LBBD2 SPECIMEN
COLLECTION TREATMENT
1 - COMMUNITY
BASED OUTPATIENT
CLINIC (CBOC) (265)
LBVP1 CBOC Bariatric Blood Draw Station, Path Svc
1 LBVP1, RCA07, LBBD1,
RCA97, LBSP1, LBBD2 LBVP1 RCA07 LBBD1 RCA97 LBSP1 LBBD2 SPECIMEN
COLLECTION TREATMENT
1 - COMMUNITY
BASED OUTPATIENT
CLINIC (CBOC) (265)
LBGM1 CBOC Laboratory Specimen Processing, Path Svc
1 LBGM1 LBGM1 LAB, GENERAL OP
CLINIC
LABORATORY WORK
AREA, GENERAL
1 - COMMUNITY
BASED OUTPATIENT
CLINIC (CBOC) (265)
USCL4
CBOC Laboratory Clean Supply Storage Room, Path Svc
1 USCL4, SRLG1 USCL4 SRLG1 STORAGE, CLEAN
SCOPE
STERILE
STORAGE
ROOM
1 - COMMUNITY
BASED OUTPATIENT
CLINIC (CBOC) (265)
TPSP1 CBOC Specimen Collection Toilet, Bldg Sprt
1 TPSP1 TPSP1 TOILET, SPECIMEN TOILET ROOM TOILET ROOM
1 - COMMUNITY
BASED OUTPATIENT
CLINIC (CBOC) (265)
EXPA1 General Exam Room, CBOC 4
EXPA1, EXBH1, EXEB1,
EXRG0, EXRG3, EXRG4,
EXP01, EXRG1, EXR10,
EXRE2, EXRC1
EXPA1 EXBH1 EXEB1 EXRG0 EXRG4 EXP01 EXRG1 EXR10 EXRE2 EXRC1 EXAM ROOM EXAM EXAMINATION
1 - COMMUNITY
BASED OUTPATIENT
CLINIC (CBOC) (265)
WRTM3 CBOC Tele Retinal Imaging Exam Room, Eye Clnc
1 WRTM3 WRTM3 TELE-RETINAL EXAM EXAMINATION
1 - COMMUNITY
BASED OUTPATIENT
CLINIC (CBOC) (265)
EXWO1 Women Veteran Exam Room, CBOC
1 EXWO1 EXWO1 EXAM, WOMENS
HEALTH EXAM EXAMINATION
1 - COMMUNITY
BASED OUTPATIENT
CLINIC (CBOC) (265)
EXPA1 General Exam Room, CBOC 1
EXPA1, EXBH1, EXEB1,
EXRG0, EXRG3, EXRG4,
EXP01, EXRG1, EXR10,
EXRE2, EXRC1
EXPA1 EXBH1 EXEB1 EXRG0 EXRG4 EXP01 EXRG1 EXR10 EXRE2 EXRC1 EXAM ROOM EXAM EXAMINATION
1 - COMMUNITY
BASED OUTPATIENT
CLINIC (CBOC) (265)
EXPA1 Multi-Use / Bariatric Exam Room, CBOC
EXPA1, EXBH1, EXEB1,
EXRG0, EXRG3, EXRG4,
EXP01, EXRG1, EXR10,
EXRE2, EXRC1
EXPA1 EXBH1 EXEB1 EXRG0 EXRG4 EXP01 EXRG1 EXR10 EXRE2 EXRC1 EXAM ROOM EXAM EXAMINATION
1 - COMMUNITY
BASED OUTPATIENT
CLINIC (CBOC) (265)
EXPA1 Podiatry Exam Room, CBOC 1
EXPA1, EXBH1, EXEB1,
EXRG0, EXRG3, EXRG4,
EXP01, EXRG1, EXR10,
EXRE2, EXRC1
EXPA1 EXBH1 EXEB1 EXRG0 EXRG4 EXP01 EXRG1 EXR10 EXRE2 EXRC1 EXAM ROOM EXAM EXAMINATION
1 - COMMUNITY
BASED OUTPATIENT
CLINIC (CBOC) (265)
OFDC1
Counseling Patient Care Consult Room, CBOC Mental Health
1 OFDC1, CLCEX, OFDC2,
CMP01 OFDC1 CLCEX OFDC2 CMP01 CONSULT CONSULTATION
1 - COMMUNITY
BASED OUTPATIENT
CLINIC (CBOC) (265)
OFDC1
Counseling Patient Care Consult Room, CBOC Mental Health
1 OFDC1, CLCEX, OFDC2,
CMP01 OFDC1 CLCEX OFDC2 CMP01 CONSULT CONSULTATION
1 - COMMUNITY
BASED OUTPATIENT
CLINIC (CBOC) (265)
TNPG1 CBOC Women Veteran Patient Toilet, Bldg Sprt
TNPG1, TLTF2, TLTF3,
TLTM2, TLTF1, TNPM2,
TLTB1, TPG01, TNPFM,
TPB01, TNPM3, TNPF3,
TLTU1 TNPG1 TLTF2 TLTF3 TLTM2 TLTF1 TNPM2 TLTB1 TPG01 TNPFM TPB01 TNPM3 TNPF3 TLTM1 TOILET TOILET ROOM TOILET ROOM
1 - COMMUNITY
BASED OUTPATIENT
CLINIC (CBOC) (265)
TNPG1 CBOC Patient Toilet, Bldg Sprt
TNPG1, TLTF2, TLTF3,
TLTM2, TLTF1, TNPM2,
TLTB1, TPG01, TNPFM,
TPB01, TNPM3, TNPF3,
TLTU1 TNPG1 TLTF2 TLTF3 TLTM2 TLTF1 TNPM2 TLTB1 TPG01 TNPFM TPB01 TNPM3 TNPF3 TLTM1 TOILET TOILET ROOM TOILET ROOM
1 - COMMUNITY
BASED OUTPATIENT
CLINIC (CBOC) (265)
PEHW1
CBOC Accessible Patient Height & Weight Station, Clncl Sprt
1 PEHW1, EXR11 EXR11 ALCOVE, PHYSICAL
EVALUATION STAFF CORRIDOR
1 - COMMUNITY
BASED OUTPATIENT
CLINIC (CBOC) (265)
WRTM2 CBOC Telehealth Exam Room, Clncl Sprt
1 WRTM2, EXTH1 WRTM2 EXTH1 TELE-HEALTH EXAM EXAMINATION
1 - COMMUNITY
BASED OUTPATIENT
CLINIC (CBOC) (265)
EXPA1 General Exam Room, CBOC 1
EXPA1, EXBH1, EXEB1,
EXRG0, EXRG3, EXRG4,
EXP01, EXRG1, EXR10,
EXRE2, EXRC1
EXPA1 EXBH1 EXEB1 EXRG0 EXRG4 EXP01 EXRG1 EXR10 EXRE2 EXRC1 EXAM ROOM EXAM EXAMINATION
1 - COMMUNITY
BASED OUTPATIENT
CLINIC (CBOC) (265)
EXPA1 General Exam Room, CBOC 1
EXPA1, EXBH1, EXEB1,
EXRG0, EXRG3, EXRG4,
EXP01, EXRG1, EXR10,
EXRE2, EXRC1
EXPA1 EXBH1 EXEB1 EXRG0 EXRG4 EXP01 EXRG1 EXR10 EXRE2 EXRC1 EXAM ROOM EXAM EXAMINATION
ROOM IDENTIFICATION ALTERNATE ROOM CODES
ROOM DATA MATRIX
1 - COMMUNITY
BASED OUTPATIENT
CLINIC (CBOC) (265)
RCA02 CBOC Point of Use Equipment Alcove, Clncl Sprt
1 RCA02 RCA02 ALCOVE, EQUIPMENT STAFF CORRIDOR
1 - COMMUNITY
BASED OUTPATIENT
CLINIC (CBOC) (265)
SRS04 CBOC Point of Use Supply Alcove, Clncl Sprt
1 SRS04, SRSP1, SRS05 SRS04 SRSP1 SRS05 STERILE STORAGE STERILE STORAGE
1 - COMMUNITY
BASED OUTPATIENT
CLINIC (CBOC) (265)
WRTM1 CBOC Hoteling Workstation, Stff Sprt
1 WRTM1, WKTM3, NSTA1,
WRCH1 WRTM1 WKTM3 NSTA1 WRCH1 PACT TEAM WORK
SPACE
1 - COMMUNITY
BASED OUTPATIENT
CLINIC (CBOC) (265)
WRTM1 CBOC Clinical Staff Workstation, Stff Sprt
1 WRTM1, WKTM3, NSTA1,
WRCH1 WRTM1 WKTM3 NSTA1 WRCH1 PACT TEAM WORK
SPACE
1 - COMMUNITY
BASED OUTPATIENT
CLINIC (CBOC) (265)
RPR01 CBOC Team Copy / Supply Alcove, Stff Sprt
1 RPR01, RPR03, MRWK1,
SACS1, SACP1 RPR01 RPR03 MRWK1 SACS1 SACP1 COPY ALCOVE STAFF CORRIDOR
1 - COMMUNITY
BASED OUTPATIENT
CLINIC (CBOC) (265)
WRTM1 CBOC Huddle Space, Stff Sprt
1 WRTM1, WKTM3, NSTA1,
WRCH1 WRTM1 WKTM3 NSTA1 WRCH1 PACT TEAM WORK
SPACE
1 - COMMUNITY
BASED OUTPATIENT
CLINIC (CBOC) (265)
RCA06 CBOC Point of Use Medication Alcove, Phrm Svc
1 RCA06 RCA06 ALCOVE, MEDICATION MEDICATION ROOM
1 - COMMUNITY
BASED OUTPATIENT
CLINIC (CBOC) (265)
SB106 CBOC Covered Drop-off / Pick-Up, Bldg Sprt
1 OUTDOOR
1 - COMMUNITY
BASED OUTPATIENT
CLINIC (CBOC) (265)
JANC1 CBOC Housekeeping Aides Closet (HAC), Bldg Sprt
1 JANC1, BSHC1, BGSH1,
JANC2 JANC1 BSHC1 BGSH1 JANC2 JANITOR'S CLOSET JANITOR'S CLOSET
1 - COMMUNITY
BASED OUTPATIENT
CLINIC (CBOC) (265)
SRGC1 CBOC Full Gas Cylinder Storage Room, Lgstcs Svc
1 SRGC1 SRGC1 GAS CYLINDER
STORAGE
1 - COMMUNITY
BASED OUTPATIENT
CLINIC (CBOC) (265)
SRGC1 CBOC Empty Gas Cylinder Storage Room, Lgstcs Svc
1 SRGC1 SRGC1 GAS CYLINDER
STORAGE
1 - COMMUNITY
BASED OUTPATIENT
CLINIC (CBOC) (265)
SRE01 CBOC Medical Equipment Storage Room, Lgstcs Svc
SRE01, SRS01, SRS02,
SRSE1, CLHS4, STSP4,
CLCS1, SRCS1, FILE1,
CLHS3, SRPB1, PRC03,
SRE01 SRS01 SRS02 SRSE1 STSP4 CLCS1 SRCS1 FILE1 CLHS3 SRPB1 PRC03 CLHS2 FSCS1 STORAGE CLEAN STORAGE
1 - COMMUNITY
BASED OUTPATIENT
CLINIC (CBOC) (265)
SRE01 CBOC Clinical Supplies Storage Room, Lgstcs Svc
SRE01, SRS01, SRS02,
SRSE1, CLHS4, STSP4,
CLCS1, SRCS1, FILE1,
CLHS3, SRPB1, PRC03,
SRE01 SRS01 SRS02 SRSE1 STSP4 CLCS1 SRCS1 FILE1 CLHS3 SRPB1 PRC03 CLHS2 FSCS1 STORAGE CLEAN STORAGE
1 - COMMUNITY
BASED OUTPATIENT
CLINIC (CBOC) (265)
CMP02 CBOC Telecommunications Room (TR), OIT
1 CMP02, TETR1, TEDR1 CMP02 TETR1 TEDR1 TELECOMM.
1 - COMMUNITY
BASED OUTPATIENT
CLINIC (CBOC) (265)
OFDC1 CBOC Staff Workroom / Storage Room, Clncl Sprt
1 OFDC1, CLCEX, OFDC2,
CMP01 OFDC1 CLCEX OFDC2 CMP01 CONSULT CONSULTATION
1 - COMMUNITY
BASED OUTPATIENT
CLINIC (CBOC) (265)
CFR01 CBOC Staff Conference Room
CFR01, CRA01, CRA02,
CRA03, CFR03, CLR08,
CFR02
CFR01 CRA01 CRA02 CRA03 CFR02 CFR03 CFR08 CONFERENCE ROOM
1 - COMMUNITY
BASED OUTPATIENT
CLINIC (CBOC) (265)
OFA05 CBOC Shared Leadership Office, Stff Sprt
1 OFA05, OFA02 OFA05 OFA02 OFFICE, SHARED
1 - COMMUNITY
BASED OUTPATIENT
CLINIC (CBOC) (265)
WRTM1 ID/ Photo HAS SVC, Clncl Sprt
1 WRTM1, WKTM3, NSTA1,
WRCH1 WRTM1 WKTM3 NSTA1 WRCH1 HAS TEAM WORK
SPACE
1 - COMMUNITY
BASED OUTPATIENT
CLINIC (CBOC) (265)
LACO1 CBOC Staff Lactation Room, Wm Vet Svc
1 LACO1 LACO1 LACTATION ROOM
1 - COMMUNITY
BASED OUTPATIENT
CLINIC (CBOC) (265)
TLTU1 CBOC Universal Staff Toilet, Bldg Sprt
TLTU1, TNPG1, TLTF2,
TLTF3, TLTM2, TLTF1,
TNPM2, TLTB1, TPG01,
TNPFM, TPB01, TNPM3,
TLTU1 TNPG1 TLTF2 TLTF3 TLTM2 TLTF1 TNPM2 TLTB1 TPG01 TNPFM TPB01 TNPM3 TNPF3 TLTM1 TOILET TOILET ROOM TOILET ROOM
1 - COMMUNITY
BASED OUTPATIENT
CLINIC (CBOC) (265)
SRE01 HAS Storage, Lgstcs Svc 1
SRE01, SRS01, SRS02,
SRSE1, CLHS4, STSP4,
CLCS1, SRCS1, FILE1,
CLHS3, SRPB1, PRC03,
SRE01 SRS01 SRS02 SRSE1 STSP4 CLCS1 SRCS1 FILE1 CLHS3 SRPB1 PRC03 CLHS2 FSCS1 STORAGE CLEAN STORAGE
1 - COMMUNITY
BASED OUTPATIENT
CLINIC (CBOC) (265)
LR001 CBOC Staff Personal Property Locker Alcove, Stff Sprt
1 LR001, LR002, LR004,
SSLK1 LR001 LR002 LR004 SSLK1 LOCKER ROOM
1 - COMMUNITY
BASED OUTPATIENT
CLINIC (CBOC) (265)
SL001
CBOC Clinical Neighborhood Staff Multipurpose Room / Breakroom, Stff Sprt
1 SL001, SSLG1, SSLG2,
SSLG3 SL001 SSLG1 SSLG2 SSLG3 STAFF LOUNGE
1 - COMMUNITY
BASED OUTPATIENT
CLINIC (CBOC) (265)
ZK100 CBOC Staff Outdoor Eating Area, Stff Sprt
1 ZK100 ZK100 RECREATION SPACE -
OUTDOOR
1 - COMMUNITY
BASED OUTPATIENT
CLINIC (CBOC) (265)
SS276 CBOC Staff Wellness / Fitness Room, Stff Sprt
1 STAFF WELLNESS FITNESS ROOM
1 - COMMUNITY
BASED OUTPATIENT
CLINIC (CBOC) (265)
OFDC1 PACT Pharmacist Office, Pharmacy Svc
1 OFDC1, CLCEX, OFDC2,
CMP01 CONSULT CONSULTATION
1 - COMMUNITY
BASED OUTPATIENT
CLINIC (CBOC) (265)
WRTM1 Admin / Flex, HAS Svc, Clncl Sprt
1 WRTM1, WKTM3, NSTA1,
WRCH1 WRTM1 WKTM3 NSTA1 WRCH1 HAS TEAMWORK
SPACE
1 - COMMUNITY
BASED OUTPATIENT
CLINIC (CBOC) (265)
BLDG SPRT Engineering Service 1 BLDG SPRT, ENG BLDG SPRT ENG Building Support
ROOM NAME FGI EQUIVALENT FOR
ASHRAE 170
FGI EQUIVALENT FOR
TABLE 1.2-6
Fl oo r F in is h
B as e
W al l F in is h
W ai ns co t M at er ia l
W ai ns co t H ei gh t
ST
C
C ei lin g
Fi ni sh
H ei gh t
N ot es
D oo r A ct io n
Si ze
(W id th
Si ze
(H ei gh t)
Ty pe
M at er ia l
G la zi ng
Fr am e
R at in g
H ar dw ar e G ro up
H ar dw ar e N ot es
In do or T em pe ra tu re
C oo lin g
F
In do or T em pe ra tu re
H ea tin g
F
In do or R el at iv e
H um id ity
R
H M ax
In do or R el at iv e
H um id ity
R
H M in
M in im um
T ot al A
C H
M in im um
O A
A C
H
R oo m A ir R et ur n G en . E xh G
S pe c Ex h S
M ax im um
N oi se
Le ve l N C
R oo m A ir B al an ce
H
VA
C N ot es
Q ua d
R ec ep ta cl es
Q ua d
R ec ep ta cl es
G
FC
I R ec ep ta cl es
U
SB
R ec ep ta cl es
N or m al
P ow er
Em er ge nc y Po w er
Po w er
Sp ec ia l
R eq ui re m en ts
(R ad io lo gy E qu ip m en t, Li ft, e tc
Po w er
N ot es
Fi xt ur e
Ty pe
C on tr ol s
N or m al
P ow er
Em er ge nc y Po w er
Li gh tin g
- S pe ci al
R eq ui re m en ts
Li gh tin g
- N ot es
D at a
O ut le ts
P ho ne
O ut le ts
W al l P ho ne
O ut le ts
IT
Sp ec ia l R eq ui re m en ts
D ur es s
A la rm
N ur se C al l
Vi de o Te le co nf er en ci ng
M ot io n
In tr us io n D et ec tio n
El ec tr on ic A cc es s an d D oo r C on tr ol
Se cu rit y
Su rv ei lla nc e
TV
A ud io /V is ua l D ev ic e
C ei lin g, C en te r o f T ile
VESTIBULE MAT RB or PT GWP: P _ _ _ GWB/P 9'-0" 20 & 11 Pair of Sliding _ 7'-0" _ Aluminum
& Glass
Insul.
Temp.
Safety Glass
Aluminum _ _ 1.1 _ _ _ _ _ _ _ _ _ M4 4 _ _ _ Y N _ _ Downlight s
Building time control Y N N/A N/A 1 Y Y Y
ALCOVE PATIENT CORRIDOR SEE
NOTE
SEE
NOTE GWB: P RWC 4'-0" _ AT 8'-0" 6 _ _ _ _ _ _ _ _ _ 6 _ _ _ _ _ _ _ _ _ _ 1 _ _ _ Y N _ _
2 X 2 recessed lensed or self-contained indirect
Multilevel switching/ dimming/ occupanc y
Y N N/A N/A 1 1 _ _ _ _ _ _ _ _ Y
LACTATION ROOM LVT RB 4" GWB: P _ _ 50 AT 9'-0" _ Swinging 3'-0" 7'-0" Flush Wood _ Int. Alum. _ 12 CS 2.2 _ _ _ _ _ _ Exh. (G) _ _ _ 4 1 1 Y N _ _
2 X 2 recessed lensed or self-contained indirect
Multilevel switching/ dimming/ occupanc y
Y N N/A N/A 1 _ _ _ _ _ _ _ _ _ Y
CONSULT CONSULTATION CPT RB 4" GWB: P;
ACCENT _ _ 40 AT 9'-0" 11 Sliding 3'-6" 7'-0" Flush Wood _ Int. Alum. _ 12S 3.3 75 70 60 _ 4 2 Return 40 NR _ 6 _ 1 _ Y N N/A _
2 X 2 recessed lensed or self-contained indirect
Multilevel switching/ dimming/ occupanc y
Y N
Multi-level switching or manual dimming
_ 1 1 _ _ Y
Staff emergenc y station where required
Y _ _ _ Y
ALCOVE PATIENT CORRIDOR SEE
NOTE
SEE
NOTE GWB: P RWC 4'-0" _ AT 8'-0" 6 _ _ _ _ _ _ _ _ _ 6 _ _ _ _ _ _ _ _ _ _ 1 _ _ _ Y N _ _
2 X 2 recessed lensed or self-contained indirect
Multilevel switching/ dimming/ occupanc y
Y N N/A N/A 3 1 _ _ _ _ _ _ _ _ Y
WAITING PUBLIC SPACE
CPT,
RSF, or
RFT
RB 4" GWB: P _ _ _ AT 9'-0" 10, 17 _ 3'-6" _
Flush w/ Narrow Vision
Wood Narrow Vision _ _ 15 AG _ _ _ _ _ _ _ _ _ _ M4 _ _ _
At least 1 per wall, not to exceed
12' spacing
Y N _ _
2 X 2 recessed lensed or self-contained indirect
Multilevel switching/ dimming/ occupanc y
Y N N/A N/A 1 1 _ _ _ _ _ _ _ Y Y
WAITING PUBLIC SPACE
CPT,
RSF, or
RFT
RB 4" GWB: P _ _ _ AT 9'-0" 10, 17 _ 3'-6" _
Flush w/ Narrow Vision
Wood Narrow Vision _ _ 15 AG _ _ _ _ _ _ _ _ _ _ M4 _ _ _
At least 1 per wall, not to exceed
12' spacing
Y N _ _
2 X 2 recessed lensed or self-contained indirect
Multilevel switching/ dimming/ occupanc y
Y N N/A N/A 1 1 _ _ _ _ _ _ _ Y Y
STORAGE CLEAN STORAGE RFT RB 4" GWB: P _ _ _ AT 8'-0" _ Swinging 3'-0" 7'-0" Flush Wood _ _ _ 35 AG 2.2 _ _ _ _ _ _ _ _ _ _
At least 1 per wall, not to exceed
12' spacing
_ _ _ Y N _ _
2 X 4 recessed lensed or self-contained indirect
Occupan cy/vacanc y Y N N/A N/A _ _ _ _ _ _ _ _ _ _ Y
TOILET TOILET ROOM TOILET ROOM PT PT 4" GWB: P CT 4'-0" SEE FGI AT 9'-0" 1, 2 Swinging 3'-6" 7'-0" Flush Wood _ "B"-HM _ 11 4.4 _ _ _ _ _ _ Exh. (G) _ _ _ _ _ 1 _ Y N
Water valve shut-off switch on lab side of pass-thru wall
Downlight s/Mirror or vanity
Vacancy sensor Y N _ _ _ _ _ _ _
Staff emergenc y station where required
_ _ _ _ Y
TOILET TOILET ROOM TOILET ROOM PT PT 4" GWB: P CT 4'-0" SEE FGI AT 9'-0" 1, 2 Swinging 3'-6" 7'-0" Flush Wood _ "B"-HM _ 11 5.5 _ _ _ _ _ _ Exh. (G) _ _ _ _ _ 1 _ Y N
Water valve shut-off switch on lab side of pass-thru wall
Downlight s/Mirror or vanity
Vacancy sensor Y N _ _ _ _ _ _ _
Staff emergenc y station where required
_ _ _ _ Y
JANITOR'S CLOSET JANITOR'S CLOSET QUARRY
TILE
QUARRY
TILE 4"
GWB;
GLAZED
COATIN
G (SC)
CERAMI
C TILE 4'-0" _ SP 8'-0" _ Swinging 3'-0" 7'-0" Flush Wood _ "B"-HM _ 14 2.2 _ _ _ _ _ _ Exh. (G) _ _ _ _ _ 1 _ Y N N/A _
Surface or wall mounted 6" x 4'
Occupan cy/vacanc y Y N N/A N/A _ _ _ _ _ _ _ _ _ _ _
PACT TEAM WORK SPACE CPT RB 4" GWB: P _ _ 40 SP 9'-0" 3 _ _ _ _ _ _ _ _ _ 6 _ _ _ _ _ _ _ _ _ M3 3 per work station _ _ _ Y Y _ _
2 X 2 recessed lensed or self-contained indirect
Multilevel switching/ dimming/ occupanc y/daylighti ng control
Y Y -minimal
Multi-level switching or manual dimming
N/A 3 per work station
3 per work station _ _ Y
Staff emergenc y station where required
_ _ _ _ Y
CONSULT CONSULTATION CPT RB 4" GWB: P;
ACCENT _ _ 40 AT 9'-0" 11 Swinging 3'-6" 7'-0" Flush Wood _ "B"-HM _ 12S 2.2 75 70 60 _ 4 2 Return 40 NR _ 5 _ 1 _ Y N N/A _
2 X 2 recessed lensed or self-contained indirect
Multilevel switching/ dimming/ occupanc y
Y N
Multi-level switching or manual dimming
_ 1 1 _ _ Y
Staff emergenc y station where required
Y _ _ _ Y
RECREATION SPACE -
OUTDOOR _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 6 _ _ _ _ _ _ _ _ _ N/A _ _ 1 _ Y N _ _
2 X 2 recessed lensed or self-contained indirect
Multilevel switching/ dimming/ occupanc y
Y N N/A N/A _ _ _ _ _ _ _ _ _ Y Y
VOLUNTEER COFFEE
STATION CPT RB 4" GWB: P _ _ _ AT 9'-0" _ _ _ _ _ _ _ _ _ 6 _ _ _ _ _ _ _ _ _ M4 _ _ 2 _ Y N _ _
2 X 2 recessed lensed or self-contained indirect
Multilevel switching/ dimming/ occupanc y
Y N N/A N/A _ _ _ _ _ _ _ _ _ _ Y
VENDING CPT RB 4" GWB: P _ _ _ AT 9'-0" _ _ _ _ _ _ _ _ _ _ 6 _ _ _ _ _ _ _ _ _ M4 _ _ 2 _ Y N _ _
2 X 2 recessed lensed or self-contained indirect
Multilevel switching/ dimming/ occupanc y
Y N N/A N/A _ _ _ _ _ _ _ _ _ _ Y
MEDICAL APPOINTMENT CONSULTATION CPT RB 4" GWB: P _ _ SEE FGI AT 9'-0" _ Swinging 3'-6" 7'-0" Flush w/ Narrow Vision
Wood Narrow Vision _ _ 12CG 2.2 75 70 60 _ 4 2 Return 40 NR _ 5 _ 1 _ Y Y _ _
2 X 2 recessed lensed or self-contained indirect
Multilevel switching/ dimming/ occupanc y
Y Y _ _ 1 1 _ _ Y
Staff emergenc y station where required
Y _ _ _ Y
STORAGE CLEAN STORAGE RFT RB 4" GWB: P _ _ _ AT 8'-0" _ Swinging 3'-0" 7'-0" Flush Wood _ _ _ 35 AG 2.2 _ _ _ _ _ _ _ _ _ _
At least 1 per wall, not to exceed
12' spacing
_ _ _ Y N _ _
2 X 4 recessed lensed or self-contained indirect
Occupan cy/vacanc y Y N N/A N/A _ _ _ _ _ _ _ _ _ _ Y
EXAM ROOM EXAM EXAMINATION WSF RB 4" GWB: P _ _ 40 AT 9'-0" 11 Sliding
3'-0"
3'-6"
7'-0" Flush Wood _ Int. Alum. _ 12S 3.3 _ _ _ _ _ _ _ _ _ _ 6 1 1 _ Y N N/A _
2 X 4 recessed lensed or self-contained indirect
Multilevel switching/ dimming/ occupanc y
Y N sealed fixture, flat lens surface on exterior
N/A 3 1 _ _ Y
Staff emergenc y station where required
_ _ _ _ Y
STORAGE CLEAN STORAGE RFT RB 4" GWB: P _ _ -- AT 8'-0" _ Swinging 3'-0" 7'-0" Flush Wood _ Int. Alum. _ 35 AG 2.2 _ _ _ _ _ _ _ _ _ _
At least 1 per wall, not to exceed
12' spacing
_ _ _ Y N _ _
Surface or chain mounted
1' x 4'
Occupan cy/vacanc y Y N N/A N/A _ _ _ _ _ _ _ _ _ _ Y
SPECIMEN COLLECTION TREATMENT WSF WSF 4" GWB: SC _ _ 40 SP 9'-0" 3 _ _ _ _ _ _ _ _ _ 6 _ _ _ _ _ _ _ _ _ _ 4 _ _ _ Y Y _ _
2 X 2 recessed lensed or self-contained indirect
Multilevel switching/ dimming/ occupanc y/daylighti ng control
Y Y -minimal
Multi-level switching or manual dimming
N/A 2 1 _ _ Y
Staff emergenc y station where required
_ _ _ _ Y
SPECIMEN COLLECTION TREATMENT WSF WSF 4" GWB: SC _ _ 40 SP 9'-0" 3 _ _ _ _ _ _ _ _ _ 6 _ _ _ _ _ _ _ _ _ _ 4 _ _ _ Y Y _ _
2 X 2 recessed lensed or self-contained indirect
Multilevel switching/ dimming/ occupanc y/daylighti ng control
Y Y -minimal
Multi-level switching or manual dimming
N/A 2 1 _ _ Y
Staff emergenc y station where required
_ _ _ _ Y
LAB, GENERAL OP CLINIC LABORATORY WORK AREA,
GENERAL WSF WSF 4" GWB: SC _ _ 40 SP 9'-0" 3 Swinging 3'-6" 7'-0"
Flush w/ Narrow Vision
Wood Narrow Vision Int. Alum. _ _ 3.3 _ _ _ _ _ _ Exh. (S) _ _ _ 6 _ _ _ Y Y _ _
2 X 2 recessed lensed or self-contained indirect
Multilevel switching/ dimming/ occupanc y/daylighti ng control
Y Y -minimal
Multi-level switching or manual dimming
N/A 6 1 _ _ Y
Staff emergenc y station where required
_ _ _ _ Y
STORAGE, CLEAN SCOPE
STERILE
STORAGE
ROOM
RES or WSF RES or WSF EP RWC 4'-0" _ GYP/EP or AT-SP 9'-0 3, 7 Swinging 3'-6" 7'-0" Flush w/ Narrow Vision
Wood Narrow Vision _ _ 15 AG 2.2 _ _ _ _ _ _ Exh. (S) _ _ _
At least 1 per wall, not to exceed
12' spacing
_ _ _ Y N _ _ 2 X 2 recessed lensed
Multilevel switching/ dimming/ occupanc y
Y N
Gyp ceiling -lights to be sealed type/flang e mounted
N/A _ _ _ _ _ _ _ _ _ _ Y
TOILET, SPECIMEN TOILET ROOM TOILET ROOM PT PT 4" GWB: P CT 4'-0" SEE FGI AT 9'-0" 1, 2 Swinging 3'-6" 7'-0" Flush Wood _ _ _ 11 4.4 _ _ _ _ _ _ Exh. (G) _ _ _ _ _ 1 _ Y N
Water valve shut-off switch on lab side of pass-thru wall
Downlight s/Mirror or vanity
Vacancy sensor Y N _ _ _ _ _ _ _
Staff emergenc y station where required
_ _ _ _ Y
EXAM ROOM EXAM EXAMINATION WSF RB 4" GWB: P _ _ 40 AT 9'-0" 11 Sliding
3'-0"
3'-6"
7'-0" Flush Wood _ Int. Alum. _ 12S 3.3 _ _ _ _ _ _ _ _ _ _ 5 1 1 _ Y N N/A _
2 X 4 recessed lensed or self-contained indirect
Multilevel switching/ dimming/ occupanc y
Y N
Multi-level switching or manual dimming
N/A 3 1 _ _ Y
Staff emergenc y station where required
_ _ _ _ Y
TELE-RETINAL EXAM EXAMINATION WSF RB 4" GWB: P _ _ 40 AT 9'-0" 24 Sliding 3'-6" 7'-0" Flush Wood _ Int. Alum. _ 17AG 3.3 _ _ _ _ _ _ _ _ _ _ 5 1 1 _ Y N N/A _
2 X 2 recessed lensed or self-contained indirect
Multilevel switching/ dimming/ occupanc y
Y N
Multi-level switching or manual dimming
N/A 3 1 _ _ Y
Staff emergenc y station where required
Y _ _ _ Y
EXAM, WOMENS HEALTH EXAM EXAMINATION WSF RB 4" GWB: P _ _ 40 AT 9'-0" 11 Sliding
3'-0"
3'-6"
7'-0" Flush Wood _ Int. Alum. _ 12S 3.3 _ _ _ _ _ _ _ _ _ _ 5 1 1 _ Y N Overhead Lift _
2 X 4 recessed lensed or self-contained indirect
Multilevel switching/ dimming/ occupanc y
Y N
Multi-level switching or manual dimming
N/A 3 1 _ _ Y
Staff emergenc y station where required
_ _ _ _ Y
EXAM ROOM EXAM EXAMINATION WSF RB 4" GWB: P _ _ 40 AT 9'-0" 11 Sliding
3'-0"
3'-6"
7'-0" Flush Wood _ Int. Alum. _ 12S 3.3 _ _ _ _ _ _ _ _ _ _ 5 1 1 _ Y N N/A _
2 X 4 recessed lensed or self-contained indirect
Multilevel switching/ dimming/ occupanc y
Y N
Multi-level switching or manual dimming
N/A 3 1 _ _ Y
Staff emergenc y station where required
_ _ _ _ Y
EXAM ROOM EXAM EXAMINATION WSF RB 4" GWB: P _ _ 40 AT 9'-0" 11 Sliding
3'-0"
3'-6"
7'-0" Flush Wood _ Int. Alum. _ 12S 3.3 _ _ _ _ _ _ _ _ _ _ 5 1 1 _ Y N Overhead Lift _
2 X 4 recessed lensed or self-contained indirect
Multilevel switching/ dimming/ occupanc y
Y N
Multi-level switching or manual dimming
N/A 3 1 _ _ Y
Staff emergenc y station where required
_ _ _ _ Y
EXAM ROOM EXAM EXAMINATION WSF RB 4" GWB: P _ _ 40 AT 9'-0" 11 Sliding
3'-0"
3'-6"
7'-0" Flush Wood _ Int. Alum. _ 12S 3.3 _ _ _ _ _ _ _ _ _ _ 5 1 1 _ Y N N/A _
2 X 4 recessed lensed or self-contained indirect
Multilevel switching/ dimming/ occupanc y
Y N
Multi-level switching or manual dimming
N/A 3 1 _ _ Y
Staff emergenc y station where required
_ _ _ _ Y
CONSULT CONSULTATION CPT RB 4" GWB: P;
ACCENT _ _ 40 AT 9'-0" 11 Swinging 3'-6" 7'-0" Flush Wood _ Int. Alum. _ 12S 2.2 75 70 60 _ 4 2 Return 40 NR _ 5 _ 1 _ Y N N/A _
2 X 2 recessed lensed or self-contained indirect
Multilevel switching/ dimming/ occupanc y
Y N
Multi-level switching or manual dimming
_ 1 1 _ _ Y
Staff emergenc y station where required
Y _ _ _ Y
CONSULT CONSULTATION CPT RB 4" GWB: P;
ACCENT _ _ 40 AT 9'-0" 11 Swinging 3'-6" 7'-0" Flush Wood _ Int. Alum. _ 12S 2.2 75 70 60 _ 4 2 Return 40 NR _ 5 _ 1 _ Y N N/A _
2 X 2 recessed lensed or self-contained indirect
Multilevel switching/ dimming/ occupanc y
Y N
Multi-level switching or manual dimming
_ 1 1 _ _ Y
Staff emergenc y station where required
Y _ _ _ Y
TOILET TOILET ROOM TOILET ROOM PT PT 4" GWB: P CT 4'-0" SEE FGI AT 9'-0" 1, 2 Swinging 3'-6" 7'-0" Flush Wood _ "B"-HM _ 11 4.4 _ _ _ _ _ _ Exh. (G) _ _ _ _ _ 1 _ Y N
Water valve shut-off switch on lab side of pass-thru wall
Downlight s/Mirror or vanity
Vacancy sensor Y N _ _ _ _ _ _ _
Staff emergenc y station where required
_ _ _ _ Y
TOILET TOILET ROOM TOILET ROOM PT PT 4" GWB: P CT 4'-0" SEE FGI AT 9'-0" 1, 2 Swinging 3'-6" 7'-0" Flush Wood _ "B"-HM _ 11 4.4 _ _ _ _ _ _ Exh. (G) _ _ _ _ _ 1 _ Y N
Water valve shut-off switch on lab side of pass-thru wall
Downlight s/Mirror or vanity
Vacancy sensor Y N _ _ _ _ _ _ _
Staff emergenc y station where required
_ _ _ _ Y
ALCOVE, PHYSICAL
EVALUATION STAFF CORRIDOR
RFT,
RSF or
WSF
RB or WSF GWB: P RWC 4'-0" _ AT 8'-0" 3, 6 _ _ _ _ _ _ _ _ _ 6 _ _ _ _ _ _ _ _ _ _ 1 _ _ _ Y N N/A _
2 X 2 recessed lensed or self-contained indirect
Multilevel switching/ dimming/ occupanc y
Y N N/A N/A _ _ _ _ _ _ _ _ _ _ Y
TELE-HEALTH EXAM EXAMINATION WSF RB 4" GWB: P _ _ 40 AT 9'-0" _ Sliding 3'-6" 7'-0" Flush Wood _ Int. Alum. _ 12G 3.3 _ _ _ _ _ _ _ _ _ _ 5 1 1 _ Y N N/A _
2 X 2 recessed lensed or self-contained indirect
Multilevel switching/ dimming/ occupanc y
Y N
Multi-level switching or manual dimming
N/A 3 1 _ _ Y
Staff emergenc y station where required
Y _ _ _ Y
EXAM ROOM EXAM EXAMINATION WSF RB 4" GWB: P _ _ 40 AT 9'-0" 11 Sliding
3'-0"
3'-6"
7'-0" Flush Wood _ Int. Alum. _ 12S 3.3 _ _ _ _ _ _ _ _ _ _ 5 1 1 _ Y N N/A _
2 X 4 recessed lensed or self-contained indirect
Multilevel switching/ dimming/ occupanc y
Y N
Multi-level switching or manual dimming
N/A 3 1 _ _ Y
Staff emergenc y station where required
_ _ _ _ Y
EXAM ROOM EXAM EXAMINATION WSF RB 4" GWB: P _ _ 40 AT 9'-0" 11 Sliding
3'-0"
3'-6"
7'-0" Flush Wood _ Int. Alum. _ 12S 3.3 _ _ _ _ _ _ _ _ _ _ 5 1 1 _ Y N N/A _
2 X 4 recessed lensed or self-contained indirect
Multilevel switching/ dimming/ occupanc y
Y N
Multi-level switching or manual dimming
N/A 3 1 _ _ Y
Staff emergenc y station where required
_ _ _ _ Y
ALCOVE, EQUIPMENT STAFF CORRIDOR
RFT,
RSF or
WSF
RB or WSF GWB: P RWC 4'-0" _ AT 8'-0" 3,6 _ _ _ _ _ _ _ _ _ 6 _ _ _ _ _ _ _ _ _ _ 1 _ _ _ Y N _ _
2 X 2 recessed lensed or self-contained indirect
Multilevel switching/ dimming/ occupanc y
Y N N/A N/A _ _ _ _ _ _ _ _ _ _ Y
STERILE STORAGE STERILE STORAGE WSF WSF GWB: P RWC 4'-0" _ AT-SP 9'-0" 3 Swinging 3'-0" 7'-0" Flush Wood _ Int. Alum. _ 121 AG 2.2 _ _ _ _ _ _ _ _ _ _ 1 _ _ _ Y N _ _
2 X 2 recessed lensed or self-contained indirect
Multilevel switching/ dimming/ occupanc y
Y N N/A N/A _ _ _ _ _ _ _ _ _ _ _
PACT TEAM WORK SPACE CPT RB 4" GWB: P _ _ 40 SP 9'-0" 3 _ _ _ _ _ _ _ _ _ 6 _ _ _ _ _ _ _ _ _ M3 3 _ _ _ Y Y _ _
2 X 2 recessed lensed or self-contained indirect
Multilevel switching/ dimming/ occupanc y/daylighti ng control
Y Y -minimal
Multi-level switching or manual dimming
N/A 3 3 _ _ Y
Staff emergenc y station where required
_ _ _ _ Y
PACT TEAM WORK SPACE CPT RB 4" GWB: P _ _ 40 SP 9'-0" 3 _ _ _ _ _ _ _ _ _ 6 _ _ _ _ _ _ _ _ _ M3 3 _ _ _ Y Y _ _
2 X 2 recessed lensed or self-contained indirect
Multilevel switching/ dimming/ occupanc y/daylighti ng control
Y Y -minimal
Multi-level switching or manual dimming
N/A 3 3 _ _ Y
Staff emergenc y station where required
_ _ _ _ Y
COPY ALCOVE STAFF CORRIDOR
CPT,
RSF or
RFT
RB 4" GWB: P _ _ _ AT 9'-0" 6 _ _ _ _ _ _ _ _ _ 6 _ _ _ _ _ _ _ _ _ _ 3 _ _ _ Y N N/A _
2 X 2 recessed lensed or self-contained indirect
Multilevel switching/ dimming/ occupanc y/daylighti ng control
Y N N/A N/A 3 1 _ _ _ _ _ _ _ _ Y
PACT TEAM WORK SPACE CPT RB 4" GWB: P _ _ 40 SP 9'-0" 3 _ _ _ _ _ _ _ _ _ 6 _ _ _ _ _ _ _ _ _ M3 3 _ _ _ Y Y _ _
2 X 2 recessed lensed or self-contained indirect
Multilevel switching/ dimming/ occupanc y/daylighti ng control
Y Y -minimal
Multi-level switching or manual dimming
N/A 3 3 _ _ Y
Staff emergenc y station where required
_ _ _ _ Y
ALCOVE, MEDICATION MEDICATION ROOM RFT or RSF RB 4" GWB: P RWC 5'-0" _ AT 9'-0" _ _ _ _ _ _ _ _ _ _ 6 _ _ _ _ _ _ _ _ _ _ 2 _ 1 _ Y
Y Refrigerat or receptacl es
N/A
2 X 2 recessed lensed or self-contained indirect
Multilevel switching/ dimming/ occupanc y
Y N N/A N/A 2 1 _ _ Y _ _ _ Y Y Y
OUTDOOR _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
JANITOR'S CLOSET JANITOR'S CLOSET QUARRY
TILE
QUARRY
TILE 4"
GWB;
GLAZED
COATIN
G (SC)
CERAMI
C TILE 4'-0" _ SP 8'-0" _ Swinging 3'-0" 7'-0" Flush Wood _ Int. Alum. _ 14 2.2 _ _ _ _ _ _ Exh. (G) _ _ _ _ _ 1 _ Y N N/A
Surface or wall mounted 6" x 4'
Occupan cy/vacanc y Y N N/A N/A _ _ _ _ _ _ _ _ _ _ _
GAS CYLINDER STORAGE WSF RB 4" GWB: P RWC 4'-0" _ AT 9'-0" _ Swinging 3'-0" 7'-0" Flush Wood _ Int. Alum. 45 MIN 34 G 2.2 75 66 30 20 _ _ Exh. (S) _ (-) _ 1 _ _ _ Y N _ _
2 X 2 recessed lensed or self-contained indirect
Multilevel switching/ dimming/ occupanc y
Y N N/A N/A _ _ _ _ _ _ _ _ _ _ _
GAS CYLINDER STORAGE WSF RB 4" GWB: P RWC 4'-0" _ AT 9'-0" _ Swinging 3'-0" 7'-0" Flush Wood _ Int. Alum. 45 MIN 34 G 2.2 75 66 30 20 _ _ Exh. (S) _ (-) _ 1 _ _ _ Y N _ _
2 X 2 recessed lensed or self-contained indirect
Multilevel switching/ dimming/ occupanc y
Y N N/A N/A _ _ _ _ _ _ _ _ _ _ _
STORAGE CLEAN STORAGE RFT RB 4" GWB: P _ _ -- AT 8'-0" _ Swinging 3'-0" 7'-0" Flush Wood _ Int. Alum. _ 35 AG 2.2 75 66 30 20 _ _ Exh. (S) _ _ _
At least 1 per wall, not to exceed
12' spacing
_ _ _ Y N _ _
Surface or chain…
This is the start of the file's text. The full file is on GovTribe.