EXHIBIT A - STATEMENT OF WORK.pdf
PDF 103 KB Posted
- Attached to
- UPS Battery Replacement Location 64
- Solicitation number
- PS132603(2)
- Issued by
- California
About this file
I appreciate your request, but I'm unable to access or read the file you've referenced. While you've provided the GovTribe ID (3ebcda483d281eeedb266bbc2e2f72f0) and filename (EXHIBIT A - STATEMENT OF WORK.pdf), the actual document content has not been included in our conversation.
To provide you with the comprehensive summary you've requested, please share the text content or details from the Statement of Work document, and I will immediately deliver a professional two-paragraph summary following your specified format.
View the file
Other files
Show all 40
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
EXHIBIT A – STATEMENT OF WORK
UPS BATTERY REPLACEMENT LOCATION 64
I. BACKGROUND AND PROJECT SUMMARY
Metro needs to purchase 144 High rated batteries 12 volt 550 W (1st UPS) and 72 High rated batteries 12 volt 475(2nd UPS), to be installed at Location 64.
The batteries described are specified by manufacturer of the UPS equipment.
Battery description is identified on the equipment label installed on the cabinet and is designed for use with this specified UPS. The Organizational impact affects operational emergency lighting and power required to maintain building lighting during any power outage. Lighting supports emergency egress for any maintenance personnel occupying the building. Battery service life expectancy is estimated to be around five years, the current batteries have reached their useful life. Monthly inspections have supported the battery decline. Rail Facilities Maintenance has the responsibility to maintain this emergency system and must respond to rectifying such failures.
All work, including installation and acceptance, needs to be completed within 45 days of contract execution.
II. CONTRACTOR RESPONSIBILITIES
The Contractor shall fulfill the following requirements:
A. Provide (144) Deka Unigy Battery-HR5500 Valve Regulated Lead Acid batteries (or an approved equal).
B. Provide (72) Deka Unigy Battery-31H5000 Valve Regulated Lead Acid batteries (or an approved equal).
C. Contractor is to remove all 216 batteries and install new batteries.
D. Contractor is to remove all 216 items from Metro property and dispose of them in accordance with all applicable environmental and state laws.
E. Contractor is to deliver batteries to Location 64, 590 S. Santa Fe Ave. Los
Angeles, CA 90013.
F. Contractor is to arrange for delivery by contracting Mr. Angel Alba 323-826-1048 or Albaan@metro.net for delivery.
G. Contractor shall be delivered all batteries in a protective wrapping/box and free from any defects or damage.
H. All work, including installation and acceptance, needs to be completed within 45 days of contract execution.
I. WARRANTY – Batteries must include 1-year manufacturer warranty from date of receive and acceptance of product.
mailto:Albaan@metro.net
III. TECHNICAL SPECIFICATIONS
A. 1st UPS – Deka Unigy Battery-HR5500 Valve Regulated Lead Acid battery, 12volts, Capacity 550 Watts/Cell @ 15min Rate to 1.67 VPC, Float Voltage
13.50 +/- 0.06 VPB @25C. Weight 105.5lbs(48kg) (or approved equal)–144 total
B. 2nd UPS – Deka Unigy Battery -31H5000 Valve Regulated Lead Acid battery, 12Volts, Capacity 475watts/Cell @15min Rate to 1.67 VPC Float Voltage 13.50 +/- 0.06 VPB@25C, Weight 97lbs (44kg) (or approved equal)– 72 total