Exhibit 3 - Clifton T Perkins Plumbing Assessment.pdf
PDF 354 KB Posted
- Attached to
- Plumbing Fixtures and Mixing Valve Repairs CTPHC
- Solicitation number
- BPM054168
- Issued by
- Howard County, Maryland
About this file
This is a plumbing assessment document for Clifton T. Perkins Hospital Center (CTPHC) in Maryland, detailing the facility's plumbing system conditions and repair requirements. The assessment identifies necessary repairs and replacements for plumbing fixtures and mixing valves throughout the facility, providing technical specifications and scope requirements for contractors bidding on the plumbing repairs and fixtures project. The document serves as a supporting exhibit for the state and local contract opportunity titled "Plumbing Fixtures and Mixing Valve Repairs CTPHC" and establishes the baseline conditions and specifications that bidders must address in their proposals.
The assessment provides the technical foundation for understanding the facility's existing plumbing infrastructure and the extent of work required for the repair and replacement project. This exhibit is critical for potential bidders to accurately estimate labor, materials, and timelines necessary to complete the plumbing improvements at CTPHC. The document enables bidders to develop informed cost proposals and project schedules based on the detailed facility assessment rather than general assumptions.
View the file
Other files
Show all 22
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1 EAST
Space Type Room # Shower Sink Tub Fixture Temp in Temp Function Fixture Temp in F Temp Function Fixture Temp in F Temp Function
Med Prep 135 1
Staff Restroom 136 1
Sec w/rest (auto) 137 1 1 0.5 74° F 100.5° F X 3.5 71° F 104.8° F X
Iso w/rest (auto) 138 1 1 0.5 71.3° F 102.1° F X 3.5 69.8° F 105.7° F X
Iso w/rest 139 1 1 0.5 gpm 70.8° F 94.3° F X
Single w/rest 141 1 1
Single w/rest (auto) 142 1 1 0.5 72° F 96.1° F X 3 gpm 74.1° F 112.1° F X
Janitor's Closet 144 1 3.5 55° F 111.2° F X
Shower 106 1 3.5 gpm 86.3° F 110.4° F X
Shower 107 1 3 gpm 89.1° F 113.2° F X
Restroom (auto) 108 1 0.5 73.2° F 105.1° F X
Restroom (auto) 109 1 0.5 gpm 72.1° F 103.4° F X
Laundry Room 119 1
Soiled Linen 120 1 1 58.1° F 119.6° F X
Clean Linen 121 1 1.5 57.7° F 120.2° F X
Shower 122 1 2.5 59.1° F 100° F X
Tub 123 1 2.5 78.1°F 115° F X 3.5 79.8° F 115.8° F X
Restroom (auto) 124 1 0.5 78.1°F 105° F X
Restroom 125 1 0.5 79° F 107.5° F X
Shower (auto) 126 1 56.8° F X
Shower 127 1 0.75 79.1° F 98.2°F X Total Fixture Count 10 15 1
Notes:
135 - No longer med prep. Now 139.
139 - Shower filled wth toilet paper, paper towels, chairs. Drains slow, sprays everywhere.
139 - Sink drains slow and sprays all over and outside of bowl 107 - Shower handle is tough to turn. Cartridge is old - recommend replacing 142 - Shower handle is tough to turn, drains slow.
141 - Danger to others. did not enter.
127 - Shower did not fully shut off. Have to spin it in reverse to get it to shut off. Anti-scold was out of position. Will need to return with a special tool to adjust it. Recommend replacing cartridge.
126 - No hot water. Pulled handle off. Cartridge is backwards and missing clip to hold anti-scold. Stops were fully open. Recommend getting anti-scold clip and flipping the cartridge.
124 - No hot water 122 - Shut off is in the middle, turn to the far right goes to fold. Won't go above 100° F.
122 - Pulled hande off - anti-scold is out of position. Need special tool to adjust.
Count Sink Shower Tub
1 EAST
119 - No sink Nurses Station - Sink in good condition and works correctly. Cold: 58.8° F; Hot: 112.8° F; Flow rate: 1.5gpm Nurses Station Bathroom - Sink old and rusted. Small drip from cold handle. Cold: 57.2° F; Hot: 113.1° F; Flow rate: 0.4gpm
2 EAST
Space Type Room # Shower Sink Tub Fixture Temp in Temp Function Fixture Temp in F Temp Function Fixture Temp in F Temp Function
Med Prep 235 1
Staff Restroom 236 1
Seclusion Room w/rest 237 1 1 0.5 75.6° F 98.8° F X 3 67.1° F 89.6° F X
Restraint Room w/rest 238 1 1 0.5 74.3° F 93.7° F X 2 73.0° F 103.1° F X
Single w/rest 239 1 1
Single w/rest 241 1 1
Single w/rest 242 1 1
Janitor's Closet 244 1 3.5 58.1° F 110.3° F X
Shower 206 1 3 66.9° F 80.1° F X
Shower 207 1 3 73.0° F 90.2° F X
Bathroom 208 1 0.5 78.0° F 100.2° F X
Bathroom 209 1 0.5 77.8° F 101.9° F X
Laundry Room 219 1
Soiled Linen 220 1
Clean Linen 221 1 1.5 597° F 110.0° F X
Shower 222 1 3 75.4° F 110.8° F X
Tub 223 1 4.5 78.1° F 112.5° F X
Bathroom 224 1 0.5 79.8° F 107.3° F X
Bathroom 225 1 0.5 80.1° F 106.9° F X
Shower 226 1 2.5 76.2° F 81.1° F X
Shower 227 1 3 61.5° F 109.6° F X Total Fixture Count 10 15 1
Notes:
219 - No Sink 220 - Could not access sink, room filled 222 - Loose handle, low hot water pressure. Recommend flipping cartridge when spare is onsite.
223 - Shower does not work. Pulled handle off and stops are fully open. Took shower head apart and cleaned. Possible blockage in the run piece up to the shower head.
226 - No hot water. Pulled handle off and stops are fully open. Tried to move anti-scold setting, but need tool to move it.
227 - Low hot water pressure. Pulled handle off and hot stop was partially closed. Opened it all the way and there is still low pressure. Recommend rebuilding both stops and cartridge 235 - Sink does not work 237 - Shower water temp does not rise above 89.6° F 239, 241, 242 - Dangerous, do not enter 207 - Shower water temp does not rise about 90.2° F 206 - Shower water temp does not rise about 50° F, water is ice cold when turned too far left
2 EAST
244 - Water temp is 110.3° F Nurses Station - Faucet works correctly. Complaints that it gets too hot sometimes. Cold: 69.9° F; Hot: 105.7° F; Flow: 1.5gpm Bathroom Faucet - Low cold water pressure. Cold: 67.7° F; Hot:107.2° F; Flow: 1.5 gpm
1 WEST
Space Type Room # Shower Sink Tub Fixture Temp in Temp Function Fixture Temp in F Temp Function Fixture Temp in F Temp Function
Restroom 107 1 0.6 72.8° F 103.2° F X
Restroom 108 1 8.48 72° F 95.6° F X
Laundry Room 122 1
Dirty Linen 123 1 0.75 59.2° F 130.1° F X
Clean Linen 124 1 2 57.3° F 128.2° F X
Janitor's Closet 125 1 3.5 56.6° F N/A NO
Bath 126 1 1.03 65.5° F 113.9° F X 3.5 67.4° F 114.1° F X
Restroom 127 1 0.5 84.2° F 114.6° F X
Restroom 128 1 0.5 79.2° F 110.1° F X
Shower 129 1 2 74.0° F 105.2° F X
Shower 130 1 2 71.2° F 110.6° F X
Med Room 138 1 0.04 56.6° F 127.5° F X
Restroom 139 1
Shower 144 1 2 62.9° F 117.0° F X
Shower 145 1 1.02 70.6° F 95.8° F X
Restraint Room w/rest 147 1 1 0.6 66.7° F 100.2° F X 3 70.1° F 103.2° F X
Single w/rest 148 1 1
Single w/rest 149 1 1
Single w/rest 150 1 1
Sec Room w/rest 140 B 1 1 0.5 75.6° F 98.1° F X 3.5 73.1° F 119.3° F X
Shower 143 A 1 2 71.2° F 110.4° F X
Sec Room w/rest 143 A 1 0.5 72.2° F 109.1° F X Total Fixture Count 10 16 1
Notes:
149 - Danger to others 148 - Danger to others 147 - Low pressure 147 - Missing aerator 130 - Low hot water pressure 130 - Pulled handle off - stops were fully open. Pulled showe heat apart and cleaned it. Still low hot pressure. Anti-scold needs to be adjusted. Recommend replacing both stops and cartridge 126 - Shower has low water pressure and drains slowly 125 - Hot water handle missing 140B - Shower water pressure too high, does not stay in shower area.
1 WEST
140B - Missing aerator 143A - Shower hot water pressure low.
Nurses Station- Sink Fixture - in good shape, works correctly. Hot needs to be shut off hard. Cold: 56.8° F; Hot: 126.6° F; Flow Rate: 1gpm Nurses Station- Bathroom Sink - in good shape, works correctly. Cold: 55.5° F; Hot: 130.6° F; Flow Rate: 1.5gpm 148, 149, 150 -Danger to others. Did not enter
2 WEST
Space Type Room # Shower Sink Tub Fixture Temp in Temp Function Fixture Temp in F Temp Function Fixture Temp in F Temp Function
Shower 227 1
Shower 226 1 1 59.1° F 73.8° F X
Restroom 225 1 0.5 63.5° F 106.1° F X
Restroom 224 1 0.5 63.1° F 104.0° F X
Tub 223 1 1 63.1° F 119.0° F X 3 64.1° F 110.5° F X
Shower 222 1 0.75 65.3° F 121.0° F X
Clean Linen 221 1 NO
Dirty Linen 220 1 0.5 60.9° F 138.8° F X
Laundry Room 219 1
Restroom 209 1 0.5 65.3° F 104.1° F X
Restroom 208 1 0.5 64.0° F 102.1° F X
Shower 207 1 0.5 59.1° F 108.8° F NO
Shower 206 1
Single w/rest 248 1 1 0.5 63.8° F 98.9° F X N/A N/A NO
Single w/rest 247 1 1
Single w/rest 246 1 1
Single w/rest 245 1 1
Janitor's Closet 243 1 2 58.2° F 132.0° F X
Restraint Room w/rest 237 1 1 0.5 63.1° F 85.0° F X 0.5 70.0° F 128.1° F X
Staff Restroom 236 1 1.5 57.6° F 131.9° F X
Med Prep 235 1 5 58.1° F 110.9° F NO Total Fixture Count 10 15 1
Notes:
236 - Faucet is loose 235 - Drains slowly, handles difficult to turn. Recommend replacing cartridges. Hot angle stop is missing its handle.
236 - Angle stops were off. Turned them on and there is a slight leak from handles when in use. Recommend replacing both hot and cold barrels, T's, and 4" spread dual wing handles 243 - Drain clogged 248 - Shower does not work. Pulled off handle and stops were fully open. Pulled shower head apart and found aerator not sitting inside. Seems to have been replaced with incorrect parts.
207 - Low water pressure, handles difficult to turn. Pulled handle off and stops were fully open. Cleaned shower head and still has low pressure. Recommend replacing cartridge.
208 - Drains slowly 227 - Out of order, no plate on wall 226 - No hot water 223 - Drains slowly 221 - Clogged aerator, unable to remove from faucet, water unable to pass through
2 WEST
237 - Clogged shower head. Hole in ceiling of shower, water leaking down. Pulled handle and stops were fully opened. Need to trace hot water lines on drawings.
206 - Patient was using shower, unable to inspect 219 - No sink 245,246,247 - Do not enter, dangerous Nurses station sink - Cold: 59.7° F; Hot: 131.1° F; Flow: 1.5gpm
3 SOUTH
Space Type Room # Shower Sink Tub Fixture Temp in Temp Function Fixture Temp in F Temp Function Fixture Temp in F Temp Function
Restroom 135 1 0.5 69.7° F 101.5° F X
Restroom 134 1 0.5 73.0° F 101.2° F X
Restroom 133 1 0.5 73.8° F 103.1° F X
Shower 132 1 3 66.2° F 105.1° F X
Shower 131 1 3 67.5° F 107° F X
Shower 130 1 3 65.6° F 106.1° F X
Bath Tub 129 1 4.5 69.2° F 99.8° F X
Utility Room 128 2 0.25 58.8° F 98.9° F X
Clean Linen 127 1
Laundry Room 126 1
Janitor's Closet 122 1 2 51.0° F 99.0° F X
Restroom 108 1 0.5 75.3° F 98.8° F X
Restroom 107 1 0.5 74.9° F 100.0° F X
Single w/rest 167 1 1
Single w/rest 163 1 1
Single w/rest 160 1 1 0.5 65.3° F 99.7° F X 3 65.1° F 110.2° F X
Single w/rest 156 1 1 0.5 64.5° F 100.8° F X 3 68.3° F 116.0° F X
Restraint Room w/rest 152 1 1 0.5 72.3° F 97.6° F X
Restraint Room w/rest 149 1 1 0.5 71.6° F 100.8° F X
Quiet Room w/rest 145 1 0.5 74.3° F 104.8° F X
Bathroom 142 1 1 Total Fixture Count 10 18 1
Notes:
131 - Out of order sign on door 128 - One sink is a washer for bed pans, not a sink. Could not test 127 - Sink ripped off wall. Drain line and water lines still there.
126 - No sink 167 - Dangerous 163 - Dangerous 152 - Sink drains slow 142 - No shower
1 SOUTH
Space Type Room # Shower Sink Tub Fixture Temp in Temp Function Fixture Temp in F Temp Function Fixture Temp in F Temp Function
Med Prep 135 1 1 gpm 60° F 107.8° F X
Staff Restroom 136 1
Restraint w/rest (auto) 137 1 1 0.5 73.1° F 83.2° F X 3 59.3° F 89.2° F X
Quiet w/rest (auto) 138 1 1 0.5 72.3° F 81.1° F X 0.75 70.2° F 100.8° F X
Single w/rest 139 1 1
Single w/rest 141 1 1
Single w/rest 142 1 1
Janitor's Closet 144 1 2.5 57.8° F 109.4° F X
Shower 106 1 3 60.1° F 102.9° F X
Shower 107 1 3 gpm 59° F 87.6° F X
Restroom (auto) 108 1 0.5 75.3° F X
Restroom (auto) 109 1 0.5 74.9° F X
Laundry Room 119 1
Soiled Linen 120 1 0.75 60.2°F 118.4° F X
Clean Linen 121 1 0.25 68.8° F 80.1° F
Shower 122 1 2.5 65.1° F 104.3° F X
Tub 123 1 2.5 79.8° F 113.2° F X 3.5 79.5° F 114.2° F
Restroom (auto) 124 1 0.5 81.2° F 102.5° F X
Restroom (auto) 125 1 0.5 81.6° F 102.2° F X
Shower 126 1 3 59.2° F 99.6° F X
Shower 127 1 3 72.1° F 98.2° F X Total Fixture Count 10 15 1
Notes 109 - Hot temp 89.6° F 108 - Hot temp 87.9° F 107 - Shower handle is tough to turn. Low water pressure.
106 - Shower does not shut off all the way. Tough to turn.
142, 141, 139 - Danger to others, did not enter.
138 - Low water pressure. Water runs out of shower and pools on the floor.
123 - Drains slowly 121 - Low pressure. Leaking from aerator 119 - No sink Nurses Station - Faucet works properly. Cold Temp: 58.4° F; Hot Temp: 79.5° F; Flow: 0.25gpm; No hot water and low flow.
Nurses Station Bathroom Sink - Good condition. Caulk starting to crack. Cold Temp: 61.8° F; Hot Temp: 103.5° F; Flow: 1.5gpm
2 SOUTH
Space Type Room # Shower Sink Tub Fixture Temp in Temp Function Fixture Temp in F Temp Function Fixture Temp in F Temp Function
Nurse Med Prep 235 1
Staff Restroom 236 1
Quiet Room w/rest 237 1 1 0.5 76.2° F 76.7° F X N/A N/A N/A NO
Single w/rest 238 1 1 0.5 73.7° F 98.7° F X 1.5 72.3° F 100.1° F X
Single w/rest 239 1 1 0.5 74.6° F 95.2° F X 1.5 79.7° F 99.8° F X
Single w/rest 241 1 1 0.5 73.8° F 100.2° F X 2 N/A 106.7° F NO
Single w/rest 242 1 1 0.5 73.2° F 94.6° F X 0.75 68.1° F 97.6° F X
Janitor's Closet 244 1 2 58.2° F N/A NO
Shower 206 1 1.5 70.1° F 105.8° F X
Shower 207 1 1.5 69.2° F 91.3° F X
Restroom 208 1 0.45 80.2° F 103.6° F X
Restroom 209 1 0.5 77.1° F 102.1° F X
Laundry Room 219 1
Soiled Linen 220 1 0.25 70.1° F 100.8° F X
Clean Linen 221 1 0.75 60.8° F 110.0° F X
Shower 222 1 2 89.6° F 109.6° F X
Tub 223 1 1.5 85.7° F 104.2° F X 3.5 89.7° F 105.0° F
Restroom 224 1 0.5 78.2° F 100.0° F X
Restroom 225 1 0.25 77.6° F 96.8° F X
Shower 226 1 0.5 78.4° F 104.8° F X
Shower 227 1 0.75 87.0° F 106.2° F X Total Fixture Count 10 15 1
Notes 207 - Low water pressure, shower handle difficult to turn 206 - Low water pressure, shower does not shut off completely 244 - No hot water 242 - Low water pressure in shower 241 - Water temp stays at 90° F 239 - Cold water in shower is warm 237 - Sink temperature does not change. Shower does not work.
235 - No sink 227 - Low water pressure, cold water stays at 87° F 225 - Water pressure too high, water going out of shower area. Only coming from center of shower head. Temperature stays at 90° F 223 - Warm water when cold is turned on.
2 SOUTH
222 - Hot/cold handles installed backwards 220 - Aerator is clogged, leaking from drain under sink 219 - No sink Nurses Station - Faucet leaks from cold handle and sprays when hot is turned on. Cold: 66.2° F; Hot: 96.9°F; Flow: 0.25gpm Bathrom Faucet - Works correctly. Cold: 59.9° F; Hot: 95.7° F; Flow: 0.25gpm
4 SOUTH
Space Type Room # Shower Sink Tub Fixture Temp in Temp Function Fixture Temp in Temp Function Fixture Temp in Temp Function Fixture Temp in F Temp Function
Restroom (Auto) 235 1 0.5 66.7° F 100.9° F X
Restroom (Auto) 234 1 0.5 70° F 105.3° F X
Restroom (Auto) 233 1 0.5 68.9° F 106.7° F X
Shower 232 1 1.5 66.3° F 102.1° F X
Shower 231 1 1 68.7° F 104.8° F X
Shower 230 1 1.5 64° F 100.8° F X
Tub 229 1 3 89.8° F 110.9° F X
Soiled Linen 228 1 0.25 65.8° F 110° F X
Clean Linen 227 1 1 56.3° F 106.7° F X
Laundry Room 226 1
Janitor's Closet 222 1 3.5 58.8° F 117.3° F X
Restroom (Auto) 208 1 0.5 68.1° F 99.6° F X
Restroom (Auto) 207 1 0.5 67.8° F 99.8° F X
Single w/ rest. (Auto) 267 1 1 0.5 63° F 105.9° F X 1.5 64.3° F 121.2° F X
Single w/ rest. (Auto) 263 1 1 0.5 62.1° F 105° F X 1.5 60.9° F 113.5° F X
Single w/ rest. (Auto) 260 1 1 0.5 63.8° F 98.7° F X 1 65.8° F 112.3° F X
Single w/ rest. (Auto) 256 1 1 0.5 58.7° F 100.6° F X 0.5 59.9° F 113° F X
Restraint Room w/rest. (A 252 1 0.5 65.6° F 110.1° F X
Restraint Room w/rest. (A 249 1 0.5 68.1° F 102.8° F
Seclusion Reoom w/rest. ( 246 1 0.5 67.8° F 101.5° F
Restroom 242 1 Total Fixture Count 6 18 1
Notes:
252 - Flow - 0.5 gpm, 65.6° F, 110.0° F 256 - Low pressure in the shower 260 - Shower head is clogged 235 - Sink drains slow 231 - Low hot water pressure 230 - Low hot water pressure 229 - No cold water, instantly warm Nurses Station - Bathroom sink faucet is loose and leaks while in use. Too much pressure. Cold: 57.8° F; Hot: 111.3° F; Flow: 2gpm Med Room - Sink is rusted. leaks from hot handle. Cold: 56.7° F; Hot: 108° F; Flow: 0.25
Count Sink 1 Sink 2 Shower Tub
1 NORTH
Space Type Room # Shower Sink Tub Fixture Temp in Temp Function Fixture Temp in F Temp Function Fixture Temp in F Temp Function Fixture Temp in F Temp Function
Patient Restroom 1N02A 1 0.3 58.1° F 105.1° F X
Patient Restroom 1N03A 1 1 gpm 57.9° F 105° F X
Patient Restroom 1N04A 1 0.3 56° F 106.8° F X
Patient Restroom 1N05A 1 0.75 54.2° F 106.2° F X
Nurses Restroom 1N07B 1 0.3 57.1° F 99.8° F X
Restroom 1N09 1 2 55.9° F 100.4 ° F X
Restroom 1N12 1 2 55.5° F 102.2° F X
Restroom 1N15 1 2 55.2° F 96.1° F X
Restroom 1N20 1 0.3 59.9° F 95.2° F X
Kitchen 1N23 1 2 59.1° F 103.6° F X
Laundry 1N24 1 4.5 55.7° F 100° F X
Showers 1N25 3 2 1 0.25 57.8° F 89.7° F X 0.5 56.6° F 98.9° F X 2.5 57.6° F 98.1° F X 5 58.1° F 99° F X
Soiled Linen 1N26 1 2 56.2° F 99.7° F X
Breakroom 1N27 1 1 57.8° F 100.6° F X
Janitor's Closet 1N28 1 4.5 56.1° F 102.8 ° F X Total Fixture Count 3 16 1
Notes:
1N25 - 2nd sink drains slowly. Tub spout is cracked and leaks when turned on. Handle above tub leaks when running 1N07B - Sink does not fully shut off 1N23 - Faucet makes whistling noise while running 1N09 - Small leak from hot handle, sink drains extremely slow 1N15 - Sink draink very slowly 1N12 - Small leak from cold handle, sink drains very slowly 1N26 - Water came out brown
Count Sink 1 Sink 2 Shower 1 Shower 2
1 NORTH
Space Type Room # Shower Sink Tub Fixture Temp in Temp Function Fixture Temp in Temp Function
Patient Restroom 1N02A 1
Patient Restroom 1N03A 1
Patient Restroom 1N04A 1
Patient Restroom 1N05A 1
Nurses Restroom 1N07B 1
Restroom 1N09 1
Restroom 1N12 1
Restroom 1N15 1
Restroom 1N19 1
Kitchen 1N23 1
Laundry 1N24 1
Showers 1N25 3 2 1 2.5 59.1° F 98.9° F X 3 gpm 81° F 102.1° F X
Soiled Linen 1N26 1
Breakroom 1N27 1
Janitor's Closet 1N28 1 Total Fixture Count 3 16 1
Count Shower 3 Tub
2 NORTH
Space Type Room # Shower Sink Tub Fixture Temp in Temp Function Fixture Temp in F Temp Function Fixture Temp in F Temp Function Fixture Temp in F Temp Function
Patient Restroom 2N02A 1 1 57° F 112.3° F X
Patient Restroom 2N03A 1 1 56.1° F 104.1° X
Patient Restroom 2N04A 1 0.25 57.2° F 99.6° F X
Patient Restroom 2N05A 1 0.25 98.7° F
Nurses Restroom 2N07B 1 0.25 56° F 99.7° F X
Restroom 2N09 1 1 57° F 99.5° F X
Restroom 2N12 1 0.25 56.1° F 83.9° F X
Restroom 2N15 1 0.25 55° F 80.3° F X
Restroom 2N19 1 0.5 56.8° F 94.8° F X
Kitchen 2N23 1 0.5 57.1° F 103.4° F X
Laundry 2N24 1 4 55.6° F 108.3° F X
Showers 2N25 3 2 1 0.25 59.8° F 105.1° F X 0.25 58.9° F 99.9° F X 2.5 55.7° F 104.3° F X 2 56.2° F 102.8° F X
Soiled Linen 2N26 1 0.5 56° F 103.8° F X
Breakroom 2N27 1 0.75 58.8° F 107.7° F X
Janitor's Closet 2N28 1 4 gpm 58.7° F 65.2° F Total Fixture Count 3 16 1
Notes:
2N28 - When hot is opened, only cole water. Cold valve turns, but only a small steam comes out.
2N27 - No/low pressure on cold water. Leaking at base of sink.
2N26 - Water came out dirty and muddy 2N25 - 2nd sink leaking from base. Both handles leak while in use. Bathtub has low cold water pressure.
2N12 - Would not go above 83.9°F. Hot handle leaks while in use.
2N05A - No cold water 2N15 - Low pressure, would not go above 80.3° F 2N09 - Leaks from hot handle while in use 2N02A - Drains slowly. Faucet whistles when hot is running.
2 NORTH
Patient Restroom 2N02A 1
Patient Restroom 2N03A 1
Patient Restroom 2N04A 1
Patient Restroom 2N05A 1
Nurses Restroom 2N07B 1
Restroom 2N09 1
Restroom 2N12 1
Restroom 2N15 1
Restroom 2N19 1
Kitchen 2N23 1
Laundry 2N24 1
Showers 2N25 3 2 1 3 58.1° F 105° F X 4.5 59.1° F 109.7° F
Soiled Linen 2N26 1
Breakroom 2N27 1
Janitor's Closet 2N28 1
3 NORTH
Space Type Room # Shower Sink Tub Fixture Temp in Temp Function Fixture Temp in F Temp Function Fixture Temp in F Temp Function Fixture Temp in Temp Function
Patient Restroom 3N02A 1 1 56.0° F 104.0° F X
Patient Restroom 3N03A 1 1 56.4° F 106.5° F X
Patient Restroom 3N04A 1 0.25 56.6° F 101.1° F X
Patient Restroom 3N05A 1 0.25 58.4° F 100.2° F X
Nurses Restroom 3N07B 1 1 55.1° F 104.9° F X
Restroom 3N09 1 0.25 57.2° F 99.8° F X
Restroom 3N12 1 1 55.2° F 103.8° F X
Restroom 3N15 1 0.25 56.6° F 85.7° F X
Restroom 3N19 1 1 55.5° F 100.0° F X
Kitchen 3N23 1 1 54.9° F 100.6° F X
Laundry 3N24 1 4.5 55.2° F 103.4° F X
Showers 3N25 3 2 1 0.5 57.8° F 102.1° F X 0.5 60.1° F 93.1° F X 3.5 58.1° F 106.1° F X 3.5 57.8° F 106.5° F X
Soiled Linen 3N26 1 2.5 55.0° F 98.9° F X
Breakroom 3N27 1 2 56.7° F 101.8° F X
Janitor's Closet 3N28 1 4.5 N/A 76.8° F NO Total Fixture Count 3 16 1
Notes:
3N28 - Cold water does not run when handle turned on 3N25 - Sink #1 drains slowly 3N25 - Showers #1 and #2 drain slowly 3N23 - Water leaks from handle when in use 3N09 - Leak from hot handle when in use 3N19 - Leak from faucet to sink.
3N04A - Sink drips from faucet.
3N02A - Sink drains slowly 3N25 - Tub does not work
3 NORTH
Patient Restroom 3N02A 1
Patient Restroom 3N03A 1
Patient Restroom 3N04A 1
Patient Restroom 3N05A 1
Nurses Restroom 3N07B 1
Restroom 3N09 1
Restroom 3N12 1
Restroom 3N15 1
Restroom 3N19 1
Kitchen 3N23 1
Laundry 3N24 1
Showers 3N25 3 2 1 3 56.1° F 105.1° F X X
Soiled Linen 3N26 1
Breakroom 3N27 1
Janitor's Closet 3N28 1
4 NORTH
Space Type Room # Shower Sink Tub Fixture Temp in Temp Function Fixture Temp in F Temp Function Fixture Temp in F Temp Function Fixture Temp in F Temp Function
Patient Restroom 4N02A 1 0.25 58.1° F 101.8° F X
Patient Restroom 4N03A 1 0.25 60° F 100.1° F X
Patient Restroom 4N04A 1 1 55.6° F 102.2° F X
Patient Restroom 4N05A 1 1 55.5° F 102.3° F X
Nurses Restroom 4N07B 1 0.25 55° F 100.3° F X
Restroom 4N09 1 1 55.3° F 99.1° F X
Restroom 4N12 1 2 56.3° F 98.7° F X
Restroom 4N15 1 1 55.7° F 100° F X
Restroom 4N19 1 1 55.2° F 98.7° F X
Kitchen 4N23 1 1 59.9° F 104.3° F X
Laundry 4N24 1 4 57.1° F 103.3° F X
Showers 4N25 3 2 1 0.5 58.1° F 100.8° F X 0.5 59.6° F 102.1° F X 2gpm 60.1° F 105.2° F X 2.5 59.7° F 101.9° F X
Soiled Linen 4N26 1 0.75 56.8° F 99.2° F X
Breakroom 4N27 1 1.5 56.6° F 100.7° F X
Janitor's Closet 4N28 1 4 53° F 89.8 X Total Fixture Count 3 16 1
Notes:
4N24 - Sink constantly runs, leaks from vacuum breaker.
4N09 - Handles are installed backwards, faucet is loose.
4N12 - High water pressure, sink drains slow 4N23 - Leaks from cold handle when in use 4N05A - Sink drains slowly 4N02A - Leaks from hot handle when in use
4 NORTH
Patient Restroom 4N02A 1
Patient Restroom 4N03A 1
Patient Restroom 4N04A 1
Patient Restroom 4N05A 1
Nurses Restroom 4N07B 1
Restroom 4N09 1
Restroom 4N12 1
Restroom 4N15 1
Restroom 4N19 1
Kitchen 4N23 1
Laundry 4N24 1
Showers 4N25 3 2 1 3 60.1° F 103.7° F X 5 55.1° F 96.1° F X
Soiled Linen 4N26 1
Breakroom 4N27 1
Janitor's Closet 4N28 1
Space Type Area Room # Shower Sink Tub
Flow Rate
S1
Range S1
Fixture S1
Restroom Silver Wing Hallway 1 0.5 57.1° F 114° F X Restroom Silver Wing Hallway 1 0.5 56.7° F 109.1° F X Restroom (Auto) Clifton's Corner 1 0.5 65° F 108.4° F X Restroom (Auto) Clinical 166 1 0.5 66.7° F 108.3° F X Exam Room 1 Clinical EX - 1 1 0.5 68.1° F 133.1° F X Exam Room Clinical 152 1 Exam Room 2 Clinical EX - 2 1 0.5 62° F 105.1° F X Office Clinical 156 1 2.5 57.8° F 130.8° F X Office Clinical 158 1 2.5 56.9° F 127.7° F X Exam Room 3 Clinical EX - 3 1 0.15 59.8° F 101.1° F X Pharmacy Clinical 129 1 0.5 62.8° F 102.3° F X Janitor's Closet Clinical 161 1 4 60.1° F 105° F X Restroom Clinical A-130 1 0.25 61.8° F 113.5° F X Restroom Clinical A-131 1 Restroom Clinical A-132 1 0.25 59.1° F 110.6° F X Restroom Clinical A-133 1 0.25 59.9° F 103.1° F X Exam Room 4 Clinical EX - 44 1 0.5 57° F 108.3° F X Exam Room Restroom Clinical EX - 44 1 0.5 62.1° F 108.8° F X X-Ray Clinical 136/137 1 1 57.3° 126° F X Dental Exam Room Clinical 147 1 0.5 69.9° F 129.5° F X Dental Exam Room Clinical 146 1 2.5 65.7°F 134.4° F Dental Lab Clinical 144 1 0.5 64.3° F 131.8° F Men's Restroom Gym 1B-100B 3 0.5 57.8° F Women's Restroom Gym 1B-100A 3 0.5 57.7° F Restroom Game Room 1B-107 1 0.5 66.2° F 81.5° F X Restroom Game Room 1B-108 1 0.5 65.5° F 83.2¯ F X Restroom Conference Room 2 Restroom Conference Room 2 2.5 61.8° F 119.7° F X Staff Restroom Conference Room 1 1 61.2° F 123.4° F X Staff Restroom Conference Room 1 1 60.1° F 120.8° F X Janitor's Closet Conference Room 1 4 58.8° F 130° F X Barbershop Rehab Flr 1 2 2 63.4° F 84.8° F X Laundry Rehab Flr 1 1R05 1 1gpm 68.5° F Patient Bathroom Rehab Flr 1 1R09 1 0.5 68.9° F 85.7° F X
Count Sink 1
Patient Bathroom Rehab Flr 1 1R10 1 0.5 69° F 86.3° F X Staff Restroom Rehab Flr 1 1R13 1 0.5 68.7° F 86.1° F X Staff Restroom Rehab Flr 1 1R14 1 0.5 68.6° F 85.9° F X Classroom Rehab Flr 1 1R16 1 2 69.4° F 85.8° X Kitchen Rehab Flr 1 1R19 1 1 64.7° F 84.9° F X Kitchen Rehab Flr 2 2R02A 1 1 62° F 83.8° F X Restroom Rehab Flr 2 2R02B 1 0.5 65.1° F 86.7° F X Total Fixture Count 3 48 0
Space Type Room # Shower Sink Tub
S1
Range S1
Fixture S1
Restroom Rehab Flr 2 2R02C 1 0.5 65.7° F 87° F X Restroom Rehab Flr 2 2R10 1 0.5 66.8° F 88.2° F X Restroom Rehab Flr 2 2R11 1 0.5 68.3° F 88.8° F X Janitor's Closet Rehab Flr 2 2R12A 1 Arts Therapy Rehab Flr 2 2R08 1 2 67.6° F 86.1° F X Arts & Crafts Rehab Flr 2 2R13 2 2 68.1° F 87.2° F X Men's Room Administration Main Level 1A15 Main 1 0.5 59.1° F 101.1° F X Women's Restroom Administration Main Level 1A14 Lobby 2 1.5 57.1° F 89.6° F X Office Restroom Administration Main Level 1A02B 1 1 61.1° F 109.8° F X Office Restroom Administration Main Level 38B 1 2.5 58.7° F 95.2° F X Men's Room Administration Main Level 1A15 2 1 56.8°F Women's Restroom Administration Main Level 1A14 Lobby 2 2.5 53.4° F 105.7° F X Janitor's Closet Administration Main Level 1A16 1 4 56° F 113.7° F X Men's Room Administration Main Level LA13 4 4 59.9° F 109.1° F X Women's Restroom Administration Main Level LA12 1 1gpm 58.8°F 115.3° F X Janitor's Closet Administration Main Level LA11 1 Women's Locker/RestroomAdmin/Dietary 1A72 2 2 1 57.9° F Restroom Admin/Dietary 1A78C 1 1 0.5 68.3° F 68.5° F X Control Restroom Admin/Dietary 1A79 1 0.5 58.1° F 115.5° F X Men's Locker/Restroom Admin/Dietary 1A85 2 0.5 61.1° F 92.8° F X Women's Locker/RestroomAdmin/Dietary 1A86 2 0.5 61.8° F 92° F X Kitchen Admin/Dietary 1K11 13 0.75 60.1° F 110.6° F X Janitor's Closet Admin/Dietary 158 1 5 165.8° F X Kitchen Serv (dining room)Admin/Dietary 1K21 1 .1 gpm 60° F Dishwashing Admin/Dietary 1K19 4 0.5 59° F 113.1° F X
Count Sink 1
Kitchen Admin/Dietary 1K20 3 Dining Room Restroom Admin/Dietary 1M04A 1 0.5 62.1° F 108.8° F X Restroom Storage 1st Flr 1S04 1 1 56.8° F 112.3° F X Restroom IT Department 1868A 1 1.5 55.8° F 90° F X Total Fixture Count 3 104 0
Notes:
1R05/1R08 - leaking plastic strainer on 2nd and 3rd washing machine.
1R05/1R08 - Hot angle stop handle is missing. Able to open angle stop with channel locks and restore hot water to faucet/eye wash station. Wate 1R19 - Not leaking anymore. No hot water.
1R13 - Sink drains very slowly 1R15 - Pulled cartridge out of handle and cleaned it. Still leaks from handle. Recommend replacing faucet. Delta 8" spread single handle.
Rehab - Found mixing station in boiler room that was only feeling 80° to the wing. Tried to adjust the mixing valve, no change in outlet temp. Rec Barbershop - Vacuum breaker is missing a rubber o-ring causing a leak. Recommend rebuild kit.
2R08 Sink - Barely gets warm 2R13 3rd sink - recommend replacing. Delta 8" spread single handle 2R13 1st sink - recommend replacing. Delta 8" spread single handle. Need lock hole cover. Therapist said they don't use the sprayer.
1A78C Shower - removed shower head and nipple - found flow restrictor was clogged. Cleaned it out and shower head now has better pressure.
1A78C Sink - Remains at a constant temp between 68.3 and 68.5° F IT I868A- Faucet - Chicago faucet- constantly dripping & high water pressure. Cold cartridge is bad and won't hold. Cartridge is corroded and hand IA72 - Shower 2 needs a shower head. It was found capped off.
IA72 - Shower 1 - need to find shut off for shower to replace cartridge. Stops on the diverter do not hold. Shut off must be below the floor.
IA72 - Sink 1 - needs new cartridge for hot handle. Suggest replacing faucet - 4" spread 2 handle. Mirror and shelf are in the way.
Main Lobby Women's - Sink 2 - cold was off at the angle stop. Turned it back on and noticed cold line has some water hammer when turned on Main Lobby Men's - Sink 2 - Leaking from cold handle. recommend replacing. 4" spread dual wing handle Main Lobby Men's - Urinal is constatly running and won't flush properly. Suggest replacing diaphragm 1A15 - Was able to get the hot handle to turn. Recommend replacing the faucet. 8" with dual wing handles. Replace both angle stops 1A02B - Low hot water pressure. Hot side angle stop does not hold. Cannot take the cartridge out. Recommend replacing faucet. 8" spread dual w LA13 - Sink 1 - Was able to flip handles and cartridges to the correct positions. Throttled water at angle stops because faucet does not have aerat 1K21 Dining Room - No hot water. Angle stop was turned off. Low flow when we opened the angle stop. Mixing valve is under the sink. Hot side i 1K21 Rack Room - Sink (8" spread wall mount) leaking from hot and cold handles - recommend replacing. Cold cartridge does not hold.
Janitors closet (outside kitching/dishwashing) - Cold is shut off at stop in faucet. Opened stop and it immediatly came out of the faucet. Recomm 1A86 Women's locker room 1st sink - hot angle stop was turned off. Cold angle stop was almost fully closed. Opened both all the way.
1A86 Women's locker room 2nd sink - Leaks from packing nut on hot side. Rubber gasket is destroyed. Low water pressure. No water comes out Conference Room Janitors Closet 123 - Sink leaks from vacuum breaker. Missing parts from vacuum breaker. Recommend rebuilding vacuum bre Conference Room 1st Staff Bathroom - 2nd sink leaks from hot handle. Tried to tighten down packing nut and it still leaks. Recommend replacing
Conference Room 2nd Staff Bathroom - 2nd sink - both cartridges are bad. Cold does not hold. Left the cold off at angle stop. Recommend replac Gym Men's Bathroom - Battery is energizer 223. No water coming out of the 1st or 2nd faucet. Pulled security panel off of the bottom of sink, fo Gym Women's Bathroom - Pulled security panel off. Hot side angle stop is on. Still only cold water coming out of the faucets. Will need to look at Gym - Used drawings in maintenance to trace out hot water lines and markings on pipe in tunnel. Traced it back to a recirc pump that is running Silverwing Hallway Men's Bathroom - Leaking from both handles. Tried to tighen packing nuts down and it still leaks. Recommend relacement - Silverwing Hallway Women's Bathroom - Leaking from hot handle. Set screws are corroded. Tried to tighten packing nut down and it still leaks. R Clinical Exam Room 2 - Sink drains very slowly.
Clinical Exam Room 3 - Sink leaks when turned on. Needs new cartridge - need key to unclog it. Delta single handle 161 - Cold cartridge does not hold. Vacuum breaker leaks. Recommend rebuilding cold and vacuum breaker. SC-5811-B6411 133 - Leaks from hot handle. Tried to tighten down the packing and it still leaks. Recommend replacing. Can rebuild but faucet is older. 4" spread 130 - Leaks from cold handle. Handle is loose. Can not tighten down packing nut anymore. Cannot get cover off of cold handle to access the screw 131 - out of order 146 - Leaks from base of the handle. Tried to clean cartridge out and it still leaks. Recommend cartridge replacement. Delta single handle.
144 - Leaking from handle when in use Exam Room 4 - Leaks from handle. Tried to clean cartridge but it still leaks. Recommend cartridge replacement. Delta single handle.
1K11 1st Sink- able to tighten packing nut and stop leak from hot handle. Recommend replacing the hot side barren and handle.
1K11 2nd Sink- Missing faucet 1K11 5th Sink - leaking from faucet nut. Was able to tighten the faucet nut and stop the leak 1K11 7th Sink (dishwashing) - Faucet is constantly running. Neither cartridge holds. Tried to tighen packing nut and it still leaks. Recommend rep 1K11 8th Sink - Cold: 57.8° F; Hot: 104.8° F; Flow 2.5 gpm 1K11 9th Sink - Cold: 61.2° F; Hot: 118.9° F; Flow 1 gpm 1K11 10th Sink - Cold handle is missing. Cannot get a good reading. Cold: 57.6° F; Hot: N/A; Flow 1 gpm 1K11 11th Sink - Leaking from faucet nut, not handle, and constantly dripping. Cold: 58.1° F; Hot: 130.4° F; Flow 10 1K11 12th Sink - Leaking from faucet nut and constantly dripping. Cold: 56.6° F; Hot: 128.8° F; Flow 10 1K11 13th Sink - Cold: 56.1° F; Hot: 120° F; Flow 5 1A85 Men's locker room 2nd sink - Drains slow Control Room - Sink makes a noise when cold water is running. Cold: 58.1° F; Hot: 115.5° F; Flow: 0.5 1A14 - Sink makes a noise when cold water is running.
LA11 - Drains very slowly LA10 CPR/Storage- Sink - Cold: 56.8° F; Hot: 112.3° F; flow: 1gpm On Call Room Sink - Cold: 58.7° F; Hot: 95.2° F; flow: 2.5gpm On Call Room Shower - Cold: 56.8° F; Hot: 94° F; flow: 4.5gpm Canteen 109A - Cold: 66.1° F; Hot: 114° F; flow: 2.5gpm Gym & Rehab - Heat exchanger is having issues, and may be the cause of low water temp in rehab and gym.
Dietary - Recirc pump was running on the dietary mixing station in the boiler room. It was valved off and running dry - will burn the pump. Did no
S2
Range S2
Fixture S2
S3
Range S3
Fixture S3
S4
Range S4
Fixture S4
0.5 56.2° F X 0.5 57.2° F X
2 123.9° F 3 59.8° F 125.1° F X
5 63.9° F X
Sink 2 Sink 3 Sink 4
S2
Range S2
Fixture S2
S3
Range S3
Fixture S3
S4
Range S4
Fixture S4
4 67.9° F 85.9° F X 2 68.3 X
0.5 50.7° F 100° F
1.5 90.8° F
4.5 56.8° 94° F X
205 55.8° F 110.2° F X
0.5 59.3° F 112.4° F X 0.5 59.5° F 114.1° F X 0.5 59.5° F 114.4° F X
4 55.7° F 113.5° F X 1 58.4° F 110.4° F X
0.5 67.6° F 107.2° F X
0.5 60.9° F 92.6° F X
0.15 62° F
4 57.8° F 113.5° F X
10 57.1° F 135.8° F X 10 58.4° F 139.8° F X
Sink 2 Sink 3 Sink 4 er was brown - flushed line and cleared aerator.
circ pump is running dle won't come off. Recommend to replace handle, cartridge, and aerator - no more than 0.5gpm wing handles. Replace angle stops - 3/8" tor.
is probably clogged up inside mixing valve. Low flow out of angle stop - blew out supply hose. Recommend replacing mixing valve, 1/2" lines. Le mend rebuilding the whole faucet.
t when hot is turned on. Reecommend replacing zurn 4" spread dual wing handles.
eaker. Speakman part # RPG05-0520 g hot cartridge - chicago faucet
SH1
Range SH1
Fixture
SH2
Restroom Silver Wing Hallway 1 Restroom Silver Wing Hallway 1 Restroom 1 Restroom 166 1 Exam Room 1 EX - 1 1 Exam Room 152 1 Exam Room 2 EX - 2 1 Office 156 1 Office 158 1 Exam Room 3 EX - 3 1 Pharmacy 129 1 Janitor's Closet 161 1 Restroom A-130 1 Restroom A-131 1 Restroom A-132 1 Restroom A-133 1 Exam Room 4 EX - 44 1 Exam Room Restroom EX - 44 X-Ray 136/137 1 Dental Exam Room 147 1 Dental Exam Room 146 1 Dental Lab 144 1 Men's Restroom 1B-100B 3 Women's Restroom 1B-100A 3 Restroom 1B-107 1 Restroom 1B-108 1 Restroom 2 Restroom 2 Staff Restroom 1 Staff Restroom 1 Janitor's Closet 1 Barbershop 2 Laundry 1R05 1 Patient Bathroom 1R09 1
Shower 2Count Shower 1
Patient Bathroom 1R10 1 Staff Restroom 1R13 1 Staff Restroom 1R14 1 Classroom 1R16 1 Kitchen 1R19 1 Kitchen 2R02A 1 Restroom 2R02B 1 Total Fixture Count 0 48 0
SH1
Range SH1
Restroom 2R02C 1 Restroom 2R10 1 Restroom 2R11 1 Janitor's Closet 2R12A 1 Arts Therapy 2R08 1 Arts & Crafts 2R13 2 Men's Room 1A15 1 Women's Restroom 1A14 2 Office Restroom 1A02B 1 Office Restroom 38B 1 Men's Room 1A43 2 Women's Restroom 1A44 2 Janitor's Closet 1A16 1 Men's Room LA13 4 Women's Restroom LA12 1 Janitor's Closet LA11 1 Women's Locker/Restroom 1A72 2 2 2 56.2° F Restroom 1A78B 1 1 Control Restroom 1A79 1 Men's Locker/Restroom 1A85 2 Women's Locker/Restroom 1A86 2 Kitchen 1K11 13 4 60° F 108.2° F X 4 57.6° F Janitor's Closet 158 1 Kitchen Serv 1K21 1 Dishwashing 1K19 4 2 63.8° F 137.6° F X
Shower 1Count Sink 5
Kitchen 1K20 3 Dining Room Restroom 1M04A 1 Restroom 1S04 1 Restroom 1868A 1 Total Fixture Count 3 104 0 eft hot side off
Range SH2
Shower 3
117.5° F X 2 56.2° F 117.5° F X
110.2° F X 1 58.7° F 63.8° F X
Shower 1
Additional Areas
Space Type Room # Shower Sink Tub Fixture Temp in Temp Function Fixture Temp in F Temp Function Fixture Temp in F Temp Function Fixture Temp in F Temp Function 1 South Restroom 139 1 1 0.5 66.7° F 87° F X 3.5 69.4° F 85.4° F X 1 South Restroom 141 1 1 0.5 80° F 108.3° F X 3 96.1° F 110° F X 1 South Restroom 142 1 1 0.5 76.6° F 95.5° F X 4.5 80° F 96.3° F X
1 East Restroom 141 1 0.5 70.1° F 96° F X 1 West Restroom 148 1 1 0.5 68.8° F 99.7° F X 3.5 95.7° F 125° F X 1 West Restroom 149 1 1 0.5 67.9° F 110.5° F X 5 77° F 116.9° F X 1 West Restroom 150 1 1 0.5 76.2° F 111.7° F X 5 76.7° F 119.6° F X 2 West Restroom 245 1 1 0.5 69.6° F 105.2° F X 3.5 73.8° F 117.2° F X 2 West Restroom 246 1 1 0.5 74.7° F 115.6° F X 4 66.2° F 124.7° F X 2 West Restroom 247 1 1 0.5 69° F 113° F X 4.5 68.1° F 108.7° F X
2 East Restroom 239 1 1 0.5 69.3° F 109° F X 5 84° F 126.3° X
2 East Restroom 241 1 1 0.5 71.6° F 122.6° F X 5 75.5° F 122.7° F X
2 East Restroom 242 1 1 0.5 71.6° F 113° F X 5 73° F 115.7° F X 3 South Restroom 163 1 1 0.5 80° F 107.5° F X 5 72.2° F 110.6° F X 3 South Restroom 167 1 1 0.5 68.3° F 107.8° F X 5 76.4° F 105.6° F X Total Fixture Count 15 14 0
Notes:
1 West, 148 - Shower head seems clogged - has restricted flow. Will not go below 95°.
1 West, 150 - Shower has missing aerator.
1 East, 141 - Sink drains slowly.
2 West, 245 - Shower head seems to be clogged - has restricted flow.
2 West, 247 - Sink drains slow. Shower handle is hard to turn.
2 East, 239 - Water runs out of the shower.
2 East, 242 - Shower drains slowly.
1 South, 139 - Shower handle is tough to turn, restricted flow.
1 South, 141 - Shower seems to have restricted flow. Instantly hot in the shower - no cold.
1 South, 142 - Shower got warm instantly.
Mixing Valves
Space Type Room # Mod # Notes
3 South 148 Powers LFMM432-1 Recirculation pump was off, has no aquastat so it runs 24/7. Before the pump was turned on, incoming temperature was 115 degrees. After pump was turned on, temp went to 140 degrees. Temp adjustment on the mixing valve was not working properly. Recommend rebuilding.
1 South Med Room Leonard LV9820347LF Temp going to the ward was 118 degrees. Incoming temp was 119 degrees on the hot side and 95 degrees on the cold. Recirculation pump is in the ceiling of the nurses station and was on. No temperature adjustment after turning the dial. Recommend rebuilding.
1 East Med Room Leonard LV981LF Temp going out was 105 degrees. Incoming temp was 98 on the hot side and 86 on the cold There is a possible backwards check vale on the 1 West Dr. Office Leonard LV9820770LF Temp going out is above 140 degrees. Incoming is 140 on the hot and 130 on the cold. Cold main coming in is extremently hot. Cold check valve is
Kitchen/Staff Cafe Under Sink Only feed the hand sink. Hot side was off - when turned on, it had extremely low flow. Recomment replacing with a cheaper and smaller mixing valve.
North/Dietary Mech room under sink RADA DRV-80 Incoming 160 degrees. Outgoing 120 degrees.
Boiler Room/Rehab Main Boiler Leonard TM155838BLF Valve from lower mixing valve was closed. Before opening valve, outgoing was 95 degrees. After opening, valve was 110 degrees. Recommend
Mixing Valves
| 1 EAST |
| 2 EAST |
| 1 WEST |
| 2 WEST |
| 3 SOUTH |
| 1 SOUTH |
| 2 SOUTH |
| 4 SOUTH |
| 1 NORTH |
| 2 NORTH |
| 3 NORTH |
| 4 NORTH |
| OTHER |
| Additional Areas |
| Mixing Valves |
File details come from the government source that posted it. Updated .