Attachment #1 – Equipment Specs
The DHWH specifications include the following with an example being the Thermal Solutions Amp Water
Heater (AMPW 2000):
Boiler / Pressure Vessel:
a. Meet the Buy America Act clause of the umbrella contract
b. ASME stainless steel heat exchanger
c. ASME Section IV certified, “H” stamp
d. Minimum 97% thermal efficiency
Combustion System:
e. Stainless steel pre-mix burner
f. Low NOx emissions
g. Full modulation, 5:1 turndown
h. Natural gas
i. Direct spark ignition with UV scanner
j. High/low gas pressure switches, manual reset
k. Zero governor gas valve
l. Variable speed combustion blower
m. Air proving switch
n. Blocked vent switch
Boiler Control System / Equipment:
o. High limit temp control, manual reset
p. Low water cutoff, manual reset
q. Water flow switch
r. Air vent valve
s. Blocked condensate switch
t. Condensate trap
u. Pressure and temperature gauge
v. ASME safety relief valve
Electrical Design:
w. 120 VAC / 60 Hz / 1 Ph (Optional 208 or
230 VAC / 60 Hz / 1 Ph)
x. Printed circuit board (PCB) fused connections