This document contains a statement of work for a federal construction contract opportunity to restore the exteriors of five historical quarters buildings located at the James H. Quillen VA Medical Center. The scope of work includes restoration and renovation such as replacing wood, installing water barriers, painting, conducting roof repair and replacement, tuckpointing and repairing brick, and extending downspouts. The period of performance is 400 calendar days. The contractor will be responsible for supervision, communication, planning, drawings, site visits, deliveries, final inspection, and closeout. Submittals are due within 60 days of the notice to proceed. Work will take place during normal business hours from Monday through Thursday, and coordination is required for any work outside of these hours or affecting patient care areas. Security, parking, and access requirements are also outlined.
View the file
Other files
Show all 27
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
APPENDIX B.19
BUILDING 45
LEAD SAMPLE SUMMARY TABLE
BUILDING 45
XRF READINGS
HA NO. Color & Substrate XRF Sample No.
Sample Location / Room Number
Results mg/cm2
Estimated Quantity
Pre-Sampling Calibration Readings
NA
1.0
N/A
2 1.1
3 1.0
4 1.0
Post Sampling Calibration Readings
329 1.0
330 1.1
331 1.0
332 1.0
01 White Plaster Wall
5 100 0.3
5,800 ft²
31 104 0.2
63 103 0.2
121 202 0.1
168 205 0.1
199 208A 0.1
250 200 0.2
White Plaster
Ceiling
28 102 0.1
2,600 ft²
68 103 0.2
105 100A 0.1
157 204 0.1
176 205 <
White Wood Door
Frame
8 100 3.0
42 frames 47 107 2.5
136 202A 8.5
220 207B 6.9
04 White Wood Door
9 100 5.0
45 doors 48 107 6.4
137 202A 8.7
221 207B 6.9
White Wood
Window Frame
98 100A <
NA151 204 <
212 207 <
White Wood
Window
99 100A < windows 152 204 <
213 207 1.1
XRF READINGS
HA NO. Color & Substrate XRF Sample No.
Sample Location / Room Number
Results mg/cm2
Estimated Quantity
White Wood Cove
Base
26 102 9.7
550 ft144 201 6.0
225 207B 9.1
White Wood Stair
Components
87 100 Stair Stringer 7.7
200 ft²88 100 Stair Picket 5.7
89 100 Stair Nosing <
Lite Yellow Plaster
Wall
221 207B 0.2
100 ft²222 207B 0.1
223 207B 0.1
10 Seafoam Brick Wall
258 B103 <
NA259 B103 <
260 B103 <
Gray Wood Stair
Components
295 B100 Stair Stringer 7.3
200 ft²296 B100 Stair Picket 6.8
297 B100 Stair Handrail 5.7
White Exterior
Wood Components
Exterior Front Porch
Siding 3.7
4,600 ft²313 Exterior Rimboard 3.0
322 Exterior Siding 8.1
White Brick Foundation
309 Exterior Front Porch <
600 ft²316 Exterior 3.0
324 Exterior 0.1
Grey Concrete
Floor
284 B101 0.9 1,500 ft²
294 B100 1.1
White Wood Trim
Components
143 201 0.1
200 ft²115 100B 0.2
78 106 4.1
CHIP SAMPLES
HA NO. Color & Substrate Chip Sample No.
Sample Location / Room Number
Results % by weigh
13 White brick foundation Pb-01 Front Porch 15
02 White plaster ceiling Pb-02 B102 0.047
14 Grey on concrete floor Pb-03 B100 0.29
01 White on plaster wall PB-04 100A 0.15
15 White wood shelf Pb-05 204A 0.0094
NA = Not Applicable < indicates result is below the detection limit for the XRF instrument or laboratory analytical method.
Client Sample Description ConcentrationLab ID Analyzed Weight Lead
Collected
EMSL Analytical, Inc.
10801 Southern Loop Blvd, Pineville, NC 28134 Phone/Fax: (704) 525-2205 / (704) 525-2382 http://www.EMSL.com charlottelab@emsl.com
Attn: Patrick Peoples Terracon 2147 Riverchase Office Road Hoover, AL 35244
Received: 9/7/2022 09:20 AM
James A. Quillen VA Medical Center - Building 45/ 18227196
Fax: (205) 942-1266 Phone: (205) 942-1289
Project:
8/30/2022Collected:
Test Report: Lead in Paint Chips by Flame AAS (SW 846 3050B/7000B)*
412208921 CustomerID: TRCN34 CustomerPO: 18227196 ProjectID:
EMSL Order:
.2362 Site: White Paint on Brick Foundation-Front Porch, Side A 412208921-0001Pb-01 15 % wt9/9/2022 g8/30/2022
.2238 Site: White Paint on Plaster Ceiling-Room B102 412208921-0002Pb-02 0.047 % wt9/9/2022 g8/30/2022
.2434 Site: Grey Paint on Concrete Floor-Room B100 412208921-0003Pb-03 0.29 % wt9/9/2022 g8/30/2022
.2154 Site: White Paint on Plaster Wall-Side B, Room 100A 412208921-0004Pb-04 0.15 % wt9/9/2022 g8/30/2022
.2160 Site: White Paint on Wood Shelf-Room 204A 412208921-0005Pb-05 0.0094 % wt9/9/2022 g8/30/2022
Aaron Hartley, Lead Technical Manager or other approved signatory
Test Report ChmSnglePrm/nQC-7.32.3 Printed: 9/12/2022 8:20:10 AM
EMSL maintains liability limited to cost of analysis. Interpretation and use of test results are the responsibility of the client. This report relates only to the samples reported above, and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. The report reflects the samples as received.
Results are generated from the field sampling data (sampling volumes and areas, locations, etc.) provided by the client on the Chain of Custody. Samples are within quality control criteria and met method specifications unless otherwise noted.
* Analysis following Lead in Paint by EMSL SOP/Determination of Environmental Lead by FLAA. Reporting limit is 0.008% wt based on the minimum sample weight per our SOP. "<" (less than) result signifies the analyte was not detected at or above the reporting limit. Measurement of uncertainty is available upon request. Definitions of modifications are available upon request.
Samples analyzed by EMSL Analytical, Inc. Pineville, NC AIHA-LAP, LLC - ELLAP 192283
Initial report from 09/12/2022 08:20:10
OrderID: 412208921
VA Mountain Home Lead-Paint Photo Page - 18227196 Building 45, Johnson City, Tennessee Date photos taken: August 30, 2022
Photo #1 HA 01 white paint on plaster walls, (lead containing).
Photo #2 HA 02 white paint on plaster ceilings, (lead containing).
Photo #3 HA 03 white paint on wooden door frames, (lead-based).
Photo #4 HA 04 white paint on wooden doors, (lead-based).
Photo #5 HA 05 white paint on wooden window frames.
Photo #6 HA 06 white paint on wooden windows, (lead-based).
Photo #7 HA 07 white paint on wooden cove base, (lead-based).
Photo #8 HA 08 white paint on wooden stairs components, (lead-based).
Photo #9 HA 09 lite yellow paint on plaster walls, (lead containing).
Photo #10 HA 10 seafoam paint on brick walls.
Photo #11 HA 11 gray paint on wooden stair components, (lead-based).
Photo #12 HA 12 white paint on wooden exterior components, (lead-based).
Photo #13 HA 13 white paint on brick foundations, (lead-based).
Photo #14 Pb-01 white paint on brick foundation, (lead-based).
Photo #15 Pb-02 white paint on plaster ceiling, (lead containing).
Photo #16 Pb-03 gray paint on concrete floor, (lead containing).
Photo #17 Pb-04 white paint on plaster wall, (lead containing).
Photo #18 Pb-05 white paint on wood shelf, (lead containing).
| JHQVAMC - LEAD APPENDICES without Drawings |
| Credentials |
| Building 3 Lead Appendix |
| Sheets |
| 3D-03 - 3D Building |
| LE-03_01 - Lead Plan - Basement |
| LE-03_02 - Lead Plan - First Floor |
| LE-03_03 - Lead Plan - Second Floor |
| LE-03_04 - Lead Plan - Attic |
| Building 5 Lead Appendix |
| Sheets |
| 3D-05 - 3D Building |
| LE-05_01 - Lead Plan - Basement |
| LE-05_02 - Lead Plan - First Floor |
| LE-05_03 - Lead Plan - Second Floor |
| LE-05_04 - Lead Plan - Attic |
JHQVAMC LCP Sampling and Plan JD AJM
SCiAps_X-550_PCS_Feb22