E101_R1_AD2___CONCESSIONS___DUGOUT_BUILDINGS_.pdf
PDF 2 MB Posted
- Solicitation number
- PE-55462-NONST-2025-000000010
- Issued by
- Wilcox County, Georgia
About this file
This is an electrical plan drawing (sheet E101) for the Rossville Middle School Athletic Field and Concessions project in Walker County, Georgia. The drawing shows detailed electrical layouts for concessions and dugout buildings, including lighting plans, power plans, and various electrical system schematics. The plans detail the placement of outlets, lighting fixtures, circuit panels, and electrical equipment for both the concessions building and home/visitor dugouts.
The technical specifications include detailed schematics for exterior outlet installations, a 208V electrical grounding system, exterior lighting timeclock contactor setup, and sewage lift station installation details. The drawing contains specific keynotes for power requirements, including provisions for wall-mounted twist-lock receptacles for electric heaters and water heater disconnect switch placement. The plans are drawn to a scale of 1/8" = 1'-0" for the main layouts, with additional no-scale detail drawings for specific components and installations.
View the file
Other files
Show all 47
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
T
PP
S
C C
T /S
PC
PP
S
PP
S w p /g fi wp/gfi wp/gfi wp/gfi w p /g fi gf gf
J gfgf g f g f gf gf gf
M
M
M w p /g f i w p /g f i w p /g f i w p /g fi w p /g fi w p /g fi
I5 E
JSE
JSE
JSE
JSE 1
RESTROOM
RESTROOM
EQUIP STORAGE
ELEC
CONCESSIONS
I5 I5E
I5 I5
I5 E
F1
F1 F1
F1
F1E
LBB
LBB- 24
LBB- 17
LBB- 19
LBB
LBB- 3
LBB- 1
LBB- 10
CONCESSIONS
RESTROOM
RESTROOM
EQUIP STORAGE
ELEC
LBB- 7
LBB- 11
LBB- 6,8
LBB- 2
LBB- 14
LBB- 12
LBB- 18
LBB- 16
LBB- 13
FUTURE
CONTACTOR
CABINET
7' AFF
LBB- 20
LBB- 9
LBB- 26,28
LBB- 5
E3
E2
E2
E2
E1
EF
EF
LBB- 30,32
LBB- 4
LBB- 34,36
LBB- 31,33
LBB- 27,29
EF
LBB- 35
LBB- 15
LBB- 22
6" X 4" I BEAM
CONCRETED BELOW
GRADE. MINIMUM 6"
DIAMETER, 24" DEEP
CONCRETE BELOW
GRADE.
ROUTE CONDUIT TO
PANELBOARD INDICATED
ON PLANS.
24"
MAXIMUM
TO TOP
OF I-BEAM
RIGID
CONDUIT
ROUND OFF I-BEAM
CORNERS 1-1/2"
RADIUS
GFI DUPLEX WITH
CAST WEATHERPROOF
COVER. COVER SHALL
BE TOP HINGED.
12" MINIMUM
TO BOTTOM
OF OUTLET
SERVICE ENTRANCE EQUIPMENT
OR REMOTE BUILDING SUPPLIED
BY A FEEDER OR BRANCH CIRCUITS
3-3/4"x10'-0" COPPER
CLAD STEEL GROUND
RODS (MAIN GND ELECTRODE)
SIZE PER NEC
250-66
INTERSYSTEM
GROUNDING
BUSBAR
GROUND BUS
SIZE (SEE RISER
DIAGRAM)
REMOVABLE
LINK
SOLID NEUTRAL
THERMA
WELD (TYP)
OZ TYPE CG
CONNECTOR
MAIN GROUND
ROD ARRANGEMENT
JUMPER
20'0" MIN OF 1/2"
REBAR IN FOOTING
(WHERE AVAILABLE)
THERMA
WELD (TYP)
BLDG.
STEEL
TO INTERCOM
LIGHTNING
PROTECTION
TO FIRE ALARM
LIGHTNING
PROTECTION
TO TELEPHONE
BACKBOARDS
LIGHTNING
PROTECTION
NOTE 5
GROUNDING SYSTEM SCHEMATIC NOTES:
1. GROUNDING & BONDING SYSTEM CONDUCTORS SHALL BE SIZED
IN ACCORDANCE NEC WITH ARTICLE 250.
2. MAIN GROUNDING ELECTRODE SHALL CONSIST OF (3) 10' x 3/4 "
DRIVEN COPPER RODS IN AN EVENLY SPACED TRIANGULAR
FORMATION.
3. TEST GROUND RESISTANCE OF EACH GROUNDING ELECTRODE
PRIOR TO CONNECTING GROUNDING ELECTRODE CONDUCTOR.
4. GROUNDING ELECTRODE CONDUCTORS SHALL BE CONNECTED
TO DIVEN RODS WITH EXOTHERMIC WELD CONNECTIONS.
5. A BONDING CONDUCTOR SIZED PER NEC TABLE 250.66 SHALL BE
PROVIDED FOR EACH METAL PIPING SYSTEM INSTALLED
IN OR ATTACHED TO THE BUILDING. FOR BUILDINGS SEPARATED
FROM SERVICE ENTRANCE PANEL, PROVIDE BONDING
CONDUCTOR TO EQUIPMENT GROUND BUS LOCATED IN PANEL FED
BY BUILDING SUPPLY CONDUCTORS.
6. MAIN BONDING JUMPER, ONLY INSTALLED IN SERVICE
ENTRANCE EQUIPMENT.
10' 10'
10'
NN
G G
S S
IG
SURGE SUPRESSOR
AS SPECIFIED
EQUIPMENT
GROUND BAR
NEUTRAL
GROUND BAR
ISOLATED
GROUND BAR
N
G
208/120V
COMPUTER
PANEL
208/120V
BRANCH CKT
PANEL
TO EXTERIOR
LIGHT FIXTURES
CK#1 CK#2
N
H
OFF
ON
PC
PHOTOCELL
@ ROOF EAVE
OFF
ON
* 3-WIRE CONNECTION
(COMMON NOT SHOWN)
INTERMATIC ET70000C SERIES
(OR PRIOR APPROVED EQUAL)
LBB-30
LBB-25
2-CIRCUIT
ELECTRONIC
TIME SWITCH
IN CLOSET 101
CONTACTOR '1'
EOMH 2-POLE
IN CLOSET 101
CONTACTOR '2'
EOMH 2-POLE
IN CLOSET 101
SPARE
SPARE
TO EXTERIOR
LIGHT FIXTURES
L
IQ
U
ID
L E
V E
L C
O N
T R
O L L E
R
STAND-BY PUMP "ON"
ALL "OFF"
EL:
EL:
EL:
UPPER GUIDE RAIL BRACKET
GUIDE RAIL
DISCHARGE PIPE
PUMP/MOTOR ASSEMBLY,
VENT
SECTION A - A
POWER CABLES
S/S PUMP LIFTING CABLE
BASIN BOTTOM
EL:
FINISHED GRADE
INLET INVERT
EL:
A A
OUTLET INVERT
EL:
LEAD PUMP "ON" (ALTERNATES)
EL:
CONTROL CABLES
NOTES 1, 2 & 4
NEMA -6 JUNCTION BOX
NOTE 4
NOTE 2
CONTROL PANEL
NOTE 3
NOTE 1
GROUND
ROD
# 8 CU 1/2"C
NOTE 4
UPPER GUIDE
RAIL BRACKET
3#8 & 1#10 CU THWN 3/4"C
TO 208V PANEL LBB
HIGH WATER ALARM "ON"
LIQUID LEVEL CONTROL
HANGER ROD
PUMP REMOVAL
ACCESS DOOR.
PREFABRICATED CONCRETE
BASIN
PREFABRICATED CONCRETE
BASIN
LIGHTNING
ARRESTOR
NOTES:
1. PROVIDE (2)1/2" CONDUITS WITH 4 # 12 FOR PUMP POWER.
2. PROVIDE 1/2" CONDUIT WITH 6 # 14 FOR PUMP CONTROLS.
3. PROVIDE UNISTRUT FRAME WITH CONCRETE FOUNDATION FOR PUMP
CONTROL PANEL. MOUNT PANEL WITH TOP AT 6' 0' ABOVE FINISHED GRADE.
SEE MANUFACTURERS CONTROL PANEL SCHEMATIC FOR CONNECTIONS.
4. CORE DRILL WALL FOR CONDUIT PENETRATIONS. CAULK SPACES
BETWEEN CONDUITS AND CORED HOLES WATERTIGHT.
F
O N
WEIL
SCALE: = 1'-0"
DRAWING NUMBER
REVISIONS
COPYRIGHT 2024 BY SOUTHERN A&E, LLC. ALL RIGHTS RESERVED.
THIS DOCUMENT IS THE PROPERTY OF SOUTHERN A&E, LLC AND SHALL
NOT BE COPIED OR REPRODUCED IN WHOLE OR IN PART WITHOUT
EXPRESSED WRITTEN CONSENT FROM SOUTHERN A&E, LLC.
12-17-2024
BID PACKAGE BP-1
SA&E PROJECT NUMBER
ORIGINAL SHEET SIZE: ARCH E1 (30" X 42")
A
TRUE
NORTH
0 8 168
1/8"
2" GRIDS 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
B
C
D
E
F
G
H
I
J
K
L
M
N
KEYPLAN
A
ROSSVILLE MIDDLE SCHOOL
NEW FIELD AND CONCESSIONS FOR:
WALKER COUNTY SCHOOLS
301 N CHEROKEE ST, LAFAYETTE, GA 30728
316 BULLDOG TRAIL, ROSSVILLE, GA 30741
746-0206
01-920-041
ISSUED FOR CONSTRUCTION
STATE BOARD OF REGISTRATION
FOR PROFESSIONAL ENGINEERS AND
LAND SURVEYORS
SOUTHERN A & E, LLC
ENGINEER FIRM
LICENSE NO: PEF003374
EXP. DATE - 06/30/2026
C
B
E101
CONCESSIONS & DUGOUT BUILDINGS
ELECTRICAL PLANS
1/8" = 1'-0"E101
1 LEVEL 01 - LIGHTING PLAN - CONCESSIONS
1/8" = 1'-0"E101
3 LEVEL 01 - POWER PLAN - CONCESSIONS
1/8" = 1'-0"E101
8 LEVEL 01 - POWER PLAN - HOME DUGOUT
1/8" = 1'-0"E101
10 LEVEL 01 - POWER PLAN - VISITORS DUGOUT
NO SCALEE101
7 DETAIL - EXTERIOR OUTLET DETAIL
NO SCALEE101
11 SCHEMATIC - 208V ELECTRICAL GROUNDING SYSTEM
NO SCALEE101
9 SCHEMATIC - EXTERIOR LIGHTING TIMECLOCK CONTACTOR
KEYNOTE SCHEDULE - POWER
# KEYNOTE DESCRIPTION
E1 PROVIDE WALL MOUNTED TWIST-LOCK RECEPTACLE FOR USE BY OWNER FOR
ELECTRIC HEATERS. VERIFY CIRCUIT SIZE OF OWNER PROVIDED HEATERS AS WELL
AS RECEPTACLE LOCATION PRIOR TO ROUGH-IN.
E2 PROVIDE TWIST-LOCK RECEPTACLE FLUSH IN CEILING FOR USE BY OWNER FOR
ELECTRIC HEATERS. VERIFY CIRCUIT SIZE OF OWNER PROVIDED HEATERS AS WELL
AS RECEPTACLE LOCATION PRIOR TO ROUGH-IN.
E3 INSTALL DISCONNECT SWITCH FOR TEWH 6" ABOVE FINISHED CEILING. LABEL
DISCONNECT AS 'WATER HEATER'.
# Doc # Date
1 AD2 1/15/25
NO SCALEE101
2 DETAIL - SEWAGE LIFT STATION INSTALLATION
erik
FRANK - SIGNED
| Sheets |
| E001 - ELECTRICAL LEGENDS |
| E002 - LIGHTING FIXTURE & MECHANICAL EQUIPMENT CONNECTION SCHEDULE |
| E003 - ELECTRICAL SITE PLAN |
| E101 - CONCESSIONS & DUGOUT BUILDINGS ELECTRICAL PLANS |
File details come from the government source that posted it. Updated .