E001_R1_AD2___ELECTRICAL_LEGENDS.pdf

PDF 2 MB Posted

Attached to
Rossville Middle School Athletic Field and Concessions
Solicitation number
PE-55462-NONST-2025-000000010
Issued by
Wilcox County, Georgia

About this file

This file contains electrical and lighting control legend diagrams for the Rossville Middle School Athletic Field and Concessions project in Walker County, Georgia. The document provides detailed electrical symbols and specifications, including raceway types, receptacle configurations, lighting fixtures, disconnect switches, and control systems. A power riser diagram shows the electrical distribution from the utility transformer to panel LBB, with fault current calculations dated December 17, 2024.

The document includes a comprehensive electrical panel schedule for Panel LBB showing connected loads of 34,824 VA with an estimated demand of 35,343 VA. The panel serves various loads including water heaters, motors, receptacles, and lighting circuits for the concessions building, dugouts, restrooms, scoreboard, and exterior lighting. Technical specifications detail conductor sizes, circuit breaker ratings, and grounding requirements throughout the facility.

View the file

Other files

File Type Posted
C106_R1_AD1.pdf PDF
01920041_Final_Spec_Manual_12_17_2024.pdf PDF
ADDENDUM_3_Complete.pdf PDF
ADDENDUM_1_complete.pdf PDF
E101_R1_AD2___CONCESSIONS___DUGOUT_BUILDINGS_.pdf PDF
U502_R1_AD1.pdf PDF
Bid Tabulation and Scoring Form.pdf PDF
Notice of Advertisement RMS Combo Field.docx DOCX document
A501_R1_AD1.pdf PDF
Contract Affidavit A.pdf PDF
C502_R1_AD1.pdf PDF
Bid Bond General Contractor.doc DOC document
C207_R1_AD1.pdf PDF
GC Compensation Proposal Form.doc DOC document
01920041_Final_BidSet_Plans_12_17_2024.pdf PDF
Payment Bond GC.doc DOC document
Addendum 04_Complete.pdf PDF
U101_R1_AD1.pdf PDF
U101_R2_AD2.pdf PDF
Consent to Release Info (01_2014_GKM).doc DOC document
E002_R1_AD2___LIGHTING_FIXTURE___MECHANICAL_E.pdf PDF
AffidavitOfNoncollusion_Offeror_(01_2014_GKM).doc DOC document
C505_R1_AD1.pdf PDF
ADDENDUM_2_complete.pdf PDF
RFP for General Contractor.docx DOCX document
Standard Form Fixed Price Contract.pdf PDF
C102_R1_AD1.pdf PDF
U502_R2_AD2.pdf PDF
Immigration and Security Form revised.pdf PDF
Performance Bond GC.doc DOC document
C104_R1_AD1.pdf PDF
C105_R1_AD1.pdf PDF
C107_R1_AD1.pdf PDF
E003_R1_AD2___ELECTRICAL_SITE_PLAN.pdf PDF
GC Compensation Proposal Form.doc DOC document
Consent to Release Info (01_2014_GKM).doc DOC document
Performance Bond GC.doc DOC document
Payment Bond GC.doc DOC document
RFP for General Contractor.docx DOCX document
Notice of Advertisement RMS Combo Field.docx DOCX document
Immigration and Security Form revised.pdf PDF
Standard Form Fixed Price Contract.pdf PDF
Bid Bond General Contractor.doc DOC document
AffidavitOfNoncollusion_Offeror_(01_2014_GKM).doc DOC document
01920041_Final_BidSet_Plans_12_17_2024.pdf PDF
Contract Affidavit A.pdf PDF
01920041_Final_Spec_Manual_12_17_2024.pdf PDF
Show all 47

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

RACEWAY CONCEALED IN CEILING, WALL, OR BELOW FLOOR. HASH MARKS INDICATE

QUANTITY OF CABLES OR CURRENT CARRYING CONDUCTORS. NO MARKS INDICATES

2 #12 AWG COPPER CONDUCTORS. USE #10 AWG FOR 120V CIRCUITS EXCEEDING 100

FT IN LENGTH AND 277V CIRCUITS EXCEEDING 230 FT. ALL RACEWAYS SHALL

CONTAIN ONE EQUIPMENT GROUNDING CONDUCTOR, SIZED PER NEC. ISOLATED

GROUND RECEPTACLE RACEWAYS SHALL CONTAIN AN ADDITIONAL ISOLATED

GROUNDING CONDUCTOR. REFER TO PANEL SCHEDULES FOR CONDUIT AND

CONDUCTOR SIZES. ARROW INDICATES HOMERUN TO PANEL-CIRCUIT.

RACEWAY EXPOSED ON STRUCTURE, WITH MARKS AS ABOVE. PAINT TO MATCH

STRUCTURE.

RACEWAY INSTALLED BELOW SLAB, WITH MARKS AS ABOVE.

RACEWAY INSTALLED BELOW GRADE WITH MARKS AS ABOVE.

EMERGENCY POWER SYSTEMS RACEWAY CONCEALED IN CEILING, WALL, OR BELOW

FLOOR, WITH MARKS AS ABOVE. INSTALLATION OF EMERGENCY POWER SYSTEMS

SHALL COMPLY WITH NFPA 110 AND NFPA 70, SPECIFICALLY ARTICLE 700.

EMERGENCY POWER SYSTEMS RACEWAY EXPOSED ON STRUCTURE, WITH MARKS

AS ABOVE. PAINT RACEWAY TO MATCH STRUCTURE. INSTALLATION OF EMERGENCY

POWER SYSTEMS SHALL COMPLY WITH NFPA 110 AND NFPA 70, SPECIFICALLY

ARTICLE 700.

20A, 125V DUPLEX TAMPER-RESISTANT TYPE RECEPTACLE MOUNTED 18" AFF, OR AS

NOTED. WP DENOTES WATER RESISTANT DEVICE WITH GASKETTED

WEATHERPROOF CAST METAL WHILE-IN-USE COVER. GFI DENOTES GROUND FAULT

CIRCUIT INTERRUPTING TYPE.

20A, 125V DUPLEX TAMPER-RESISTANT TYPE RECEPTACLE MOUNTED ABOVE

COUNTERTOP BACKSPLASH. COORDINATE EXACT LOCATION WITH MILLWORK

INSTALLER. 46" AFF, OR AS NOTED. MARKS AS ABOVE.

20A, 125V ISOLATED GROUND DUPLEX TAMPER-RESISTANT RECEPTACLE MOUNTED

18" AFF, OR AS NOTED. MARKS AS ABOVE.

20A, 125V QUADRUPLEX TAMPER-RESISTANT TYPE RECEPTACLE MOUNTED 18" AFF,

OR AS NOTED.

20A, 125V QUADRUPLEX ISOLATED GROUND TAMPER-RESISTANT TYPE RECEPTACLE

MOUNTED 18" AFF, OR AS NOTED.

SPECIAL RECEPTACLE, FLUSH MOUNTED 18" AFF, OR AS NOTED. PROVIDE NEMA TYPE

RECEPTACLE AS NOTED, UNLESS OTHERWISE REQUIRED BY EQUIPMENT.

20A, 125V SINGLE RECEPTACLE INSTALLED 96" ABOVE FINISHED FLOOR.

20A, 125V DUPLEX TAMPER-RESISTANT RECEPTACLE INSTALLED IN SINGLE SERVICE

FLOOR BOX WITH HINGED COVER.

20A, 125V ISOLATED GROUND DUPLEX TAMPER-RESISTANT RECEPTACLE INSTALLED

IN MULTI-SERVICE FLOOR BOX. INSTALL IN COMMON BOX WITH TELECOM/DATA

AND/OR AV OUTLETS SHOWN AT THE SAME LOCATION.

20A, 125V QUADRUPLEX TAMPER-RESISTANT RECEPTACLE INSTALLED IN SINGLE

SERVICE FLOOR BOX WITH HINGED COVER.

20A, 125V QUADRUPLEX ISOLATED GROUND TAMPER-RESISTANT RECEPTACLE

INSTALLED IN MULTI-SERVICE FLOOR BOX. INSTALL IN COMMON BOX WITH

TELECOM/DATA AND/OR AV OUTLETS SHOWN AT THE SAME LOCATION.

SPECIAL RECEPTACLE, FLUSH MOUNTED IN FLOOR BOX. PROVIDE NEMA TYPE

RECEPTACLE AS NOTED, UNLESS OTHERWISE REQUIRED BY EQUIPMENT.

WALL MOUNTED (LEFT), CEILING MOUNTED (RIGHT) JUNCTION BOX.

FLOOR MOUNTED JUNCTION BOX, CAST IRON WITH WEATHERPROOF COVER. FOR

INSTALLATION IN KITCHEN AREAS, REFER TO DETAIL - KITCHEN FLOOR RECEPTACLE.

FLOOR MOUNTED OUTLET IN FS DEVICE BOX WITH GASKETTED COVER. IN KITCHEN

AREAS, REFER TO DETAIL - KITCHEN FLOOR RECEPTACLE.

DUPLEX RECEPTACLE FLUSH MOUNTED IN SUSPENDED CEILING. UTILITIZE T-GRID

BOX HANGER SUPPORTED FROM STRUCTURE. MAKE FINAL CONNECTION WITH

FLEXIBLE WIRING METHOD TO J-BOX AT STRUCTURE.

DUPLEX ISOLATED GROUND RECEPTACLE FLUSH MOUNTED IN SUSPENDED CEILING.

UTILITIZE T-GRID BOX HANGER SUPPORTED FROM STRUCTURE. MAKE FINAL

CONNECTION WITH FLEXIBLE WIRING METHOD TO J-BOX AT STRUCTURE.

DUPLEX RECEPTACLE SUSPENDED FROM ABOVE. REFER TO POWER DROP DETAIL.

DUPLEX ISOLATED GROUND RECEPTACLE SUSPENDED FROM ABOVE. REFER TO

POWER DROP DETAIL.

TELE-POWER POLE, WITH SEPARATE COMPARTMENTS FOR COMMUNICATIONS AND

POWER CABLING. REFER TO SPECIFICATIONS.

CEILING MOUNTED (LEFT) AND WALL WALL MOUNTED (RIGHT) EXIT SIGNS. SHADING

INDICATES LIT FACES. SIDE TRIANGLES INDICATE EMERGENCY LAMP HEADS.

ARROWS INDICATE CHEVRONS TO BE ILLUMINATED.

LIGHTING FIXTURE, TYPE AS INDICATED BY CAPITAL LETTER. REFER TO LIGHTING

FIXTURE SCHEDULE. LOWER CASE LETTER DESIGNATION INDICATES SWITCHING

OR CONTROL ZONE. NUMERIC DESIGNATION INDICATES CIRCUIT.

EMERGENCY LIGHTING FIXTURE WITH NOTATION AS ABOVE.

SUSPENDED OR SURFACE MOUNTED STRIP OR LINEAR LIGHTING FIXTURE WITH

NOTATION AS ABOVE. HALF SHADED IS AN EMERGENCY.

RECESSED DOWNLIGHT LIGHTING FIXTURE WITH NOTATION AS ABOVE.

WALL BATTERY PACK EMERGENCY LIGHTING FIXTURE WITH DESIGNATIONS AS ABOVE.

20A, 120/277V SPST LIGHTING TOGGLE SWITCH. '2' DENOTES DPST, '3' DENOTES 3-

WAY, '4' DENOTES 4-WAY; 'K' DENOTES KEY OPERATED SWITCH; 'MC' DENOTES

MOMENTARY CONTACT; 'HOA' DENOTES HAND/OFF/AUTO SWITCH; 'WP' DENOTES

WATERPROOF COVER PLATE.

DISCONNECT SWITCH, NON-FUSED UNLESS OTHERWISE NOTED. NEMA TYPE

PER ENVIRONMENT. AMPERE RATING PER CONNECTION SCHEDULE.

DISCONNECT SWITCH, FUSED UNLESS OTHERWISE NOTED. NEMA TYPE PER

ENVIRONMENT. AMPERE RATING PER CONNECTION SCHEDULE.

MAGNETIC MOTOR STARTER, FURNISHED BY DIVISION 23, INSTALLATION AND POWER

WIRING BY DIVISION 26.

MOTOR RATED SWITCH (MANUAL MOTOR STARTER WITHOUT OVERLOADS) IN A NEMA

250 TYPE 1 ENCLOSURE. SINGLE POLE, 16A RATED, UNLESS OTHERWISE NOTED.

EMERGENCY LIGHTING INVERTER, WALL MOUNTED UNLESS OTHERWISE NOTED. TEXT

INDICATES OUTPUT POWER CAPACITY

EMERGENCY RECESSED DOWNLIGHT LIGHTING FIXTURE WITH NOTATION AS ABOVE.

20A, 125V DUPLEX RECEPTACLE (LEFT) QUAD RECEPTACLE (RIGHT) INSTALLED IN

POKE-THRU DEVICE.

20A, 125V DUPLEX ISOLATED GROUND RECEPTACLE (LEFT) AND QUAD ISOLATED

GROUND RECEPTACLE (RIGHT) INSTALLED IN POKE-THRU DEVICE.

20A, 125V QUADRUPLEX TAMPER-RESISTANT TYPE RECEPTACLE MOUNTED ABOVE

COUNTERTOP BACKSPLASH. COORDINATE EXACT LOCATION WITH MILLWORK

INSTALLER. 46" AFF, OR AS NOTED. MARKS AS ABOVE.

J-HOOK SYSTEM FOR SUPPORT OF COMMUNICATIONS & PROTECTION CONDUCTORS.

SEE SPECIFICATIONS.

MECHANICAL CONTROL DEVICES (SENSOR, THERMOSTAT, WALL SWITCH, INTERVAL

TIMER, NIGHT SETBACK, HUMIDISTAT, CO2 SENSOR, EMERGENCY STOP) TO BE

INSTALLED BY DIVISION 23. ELECTRICAL CONTRACTOR SHALL PROVIDE A FLUSH WALL

MOUNTED OUTLET BOX WITH CONDUIT STUBBED OUT 6" ABOVE TYPE 2 CEILING WITH

BUSHED OPENING AT LOCATION SHOWN. WHERE MULTIPLE DEVICES ARE SHOWN

WITHIN A SINGLE RECTANGLE, MULTIPLE DEVICES WILL BE INSTALLED IN A SINGLE

OUTLET BOX LOCATION. WALL SWITCH SHALL BE PROVIDED AND INSTALLED BY

ELECTRICAL CONTRACTOR. VERIFY BOX REQUIREMENTS AND MOUNTING HEIGHTS

WITH DIVISION 23 AND/OR CONTROLS CONTRACTOR PRIOR TO INSTALLATION.

LA-2

WP/GFI

GFI

SP

JJ

J

P

A a

M

720W

JJJ

ELECTRICAL SYMBOLS LEGEND

note: all symbols do not necessarily appear on drawings

DRY TYPE VENTILATED TRANSFORMER.

480Y/277 VAC PANELBOARD (LEFT) AND 208Y/120 VAC PANELBOARD (RIGHT).

MOTOR; HORSEPOWER RATING AS INDICATED; F INDICATES HORSEPOWER RATING

LESS THAN 1/10.

C CONTACTOR IN SURFACE WALL MOUNTED ENCLOSURE.

S T

IW

HN

EC

H

PP

L

H

C

T/S

T

CEILING MOUNTED OCCUPANCY SENSOR, DUAL TECHNOLOGY TYPE. 'L' DENOTES LARGE

AREA; 'S' DENOTES SMALL AREA COVERAGE. SUBSCRIPT "D" DENOTES DIGITAL SENSOR

FOR OPERATION WITH DIGITAL ROOM CONTROLLER.

CEILING MOUNTED OCCUPANCY SENSOR, PASSIVE INFRARED TYPE. 'L' DENOTES LARGE

AREA; 'S' DENOTES SMALL AREA; 'H' DENOTES HIGH BAY COVERAGE. SUBSCRIPT "D"

DENOTES DIGITAL SENSOR FOR OPERATION WITH DIGITAL ROOM CONTROLLER.

CEILING MOUNTED OCCUPANCY SENSOR, ULTRASONIC TYPE. 'L' DENOTES LARGE

AREA; 'S' DENOTES SMALL AREA; 'H' DENOTES HALLWAY COVERAGE. SUBSCRIPT "D"

DENOTES DIGITAL SENSOR FOR OPERATION WITH DIGITAL ROOM CONTROLLER.

DUAL TECHNOLOGY WALL MOUNTED OCCUPANCY SENSOR, LOCATED AT 10'0" AFF, OR

6" BELOW CEILING. SUBSCRIPT "D" DENOTES DIGITAL SENSOR FOR OPERATION WITH

DIGITAL ROOM CONTROLLER.

PASSIVE INFRARED WALL MOUNTED OCCUPANCY SENSOR, LOCATED AT 10'0" AFF, OR

6" BELOW CEILING. SUBSCRIPT "D" DENOTES DIGITAL SENSOR FOR OPERATION WITH

DIGITAL ROOM CONTROLLER.

LIGHTING CONTROL POWER PACK OR SLAVE PACK, WITH 24V CABLING TO SENSOR

DEVICES IN SAME ZONE/SPACE. POWER PACKS INSTALLED IN CORRIDORS, HALLWAYS,

PASSAGES, LOBBIES, STAIRS AND COMMONS AREAS SHALL INCLUDE AN INPUT

CONTACT FOR FIRE ALARM SYSTEM OVERRIDE OF MOTION SENSORS.

PHOTOCELL CONTROL, WITH CABLING TO TIME SWITCH OR CONTACTOR WHEN USED

TO INDIRECTLY CONTROL LIGHTING CIRCUIT(S).

LIGHTING CONTACTOR INSTALLED IN SURFACE WALL MOUNTED ENCLOSURE 12"

BELOW CEILING, OR AS NOTED.

WALL SWITCH OCCUPANCY SENSOR, 120V/277V, MOUNTED AT 48" AFF. TEXT DENOTES

TYPE: P=INFRARED, T=DUAL TECHNOLOGY, D=DIMMING, 2R=DUAL RELAY.

DIGITAL LIGHTING CONTROL SYSTEM ROOM CONTROLLER WITH UTP CABLING TO

OTHER COMPONENTS LOCATED IN SAME SPACE.

LIGHTING CONTROL TIME SWITCH PER SPECIFICATIONS INSTALLED 60" AFF, U.O.N.

LIGHTING CONTROL SYMBOLS LEGEND

note: all symbols do not necessarily appear on drawings

RC

SINGLE GANG, DIGITAL WALL SWITCH FOR OPERATION WITH DIGITAL LIGHTING SYSTEM

ROOM CONTROLLER. REFER TO LIGHTING SCHEMATICS FOR BUTTON FUNCTIONS. 2-

BUTTON: ON/OFF; 4-BUTTON: ON/OFF/RAISE/LOWER; 5-BUTTON: SCENE OR PRESET

SELECTION; 6-BUTTON: COLOR TEMPERATURE SELECTION; PROGRAMMABLE TOUCH-

SCREEN CONTROLLER.

DL DAYLIGHT SENSOR FOR AUTOMATIC DIMMING CONTROL.

D

D

D

D

D

5 6

ER

EMERGENCY LIGHTING RELAY, FOR OVERRIDE OF LOCAL LIGHTING CONTROLS ON

LOSS OF NORMAL POWER. SHUNT DEVICES SHALL BE UL 924 LISTED. TRANSFER

DEVICES SHALL BE UL 1008 LISTED.

PC

TS

LOW-VOLTAGE MOMENTARY CONTACT SWITCH (LEFT) AND LOW-VOLTAGE DIMMER

(RIGHT) FOR MANUAL ON AND OFF CONTROL OR DIMMING CONTROL.

0-10V SLIDE DIMMER WITH PUSH BUTTON FOR MANUAL ON AND DIMMING CONTROL.

LIGHTING CONTROL NOTE: AT EACH LOCATION WHERE DIMMING CONTROLS ARE INDICATED, PROVIDE 0-10V CLASS 2 CABLING FROM CONTROL DEVICE TO EACH LIGHTING FIXTURE IN THE SPACE/ZONE.

ELEC

TEST WELL -

12" x 12" x 12" PRECAST

HANDHOLE PER SECTIONS

26 05 26 AND 26 05 33.

(3) 3/4" x 10' LONG COPPER

CLAD STEEL GROUND RODS

FOR MAIN SERVICE GROUNDING

ELECTRODE ASSEMBLY. REFER

TO GROUNDING SCHEMATIC.

#3/0 AWG CU

IN 3/4" CONDUIT

LBB

10'

10'

10'

PAD MTD UTILITY

CO. TRANSFORMER

M

AVAILABLE FAULT CURRENT:

8,617 AMPS

CALCUALTED ON

12/17/2024

REFER TO NOTE 4.

SPD

G

ISBB

FINISHED

FLOOR

2.5" CONDUITS TO PULLBOXES.

REFER TO SITE PLAN.

FUTURE FIELD

LIGHTING

CONTACTOR

CABINET

ELECTRICAL RISER DIAGRAM NOTES:

1. REFER TO PANELBOARD SCHEDULES FOR CONDUIT AND CONDUCTOR SIZES.

2. REFER TO SITE PLAN AND 1/8" SCALE DRAWINGS FOR LOCATIONS OF PANELS.

3. SURGE PROTECTIVE DEVICE (SPD) PER SECTION 262413 AND/OR 262416. SPD SHALL BE

INSTALLED BY AND SHIPPED FROM THE PANELBOARD AND/OR SWITCHBOARD

MANUFACTURER'S FACTORY.

4. PER NEC ARTICLE 110.24, PROVIDE BLACK PHENOLIC NAMEPLATE WITH WHITE

LETTERING WITH MAXIMUM AVAILABLE FAULT CURRENT AND THE DATE IT WAS

CALCULATED AND PERMANENTLY AFFIX TO SERVICE ENTRANCE EQUIPMENT. REFER

TO SPECIFICATION SECTION 260553 FOR DETAILS.

DRAWING NUMBER

REVISIONS

COPYRIGHT 2024 BY SOUTHERN A&E, LLC. ALL RIGHTS RESERVED.

THIS DOCUMENT IS THE PROPERTY OF SOUTHERN A&E, LLC AND SHALL

NOT BE COPIED OR REPRODUCED IN WHOLE OR IN PART WITHOUT

EXPRESSED WRITTEN CONSENT FROM SOUTHERN A&E, LLC.

12-17-2024

BID PACKAGE BP-1

SA&E PROJECT NUMBER

ORIGINAL SHEET SIZE: ARCH E1 (30" X 42")

A

12" GRIDS 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19

B

C

D

E

F

G

H

I

J

K

L

M

N

ROSSVILLE MIDDLE SCHOOL

NEW FIELD AND CONCESSIONS FOR:

WALKER COUNTY SCHOOLS

301 N CHEROKEE ST, LAFAYETTE, GA 30728

316 BULLDOG TRAIL, ROSSVILLE, GA 30741

746-0206

01-920-041

ISSUED FOR CONSTRUCTION

STATE BOARD OF REGISTRATION

FOR PROFESSIONAL ENGINEERS AND

LAND SURVEYORS

SOUTHERN A & E, LLC

ENGINEER FIRM

LICENSE NO: PEF003374

EXP. DATE - 06/30/2026

E001

ELECTRICAL LEGENDS

NO SCALEE001

2 POWER RISER DIAGRAM

Water Heater 8320 VA 100.00% 8320 VA

Other 0 VA 0.00% 0 VA

Nonseasonal Motor 2845 VA 100.00% 2845 VA

Heating/Cooling 0 VA 0.00% 0 VA

Heating 0 VA 0.00% 0 VA

Cooling 0 VA 0.00% 0 VA Total Est. Demand Current: 98 A

Motor 1261 VA 125.00% 1576 VA Total Est. Demand: 35343 VA

Receptacle 10060 VA 99.70% 10030 VA Total Conn. Load: 34824 VA

Lighting 938 VA 125.00% 1172 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Apparent Load [VA] 12293 12037 10494

65 66

63 64

61 62

59 60

57 58

55 56

53 54

51 52

49 50

47 48

45 46

43 LIFT STATION REC 1/2"C,1#12,#12N,#12G 20 180 44

41 841 0 20 -- SPARE 42

39 841 0 20 -- SPARE 40

LIFT STATION 3/4"C,3#8,#10G 15

841 0 20 -- SPARE 38

35 EF-3 1/2"C,1#12,#12N,#12G 15 528 1000 36

33 1000 1000

20 1/2"C,2#12,#12G EH RESTROOM 102

EH RESTROOM 103 1/2"C,2#12,#12G 20

1000 2000 32

29 2000 2000

25 1/2"C,2#10,#10G EH STORAGE 105

EH CONCESSIONS 101 1/2"C,2#10,#10G 25

2000 4160 28

25 REC SCORER'S TABLE 3/4"PVC,1#10,#10N... 20 360 4160

50 1/2"C,2#8,#10G EWH

23 SCOREBOARD 1/2"C,1#8,#8N,#8G 20 1200 554 20 1/2"C,1#12,#12N,#12G LIGHTS CONCESS BLDG 24

21 REC SCOREBOARD 1/2"C,1#8,#8N,#8G 20 180 540 20 1/2"C,1#10,#10N,#10G REC DUGOUT 22

19 EXTERIOR BLDG LTS 1/2"C,1#12,#12N,#12G 20 192 180 20 1/2"C,1#12,#12N,#12G REC CONCESSIONS 101 20

17 EXTERIOR BLDG LTS 1/2"C,1#12,#12N,#12G 20 192 180 20 1/2"C,1#12,#12N,#12G REC CONCESSIONS 101 18

15 REC DUGOUT 1/2"C,1#10,#10N,#10G 20 540 180 20 1/2"C,1#12,#12N,#12G REC CONCESSIONS 101 16

13 REC RESTROOMS 1/2"C,1#12,#12N,#12G 20 360 180 20 1/2"C,1#12,#12N,#12G REC CONCESSIONS 101 14

11 REC EQ STORAGE 105 1/2"C,1#12,#12N,#12G 20 360 180 20 1/2"C,1#12,#12N,#12G REC CONCESSIONS 101 12

9 REC CONCESSIONS 101 1/2"C,1#12,#12N,#12G 20 180 180 20 1/2"C,1#12,#12N,#12G REC CONCESSIONS 101 10

7 REFRIGERATOR 1/2"C,1#12,#12N,#12G GF 20 1200 1100 8

5 REC EXTERIOR 1/2"C,1#12,#12N,#12G 20 360 1100

20 1/2"C,2#10,#10G ICE MACHINE

3 REC EXTERIOR 1/2"C,1#12,#12N,#12G 20 180 1056 15 1/2"C,1#12,#12N,#12G EF-1,2 4

1 REC EXTERIOR 1/2"C,1#12,#12N,#12G 20 360 180 20 1/2"C,1#12,#12N,#12G REC CONCESSIONS 101 2

Ckt Description Conduit & Wire N Trip A B C Trip N Conduit & Wire Ckt Description

GF = GFCI AF = AFCI ST = SHUNT TRIP HL = HANDLE LOCK X = CIRCUIT AND OCPD EXISTING TO REMAIN

Notes (Column N):

Feed-Thru Lugs: No Supply From: UTILITY XFRMR

Mounting: Surface Ground Bus: Yes Feeder: 3"C,3-350kcmil,350kcmil N,#2G

Enclosure: Type 1 Neutral Bus: Yes/100.00% Mains: 300 A MCB

Location: ELEC 104 Distribution System: 208/120V 3P 4W Wye AIC: 10,000

Branch Panel: LBB

# Doc # Date

1 AD2 1/15/25

erik

FRANK - SIGNED

Sheets
E001 - ELECTRICAL LEGENDS

File details come from the government source that posted it. Updated .