E001_R1_AD2___ELECTRICAL_LEGENDS.pdf
PDF 2 MB Posted
- Solicitation number
- PE-55462-NONST-2025-000000010
- Issued by
- Wilcox County, Georgia
About this file
This file contains electrical and lighting control legend diagrams for the Rossville Middle School Athletic Field and Concessions project in Walker County, Georgia. The document provides detailed electrical symbols and specifications, including raceway types, receptacle configurations, lighting fixtures, disconnect switches, and control systems. A power riser diagram shows the electrical distribution from the utility transformer to panel LBB, with fault current calculations dated December 17, 2024.
The document includes a comprehensive electrical panel schedule for Panel LBB showing connected loads of 34,824 VA with an estimated demand of 35,343 VA. The panel serves various loads including water heaters, motors, receptacles, and lighting circuits for the concessions building, dugouts, restrooms, scoreboard, and exterior lighting. Technical specifications detail conductor sizes, circuit breaker ratings, and grounding requirements throughout the facility.
View the file
Other files
Show all 47
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
RACEWAY CONCEALED IN CEILING, WALL, OR BELOW FLOOR. HASH MARKS INDICATE
QUANTITY OF CABLES OR CURRENT CARRYING CONDUCTORS. NO MARKS INDICATES
2 #12 AWG COPPER CONDUCTORS. USE #10 AWG FOR 120V CIRCUITS EXCEEDING 100
FT IN LENGTH AND 277V CIRCUITS EXCEEDING 230 FT. ALL RACEWAYS SHALL
CONTAIN ONE EQUIPMENT GROUNDING CONDUCTOR, SIZED PER NEC. ISOLATED
GROUND RECEPTACLE RACEWAYS SHALL CONTAIN AN ADDITIONAL ISOLATED
GROUNDING CONDUCTOR. REFER TO PANEL SCHEDULES FOR CONDUIT AND
CONDUCTOR SIZES. ARROW INDICATES HOMERUN TO PANEL-CIRCUIT.
RACEWAY EXPOSED ON STRUCTURE, WITH MARKS AS ABOVE. PAINT TO MATCH
STRUCTURE.
RACEWAY INSTALLED BELOW SLAB, WITH MARKS AS ABOVE.
RACEWAY INSTALLED BELOW GRADE WITH MARKS AS ABOVE.
EMERGENCY POWER SYSTEMS RACEWAY CONCEALED IN CEILING, WALL, OR BELOW
FLOOR, WITH MARKS AS ABOVE. INSTALLATION OF EMERGENCY POWER SYSTEMS
SHALL COMPLY WITH NFPA 110 AND NFPA 70, SPECIFICALLY ARTICLE 700.
EMERGENCY POWER SYSTEMS RACEWAY EXPOSED ON STRUCTURE, WITH MARKS
AS ABOVE. PAINT RACEWAY TO MATCH STRUCTURE. INSTALLATION OF EMERGENCY
POWER SYSTEMS SHALL COMPLY WITH NFPA 110 AND NFPA 70, SPECIFICALLY
ARTICLE 700.
20A, 125V DUPLEX TAMPER-RESISTANT TYPE RECEPTACLE MOUNTED 18" AFF, OR AS
NOTED. WP DENOTES WATER RESISTANT DEVICE WITH GASKETTED
WEATHERPROOF CAST METAL WHILE-IN-USE COVER. GFI DENOTES GROUND FAULT
CIRCUIT INTERRUPTING TYPE.
20A, 125V DUPLEX TAMPER-RESISTANT TYPE RECEPTACLE MOUNTED ABOVE
COUNTERTOP BACKSPLASH. COORDINATE EXACT LOCATION WITH MILLWORK
INSTALLER. 46" AFF, OR AS NOTED. MARKS AS ABOVE.
20A, 125V ISOLATED GROUND DUPLEX TAMPER-RESISTANT RECEPTACLE MOUNTED
18" AFF, OR AS NOTED. MARKS AS ABOVE.
20A, 125V QUADRUPLEX TAMPER-RESISTANT TYPE RECEPTACLE MOUNTED 18" AFF,
OR AS NOTED.
20A, 125V QUADRUPLEX ISOLATED GROUND TAMPER-RESISTANT TYPE RECEPTACLE
MOUNTED 18" AFF, OR AS NOTED.
SPECIAL RECEPTACLE, FLUSH MOUNTED 18" AFF, OR AS NOTED. PROVIDE NEMA TYPE
RECEPTACLE AS NOTED, UNLESS OTHERWISE REQUIRED BY EQUIPMENT.
20A, 125V SINGLE RECEPTACLE INSTALLED 96" ABOVE FINISHED FLOOR.
20A, 125V DUPLEX TAMPER-RESISTANT RECEPTACLE INSTALLED IN SINGLE SERVICE
FLOOR BOX WITH HINGED COVER.
20A, 125V ISOLATED GROUND DUPLEX TAMPER-RESISTANT RECEPTACLE INSTALLED
IN MULTI-SERVICE FLOOR BOX. INSTALL IN COMMON BOX WITH TELECOM/DATA
AND/OR AV OUTLETS SHOWN AT THE SAME LOCATION.
20A, 125V QUADRUPLEX TAMPER-RESISTANT RECEPTACLE INSTALLED IN SINGLE
SERVICE FLOOR BOX WITH HINGED COVER.
20A, 125V QUADRUPLEX ISOLATED GROUND TAMPER-RESISTANT RECEPTACLE
INSTALLED IN MULTI-SERVICE FLOOR BOX. INSTALL IN COMMON BOX WITH
TELECOM/DATA AND/OR AV OUTLETS SHOWN AT THE SAME LOCATION.
SPECIAL RECEPTACLE, FLUSH MOUNTED IN FLOOR BOX. PROVIDE NEMA TYPE
RECEPTACLE AS NOTED, UNLESS OTHERWISE REQUIRED BY EQUIPMENT.
WALL MOUNTED (LEFT), CEILING MOUNTED (RIGHT) JUNCTION BOX.
FLOOR MOUNTED JUNCTION BOX, CAST IRON WITH WEATHERPROOF COVER. FOR
INSTALLATION IN KITCHEN AREAS, REFER TO DETAIL - KITCHEN FLOOR RECEPTACLE.
FLOOR MOUNTED OUTLET IN FS DEVICE BOX WITH GASKETTED COVER. IN KITCHEN
AREAS, REFER TO DETAIL - KITCHEN FLOOR RECEPTACLE.
DUPLEX RECEPTACLE FLUSH MOUNTED IN SUSPENDED CEILING. UTILITIZE T-GRID
BOX HANGER SUPPORTED FROM STRUCTURE. MAKE FINAL CONNECTION WITH
FLEXIBLE WIRING METHOD TO J-BOX AT STRUCTURE.
DUPLEX ISOLATED GROUND RECEPTACLE FLUSH MOUNTED IN SUSPENDED CEILING.
UTILITIZE T-GRID BOX HANGER SUPPORTED FROM STRUCTURE. MAKE FINAL
CONNECTION WITH FLEXIBLE WIRING METHOD TO J-BOX AT STRUCTURE.
DUPLEX RECEPTACLE SUSPENDED FROM ABOVE. REFER TO POWER DROP DETAIL.
DUPLEX ISOLATED GROUND RECEPTACLE SUSPENDED FROM ABOVE. REFER TO
POWER DROP DETAIL.
TELE-POWER POLE, WITH SEPARATE COMPARTMENTS FOR COMMUNICATIONS AND
POWER CABLING. REFER TO SPECIFICATIONS.
CEILING MOUNTED (LEFT) AND WALL WALL MOUNTED (RIGHT) EXIT SIGNS. SHADING
INDICATES LIT FACES. SIDE TRIANGLES INDICATE EMERGENCY LAMP HEADS.
ARROWS INDICATE CHEVRONS TO BE ILLUMINATED.
LIGHTING FIXTURE, TYPE AS INDICATED BY CAPITAL LETTER. REFER TO LIGHTING
FIXTURE SCHEDULE. LOWER CASE LETTER DESIGNATION INDICATES SWITCHING
OR CONTROL ZONE. NUMERIC DESIGNATION INDICATES CIRCUIT.
EMERGENCY LIGHTING FIXTURE WITH NOTATION AS ABOVE.
SUSPENDED OR SURFACE MOUNTED STRIP OR LINEAR LIGHTING FIXTURE WITH
NOTATION AS ABOVE. HALF SHADED IS AN EMERGENCY.
RECESSED DOWNLIGHT LIGHTING FIXTURE WITH NOTATION AS ABOVE.
WALL BATTERY PACK EMERGENCY LIGHTING FIXTURE WITH DESIGNATIONS AS ABOVE.
20A, 120/277V SPST LIGHTING TOGGLE SWITCH. '2' DENOTES DPST, '3' DENOTES 3-
WAY, '4' DENOTES 4-WAY; 'K' DENOTES KEY OPERATED SWITCH; 'MC' DENOTES
MOMENTARY CONTACT; 'HOA' DENOTES HAND/OFF/AUTO SWITCH; 'WP' DENOTES
WATERPROOF COVER PLATE.
DISCONNECT SWITCH, NON-FUSED UNLESS OTHERWISE NOTED. NEMA TYPE
PER ENVIRONMENT. AMPERE RATING PER CONNECTION SCHEDULE.
DISCONNECT SWITCH, FUSED UNLESS OTHERWISE NOTED. NEMA TYPE PER
ENVIRONMENT. AMPERE RATING PER CONNECTION SCHEDULE.
MAGNETIC MOTOR STARTER, FURNISHED BY DIVISION 23, INSTALLATION AND POWER
WIRING BY DIVISION 26.
MOTOR RATED SWITCH (MANUAL MOTOR STARTER WITHOUT OVERLOADS) IN A NEMA
250 TYPE 1 ENCLOSURE. SINGLE POLE, 16A RATED, UNLESS OTHERWISE NOTED.
EMERGENCY LIGHTING INVERTER, WALL MOUNTED UNLESS OTHERWISE NOTED. TEXT
INDICATES OUTPUT POWER CAPACITY
EMERGENCY RECESSED DOWNLIGHT LIGHTING FIXTURE WITH NOTATION AS ABOVE.
20A, 125V DUPLEX RECEPTACLE (LEFT) QUAD RECEPTACLE (RIGHT) INSTALLED IN
POKE-THRU DEVICE.
20A, 125V DUPLEX ISOLATED GROUND RECEPTACLE (LEFT) AND QUAD ISOLATED
GROUND RECEPTACLE (RIGHT) INSTALLED IN POKE-THRU DEVICE.
20A, 125V QUADRUPLEX TAMPER-RESISTANT TYPE RECEPTACLE MOUNTED ABOVE
COUNTERTOP BACKSPLASH. COORDINATE EXACT LOCATION WITH MILLWORK
INSTALLER. 46" AFF, OR AS NOTED. MARKS AS ABOVE.
J-HOOK SYSTEM FOR SUPPORT OF COMMUNICATIONS & PROTECTION CONDUCTORS.
SEE SPECIFICATIONS.
MECHANICAL CONTROL DEVICES (SENSOR, THERMOSTAT, WALL SWITCH, INTERVAL
TIMER, NIGHT SETBACK, HUMIDISTAT, CO2 SENSOR, EMERGENCY STOP) TO BE
INSTALLED BY DIVISION 23. ELECTRICAL CONTRACTOR SHALL PROVIDE A FLUSH WALL
MOUNTED OUTLET BOX WITH CONDUIT STUBBED OUT 6" ABOVE TYPE 2 CEILING WITH
BUSHED OPENING AT LOCATION SHOWN. WHERE MULTIPLE DEVICES ARE SHOWN
WITHIN A SINGLE RECTANGLE, MULTIPLE DEVICES WILL BE INSTALLED IN A SINGLE
OUTLET BOX LOCATION. WALL SWITCH SHALL BE PROVIDED AND INSTALLED BY
ELECTRICAL CONTRACTOR. VERIFY BOX REQUIREMENTS AND MOUNTING HEIGHTS
WITH DIVISION 23 AND/OR CONTROLS CONTRACTOR PRIOR TO INSTALLATION.
LA-2
WP/GFI
GFI
SP
JJ
J
P
A a
M
720W
JJJ
ELECTRICAL SYMBOLS LEGEND
note: all symbols do not necessarily appear on drawings
DRY TYPE VENTILATED TRANSFORMER.
480Y/277 VAC PANELBOARD (LEFT) AND 208Y/120 VAC PANELBOARD (RIGHT).
MOTOR; HORSEPOWER RATING AS INDICATED; F INDICATES HORSEPOWER RATING
LESS THAN 1/10.
C CONTACTOR IN SURFACE WALL MOUNTED ENCLOSURE.
S T
IW
HN
EC
H
PP
L
H
C
T/S
T
CEILING MOUNTED OCCUPANCY SENSOR, DUAL TECHNOLOGY TYPE. 'L' DENOTES LARGE
AREA; 'S' DENOTES SMALL AREA COVERAGE. SUBSCRIPT "D" DENOTES DIGITAL SENSOR
FOR OPERATION WITH DIGITAL ROOM CONTROLLER.
CEILING MOUNTED OCCUPANCY SENSOR, PASSIVE INFRARED TYPE. 'L' DENOTES LARGE
AREA; 'S' DENOTES SMALL AREA; 'H' DENOTES HIGH BAY COVERAGE. SUBSCRIPT "D"
DENOTES DIGITAL SENSOR FOR OPERATION WITH DIGITAL ROOM CONTROLLER.
CEILING MOUNTED OCCUPANCY SENSOR, ULTRASONIC TYPE. 'L' DENOTES LARGE
AREA; 'S' DENOTES SMALL AREA; 'H' DENOTES HALLWAY COVERAGE. SUBSCRIPT "D"
DENOTES DIGITAL SENSOR FOR OPERATION WITH DIGITAL ROOM CONTROLLER.
DUAL TECHNOLOGY WALL MOUNTED OCCUPANCY SENSOR, LOCATED AT 10'0" AFF, OR
6" BELOW CEILING. SUBSCRIPT "D" DENOTES DIGITAL SENSOR FOR OPERATION WITH
DIGITAL ROOM CONTROLLER.
PASSIVE INFRARED WALL MOUNTED OCCUPANCY SENSOR, LOCATED AT 10'0" AFF, OR
6" BELOW CEILING. SUBSCRIPT "D" DENOTES DIGITAL SENSOR FOR OPERATION WITH
DIGITAL ROOM CONTROLLER.
LIGHTING CONTROL POWER PACK OR SLAVE PACK, WITH 24V CABLING TO SENSOR
DEVICES IN SAME ZONE/SPACE. POWER PACKS INSTALLED IN CORRIDORS, HALLWAYS,
PASSAGES, LOBBIES, STAIRS AND COMMONS AREAS SHALL INCLUDE AN INPUT
CONTACT FOR FIRE ALARM SYSTEM OVERRIDE OF MOTION SENSORS.
PHOTOCELL CONTROL, WITH CABLING TO TIME SWITCH OR CONTACTOR WHEN USED
TO INDIRECTLY CONTROL LIGHTING CIRCUIT(S).
LIGHTING CONTACTOR INSTALLED IN SURFACE WALL MOUNTED ENCLOSURE 12"
BELOW CEILING, OR AS NOTED.
WALL SWITCH OCCUPANCY SENSOR, 120V/277V, MOUNTED AT 48" AFF. TEXT DENOTES
TYPE: P=INFRARED, T=DUAL TECHNOLOGY, D=DIMMING, 2R=DUAL RELAY.
DIGITAL LIGHTING CONTROL SYSTEM ROOM CONTROLLER WITH UTP CABLING TO
OTHER COMPONENTS LOCATED IN SAME SPACE.
LIGHTING CONTROL TIME SWITCH PER SPECIFICATIONS INSTALLED 60" AFF, U.O.N.
LIGHTING CONTROL SYMBOLS LEGEND
note: all symbols do not necessarily appear on drawings
RC
SINGLE GANG, DIGITAL WALL SWITCH FOR OPERATION WITH DIGITAL LIGHTING SYSTEM
ROOM CONTROLLER. REFER TO LIGHTING SCHEMATICS FOR BUTTON FUNCTIONS. 2-
BUTTON: ON/OFF; 4-BUTTON: ON/OFF/RAISE/LOWER; 5-BUTTON: SCENE OR PRESET
SELECTION; 6-BUTTON: COLOR TEMPERATURE SELECTION; PROGRAMMABLE TOUCH-
SCREEN CONTROLLER.
DL DAYLIGHT SENSOR FOR AUTOMATIC DIMMING CONTROL.
D
D
D
D
D
5 6
ER
EMERGENCY LIGHTING RELAY, FOR OVERRIDE OF LOCAL LIGHTING CONTROLS ON
LOSS OF NORMAL POWER. SHUNT DEVICES SHALL BE UL 924 LISTED. TRANSFER
DEVICES SHALL BE UL 1008 LISTED.
PC
TS
LOW-VOLTAGE MOMENTARY CONTACT SWITCH (LEFT) AND LOW-VOLTAGE DIMMER
(RIGHT) FOR MANUAL ON AND OFF CONTROL OR DIMMING CONTROL.
0-10V SLIDE DIMMER WITH PUSH BUTTON FOR MANUAL ON AND DIMMING CONTROL.
LIGHTING CONTROL NOTE: AT EACH LOCATION WHERE DIMMING CONTROLS ARE INDICATED, PROVIDE 0-10V CLASS 2 CABLING FROM CONTROL DEVICE TO EACH LIGHTING FIXTURE IN THE SPACE/ZONE.
ELEC
TEST WELL -
12" x 12" x 12" PRECAST
HANDHOLE PER SECTIONS
26 05 26 AND 26 05 33.
(3) 3/4" x 10' LONG COPPER
CLAD STEEL GROUND RODS
FOR MAIN SERVICE GROUNDING
ELECTRODE ASSEMBLY. REFER
TO GROUNDING SCHEMATIC.
#3/0 AWG CU
IN 3/4" CONDUIT
LBB
10'
10'
10'
PAD MTD UTILITY
CO. TRANSFORMER
M
AVAILABLE FAULT CURRENT:
8,617 AMPS
CALCUALTED ON
12/17/2024
REFER TO NOTE 4.
SPD
G
ISBB
FINISHED
FLOOR
2.5" CONDUITS TO PULLBOXES.
REFER TO SITE PLAN.
FUTURE FIELD
LIGHTING
CONTACTOR
CABINET
ELECTRICAL RISER DIAGRAM NOTES:
1. REFER TO PANELBOARD SCHEDULES FOR CONDUIT AND CONDUCTOR SIZES.
2. REFER TO SITE PLAN AND 1/8" SCALE DRAWINGS FOR LOCATIONS OF PANELS.
3. SURGE PROTECTIVE DEVICE (SPD) PER SECTION 262413 AND/OR 262416. SPD SHALL BE
INSTALLED BY AND SHIPPED FROM THE PANELBOARD AND/OR SWITCHBOARD
MANUFACTURER'S FACTORY.
4. PER NEC ARTICLE 110.24, PROVIDE BLACK PHENOLIC NAMEPLATE WITH WHITE
LETTERING WITH MAXIMUM AVAILABLE FAULT CURRENT AND THE DATE IT WAS
CALCULATED AND PERMANENTLY AFFIX TO SERVICE ENTRANCE EQUIPMENT. REFER
TO SPECIFICATION SECTION 260553 FOR DETAILS.
DRAWING NUMBER
REVISIONS
COPYRIGHT 2024 BY SOUTHERN A&E, LLC. ALL RIGHTS RESERVED.
THIS DOCUMENT IS THE PROPERTY OF SOUTHERN A&E, LLC AND SHALL
NOT BE COPIED OR REPRODUCED IN WHOLE OR IN PART WITHOUT
EXPRESSED WRITTEN CONSENT FROM SOUTHERN A&E, LLC.
12-17-2024
BID PACKAGE BP-1
SA&E PROJECT NUMBER
ORIGINAL SHEET SIZE: ARCH E1 (30" X 42")
A
12" GRIDS 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
B
C
D
E
F
G
H
I
J
K
L
M
N
ROSSVILLE MIDDLE SCHOOL
NEW FIELD AND CONCESSIONS FOR:
WALKER COUNTY SCHOOLS
301 N CHEROKEE ST, LAFAYETTE, GA 30728
316 BULLDOG TRAIL, ROSSVILLE, GA 30741
746-0206
01-920-041
ISSUED FOR CONSTRUCTION
STATE BOARD OF REGISTRATION
FOR PROFESSIONAL ENGINEERS AND
LAND SURVEYORS
SOUTHERN A & E, LLC
ENGINEER FIRM
LICENSE NO: PEF003374
EXP. DATE - 06/30/2026
E001
ELECTRICAL LEGENDS
NO SCALEE001
2 POWER RISER DIAGRAM
Water Heater 8320 VA 100.00% 8320 VA
Other 0 VA 0.00% 0 VA
Nonseasonal Motor 2845 VA 100.00% 2845 VA
Heating/Cooling 0 VA 0.00% 0 VA
Heating 0 VA 0.00% 0 VA
Cooling 0 VA 0.00% 0 VA Total Est. Demand Current: 98 A
Motor 1261 VA 125.00% 1576 VA Total Est. Demand: 35343 VA
Receptacle 10060 VA 99.70% 10030 VA Total Conn. Load: 34824 VA
Lighting 938 VA 125.00% 1172 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Apparent Load [VA] 12293 12037 10494
65 66
63 64
61 62
59 60
57 58
55 56
53 54
51 52
49 50
47 48
45 46
43 LIFT STATION REC 1/2"C,1#12,#12N,#12G 20 180 44
41 841 0 20 -- SPARE 42
39 841 0 20 -- SPARE 40
LIFT STATION 3/4"C,3#8,#10G 15
841 0 20 -- SPARE 38
35 EF-3 1/2"C,1#12,#12N,#12G 15 528 1000 36
33 1000 1000
20 1/2"C,2#12,#12G EH RESTROOM 102
EH RESTROOM 103 1/2"C,2#12,#12G 20
1000 2000 32
29 2000 2000
25 1/2"C,2#10,#10G EH STORAGE 105
EH CONCESSIONS 101 1/2"C,2#10,#10G 25
2000 4160 28
25 REC SCORER'S TABLE 3/4"PVC,1#10,#10N... 20 360 4160
50 1/2"C,2#8,#10G EWH
23 SCOREBOARD 1/2"C,1#8,#8N,#8G 20 1200 554 20 1/2"C,1#12,#12N,#12G LIGHTS CONCESS BLDG 24
21 REC SCOREBOARD 1/2"C,1#8,#8N,#8G 20 180 540 20 1/2"C,1#10,#10N,#10G REC DUGOUT 22
19 EXTERIOR BLDG LTS 1/2"C,1#12,#12N,#12G 20 192 180 20 1/2"C,1#12,#12N,#12G REC CONCESSIONS 101 20
17 EXTERIOR BLDG LTS 1/2"C,1#12,#12N,#12G 20 192 180 20 1/2"C,1#12,#12N,#12G REC CONCESSIONS 101 18
15 REC DUGOUT 1/2"C,1#10,#10N,#10G 20 540 180 20 1/2"C,1#12,#12N,#12G REC CONCESSIONS 101 16
13 REC RESTROOMS 1/2"C,1#12,#12N,#12G 20 360 180 20 1/2"C,1#12,#12N,#12G REC CONCESSIONS 101 14
11 REC EQ STORAGE 105 1/2"C,1#12,#12N,#12G 20 360 180 20 1/2"C,1#12,#12N,#12G REC CONCESSIONS 101 12
9 REC CONCESSIONS 101 1/2"C,1#12,#12N,#12G 20 180 180 20 1/2"C,1#12,#12N,#12G REC CONCESSIONS 101 10
7 REFRIGERATOR 1/2"C,1#12,#12N,#12G GF 20 1200 1100 8
5 REC EXTERIOR 1/2"C,1#12,#12N,#12G 20 360 1100
20 1/2"C,2#10,#10G ICE MACHINE
3 REC EXTERIOR 1/2"C,1#12,#12N,#12G 20 180 1056 15 1/2"C,1#12,#12N,#12G EF-1,2 4
1 REC EXTERIOR 1/2"C,1#12,#12N,#12G 20 360 180 20 1/2"C,1#12,#12N,#12G REC CONCESSIONS 101 2
Ckt Description Conduit & Wire N Trip A B C Trip N Conduit & Wire Ckt Description
GF = GFCI AF = AFCI ST = SHUNT TRIP HL = HANDLE LOCK X = CIRCUIT AND OCPD EXISTING TO REMAIN
Notes (Column N):
Feed-Thru Lugs: No Supply From: UTILITY XFRMR
Mounting: Surface Ground Bus: Yes Feeder: 3"C,3-350kcmil,350kcmil N,#2G
Enclosure: Type 1 Neutral Bus: Yes/100.00% Mains: 300 A MCB
Location: ELEC 104 Distribution System: 208/120V 3P 4W Wye AIC: 10,000
Branch Panel: LBB
# Doc # Date
1 AD2 1/15/25
erik
FRANK - SIGNED
| Sheets |
| E001 - ELECTRICAL LEGENDS |