E002_R1_AD2___LIGHTING_FIXTURE___MECHANICAL_E.pdf
PDF 2 MB Posted
- Solicitation number
- PE-55462-NONST-2025-000000010
- Issued by
- Wilcox County, Georgia
About this file
This document is a lighting fixture and mechanical equipment connection schedule document for the Rossville Middle School Athletic Field and Concessions project in Walker County Schools, Georgia. The drawing includes detailed specifications for various lighting fixtures (F1, F1E, I5, I5E, JSE) with their respective lamp lumens, CCT ratings, voltages, and mounting requirements, along with approved manufacturers and model numbers. The mechanical equipment connection schedule details specifications for exhaust fans (EF-1, EF-2, EF-3), a scoreboard, sewage lift station, and tankless electric water heater (TEWH-1), including voltage requirements and disconnect types.
The document contains four detailed electrical schematics showing the connection configurations for light fixtures with occupancy sensors, bathroom exhaust fan setups, and low voltage on/off switch implementations. The drawings include specific wiring diagrams with power pack connections, slave pack configurations, and control wiring specifications. The document is dated January 15, 2025, as part of Bid Package BP-1, with project number 746-0206 and was prepared by Southern A&E, LLC under engineer firm license PEF003374.
View the file
Other files
Show all 47
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
LIGHTING FIXTURE SCHEDULE NOTES:
1. PROVIDE REMOTE TEST SWITCH FOR EMERGENCY BATTERY OPERATION AT LOCATION SHOWN ON DRAWING. SWITCH SHALL CONTROL ALL EMERGENCY BALLAST LOCATED IN THAT SPACE.
2. SHADED ROWS INDICATE ROWS UPDATED IN THE LATEST REVISION.
MECHANICAL EQUIPMENT CONNECTION SCHEDULE NOTES:
1. PROVIDE CONDUIT FOR CONTROL WIRING AS SHOWN ON DETAIL SHEET.
2. COORDINATE HEIGHT OF JUNCTION BOX WITH MECHANICAL CONTRACTOR. PROVIDE POWER CONNECTION TO CONDENSATE PUMP (WHERE INSTALLED).
REFER TO DETAIL SHEET.
3. FOR ALL HVAC EQUIPMENT, PROVIDE MINIMUM OF 1/2"C FROM ACCESSIBLE CEILING, CONTROL DEVICE AND/OR CONTROL PANEL TO UNIT CONNECTION POINT FOR CONTROL WIRING. LINE VOLTAGE CONTROL WIRING SHALL BE BY DIVISION 26, LOW-VOLTAGE CONTROL WIRING SHALL BE BY OTHERS.
4. REFER TO MECHANICAL DRAWINGS FOR EXHAUST FAN INTERLOCK WITH LIGHTS. PROVIDE RELAY AS REQUIRED. COORDINATE WITH MECHANICAL
CONTRACTOR.
5. SHADED ROWS INDICATE ROWS UPDATED IN THE LATEST REVISION.
LOCAL
OFF SWITCH
LOCAL
OFF SWITCH
LIGHTING
CIRCUIT
Red (Line)
Red (Load)
Wht
Blk
R e d
B lk
B lu
C o n tr o l
C o m m o n
V
D C
C o m m o n
C o n tr o l
V
D C
N
Hot
POWER PACK
LIGHT
LOAD
LIGHT
LOAD
WHEN MORE THAN ONE
SWITCH IS CONTROLLED
BY A SINGLE SENSOR
WHEN MORE THAN ONE
SENSOR IS INSTALLED
ON ONE CIRCUIT
SWITCHING
Fan
MOTOR RATED
SERVICE DISCONNECT
SWITCH
LOCAL
OFF SWITCH
Connect to contactor coil
LIGHTING
CIRCUIT
Red (Line)
Red (Load)
Wht
Blk
R e d
B lk
B lu
C o n tr o l
C o m m o n
V
D C
N
Hot
N
Hot
FAN
CIRCUIT
POWER PACK
LIGHT
LOAD
SLAVE
PACK
24V DC
OCCUPANCY
SENSOR
Fan
DIODE
1N4001
LOCAL
OFF SWITCH
MOTOR RATED
DISCONNECT SWITCH
LOCAL
OFF SWITCH
DIODE
1N4001
LIGHTING
CIRCUIT
LIGHTING
CIRCUIT
N
Hot
Red (Line)
Red (Load)
Wht
Blk
R e d
B lu
B lk
R e d
B lk
B lu
N
Hot
C o n tr o l
C o m m o n
V
D C
V
D C
C o m m o n
C o n tr o l
Wht Red (Line)
N
Hot Blk Red (Load)
FAN
CIRCUIT
POWER PACK
LOAD
POWER PACK
LOAD
24V DC
OCCUPANCY
SENSOR
24V DC
OCCUPANCY
SENSOR
SLAVE
PACK
LIGHTING
CIRCUIT
Red (Line)
Red (Load)
Wht
Blk
R e d
B lk
G re y O n
C o m m o n
V
D C
N
Hot
POWER PACK
LIGHT
LOAD
LIGHT
LOAD
OCCUPANCY
SENSOR(S)
+24V DC
Common
LOW VOLTAGE
ON/OFF SWITCH
POWER PACK SWITCH
SET TO MANUAL
B lu
Control
O ff
O n
C o m m o n
V D
C
LOW VOLTAGE
ON/OFF SWITCH
O ff
ADDITIONAL SWITCHES
CONNECTED IN PARALLEL
DRAWING NUMBER
REVISIONS
COPYRIGHT 2024 BY SOUTHERN A&E, LLC. ALL RIGHTS RESERVED.
THIS DOCUMENT IS THE PROPERTY OF SOUTHERN A&E, LLC AND SHALL
NOT BE COPIED OR REPRODUCED IN WHOLE OR IN PART WITHOUT
EXPRESSED WRITTEN CONSENT FROM SOUTHERN A&E, LLC.
12-17-2024
BID PACKAGE BP-1
SA&E PROJECT NUMBER
ORIGINAL SHEET SIZE: ARCH E1 (30" X 42")
A
12" GRIDS 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
B
C
D
E
F
G
H
I
J
K
L
M
N
ROSSVILLE MIDDLE SCHOOL
NEW FIELD AND CONCESSIONS FOR:
WALKER COUNTY SCHOOLS
301 N CHEROKEE ST, LAFAYETTE, GA 30728
316 BULLDOG TRAIL, ROSSVILLE, GA 30741
746-0206
01-920-041
ISSUED FOR CONSTRUCTION
STATE BOARD OF REGISTRATION
FOR PROFESSIONAL ENGINEERS AND
LAND SURVEYORS
SOUTHERN A & E, LLC
ENGINEER FIRM
LICENSE NO: PEF003374
EXP. DATE - 06/30/2026
E002
LIGHTING FIXTURE & MECHANICAL
EQUIPMENT CONNECTION SCHEDULE
LIGHTING FIXTURE SCHEDULE
Type Lamp
(Lumens) Initial CCT Voltage
Input Power Mounting Height
Approved Manufacturers and Catalog Numbers
Type CommentsManufacturer 1 Model 1 Manufacturer 2 Model 2 Manufacturer 3 Model 3
F1 5000 4000 K 120/277 42 VA SURFACE OR SUPENDED VIA Y-TOGGLE &
AIRCRAFT CABLE. HEIGHT: 12'-0"AFF, U.O.N.
METALUX 4SNLED-LD5-50SL-LW-UNV-L840-CD-1 LITHONIA ZL1D-L48-SMR-5000LM-FST-MV
OLT-40K-80CRI-WH
COLUMBIA LCL4-40ML-E-U SURFACE OR SUPENDED STRIP FIXTURE. COLOR: WHITE. LENS:
ROUND, FROSTED, WIDE DISTRIBUTION.
F1E 5000 4000 K 120/277 42 VA SURFACE OR SUPENDED VIA Y-TOGGLE &
AIRCRAFT CABLE. HEIGHT: 10'-0" AFF,
U.O.N.
METALUX 4SNLED-LD5-50SL-LW-UNV-L840-CD-1-EL14W LITHONIA ZL1D-L48-SMR-5000LM-FST-MV
OLT-40K-80CRI-WH-E7W
COLUMBIA LCL4-40ML-E-U-ELL14 SAME AS TYPE 'F1' LIGHTING FIXTURE BUT PROVIDED WITH
EMERGENCY BATTERY PACK PER SECTION 265100.
I5 5500 120/277 57 VA SURFACE MOUNTED METALUX 4VT2-LD5-6-DR-UNV-L835-WL COLUMBIA LXEM4-35ML-RFA-E-U OR APPROVED EQUAL WET LOCATION LISTED
I5E 5500 120/277 57 VA SURFACE MOUNTED METALUX 4VT2-LD5-6-DR-UNV-L835-WL-EL10W COLUMBIA LXEM4-35ML-RFA-E-U-ELL14 OR APPROVED EQUAL SAME AS TYPE 'I5' LIGHTING FIXTURE BUT PROVIDED WITH
EMERGENCY BATTERY PACK PER SECTION 265100.
JSE 6000 4000 K 120/277 48 VA HEIGHT VARIES. REFER TO PLANS. LITHONIA WDGE2 LED-P5-40K-80CRI-VW-MVOLT-SRM-DS-DDBXD-E20WC OR APPROVED EQUAL SAME AS TYPE 'JS' LIGHTING FIXTURE BUT PROVIDED W/
EMERGENCY BATTERY PACK PER SECTION 265100.
MECHANICAL EQUIPMENT CONNECTION SCHEDULE
Equipment ID Voltage Number of Poles Disconnect Type Enclosure Rating Comments
EXHAUST FAN
EF-1 120 V 1 MOTOR RATED SWITCH
EF-2 120 V 1 MOTOR RATED SWITCH
EF-3 120 V 1 MOTOR RATED SWITCH
SCOREBOARD
SCOREBOARD 120 V 1 30A FUSIBLE SAFETY SWITCH NEMA 3R
SEWAGE LIFT STATION
SEWAGE LIFT
STATION
208 V 3 30A FUSIBLE SAFETY SWITCH NEMA 3R
TANKLESS ELECTRIC WATER HEATER
TEWH-1 208 V 2 60A FUSIBLE SAFETY SWITCH NEMA 1
NO SCALEE002
1 SCHEMATIC - CONNECTION OF LIGHT FIXTURES WITH OCCUPANCY SENSORS
12" = 1'-0"E002
2 SCHEMATIC - SINGLE BATHROOM WITH EXHAUST FAN AND OCCUPANCY SENSOR
12" = 1'-0"E002
SCHEMATIC - TWO BATHROOMS WITH COMMON EXHAUST
FAN AND OCCUPANCY SENSORS
12" = 1'-0"E002
SCHEMATIC - CONNECTION OF LOW VOLTAGE ON/OFF
SWITCH AND OCCUPANCY SENSOR WITH POWER PACK
# Doc # Date
1 AD2 1/15/25
erik
FRANK - SIGNED
| Sheets |
| E001 - ELECTRICAL LEGENDS |
| E002 - LIGHTING FIXTURE & MECHANICAL EQUIPMENT CONNECTION SCHEDULE |
| E003 - ELECTRICAL SITE PLAN |
| E101 - CONCESSIONS & DUGOUT BUILDINGS ELECTRICAL PLANS |
File details come from the government source that posted it. Updated .