Drawings Part 5 of 9.pdf

PDF 16 MB Posted

Attached to
Y1DZ--437-21-205 EHRM Infrastructure Upgrades Construction Fargo, ND
Solicitation number
36C77622B0030
Issued by

About this file

This document contains details of a federal solicitation opportunity for construction services. The solicitation seeks to upgrade the entire IT infrastructure for the Fargo VA Health Care System campus to the latest VA and industry standards, including demolition, new construction, various trade works, asbestos abatement, and coordination to minimize downtime. The construction work shall be completed in accordance with specifications, drawings, codes, and other requirements. The solicitation was issued by the Department of Veterans Affairs Technology Acquisition Center Austin.

View the file

Other files

File Type Posted
Wage Rates - Cass County - 6.17.22.pdf PDF
36C77622B0030 0005.docx DOCX document
Addendum Fiber Duct Bank.pdf PDF
36C77622B0030 0004.docx DOCX document
Technical Question Tracking Sheet - Infra Upgrades - Fargo.docx DOCX document
PCRA 437-21-205 Zone 2.pdf PDF
ICRA Zones.pdf PDF
PCRA 437-21-205 Zone 4.pdf PDF
36C77622B0030 0003.pdf PDF
PCRA 437-21-205 Zone 5.pdf PDF
PCRA 437-21-205 Zone 3.pdf PDF
36C77622B0030 0002.pdf PDF
Site Visit Sign-in Sheet - Fargo.pdf PDF
36C77622B0030 0001.pdf PDF
Wage Rates - Cass County - 4.15.22.pdf PDF
36C77622B0030 0001.pdf PDF
Wage Rates - Cass County - 4.25.22.pdf PDF
Reference Only - Basis of Design BOD Part 3 of 7.pdf PDF
Reference Only - Basis of Design BOD Part 2 of 7.pdf PDF
Reference Only - Basis of Design BOD Part 7 of 7.pdf PDF
Reference Only - Basis of Design BOD Part 6 of 7.pdf PDF
BOD Appendix A ACM Survey Report.pdf PDF
Specifications Vol 01 Rev.pdf PDF
36C77622B0030_1.pdf PDF
Drawings Part 7 of 9.pdf PDF
Reference Only - EHRM Design Alerts 1-8.pdf PDF
COVID-19 Safety Protocols 12-14-21.pdf PDF
Contractor Safety - Environmental Form.docx DOCX document
Reference Only - Basis of Design BOD Part 5 of 7.pdf PDF
Specifications Vol 02 Rev.pdf PDF
Reference Only - Basis of Design BOD Part 1 of 7.pdf PDF
Drawings Part 2 of 9.pdf PDF
Drawings Part 6 of 9.pdf PDF
Drawings Part 8 of 9.pdf PDF
Reference Only - Basis of Design BOD Part 4 of 7.pdf PDF
Drawings Part 9 of 9.pdf PDF
Drawings Part 4 of 9.pdf PDF
Drawings Part 1 of 9.pdf PDF
Reference Only - Infra Stdrd for Telecomm Spaces 3.1 - ISTS.pdf PDF
Drawings Part 3 of 9.pdf PDF
Show all 40

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SW OFFICE

3C-01

STORAGE

3C-03

HAC

3C-05

TOILET

3C-07

CHART ROOM

3B-27

TR

3B-23

3B-39A, PNL 93N1,SEC2/CKT 43

3B-39A, PNL EC93N1,SEC2/CKT 31

TRAC-3B23B

TRAC-3B23A

3B-39A, PNL EC93N1/CKT 39, 41

3B-39A, PNL EC93N1/CKT 40, 42

SW OFFICE

3C-01

STORAGE

3C-03

HAC

3C-05

TOILET

3C-07

CHART ROOM

3B-27

TR

3B-23

OS

3B-39A, PNL 93N1,SEC2/CKT 43

3B-39A, PNL EC93N1,SEC2/CKT 31

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

K:

\C

C G

_P R

O

JE

C

TS

\2

8\

-1

6C

9D

V

IS

N

ID

IQ

(N or th D ak ot a

Io w

a) \4

-2

1-

EH

R M

F ar go , N

D \4

- D es D oc s\

2-

D ra w in gs \W

O R

KI

N

G \E

P- B0

1-

1.

dw g 3/

/2

:4

0:

P M

ISSUE FOR BIDOffice of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES

FARGO VA HEALTH CARE SYSTEM

437-21-205

Revisions: Date:

www. bancroft-ae.com

3300 Dundee RD.

Northbrook, IL 60062

T: 847.952.9362

ISSUE FOR BID 03-18-22

3/18/2022

SHEET OF 281

Bancroft Project No: 18-121

ELECTRICAL - BUILDING 1-9-46 -

ENLARGED PLANS - THIRD FLOOR

WG BX

EP-01-431

01, 09, 46

A. CONTACT VA IT PRIOR TO WORKING IN DATA CENTER OR IT CLOSET.

B. USE PRECAUTIONS TO AVOID SNAGGING WIRING OR DAMAGING EQUIPMENT.

C. WHEN NEW TR ROOM(S) ARE CONSTRUCTED, IT COMMUNICATIONS EQUIPMENT WILL BE

MOVED TO NEW TR ROOM. “BIOENGINEERING” TYPE EQUIPMENT; I.E. SECURITY, NURSE

CALL, PHILLIPS, ETC, WILL REMAIN IN ORIGINAL CLOSET, AND MUST REMAIN OPERATIONAL.

D. PROTECT IT EQUIPMENT FROM DUST, DURING WORK THAT CREATES DUST.

E. SEE PANEL SCHEDULES ON DRAWING SERIES E600 FOR UPS PANEL SCHEDULES AND UPS

CIRCUIT NUMBERS.

F. NORMAL AND EMERGENCY WIRING TO TR ROOM LIGHTS AND RECEPTACLES IS SHOWN IN

THE SAME BUILDING AS THE TR. NOTATION FOR EACH CIRCUIT IS (ROOM, PANEL AND

CIRCUIT). CONTRACTOR TO INSTALL NEW 20A BREAKERS AND UPDATE PANEL CIRCUIT INDEX.

G. SEE DRAWING SERIES E700 FOR SINGLE LINE DRAWINGS.

H. NOTE THAT KEY NOTES MAINLY APPLY TO NEW/RELOCATED TR CLOSETS. ELECTRICAL WORK

IS NOT REQUIRED IN EXISTING IT CLOSETS THAT REMAIN OPERATIONAL.

I. UPS POWER TO RACKS / CABINETS IN NEW TR's MUST BE PROVIDED TO THE TOP OF THE

RACKS / CABINETS. NO POWER WIRING ON FLOORS!

J. RECEPTACLES ABOVE RACKS MUST BE NEMA L21-30R, LOCKING RECEPTACLES.

K. INSTALL LIGHTING CONTROLS PER LIGHTING DETAIL ON DETAIL DRAWING E501.

1. UPS POWER TO RACKS.

2. NORMAL POWER TO ROOM RECEPTACLES, AND LIGHTS. CONTACT COR PRIOR TO

INSTALLING LIGHTING TO DETERMINE OPTIMUM LOCATION FOR LIGHT FIXTURES.

3. EMERGENCY POWER TO ROOM RECEPTACLES AND LIGHTS. CONTACT COR PRIOR TO

INSTALLING LIGHTING TO DETERMINE OPTIMUM LOCATION FOR LIGHT FIXTURES.

4. OCCUPANCY SENSOR - HIGH MOUNT.

5. ONLY BRANCH CIRCUIT IS SHOWN FROM POWER PANEL TO COOLING UNIT. INSTALL

CONDUIT AND WIRE PER DETAIL ON DRAWING E501. CONTRACTOR TO WORK WITH

MECHANICAL CONTRACTOR TO ROUTE POWER AND TUBING TO OUTDOOR UNIT.

_J

■ L______'::==="---------

~~~~.,.■:e.~

I

I 0 I L______..=====-------------'==== 0

I

I

I

I 0

I i'"'""i""""""'i""'_ ___ __J,~---- 00-00-oo-oo-oo-oo-ool..oo

I

I

00-00-00-00-C

ENLARGED LIGHTING PLAN RM 38-23

1/4"=1'-0" 0 1' 2' •• ----

-/3()./flu

BANCROFT ARCHITECTS+ ENGINEERS

~~o ~ o ~o :20~0~0 ..

■ ■ L______'::===:::'__ __ lo 0 o 1===: I l===:@o ' @o ,L______..======-----------'='==

I===: I ,?---..__"'11 o l===:@o I

I

I

1,-------'@o ' I

I

0 ,~----- 00-00-0, 00-00-00-ool..oo 00-00-00-00-C

ENLARGED POWER PLAN RM 38-23

1/4"=1'-0" 0 I' 2' 4'

ELECTRICAL GENERAL NOTES

@ ELECTRICAL KEY NOTES

ROOM 3B-23

J

1 ROOM 3D-1 O

N CD KEYPLAN

::===============:~=========:~==========:I::========:

VA ID□

JMcAllister Snapshot

JMcAllister Rectangle

JMcAllister Text Box

SHEET OF 279

JMcAllister Text Box

TELE.

3C-98

TELE.

3C-97

ADMIN COOR

3D-14

MECHANICAL ROOM

3A-01

TR

3D-12

1 1 1 1

TRAC-3D12A TRAC-3D12B

3C-93, PNL EC13C1

3C-93, PNL 13C5

3C-93, PNL EC13C1

3C-93, PNL EC13C1

3D-10

3C-93, PNL 13C5

TELE.

3C-98

TELE.

3C-97

ADMIN COOR

3D-14

MECHANICAL ROOM

3A-01

TR

3D-12

OS

43C-93, PNL 13C5 2

3C-93, PNL EC13C1

3D-10

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

K:

\C

C G

_P R

O

JE

C

TS

\2

8\

-1

6C

9D

V

IS

N

ID

IQ

(N or th D ak ot a

Io w

a) \4

-2

1-

EH

R M

F ar go , N

D \4

- D es D oc s\

2-

D ra w in gs \W

O R

KI

N

G \E

P- B0

1-

2.

dw g 3/

/2

1:

:4

PM

ISSUE FOR BIDOffice of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES

FARGO VA HEALTH CARE SYSTEM

437-21-205

Revisions: Date:

www. bancroft-ae.com

3300 Dundee RD.

Northbrook, IL 60062

T: 847.952.9362

ISSUE FOR BID 03-18-22

3/18/2022

SHEET OF 281

Bancroft Project No: 18-121

ELECTRICAL - BUILDING 1-9-46 -

ENLARGED PLANS - THIRD FLOOR

WG BX

EP-01-432

01, 09, 46

A. CONTACT VA IT PRIOR TO WORKING IN DATA CENTER OR IT CLOSET.

B. USE PRECAUTIONS TO AVOID SNAGGING WIRING OR DAMAGING EQUIPMENT.

C. WHEN NEW TR ROOM(S) ARE CONSTRUCTED, IT COMMUNICATIONS EQUIPMENT WILL BE

MOVED TO NEW TR ROOM. “BIOENGINEERING” TYPE EQUIPMENT; I.E. SECURITY, NURSE

CALL, PHILLIPS, ETC, WILL REMAIN IN ORIGINAL CLOSET, AND MUST REMAIN OPERATIONAL.

D. PROTECT IT EQUIPMENT FROM DUST, DURING WORK THAT CREATES DUST.

E. SEE PANEL SCHEDULES ON DRAWING SERIES E600 FOR UPS PANEL SCHEDULES AND UPS

CIRCUIT NUMBERS.

F. NORMAL AND EMERGENCY WIRING TO TR ROOM LIGHTS AND RECEPTACLES IS SHOWN IN

THE SAME BUILDING AS THE TR. NOTATION FOR EACH CIRCUIT IS (ROOM, PANEL AND

CIRCUIT). CONTRACTOR TO INSTALL NEW 20A BREAKERS AND UPDATE PANEL CIRCUIT INDEX.

G. SEE DRAWING SERIES E700 FOR SINGLE LINE DRAWINGS.

H. NOTE THAT KEY NOTES MAINLY APPLY TO NEW/RELOCATED TR CLOSETS. ELECTRICAL WORK

IS NOT REQUIRED IN EXISTING IT CLOSETS THAT REMAIN OPERATIONAL.

I. UPS POWER TO RACKS / CABINETS IN NEW TR's MUST BE PROVIDED TO THE TOP OF THE

RACKS / CABINETS. NO POWER WIRING ON FLOORS!

J. RECEPTACLES ABOVE RACKS MUST BE NEMA L21-30R, LOCKING RECEPTACLES.

K. INSTALL LIGHTING CONTROLS PER LIGHTING DETAIL ON DETAIL DRAWING E501.

L. PANEL CIRCUITS ARE SUGGESTIONS. CONTRACTOR TO SELECT CIRCUITS AND BREAKERS

BASED ON FIELD CONDITIONS DURING WIRING.

1. UPS POWER TO RACKS.

2. NORMAL POWER TO ROOM RECEPTACLES, AND LIGHTS. CONTACT COR PRIOR TO

INSTALLING LIGHTING TO DETERMINE OPTIMUM LOCATION FOR LIGHT FIXTURES.

3. EMERGENCY POWER TO ROOM RECEPTACLES AND LIGHTS. CONTACT COR PRIOR TO

INSTALLING LIGHTING TO DETERMINE OPTIMUM LOCATION FOR LIGHT FIXTURES.

4. OCCUPANCY SENSOR - HIGH MOUNT.

5. ONLY BRANCH CIRCUIT IS SHOWN FROM POWER PANEL TO COOLING UNIT. INSTALL

CONDUIT AND WIRE PER DETAIL ON DRAWING E501. CONTRACTOR TO WORK WITH

MECHANICAL CONTRACTOR TO ROUTE POWER AND TUBING TO OUTDOOR UNIT.

~; LJ

1 ■ 1 .. II

I [8] ■

-b9-t

- I I ' ~- 0-01111!!!!!!!!!110_0_0_0_0_0_0 , ~ ~-- \l

■ ~-~ _b ~-~

---"ic._H__!J-----~:

I o-

13 ~

- a,1-\.CA I // ' '

BANCROFT ARCHITECTS+ ENGINEERS V

LJ

~~1 ■ 1

~ ~---::-:::::-::::::-...::73~- A

"" : I I I -------vi_ (===[I_IJ::)-, s , ~ '. (/;H...____, [8]

II

I ,0 ~

~O L,!to O O ~~

CD~ -

~ :::f o t ~o ~o o"' ~ --_ I ' ~-

-o_ollll!!!!!!!!!llolli:::..ilo......._.01i.......10L- 0-0-0~

~ ~-- \'-----'-'-I~--

----------j!_H_!)----~:

I

ELECTRICAL GENERAL NOTES

@ ELECTRICAL KEY NOTES

00-C

0 ___,/

_o

00 OU

ROOM 3B-23

J ROOM 3D-10

) I L - ~~'~I -L~

- _J

C C

I I N

CD KEY PLAN

I I

:c==========~::==========;:c============:l;:========;I

VA ID□

JMcAllister Snapshot

JMcAllister Rectangle

JMcAllister Text Box

SHEET OF 279

JMcAllister

CONDUIT # 6 & 8

PANEL EBUPS-014CA

CONDUIT TO PENTHOUSE

CONDUIT 8

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

K:

\C

C G

_P R

O

JE

C

TS

\2

8\

-1

6C

9D

V

IS

N

ID

IQ

(N or th D ak ot a

Io w

a) \4

-2

1-

EH

R M

F ar go , N

D \4

- D es D oc s\

2-

D ra w in gs \W

O R

KI

N

G \E

P- B0

1-

4.

dw g 3/

/2

4:

:4

PM

ISSUE FOR BIDOffice of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES

FARGO VA HEALTH CARE SYSTEM

437-21-205

Revisions: Date:

www. bancroft-ae.com

3300 Dundee RD.

Northbrook, IL 60062

T: 847.952.9362

ISSUE FOR BID 03-18-22

3/18/2022

SHEET OF 281

Bancroft Project No: 18-121

ELECTRICAL - BUILDING 1-9-46 -

FOURTH FLOOR PLAN

WG BX

EP-01-104

01, 09, 46

1. INSTALL LIGHTING FIXTURES PER LIGHTING SCHEDULE. CONTACT COR PRIOR TO

INSTALLING LIGHTING TO DETERMINE OPTIMUM LOCATION FOR LIGHT FIXTURES.

2. INSTALL LIGHTING CONTROLS PER nLIGHT DETAIL ON DRAWING E501.

3. ROUTE FEEDER CONDUIT #6 (DRAWING EP-01-10B) UP INTO MECHANICAL ROOM 4D-06

AND INSTALL NEW PANEL EBUPS014CA, ON EAST WALL. MOVE HONEYWELL CONDUITS

AND RELOCATE THE THERMOSTAT.

4. CONTRACTOR TO ROUTE CONDUIT #8 FROM ROOM 4D-06 INTO CORRIDOR HEADING

WEST TO ELEVATORS 1, 2, 3, AND UP INTO ROOM PENTHOUSE A. CONTINUE CONDUIT TO

PANEL EBUPS095CA. INSTALL UPS PANEL ON NORTH WALL, NEXT TO DOORWAY.

CONTRACTOR TO PROVIDE DETAILED ROUTING BASED ON FIELD CONDITIONS.

A. CONTRACTOR TO DETERMINE DETAILED CONDUIT ROUTING BASED ON FIELD CONDITIONS.

B. NORMAL POWER TO WALL OUTLETS AND LIGHTS IS ROUTED FROM ELECTRIC CLOSET THAT IS

IN THE SAME BUILDING AS THE LOCATION OF THE TR. CONTRACTOR TO SELECT OPTIMAL

ROUTING BASED ON FIELD CONDITIONS. THIS CONDUIT IS NOT SHOWN ON DRAWINGS. IF

THIS ROUTING IS DIFFERENT, IT WILL BE NOTED ON THE KEY NOTES.

C. UPS POWER IS ON THE EMERGENCY CRITICAL BRANCH AND MUST BE IN SEPARATE CONDUITS

FROM NORMAL POWER.

D. EQUIPMENT POWER TO TECHNOLOGY ROOM FANS AND CONDENSERS IS FROM EQUIPMENT

BRANCH OF EMERGENCY POWER AND MUST BE IN CONDUITS SEPARATE FROM NORMAL

POWER.

E. CONTACT VA IT PRIOR TO WORKING IN IT CLOSET.

F. FOLLOW VA LOCK OUT TAG OUT PROCEDURES FOR SAFETY.

G. SEE PANEL SCHEDULES ON DRAWING SERIES E600 FOR PANEL SCHEDULES AND CIRCUIT

NUMBERS.

H. SEE DRAWING SERIES E700 FOR SINGLE LINE DRAWINGS.

I. NOTE THAT KEY NOTES MAINLY APPLY TO NEW/RELOCATED TR CLOSETS. ELECTRICAL WORK IS

NOT REQUIRED IN EXISTING IT CLOSETS THAT REMAIN OPERATIONAL.

J. UPS POWER TO RACKS / CABINETS IN NEW TR's MUST BE PROVIDED TO THE TOP OF THE

RACKS / CABINETS. NO POWER WIRING ON FLOORS!

K. RECEPTACLES ABOVE RACKS MUST BE NEMA L21-30R, LOCKING RECEPTACLE.

STAIRWELL #14 4B 58

1 BED

4B-5

TOILET

B-55 4B-55 ~- 0 4B-

TORAG LAUNDR 1

4A-70

STORAGE

4A-67 4A-63

PSYCH S.W.

OFFICE OFFICE

4A-66 H--""""TTT'Fr19'1""'~l'sTORAGE

F+=;?

4B 60

NO

1 BED U)W

I _J

-60A mo

TOILET

U)

1&2

EP-01-441

<r:O v- U) U)

I 3 mu ,tj- w

D 4B-70 4B-70A

NURSE

STATION

4B-48

REPORT

4B-46

PSYCH.

OFFICE

4B-44

PSYCH.

RES.

4B-42

NOUR.

4B-40

MULTI

PURPOSE

□ · 4B-26

ADDICTION

THERAPY

TOILET

[I]

4B-24

PSYCH.

=□ OFFICE 0

4B-20

GROUP

□ ROOM

_}L

4A-20

GROUP

ROOM

= 4A-22

MH NURSE

OFFICE

4A-24

NURSING

OFFICE

4A-26

PSYCH.

OFFICE

4A-28

0 PSYCH.

OFFICE

4A-30

PSYCH.

OFFICE/

EXAM

□ 4A-32

NURSE

OFFICE

4A-34

NURSING

OFFICE

4A-61 S.W.

0 4A-36 °

4A-59 4A-57 4A-55 TESTING

S.E. S.W. S.W.

OFFICE SUPR. OFFICE OFFICE

0 E

4A-53

STF. TLT.

4A-68 4A-64 4A S.W. COPIER ofFfcE

OFFICE

-60

SUICIDE

PREV.

COO RD.

4A

SOCIAL

WORK

SUPR.

4A-56

PSYCH

OFFICE

4A-54

BREAK

STAIRWELL #13 □ □ D □

D 4B- 70B 4B-72 ~4'-t_l: - 7 4A 4B- 76

~~"URSE 1 BED ILET 1 BED

LOUNGE4B-7 -74

TO I LE ~ =======~ ~=="=,!l;ll, 4B-71

MECH/ELEC S #15

4B-49 °

CLEAN

4B-47

OILED

4B-73 ° 4B

1 BED 1 B

4B-73 ~lic====c/14B-75

TOILET TOILE

4C-39

1 AUDIO\

EYE\EN1

1 RECEPTION

4C-40

WAITING

1 VICTORY

ELEVATORS (7,8)

00 0

0 4C 28 4C 29

AUDIO AUDIO

OFFICE TECH

4C-27

ELEC

pc===''77 lt::::=J,i, 4C-26 4C-25 4B-45

NURSE

CHIEF AUDIO

AUDIO OFFICE

MNGR

4B-43

4C-23

HEARING

;,:..,.°1RF=-v· -====j"·;:=--====;;=i~~--"'5-~-:1;1:===LA=B==sl 4B-35 4B-34 4B-33 4B-32 4C-22

CLINICAL

S.W.

4B-36

4C-23A

WORK

MHICM

RANGE

OFFICE

SATP ADMIN. ADMIN. ADMIN. EYE

OFFICE OFFICE OFFICE OFFICE INTAKE (2

4C-2 1

EY!t

IN1~KE

4C-50 4C-48

ENT

SURG

OFFICE

4C-49

ENT

EXAM

ENT

EXAM,/71;1:====::;,i

4C-44

FITTING &

DISPLA

4C-4

ENT

F=r-'- 0 UITE

4C-47

CLEAN

4C-46

SOILED

= Cil

4C-35 4C-34 4C-5

AUDIO AUDIO CERUMEN

TECH. OFFICE MANAGEMEN

Ow ,tj- (_') N <(

I □-:

uo f l/)

DJ

PROCED

Cil

4C-30

AUDIOL SUITE

4C-31 4C-32

AUDIO AUDIO

EXAM EXAM

SUITE SUITE

4C-51

ENT

EXAM

4C-52

INTAKE

Cil

Cil

4C-33

AUDIO

EXAM

SUITE

D

4C-16 4C-14 4C-13 4C-12

EYE EYE

EXAM EXAM

m 4C-15

WAITING □

4C-17 4C-11

TELE- EYE

RETINAL EXAM

EYE EYE

EXAM EXAM

4C-10

EYE

EXAM

H

H

H

4A-15

WAITING 4A-07

MEN

~ 4A-05

4A-03 4A-O 1

S.W. PSYCH.

4A-23A

STORAGE

4A-23

0 GROUP 0

ROOM

4A-27

PSYCH.

OFFICE

0 4A-29

PSYCH.

OFFICE

4A-31

NURSE

RESID

4A-3

INTERN

~+1

STAIRWELL #9

STAIRWELL #10

4A-47 4A-45 4A-43

PSYCH PSYCH. PSYCH. ~=:::JE"=::;1

TECH. OFFICE OFFICE

4A-40

MECHANICAL

ROOM

~ WOMEN OFFICE OFFICE

NORTH

4C-55

WOMEN

4C-56

MEN

4D-08

ELEVATOR #4

EQUIPMEN't

ROOM

4D-05

MECHANICAL

ROOM

4A-50

HCHV

OFFICE

4A-48 4A-46

PSYCH PSYCH.

OFFICE OFFICE

4A-44

PSYCH.

OFFICE

4A-42

PSYCH ~=:::JE"=:=J

OFFIC EB 1 BUILDING 1, 9, 46 - FOURTH FLOOR PLAN

1/16"=1·-o· o 4' a' 11' ---- D □

-/3()./flu

BANCROFT ARCHITECTS+ ENGINEERS VA

ELECTRICAL GENERAL NOTES

@ ELECTRICAL KEY NOTES

STAIRWELL #7

rr======~~-~-~-=-~~

4D-07A

ELEVATOR #5

EQUIPMEN't

ROOM

STAIRWELL #2

4E-14

ASSOC

cos E

STAIRWELL #2

,tj- _J <r:

N U □-:

I -<r:

WO□-:

v Wm

2- _J

1° 4E-23

, OFFICE

I ~=lie-'=====~ "-------, 4E-22

CLINICAL

EDUCATOR

4E-1 ,-----------laaali-l TR

4E-10

LIBRARY

4E-20

-21 COMP APP

TLT TRAINER

N

I

I

I

I I I I I 1&2

EP-01-44

4E-19

MECHANICAL

ROOM

l c:_

4E-19A

ELEVATOR #6

EQUIPMEN't ROOM "-1:::"'T'!rlinmrr'""'H

STAIRWELL #1

ROOM 4B-23

ROOM 4E-15A

I '7 I

EB KEY PLAN

ID□

JMcAllister Snapshot

JMcAllister Rectangle

JMcAllister Text Box

SHEET OF 279

JMcAllister

PHARM.

OFFICE

4B-28

PSYCH.

OFFICE

4B-24

ADDICTION

THERAPY TR

4B-23

4B-71, PNL 94N1

TRAC-4B23ATRAC-4B23A

4B-71, PNL EC94N2

4B-71, PNL EC94N2 4B-71, PNL EC94N2

PHARM.

OFFICE

4B-28

PSYCH.

OFFICE

4B-24

ADDICTION

THERAPY TR

4B-23

OS 4

4B-71, PNL 94N1 2

4B-71, PNL EC94N2

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

K:

\C

C G

_P R

O

JE

C

TS

\2

8\

-1

6C

9D

V

IS

N

ID

IQ

(N or th D ak ot a

Io w

a) \4

-2

1-

EH

R M

F ar go , N

D \4

- D es D oc s\

2-

D ra w in gs \W

O R

KI

N

G \E

P- B0

1-

1.

dw g 3/

/2

2:

:2

PM

ISSUE FOR BIDOffice of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES

FARGO VA HEALTH CARE SYSTEM

437-21-205

Revisions: Date:

www. bancroft-ae.com

3300 Dundee RD.

Northbrook, IL 60062

T: 847.952.9362

ISSUE FOR BID 03-18-22

3/18/2022

SHEET OF 281

Bancroft Project No: 18-121

ELECTRICAL - BUILDING 1-9-46 -

ENLARGED PLANS - FOURTH FLOOR

WG BX

EP-01-441

01, 09, 46

A. CONTACT VA IT PRIOR TO WORKING IN DATA CENTER OR IT CLOSET.

B. USE PRECAUTIONS TO AVOID SNAGGING WIRING OR DAMAGING EQUIPMENT.

C. WHEN NEW TR ROOM(S) ARE CONSTRUCTED, IT COMMUNICATIONS EQUIPMENT WILL BE

MOVED TO NEW TR ROOM. “BIOENGINEERING” TYPE EQUIPMENT; I.E. SECURITY, NURSE

CALL, PHILLIPS, ETC, WILL REMAIN IN ORIGINAL CLOSET, AND MUST REMAIN OPERATIONAL.

D. PROTECT IT EQUIPMENT FROM DUST, DURING WORK THAT CREATES DUST.

E. SEE PANEL SCHEDULES ON DRAWING SERIES E600 FOR UPS PANEL SCHEDULES AND UPS

CIRCUIT NUMBERS.

F. NORMAL AND EMERGENCY WIRING TO TR ROOM LIGHTS AND RECEPTACLES IS SHOWN IN

THE SAME BUILDING AS THE TR. NOTATION FOR EACH CIRCUIT IS (ROOM, PANEL AND

CIRCUIT). CONTRACTOR TO INSTALL NEW 20A BREAKERS AND UPDATE PANEL CIRCUIT INDEX.

G. SEE DRAWING SERIES E700 FOR SINGLE LINE DRAWINGS.

H. NOTE THAT KEY NOTES MAINLY APPLY TO NEW/RELOCATED TR CLOSETS. ELECTRICAL WORK

IS NOT REQUIRED IN EXISTING IT CLOSETS THAT REMAIN OPERATIONAL.

I. CONTRACTOR TO ROUTE NEW CONDUIT #7 UPS POWER, FROM ROOM BC-50A IN BASEMENT

(SEE DRAWING EP-01-10B), THEN ROUTE UP TO 1ST FLOOR PASSAGE TO BLDG 40 (SEE

DRAWING EP-01-101) AND INSTALL NEW PANEL UPS BLDG 40 IN ROOM 102B. CONTRACTOR

TO LOCATE NEW UPS PANEL BASED ON FIELD CONDITIONS AND NEC 3 FT EXCLUSION

REQUIREMENTS.

J. UPS POWER TO RACKS / CABINETS IN NEW TR's MUST BE PROVIDED TO THE TOP OF THE

RACKS / CABINETS. NO POWER WIRING ON FLOORS!

K. RECEPTACLES ABOVE RACKS MUST BE NEMA L21-30R, LOCKING RECEPTACLES.

L. INSTALL LIGHTING CONTROLS PER LIGHTING DETAIL ON DETAIL DRAWING.

1. UPS POWER TO RACKS. ROUTE CONDUIT AND INSTALL NEW UPS PANEL UPS BLDG 40, IN

ROOM 102B.

2. NORMAL POWER TO ROOM RECEPTACLES, AND LIGHTS. CONTACT COR PRIOR TO

INSTALLING LIGHTING TO DETERMINE OPTIMUM LOCATION FOR LIGHT FIXTURES.

3. EMERGENCY POWER TO ROOM RECEPTACLES AND LIGHTS. CONTACT COR PRIOR TO

INSTALLING LIGHTING TO DETERMINE OPTIMUM LOCATION FOR LIGHT FIXTURES.

4. OCCUPANCY SENSOR - HIGH MOUNT.

5. ONLY BRANCH CIRCUIT IS SHOWN FROM POWER PANEL TO COOLING UNIT,

CONTRACTOR TO WORK WITH MECHANICAL CONTRACTOR TO ROUTE POWER AND

TUBING TO OUTDOOR UNIT.

J

0 0 0 0 0

0 I

!'lfr~ Qo I

I

~---0 I ~~~ oo oo oo oo oo oo oo lta-lo _......,.F']

ENLARGED LIGHTING PLAN RM 48-23

1/4"=1'-o" 0 I' 'I 4' ----

-/3()./flu

BANCROFT ARCHITECTS+ ENGINEERS

J

VA

----' ; 0 0 0 0 ii ~o ~o ~o ~a , I

'-'--------'-'--------'--'--------'-L---....YI '

I\

ELECTRICAL GENERAL NOTES

ELECTRICAL KEY NOTES

ROOM 4B-23

ROOM 4E-15A

I n

L,------ -J 7 -

N ED KEYPLAN

::==============::========::============:I::======:

ID□

JMcAllister Snapshot

JMcAllister Rectangle

JMcAllister Text Box

SHEET OF 279

JMcAllister

EDUC. DIR.

4E-16

COMPUTER

TRAINING ROOM

4E-15

TR

4E-15A

TRAC-4E15AA

TRAC-4E15AB

4E-10, PNL EB151

4E-10, PNL EB151

4E-10, PNL EB151

4E-10, PNL 14C1

EDUC. DIR.

OFFICE

4E-16

COMPUTER

TRAINING ROOM

4E-15

TR

4E-15A

OS 4

4E-10, PNL EB151

24E-10, PNL 14C1

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

K:

\C

C G

_P R

O

JE

C

TS

\2

8\

-1

6C

9D

V

IS

N

ID

IQ

(N or th D ak ot a

Io w

a) \4

-2

1-

EH

R M

F ar go , N

D \4

- D es D oc s\

2-

D ra w in gs \W

O R

KI

N

G \E

P- B0

1-

2.

dw g 3/

/2

2:

:4

PM

ISSUE FOR BIDOffice of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES

FARGO VA HEALTH CARE SYSTEM

437-21-205

Revisions: Date:

www. bancroft-ae.com

3300 Dundee RD.

Northbrook, IL 60062

T: 847.952.9362

ISSUE FOR BID 03-18-22

3/18/2022

SHEET OF 281

Bancroft Project No: 18-121

ELECTRICAL - BUILDING 1-9-46 -

ENLARGED PLANS - FOURTH FLOOR

WG BX

EP-01-442

01, 09, 46

1. UPS POWER TO RACKS.

2. NORMAL POWER TO ROOM RECEPTACLES, AND LIGHTS. THIS RUN IS ABOUT 320 FT

LONG, USE 2#10 & 1#10G, ¾ IN C. CONTACT COR PRIOR TO INSTALLING LIGHTING TO

DETERMINE OPTIMUM LOCATION FOR LIGHT FIXTURES.

3. EMERGENCY POWER TO ROOM RECEPTACLES AND LIGHTS. CONTACT COR PRIOR TO

INSTALLING LIGHTING TO DETERMINE OPTIMUM LOCATION FOR LIGHT FIXTURES.

4. OCCUPANCY SENSOR - HIGH MOUNT.

5. ONLY BRANCH CIRCUIT IS SHOWN FROM POWER PANEL TO COOLING UNIT. INSTALL

CONDUIT AND WIRE PER DETAIL ON DRAWING E501. CONTRACTOR TO WORK WITH

MECHANICAL CONTRACTOR TO ROUTE POWER AND TUBING TO OUTDOOR UNIT.

A. CONTACT VA IT PRIOR TO WORKING IN DATA CENTER OR IT CLOSET.

B. USE PRECAUTIONS TO AVOID SNAGGING WIRING OR DAMAGING EQUIPMENT.

C. WHEN NEW TR ROOM(S) ARE CONSTRUCTED, IT COMMUNICATIONS EQUIPMENT WILL BE

MOVED TO NEW TR ROOM. “BIOENGINEERING” TYPE EQUIPMENT; I.E. SECURITY, NURSE

CALL, PHILLIPS, ETC, WILL REMAIN IN ORIGINAL CLOSET, AND MUST REMAIN OPERATIONAL.

D. PROTECT IT EQUIPMENT FROM DUST, DURING WORK THAT CREATES DUST.

E. SEE PANEL SCHEDULES ON DRAWING SERIES E600 FOR UPS PANEL SCHEDULES AND UPS

CIRCUIT NUMBERS.

F. NORMAL AND EMERGENCY WIRING TO TR ROOM LIGHTS AND RECEPTACLES IS SHOWN IN

THE SAME BUILDING AS THE TR. NOTATION FOR EACH CIRCUIT IS (ROOM, PANEL AND

CIRCUIT). CONTRACTOR TO INSTALL NEW 20A BREAKERS AND UPDATE PANEL CIRCUIT INDEX.

G. SEE DRAWING SERIES E700 FOR SINGLE LINE DRAWINGS.

H. NOTE THAT KEY NOTES MAINLY APPLY TO NEW/RELOCATED TR CLOSETS. ELECTRICAL WORK

IS NOT REQUIRED IN EXISTING IT CLOSETS THAT REMAIN OPERATIONAL.

I. UPS POWER TO RACKS / CABINETS IN NEW TR's MUST BE PROVIDED TO THE TOP OF THE

RACKS / CABINETS. NO POWER WIRING ON FLOORS!

J. RECEPTACLES ABOVE RACKS MUST BE NEMA L21-30R, LOCKING RECEPTACLES.

K. INSTALL LIGHTING CONTROLS PER LIGHTING DETAIL ON DETAIL DRAWING E501.

L. PANEL CIRCUITS ARE SUGGESTIONS. CONTRACTOR TO SELECT CIRCUITS AND BREAKERS

BASED ON FIELD CONDITIONS DURING WIRING.

ELECTRICAL GENERAL NOTES

@ ELECTRICAL KEY NOTES

/ I ) -"' I A • I I \ I I

' I I

I -~ '. I 0 t "'- : I

I\ ~ !-tA- 0

• • '. •o Oo l

• • '" ( 'h \ - @o V 0

/_o / - @o ~ ""---'. -~ p

~ I I I I I I I ~ \

6: I r-r-

C_

T rr

ROOM 4B-23

'I

IL

ROOM 4E-15A

' le_________, N CD KEYPLAN

I I

13 ~

- a,1-\.CA I // ' '

:c==========~::==========;:c============:l;:========;I

BANCROFT ARCHITECTS+ ENGINEERS V VA ID□

JMcAllister Snapshot

JMcAllister Rectangle

JMcAllister Text Box

SHEET OF 279

JMcAllister

UPS CONDUIT FROM FOURTH FLOOR

TR

TR

TR

EC95C5

100A

EB95C3,A

225A

EB465C3

225A

EB465C2

225A

ES465C1

EB465C1

225A

EBUPS-095CA

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

K:

\C

C G

_P R

O

JE

C

TS

\2

8\

-1

6C

9D

V

IS

N

ID

IQ

(N or th D ak ot a

Io w

a) \4

-2

1-

EH

R M

F ar go , N

D \4

- D es D oc s\

2-

D ra w in gs \W

O R

KI

N

G \E

P- B0

1-

5.

dw g 3/

/2

4:

:4

PM

ISSUE FOR BIDOffice of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES

FARGO VA HEALTH CARE SYSTEM

437-21-205

Revisions: Date:

www. bancroft-ae.com

3300 Dundee RD.

Northbrook, IL 60062

T: 847.952.9362

ISSUE FOR BID 03-18-22

3/18/2022

SHEET OF 281

Bancroft Project No: 18-121

ELECTRICAL - BUILDING 1-9-46 -

PENTHOUSE PLAN

WG BX

EP-01-105

01, 09, 46

1. INSTALL LIGHTING FIXTURES PER LIGHTING SCHEDULE. CONTACT COR PRIOR TO

INSTALLING LIGHTING TO DETERMINE OPTIMUM LOCATION FOR LIGHT FIXTURES.

2. INSTALL LIGHTING CONTROLS PER nLIGHT DETAIL ON DRAWING E501.

3. ROUTE UPS BRANCH CIRCUITS TO FEED RACKS FROM 4th FLOOR PNL EBUPS095CA.

CONTRACTOR TO DETERMINE BEST ROUTING BASED ON FIELD CONDITIONS.

A. CONTRACTOR TO DETERMINE DETAILED CONDUIT ROUTING BASED ON FIELD CONDITIONS.

B. NORMAL POWER TO WALL OUTLETS AND LIGHTS IS ROUTED FROM ELECTRIC CLOSET THAT IS

IN THE SAME BUILDING AS THE LOCATION OF THE TR. CONTRACTOR TO SELECT OPTIMAL

ROUTING BASED ON FIELD CONDITIONS. THIS CONDUIT IS NOT SHOWN ON DRAWINGS. IF

THIS ROUTING IS DIFFERENT, IT WILL BE NOTED ON THE KEY NOTES.

C. UPS POWER IS ON THE EMERGENCY CRITICAL BRANCH AND MUST BE IN SEPARATE CONDUITS

FROM NORMAL POWER.

D. EQUIPMENT POWER TO TECHNOLOGY ROOM FANS AND CONDENSERS IS FROM EQUIPMENT

BRANCH OF EMERGENCY POWER AND MUST BE IN CONDUITS SEPARATE FROM NORMAL

POWER.

E. CONTACT VA IT PRIOR TO WORKING IN IT CLOSET.

F. FOLLOW VA LOCK OUT TAG OUT PROCEDURES FOR SAFETY.

G. SEE PANEL SCHEDULES ON DRAWING SERIES E600 FOR PANEL SCHEDULES AND CIRCUIT

NUMBERS.

H. SEE DRAWING SERIES E700 FOR SINGLE LINE DRAWINGS.

I. NOTE THAT KEY NOTES MAINLY APPLY TO NEW/RELOCATED TR CLOSETS. ELECTRICAL WORK

IS NOT REQUIRED IN EXISTING IT CLOSETS THAT REMAIN OPERATIONAL.

J. UPS POWER TO RACKS / CABINETS IN NEW TR's MUST BE PROVIDED TO THE TOP OF THE

RACKS / CABINETS. NO POWER WIRING ON FLOORS!

K. RECEPTACLES ABOVE RACKS MUST BE NEMA L21-30R, LOCKING RECEPTACLE.

L. BRANCH ROUTING FROM 4th FLOOR TO PENTHOUSE TR'S IS “PROPOSED”, CONTRACTOR TO

ROUTE BASED ON FIELD CONDITIONS.

J~~

C

ELEV.

7 & B

MECH.

INTERMEDIATE LEVEL

ELEV.

7 & B

MECH.

TOP LEVEL

STAIRWELL #13

G G

□□□□□□□a

MACHINE AND ATTIC SPACE 1&2

EP-01-451

z w z I u w

~--j,i u z w z I

,I

MACHINE AND ATTIC SPACE

3&4 tPcc01& 1 u

STAIRWELL #9

@□B @8

PENTHOUSE-C

MECHANICAL

5&6 b V '

,-..EP~-0=1~~45_,1 ~ """ ==.=:===iv

ELEV 1,2,&3

PLATFORM i ~ 121 (9 D

PENTHOUSE-B

AUUIIIUl'J

D

NORTH

EB 1 BUILDING 1, 9, 46 - PENTI-iOUSE PLAN 0 4' 8' ----,, -/3()./flu

BANCROFT ARCHITECTS+ ENGINEERS

□□□□□□[)□ r;;i @@ i

□ ~B ~ □

0 □□□□□□□□□

VA

ELECTRICAL GENERAL NOTES

ELECTRICAL KEY NOTES

ROOM 501

I' ROOM 503

7 J

L_

I LJ

c; J

ROOM 5~

N

EB KEY PLAN

ID□

JMcAllister Snapshot

JMcAllister Rectangle

JMcAllister Text Box

SHEET OF 279

JMcAllister

TR

OS

PNL 94C1 PNL EC95C5

TR

TRAC-5-501

PNL 94C1

PNL EC95C5

PNL EC95C5

TR

TRAC-5-502

PNL 94C1

PNL EC95C5 / CKT 9, 11 PNL EC95C5 / CKT 13

TR

3OS

42PNL 94C1

PNL EC95C5 / CKT13 3

OS 4

TR

PENTHOUSE-C

PNL 465C1

PENTHOUSE-C

PNL EB465C2

TR

503 TRAC-5-503A

TRAC-5-503B

ACCU-5-503BACCU-5-503A

5 5

PENTHOUSE-C

PNL EB465C2

PENTHOUSE-C

PNL 465C1

PENTHOUSE-C

PNL EB465C2

PENTHOUSE-C

PNL EB465C2

NOTE: PANEL EC95C5 AND 94C1 ARE

LOCATED ON 5th FLOOR ACROSS

FROM ELEVATOR 1, 2, 3

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

K:

\C

C G

_P R

O

JE

C

TS

\2

8\

-1

6C

9D

V

IS

N

ID

IQ

(N or th D ak ot a

Io w

a) \4

-2

1-

EH

R M

F ar go , N

D \4

- D es D oc s\

2-

D ra w in gs \W

O R

KI

N

G \E

P- B0

1-

1.

dw g 3/

/2

6:

:3

PM

ISSUE FOR BIDOffice of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES

FARGO VA HEALTH CARE SYSTEM

437-21-205

Revisions: Date:

www. bancroft-ae.com

3300 Dundee RD.

Northbrook, IL 60062

T: 847.952.9362

ISSUE FOR BID 03-18-22

3/18/2022

SHEET OF 281

Bancroft Project No: 18-121

ELECTRICAL - BUILDING 1-9-46 -

ENLARGED PLANS - PENTHOUSE

WG BX

EP-01-451

01, 09, 46

A. CONTACT VA IT PRIOR TO WORKING IN DATA CENTER OR IT CLOSET.

B. USE PRECAUTIONS TO AVOID SNAGGING WIRING OR DAMAGING EQUIPMENT.

C. WHEN NEW TR ROOM(S) ARE CONSTRUCTED, IT COMMUNICATIONS EQUIPMENT WILL BE

MOVED TO NEW TR ROOM. “BIOENGINEERING” TYPE EQUIPMENT; I.E. SECURITY, NURSE

CALL, PHILLIPS, ETC, WILL REMAIN IN ORIGINAL CLOSET, AND MUST REMAIN OPERATIONAL.

D. PROTECT IT EQUIPMENT FROM DUST, DURING WORK THAT CREATES DUST.

E. SEE PANEL SCHEDULES ON DRAWING SERIES E600 FOR UPS PANEL SCHEDULES AND UPS

CIRCUIT NUMBERS.

F. NORMAL AND EMERGENCY WIRING TO TR ROOM LIGHTS AND RECEPTACLES IS SHOWN IN

THE SAME BUILDING AS THE TR. NOTATION FOR EACH CIRCUIT IS (ROOM, PANEL AND

CIRCUIT). CONTRACTOR TO INSTALL NEW 20A BREAKERS AND UPDATE PANEL CIRCUIT INDEX.

G. SEE DRAWING SERIES E700 FOR SINGLE LINE DRAWINGS.

H. NOTE THAT KEY NOTES MAINLY APPLY TO NEW/RELOCATED TR CLOSETS. ELECTRICAL WORK

IS NOT REQUIRED IN EXISTING IT CLOSETS THAT REMAIN OPERATIONAL.

I. UPS POWER TO RACKS / CABINETS IN NEW TR's MUST BE PROVIDED TO THE TOP OF THE

RACKS / CABINETS. NO POWER WIRING ON FLOORS!

J. RECEPTACLES ABOVE RACKS MUST BE NEMA L21-30R, LOCKING RECEPTACLES.

K. INSTALL LIGHTING CONTROLS PER LIGHTING DETAIL ON DETAIL DRAWING E501.

1. UPS POWER TO RACKS.

2. NORMAL POWER TO ROOM RECEPTACLES, AND LIGHTS. CONTACT COR PRIOR TO

INSTALLING LIGHTING TO DETERMINE OPTIMUM LOCATION FOR LIGHT FIXTURES.

3. EMERGENCY POWER TO ROOM RECEPTACLES AND LIGHTS. CONTACT COR PRIOR TO

INSTALLING LIGHTING TO DETERMINE OPTIMUM LOCATION FOR LIGHT FIXTURES.

4. OCCUPANCY SENSOR - HIGH MOUNT.

5. ONLY BRANCH CIRCUIT IS SHOWN FROM POWER PANEL TO COOLING UNIT. INSTALL

CONDUIT AND WIRE PER DETAIL ON DRAWING E501. CONTRACTOR TO WORK WITH

MECHANICAL CONTRACTOR TO ROUTE POWER AND TUBING TO OUTDOOR UNIT.

H H

I 0 I

' 0 0 0

0 I 0 0

ENLARGED LIGHTING PLAN RM 502 3 1-----------

1/4"=1'-0" o ,. ,. ,. • ----

H H

H H

ENLARGED POWER PLAN RM 501 2 1----------

1/4·=1·-o· o ,. r 4• a·

ENLARGED POWER PLAN RM 502 4 1----------

1/4"=1'-0" o ,. t ,. • ---- ----

-/3()./flu

BANCROFT ARCHITECTS+ ENGINEERS

• 0

I Oo

B

ENLARGED LIGHTING PLAN RM 503 5 1-----------1/4·=1·-o· 0 I' 2' 4' 8' ----

0 • 0 0 o@ I o@ o@ o@ 0

0 0

@B~ ;q ~ Of to

CT]

B

ELECTRICAL GENERAL NOTES

@ ELECTRICAL KEY NOTES

I J

I

N CD KEYPLAN

ROOM 501

ROOM 503

::===============:~=========:~==========:I::========:

VA ID□

JMcAllister Snapshot

JMcAllister Rectangle

JMcAllister Text Box

SHEET OF 279

JMcAllister

AREA 1

AREA 2

AREA 4

AREA 5

AREA 3

ACCU-1B-121

ACCU-BB-92B

ACCU-BB-92A

ACCU-4B23A

ACCU-3B23A

ACCU-4B23B

ACCU-3B23B

ACCU-2C33B

ACCU-BC-02A

ACCU-BC-02B

ACCU-1C99A

ACCU-1C99B

ACCU-BA30A

ACCU-1A54AA

ACCU-2A24A

ACCU-BA30B

ACCU-1A54AB

ACCU-2A24B

ACCU-2C90B

ACCU-2C90A

ACCU-4E15A

ACCU-2D-18A

ACCU-3D-12B

ACCU-3D-12A

ACCU-1D-64A

ACCU-1D-64B

ACCU-BD84

ACCU-1D-158

ACCU-502

ACCU-5-503B

ACCU-5-503A

ACCU-5-501

ACCU-2C33A

ACCU-BD02

ACCU-2D-18B

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

K:

\C

C G

_P R

O

JE

C

TS

\2

8\

-1

6C

9D

V

IS

N

ID

IQ

(N or th D ak ot a

Io w

a) \4

-2

1-

EH

R M

F ar go , N

D \4

- D es D oc s\

2-

D ra w in gs \W

O R

KI

N

G \E

P-

-1

.d w g 3/

/2

3:

:1

PM

ISSUE FOR BIDOffice of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES

FARGO VA HEALTH CARE SYSTEM

437-21-205

Revisions: Date:

www. bancroft-ae.com

3300 Dundee RD.

Northbrook, IL 60062

T: 847.952.9362

ISSUE FOR BID 03-18-22

3/18/2022

SHEET OF 281

Bancroft Project No: 18-121

ELECTRICAL - BUILDING 1-9-46 -

ENLARGED PLANS - ROOF

WG BX

EP-01-106

01, 09, 46

A. MECHANICAL EQUIPMENT SHOWN ON DRAWING EP-01-106 IS FOR INFORMATION ONLY.

B. ELECTRICAL CONTRACTOR TO WORK WITH MECHANICAL CONTRACTOR TO ROUTE POWER

FROM POWER PANEL TO DISCONNECT(S) AT EVAPORATOR(S) IN TR ROOMS, THEN TO

DISCONNECT(S) ON OUTDOOR CONDENSER UNIT(S). CONDUITS AND TUBING FROM TR

EVAPORATOR UNITS TO CONDENSER UNITS SHALL UTILIZE COMMON ROUTING AND

SUPPORTS.

C. SEE WIRING DETAIL AND BLOCK DIAGRAM ON DRAWING E501 FOR WIRING AND CONDUIT TO

EVAPORATORS AND CONDENSING UNITS.

D. INSTALL A NEMA 1 2-POLE DISCONNECT AT EACH EVAPORATOR AND A NEMA 3R 2-POLE

DISCONNECT AT EACH CONDENSING UNIT. NOTE THAT THE DISCONNECT BODIES ARE ALSO

USED TO ROUTE THE RED 120V CONTROL WIRE AND GROUND WIRES BETWEEN THE

EVAPORATORS AND CONDENSING UNITS.

E. EQUIPMENT POWER TO TECHNOLOGY ROOM FANS AND CONDENSERS IS FROM EQUIPMENT

BRANCH OF EMERGENCY POWER AND MUST BE IN CONDUITS SEPARATE FROM NORMAL

POWER.

F. CONTACT VA IT PRIOR TO WORKING IN IT CLOSET.

G. FOLLOW VA NEC 70E LOCK OUT TAG OUT PROCEDURES FOR SAFETY.

j~~ C

ELEV.

7 & 8

MECH.

INTERMEDIATE LEVEL

ELEV.

7 & 8

MECH.

TOP LEVEL

STAIRWE_L #13

MACHINE AND ATTIC SPACE

□ □□□□□□□□□□□□tg)

□ 0

□ 0

MACHINE AND ATTIC SPACE

w u u

0 z w z I

\i "

STAIRWELL #9

w u

"' ~ u z w z I u " ~ a

®□B ®B

==:==B a

PENTHOUSE-C

MECHANICAL

a

PENTHOUSE-A

PENTHOUSE-B

ADDITION

NORTH

rn

ENG

STORAGE

m

T

EB 1 BUILDING 1, 9, 46 - ROOF PLAN

1/16"=1'-0" 0 4' tf ,. ----

-/3()./flu

BANCROFT ARCHITECTS+ ENGINEERS

□□□□□□[)□ li:l ®@

II

0 □□□□□□□□□

ELECTRICAL GENERAL NOTES

N

EB KEY PLAN

VA ID□

JMcAllister Snapshot

JMcAllister Rectangle

JMcAllister Text Box

SHEET OF 279

JMcAllister

OPEN OFFICE

OFFICE

OFFICE

RESTROOM

TR

1a

PNL EB11C1

TRAC-3-0006

ACCU-03-0006

PNL EB11C1

OPEN OFFICE

OFFICE

OFFICE

RESTROOM

TR

OS2

PNL EB11C1

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

K:

\C

C G

_P R

O

JE

C

TS

\2

8\

-1

6C

9D

V

IS

N

ID

IQ

(N or th D ak ot a

Io w

a) \4

-2

1-

EH

R M

F ar go , N

D \4

- D es D oc s\

2-

D ra w in gs \W

O R

KI

N

G \E

P-

-1

.d w g 3/

/2

:3

5:

A M

ISSUE FOR BIDOffice of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES

FARGO VA HEALTH CARE SYSTEM

437-21-205

Revisions: Date:

www. bancroft-ae.com

3300 Dundee RD.

Northbrook, IL 60062

T: 847.952.9362

ISSUE FOR BID 03-18-22

3/18/2022

SHEET OF 281

Bancroft Project No: 18-121

ELECTRICAL - BUILDING 3 - ENLARGED

PLANS - FIRST FLOOR

WG BX

EP-03-101

A. CONTACT VA IT PRIOR TO WORKING IN DATA CENTER OR IT CLOSET.

B. USE PRECAUTIONS TO AVOID SNAGGING WIRING OR DAMAGING EQUIPMENT.

C. WHEN NEW TR ROOM(S) ARE CONSTRUCTED, IT COMMUNICATIONS EQUIPMENT WILL BE

MOVED TO NEW TR ROOM. “BIOENGINEERING” TYPE EQUIPMENT; I.E. SECURITY, NURSE

CALL, PHILLIPS, ETC, WILL REMAIN IN ORIGINAL CLOSET, AND MUST REMAIN OPERATIONAL.

D. PROTECT IT EQUIPMENT FROM DUST, DURING WORK THAT CREATES DUST.

E. NOTE THAT KEY NOTES MAINLY APPLY TO NEW/RELOCATED TR CLOSETS. ELECTRICAL WORK

IS NOT REQUIRED IN EXISTING IT CLOSETS THAT REMAIN OPERATIONAL.

F. RECEPTACLES TO POWER THE UPS IN THE NEW RACK SHALL BE ABOVE RACK, MUST BE NEMA

L21-30R, LOCKING RECEPTACLES.

G. INSTALL LIGHTING CONTROLS PER LIGHTING DETAIL ON DETAIL DRAWING E501.

H. ONLY PANEL IS IDENTIFIED FOR WIRING. CONTRACTOR TO SELECT CIRCUITS BASED ON FIELD

CONDITIONS.

1. EMERGENCY POWER TO ROOM RACK, RECEPTACLES, AND LIGHTS. CONTRACTOR TO

TERMINATE FROM EXISTING EMERGENCY POWER PANEL.

a. PROVIDE TWO L21-30 RECEPTACLES TO TOP OF RACK FROM EMERGENCY POWER IN

BLDG.

b. TERMINATE EMERGENCY POWER TO LIGHTS AND WALL RECEPTACLES FROM A 1-POLE, 20A, 120V CIRCUIT. CONTACT COR PRIOR TO INSTALLING LIGHTING TO DETERMINE

OPTIMUM LOCATION FOR LIGHT FIXTURES.

2. OCCUPANCY SENSOR - HIGH MOUNT.

3. ONLY BRANCH CIRCUIT IS SHOWN FROM POWER PANEL TO COOLING UNIT. INSTALL

CONDUIT AND WIRE PER DETAIL ON DRAWING E501. CONTRACTOR TO WORK WITH

MECHANICAL CONTRACTOR TO ROUTE POWER AND TUBING TO OUTDOOR UNIT.

CONDUIT MUST BE CONCEALED IN WALLS OR FROM BELOW.

ELECTRICAL GENERAL NOTES

oQ 0 Ou,, @ 0 ELECTRICAL KEY NOTES i t 0

EB BUILDING 3 - FIRST FLOOR POWER PLAN N 2 1---------

1/4"•1'-o" o ,. r ~ • ----

-/3()./flu ::==============:::=========:::============:I::=======:

BANCROFT ARCHITECTS+ ENGINEERS VA ID□

JMcAllister Snapshot

JMcAllister Rectangle

JMcAllister Text Box

SHEET OF 279

JMcAllister

PNL EB101N1

PNL EB101N2

PA

NE

L E B1

N3

PA

NE

L E B1

N2

PA

NE

L E B1

N1

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

K:

\C

C G

_P R

O

JE

C

TS

\2

8\

-1

6C

9D

V

IS

N

ID

IQ

(N or th D ak ot a

Io w

a) \4

-2

1-

EH

R M

F ar go , N

D \4

- D es D oc s\

2-

D ra w in gs \W

O R

KI

N

G \E

P-

-1

.d w g 3/

/2

3:

:4

PM

ISSUE FOR BIDOffice of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES

FARGO VA HEALTH CARE SYSTEM

437-21-205

Revisions: Date:

www. bancroft-ae.com

3300 Dundee RD.

Northbrook, IL 60062

T: 847.952.9362

ISSUE FOR BID 03-18-22

3/18/2022

SHEET OF 281

Bancroft Project No: 18-121

ELECTRICAL - BUILDING 10 - ENLARGED

PLANS - FIRST FLOOR

WG BX

EP-10-101

A. CONTACT VA IT PRIOR TO WORKING IN DATA CENTER OR IT CLOSET.

B. USE PRECAUTIONS TO AVOID SNAGGING WIRING OR DAMAGING EQUIPMENT.

C. WHEN NEW TR ROOM(S) ARE CONSTRUCTED, IT COMMUNICATIONS EQUIPMENT WILL

BE MOVED TO NEW TR ROOM. “BIOENGINEERING” TYPE EQUIPMENT, I.E. SECURITY,

NURSE CALL, PHILLIPS, ETC, WILL REMAIN IN ORIGINAL CLOSET, AND MUST REMAIN

OPERATIONAL.

D. PROTECT IT EQUIPMENT FROM DUST, DURING WORK THAT CREATES DUST.

E. NOTE THAT KEY NOTES MAINLY APPLY TO NEW/RELOCATED TR CLOSETS. ELECTRICAL

WORK IS NOT REQUIRED IN EXISTING IT CLOSETS THAT REMAIN OPERATIONAL.

F. TERMINATE BOTH POWER AND HVAC TO EMERGENCY (EB) POWER. CONTRACTOR TO

SELECT EMERGENCY POWER FOR THE EMCOR OR EQUAL CABINET.

1. FROM PANEL EB101N1, TERMINATE ONE 30A, 3-POLE, 208/120V CIRCUIT TO THE

POWER CONNECTION ON THE EMCOR OR EQUAL CABINET.

2. FROM PANEL EB101N2, TERMINATE ONE 30A, 3-POLE, 208/120V CIRCUIT TO THE HVAC

CONNECTION ON THE EMCOR OR EQUAL CABINET.

ELECTRICAL GENERAL NOTES

@ ELECTRICAL KEY NOTES

STORAGE

I\ ~== I\ IV -

h::l I\

GENERATOR

0 \_ 0005

STORAGE

i ~

CD ODOB ~ 8 0

SHOP

0[ - ~

0003 \ ) CLOSET

L_

LOCKER

OFFICE

LJ _)

I

I I

13 ~

- Clfitvt I IJ '

::==============:::=========:::==========:l::======:I

BANCROFT ARCHITECTS+ ENGINEERS V VA ID□

JMcAllister Snapshot

JMcAllister Rectangle

JMcAllister Text Box

SHEET OF 279

JMcAllister

RBB1

TRAC-11-0001

ACCU-51-1029

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

K:

\C

C G

_P R

O

JE

C

TS

\2

8\

-1

6C

9D

V

IS

N

ID

IQ

(N or th D ak ot a

Io w

a) \4

-2

1-

EH

R M

F ar go , N

D \4

- D es D oc s\

2-

D ra w in gs \W

O R

KI

N

G \E

P-

-1

.d w g 3/

/2

:3

6:

P M

ISSUE FOR BIDOffice of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES

FARGO VA HEALTH CARE SYSTEM

437-21-205

Revisions: Date:

www. bancroft-ae.com

3300 Dundee RD.

Northbrook, IL 60062

T: 847.952.9362

ISSUE FOR BID 03-18-22

3/18/2022

SHEET OF 281

Bancroft Project No: 18-121

ELECTRICAL - BUILDING 11 - ENLARGED

PLANS - FIRST FLOOR GARAGE

WG BX

EP-11-101

A. CONTACT VA IT PRIOR TO WORKING IN DATA CENTER OR IT CLOSET.

B. USE PRECAUTIONS TO AVOID SNAGGING WIRING OR DAMAGING EQUIPMENT.

C. PROTECT IT EQUIPMENT FROM DUST, DURING WORK THAT CREATES DUST.

D. CONNECT CONDUIT TO TOP OF TELECOMMUNICATIONS ENCLOSURE, AND ROUT

MULTICONDUCTOR CABLE INSIDE BACK OF ENCLOSURE, AND TERMINATE WITH L5-20

CONNECTOR, FOR UPS TO PLUG INTO.

E. NOTE: SELECT PANELS EB101N1 AND EB101N2 CIRCUITS FOR TELECOMMUNICATIONS

ENCLOSURE.

1. PROVIDE ONE 30A, 120V L5-30 RECEPTACLE TO TOP LEFT SIDE OF

TELECOMMUNICATIONS ENCLOSURE.

2. PROVIDE ONE 30A, 120V L5-30 RECEPTACLE TO TOP RIGHT SIDE OF

TELECOMMUNICATIONS ENCLOSURE.

3. PROVIDE ONE 20A, SINGLE POLE CIRCUIT TO EXHAUST FAN IN TELECOMMUNICATIONS

ENCLOSURE.

4. ONLY BRANCH CIRCUIT IS SHOWN FROM POWER PANEL TO COOLING UNIT. INSTALL

CONDUIT AND WIRE PER DETAIL ON DRAWING E501. CONTRACTOR TO WORK WITH

MECHANICAL CONTRACTOR TO ROUTE POWER AND TUBING TO OUTDOOR UNIT.

CONDUIT MUST BE CONCEALED IN WALLS OR FROM BELOW.

GENERATOR

TRANSFORM ER

N

EB 1

BUILDING 11 - FIRST FLOOR POWER PLAN

1/8"=1'-0" 02'4' t ----

-/30Jhu

BANCROFT ARCHITECTS+ ENGINEERS

SAND ROOM

HAC

TOILET/HAC

VA

ID

SHOP (OFFICE)

ELECTRICAL GENERAL NOTES

@ ELECTRICAL KEY NOTES

ID□

JMcAllister Snapshot

JMcAllister Rectangle

JMcAllister Text Box

SHEET OF 279

JMcAllister

RBB

PANEL 12

PNL B12P1

TRAC-12-0005

ACCU-12-10285

PNL B12P1

PANEL B12P1

PNL B12P1

TR

PANEL B12P1

OS

PNL B12P1

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

K:

\C

C G

_P R

O

JE

C

TS

\2

8\

-1

6C

9D

V

IS

N

ID

IQ

(N or th D ak ot a

Io w

a) \4

-2

1-

EH

R M

F ar go , N

D \4

- D es D oc s\

2-

D ra w in gs \W

O R

KI

N

G \E

P-

-1

.d w g 3/

/2

3:

:5

PM

ISSUE FOR BIDOffice of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES

FARGO VA HEALTH CARE SYSTEM

437-21-205

Revisions: Date:

www. bancroft-ae.com

3300 Dundee RD.

Northbrook, IL 60062

T: 847.952.9362

ISSUE FOR BID 03-18-22

3/18/2022

SHEET OF 281

Bancroft Project No: 18-121

ELECTRICAL - BUILDING 12 - ENLARGED

PLANS - FIRST FLOOR

WG BX

EP-12-101

A. CONTACT VA IT PRIOR TO WORKING IN DATA CENTER OR IT CLOSET.

B. USE PRECAUTIONS TO AVOID SNAGGING WIRING OR DAMAGING EQUIPMENT.

C. PROTECT IT EQUIPMENT FROM DUST, DURING WORK THAT CREATES DUST.

D. NOTE THAT KEY NOTES MAINLY APPLY TO NEW/RELOCATED TR CLOSETS. ELECTRICAL

WORK IS NOT REQUIRED IN EXISTING IT CLOSETS THAT REMAIN OPERATIONAL.

E. RECEPTACLE TO POWER THE UPS IN THE NEW RACK SHALL BE ABOVE RACK, MUST BE

NEMA L21-30R, LOCKING RECEPTACLE.

F. INSTALL LIGHTING CONTROLS PER LIGHTING DETAIL ON DETAIL DRAWING E501.

1. NORMAL POWER TO ROOM RECEPTACLES, AND LIGHTS. CONTRACTOR TO TERMINATE

FROM EXISTING NORMAL POWER PANEL B12P1. CONTRACTOR TO TERMINATE TO 20A

BREAKER.

2. PROVIDE TWO 30A, 3-POLE, 208V L21-30 LOCKING RECEPTACLES AT TOP OF RACK.

CIRCUITS CAN BE FROM SAME PANEL.

3. OCCUPANCY SENSOR - HIGH MOUNT.

4. ONLY BRANCH CIRCUIT IS SHOWN FROM POWER PANEL TO COOLING UNIT. INSTALL

CONDUIT AND WIRE PER DETAIL ON DRAWING E501. CONTRACTOR TO WORK WITH

MECHANICAL CONTRACTOR TO ROUTE POWER AND TUBING TO OUTDOOR UNIT.

WAREHOUSE

1 0006 1

BREAK ROOM

1 0004 1

I I

BUILDING 12 - ENLARGED LIGHTING PLAN

1/4"=1'-0" 01'2' 4' • ----

VAULT

1 0008 1

OFFICE

BATHROOM

1 0002 1

1 0001 1

-/30Jhu

BANCROFT ARCHITECTS+ ENGINEERS

of

WAREHOUSE

1 0005 1

BREAK ROOM

1 0004 1

I I

VAULT

1 oooa 1

OFFICE

BATHROOM

1 0002 1

1 0001 1

2 BUILDING 12 - ENLARGED POWER PLAN

1/4"=1'-0" 01'2' 4' ••

VA

ELECTRICAL GENERAL NOTES

ELECTRICAL COMMON NOTES

N

CD KEY PLAN

ID□

JMcAllister Snapshot

JMcAllister Rectangle

JMcAllister Text Box

SHEET OF 279

JMcAllister

RB

B

PA

NE

L 1

C2

PA

NE

L 1

C4

PANEL 131C1

PANEL 131C1-B

PA

NE

L 1

C3

ACCU-13-101

TRAC-13-101

UPS - PANEL 131C1, CKT 44, 46, 48

PD

U -

PA

NE

L 1

C1 , C

KT

, 4 5, FAN - PANEL 131C1, CKT 33

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

K:

\C

C G

_P R

O

JE

C

TS

\2

8\

-1

6C

9D

V

IS

N

ID

IQ

(N or th D ak ot a

Io w

a) \4

-2

1-

EH

R M

F ar go , N

D \4

- D es D oc s\

2-

D ra w in gs \W

O R

KI

N

G \E

P-

-1

.d w g 3/

/2

:3

6:

P M

ISSUE FOR BIDOffice of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES

FARGO VA HEALTH CARE SYSTEM

437-21-205

Revisions: Date:

www. bancroft-ae.com

3300 Dundee RD.

Northbrook, IL 60062

T: 847.952.9362

ISSUE FOR BID 03-18-22

3/18/2022

SHEET OF 281

Bancroft Project No: 18-121

ELECTRICAL - BUILDING 13 - ENLARGED

PLANS - FIRST FLOOR

WG BX

EP-13-101

A. CONTACT VA IT PRIOR TO WORKING IN DATA CENTER OR IT CLOSET.

B. USE PRECAUTIONS TO AVOID SNAGGING WIRING OR DAMAGING EQUIPMENT.

C. PROTECT IT EQUIPMENT FROM DUST, DURING WORK THAT CREATES DUST.

D. RECEPTACLE TO POWER THE UPS AND PDU IN THE NEW RACK SHALL BE ABOVE RACK,

MUST BE NEMA L21-30R, LOCKING RECEPTACLES.

1. NORMAL POWER TO RACK AND PDU. CONTRACTOR TO TERMINATE TWO L5-30 30A,

1-POLE, TO TWO 120V BREAKERS ON PANEL 131C1.

2. ONLY BRANCH CIRCUIT IS SHOWN FROM POWER PANEL TO COOLING UNIT. INSTALL

CONDUIT AND WIRE PER DETAIL ON DRAWING E501. CONTRACTOR TO WORK WITH

MECHANICAL CONTRACTOR TO ROUTE POWER AND TUBING TO OUTDOOR UNIT.

BACK STAIRWAY ,

r

MECHANICAL ROOM

r

(J

/ BACK ENTRY

654321

D

□ CJ_CJ_

ELECTRICAL GENERAL NOTES

@ ELECTRICAL KEY NOTES

01 ) ,., I

I

ICT)~ /c ~ ~ \__ LJ I ) ~

~ "/ ~ - I

Y1.,., 0 -@ -=ii ~ L_

BUILDING 13 - RAST FLOOR POWER PLAN

1/8"=1'-0" o r •· t ,r

I I

13 ~

- Clfitvt I IJ '

::==============:::=========:::==========:l::======:I

BANCROFT ARCHITECTS+ ENGINEERS V VA ID□

JMcAllister Snapshot

JMcAllister Rectangle

JMcAllister Text Box

SHEET OF 279

JMcAllister

BASEMENT FLOOR PLAN

RBB

PANEL 30W

PNL 30W / CKT 21

PNL 30W / CKT 242

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

K:

\C

C G

_P R

O

JE

C

TS

\2

8\

-1

6C

9D

V

IS

N

ID

IQ

(N or th D ak ot a

Io w

a) \4

-2

1-

EH

R M

F ar go , N

D \4

- D es D oc s\

2-

D ra w in gs \W

O R

KI

N

G \A

-B

-4

.d w g 3/

/2

3:

:5

PM

75% SUBMISSION

DESIGN DEVELOPMENT

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES

FARGO VA HEALTH CARE SYSTEM

437-21-205

Project Director

Revisions: Date:

www. bancroft-ae.com

3300 Dundee RD.

Northbrook, IL 60062

T: 847.952.9362

35% SCHEMATIC DESIGN SUBMISSION 09-28-21

75% DESIGN DEVELOPMENT SUBMISSION 12-08-21

12/08/2021

50% DESIGN DEVELOPMENT SUBMISSION 11-01-21

75% DESIGN DEVELOPMENT SUBMITTAL - VA REVIEW ONLY - NOT FOR CONSTRUCTION

A. CONTACT VA IT PRIOR TO WORKING IN DATA CENTER OR IT CLOSET.

B. USE PRECAUTIONS TO AVOID SNAGGING WIRING OR DAMAGING EQUIPMENT.

C. PROTECT IT EQUIPMENT FROM DUST, DURING WORK THAT CREATES DUST.

D. NOTE THAT KEY NOTES MAINLY APPLY TO NEW/RELOCATED TR CLOSETS. ELECTRICAL

WORK IS NOT REQUIRED IN EXISTING IT CLOSETS THAT REMAIN OPERATIONAL.

E. NOTE: BUILDING 30 HAS 240V RESIDENTIAL POWER, AND CAN ONLY PROVIDE TWO

120V CIRCUITS. ONE CIRCUIT FOR A 120V UPS, AND ONE CIRCUIT FOR SMALL EXHAUST

FAN.

F. CONNECT CONDUIT TO TOP OF COMMUNICATIONS ENCLOSURE, AND ROUT

MULTICONDUCTOR CABLE INSIDE BACK OF ENCLOSURE, AND TERMINATE WITH L5-20

CONNECTOR, FOR UPS TO PLUG INTO.

1. CONTRACTOR TO TERMINATE FROM 120V NORMAL POWER PANEL. CONNECT ONE

15A, 1-POLE, 120V CIRCUIT TO THE UPS INSIDE THE WALL MOUNTED CABINET. USE

2#10 & 1#8G, ¾ IN C, CABLE FROM NORMAL POWER PANEL TO PLUG INSIDE WALL

CABINET. THERE IS NO SPACE FOR CONDUIT INSIDE THE CABINET, SO CONDUCTORS

MUST BE A CABLE.

2. CONTRACTOR TO TERMINATE FROM 120V NORMAL POWER PANEL. CONNECT ONE

15A, 1-POLE, 120V CIRCUIT TO FAN. USE 2#10 & 1#8G, ¾ IN C, CABLE FROM NORMAL

POWER PANEL TO FAN INSIDE WALL CABINET.

ELECTRICAL - BUILDING 30 - BASEMENT

POWER PLAN

WG BX

EP-30-101

ELECTRICAL GENERAL NOTES

<x> ELECTRICAL KEY NOTES

' I

I

- i

( / 1 \ B4~1~~1NG 30 - BASEMENCT ,P?WER PLANO

I

KEY PLAN

13 'X Clfitvt I IJ '

BANCROFT ARCHITECTS+ ENGINEERS V

VA _J_J

I I I I I I

JMcAllister Snapshot

JMcAllister Rectangle

JMcAllister Text Box

SHEET OF 279

JMcAllister

102B

CONTINUATION SEE

DRAWING EP-01-101

CONDUIT # 7

ROOM 111, PNL 401N1

ROOM 111, PNL ES401N1

CONDUIT TO UP

SECOND FLOOR TR ROOM

PANEL 401N3

PANEL 401N1 (LP1-SECTION 1)

PA

NE

L R

OB

9E B1

PANEL ES401N1

PANEL 401N2 (LP4)

PANEL (LP1-SECTION 2)

TRAC-40-102BA

TRAC-40-102BB

CHIEF

102A

STAIR #1

WOMEN

PANEL EBUPS-401WA

SE

RV

ICE

EN

TR

AN

CE

LD

S

LD

S S

EC

-1

LD

S S

EC

-2

CONDUIT UPS TO RACKS

PNL ES401N1

PNL ES401N1

TRAC-40-102BC

PNL ES401N1

TR

102B

OS4

ROOM 111, PNL 401N1

ROOM 111, PNL ES401N1

CHIEF

102A

STAIR #1

WOMEN

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

K:

\C

C G

_P R

O

JE

C

TS

\2

8\

-1

6C

9D

V

IS

N

ID

IQ

(N or th D ak ot a

Io w

a) \4

-2

1-

EH

R M

F ar go , N

D \4

- D es D oc s\

2-

D ra w in gs \W

O R

KI

N

G \E

P-

-1

.d w g 3/

/2

:3

4:

A M

ISSUE FOR BIDOffice of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES

FARGO VA HEALTH CARE SYSTEM

437-21-205

Revisions: Date:

www. bancroft-ae.com

3300 Dundee RD.

Northbrook, IL 60062

T: 847.952.9362

ISSUE FOR BID 03-18-22

3/18/2022

SHEET OF 281

Bancroft Project No: 18-121

ELECTRICAL - BUILDING 40 - ENLARGED

PLANS - FIRST FLOOR

WG BX

EP-40-101

A. CONTACT VA IT PRIOR TO WORKING IN DATA CENTER OR IT CLOSET.

B. USE PRECAUTIONS TO AVOID SNAGGING WIRING OR DAMAGING EQUIPMENT.

C. WHEN NEW TR ROOM(S) ARE CONSTRUCTED, IT COMMUNICATIONS EQUIPMENT WILL

BE MOVED TO NEW TR ROOM. “BIOENGINEERING” TYPE EQUIPMENT; I.E. SECURITY,

NURSE CALL, PHILLIPS, ETC, WILL REMAIN IN ORIGINAL CLOSET, AND MUST REMAIN

OPERATIONAL.

D. PROTECT IT EQUIPMENT FROM DUST, DURING WORK THAT CREATES DUST.

E. SEE PANEL SCHEDULES ON DRAWING SERIES E600 FOR UPS PANEL SCHEDULES AND

UPS CIRCUIT NUMBERS.

F. NORMAL AND EMERGENCY WIRING TO TR ROOM LIGHTS AND RECEPTACLES IS SHOWN

ON INDIVIDUAL EP DRAWINGS. NOTATION FOR EACH CIRCUIT IS (ROOM, PANEL AND

CIRCUIT). CONTRACTOR TO INSTALL NEW 20A BREAKER AND UPDATE PANEL CIRCUIT

INDEX.

G. SEE DRAWING SERIES E700 FOR SINGLE LINE DRAWINGS.

H. NOTE THAT KEY NOTES MAINLY APPLY TO NEW/RELOCATED TR CLOSETS. ELECTRICAL

WORK IS NOT REQUIRED IN EXISTING IT CLOSETS THAT REMAIN OPERATIONAL.

I. POWER TO RACKS / CABINETS IN NEW TR's MUST BE PROVIDED TO THE TOP OF THE

RACKS / CABINETS. NO POWER WIRING ON FLOORS!

J. RECEPTACLES ABOVE RACKS MUST BE NEMA L21-30R, LOCKING RECEPTACLES.

K. INSTALL LIGHTING CONTROLS PER LIGHTING DETAIL ON DETAIL DRAWING E501.

L. INSTALL PANEL EBUPS401WA IN ELECTRIC CLOSET 111.

1. POWER TO RACKS. CONTRACTOR TO SELECT 30A, 3-POLE, 208V/120V CIRCUITS ON PNL

UPS91 BLDG 40 FOR THE FOUR TR RACKS.

2. NORMAL POWER TO ROOM RECEPTACLES, AND LIGHTS. CONTRACTOR TO LOCATE

SPARE NORMAL POWER CIRCUIT IN ELEC. CLOSET ROOM 111, PANELS 401N1, N2 AND

ROUTE THIS CIRCUIT TO TR 102B.

3. EMERGENCY POWER TO ROOM RECEPTACLES AND LIGHTS. CONTRACTOR TO LOCATE

SPARE EMERGENCY POWER CIRCUIT IN ELECTRICAL CLOSET ROOM 111, PANEL ES401N1

AND ROUTE THIS CIRCUIT TO TR 102B.

4. OCCUPANCY SENSOR - HIGH MOUNT.

5. LIGHT FIXTURE FROM PNL ES401N1. CONTACT COR PRIOR TO INSTALLING LIGHT

FIXTURES TO SELECT OPTIMUM LIGHT FIXTURE LOCATION.

6. ONLY BRANCH CIRCUIT IS SHOWN FROM POWER PANEL TO COOLING UNIT. INSTALL

CONDUIT AND WIRE PER DETAIL ON DRAWING E501. CONTRACTOR TO WORK WITH

MECHANICAL CONTRACTOR TO ROUTE POWER AND TUBING TO OUTDOOR UNIT.

ELECTRICAL GENERAL NOTES

I I r 7 r , I r , I r , I r , I r 7

1I I I I I I

0 -~ .

......__ 0

0 -

I I -

" 0

- . .. •• 0

- CJ-----;

I I

- -~ •• 0

- 0 \ \ 0

,...... " oQ " I t--._

C a ' I ' 0

"' 0 ~, -

>- " 0 0 0 ® " ELECTRICAL KEY NOTES . .. ••

" " " 0

I\ a ~ rn bbl rn ~

~ I

I I

I I 11 ~

1 ENLARGED LIGHTING PLAN RM 1028

0 1' 't 4' • ----

I I r 1 r I I I I 1 \ I

~ I I I @-L...J c:::::J- c:::::J - - ~ -

( )---......__ ; o- 0 @

JI

&-- @O r.l• • -

0 7 " - ~ -if ~ @O -

D I I C -

D If I

- D ""- 0

-4- @O I " oD / \ / ( jf I

~ D ( - ~ r---._

L c:::::J---, - il ~ _J 0 C

' L-----, '

' I " ~ ' ' "

CD ~

J { I LJ )

:>- \ / : ' t

I\ I ~ rn d rn ~ ~ ~

I I

~ ~""· I "" "" 0 0 0 0

) ) le

I I

II

I I 11 -

N ED KEYPLAN

-/3()./flu ::===============:~=========;::============:I::========:

BANCROFT ARCHITECTS+ ENGINEERS VA ID□

JMcAllister Snapshot

JMcAllister Rectangle

JMcAllister Text Box

SHEET OF 279

JMcAllister

TR

204C

11ROOM 213, PNL 402W

TO FIRST FLOOR

ROOM 111, PNL ES401N1

UPS CONDUIT FROM

FIRST FLOOR TR ROOM

PA

NE

L 4

W2

ELECTRICAL

PA

NE

L 4

W1

PA

NE

L 4

W3

PA

NE

L 4

W4

TRAC-40-204CA

OPEN

OFFICE

HEARING

ROOM

ADJUNCT CHIEF

OFFICE

204C

OPEN

OFFICE

ADJUNCTION

RECEPTION

STAIR # 1

ROOM 111, PNL ES401N1

TR

204C

OS

ROOM 213, PNL 402W

TO FIRST FLOOR

ROOM 111, PNL ES401N1

HEARING

ROOM

ADJUNCT CHIEF

OFFICE

204C

ADJUNCTION

RECEPTION

STAIR # 1

ACCU-40-102BB

ACCU-40-102BA

ACCU-40-204C

ACCU-40-102BC

6 6

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

K:

\C

C G

_P R

O

JE

C

TS

\2

8\

-1

6C

9D

V

IS

N

ID

IQ

(N or th D ak ot a

Io w

a) \4

-2

1-

EH

R M

F ar go , N

D \4

- D es D oc s\

2-

D ra w in gs \W

O R

KI

N

G \E

P-

-1

.d w g 3/

/2

9:

:1

AM

ISSUE FOR BIDOffice of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES

FARGO VA HEALTH CARE SYSTEM

437-21-205

Revisions: Date:

www. bancroft-ae.com

3300 Dundee RD.

Northbrook, IL 60062

T: 847.952.9362

ISSUE FOR BID 03-18-22

3/18/2022

SHEET OF 281

Bancroft Project No: 18-121

ELECTRICAL - BUILDING 40 - ENLARGED

PLANS - SECOND FLOOR

WG BX

EP-40-102

A. CONTACT VA IT PRIOR TO WORKING IN DATA CENTER OR IT CLOSET.

B. USE PRECAUTIONS TO AVOID SNAGGING WIRING OR DAMAGING EQUIPMENT.

C. WHEN NEW TR ROOM(S) ARE CONSTRUCTED, IT COMMUNICATIONS EQUIPMENT WILL

BE MOVED TO NEW TR ROOM. “BIOENGINEERING” TYPE EQUIPMENT; I.E. SECURITY,

NURSE CALL, PHILLIPS, ETC, WILL REMAIN IN ORIGINAL CLOSET, AND MUST REMAIN

OPERATIONAL.

D. PROTECT IT EQUIPMENT FROM DUST, DURING WORK THAT CREATES DUST.

E. SEE PANEL SCHEDULES ON DRAWING SERIES E600 FOR UPS PANEL SCHEDULES AND

UPS CIRCUIT NUMBERS.

F. NORMAL AND EMERGENCY WIRING TO TR ROOM LIGHTS AND RECEPTACLES IS SHOWN

ON INDIVIDUAL EP DRAWINGS. NOTATION FOR EACH CIRCUIT IS (ROOM, PANEL AND

CIRCUIT). CONTRACTOR TO INSTALL NEW 20A BREAKER AND UPDATE PANEL CIRCUIT

INDEX.

G. SEE DRAWING SERIES E700 FOR SINGLE LINE DRAWINGS.

H. NOTE THAT KEY NOTES MAINLY APPLY TO NEW/RELOCATED TR CLOSETS. ELECTRICAL

WORK IS NOT REQUIRED IN EXISTING IT CLOSETS THAT REMAIN OPERATIONAL.

I. UPS POWER TO RACKS / CABINETS IN NEW TR's MUST BE PROVIDED TO THE TOP OF

THE RACKS / CABINETS. NO POWER WIRING ON FLOORS!

J. RECEPTACLES ABOVE RACKS MUST BE NEMA L21-30R, LOCKING RECEPTACLES.

K. INSTALL LIGHTING CONTROLS PER LIGHTING DETAIL ON DETAIL DRAWING E501.

1. UPS POWER TO RACKS. ROUTE CONDUIT FROM 1st FLOOR ROOM 111, PANEL

EBUPS401WA, AND TERMINATE TO TR RACK RECEPTACLES IN ROOM 204C.

2. NORMAL POWER TO ROOM RECEPTACLES, AND LIGHTS. CONTRACTOR TO LOCATE

SPARE NORMAL POWER CIRCUIT IN ELECTRICAL CLOSET ROOM 204A, PANEL(S) 402 AND

ROUTE THIS CIRCUIT TO TR 40-204C.

3. EMERGENCY POWER TO ROOM RECEPTACLES AND LIGHTS. CONTRACTOR TO LOCATE

SPARE EMERGENCY POWER CIRCUIT ON 1st FLOOR, IN ELECTRICAL CLOSET ROOM 111, PANEL ES401N1 AND ROUTE THIS CIRCUIT TO 2nd FLOOR TR 40-204C.

4. OCCUPANCY SENSOR - HIGH MOUNT.

5. UPS POWER FROM 1st FLOOR TR ROOM 102B INTO 2nd FLOOR TR ROOM 204C.

6. ONLY BRANCH CIRCUIT IS SHOWN FROM POWER PANEL TO COOLING UNIT. INSTALL

CONDUIT AND WIRE PER DETAIL ON DRAWING E501. CONTRACTOR TO WORK WITH

MECHANICAL CONTRACTOR TO ROUTE POWER AND TUBING TO…