Drawings Part 3 of 9.pdf

PDF 12 MB Posted

Attached to
Y1DZ--437-21-205 EHRM Infrastructure Upgrades Construction Fargo, ND
Solicitation number
36C77622B0030
Issued by

About this file

This document provides details for a federal construction contract solicitation. The solicitation seeks construction services for the Fargo VA Health Care System project 437-21-205, EHRM Infrastructure Upgrades in Fargo, North Dakota. Work will include demolition, new construction, plumbing, mechanical, fire protection, electrical systems, asbestos abatement, masonry, structural work and other efforts to upgrade the entire Fargo campus information technology infrastructure to the latest VA and industry standards while minimizing downtime. The solicitation was issued by the Department of Veterans Affairs Technology Acquisition Center Austin. Services are to be provided in accordance with specifications, drawings, codes and regulatory requirements.

View the file

Other files

File Type Posted
Wage Rates - Cass County - 6.17.22.pdf PDF
36C77622B0030 0005.docx DOCX document
Addendum Fiber Duct Bank.pdf PDF
36C77622B0030 0004.docx DOCX document
Technical Question Tracking Sheet - Infra Upgrades - Fargo.docx DOCX document
PCRA 437-21-205 Zone 2.pdf PDF
ICRA Zones.pdf PDF
PCRA 437-21-205 Zone 4.pdf PDF
36C77622B0030 0003.pdf PDF
PCRA 437-21-205 Zone 5.pdf PDF
PCRA 437-21-205 Zone 3.pdf PDF
36C77622B0030 0002.pdf PDF
Site Visit Sign-in Sheet - Fargo.pdf PDF
36C77622B0030 0001.pdf PDF
Wage Rates - Cass County - 4.15.22.pdf PDF
36C77622B0030 0001.pdf PDF
Wage Rates - Cass County - 4.25.22.pdf PDF
Reference Only - Basis of Design BOD Part 3 of 7.pdf PDF
Reference Only - Basis of Design BOD Part 2 of 7.pdf PDF
Reference Only - Basis of Design BOD Part 7 of 7.pdf PDF
Reference Only - Basis of Design BOD Part 6 of 7.pdf PDF
BOD Appendix A ACM Survey Report.pdf PDF
Specifications Vol 01 Rev.pdf PDF
36C77622B0030_1.pdf PDF
Drawings Part 7 of 9.pdf PDF
Reference Only - EHRM Design Alerts 1-8.pdf PDF
COVID-19 Safety Protocols 12-14-21.pdf PDF
Contractor Safety - Environmental Form.docx DOCX document
Reference Only - Basis of Design BOD Part 5 of 7.pdf PDF
Specifications Vol 02 Rev.pdf PDF
Reference Only - Basis of Design BOD Part 1 of 7.pdf PDF
Drawings Part 2 of 9.pdf PDF
Drawings Part 6 of 9.pdf PDF
Drawings Part 8 of 9.pdf PDF
Reference Only - Basis of Design BOD Part 4 of 7.pdf PDF
Drawings Part 9 of 9.pdf PDF
Drawings Part 4 of 9.pdf PDF
Drawings Part 1 of 9.pdf PDF
Drawings Part 5 of 9.pdf PDF
Reference Only - Infra Stdrd for Telecomm Spaces 3.1 - ISTS.pdf PDF
Show all 40

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

B

B

A-12-101

A-12-101

A-12-101

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

K:

\C

C G

_P R

O

JE

C

TS

\2

8\

-1

6C

9D

V

IS

N

ID

IQ

(N or th D ak ot a

Io w

a) \4

-2

1-

EH

R M

F ar go , N

D \4

- D es D oc s\

2-

D ra w in gs \W

O R

KI

N

G \A

-B

-1

.d w g 3/

/2

9:

:2

AM

ISSUE FOR BIDOffice of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES

FARGO VA HEALTH CARE SYSTEM

437-21-205

Revisions: Date:

www. bancroft-ae.com

3300 Dundee RD.

Northbrook, IL 60062

T: 847.952.9362

ISSUE FOR BID 03-18-22

3/18/2022

SHEET OF 279

Bancroft Project No: 18-121

ARCHITECTURE - BUILDING 12 - FIRST

FLOOR & ENLARGED PLANS

DA JM

A-12-101

1. REMOVE EXISTING WALL MOUNTED SERVER RACK PATCH AND REPAIR

WALL TO PROVIDE FOR SMOOTH SURFACE FOR PAINT.

2. REMOVE EXISTING WINDOW ASSEMBLY IN ITS ENTIRETY. PREP OPENING

FOR INFILL CONSTRUCTION.

3. REMOVE EXISTING DOOR, FRAME AND HARDWARE. PREPARE WALL

CONSTRUCTION AT OPENING FOR NEW FRAME.

4. PREPARE LEVEL CONCRETE FLOOR AS REQUIRED TO RECIEVE NEW

SCHEDULED FLOOR FINISH.

5. INSTALL TEMPORARY EDGE GUARD.

6. SUPPLY AND STALL WALK OFF MATS.

7. ENTIRE NORTH WALL REMOVE PAINT SCALE AND PEALS, THEN BRICK

SURFACE TO CREATE A SMOOTH SUBSTRATE FOR NEW PAINT.

NOT USED

1. EXISTING NON-RATED WALLS TO BE BROUGHT TO 1HR RATING. INSTALL

RE-ENTERABLE MECHANICAL FIRESTOP AT ALL PENETRATIONS.

2. REMOVE EXISTING DOOR, FRAME AND HARDWARE TO PREPARE FOR NEW.

3. FIRE EXTINGUISHER CABINET MOUNTED 48" A.F.F. TO CENTERLINE OF

HANDLE.

4. CONTRACTOR TO CONFIRM FIRE-RATED SEALANT AT BASE AND PERIMETER

OF PARTITIONS. IF NOT EXISTING - INSTALL (BOTH SIDES OF PARTITIONS)

TO MAKE 1-HOUR RATED.

5. PAINT OUTSIDE PERIMETER OF GYP. BD. WALLS AND TOP OF CEILING SHAFT

WALL ASSEMBLY.

CONTRACTOR IS REQUIRED TO MAINTAIN ALL RATED PARTITIONS.

SMOKE BARRIER

1 HR FIRE BARRIER

2 HR FIRE BARRIER

SMOKE BARRIER (EXISTING)

1 HR FIRE BARRIER (EXISTING)

2 HR FIRE BARRIER (EXISTING)

C1. INSTALL 1HR RATED CEILING SHAFT WALL ASSEMBLY. SEE

SPEC SECTION 07 84 00 FOR REQUIRMENTS.

C2. PROVIDE AND INSTALL VISQUEEN TYPE PLASTIC SHEET AS

REQUIRED TO MAINTAIN TYPE IV INFECTION CONTROL

PRECAUTIONS DURING CONSTRUCTION OF CEILING SHAFT

WALL. EXTEND AND SEAL TO ROOF DECK/STRUCTURE ABOVE.

A. FOR GENERAL NOTES AND LEGENDS REFER TO SHEET A001.

B. FOR GENERAL INFECTION CONTROL NOTES AND DETAILS REFER TO SHEET GI101.

C. FOR FINISH SCHEDULE REFER TO SHEET AF-601.

D. EXISTING IT/TR/OI&T ROOMS TO REMAIN ACTIVE DURING CONSTRUCTION. G.C. TO PROTECT EQUIPMENT DURING CONSTRUCTION WITH VISQUEEN.

CONTRACTOR TO ENSURE CONTINUOUS OPERATION OF EQUIPMENT.

E. NOT ALL KEY NOTES APPLY TO ALL PLAN SHEETS. G.C. TO APPLY ONLY AS INDICATED PER EACH SHEET.

F. MAINTAIN A 4 ' - 0" CLEAR PATH OF TRAVEL IN THE CORRIDORS AT ALL TIMES.

G. ALL WORK TO BE PERFORMED AS PART OF TR MODIFICATION SHALL BE CONSIDERED AS TYPE IV AND FOLLOW "INFECTION CONTROL PRECAUTIONS

FOR CLASS IV" ON SHEET GI101.

H. APPLY FIRE RATED SEALANT TO ALL EXISTING AND NEW PENETRATIONS IN EXISTING WALLS TO MAKE EXISTING WALLS A 1 HR ASSEMBLY. BASIS OF

DESIGN FOR 1 HR WALL IS UL 419 ASSEMBLY.

4'X8' AC GRADE 3/4" TRADE SIZE FIRE RATED PLYWOOD BACKBOARD PAINTED HIGH GLOSS

WHITE WITH (2) COATS OF FIRE RESISTANT PAINT FOR SERVICE

PROVIDER/SECURITY/VIDEO/ETC. AROUND PERIMETER WALLS OF TRS AND ENTRANCE ROOMS

AS SHOWN. ENSURE THAT FIRE RATING STAMP IS TO REMAIN UNCOVERED BY PAINT.

DENOTES SIGNAGE LOCATION DENOTES NEW CEILING

TR

I 0005

I

I I

I WAREHOUSE

I 1 0006 1 I

L ___ _J

BREAK ROOM

1 0004 1

VAULT

1 oooB 1

BATHROOM

1 0002 1

OFFICE

1 0001 1 cr:::=:::7::'._______'::==:::::E:3:=:=='--,..,-':===::E::3:::::==::'._,..,_ '--=-~=1~1--------"~

NORTH

E9 1

BUILDING 12 - FIRST FLOOR PLAN

• 0 I

I

• II

II

3'-10"

1/8"=1'-0"

WAREHOUSE

1 0006 1

0 ENLARGED DEMO PLAN RM 0005 2 i----------,--------1 / 4" = 1' -o ~ o r r +· a·

WAREHOUSE

1 0006 1

0 ENLARGED PLAN RM 0005 3 r----------1 / 4 -= 1 ' - o" o 1' 2' +· 8'

-/3()./flu

BANCROFT ARCHITECTS+ ENGINEERS

O't4' 8' ----

WAREHOUSE □

1 0006 1

4 REFLECTED CEILING PLAN RM 0005

1/4"=1·-o· 01''l +· 8' ----

VA

GENERAL NOTES

0 DEMO CEILING KEYNOTES 0 DEMOLITION PLAN KEYNOTES

@ CEILING PLAN KEYNOTES @ FLOOR PLAN KEYNOTES

RA TED PARTITION LEGEND

------ ------_a_o_ •o_o_

■ 00-00- ■00-00-

FLOOR PLAN LEGEND

ID□

AutoCAD SHX Text 4/A503

AutoCAD SHX Text 3/A503

AutoCAD SHX Text 4/A503

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 1'

AutoCAD SHX Text 2'

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 1/4"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

ENLARGED DEMO PLAN RM 0005

AutoCAD SHX Text

AutoCAD SHX Text 1'

AutoCAD SHX Text 2'

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 1/4"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

ENLARGED PLAN RM 0005

AutoCAD SHX Text

AutoCAD SHX Text 1'

AutoCAD SHX Text 2'

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 1/4"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

REFLECTED CEILING PLAN RM 0005

AutoCAD SHX Text

DEMOLITION PLAN KEYNOTES

AutoCAD SHX Text

DEMO CEILING KEYNOTES

AutoCAD SHX Text

GENERAL NOTES

AutoCAD SHX Text

FLOOR PLAN KEYNOTES

AutoCAD SHX Text

CEILING PLAN KEYNOTES

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text

AutoCAD SHX Text 2'

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 16'

AutoCAD SHX Text 1/8"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

BUILDING 12 - FIRST FLOOR PLAN

AutoCAD SHX Text

NORTH

AutoCAD SHX Text

DEMOLITION PLAN KEYNOTES

AutoCAD SHX Text

DEMO CEILING KEYNOTES

AutoCAD SHX Text

GENERAL NOTES

AutoCAD SHX Text

FLOOR PLAN KEYNOTES

AutoCAD SHX Text

CEILING PLAN KEYNOTES

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text

RATED PARTITION LEGEND

AutoCAD SHX Text

FLOOR PLAN LEGEND

AutoCAD SHX Text X

JMcAllister Snapshot

JMcAllister Text Box

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

K:

\C

C G

_P R

O

JE

C

TS

\2

8\

-1

6C

9D

V

IS

N

ID

IQ

(N or th D ak ot a

Io w

a) \4

-2

1-

EH

R M

F ar go , N

D \4

- D es D oc s\

2-

D ra w in gs \W

O R

KI

N

G \A

-B

-1

.d w g 3/

/2

9:

:4

AM

ISSUE FOR BIDOffice of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES

FARGO VA HEALTH CARE SYSTEM

437-21-205

Revisions: Date:

www. bancroft-ae.com

3300 Dundee RD.

Northbrook, IL 60062

T: 847.952.9362

ISSUE FOR BID 03-18-22

3/18/2022

SHEET OF 279

Bancroft Project No: 18-121

ARCHITECTURAL - BUILDING 13 - FIRST

FLOOR PLANS

DA JM

A-13-101

1. REMOVE EXISTING WALL MOUNTED SERVER RACK.

2. REMOVE MILLWORK AS REQUIRED TO ACCOMMODATE FIRE

EXTINGUISHER.

1. PROVIDE AND INSTALL WALL MOUNTED TELECOMMUNICATIONS

ENCLOSURE (TE). SEE ELECTRICAL AND TECHNOLOGY DRAWINGS FOR

ADDITIONAL INFORMATION. MOUNT T/ RACK @ 6' - 0" A.F.F.

2. PROVIDE AND INSTALL BRACKET MOUNTED CLEAN AGENT FIRE

EXTINGUISHER. MOUNT AT 48" A.F.F. TO CENTER LINE OF HANDLE.

A. FOR GENERAL NOTES AND LEGENDS REFER TO SHEET A001.

B. FOR GENERAL INFECTION CONTROL NOTES AND DETAILS REFER TO SHEET GI101.

C. FOR FINISH SCHEDULE REFER TO SHEET AF-601.

D. EXISTING IT/TR/OI&T ROOMS TO REMAIN ACTIVE DURING CONSTRUCTION. G.C. TO PROTECT EQUIPMENT DURING CONSTRUCTION WITH VISQUEEN.

CONTRACTOR TO ENSURE CONTINUOUS OPERATION OF EQUIPMENT.

E. NOT ALL KEY NOTES APPLY TO ALL PLAN SHEETS. G.C. TO APPLY ONLY AS INDICATED PER EACH SHEET.

F. MAINTAIN A 4 ' - 0" CLEAR PATH OF TRAVEL IN THE CORRIDORS AT ALL TIMES.

G. ALL WORK TO BE PERFORMED AS PART OF TR MODIFICATION SHALL BE CONSIDERED AS TYPE IV AND FOLLOW "INFECTION CONTROL PRECAUTIONS

FOR CLASS IV" ON SHEET GI101.

H. APPLY FIRE RATED SEALANT TO ALL EXISTING AND NEW PENETRATIONS IN EXISTING WALLS TO MAKE EXISTING WALLS A 1 HR ASSEMBLY. BASIS OF

DESIGN FOR 1 HR WALL IS UL 419 ASSEMBLY.

DENOTES SIGNAGE LOCATION

>-~l)

\ •• 4- J 2 1 I

IE "" i, BACK STAIRWAY '

CLEAN LINEN

MECHANICAL ROOM 'OILED

I NEN

J ELEC. □ □ □ □ □

( SERV.

I \__ LJ "- ~ X L./ I

I 2 t----. LUNCH - ~I SHOWE V I'- SHOWER / BACK ENTRY 1 r- J OFFICE ROOM CART WASH AREA y "'7 ROOM ROOM _yr >-.J '77 - - -

ISSUE\__ --{ECEIVING

N E9 (De--~-/8~-~1~-?.I_NG_1_3 _-_FIR_s_,T_'F7-. 0-~-~ _DE_M_~LITION PLAN

BACK STAIRWAY

MECHANICAL ROOM

654-321 i, J ELEC.

( SERV.

0'" ~

/ BACK ENTRY • 1 ,-..__ -@

t=::'.::::~====3::::~ -c___,Y -D

CLEAN LINEN

LUNCH

OFFICE ROOM

ISSUE \__---n....1..u

N

I

X L./

SHOWER/"" I'- SHOWER

ROOM ROOM

E9 (De--~-/8~-~1~-?.I_NG_1_3 _-_FIR_s_,T_,'.7-. 0-~-~ _PL_A_~ ..

13 ~

- a,1-\.CA I // ' '

BANCROFT ARCHITECTS+ ENGINEERS V

CART WASH AREA

'. OILED

II------"'' N EN

u..i.i:r-/4 EC EIVI NG

VA

GENERAL NOTES

FLOOR PLAN LEGEND

0 DEMOLlllON PLAN KEYNOTES @ FLOOR PLAN KEYNOTES

I I

:c==========~::==========;:c============:l;:========;I

ID□

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

DN

AutoCAD SHX Text

UP

AutoCAD SHX Text

CLEAN LINEN

AutoCAD SHX Text

SOILED

AutoCAD SHX Text

LINEN

AutoCAD SHX Text

RECEIVING

AutoCAD SHX Text

ELEC.

AutoCAD SHX Text

SERV.

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

LUNCH

AutoCAD SHX Text

ROOM

AutoCAD SHX Text

ISSUE

AutoCAD SHX Text

SHOWER

AutoCAD SHX Text

ROOM

AutoCAD SHX Text

ROOM

AutoCAD SHX Text

SHOWER

AutoCAD SHX Text

CART WASH AREA

AutoCAD SHX Text

MECHANICAL ROOM

AutoCAD SHX Text

BACK ENTRY

AutoCAD SHX Text

BACK STAIRWAY

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

DN

AutoCAD SHX Text

UP

AutoCAD SHX Text

CLEAN LINEN

AutoCAD SHX Text

SOILED

AutoCAD SHX Text

LINEN

AutoCAD SHX Text

RECEIVING

AutoCAD SHX Text

ELEC.

AutoCAD SHX Text

SERV.

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

LUNCH

AutoCAD SHX Text

ROOM

AutoCAD SHX Text

ISSUE

AutoCAD SHX Text

SHOWER

AutoCAD SHX Text

ROOM

AutoCAD SHX Text

ROOM

AutoCAD SHX Text

SHOWER

AutoCAD SHX Text

CART WASH AREA

AutoCAD SHX Text

MECHANICAL ROOM

AutoCAD SHX Text

BACK ENTRY

AutoCAD SHX Text

BACK STAIRWAY

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 2'

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 16'

AutoCAD SHX Text 1/8"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

BUILDING 13 - FIRST FLOOR DEMOLITION PLAN

AutoCAD SHX Text

AutoCAD SHX Text 2'

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 16'

AutoCAD SHX Text 1/8"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

BUILDING 13 - FIRST FLOOR PLAN

AutoCAD SHX Text

DEMOLITION PLAN KEYNOTES

AutoCAD SHX Text

GENERAL NOTES

AutoCAD SHX Text

FLOOR PLAN KEYNOTES

AutoCAD SHX Text X

AutoCAD SHX Text N

AutoCAD SHX Text N

AutoCAD SHX Text X

AutoCAD SHX Text

FLOOR PLAN LEGEND

JMcAllister Snapshot

JMcAllister

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

K:

\C

C G

_P R

O

JE

C

TS

\2

8\

-1

6C

9D

V

IS

N

ID

IQ

(N or th D ak ot a

Io w

a) \4

-2

1-

EH

R M

F ar go , N

D \4

- D es D oc s\

2-

D ra w in gs \W

O R

KI

N

G \A

-B

-1

.d w g 3/

/2

9:

:5

AM

ISSUE FOR BIDOffice of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES

FARGO VA HEALTH CARE SYSTEM

437-21-205

Revisions: Date:

www. bancroft-ae.com

3300 Dundee RD.

Northbrook, IL 60062

T: 847.952.9362

ISSUE FOR BID 03-18-22

3/18/2022

SHEET OF 279

Bancroft Project No: 18-121

ARCHITECTURAL - BUILDING 30 -

BASEMENT FLOOR PLANS

DA JM

A-30-101

1. REMOVE EXISTING WALL MOUNTED SERVER RACK. 1. PROVIDE AND INSTALL FLOOR MOUNTED TELECOMMUNICATIONS

ENCLOSURE (TE). SEE ELECTRICAL AND TECHNOLOGY DRAWINGS FOR

ADDITIONAL INFORMATION.

2. PAINT WALL. SEE ROOM FINISH SCHEDULE.

3. PROVIDE AND INSTALL BRACKET MOUNTED CLEAN AGENT FIRE

EXTINGUISHER. MOUNT AT 48" A.F.F. TO CENTER LINE OF HANDLE.

A. FOR GENERAL NOTES AND LEGENDS REFER TO SHEET A001.

B. FOR GENERAL INFECTION CONTROL NOTES AND DETAILS REFER TO SHEET GI101.

C. FOR FINISH SCHEDULE REFER TO SHEET AF-601.

D. EXISTING IT/TR/OI&T ROOMS TO REMAIN ACTIVE DURING CONSTRUCTION. G.C. TO PROTECT EQUIPMENT DURING CONSTRUCTION WITH VISQUEEN.

CONTRACTOR TO ENSURE CONTINUOUS OPERATION OF EQUIPMENT.

E. NOT ALL KEY NOTES APPLY TO ALL PLAN SHEETS. G.C. TO APPLY ONLY AS INDICATED PER EACH SHEET.

F. MAINTAIN A 4 ' - 0" CLEAR PATH OF TRAVEL IN THE CORRIDORS AT ALL TIMES.

G. ALL WORK TO BE PERFORMED AS PART OF TR MODIFICATION SHALL BE CONSIDERED AS TYPE IV AND FOLLOW "INFECTION CONTROL PRECAUTIONS

FOR CLASS IV" ON SHEET GI101.

H. APPLY FIRE RATED SEALANT TO ALL EXISTING AND NEW PENETRATIONS IN EXISTING WALLS TO MAKE EXISTING WALLS A 1 HR ASSEMBLY. BASIS OF

DESIGN FOR 1 HR WALL IS UL 419 ASSEMBLY.

DENOTES SIGNAGE LOCATION

N

I ' 0-/;;;\ ~

11tttttt1111

~ . lltftttf1111 .

ffi 0 ~~l~~ING 30 - FLOOR PLAN

11111,111111

. 111111111111

GENERAL NOTES

FLOOR PLAN LEGEND

0 DEMOLITION PLAN KEYNOTES @ FLOOR PLAN KEYNOTES

02'4' B' 16'

0 2' 4' II' ,..

I I

13 ~

- a,1-\.CA I // ' '

:c==========~::==========;:c============:l;:========;I

BANCROFT ARCHITECTS+ ENGINEERS V VA ID□

AutoCAD SHX Text

BASEMENT

AutoCAD SHX Text

BASEMENT

AutoCAD SHX Text

BASEMENT

AutoCAD SHX Text

BASEMENT

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 2'

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 16'

AutoCAD SHX Text 1/8"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

BUILDING 30 - DEMO PLAN

AutoCAD SHX Text

AutoCAD SHX Text 2'

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 16'

AutoCAD SHX Text 1/8"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

BUILDING 30 - FLOOR PLAN

AutoCAD SHX Text

GENERAL NOTES

AutoCAD SHX Text

FLOOR PLAN KEYNOTES

AutoCAD SHX Text X

AutoCAD SHX Text

DEMOLITION PLAN KEYNOTES

AutoCAD SHX Text

GENERAL NOTES

AutoCAD SHX Text

FLOOR PLAN KEYNOTES

AutoCAD SHX Text X

AutoCAD SHX Text N

AutoCAD SHX Text N

AutoCAD SHX Text X

AutoCAD SHX Text

FLOOR PLAN LEGEND

JMcAllister Snapshot

JMcAllister

A-40-101

A-40-101

A-40-101

A-40-101

TELE / EQUIP

102B

CHIEF

102A

STAIR #1

WOMEN

MEN

HAC

TELE / EQUIP

102B

CHIEF

102A

102B

CHIEF

102A

TR

102B

B B

D1 B

CHIEF

102A

TR

102B

TELE / EQUIP

102B

CHIEF

102A

GENERAL NOTES

A. FOR GENERAL NOTES AND LEGENDS REFER TO SHEET A001.

B. FOR GENERAL INFECTION CONTROL NOTES AND DETAILS REFER TO SHEET GI101.

C. FOR FINISH SCHEDULE REFER TO SHEET AF-601.

D. EXISTING IT/TR/OI&T ROOMS TO REMAIN ACTIVE DURING CONSTRUCTION. G.C. TO PROTECT EQUIPMENT DURING CONSTRUCTION WITH VISQUEEN. CONTRACTOR TO ENSURE

CONTINUOUS OPERATION OF EQUIPMENT.

E. NOT ALL KEY NOTES APPLY TO ALL PLAN SHEETS. G.C. TO APPLY ONLY AS INDICATED PER EACH SHEET.

F. MAINTAIN A 4 ' - 0" CLEAR PATH OF TRAVEL IN THE CORRIDORS AT ALL TIMES.

G. ALL WORK TO BE PERFORMED AS PART OF TR MODIFICATION SHALL BE CONSIDERED AS TYPE IV AND FOLLOW "INFECTION CONTROL PRECAUTIONS FOR CLASS IV" ON SHEET GI101.

H. APPLY FIRE RATED SEALANT TO ALL EXISTING AND NEW PENETRATIONS IN EXISTING WALLS TO MAKE EXISTING WALLS A 1 HR ASSEMBLY. BASIS OF DESIGN FOR 1 HR WALL IS UL 419

ASSEMBLY.

CONTRACTOR IS REQUIRED TO MAINTAIN ALL RATED PARTITIONS.

SMOKE BARRIER

1 HR FIRE BARRIER

2 HR FIRE BARRIER

SMOKE BARRIER (EXISTING)

1 HR FIRE BARRIER (EXISTING)

2 HR FIRE BARRIER (EXISTING)

RATED PARTITION LEGEND

1. G.C. TO CAREFULLY REMOVE EQUIPMENT WITHIN EXISTING OI&T OR IRM ROOM AND TURN

OVER TO VA.

2. EXISTING HANDRAIL, WALL BASE AND CARPET TO BE MODIFIED TO ACCEPT NEW DOOR.

3. SUPPLY AND INSTALL WALK OFF MAT(S). SEE DETAILS ON SHEET GI101.

4. REMOVE EXISTING DOOR, FRAME AND HARDWARE IN ITS ENTIRETY. INFILL WALL WITH

METAL STUDS AND DRYWALL. ALIGN WITH EXISTING WALLS, PATCH, LEVEL AND FINISH

TO MATCH EXISTING WALL FINISH.

5. REMOVE EXISTING DOOR, FRAME AND HARDWARE IN ITS ENTIRETY FOR INSTALLATION

OF NEW DOOR AND FRAME. PORTIONS OF EXISTING WALL TO BE DEMOLISHED TO

RECEIVE NEW LARGER SIZE DOOR AND FRAME ASSEMBLY. PATCH ADJACENT WALLS TO

MATCH ADJACENT CONDITIONS. RELOCATE ALL WALL MOUNTED ITEMS INCLUDING ROOM

SIGNAGE, CHAIR RAILS, CORNER GUARDS AND WALL MOUNTED ADJACENT TO EXISTING

CORRIDOR DOOR AND REINSTALL AT NEW DOOR LOCATION.

6. REMOVE EXISTING DOOR, FRAME AND HARDWARE. PREPARE WALL CONSTRUCTION AT

OPENING FOR NEW FRAME.

7. REMOVE EXISTING CARPET AND REMOVE ALL ASSOCIATED ADHESIVE. PREP AND LEVEL

EXISTING CONCRETE FLOOR TO RECEIVE NEW FINISH.

8. G.C. TO CAREFULLY REMOVE ALL CASEWORK AND PLUMBING FIXTURE. CAP SUPPLY AT

MAINS TO PREVENT DEADLEGS.

9. INSTALL TEMPORARY FLAME RESISTANT CONSTRUCTION PANELS WITH DOOR ENTRY.

BASIS OF DESIGN IS EDGE GUARD.

DEMOLITION PLAN KEYNOTES

D1. STRUCTURE IS FIRE PROTECTED. FIRE PROOFING MAY BE DISTURBED

DURING DEMOLITION. PATCH ANY FIREPROOFING ON STEEL THAT IS

MISSING.

D2. REMOVE EXISTING CEILING GRID TO EXTENT REQUIRED TO

ACCOMMODATE NEW PARTITIONS.

D3. REMOVE LIGHT FIXTURE.

D4. SEE FIRE PROTECTION DRAWINGS FOR SPRINKLER HEAD MODIFICATIONS.

DEMO CEILING KEYNOTES

X

X

1. FINISH WALL CORNER TO CORNER AND FLOOR TO CEILING. PRIOR TO PAINTING THE

ENTIRE WALL SURFACE WITH (1) FINISH COAT OF PAINT, PROVIDE (1) PRIME COAT AND

(2) FINISH COATS OVER PATCHED/REPAIRED WALL SURFACES.

2. INSTALL NEW HANDRAIL, NEW CRASH RAIL AND WALL BASE TO CREATE LONG

CONTINUOUS RUN. EXTEND HANDRAIL, CRASH RAIL AND WALL BASE TO NEXT

ASSEMBLY JOINT. FOR DETAILS SEE SHEET A-502.

3. MODIFY EXISTING WALL CONSTRUCTION TO CONSTRUCT A WALL ASSEMBLY THAT IS

1HR RATED PARTITION, AS IDENTIFIED AS WALL TYPE A ON SHEET A501. THIS INCLUDES

ADDING 58" GYP. BOARD TO UNDERSIDE OF DECK ON BOTH SIDES OF WALL. BASIS OF

DESIGN FOR 1HR WALL IS UL 419 ASSEMBLY.

4. PAINT FULL EXTENT OF EXPOSED WALL. SEE FINISH SCHEDULE.

5. WINDOW OPENING INFILL CONSTRUCTION.

6. CONTRACTOR TO CONFIRM FIRE RATED SEALANT AT HEAD AND BASE OF PARTITION. IF

NOT EXISTING - INSTALL (BOTH SIDES OF PARTITION) TO MAKE 1-HR RATING.

7. PROVIDE 1' - 0" X 1' - 0" ACCESS HATCH TO BE LOCATED FOR VALVE ACCESS.

8. FIRE EXTINGUISHER CABINET MOUNTED 48" A.F.F. TO CENTERLINE OF HANDLE.

FLOOR PLAN KEYNOTES

CEILING PLAN KEYNOTESX

X

FLOOR PLAN LEGEND

4'X8' AC GRADE 3/4" TRADE SIZE FIRE RATED PLYWOOD BACKBOARD PAINTED HIGH GLOSS

WHITE WITH (2) COATS OF FIRE RESISTANT PAINT FOR SERVICE

PROVIDER/SECURITY/VIDEO/ETC. AROUND PERIMETER WALLS OF TRS AND ENTRANCE ROOMS

AS SHOWN. ENSURE THAT FIRE RATING STAMP IS TO REMAIN UNCOVERED BY PAINT.

C1. CONTRACTOR TO PAINT UNDERSIDE OF DECK WHERE FIREPROOFING OR

INSULATION ISN'T PRESENT BRIGHT WHITE. SEE ROOM FINISH SCHEDULE ,

FOR BID PURPOSES ASSUME ENTIRE CEILING PERIMETER IS TO BE PAINTED.

C2. INSTALL NEW CEILING GRID AND EDGE ANGLE. INSTALL NEW CEILING TILES

TO MATCH EXISTING.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

K:

\C

C G

_P R

O

JE

C

TS

\2

8\

-1

6C

9D

V

IS

N

ID

IQ

(N or th D ak ot a

Io w

a) \4

-2

1-

EH

R M

F ar go , N

D \4

- D es D oc s\

2-

D ra w in gs \W

O R

KI

N

G \A

-B

-1

.d w g 3/

/2

:0

0:

A M

ISSUE FOR BIDOffice of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES

FARGO VA HEALTH CARE SYSTEM

437-21-205

Revisions: Date:

www. bancroft-ae.com

3300 Dundee RD.

Northbrook, IL 60062

T: 847.952.9362

ISSUE FOR BID 03-18-22

3/18/2022

SHEET OF 279

Bancroft Project No: 18-121

ARCHITECTURAL - BUILDING 40 - FIRST

FLOOR PLANS

DA JM

A-40-101

10. G.C. TO CAREFULLY REMOVE FURNITURE AND TURN OVER TO VA.

11. PREPARE AND LEVEL EXISTING CONCRETE FLOOR AS REQUIRED TO RECEIVE NEW

SCHEDULED FLOOR FINISH.

12. REMOVE PARTITION IN ITS ENTIRETY. PATCH AS REQUIRED ADJACENT WALL TO REMAIN

TO RECEIVE NEW CONSTRUCTION OF RATED WALL PARTITION.

13. PREPARE OPENING IN WALL FOR NEW FIRE EXTINGUISHER CABINET. SEE DETAIL 1/A-502.

14. PREPARE OPENING IN EXISTING PARTITION TO RECEIVE NEW DOOR AND FRAME. SEE

DOOR SCHEDULE.

DENOTES SIGNAGE LOCATION DENOTES NEW CEILING

9. CONTRACTOR TO CONFIRM FIRE-RATED SEALANT AT HEAD AND BASE OF PARTITION. IF

NOT EXISTING INSTALL (BOTH SIDES OF PARTITION) TO MAKE 2-HR RATED.

10. G.C. TO CAREFULLY REMOVE FURNITURE AND TURN OVER TO VA.

11. PREPARE AND LEVEL EXISTING CONCRETE FLOOR AS REQUIRED TO RECEIVE NEW

SCHEDULED FLOOR FINISH.

12. REMOVE PARTITION IN ITS ENTIRETY. PATCH AS REQUIRED ADJACENT WALL TO REMAIN

TO RECEIVE NEW CONSTRUCTION OF RATED WALL PARTITION.

13. PREPARE OPENING IN WALL FOR NEW FIRE EXTINGUISHER CABINET. SEE DETAIL 1/A-502.

14. PREPARE OPENING IN EXISTING PARTITION TO RECEIVE NEW DOOR AND FRAME. SEE

DOOR SCHEDULE.

15. REMOVE EXISTING WINDOW ASSEMBLY IN ITS ENTIRETY. PREP OPENING FOR INFILL.

I I_ I I

( I\ (

-11

/,,, II

I II

I II

(PHASE-2)

>•.,(-'' I .>J;:( . ~· ·~

~h::::i~·';'=r ---

(PHASE-1)

I I\

NORTH

EB CD

I

0 ENLARGED DEMO PLAN RM 1028

1/4"=1'-0" 0 1' 2' 4' ,.

IX] [!I

[!I

M JYl

.L ~

BUILDING 40 - FIRST FLOOR PLAN

1/a"=l'-o"

=:::::u---a: ___ ..,------- ~~ I

0 ENLARGED DEMO CEILING PLAN RM 1028

1/4"=1'-0" 0 1' l' 4' ,.

-/3()./flu

BANCROFT ARCHITECTS+ ENGINEERS

I _I_

I I

( I\ I

I I

[!I

[!I

~ l.) ~

0 2' 4' ,. 16'

-------'---------rr+--""""'"'-1 I

6 }----_.

-\("\ -v-

I A__) A_,, I

' =TI: I

I

I I

II

I

'\ I --

--00-00 < uu Jfl I I

~ LJVu 0 .Q I.Q ,Q

[ I 0 TI TI 'V' ,'i?i.

ID<'I I\

\ ~< I I nn

I =

6/Qg03

I t=------{ 9

0 ENLARGED PLAN RM 1028 4 l-------- 0 ENLARGED CEILING PLAN RM 1028 1/4n=1'-0n O 1' 2' 4' 8' 1/4"=1'-0" 0 1' 2' 4' ,.

VA

0 □

0 □

••••••••• ••••••••• _ D_O_ •o_o _

■00-00- 100-00-

ID□

AutoCAD SHX Text 5/A503

AutoCAD SHX Text

(PHASE-2)

AutoCAD SHX Text

(PHASE-2)

AutoCAD SHX Text

(PHASE-1)

AutoCAD SHX Text

(PHASE-1)

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6/A503

AutoCAD SHX Text 6/A503

AutoCAD SHX Text 5/A503

AutoCAD SHX Text

AutoCAD SHX Text 2'

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 16'

AutoCAD SHX Text 1/8"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

BUILDING 40 - FIRST FLOOR PLAN

AutoCAD SHX Text

NORTH

AutoCAD SHX Text

AutoCAD SHX Text 1'

AutoCAD SHX Text 2'

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 1/4"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

ENLARGED PLAN RM 102B

AutoCAD SHX Text

AutoCAD SHX Text 1'

AutoCAD SHX Text 2'

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 1/4"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

ENLARGED DEMO PLAN RM 102B

AutoCAD SHX Text

AutoCAD SHX Text 1'

AutoCAD SHX Text 2'

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 1/4"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

ENLARGED DEMO CEILING PLAN RM 102B

AutoCAD SHX Text

AutoCAD SHX Text 1'

AutoCAD SHX Text 2'

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 1/4"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

ENLARGED CEILING PLAN RM 102B

AutoCAD SHX Text X

JMcAllister Snapshot

JMcAllister

ADJUNCT CHIEF

OFFICE

204C

TR

202A

OPEN

OFFICE

HEARING

ROOM

ADJUNCTION

RECEPTION

STAIR # 1

HAC

A-40-102 A-40-102

A-40-102

A-40-102

TR

202A

STAIR # 1

2A

B B

B

ADJUNCT CHIEF

202A

STAIR # 1

ADJUNCT CHIEF

202A

STAIR # 1

TR

202A

STAIR # 1

GENERAL NOTES

A. FOR GENERAL NOTES AND LEGENDS REFER TO SHEET A001.

B. FOR GENERAL INFECTION CONTROL NOTES AND DETAILS REFER TO SHEET GI101.

C. FOR FINISH SCHEDULE REFER TO SHEET AF-601.

D. EXISTING IT/TR/OI&T ROOMS TO REMAIN ACTIVE DURING CONSTRUCTION. G.C. TO PROTECT EQUIPMENT DURING CONSTRUCTION WITH VISQUEEN. CONTRACTOR TO ENSURE

CONTINUOUS OPERATION OF EQUIPMENT.

E. NOT ALL KEY NOTES APPLY TO ALL PLAN SHEETS. G.C. TO APPLY ONLY AS INDICATED PER EACH SHEET.

F. MAINTAIN A 4 ' - 0" CLEAR PATH OF TRAVEL IN THE CORRIDORS AT ALL TIMES.

G. ALL WORK TO BE PERFORMED AS PART OF TR MODIFICATION SHALL BE CONSIDERED AS TYPE IV AND FOLLOW "INFECTION CONTROL PRECAUTIONS FOR CLASS IV" ON SHEET GI101.

H. APPLY FIRE RATED SEALANT TO ALL EXISTING AND NEW PENETRATIONS IN EXISTING WALLS TO MAKE EXISTING WALLS A 1 HR ASSEMBLY. BASIS OF DESIGN FOR 1 HR WALL IS UL 419

ASSEMBLY.

CONTRACTOR IS REQUIRED TO MAINTAIN ALL RATED PARTITIONS.

SMOKE BARRIER

1 HR FIRE BARRIER

2 HR FIRE BARRIER

SMOKE BARRIER (EXISTING)

1 HR FIRE BARRIER (EXISTING)

2 HR FIRE BARRIER (EXISTING)

RATED PARTITION LEGEND

1. G.C. TO CAREFULLY REMOVE EQUIPMENT WITHIN EXISTING OI&T OR IRM ROOM AND TURN

OVER TO VA.

2. EXISTING HANDRAIL, WALL BASE AND CARPET TO BE MODIFIED TO ACCEPT NEW DOOR.

3. SUPPLY AND INSTALL WALK OFF MAT(S). SEE DETAILS ON SHEET GI101.

4. REMOVE EXISTING DOOR, FRAME AND HARDWARE IN ITS ENTIRETY. INFILL WALL WITH

METAL STUDS AND DRYWALL. ALIGN WITH EXISTING WALLS, PATCH, LEVEL AND FINISH

TO MATCH EXISTING WALL FINISH.

5. REMOVE EXISTING DOOR, FRAME AND HARDWARE IN ITS ENTIRETY FOR INSTALLATION

OF NEW DOOR AND FRAME. PORTIONS OF EXISTING WALL TO BE DEMOLISHED TO

RECEIVE NEW LARGER SIZE DOOR AND FRAME ASSEMBLY. PATCH ADJACENT WALLS TO

MATCH ADJACENT CONDITIONS. RELOCATE ALL WALL MOUNTED ITEMS INCLUDING ROOM

SIGNAGE, CHAIR RAILS, CORNER GUARDS AND WALL MOUNTED ADJACENT TO EXISTING

CORRIDOR DOOR AND REINSTALL AT NEW DOOR LOCATION.

6. REMOVE EXISTING DOOR, FRAME AND HARDWARE. PREPARE WALL CONSTRUCTION AT

OPENING FOR NEW FRAME.

7. REMOVE EXISTING CARPET AND REMOVE ALL ASSOCIATED ADHESIVE. PREP AND LEVEL

EXISTING CONCRETE FLOOR TO RECEIVE NEW FINISH.

8. G.C. TO CAREFULLY REMOVE ALL CASEWORK AND PLUMBING FIXTURE. CAP SUPPLY AT

MAINS TO PREVENT DEADLEGS.

9. INSTALL TEMPORARY FLAME RESISTANT CONSTRUCTION PANELS WITH DOOR ENTRY.

BASIS OF DESIGN IS EDGE GUARD.

DEMOLITION PLAN KEYNOTES

D1. STRUCTURE IS FIRE PROTECTED. FIRE PROOFING MAY BE DISTURBED

DURING DEMOLITION. PATCH ANY FIREPROOFING ON STEEL THAT IS

MISSING.

D2. REMOVE EXISTING CEILING GRID TO EXTENT REQUIRED TO

ACCOMMODATE NEW PARTITIONS.

D3. REMOVE LIGHT FIXTURE.

D4. SEE FIRE PROTECTION DRAWINGS FOR SPRINKLER HEAD MODIFICATIONS.

DEMO CEILING KEYNOTES

X

X

1. FINISH WALL CORNER TO CORNER AND FLOOR TO CEILING. PRIOR TO PAINTING THE

ENTIRE WALL SURFACE WITH (1) FINISH COAT OF PAINT, PROVIDE (1) PRIME COAT AND

(2) FINISH COATS OVER PATCHED/REPAIRED WALL SURFACES.

2. INSTALL NEW HANDRAIL, NEW CRASH RAIL AND WALL BASE TO CREATE LONG

CONTINUOUS RUN. EXTEND HANDRAIL, CRASH RAIL AND WALL BASE TO NEXT

ASSEMBLY JOINT. FOR DETAILS SEE SHEET A-502.

3. MODIFY EXISTING WALL CONSTRUCTION TO CONSTRUCT A WALL ASSEMBLY THAT IS

1HR RATED PARTITION, AS IDENTIFIED AS WALL TYPE A ON SHEET A501. THIS INCLUDES

ADDING 58" GYP. BOARD TO UNDERSIDE OF DECK ON BOTH SIDES OF WALL. BASIS OF

DESIGN FOR 1HR WALL IS UL 419 ASSEMBLY.

4. PAINT FULL EXTENT OF EXPOSED WALL. SEE FINISH SCHEDULE.

5. WINDOW OPENING INFILL CONSTRUCTION.

6. CONTRACTOR TO CONFIRM FIRE RATED SEALANT AT HEAD AND BASE OF PARTITION. IF

NOT EXISTING - INSTALL (BOTH SIDES OF PARTITION) TO MAKE 1-HR RATING.

7. PROVIDE 1' - 0" X 1' - 0" ACCESS HATCH TO BE LOCATED FOR VALVE ACCESS.

8. FIRE EXTINGUISHER CABINET MOUNTED 48" A.F.F. TO CENTERLINE OF HANDLE.

FLOOR PLAN KEYNOTES

CEILING PLAN KEYNOTESX

X

FLOOR PLAN LEGEND

4'X8' AC GRADE 3/4" TRADE SIZE FIRE RATED PLYWOOD BACKBOARD PAINTED HIGH GLOSS

WHITE WITH (2) COATS OF FIRE RESISTANT PAINT FOR SERVICE

PROVIDER/SECURITY/VIDEO/ETC. AROUND PERIMETER WALLS OF TRS AND ENTRANCE ROOMS

AS SHOWN. ENSURE THAT FIRE RATING STAMP IS TO REMAIN UNCOVERED BY PAINT.

C1. CONTRACTOR TO PAINT UNDERSIDE OF DECK WHERE FIREPROOFING OR

INSULATION ISN'T PRESENT BRIGHT WHITE. SEE ROOM FINISH SCHEDULE ,

FOR BID PURPOSES ASSUME ENTIRE CEILING PERIMETER IS TO BE PAINTED.

C2. INSTALL NEW CEILING GRID AND EDGE ANGLE. INSTALL NEW CEILING TILES

TO MATCH EXISTING.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

K:

\C

C G

_P R

O

JE

C

TS

\2

8\

-1

6C

9D

V

IS

N

ID

IQ

(N or th D ak ot a

Io w

a) \4

-2

1-

EH

R M

F ar go , N

D \4

- D es D oc s\

2-

D ra w in gs \W

O R

KI

N

G \A

-B

-1

.d w g 3/

/2

:0

1:

A M

ISSUE FOR BIDOffice of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES

FARGO VA HEALTH CARE SYSTEM

437-21-205

Revisions: Date:

www. bancroft-ae.com

3300 Dundee RD.

Northbrook, IL 60062

T: 847.952.9362

ISSUE FOR BID 03-18-22

3/18/2022

SHEET OF 279

Bancroft Project No: 18-121

ARCHITECTURAL - BUILDING 40 -

SECOND FLOOR & ENLARGED PLANS

DA JM

A-40-102

10. G.C. TO CAREFULLY REMOVE FURNITURE AND TURN OVER TO VA.

11. PREPARE AND LEVEL EXISTING CONCRETE FLOOR AS REQUIRED TO RECEIVE NEW

SCHEDULED FLOOR FINISH.

12. REMOVE PARTITION IN ITS ENTIRETY. PATCH AS REQUIRED ADJACENT WALL TO REMAIN

TO RECEIVE NEW CONSTRUCTION OF RATED WALL PARTITION.

13. PREPARE OPENING IN WALL FOR NEW FIRE EXTINGUISHER CABINET. SEE DETAIL 1/A-502.

14. PREPARE OPENING IN EXISTING PARTITION TO RECEIVE NEW DOOR AND FRAME. SEE

DOOR SCHEDULE.

DENOTES SIGNAGE LOCATION

9. CONTRACTOR TO CONFIRM FIRE-RATED SEALANT AT HEAD AND BASE OF PARTITION. IF

NOT EXISTING INSTALL (BOTH SIDES OF PARTITION) TO MAKE 2-HR RATED.

10. G.C. TO CAREFULLY REMOVE FURNITURE AND TURN OVER TO VA.

11. PREPARE AND LEVEL EXISTING CONCRETE FLOOR AS REQUIRED TO RECEIVE NEW

SCHEDULED FLOOR FINISH.

12. REMOVE PARTITION IN ITS ENTIRETY. PATCH AS REQUIRED ADJACENT WALL TO REMAIN

TO RECEIVE NEW CONSTRUCTION OF RATED WALL PARTITION.

13. PREPARE OPENING IN WALL FOR NEW FIRE EXTINGUISHER CABINET. SEE DETAIL 1/A-502.

14. PREPARE OPENING IN EXISTING PARTITION TO RECEIVE NEW DOOR AND FRAME. SEE

DOOR SCHEDULE.

15. REMOVE EXISTING WINDOW ASSEMBLY IN ITS ENTIRETY. PREP OPENING FOR INFILL.

A502

A502

I I I I I

C,T,U, 204A

~ r Cl Cl

\__ "213 204 B"---I _J

\__ I I I I LJ

f-----i z:

. :::r::: Cl Cl Cl

LJ

w

212 ~

I\

__,,;AMER LEGIDN7 AMVETS .

TAIR _/ ~·2 21n 209 2_8 u u

NDVA MNDVA I"----.. DAV

211 _;210A 2 0 9A"-- ~OBA 207~ 207

206 l....!!!!!:: ,- I

J J J j .L ~ .L rnDAr.;r=- Q I I

NORTH

EB 1 BUILDING 40 - SECOND FLOOR PLAN

1/8"=1'-o"

- - -+--7-_ ..,.__.,, I 0 - , - - , - -1- - ,:'--=--r--

1 I I I I

I

• --+---b--1 __ I __ D2 g ,r---

1 II IJ....-11 --I D 3

• _ -t-_ j'=----

___ --:!J_ _ D4

• I I I "' I I _ -t __ 1r--__ 1 ___ -,t __ t- _ :n--

• I ~ II I 0

- -t- - j!=----1---i- - t- - g 0 I I I ....--'-----'-,

- -+- --1- - -1- --+- - - :

, _::::] 0 0 rn r-vv- V\ /\ A__A "-.___,)

I I

:::;"I I

I I / \ I --,...

u ~ \__ \

I w< uu

I I ( _) l..) L/ L.J

:) Q Q Q

\__ r

Cl 5' CJ 'V'I~~

I I I\

~<M~~ \

~ Lioo_ C:

~ r u 0

VFw __/~06A 205~ 205

I I

02'4' 8' ,., ----

I

I

0 0 0

0 ~4~~9 40 ROOF PLAN

-/3()./flu

BANCROFT ARCHITECTS+ ENGINEERS

IJt--1:,>-i It-- 0 .....___, l o,lt--

0 1' 2' 4' 8'

0 □

0 □

••••••••• • •••••••• _ D_O_ •o_o _

■00-00- 100-00-

::================:::==========;~=======~I::======:

VA ID□

AutoCAD SHX Text C.T.U.

AutoCAD SHX Text

MECHANICAL

AutoCAD SHX Text

MEN

AutoCAD SHX Text

STAIR

AutoCAD SHX Text #2

AutoCAD SHX Text

AutoCAD SHX Text 204A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 210A

AutoCAD SHX Text

AMER

AutoCAD SHX Text

LEGION

AutoCAD SHX Text

STORAGE &

AutoCAD SHX Text

AutoCAD SHX Text

AMVETS

AutoCAD SHX Text

AutoCAD SHX Text 209A

AutoCAD SHX Text

NDVA

AutoCAD SHX Text

AutoCAD SHX Text 208A

AutoCAD SHX Text

DAV

AutoCAD SHX Text 205A

AutoCAD SHX Text 207A

AutoCAD SHX Text 206A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

MNDVA

AutoCAD SHX Text

VFW

AutoCAD SHX Text

AutoCAD SHX Text 204B

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6/A503

AutoCAD SHX Text 5/A503

AutoCAD SHX Text 5/A503

AutoCAD SHX Text 6/A503

AutoCAD SHX Text

AutoCAD SHX Text 2'

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 16'

AutoCAD SHX Text 1/8"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

BUILDING 40 - SECOND FLOOR PLAN

AutoCAD SHX Text

NORTH

AutoCAD SHX Text

AutoCAD SHX Text 1'

AutoCAD SHX Text 2'

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 1/4"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

ENLARGED DEMO PLAN RM 202A

AutoCAD SHX Text

AutoCAD SHX Text 1'

AutoCAD SHX Text 2'

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 1/4"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

ENLARGED PLAN RM 202A

AutoCAD SHX Text

AutoCAD SHX Text 1'

AutoCAD SHX Text 2'

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 1/4"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

REFLECTED CEILING DEMO PLAN RM 202A

AutoCAD SHX Text

AutoCAD SHX Text 1'

AutoCAD SHX Text 2'

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 1/4"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

REFLECTED CEILING PLAN RM 202A

AutoCAD SHX Text X

AutoCAD SHX Text

AutoCAD SHX Text 1'

AutoCAD SHX Text 2'

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 1/4"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

BLDG 40 ROOF PLAN

JMcAllister Snapshot

JMcAllister

TR

VESTIBULE

A-51-102

A-51-102

A-51-102

A-51-102

C

TR

VESTIBULE

TR

VESTIBULE

A-51-101

A-51-101

A-51-101

A-51-101

AREA OF RESCUE

ASSISTANCE

(2 WHEELCHAIRS).

SEE CIVIL

DRAWINGS FOR

FURTHER DETAIL.

STEP UP, 7" RISER

TR

VESTIBULE

EXIT 2 - EXISTING DOOR TO REMAIN. PROTECT

DURING CONSTRUCTION. PROVIDE SIGN PLACARD

READING: "NOT AN EXIT. USE EXIT AT WEST END."

EXISTING FENCE

PROVIDE SIGN PLACARDS READING:

"EAST EXIT TEMPORARILY CLOSED.

UTILIZE EXIT AT WEST END."

PROTECT EXISTING WINDOW

DURING CONSTRUCTION

TEMPORARY

CONSTRUCTION

FENCE

EXIT DISTANCE =

99'-0"

COMMON PATH OF

TRAVEL = 117'-0"

EXIT 1

TEMPORARY

CONSTRUCTION FENCE

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

K:

\C

C G

_P R

O

JE

C

TS

\2

8\

-1

6C

9D

V

IS

N

ID

IQ

(N or th D ak ot a

Io w

a) \4

-2

1-

EH

R M

F ar go , N

D \4

- D es D oc s\

2-

D ra w in gs \W

O R

KI

N

G \A

-B

-1

.d w g 3/

/2

:0

3:

A M

ISSUE FOR BIDOffice of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES

FARGO VA HEALTH CARE SYSTEM

437-21-205

Revisions: Date:

www. bancroft-ae.com

3300 Dundee RD.

Northbrook, IL 60062

T: 847.952.9362

ISSUE FOR BID 03-18-22

3/18/2022

SHEET OF 279

Bancroft Project No: 18-121

ARCHITECTURAL - BUILDING 51 -

ENLARGED PLANS & ELEVATIONS

DA JM

A-51-101

1. INSTALL DUST CONTAINMENT AND INFECTION

CONTROL PANEL SYSTEM.

2. INSTALL STICKY MATS BOTH SIDES OF PANEL

DOOR.

3. SEE 4/GI101 FOR INFECTION CONTROL /

CONSTRUCTION SIGNAGE TO BE POSTED.

4. REMOVE SIDING AND INSULATION TO EXTENT

REQUIRED TO ALLOW FOR INSTALLATION OF

ADDITIONAL WALLS AND ROOF CONSTRUCTION.

PREP SUBSTRATE TO CLEANLY RECEIVE NEW

ADJACENT WALL CONSTRUCTION.

5. REMOVE EXISTING WALL MOUNTED SERVER

RACK.

1. 4'X8' AC GRADE 3/4" TRADE SIZE FIRE RATED PLYWOOD BACKBOARD PAINTED HIGH

GLOSS WHITE WITH (2) COATS OF FIRE RESISTANT PAINT FOR SERVICE

PROVIDER/SECURITY/VIDEO/ETC. AROUND PERIMETER WALLS OF TR.

2. GUTTER

3. DOWNSPOUT

4. SNOW GUARD SYSTEM

5. FIRE EXTINGUISHER AND CABINET

6. SIGN 55. SEE SIGNAGE SCHEDULE ON AS-601.

7. SIGN 56. SEE SIGNAGE SCHEDULE ON AS-601.

CONTRACTOR IS REQUIRED TO MAINTAIN ALL RATED PARTITIONS.

SMOKE BARRIER

1 HR FIRE BARRIER

2 HR FIRE BARRIER

SMOKE BARRIER (EXISTING)

1 HR FIRE BARRIER (EXISTING)

2 HR FIRE BARRIER (EXISTING)

A. FOR GENERAL NOTES AND LEGENDS REFER TO SHEET A001.

B. FOR GENERAL INFECTION CONTROL NOTES AND DETAILS REFER TO SHEET GI101.

C. FOR FINISH SCHEDULE REFER TO SHEET AF-601.

EXIT LIMITATIONS ANALYSIS

· BUILDING OCCUPANCY = BUSINESS

· FULLY SPRINKLERED

· GROSS SF = 3,875

· OCCUPANT LOAD = 26

· MAXIMUM ALLOWABLE COMMON PATH OF TRAVEL IS 100'-0"

·· A SINGLE EXIT IS PERMITTED BY NFPA 101, 39.2.4.6 (EXISTING BUSINESS) FOR

SPINKLERED BUILDINGS WITH A COMMON PATH OF TRAVEL NOT EXCEEDING

100'-0"

·· OTHERWISE, TWO MEANS OF EGRESS ARE REQUIRED

SAFETY PROCEDURE

· OFFICES 1008, 1010, 1011, 1013 SHALL NOT BE OCCUPIED WHEN EXIT 2 IS REQUIRED

TO BE CLOSED DURING CONSTRUCTION

DENOTES NEW CEILING

MECHANICAL

ROOM

1024 1025 L

HAC JA

1028 n

TOILET LJ

WORK AREA

TOILET

TORAG 1021

WAITING

OFFICE

RECEPTION

OFFICE

1018 1017 OFFICE

OFFICE RAG

OFFICE

OFFICE

OFFICE

OFFICE

1 BUILDING 51 - FIRST FLOOR PLAN

OFFICE

3'-o"

MIN.

OFFIC:F

I I I I v-EJ I I I I I I ~-51-10~ I I I

OFFICE

OFFIC:F

omcE

OFFICE

omcE

1012 1011

TOILET OFFICE

OFFICE

CONF./BREAK

9/A-51-101 • 10'-10"

10'-10"

C 7/A-51-101

OFFICE I

u u.J u Li" b:, I ---

OFFICE

1 O"

I

N -

' .,..-----.._ --'-+-----i I U')

I

'\i •· .- · ... :. .

' ~. ~-- .' ~ .. ~"""-,+--+----+-f-

0 2' 4' B'

-0

~~ "' I

CX) - ~

IX)

16'

OFFICE

MECHANICAL

ROOM

1028 n

TOILET LJ

WORK AREA

TOILET

OFFICE

RECEPTION

OFFICE

1018 1017 OFFICE

OFFICE RAG

OFFICE

OFFICE

OFFICE

omcE

BUILDING 51 - CONSTRUCTION LIFE SAFETY PLAN

1/8"=1·-o·

9/A-51-101

-51-1

I SLOPE

~1 g

VI

I SLOPE

7/A-51-101

-51-10

-51-10

OFFICE

omcE

OFFICE

- 11 '-:P'---0 o 2· 4• a· 16' ----

CONSTRUCTION LIFE SAFETY SUMMARY

METAL ROOF PANELS

GENERAL NOTES

FLOOR PLAN KEYNOTES

00 DEMOLITION PLAN KEYNOTES

RATED PAR I I I ION LEDGED

•o_o_

■□□- □o- 100-00-

CEILING PLAN LEDGED

,,.-- METAL RAKE CLEAT

-"ilc'n -~ METAL SUPPORT ANGLES

,,------ PREFINISHED RAKE TRIM. MATCH

DEPTH OF EAVE.

0,__~_

~-=~-A_

_R_G_ED_DE_M_O_P_LA_~-,-. ,-. -.-. --,. 0,__E_

~-=~--!R_G_ED_PL_A_N ______

-,. -, -,. --,. 0,__-~

~-=~--!R_G_E_D_C_EIL_IN_G_P_LA_~-,-. ,-. -.-. --,. 0-~-1~-=~-0 .. R_G_ED_ROO_F_P_L~-~--,-. -.-. --,.

\ I , =

~ CONTINUOUS METAL CLEAT

F::;,:~ BRICK VENEER

-- I __ __ ::::::t __

STANDING SEAM

METAL ROOF

SNOW GUARD

METAL SIDING

P/ ROOF

' EL +119'- 10"

DOWNSPOUT - COORDINATE

LOCATION WITH INTEGRAL

SPLASH PAN. SEE CIVIL.

RELOCATE LIGHT FIXTURE

FROM ABOVE EXISTING

ALUMINUM ENTRANCE DOOR

T/ FLOOR

' EL +100'- O"

PROVIDE AND INSTALL DOUBLE

AUTHENTICATION CARD READER

AS PER SPECIFICATIONS

BUILDING 51 ADDITION - NORll-i ELEVATION 1/B"=l'-o" 0 2' 4' B' 18' ---- 8

METAL SIDING

I

_I - - --1:: = = =b -i------r-- -_ -__ - ~ ~

-51-10

BUILDING 51 ADDITION - EAST ELEVATION

1/8"=1 ·-o·

FLASH METAL ROOF

SYSTEM INTO

EXISTING SIDING

P/ ROOF

EL +119'- 10"

GUTTER EDGE W /

DOWNSPOUT

FACE BRICK

PRECAST PANELS

~ TI FLOOR

ci_ +100·- o"

0 'J' 4' ,. 18'

-/3()./flu

BANCROFT ARCHITECTS+ ENGINEERS

STANDING SEAM METAL ROOF --~

SNOW GUARD~

FACE BRICK

P/ ROOF •

EL +119'- 10"

NEW DOWNSPOUT - -

FABRICATE TO DRAIN

TO EXISTING GRAVEL

DRAINAGE BED

EXISTING FENCE ~

PRECAST PANELS

~ ~ +~~~~- o"

C-------BC-----------jE

EXISTING DOWNSPOUT - MODIFY TO

I _ _ _ ALLOW ROOM FOR NEW DOWNSPOUT

EXISTING GRAVEL DRAINAGE BED

J

-51-10

BUILDING 51 ADDITION - SOUTH ELEV A TION

1/8"=1'-o" o 2· ,.. e· 1e·

VA

,,----- EXISTING SIDING

~- CONTINUOUS METAL ANGLE

ATTACHED TO EXISTING SUBSTRATE

~- VAPOR BARRIER MEMBRANE

EXPANSION JOINT TRIM. SLIDE

TRIM UNDER EXISTING SIDING.

EXPANSION JOINT CLEAT

METAL ROOF PANELS

LIGHT GAUGE

STEEL TRUSS -

SEE STRUCTURAL

FIRE RATED WALL

- SEE PLAN

2" EXPANSION JOINT

.,.._____ EXISTING WALL

ROOF EXP JT DTL AT WALL

1/B"=l'-o" 0 2' 4' ff 18' ----

® ~~~~ DETAIL AT BRICK VENEER 'l.iii'~· ·--· iiiii·~· =~18• n

METAL ROOF PANELS ,,.-- MET AL RAKE CLEAT

~- METAL SUPPORT ANGLES

,,------ PREFINISHED RAKE TRIM. MATCH

DEPTH OF EAVE.

~+~~'====:""'i--~- METAL STUD FRAMING

~~k~ E~•-----~ CONTINUOUS METAL CLEAT

...____ PREFINISHED METAL FASCIA.

EXTEND UP BEHIND METAL CLEAT.

'--- SCREEN SOFFIT VENT

PREFINISHED METAL S-SLIP

RECEIVER FOR SOFFIT SCREEN

STEEL SIDING J-CHANNEL

'------- STEEL SIDING

ROOF DETAIL AT SIDING

1/8"=1·-o· D 2' 4' ,. 16' ----

ID□

AutoCAD SHX Text

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

AutoCAD SHX Text A-51-102

AutoCAD SHX Text

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text A-51-102

AutoCAD SHX Text

SLOPE

AutoCAD SHX Text

SLOPE

AutoCAD SHX Text

SLOPE

AutoCAD SHX Text

SLOPE

AutoCAD SHX Text A-51-102

AutoCAD SHX Text

AutoCAD SHX Text A-51-101

AutoCAD SHX Text

AutoCAD SHX Text A-51-101

AutoCAD SHX Text

AutoCAD SHX Text A-51-101

AutoCAD SHX Text

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text A-51-102

AutoCAD SHX Text

AutoCAD SHX Text

MECHANICAL

AutoCAD SHX Text

ROOM

AutoCAD SHX Text

AutoCAD SHX Text

TOILET

AutoCAD SHX Text

AutoCAD SHX Text

TOILET

AutoCAD SHX Text

AutoCAD SHX Text

WAITING

AutoCAD SHX Text

AutoCAD SHX Text

VESTIBULE

AutoCAD SHX Text

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

AutoCAD SHX Text

CONF./BREAK

AutoCAD SHX Text

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

AutoCAD SHX Text

RECEPTION

AutoCAD SHX Text

AutoCAD SHX Text

STORAGE

AutoCAD SHX Text

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

AutoCAD SHX Text

STORAGE

AutoCAD SHX Text

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

AutoCAD SHX Text

TOILET

AutoCAD SHX Text

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

AutoCAD SHX Text

WORK AREA

AutoCAD SHX Text

AutoCAD SHX Text

DATA

AutoCAD SHX Text

AutoCAD SHX Text

HAC

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

T/ FLOOR EL +100'- 0"

AutoCAD SHX Text

P/ ROOF EL +119'- 10"

AutoCAD SHX Text

STANDING SEAM METAL ROOF

AutoCAD SHX Text

SNOW GUARD

AutoCAD SHX Text

METAL SIDING

AutoCAD SHX Text

DOWNSPOUT - COORDINATE LOCATION WITH INTEGRAL SPLASH PAN. SEE CIVIL.

AutoCAD SHX Text

RELOCATE LIGHT FIXTURE FROM ABOVE EXISTING ALUMINUM ENTRANCE DOOR

AutoCAD SHX Text

PROVIDE AND INSTALL DOUBLE AUTHENTICATION CARD READER AS PER SPECIFICATIONS

AutoCAD SHX Text

AutoCAD SHX Text A-51-102

AutoCAD SHX Text

T/ FLOOR EL +100'- 0"

AutoCAD SHX Text

AutoCAD SHX Text 7.5

AutoCAD SHX Text

P/ ROOF EL +119'- 10"

AutoCAD SHX Text

FACE BRICK

AutoCAD SHX Text

GUTTER EDGE W/ DOWNSPOUT

AutoCAD SHX Text

METAL SIDING

AutoCAD SHX Text

PRECAST PANELS

AutoCAD SHX Text

FLASH METAL ROOF SYSTEM INTO EXISTING SIDING

AutoCAD SHX Text

AutoCAD SHX Text A-51-102

AutoCAD SHX Text

T/ FLOOR EL +100'- 0"

AutoCAD SHX Text

P/ ROOF EL +119'- 10"

AutoCAD SHX Text

STANDING SEAM METAL ROOF

AutoCAD SHX Text

SNOW GUARD

AutoCAD SHX Text

FACE BRICK

AutoCAD SHX Text

PRECAST PANELS

AutoCAD SHX Text

EXISTING FENCE

AutoCAD SHX Text

NEW DOWNSPOUT - FABRICATE TO DRAIN TO EXISTING GRAVEL DRAINAGE BED

AutoCAD SHX Text

EXISTING DOWNSPOUT - MODIFY TO ALLOW ROOM FOR NEW DOWNSPOUT

AutoCAD SHX Text

EXISTING GRAVEL DRAINAGE BED

AutoCAD SHX Text

AutoCAD SHX Text A-51-102

AutoCAD SHX Text A-51-102

AutoCAD SHX Text

AutoCAD SHX Text

MECHANICAL

AutoCAD SHX Text

ROOM

AutoCAD SHX Text

AutoCAD SHX Text

TOILET

AutoCAD SHX Text

AutoCAD SHX Text

TOILET

AutoCAD SHX Text

AutoCAD SHX Text

WAITING

AutoCAD SHX Text

AutoCAD SHX Text

VESTIBULE

AutoCAD SHX Text

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

AutoCAD SHX Text

CONF./BREAK

AutoCAD SHX Text

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

AutoCAD SHX Text

RECEPTION

AutoCAD SHX Text

AutoCAD SHX Text

STORAGE

AutoCAD SHX Text

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

AutoCAD SHX Text

STORAGE

AutoCAD SHX Text

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

AutoCAD SHX Text

TOILET

AutoCAD SHX Text

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

AutoCAD SHX Text

WORK AREA

AutoCAD SHX Text

AutoCAD SHX Text

DATA

AutoCAD SHX Text

AutoCAD SHX Text

HAC

AutoCAD SHX Text A-51-102

AutoCAD SHX Text

EXISTING SIDING

AutoCAD SHX Text

CONTINUOUS METAL ANGLE ATTACHED TO EXISTING SUBSTRATE

AutoCAD SHX Text

EXPANSION JOINT TRIM. SLIDE TRIM UNDER EXISTING SIDING.

AutoCAD SHX Text

EXPANSION JOINT CLEAT

AutoCAD SHX Text

VAPOR BARRIER MEMBRANE

AutoCAD SHX Text

METAL ROOF PANELS

AutoCAD SHX Text

LIGHT GAUGE STEEL TRUSS - SEE STRUCTURAL

AutoCAD SHX Text

FIRE RATED WALL - SEE PLAN

AutoCAD SHX Text

EXISTING WALL

AutoCAD SHX Text

2" EXPANSION JOINT

AutoCAD SHX Text

PREFINISHED RAKE TRIM. MATCH DEPTH OF EAVE.

AutoCAD SHX Text

METAL ROOF PANELS

AutoCAD SHX Text

METAL SUPPORT ANGLES

AutoCAD SHX Text

CONTINUOUS METAL CLEAT

AutoCAD SHX Text

BRICK VENEER

AutoCAD SHX Text

METAL RAKE CLEAT

AutoCAD SHX Text

PREFINISHED RAKE TRIM. MATCH DEPTH OF EAVE.

AutoCAD SHX Text

METAL ROOF PANELS

AutoCAD SHX Text

METAL SUPPORT ANGLES

AutoCAD SHX Text

CONTINUOUS METAL CLEAT

AutoCAD SHX Text

PREFINISHED METAL S-SLIP RECEIVER FOR SOFFIT SCREEN

AutoCAD SHX Text

METAL RAKE CLEAT

AutoCAD SHX Text

PREFINISHED METAL FASCIA. EXTEND UP BEHIND METAL CLEAT.

AutoCAD SHX Text

SCREEN SOFFIT VENT

AutoCAD SHX Text

STEEL SIDING J-CHANNEL

AutoCAD SHX Text

STEEL SIDING

AutoCAD SHX Text

METAL STUD FRAMING

AutoCAD SHX Text

AutoCAD SHX Text 1'

AutoCAD SHX Text 2'

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 1/4"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

ENLARGED DEMO PLAN

AutoCAD SHX Text

AutoCAD SHX Text 1'

AutoCAD SHX Text 2'

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 1/4"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

ENLARGED PLAN

AutoCAD SHX Text

AutoCAD SHX Text 1'

AutoCAD SHX Text 2'

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 1/4"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

ENLARGED ROOF PLAN

AutoCAD SHX Text

AutoCAD SHX Text 1'

AutoCAD SHX Text 2'

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 1/4"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

ENLARGED CEILING PLAN

AutoCAD SHX Text

DEMOLITION PLAN KEYNOTES

AutoCAD SHX Text

GENERAL NOTES

AutoCAD SHX Text

FLOOR PLAN KEYNOTES

AutoCAD SHX Text X

AutoCAD SHX Text

AutoCAD SHX Text 2'

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 16'

AutoCAD SHX Text 1/8"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

BUILDING 51 - FIRST FLOOR PLAN

AutoCAD SHX Text

RATED PARTITION LEDGED

AutoCAD SHX Text

AutoCAD SHX Text 2'

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 16'

AutoCAD SHX Text 1/8"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

BUILDING 51 ADDITION - NORTH ELEVATION

AutoCAD SHX Text

AutoCAD SHX Text 2'

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 16'

AutoCAD SHX Text 1/8"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

BUILDING 51 ADDITION - EAST ELEVATION

AutoCAD SHX Text

AutoCAD SHX Text 2'

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 16'

AutoCAD SHX Text 1/8"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

BUILDING 51 ADDITION - SOUTH ELEVATION

AutoCAD SHX Text

AutoCAD SHX Text 2'

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 16'

AutoCAD SHX Text 1/8"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

BUILDING 51 - CONSTRUCTION LIFE SAFETY PLAN

AutoCAD SHX Text 7/A-51-101

AutoCAD SHX Text 8/A-51-101

AutoCAD SHX Text 9/A-51-101

AutoCAD SHX Text

CONSTRUCTION LIFE SAFETY SUMMARY

AutoCAD SHX Text 7/A-51-101

AutoCAD SHX Text 8/A-51-101

AutoCAD SHX Text 9/A-51-101

AutoCAD SHX Text

AutoCAD SHX Text 2'

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 16'

AutoCAD SHX Text 1/8"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

ROOF EXP JT DTL AT WALL

AutoCAD SHX Text

AutoCAD SHX Text 2'

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 16'

AutoCAD SHX Text 1/8"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

ROOF DETAIL AT SIDING

AutoCAD SHX Text

AutoCAD SHX Text 2'

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 16'

AutoCAD SHX Text 1/8"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

ROOF DETAIL AT BRICK VENEER

AutoCAD SHX Text

CEILING PLAN LEDGED

JMcAllister Snapshot

JMcAllister

A-51-102

A-51-102

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

K:

\C

C G

_P R

O

JE

C

TS

\2

8\

-1

6C

9D

V

IS

N

ID

IQ

(N or th D ak ot a

Io w

a) \4

-2

1-

EH

R M

F ar go , N

D \4

- D es D oc s\

2-

D ra w in gs \W

O R

KI

N

G \A

-B

-1

.d w g 3/

/2

9:

:1

AM

ISSUE FOR BIDOffice of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES

FARGO VA HEALTH CARE SYSTEM

437-21-205

Revisions: Date:

www. bancroft-ae.com

3300 Dundee RD.

Northbrook, IL 60062

T: 847.952.9362

ISSUE FOR BID 03-18-22

3/18/2022

SHEET OF 279

Bancroft Project No: 18-121

ARCHITECTURAL - BUILDING 51 -

SECTIONS AND DETAILS

DA JM

A-51-102

PREFINISHED METAL STANDING -~

SEAM ROOF PANELS

ICE AND WATER SHIELD AT -~

BOTTOM 48" OF ROOF

CONTINUOUS FLASHING

PREFINISHED METAL FASCIA AND GUTTER.

MATCH SHAPE/Sn'LE OF EXISTING

GUTTER ON ADJACENT BUILDING.

GUTTER HANGER BRACKET -~

METAL END TRACK AT

END OF TRUSS

PREFINISHED METAL FASCIA. EXTEND

UP BEHIND GUTTER. FACE ANCHOR

THROUGH SOFFIT TO FRAMING.

SCREEN SOFFIT VENT (APPROX. 2" WIDTH)

PREFINISHED METAL S-SLIP RECEIVER

FOR SOFFIT SCREEN

GALVANIZED CONTINUOUS METAL

L -BRACKET TO SUPPORT S-SLIP RECEIVER

BUILDING 51 - EAVE DETAIL AT SIDING

1-1/2"=1'-o"

CONTINUOUS FLASHING

METAL END TRACK AT END OF

TRUSS

PREFINISHED METAL FASCIA AND GUTTER. +"-...-.:;,....,

MATCH SHAPE/Sn'LE OF EXISTING

GUTTER ON ADJACENT BUILDING.

SCREEN SOFFIT VENT (APPROX.

2" WIDTH)

'i' B.O. FIN. CLG.

9'-0"

STEEL LAP SIDING - 6"

EXPOSURE

2" RIGID INSULATION

MOISTURE BARRIER

1 /2" FIBERGLASS MAT GYPSUM SHEATHING --

6" METAL STUD W/ BATT INSULATION -~

5/8" GYPSUM BOARD

FLEXIBLE FLASHING W/ STAINLESS STEEL DRIP

EDGE. INSERT DRIP EDGE INTO SAWCUT IN SLAB

AND FILL WITH CONTINUOUS BED OF SEALANT.

LOXON XP (OR VA APPROVED EQUAL)

WATERPROOFING MASONRY COATING EXTEND MIN

2" BELLOW CONCRETE STOOP OR WALK

STOOP- CONG. OVER DECK--~

SEE STRUCT. DWGS.

I .

1/2'

SUSPENDED

A.C.T. CEILING

SCHED. BASE -

)XP.

½ ISOLATION

JOINT WITH

COMPRESSIBLE

FILLER

•. ~7'--------jg • , : • - ". . 11, A . • ... ·. ----~-~ -~-- _ ... , .. · .. •,,: ~ __ _.~ _·_ -..:..--,-.....:., ·r· L

VOID BELOW STOOP- SEE

STRUCT. DWGS.

. -..... · .r . ~.

: ... · .J .. ·•.

• A • J--:- - .• •

.•• 1 ..

. I ...

. . J

'!·- · I •.

• I : . i-

2' POLYS1YRENE

INSULATION AS

SPECIFIED

· .. I· :J::' ~;1--.~ CONC. FND. WALL

I :·+ ··. ~ AND FTG, 1YP.-

• • _ •1 •• ~ 1 SEE STRUCT.

_ .. _.. -~ ,. · • • DWGS.

.. .. . _. r :- -. -.. · . . ·L·~·· ..

CD BUILDING 51 - SECTION 11--------

3/4"=1'-o" , 11,· ,· , I'

MANUFACTURER'S METAL RIDGE

TRIM WITH PERFORATED VENT

1 1/t

COMPOSITE DECK

SEE STRUCT. DWGS.

8" CM

2-1/2'' MTL

STUDS @ 16

O.C.- EA. SID

u

E

5/8" GYPSUM BD

EA. SID E

SCHED. BASE-1'/P

1/2'' ISOLATIO

JOINT- EA. SID ~~

2" POLYS1YEREN

INSULATION A

SPECIFIED, 1YP

E s

· s '

STEEL BEAM, SEE

STRUCTURAL DWGS

1 HR RATED WALL

ASSEMBLY TO UNDERSIDE

OF CONCRETE/METAL

DECK ABOVE

1 HR RATED WALL

ASSEMBLY TO UNDERSIDE

OF CONCRETE/METAL

DECK ABOVE

L

/I CONC. FOUNDATION

/ , WALL AND FOOTING

SEE STRUCTURAL

DRWGS.

0 BUILDING 51 - SECTION 2 ------

3 / 4" = 1 '-o" o 111 ,. 2· :s·

CONTINUOUS FLASHING

PREFINISHED METAL FASCIA AND

GUTTER. MATCH SHAPE/Sn'LE OF

EXISTING GUTTER ON ADJACENT

BUILDING.

T.O CMU

13'-4"

...._...._-J..__ METAL END TRACK AT END

OF TRUSS

---._ ___ SCREEN SOFFIT VENT

(APPROX. 2.5" WIDTH)

~--- CONTINUOUS PREFINISHED

METAL L -BRACKET TO HOLD

SCREEN SOFFIT VENT

BUILDING 51 - EA VE DETAIL AT BRICK

1-1/2"=1'-0" 0 .......-- '0

,. 1 1ft I

STANDING SEAM STEEL METAL ROOF OVER 30# ROOFING

FELT OVER DENSDECK OVER PLYWOOD DECK OVER LIGHT

GAUGE STEEL TRUSSES. PROVIDE "HIGH-TEMPERATURE" 1YPE

ICE AND WATER SHIELD MEMBRANE AT BOTTOM 48" OF ROOF.

~- LIGHT GAUGE STEEL ROOF

TRUSSES- SEE STRUCT.

CONTINUOUS

FLASHING

PREFINISHED METAL

FASCIA AND GUTTER.

MATCH SHAPE/S1YLE OF 7 EXISTING GUTTER ON

ADJACENT BUILDING.

T.O CMU'i' 13'-4"

I METAL END TRACK AT

_J END OF TRUSS

B.O. TRUSS

11'-7"

T.O. BEAM

• 11 '-2"

SCREEN SOFFIT VENT

(APPROX. 2.5" WIDTH)

12" FOIL FACED BATT

INSULATION

CMU BOND BEAMS,

1YP.- SEE STRUCT.

DWGS.

------- FACE BRICK

------- AIR SPACE

....i------

----- MASONRY TIES @ 16"

O.C. VERT.

,.-.,.-- ~=,---- ------- 3" RIGID INSULA Tl ON

8" NOMINAL CMU -,

5/8" GYPSUM BOARD

2 1 /2'' METAL STUDS

@ 16" O.C.

1 /2'' ISOLATION JOINT

WITH COMPRESSIVE

FILLER

SLAB ON GRADE

SEE STRUCT. DWGS.

.,,,.-- FLUID-APPLIED VAPOR

BARRIER RETARDER

EXTEND UP AND OVER

CMU WALL

l""'l-J<..----,=-PRE-CAST WATER-TABLE

TO MATCH EXISTING

INSTALL WEEP VENTS AT

BASE @ 24' O.C.

tftLJ._.'.4'--:,;r- FLEXIBLE FLASHING

,,.------ STAINLESS STEEL DRIP

EDGE :.,. r ,__ .-· -.. ~, -. ,___,,_,,_ " . ~• ~. '--1" T.O. o~.:'6~"' ~g ~ ~ ~ ·~ • • •

· ·· · : ·• · FIN. PAVEMENT

2" POLYS1YERENE _.1.:..-----· tt1-~ ,.: •: :·•' COMPRESSIBLE

INSULATION AS • • · JOINT FILLER

SPECIFIED l 1'-5" l LOXON XP (OR VA

, ' APPROVED EQUAL)

WATERPROOFING MASONRY

COATING EXTEND MIN. 2"

CONG. FOUNDATION ~

WALL AND FOOTING- 1'\

SEE STRUCTURAL \ '\

DRWGS.

I

. . '4~ .. -·~ •, . ··. ... . . .· .

... 4 ... . .. .. . ·~ •• ..

BELOW CONCRETE STOOP

OR WALK

0 BUILDING 51 - SECTION 3 1--------

3/4":1'-o" o 112· r 2· 3•

-- I

-/3()./flu

BANCROFT ARCHITECTS+ ENGINEERS

EXIST. BUILDING

EXIST. RIGID INSULATION

EXIST. STEEL LAP SIDING

P.T. BLOCKING…