Drawings Part 3 of 9.pdf
PDF 12 MB Posted
- Solicitation number
- 36C77622B0030
About this file
This document provides details for a federal construction contract solicitation. The solicitation seeks construction services for the Fargo VA Health Care System project 437-21-205, EHRM Infrastructure Upgrades in Fargo, North Dakota. Work will include demolition, new construction, plumbing, mechanical, fire protection, electrical systems, asbestos abatement, masonry, structural work and other efforts to upgrade the entire Fargo campus information technology infrastructure to the latest VA and industry standards while minimizing downtime. The solicitation was issued by the Department of Veterans Affairs Technology Acquisition Center Austin. Services are to be provided in accordance with specifications, drawings, codes and regulatory requirements.
View the file
Other files
Show all 40
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
B
B
A-12-101
A-12-101
A-12-101
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
K:
\C
C G
_P R
O
JE
C
TS
\2
8\
-1
6C
9D
V
IS
N
ID
IQ
(N or th D ak ot a
Io w
a) \4
-2
1-
EH
R M
F ar go , N
D \4
- D es D oc s\
2-
D ra w in gs \W
O R
KI
N
G \A
-B
-1
.d w g 3/
/2
9:
:2
AM
ISSUE FOR BIDOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES
FARGO VA HEALTH CARE SYSTEM
437-21-205
Revisions: Date:
www. bancroft-ae.com
3300 Dundee RD.
Northbrook, IL 60062
T: 847.952.9362
ISSUE FOR BID 03-18-22
3/18/2022
SHEET OF 279
Bancroft Project No: 18-121
ARCHITECTURE - BUILDING 12 - FIRST
FLOOR & ENLARGED PLANS
DA JM
A-12-101
1. REMOVE EXISTING WALL MOUNTED SERVER RACK PATCH AND REPAIR
WALL TO PROVIDE FOR SMOOTH SURFACE FOR PAINT.
2. REMOVE EXISTING WINDOW ASSEMBLY IN ITS ENTIRETY. PREP OPENING
FOR INFILL CONSTRUCTION.
3. REMOVE EXISTING DOOR, FRAME AND HARDWARE. PREPARE WALL
CONSTRUCTION AT OPENING FOR NEW FRAME.
4. PREPARE LEVEL CONCRETE FLOOR AS REQUIRED TO RECIEVE NEW
SCHEDULED FLOOR FINISH.
5. INSTALL TEMPORARY EDGE GUARD.
6. SUPPLY AND STALL WALK OFF MATS.
7. ENTIRE NORTH WALL REMOVE PAINT SCALE AND PEALS, THEN BRICK
SURFACE TO CREATE A SMOOTH SUBSTRATE FOR NEW PAINT.
NOT USED
1. EXISTING NON-RATED WALLS TO BE BROUGHT TO 1HR RATING. INSTALL
RE-ENTERABLE MECHANICAL FIRESTOP AT ALL PENETRATIONS.
2. REMOVE EXISTING DOOR, FRAME AND HARDWARE TO PREPARE FOR NEW.
3. FIRE EXTINGUISHER CABINET MOUNTED 48" A.F.F. TO CENTERLINE OF
HANDLE.
4. CONTRACTOR TO CONFIRM FIRE-RATED SEALANT AT BASE AND PERIMETER
OF PARTITIONS. IF NOT EXISTING - INSTALL (BOTH SIDES OF PARTITIONS)
TO MAKE 1-HOUR RATED.
5. PAINT OUTSIDE PERIMETER OF GYP. BD. WALLS AND TOP OF CEILING SHAFT
WALL ASSEMBLY.
CONTRACTOR IS REQUIRED TO MAINTAIN ALL RATED PARTITIONS.
SMOKE BARRIER
1 HR FIRE BARRIER
2 HR FIRE BARRIER
SMOKE BARRIER (EXISTING)
1 HR FIRE BARRIER (EXISTING)
2 HR FIRE BARRIER (EXISTING)
C1. INSTALL 1HR RATED CEILING SHAFT WALL ASSEMBLY. SEE
SPEC SECTION 07 84 00 FOR REQUIRMENTS.
C2. PROVIDE AND INSTALL VISQUEEN TYPE PLASTIC SHEET AS
REQUIRED TO MAINTAIN TYPE IV INFECTION CONTROL
PRECAUTIONS DURING CONSTRUCTION OF CEILING SHAFT
WALL. EXTEND AND SEAL TO ROOF DECK/STRUCTURE ABOVE.
A. FOR GENERAL NOTES AND LEGENDS REFER TO SHEET A001.
B. FOR GENERAL INFECTION CONTROL NOTES AND DETAILS REFER TO SHEET GI101.
C. FOR FINISH SCHEDULE REFER TO SHEET AF-601.
D. EXISTING IT/TR/OI&T ROOMS TO REMAIN ACTIVE DURING CONSTRUCTION. G.C. TO PROTECT EQUIPMENT DURING CONSTRUCTION WITH VISQUEEN.
CONTRACTOR TO ENSURE CONTINUOUS OPERATION OF EQUIPMENT.
E. NOT ALL KEY NOTES APPLY TO ALL PLAN SHEETS. G.C. TO APPLY ONLY AS INDICATED PER EACH SHEET.
F. MAINTAIN A 4 ' - 0" CLEAR PATH OF TRAVEL IN THE CORRIDORS AT ALL TIMES.
G. ALL WORK TO BE PERFORMED AS PART OF TR MODIFICATION SHALL BE CONSIDERED AS TYPE IV AND FOLLOW "INFECTION CONTROL PRECAUTIONS
FOR CLASS IV" ON SHEET GI101.
H. APPLY FIRE RATED SEALANT TO ALL EXISTING AND NEW PENETRATIONS IN EXISTING WALLS TO MAKE EXISTING WALLS A 1 HR ASSEMBLY. BASIS OF
DESIGN FOR 1 HR WALL IS UL 419 ASSEMBLY.
4'X8' AC GRADE 3/4" TRADE SIZE FIRE RATED PLYWOOD BACKBOARD PAINTED HIGH GLOSS
WHITE WITH (2) COATS OF FIRE RESISTANT PAINT FOR SERVICE
PROVIDER/SECURITY/VIDEO/ETC. AROUND PERIMETER WALLS OF TRS AND ENTRANCE ROOMS
AS SHOWN. ENSURE THAT FIRE RATING STAMP IS TO REMAIN UNCOVERED BY PAINT.
DENOTES SIGNAGE LOCATION DENOTES NEW CEILING
TR
I 0005
I
I I
I WAREHOUSE
I 1 0006 1 I
L ___ _J
BREAK ROOM
1 0004 1
VAULT
1 oooB 1
BATHROOM
1 0002 1
OFFICE
1 0001 1 cr:::=:::7::'._______'::==:::::E:3:=:=='--,..,-':===::E::3:::::==::'._,..,_ '--=-~=1~1--------"~
NORTH
E9 1
BUILDING 12 - FIRST FLOOR PLAN
• 0 I
I
• II
II
3'-10"
1/8"=1'-0"
WAREHOUSE
1 0006 1
0 ENLARGED DEMO PLAN RM 0005 2 i----------,--------1 / 4" = 1' -o ~ o r r +· a·
WAREHOUSE
1 0006 1
0 ENLARGED PLAN RM 0005 3 r----------1 / 4 -= 1 ' - o" o 1' 2' +· 8'
-/3()./flu
BANCROFT ARCHITECTS+ ENGINEERS
O't4' 8' ----
WAREHOUSE □
1 0006 1
4 REFLECTED CEILING PLAN RM 0005
1/4"=1·-o· 01''l +· 8' ----
VA
GENERAL NOTES
0 DEMO CEILING KEYNOTES 0 DEMOLITION PLAN KEYNOTES
@ CEILING PLAN KEYNOTES @ FLOOR PLAN KEYNOTES
RA TED PARTITION LEGEND
------ ------_a_o_ •o_o_
■ 00-00- ■00-00-
FLOOR PLAN LEGEND
ID□
AutoCAD SHX Text 4/A503
AutoCAD SHX Text 3/A503
AutoCAD SHX Text 4/A503
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 1'
AutoCAD SHX Text 2'
AutoCAD SHX Text 4'
AutoCAD SHX Text 8'
AutoCAD SHX Text 1/4"=1'-0"
AutoCAD SHX Text
AutoCAD SHX Text
ENLARGED DEMO PLAN RM 0005
AutoCAD SHX Text
AutoCAD SHX Text 1'
AutoCAD SHX Text 2'
AutoCAD SHX Text 4'
AutoCAD SHX Text 8'
AutoCAD SHX Text 1/4"=1'-0"
AutoCAD SHX Text
AutoCAD SHX Text
ENLARGED PLAN RM 0005
AutoCAD SHX Text
AutoCAD SHX Text 1'
AutoCAD SHX Text 2'
AutoCAD SHX Text 4'
AutoCAD SHX Text 8'
AutoCAD SHX Text 1/4"=1'-0"
AutoCAD SHX Text
AutoCAD SHX Text
REFLECTED CEILING PLAN RM 0005
AutoCAD SHX Text
DEMOLITION PLAN KEYNOTES
AutoCAD SHX Text
DEMO CEILING KEYNOTES
AutoCAD SHX Text
GENERAL NOTES
AutoCAD SHX Text
FLOOR PLAN KEYNOTES
AutoCAD SHX Text
CEILING PLAN KEYNOTES
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text
AutoCAD SHX Text 2'
AutoCAD SHX Text 4'
AutoCAD SHX Text 8'
AutoCAD SHX Text 16'
AutoCAD SHX Text 1/8"=1'-0"
AutoCAD SHX Text
AutoCAD SHX Text
BUILDING 12 - FIRST FLOOR PLAN
AutoCAD SHX Text
NORTH
AutoCAD SHX Text
DEMOLITION PLAN KEYNOTES
AutoCAD SHX Text
DEMO CEILING KEYNOTES
AutoCAD SHX Text
GENERAL NOTES
AutoCAD SHX Text
FLOOR PLAN KEYNOTES
AutoCAD SHX Text
CEILING PLAN KEYNOTES
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text
RATED PARTITION LEGEND
AutoCAD SHX Text
FLOOR PLAN LEGEND
AutoCAD SHX Text X
JMcAllister Snapshot
JMcAllister Text Box
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
K:
\C
C G
_P R
O
JE
C
TS
\2
8\
-1
6C
9D
V
IS
N
ID
IQ
(N or th D ak ot a
Io w
a) \4
-2
1-
EH
R M
F ar go , N
D \4
- D es D oc s\
2-
D ra w in gs \W
O R
KI
N
G \A
-B
-1
.d w g 3/
/2
9:
:4
AM
ISSUE FOR BIDOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES
FARGO VA HEALTH CARE SYSTEM
437-21-205
Revisions: Date:
www. bancroft-ae.com
3300 Dundee RD.
Northbrook, IL 60062
T: 847.952.9362
ISSUE FOR BID 03-18-22
3/18/2022
SHEET OF 279
Bancroft Project No: 18-121
ARCHITECTURAL - BUILDING 13 - FIRST
FLOOR PLANS
DA JM
A-13-101
1. REMOVE EXISTING WALL MOUNTED SERVER RACK.
2. REMOVE MILLWORK AS REQUIRED TO ACCOMMODATE FIRE
EXTINGUISHER.
1. PROVIDE AND INSTALL WALL MOUNTED TELECOMMUNICATIONS
ENCLOSURE (TE). SEE ELECTRICAL AND TECHNOLOGY DRAWINGS FOR
ADDITIONAL INFORMATION. MOUNT T/ RACK @ 6' - 0" A.F.F.
2. PROVIDE AND INSTALL BRACKET MOUNTED CLEAN AGENT FIRE
EXTINGUISHER. MOUNT AT 48" A.F.F. TO CENTER LINE OF HANDLE.
A. FOR GENERAL NOTES AND LEGENDS REFER TO SHEET A001.
B. FOR GENERAL INFECTION CONTROL NOTES AND DETAILS REFER TO SHEET GI101.
C. FOR FINISH SCHEDULE REFER TO SHEET AF-601.
D. EXISTING IT/TR/OI&T ROOMS TO REMAIN ACTIVE DURING CONSTRUCTION. G.C. TO PROTECT EQUIPMENT DURING CONSTRUCTION WITH VISQUEEN.
CONTRACTOR TO ENSURE CONTINUOUS OPERATION OF EQUIPMENT.
E. NOT ALL KEY NOTES APPLY TO ALL PLAN SHEETS. G.C. TO APPLY ONLY AS INDICATED PER EACH SHEET.
F. MAINTAIN A 4 ' - 0" CLEAR PATH OF TRAVEL IN THE CORRIDORS AT ALL TIMES.
G. ALL WORK TO BE PERFORMED AS PART OF TR MODIFICATION SHALL BE CONSIDERED AS TYPE IV AND FOLLOW "INFECTION CONTROL PRECAUTIONS
FOR CLASS IV" ON SHEET GI101.
H. APPLY FIRE RATED SEALANT TO ALL EXISTING AND NEW PENETRATIONS IN EXISTING WALLS TO MAKE EXISTING WALLS A 1 HR ASSEMBLY. BASIS OF
DESIGN FOR 1 HR WALL IS UL 419 ASSEMBLY.
DENOTES SIGNAGE LOCATION
>-~l)
\ •• 4- J 2 1 I
IE "" i, BACK STAIRWAY '
CLEAN LINEN
MECHANICAL ROOM 'OILED
I NEN
J ELEC. □ □ □ □ □
( SERV.
I \__ LJ "- ~ X L./ I
I 2 t----. LUNCH - ~I SHOWE V I'- SHOWER / BACK ENTRY 1 r- J OFFICE ROOM CART WASH AREA y "'7 ROOM ROOM _yr >-.J '77 - - -
ISSUE\__ --{ECEIVING
N E9 (De--~-/8~-~1~-?.I_NG_1_3 _-_FIR_s_,T_'F7-. 0-~-~ _DE_M_~LITION PLAN
BACK STAIRWAY
MECHANICAL ROOM
654-321 i, J ELEC.
( SERV.
0'" ~
/ BACK ENTRY • 1 ,-..__ -@
t=::'.::::~====3::::~ -c___,Y -D
CLEAN LINEN
LUNCH
OFFICE ROOM
ISSUE \__---n....1..u
N
I
X L./
SHOWER/"" I'- SHOWER
ROOM ROOM
E9 (De--~-/8~-~1~-?.I_NG_1_3 _-_FIR_s_,T_,'.7-. 0-~-~ _PL_A_~ ..
13 ~
- a,1-\.CA I // ' '
BANCROFT ARCHITECTS+ ENGINEERS V
CART WASH AREA
'. OILED
II------"'' N EN
u..i.i:r-/4 EC EIVI NG
VA
GENERAL NOTES
FLOOR PLAN LEGEND
0 DEMOLlllON PLAN KEYNOTES @ FLOOR PLAN KEYNOTES
I I
:c==========~::==========;:c============:l;:========;I
ID□
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
DN
AutoCAD SHX Text
UP
AutoCAD SHX Text
CLEAN LINEN
AutoCAD SHX Text
SOILED
AutoCAD SHX Text
LINEN
AutoCAD SHX Text
RECEIVING
AutoCAD SHX Text
ELEC.
AutoCAD SHX Text
SERV.
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
LUNCH
AutoCAD SHX Text
ROOM
AutoCAD SHX Text
ISSUE
AutoCAD SHX Text
SHOWER
AutoCAD SHX Text
ROOM
AutoCAD SHX Text
ROOM
AutoCAD SHX Text
SHOWER
AutoCAD SHX Text
CART WASH AREA
AutoCAD SHX Text
MECHANICAL ROOM
AutoCAD SHX Text
BACK ENTRY
AutoCAD SHX Text
BACK STAIRWAY
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
DN
AutoCAD SHX Text
UP
AutoCAD SHX Text
CLEAN LINEN
AutoCAD SHX Text
SOILED
AutoCAD SHX Text
LINEN
AutoCAD SHX Text
RECEIVING
AutoCAD SHX Text
ELEC.
AutoCAD SHX Text
SERV.
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
LUNCH
AutoCAD SHX Text
ROOM
AutoCAD SHX Text
ISSUE
AutoCAD SHX Text
SHOWER
AutoCAD SHX Text
ROOM
AutoCAD SHX Text
ROOM
AutoCAD SHX Text
SHOWER
AutoCAD SHX Text
CART WASH AREA
AutoCAD SHX Text
MECHANICAL ROOM
AutoCAD SHX Text
BACK ENTRY
AutoCAD SHX Text
BACK STAIRWAY
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 2'
AutoCAD SHX Text 4'
AutoCAD SHX Text 8'
AutoCAD SHX Text 16'
AutoCAD SHX Text 1/8"=1'-0"
AutoCAD SHX Text
AutoCAD SHX Text
BUILDING 13 - FIRST FLOOR DEMOLITION PLAN
AutoCAD SHX Text
AutoCAD SHX Text 2'
AutoCAD SHX Text 4'
AutoCAD SHX Text 8'
AutoCAD SHX Text 16'
AutoCAD SHX Text 1/8"=1'-0"
AutoCAD SHX Text
AutoCAD SHX Text
BUILDING 13 - FIRST FLOOR PLAN
AutoCAD SHX Text
DEMOLITION PLAN KEYNOTES
AutoCAD SHX Text
GENERAL NOTES
AutoCAD SHX Text
FLOOR PLAN KEYNOTES
AutoCAD SHX Text X
AutoCAD SHX Text N
AutoCAD SHX Text N
AutoCAD SHX Text X
AutoCAD SHX Text
FLOOR PLAN LEGEND
JMcAllister Snapshot
JMcAllister
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
K:
\C
C G
_P R
O
JE
C
TS
\2
8\
-1
6C
9D
V
IS
N
ID
IQ
(N or th D ak ot a
Io w
a) \4
-2
1-
EH
R M
F ar go , N
D \4
- D es D oc s\
2-
D ra w in gs \W
O R
KI
N
G \A
-B
-1
.d w g 3/
/2
9:
:5
AM
ISSUE FOR BIDOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES
FARGO VA HEALTH CARE SYSTEM
437-21-205
Revisions: Date:
www. bancroft-ae.com
3300 Dundee RD.
Northbrook, IL 60062
T: 847.952.9362
ISSUE FOR BID 03-18-22
3/18/2022
SHEET OF 279
Bancroft Project No: 18-121
ARCHITECTURAL - BUILDING 30 -
BASEMENT FLOOR PLANS
DA JM
A-30-101
1. REMOVE EXISTING WALL MOUNTED SERVER RACK. 1. PROVIDE AND INSTALL FLOOR MOUNTED TELECOMMUNICATIONS
ENCLOSURE (TE). SEE ELECTRICAL AND TECHNOLOGY DRAWINGS FOR
ADDITIONAL INFORMATION.
2. PAINT WALL. SEE ROOM FINISH SCHEDULE.
3. PROVIDE AND INSTALL BRACKET MOUNTED CLEAN AGENT FIRE
EXTINGUISHER. MOUNT AT 48" A.F.F. TO CENTER LINE OF HANDLE.
A. FOR GENERAL NOTES AND LEGENDS REFER TO SHEET A001.
B. FOR GENERAL INFECTION CONTROL NOTES AND DETAILS REFER TO SHEET GI101.
C. FOR FINISH SCHEDULE REFER TO SHEET AF-601.
D. EXISTING IT/TR/OI&T ROOMS TO REMAIN ACTIVE DURING CONSTRUCTION. G.C. TO PROTECT EQUIPMENT DURING CONSTRUCTION WITH VISQUEEN.
CONTRACTOR TO ENSURE CONTINUOUS OPERATION OF EQUIPMENT.
E. NOT ALL KEY NOTES APPLY TO ALL PLAN SHEETS. G.C. TO APPLY ONLY AS INDICATED PER EACH SHEET.
F. MAINTAIN A 4 ' - 0" CLEAR PATH OF TRAVEL IN THE CORRIDORS AT ALL TIMES.
G. ALL WORK TO BE PERFORMED AS PART OF TR MODIFICATION SHALL BE CONSIDERED AS TYPE IV AND FOLLOW "INFECTION CONTROL PRECAUTIONS
FOR CLASS IV" ON SHEET GI101.
H. APPLY FIRE RATED SEALANT TO ALL EXISTING AND NEW PENETRATIONS IN EXISTING WALLS TO MAKE EXISTING WALLS A 1 HR ASSEMBLY. BASIS OF
DESIGN FOR 1 HR WALL IS UL 419 ASSEMBLY.
DENOTES SIGNAGE LOCATION
N
I ' 0-/;;;\ ~
11tttttt1111
~ . lltftttf1111 .
ffi 0 ~~l~~ING 30 - FLOOR PLAN
11111,111111
. 111111111111
GENERAL NOTES
FLOOR PLAN LEGEND
0 DEMOLITION PLAN KEYNOTES @ FLOOR PLAN KEYNOTES
02'4' B' 16'
0 2' 4' II' ,..
I I
13 ~
- a,1-\.CA I // ' '
:c==========~::==========;:c============:l;:========;I
BANCROFT ARCHITECTS+ ENGINEERS V VA ID□
AutoCAD SHX Text
BASEMENT
AutoCAD SHX Text
BASEMENT
AutoCAD SHX Text
BASEMENT
AutoCAD SHX Text
BASEMENT
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 2'
AutoCAD SHX Text 4'
AutoCAD SHX Text 8'
AutoCAD SHX Text 16'
AutoCAD SHX Text 1/8"=1'-0"
AutoCAD SHX Text
AutoCAD SHX Text
BUILDING 30 - DEMO PLAN
AutoCAD SHX Text
AutoCAD SHX Text 2'
AutoCAD SHX Text 4'
AutoCAD SHX Text 8'
AutoCAD SHX Text 16'
AutoCAD SHX Text 1/8"=1'-0"
AutoCAD SHX Text
AutoCAD SHX Text
BUILDING 30 - FLOOR PLAN
AutoCAD SHX Text
GENERAL NOTES
AutoCAD SHX Text
FLOOR PLAN KEYNOTES
AutoCAD SHX Text X
AutoCAD SHX Text
DEMOLITION PLAN KEYNOTES
AutoCAD SHX Text
GENERAL NOTES
AutoCAD SHX Text
FLOOR PLAN KEYNOTES
AutoCAD SHX Text X
AutoCAD SHX Text N
AutoCAD SHX Text N
AutoCAD SHX Text X
AutoCAD SHX Text
FLOOR PLAN LEGEND
JMcAllister Snapshot
JMcAllister
A-40-101
A-40-101
A-40-101
A-40-101
TELE / EQUIP
102B
CHIEF
102A
STAIR #1
WOMEN
MEN
HAC
TELE / EQUIP
102B
CHIEF
102A
102B
CHIEF
102A
TR
102B
B B
D1 B
CHIEF
102A
TR
102B
TELE / EQUIP
102B
CHIEF
102A
GENERAL NOTES
A. FOR GENERAL NOTES AND LEGENDS REFER TO SHEET A001.
B. FOR GENERAL INFECTION CONTROL NOTES AND DETAILS REFER TO SHEET GI101.
C. FOR FINISH SCHEDULE REFER TO SHEET AF-601.
D. EXISTING IT/TR/OI&T ROOMS TO REMAIN ACTIVE DURING CONSTRUCTION. G.C. TO PROTECT EQUIPMENT DURING CONSTRUCTION WITH VISQUEEN. CONTRACTOR TO ENSURE
CONTINUOUS OPERATION OF EQUIPMENT.
E. NOT ALL KEY NOTES APPLY TO ALL PLAN SHEETS. G.C. TO APPLY ONLY AS INDICATED PER EACH SHEET.
F. MAINTAIN A 4 ' - 0" CLEAR PATH OF TRAVEL IN THE CORRIDORS AT ALL TIMES.
G. ALL WORK TO BE PERFORMED AS PART OF TR MODIFICATION SHALL BE CONSIDERED AS TYPE IV AND FOLLOW "INFECTION CONTROL PRECAUTIONS FOR CLASS IV" ON SHEET GI101.
H. APPLY FIRE RATED SEALANT TO ALL EXISTING AND NEW PENETRATIONS IN EXISTING WALLS TO MAKE EXISTING WALLS A 1 HR ASSEMBLY. BASIS OF DESIGN FOR 1 HR WALL IS UL 419
ASSEMBLY.
CONTRACTOR IS REQUIRED TO MAINTAIN ALL RATED PARTITIONS.
SMOKE BARRIER
1 HR FIRE BARRIER
2 HR FIRE BARRIER
SMOKE BARRIER (EXISTING)
1 HR FIRE BARRIER (EXISTING)
2 HR FIRE BARRIER (EXISTING)
RATED PARTITION LEGEND
1. G.C. TO CAREFULLY REMOVE EQUIPMENT WITHIN EXISTING OI&T OR IRM ROOM AND TURN
OVER TO VA.
2. EXISTING HANDRAIL, WALL BASE AND CARPET TO BE MODIFIED TO ACCEPT NEW DOOR.
3. SUPPLY AND INSTALL WALK OFF MAT(S). SEE DETAILS ON SHEET GI101.
4. REMOVE EXISTING DOOR, FRAME AND HARDWARE IN ITS ENTIRETY. INFILL WALL WITH
METAL STUDS AND DRYWALL. ALIGN WITH EXISTING WALLS, PATCH, LEVEL AND FINISH
TO MATCH EXISTING WALL FINISH.
5. REMOVE EXISTING DOOR, FRAME AND HARDWARE IN ITS ENTIRETY FOR INSTALLATION
OF NEW DOOR AND FRAME. PORTIONS OF EXISTING WALL TO BE DEMOLISHED TO
RECEIVE NEW LARGER SIZE DOOR AND FRAME ASSEMBLY. PATCH ADJACENT WALLS TO
MATCH ADJACENT CONDITIONS. RELOCATE ALL WALL MOUNTED ITEMS INCLUDING ROOM
SIGNAGE, CHAIR RAILS, CORNER GUARDS AND WALL MOUNTED ADJACENT TO EXISTING
CORRIDOR DOOR AND REINSTALL AT NEW DOOR LOCATION.
6. REMOVE EXISTING DOOR, FRAME AND HARDWARE. PREPARE WALL CONSTRUCTION AT
OPENING FOR NEW FRAME.
7. REMOVE EXISTING CARPET AND REMOVE ALL ASSOCIATED ADHESIVE. PREP AND LEVEL
EXISTING CONCRETE FLOOR TO RECEIVE NEW FINISH.
8. G.C. TO CAREFULLY REMOVE ALL CASEWORK AND PLUMBING FIXTURE. CAP SUPPLY AT
MAINS TO PREVENT DEADLEGS.
9. INSTALL TEMPORARY FLAME RESISTANT CONSTRUCTION PANELS WITH DOOR ENTRY.
BASIS OF DESIGN IS EDGE GUARD.
DEMOLITION PLAN KEYNOTES
D1. STRUCTURE IS FIRE PROTECTED. FIRE PROOFING MAY BE DISTURBED
DURING DEMOLITION. PATCH ANY FIREPROOFING ON STEEL THAT IS
MISSING.
D2. REMOVE EXISTING CEILING GRID TO EXTENT REQUIRED TO
ACCOMMODATE NEW PARTITIONS.
D3. REMOVE LIGHT FIXTURE.
D4. SEE FIRE PROTECTION DRAWINGS FOR SPRINKLER HEAD MODIFICATIONS.
DEMO CEILING KEYNOTES
X
X
1. FINISH WALL CORNER TO CORNER AND FLOOR TO CEILING. PRIOR TO PAINTING THE
ENTIRE WALL SURFACE WITH (1) FINISH COAT OF PAINT, PROVIDE (1) PRIME COAT AND
(2) FINISH COATS OVER PATCHED/REPAIRED WALL SURFACES.
2. INSTALL NEW HANDRAIL, NEW CRASH RAIL AND WALL BASE TO CREATE LONG
CONTINUOUS RUN. EXTEND HANDRAIL, CRASH RAIL AND WALL BASE TO NEXT
ASSEMBLY JOINT. FOR DETAILS SEE SHEET A-502.
3. MODIFY EXISTING WALL CONSTRUCTION TO CONSTRUCT A WALL ASSEMBLY THAT IS
1HR RATED PARTITION, AS IDENTIFIED AS WALL TYPE A ON SHEET A501. THIS INCLUDES
ADDING 58" GYP. BOARD TO UNDERSIDE OF DECK ON BOTH SIDES OF WALL. BASIS OF
DESIGN FOR 1HR WALL IS UL 419 ASSEMBLY.
4. PAINT FULL EXTENT OF EXPOSED WALL. SEE FINISH SCHEDULE.
5. WINDOW OPENING INFILL CONSTRUCTION.
6. CONTRACTOR TO CONFIRM FIRE RATED SEALANT AT HEAD AND BASE OF PARTITION. IF
NOT EXISTING - INSTALL (BOTH SIDES OF PARTITION) TO MAKE 1-HR RATING.
7. PROVIDE 1' - 0" X 1' - 0" ACCESS HATCH TO BE LOCATED FOR VALVE ACCESS.
8. FIRE EXTINGUISHER CABINET MOUNTED 48" A.F.F. TO CENTERLINE OF HANDLE.
FLOOR PLAN KEYNOTES
CEILING PLAN KEYNOTESX
X
FLOOR PLAN LEGEND
4'X8' AC GRADE 3/4" TRADE SIZE FIRE RATED PLYWOOD BACKBOARD PAINTED HIGH GLOSS
WHITE WITH (2) COATS OF FIRE RESISTANT PAINT FOR SERVICE
PROVIDER/SECURITY/VIDEO/ETC. AROUND PERIMETER WALLS OF TRS AND ENTRANCE ROOMS
AS SHOWN. ENSURE THAT FIRE RATING STAMP IS TO REMAIN UNCOVERED BY PAINT.
C1. CONTRACTOR TO PAINT UNDERSIDE OF DECK WHERE FIREPROOFING OR
INSULATION ISN'T PRESENT BRIGHT WHITE. SEE ROOM FINISH SCHEDULE ,
FOR BID PURPOSES ASSUME ENTIRE CEILING PERIMETER IS TO BE PAINTED.
C2. INSTALL NEW CEILING GRID AND EDGE ANGLE. INSTALL NEW CEILING TILES
TO MATCH EXISTING.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
K:
\C
C G
_P R
O
JE
C
TS
\2
8\
-1
6C
9D
V
IS
N
ID
IQ
(N or th D ak ot a
Io w
a) \4
-2
1-
EH
R M
F ar go , N
D \4
- D es D oc s\
2-
D ra w in gs \W
O R
KI
N
G \A
-B
-1
.d w g 3/
/2
:0
0:
A M
ISSUE FOR BIDOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES
FARGO VA HEALTH CARE SYSTEM
437-21-205
Revisions: Date:
www. bancroft-ae.com
3300 Dundee RD.
Northbrook, IL 60062
T: 847.952.9362
ISSUE FOR BID 03-18-22
3/18/2022
SHEET OF 279
Bancroft Project No: 18-121
ARCHITECTURAL - BUILDING 40 - FIRST
FLOOR PLANS
DA JM
A-40-101
10. G.C. TO CAREFULLY REMOVE FURNITURE AND TURN OVER TO VA.
11. PREPARE AND LEVEL EXISTING CONCRETE FLOOR AS REQUIRED TO RECEIVE NEW
SCHEDULED FLOOR FINISH.
12. REMOVE PARTITION IN ITS ENTIRETY. PATCH AS REQUIRED ADJACENT WALL TO REMAIN
TO RECEIVE NEW CONSTRUCTION OF RATED WALL PARTITION.
13. PREPARE OPENING IN WALL FOR NEW FIRE EXTINGUISHER CABINET. SEE DETAIL 1/A-502.
14. PREPARE OPENING IN EXISTING PARTITION TO RECEIVE NEW DOOR AND FRAME. SEE
DOOR SCHEDULE.
DENOTES SIGNAGE LOCATION DENOTES NEW CEILING
9. CONTRACTOR TO CONFIRM FIRE-RATED SEALANT AT HEAD AND BASE OF PARTITION. IF
NOT EXISTING INSTALL (BOTH SIDES OF PARTITION) TO MAKE 2-HR RATED.
10. G.C. TO CAREFULLY REMOVE FURNITURE AND TURN OVER TO VA.
11. PREPARE AND LEVEL EXISTING CONCRETE FLOOR AS REQUIRED TO RECEIVE NEW
SCHEDULED FLOOR FINISH.
12. REMOVE PARTITION IN ITS ENTIRETY. PATCH AS REQUIRED ADJACENT WALL TO REMAIN
TO RECEIVE NEW CONSTRUCTION OF RATED WALL PARTITION.
13. PREPARE OPENING IN WALL FOR NEW FIRE EXTINGUISHER CABINET. SEE DETAIL 1/A-502.
14. PREPARE OPENING IN EXISTING PARTITION TO RECEIVE NEW DOOR AND FRAME. SEE
DOOR SCHEDULE.
15. REMOVE EXISTING WINDOW ASSEMBLY IN ITS ENTIRETY. PREP OPENING FOR INFILL.
I I_ I I
( I\ (
-11
/,,, II
I II
I II
(PHASE-2)
>•.,(-'' I .>J;:( . ~· ·~
~h::::i~·';'=r ---
(PHASE-1)
I I\
NORTH
EB CD
I
0 ENLARGED DEMO PLAN RM 1028
1/4"=1'-0" 0 1' 2' 4' ,.
IX] [!I
[!I
M JYl
.L ~
BUILDING 40 - FIRST FLOOR PLAN
1/a"=l'-o"
=:::::u---a: ___ ..,------- ~~ I
0 ENLARGED DEMO CEILING PLAN RM 1028
1/4"=1'-0" 0 1' l' 4' ,.
-/3()./flu
BANCROFT ARCHITECTS+ ENGINEERS
I _I_
I I
( I\ I
I I
[!I
[!I
~ l.) ~
0 2' 4' ,. 16'
-------'---------rr+--""""'"'-1 I
6 }----_.
-\("\ -v-
I A__) A_,, I
' =TI: I
I
I I
II
I
'\ I --
--00-00 < uu Jfl I I
~ LJVu 0 .Q I.Q ,Q
[ I 0 TI TI 'V' ,'i?i.
ID<'I I\
\ ~< I I nn
I =
6/Qg03
I t=------{ 9
0 ENLARGED PLAN RM 1028 4 l-------- 0 ENLARGED CEILING PLAN RM 1028 1/4n=1'-0n O 1' 2' 4' 8' 1/4"=1'-0" 0 1' 2' 4' ,.
VA
0 □
0 □
••••••••• ••••••••• _ D_O_ •o_o _
■00-00- 100-00-
ID□
AutoCAD SHX Text 5/A503
AutoCAD SHX Text
(PHASE-2)
AutoCAD SHX Text
(PHASE-2)
AutoCAD SHX Text
(PHASE-1)
AutoCAD SHX Text
(PHASE-1)
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6/A503
AutoCAD SHX Text 6/A503
AutoCAD SHX Text 5/A503
AutoCAD SHX Text
AutoCAD SHX Text 2'
AutoCAD SHX Text 4'
AutoCAD SHX Text 8'
AutoCAD SHX Text 16'
AutoCAD SHX Text 1/8"=1'-0"
AutoCAD SHX Text
AutoCAD SHX Text
BUILDING 40 - FIRST FLOOR PLAN
AutoCAD SHX Text
NORTH
AutoCAD SHX Text
AutoCAD SHX Text 1'
AutoCAD SHX Text 2'
AutoCAD SHX Text 4'
AutoCAD SHX Text 8'
AutoCAD SHX Text 1/4"=1'-0"
AutoCAD SHX Text
AutoCAD SHX Text
ENLARGED PLAN RM 102B
AutoCAD SHX Text
AutoCAD SHX Text 1'
AutoCAD SHX Text 2'
AutoCAD SHX Text 4'
AutoCAD SHX Text 8'
AutoCAD SHX Text 1/4"=1'-0"
AutoCAD SHX Text
AutoCAD SHX Text
ENLARGED DEMO PLAN RM 102B
AutoCAD SHX Text
AutoCAD SHX Text 1'
AutoCAD SHX Text 2'
AutoCAD SHX Text 4'
AutoCAD SHX Text 8'
AutoCAD SHX Text 1/4"=1'-0"
AutoCAD SHX Text
AutoCAD SHX Text
ENLARGED DEMO CEILING PLAN RM 102B
AutoCAD SHX Text
AutoCAD SHX Text 1'
AutoCAD SHX Text 2'
AutoCAD SHX Text 4'
AutoCAD SHX Text 8'
AutoCAD SHX Text 1/4"=1'-0"
AutoCAD SHX Text
AutoCAD SHX Text
ENLARGED CEILING PLAN RM 102B
AutoCAD SHX Text X
JMcAllister Snapshot
JMcAllister
ADJUNCT CHIEF
OFFICE
204C
TR
202A
OPEN
OFFICE
HEARING
ROOM
ADJUNCTION
RECEPTION
STAIR # 1
HAC
A-40-102 A-40-102
A-40-102
A-40-102
TR
202A
STAIR # 1
2A
B B
B
ADJUNCT CHIEF
202A
STAIR # 1
ADJUNCT CHIEF
202A
STAIR # 1
TR
202A
STAIR # 1
GENERAL NOTES
A. FOR GENERAL NOTES AND LEGENDS REFER TO SHEET A001.
B. FOR GENERAL INFECTION CONTROL NOTES AND DETAILS REFER TO SHEET GI101.
C. FOR FINISH SCHEDULE REFER TO SHEET AF-601.
D. EXISTING IT/TR/OI&T ROOMS TO REMAIN ACTIVE DURING CONSTRUCTION. G.C. TO PROTECT EQUIPMENT DURING CONSTRUCTION WITH VISQUEEN. CONTRACTOR TO ENSURE
CONTINUOUS OPERATION OF EQUIPMENT.
E. NOT ALL KEY NOTES APPLY TO ALL PLAN SHEETS. G.C. TO APPLY ONLY AS INDICATED PER EACH SHEET.
F. MAINTAIN A 4 ' - 0" CLEAR PATH OF TRAVEL IN THE CORRIDORS AT ALL TIMES.
G. ALL WORK TO BE PERFORMED AS PART OF TR MODIFICATION SHALL BE CONSIDERED AS TYPE IV AND FOLLOW "INFECTION CONTROL PRECAUTIONS FOR CLASS IV" ON SHEET GI101.
H. APPLY FIRE RATED SEALANT TO ALL EXISTING AND NEW PENETRATIONS IN EXISTING WALLS TO MAKE EXISTING WALLS A 1 HR ASSEMBLY. BASIS OF DESIGN FOR 1 HR WALL IS UL 419
ASSEMBLY.
CONTRACTOR IS REQUIRED TO MAINTAIN ALL RATED PARTITIONS.
SMOKE BARRIER
1 HR FIRE BARRIER
2 HR FIRE BARRIER
SMOKE BARRIER (EXISTING)
1 HR FIRE BARRIER (EXISTING)
2 HR FIRE BARRIER (EXISTING)
RATED PARTITION LEGEND
1. G.C. TO CAREFULLY REMOVE EQUIPMENT WITHIN EXISTING OI&T OR IRM ROOM AND TURN
OVER TO VA.
2. EXISTING HANDRAIL, WALL BASE AND CARPET TO BE MODIFIED TO ACCEPT NEW DOOR.
3. SUPPLY AND INSTALL WALK OFF MAT(S). SEE DETAILS ON SHEET GI101.
4. REMOVE EXISTING DOOR, FRAME AND HARDWARE IN ITS ENTIRETY. INFILL WALL WITH
METAL STUDS AND DRYWALL. ALIGN WITH EXISTING WALLS, PATCH, LEVEL AND FINISH
TO MATCH EXISTING WALL FINISH.
5. REMOVE EXISTING DOOR, FRAME AND HARDWARE IN ITS ENTIRETY FOR INSTALLATION
OF NEW DOOR AND FRAME. PORTIONS OF EXISTING WALL TO BE DEMOLISHED TO
RECEIVE NEW LARGER SIZE DOOR AND FRAME ASSEMBLY. PATCH ADJACENT WALLS TO
MATCH ADJACENT CONDITIONS. RELOCATE ALL WALL MOUNTED ITEMS INCLUDING ROOM
SIGNAGE, CHAIR RAILS, CORNER GUARDS AND WALL MOUNTED ADJACENT TO EXISTING
CORRIDOR DOOR AND REINSTALL AT NEW DOOR LOCATION.
6. REMOVE EXISTING DOOR, FRAME AND HARDWARE. PREPARE WALL CONSTRUCTION AT
OPENING FOR NEW FRAME.
7. REMOVE EXISTING CARPET AND REMOVE ALL ASSOCIATED ADHESIVE. PREP AND LEVEL
EXISTING CONCRETE FLOOR TO RECEIVE NEW FINISH.
8. G.C. TO CAREFULLY REMOVE ALL CASEWORK AND PLUMBING FIXTURE. CAP SUPPLY AT
MAINS TO PREVENT DEADLEGS.
9. INSTALL TEMPORARY FLAME RESISTANT CONSTRUCTION PANELS WITH DOOR ENTRY.
BASIS OF DESIGN IS EDGE GUARD.
DEMOLITION PLAN KEYNOTES
D1. STRUCTURE IS FIRE PROTECTED. FIRE PROOFING MAY BE DISTURBED
DURING DEMOLITION. PATCH ANY FIREPROOFING ON STEEL THAT IS
MISSING.
D2. REMOVE EXISTING CEILING GRID TO EXTENT REQUIRED TO
ACCOMMODATE NEW PARTITIONS.
D3. REMOVE LIGHT FIXTURE.
D4. SEE FIRE PROTECTION DRAWINGS FOR SPRINKLER HEAD MODIFICATIONS.
DEMO CEILING KEYNOTES
X
X
1. FINISH WALL CORNER TO CORNER AND FLOOR TO CEILING. PRIOR TO PAINTING THE
ENTIRE WALL SURFACE WITH (1) FINISH COAT OF PAINT, PROVIDE (1) PRIME COAT AND
(2) FINISH COATS OVER PATCHED/REPAIRED WALL SURFACES.
2. INSTALL NEW HANDRAIL, NEW CRASH RAIL AND WALL BASE TO CREATE LONG
CONTINUOUS RUN. EXTEND HANDRAIL, CRASH RAIL AND WALL BASE TO NEXT
ASSEMBLY JOINT. FOR DETAILS SEE SHEET A-502.
3. MODIFY EXISTING WALL CONSTRUCTION TO CONSTRUCT A WALL ASSEMBLY THAT IS
1HR RATED PARTITION, AS IDENTIFIED AS WALL TYPE A ON SHEET A501. THIS INCLUDES
ADDING 58" GYP. BOARD TO UNDERSIDE OF DECK ON BOTH SIDES OF WALL. BASIS OF
DESIGN FOR 1HR WALL IS UL 419 ASSEMBLY.
4. PAINT FULL EXTENT OF EXPOSED WALL. SEE FINISH SCHEDULE.
5. WINDOW OPENING INFILL CONSTRUCTION.
6. CONTRACTOR TO CONFIRM FIRE RATED SEALANT AT HEAD AND BASE OF PARTITION. IF
NOT EXISTING - INSTALL (BOTH SIDES OF PARTITION) TO MAKE 1-HR RATING.
7. PROVIDE 1' - 0" X 1' - 0" ACCESS HATCH TO BE LOCATED FOR VALVE ACCESS.
8. FIRE EXTINGUISHER CABINET MOUNTED 48" A.F.F. TO CENTERLINE OF HANDLE.
FLOOR PLAN KEYNOTES
CEILING PLAN KEYNOTESX
X
FLOOR PLAN LEGEND
4'X8' AC GRADE 3/4" TRADE SIZE FIRE RATED PLYWOOD BACKBOARD PAINTED HIGH GLOSS
WHITE WITH (2) COATS OF FIRE RESISTANT PAINT FOR SERVICE
PROVIDER/SECURITY/VIDEO/ETC. AROUND PERIMETER WALLS OF TRS AND ENTRANCE ROOMS
AS SHOWN. ENSURE THAT FIRE RATING STAMP IS TO REMAIN UNCOVERED BY PAINT.
C1. CONTRACTOR TO PAINT UNDERSIDE OF DECK WHERE FIREPROOFING OR
INSULATION ISN'T PRESENT BRIGHT WHITE. SEE ROOM FINISH SCHEDULE ,
FOR BID PURPOSES ASSUME ENTIRE CEILING PERIMETER IS TO BE PAINTED.
C2. INSTALL NEW CEILING GRID AND EDGE ANGLE. INSTALL NEW CEILING TILES
TO MATCH EXISTING.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
K:
\C
C G
_P R
O
JE
C
TS
\2
8\
-1
6C
9D
V
IS
N
ID
IQ
(N or th D ak ot a
Io w
a) \4
-2
1-
EH
R M
F ar go , N
D \4
- D es D oc s\
2-
D ra w in gs \W
O R
KI
N
G \A
-B
-1
.d w g 3/
/2
:0
1:
A M
ISSUE FOR BIDOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES
FARGO VA HEALTH CARE SYSTEM
437-21-205
Revisions: Date:
www. bancroft-ae.com
3300 Dundee RD.
Northbrook, IL 60062
T: 847.952.9362
ISSUE FOR BID 03-18-22
3/18/2022
SHEET OF 279
Bancroft Project No: 18-121
ARCHITECTURAL - BUILDING 40 -
SECOND FLOOR & ENLARGED PLANS
DA JM
A-40-102
10. G.C. TO CAREFULLY REMOVE FURNITURE AND TURN OVER TO VA.
11. PREPARE AND LEVEL EXISTING CONCRETE FLOOR AS REQUIRED TO RECEIVE NEW
SCHEDULED FLOOR FINISH.
12. REMOVE PARTITION IN ITS ENTIRETY. PATCH AS REQUIRED ADJACENT WALL TO REMAIN
TO RECEIVE NEW CONSTRUCTION OF RATED WALL PARTITION.
13. PREPARE OPENING IN WALL FOR NEW FIRE EXTINGUISHER CABINET. SEE DETAIL 1/A-502.
14. PREPARE OPENING IN EXISTING PARTITION TO RECEIVE NEW DOOR AND FRAME. SEE
DOOR SCHEDULE.
DENOTES SIGNAGE LOCATION
9. CONTRACTOR TO CONFIRM FIRE-RATED SEALANT AT HEAD AND BASE OF PARTITION. IF
NOT EXISTING INSTALL (BOTH SIDES OF PARTITION) TO MAKE 2-HR RATED.
10. G.C. TO CAREFULLY REMOVE FURNITURE AND TURN OVER TO VA.
11. PREPARE AND LEVEL EXISTING CONCRETE FLOOR AS REQUIRED TO RECEIVE NEW
SCHEDULED FLOOR FINISH.
12. REMOVE PARTITION IN ITS ENTIRETY. PATCH AS REQUIRED ADJACENT WALL TO REMAIN
TO RECEIVE NEW CONSTRUCTION OF RATED WALL PARTITION.
13. PREPARE OPENING IN WALL FOR NEW FIRE EXTINGUISHER CABINET. SEE DETAIL 1/A-502.
14. PREPARE OPENING IN EXISTING PARTITION TO RECEIVE NEW DOOR AND FRAME. SEE
DOOR SCHEDULE.
15. REMOVE EXISTING WINDOW ASSEMBLY IN ITS ENTIRETY. PREP OPENING FOR INFILL.
A502
A502
I I I I I
C,T,U, 204A
~ r Cl Cl
\__ "213 204 B"---I _J
\__ I I I I LJ
f-----i z:
. :::r::: Cl Cl Cl
LJ
w
212 ~
I\
__,,;AMER LEGIDN7 AMVETS .
TAIR _/ ~·2 21n 209 2_8 u u
NDVA MNDVA I"----.. DAV
211 _;210A 2 0 9A"-- ~OBA 207~ 207
206 l....!!!!!:: ,- I
J J J j .L ~ .L rnDAr.;r=- Q I I
NORTH
EB 1 BUILDING 40 - SECOND FLOOR PLAN
1/8"=1'-o"
- - -+--7-_ ..,.__.,, I 0 - , - - , - -1- - ,:'--=--r--
1 I I I I
I
• --+---b--1 __ I __ D2 g ,r---
1 II IJ....-11 --I D 3
• _ -t-_ j'=----
___ --:!J_ _ D4
• I I I "' I I _ -t __ 1r--__ 1 ___ -,t __ t- _ :n--
• I ~ II I 0
- -t- - j!=----1---i- - t- - g 0 I I I ....--'-----'-,
- -+- --1- - -1- --+- - - :
, _::::] 0 0 rn r-vv- V\ /\ A__A "-.___,)
I I
:::;"I I
I I / \ I --,...
u ~ \__ \
I w< uu
I I ( _) l..) L/ L.J
:) Q Q Q
\__ r
Cl 5' CJ 'V'I~~
I I I\
~<M~~ \
~ Lioo_ C:
~ r u 0
VFw __/~06A 205~ 205
I I
02'4' 8' ,., ----
I
I
0 0 0
0 ~4~~9 40 ROOF PLAN
-/3()./flu
BANCROFT ARCHITECTS+ ENGINEERS
IJt--1:,>-i It-- 0 .....___, l o,lt--
0 1' 2' 4' 8'
0 □
0 □
••••••••• • •••••••• _ D_O_ •o_o _
■00-00- 100-00-
::================:::==========;~=======~I::======:
VA ID□
AutoCAD SHX Text C.T.U.
AutoCAD SHX Text
MECHANICAL
AutoCAD SHX Text
MEN
AutoCAD SHX Text
STAIR
AutoCAD SHX Text #2
AutoCAD SHX Text
AutoCAD SHX Text 204A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 210A
AutoCAD SHX Text
AMER
AutoCAD SHX Text
LEGION
AutoCAD SHX Text
STORAGE &
AutoCAD SHX Text
AutoCAD SHX Text
AMVETS
AutoCAD SHX Text
AutoCAD SHX Text 209A
AutoCAD SHX Text
NDVA
AutoCAD SHX Text
AutoCAD SHX Text 208A
AutoCAD SHX Text
DAV
AutoCAD SHX Text 205A
AutoCAD SHX Text 207A
AutoCAD SHX Text 206A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
MNDVA
AutoCAD SHX Text
VFW
AutoCAD SHX Text
AutoCAD SHX Text 204B
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6/A503
AutoCAD SHX Text 5/A503
AutoCAD SHX Text 5/A503
AutoCAD SHX Text 6/A503
AutoCAD SHX Text
AutoCAD SHX Text 2'
AutoCAD SHX Text 4'
AutoCAD SHX Text 8'
AutoCAD SHX Text 16'
AutoCAD SHX Text 1/8"=1'-0"
AutoCAD SHX Text
AutoCAD SHX Text
BUILDING 40 - SECOND FLOOR PLAN
AutoCAD SHX Text
NORTH
AutoCAD SHX Text
AutoCAD SHX Text 1'
AutoCAD SHX Text 2'
AutoCAD SHX Text 4'
AutoCAD SHX Text 8'
AutoCAD SHX Text 1/4"=1'-0"
AutoCAD SHX Text
AutoCAD SHX Text
ENLARGED DEMO PLAN RM 202A
AutoCAD SHX Text
AutoCAD SHX Text 1'
AutoCAD SHX Text 2'
AutoCAD SHX Text 4'
AutoCAD SHX Text 8'
AutoCAD SHX Text 1/4"=1'-0"
AutoCAD SHX Text
AutoCAD SHX Text
ENLARGED PLAN RM 202A
AutoCAD SHX Text
AutoCAD SHX Text 1'
AutoCAD SHX Text 2'
AutoCAD SHX Text 4'
AutoCAD SHX Text 8'
AutoCAD SHX Text 1/4"=1'-0"
AutoCAD SHX Text
AutoCAD SHX Text
REFLECTED CEILING DEMO PLAN RM 202A
AutoCAD SHX Text
AutoCAD SHX Text 1'
AutoCAD SHX Text 2'
AutoCAD SHX Text 4'
AutoCAD SHX Text 8'
AutoCAD SHX Text 1/4"=1'-0"
AutoCAD SHX Text
AutoCAD SHX Text
REFLECTED CEILING PLAN RM 202A
AutoCAD SHX Text X
AutoCAD SHX Text
AutoCAD SHX Text 1'
AutoCAD SHX Text 2'
AutoCAD SHX Text 4'
AutoCAD SHX Text 8'
AutoCAD SHX Text 1/4"=1'-0"
AutoCAD SHX Text
AutoCAD SHX Text
BLDG 40 ROOF PLAN
JMcAllister Snapshot
JMcAllister
TR
VESTIBULE
A-51-102
A-51-102
A-51-102
A-51-102
C
TR
VESTIBULE
TR
VESTIBULE
A-51-101
A-51-101
A-51-101
A-51-101
AREA OF RESCUE
ASSISTANCE
(2 WHEELCHAIRS).
SEE CIVIL
DRAWINGS FOR
FURTHER DETAIL.
STEP UP, 7" RISER
TR
VESTIBULE
EXIT 2 - EXISTING DOOR TO REMAIN. PROTECT
DURING CONSTRUCTION. PROVIDE SIGN PLACARD
READING: "NOT AN EXIT. USE EXIT AT WEST END."
EXISTING FENCE
PROVIDE SIGN PLACARDS READING:
"EAST EXIT TEMPORARILY CLOSED.
UTILIZE EXIT AT WEST END."
PROTECT EXISTING WINDOW
DURING CONSTRUCTION
TEMPORARY
CONSTRUCTION
FENCE
EXIT DISTANCE =
99'-0"
COMMON PATH OF
TRAVEL = 117'-0"
EXIT 1
TEMPORARY
CONSTRUCTION FENCE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
K:
\C
C G
_P R
O
JE
C
TS
\2
8\
-1
6C
9D
V
IS
N
ID
IQ
(N or th D ak ot a
Io w
a) \4
-2
1-
EH
R M
F ar go , N
D \4
- D es D oc s\
2-
D ra w in gs \W
O R
KI
N
G \A
-B
-1
.d w g 3/
/2
:0
3:
A M
ISSUE FOR BIDOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES
FARGO VA HEALTH CARE SYSTEM
437-21-205
Revisions: Date:
www. bancroft-ae.com
3300 Dundee RD.
Northbrook, IL 60062
T: 847.952.9362
ISSUE FOR BID 03-18-22
3/18/2022
SHEET OF 279
Bancroft Project No: 18-121
ARCHITECTURAL - BUILDING 51 -
ENLARGED PLANS & ELEVATIONS
DA JM
A-51-101
1. INSTALL DUST CONTAINMENT AND INFECTION
CONTROL PANEL SYSTEM.
2. INSTALL STICKY MATS BOTH SIDES OF PANEL
DOOR.
3. SEE 4/GI101 FOR INFECTION CONTROL /
CONSTRUCTION SIGNAGE TO BE POSTED.
4. REMOVE SIDING AND INSULATION TO EXTENT
REQUIRED TO ALLOW FOR INSTALLATION OF
ADDITIONAL WALLS AND ROOF CONSTRUCTION.
PREP SUBSTRATE TO CLEANLY RECEIVE NEW
ADJACENT WALL CONSTRUCTION.
5. REMOVE EXISTING WALL MOUNTED SERVER
RACK.
1. 4'X8' AC GRADE 3/4" TRADE SIZE FIRE RATED PLYWOOD BACKBOARD PAINTED HIGH
GLOSS WHITE WITH (2) COATS OF FIRE RESISTANT PAINT FOR SERVICE
PROVIDER/SECURITY/VIDEO/ETC. AROUND PERIMETER WALLS OF TR.
2. GUTTER
3. DOWNSPOUT
4. SNOW GUARD SYSTEM
5. FIRE EXTINGUISHER AND CABINET
6. SIGN 55. SEE SIGNAGE SCHEDULE ON AS-601.
7. SIGN 56. SEE SIGNAGE SCHEDULE ON AS-601.
CONTRACTOR IS REQUIRED TO MAINTAIN ALL RATED PARTITIONS.
SMOKE BARRIER
1 HR FIRE BARRIER
2 HR FIRE BARRIER
SMOKE BARRIER (EXISTING)
1 HR FIRE BARRIER (EXISTING)
2 HR FIRE BARRIER (EXISTING)
A. FOR GENERAL NOTES AND LEGENDS REFER TO SHEET A001.
B. FOR GENERAL INFECTION CONTROL NOTES AND DETAILS REFER TO SHEET GI101.
C. FOR FINISH SCHEDULE REFER TO SHEET AF-601.
EXIT LIMITATIONS ANALYSIS
· BUILDING OCCUPANCY = BUSINESS
· FULLY SPRINKLERED
· GROSS SF = 3,875
· OCCUPANT LOAD = 26
· MAXIMUM ALLOWABLE COMMON PATH OF TRAVEL IS 100'-0"
·· A SINGLE EXIT IS PERMITTED BY NFPA 101, 39.2.4.6 (EXISTING BUSINESS) FOR
SPINKLERED BUILDINGS WITH A COMMON PATH OF TRAVEL NOT EXCEEDING
100'-0"
·· OTHERWISE, TWO MEANS OF EGRESS ARE REQUIRED
SAFETY PROCEDURE
· OFFICES 1008, 1010, 1011, 1013 SHALL NOT BE OCCUPIED WHEN EXIT 2 IS REQUIRED
TO BE CLOSED DURING CONSTRUCTION
DENOTES NEW CEILING
MECHANICAL
ROOM
1024 1025 L
HAC JA
1028 n
TOILET LJ
WORK AREA
TOILET
TORAG 1021
WAITING
OFFICE
RECEPTION
OFFICE
1018 1017 OFFICE
OFFICE RAG
OFFICE
OFFICE
OFFICE
OFFICE
1 BUILDING 51 - FIRST FLOOR PLAN
OFFICE
3'-o"
MIN.
OFFIC:F
I I I I v-EJ I I I I I I ~-51-10~ I I I
OFFICE
OFFIC:F
omcE
OFFICE
omcE
1012 1011
TOILET OFFICE
OFFICE
CONF./BREAK
9/A-51-101 • 10'-10"
10'-10"
C 7/A-51-101
OFFICE I
u u.J u Li" b:, I ---
OFFICE
1 O"
I
N -
' .,..-----.._ --'-+-----i I U')
I
'\i •· .- · ... :. .
' ~. ~-- .' ~ .. ~"""-,+--+----+-f-
0 2' 4' B'
-0
~~ "' I
CX) - ~
IX)
16'
OFFICE
MECHANICAL
ROOM
1028 n
TOILET LJ
WORK AREA
TOILET
OFFICE
RECEPTION
OFFICE
1018 1017 OFFICE
OFFICE RAG
OFFICE
OFFICE
OFFICE
omcE
BUILDING 51 - CONSTRUCTION LIFE SAFETY PLAN
1/8"=1·-o·
9/A-51-101
-51-1
I SLOPE
~1 g
VI
I SLOPE
7/A-51-101
-51-10
-51-10
OFFICE
omcE
OFFICE
- 11 '-:P'---0 o 2· 4• a· 16' ----
CONSTRUCTION LIFE SAFETY SUMMARY
METAL ROOF PANELS
GENERAL NOTES
FLOOR PLAN KEYNOTES
00 DEMOLITION PLAN KEYNOTES
RATED PAR I I I ION LEDGED
•o_o_
■□□- □o- 100-00-
CEILING PLAN LEDGED
,,.-- METAL RAKE CLEAT
-"ilc'n -~ METAL SUPPORT ANGLES
,,------ PREFINISHED RAKE TRIM. MATCH
DEPTH OF EAVE.
0,__~_
~-=~-A_
_R_G_ED_DE_M_O_P_LA_~-,-. ,-. -.-. --,. 0,__E_
~-=~--!R_G_ED_PL_A_N ______
-,. -, -,. --,. 0,__-~
~-=~--!R_G_E_D_C_EIL_IN_G_P_LA_~-,-. ,-. -.-. --,. 0-~-1~-=~-0 .. R_G_ED_ROO_F_P_L~-~--,-. -.-. --,.
\ I , =
~ CONTINUOUS METAL CLEAT
F::;,:~ BRICK VENEER
-- I __ __ ::::::t __
STANDING SEAM
METAL ROOF
SNOW GUARD
METAL SIDING
P/ ROOF
' EL +119'- 10"
DOWNSPOUT - COORDINATE
LOCATION WITH INTEGRAL
SPLASH PAN. SEE CIVIL.
RELOCATE LIGHT FIXTURE
FROM ABOVE EXISTING
ALUMINUM ENTRANCE DOOR
T/ FLOOR
' EL +100'- O"
PROVIDE AND INSTALL DOUBLE
AUTHENTICATION CARD READER
AS PER SPECIFICATIONS
BUILDING 51 ADDITION - NORll-i ELEVATION 1/B"=l'-o" 0 2' 4' B' 18' ---- 8
METAL SIDING
I
_I - - --1:: = = =b -i------r-- -_ -__ - ~ ~
-51-10
BUILDING 51 ADDITION - EAST ELEVATION
1/8"=1 ·-o·
FLASH METAL ROOF
SYSTEM INTO
EXISTING SIDING
P/ ROOF
EL +119'- 10"
GUTTER EDGE W /
DOWNSPOUT
FACE BRICK
PRECAST PANELS
~ TI FLOOR
ci_ +100·- o"
0 'J' 4' ,. 18'
-/3()./flu
BANCROFT ARCHITECTS+ ENGINEERS
STANDING SEAM METAL ROOF --~
SNOW GUARD~
FACE BRICK
P/ ROOF •
EL +119'- 10"
NEW DOWNSPOUT - -
FABRICATE TO DRAIN
TO EXISTING GRAVEL
DRAINAGE BED
EXISTING FENCE ~
PRECAST PANELS
~ ~ +~~~~- o"
C-------BC-----------jE
EXISTING DOWNSPOUT - MODIFY TO
I _ _ _ ALLOW ROOM FOR NEW DOWNSPOUT
EXISTING GRAVEL DRAINAGE BED
J
-51-10
BUILDING 51 ADDITION - SOUTH ELEV A TION
1/8"=1'-o" o 2· ,.. e· 1e·
VA
,,----- EXISTING SIDING
~- CONTINUOUS METAL ANGLE
ATTACHED TO EXISTING SUBSTRATE
~- VAPOR BARRIER MEMBRANE
EXPANSION JOINT TRIM. SLIDE
TRIM UNDER EXISTING SIDING.
EXPANSION JOINT CLEAT
METAL ROOF PANELS
LIGHT GAUGE
STEEL TRUSS -
SEE STRUCTURAL
FIRE RATED WALL
- SEE PLAN
2" EXPANSION JOINT
.,.._____ EXISTING WALL
ROOF EXP JT DTL AT WALL
1/B"=l'-o" 0 2' 4' ff 18' ----
® ~~~~ DETAIL AT BRICK VENEER 'l.iii'~· ·--· iiiii·~· =~18• n
METAL ROOF PANELS ,,.-- MET AL RAKE CLEAT
~- METAL SUPPORT ANGLES
,,------ PREFINISHED RAKE TRIM. MATCH
DEPTH OF EAVE.
~+~~'====:""'i--~- METAL STUD FRAMING
~~k~ E~•-----~ CONTINUOUS METAL CLEAT
...____ PREFINISHED METAL FASCIA.
EXTEND UP BEHIND METAL CLEAT.
'--- SCREEN SOFFIT VENT
PREFINISHED METAL S-SLIP
RECEIVER FOR SOFFIT SCREEN
STEEL SIDING J-CHANNEL
'------- STEEL SIDING
ROOF DETAIL AT SIDING
1/8"=1·-o· D 2' 4' ,. 16' ----
ID□
AutoCAD SHX Text
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text A-51-102
AutoCAD SHX Text
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text A-51-102
AutoCAD SHX Text
SLOPE
AutoCAD SHX Text
SLOPE
AutoCAD SHX Text
SLOPE
AutoCAD SHX Text
SLOPE
AutoCAD SHX Text A-51-102
AutoCAD SHX Text
AutoCAD SHX Text A-51-101
AutoCAD SHX Text
AutoCAD SHX Text A-51-101
AutoCAD SHX Text
AutoCAD SHX Text A-51-101
AutoCAD SHX Text
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text A-51-102
AutoCAD SHX Text
AutoCAD SHX Text
MECHANICAL
AutoCAD SHX Text
ROOM
AutoCAD SHX Text
AutoCAD SHX Text
TOILET
AutoCAD SHX Text
AutoCAD SHX Text
TOILET
AutoCAD SHX Text
AutoCAD SHX Text
WAITING
AutoCAD SHX Text
AutoCAD SHX Text
VESTIBULE
AutoCAD SHX Text
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
CONF./BREAK
AutoCAD SHX Text
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
RECEPTION
AutoCAD SHX Text
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
TOILET
AutoCAD SHX Text
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
WORK AREA
AutoCAD SHX Text
AutoCAD SHX Text
DATA
AutoCAD SHX Text
AutoCAD SHX Text
HAC
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
T/ FLOOR EL +100'- 0"
AutoCAD SHX Text
P/ ROOF EL +119'- 10"
AutoCAD SHX Text
STANDING SEAM METAL ROOF
AutoCAD SHX Text
SNOW GUARD
AutoCAD SHX Text
METAL SIDING
AutoCAD SHX Text
DOWNSPOUT - COORDINATE LOCATION WITH INTEGRAL SPLASH PAN. SEE CIVIL.
AutoCAD SHX Text
RELOCATE LIGHT FIXTURE FROM ABOVE EXISTING ALUMINUM ENTRANCE DOOR
AutoCAD SHX Text
PROVIDE AND INSTALL DOUBLE AUTHENTICATION CARD READER AS PER SPECIFICATIONS
AutoCAD SHX Text
AutoCAD SHX Text A-51-102
AutoCAD SHX Text
T/ FLOOR EL +100'- 0"
AutoCAD SHX Text
AutoCAD SHX Text 7.5
AutoCAD SHX Text
P/ ROOF EL +119'- 10"
AutoCAD SHX Text
FACE BRICK
AutoCAD SHX Text
GUTTER EDGE W/ DOWNSPOUT
AutoCAD SHX Text
METAL SIDING
AutoCAD SHX Text
PRECAST PANELS
AutoCAD SHX Text
FLASH METAL ROOF SYSTEM INTO EXISTING SIDING
AutoCAD SHX Text
AutoCAD SHX Text A-51-102
AutoCAD SHX Text
T/ FLOOR EL +100'- 0"
AutoCAD SHX Text
P/ ROOF EL +119'- 10"
AutoCAD SHX Text
STANDING SEAM METAL ROOF
AutoCAD SHX Text
SNOW GUARD
AutoCAD SHX Text
FACE BRICK
AutoCAD SHX Text
PRECAST PANELS
AutoCAD SHX Text
EXISTING FENCE
AutoCAD SHX Text
NEW DOWNSPOUT - FABRICATE TO DRAIN TO EXISTING GRAVEL DRAINAGE BED
AutoCAD SHX Text
EXISTING DOWNSPOUT - MODIFY TO ALLOW ROOM FOR NEW DOWNSPOUT
AutoCAD SHX Text
EXISTING GRAVEL DRAINAGE BED
AutoCAD SHX Text
AutoCAD SHX Text A-51-102
AutoCAD SHX Text A-51-102
AutoCAD SHX Text
AutoCAD SHX Text
MECHANICAL
AutoCAD SHX Text
ROOM
AutoCAD SHX Text
AutoCAD SHX Text
TOILET
AutoCAD SHX Text
AutoCAD SHX Text
TOILET
AutoCAD SHX Text
AutoCAD SHX Text
WAITING
AutoCAD SHX Text
AutoCAD SHX Text
VESTIBULE
AutoCAD SHX Text
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
CONF./BREAK
AutoCAD SHX Text
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
RECEPTION
AutoCAD SHX Text
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
TOILET
AutoCAD SHX Text
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
WORK AREA
AutoCAD SHX Text
AutoCAD SHX Text
DATA
AutoCAD SHX Text
AutoCAD SHX Text
HAC
AutoCAD SHX Text A-51-102
AutoCAD SHX Text
EXISTING SIDING
AutoCAD SHX Text
CONTINUOUS METAL ANGLE ATTACHED TO EXISTING SUBSTRATE
AutoCAD SHX Text
EXPANSION JOINT TRIM. SLIDE TRIM UNDER EXISTING SIDING.
AutoCAD SHX Text
EXPANSION JOINT CLEAT
AutoCAD SHX Text
VAPOR BARRIER MEMBRANE
AutoCAD SHX Text
METAL ROOF PANELS
AutoCAD SHX Text
LIGHT GAUGE STEEL TRUSS - SEE STRUCTURAL
AutoCAD SHX Text
FIRE RATED WALL - SEE PLAN
AutoCAD SHX Text
EXISTING WALL
AutoCAD SHX Text
2" EXPANSION JOINT
AutoCAD SHX Text
PREFINISHED RAKE TRIM. MATCH DEPTH OF EAVE.
AutoCAD SHX Text
METAL ROOF PANELS
AutoCAD SHX Text
METAL SUPPORT ANGLES
AutoCAD SHX Text
CONTINUOUS METAL CLEAT
AutoCAD SHX Text
BRICK VENEER
AutoCAD SHX Text
METAL RAKE CLEAT
AutoCAD SHX Text
PREFINISHED RAKE TRIM. MATCH DEPTH OF EAVE.
AutoCAD SHX Text
METAL ROOF PANELS
AutoCAD SHX Text
METAL SUPPORT ANGLES
AutoCAD SHX Text
CONTINUOUS METAL CLEAT
AutoCAD SHX Text
PREFINISHED METAL S-SLIP RECEIVER FOR SOFFIT SCREEN
AutoCAD SHX Text
METAL RAKE CLEAT
AutoCAD SHX Text
PREFINISHED METAL FASCIA. EXTEND UP BEHIND METAL CLEAT.
AutoCAD SHX Text
SCREEN SOFFIT VENT
AutoCAD SHX Text
STEEL SIDING J-CHANNEL
AutoCAD SHX Text
STEEL SIDING
AutoCAD SHX Text
METAL STUD FRAMING
AutoCAD SHX Text
AutoCAD SHX Text 1'
AutoCAD SHX Text 2'
AutoCAD SHX Text 4'
AutoCAD SHX Text 8'
AutoCAD SHX Text 1/4"=1'-0"
AutoCAD SHX Text
AutoCAD SHX Text
ENLARGED DEMO PLAN
AutoCAD SHX Text
AutoCAD SHX Text 1'
AutoCAD SHX Text 2'
AutoCAD SHX Text 4'
AutoCAD SHX Text 8'
AutoCAD SHX Text 1/4"=1'-0"
AutoCAD SHX Text
AutoCAD SHX Text
ENLARGED PLAN
AutoCAD SHX Text
AutoCAD SHX Text 1'
AutoCAD SHX Text 2'
AutoCAD SHX Text 4'
AutoCAD SHX Text 8'
AutoCAD SHX Text 1/4"=1'-0"
AutoCAD SHX Text
AutoCAD SHX Text
ENLARGED ROOF PLAN
AutoCAD SHX Text
AutoCAD SHX Text 1'
AutoCAD SHX Text 2'
AutoCAD SHX Text 4'
AutoCAD SHX Text 8'
AutoCAD SHX Text 1/4"=1'-0"
AutoCAD SHX Text
AutoCAD SHX Text
ENLARGED CEILING PLAN
AutoCAD SHX Text
DEMOLITION PLAN KEYNOTES
AutoCAD SHX Text
GENERAL NOTES
AutoCAD SHX Text
FLOOR PLAN KEYNOTES
AutoCAD SHX Text X
AutoCAD SHX Text
AutoCAD SHX Text 2'
AutoCAD SHX Text 4'
AutoCAD SHX Text 8'
AutoCAD SHX Text 16'
AutoCAD SHX Text 1/8"=1'-0"
AutoCAD SHX Text
AutoCAD SHX Text
BUILDING 51 - FIRST FLOOR PLAN
AutoCAD SHX Text
RATED PARTITION LEDGED
AutoCAD SHX Text
AutoCAD SHX Text 2'
AutoCAD SHX Text 4'
AutoCAD SHX Text 8'
AutoCAD SHX Text 16'
AutoCAD SHX Text 1/8"=1'-0"
AutoCAD SHX Text
AutoCAD SHX Text
BUILDING 51 ADDITION - NORTH ELEVATION
AutoCAD SHX Text
AutoCAD SHX Text 2'
AutoCAD SHX Text 4'
AutoCAD SHX Text 8'
AutoCAD SHX Text 16'
AutoCAD SHX Text 1/8"=1'-0"
AutoCAD SHX Text
AutoCAD SHX Text
BUILDING 51 ADDITION - EAST ELEVATION
AutoCAD SHX Text
AutoCAD SHX Text 2'
AutoCAD SHX Text 4'
AutoCAD SHX Text 8'
AutoCAD SHX Text 16'
AutoCAD SHX Text 1/8"=1'-0"
AutoCAD SHX Text
AutoCAD SHX Text
BUILDING 51 ADDITION - SOUTH ELEVATION
AutoCAD SHX Text
AutoCAD SHX Text 2'
AutoCAD SHX Text 4'
AutoCAD SHX Text 8'
AutoCAD SHX Text 16'
AutoCAD SHX Text 1/8"=1'-0"
AutoCAD SHX Text
AutoCAD SHX Text
BUILDING 51 - CONSTRUCTION LIFE SAFETY PLAN
AutoCAD SHX Text 7/A-51-101
AutoCAD SHX Text 8/A-51-101
AutoCAD SHX Text 9/A-51-101
AutoCAD SHX Text
CONSTRUCTION LIFE SAFETY SUMMARY
AutoCAD SHX Text 7/A-51-101
AutoCAD SHX Text 8/A-51-101
AutoCAD SHX Text 9/A-51-101
AutoCAD SHX Text
AutoCAD SHX Text 2'
AutoCAD SHX Text 4'
AutoCAD SHX Text 8'
AutoCAD SHX Text 16'
AutoCAD SHX Text 1/8"=1'-0"
AutoCAD SHX Text
AutoCAD SHX Text
ROOF EXP JT DTL AT WALL
AutoCAD SHX Text
AutoCAD SHX Text 2'
AutoCAD SHX Text 4'
AutoCAD SHX Text 8'
AutoCAD SHX Text 16'
AutoCAD SHX Text 1/8"=1'-0"
AutoCAD SHX Text
AutoCAD SHX Text
ROOF DETAIL AT SIDING
AutoCAD SHX Text
AutoCAD SHX Text 2'
AutoCAD SHX Text 4'
AutoCAD SHX Text 8'
AutoCAD SHX Text 16'
AutoCAD SHX Text 1/8"=1'-0"
AutoCAD SHX Text
AutoCAD SHX Text
ROOF DETAIL AT BRICK VENEER
AutoCAD SHX Text
CEILING PLAN LEDGED
JMcAllister Snapshot
JMcAllister
A-51-102
A-51-102
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
K:
\C
C G
_P R
O
JE
C
TS
\2
8\
-1
6C
9D
V
IS
N
ID
IQ
(N or th D ak ot a
Io w
a) \4
-2
1-
EH
R M
F ar go , N
D \4
- D es D oc s\
2-
D ra w in gs \W
O R
KI
N
G \A
-B
-1
.d w g 3/
/2
9:
:1
AM
ISSUE FOR BIDOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES
FARGO VA HEALTH CARE SYSTEM
437-21-205
Revisions: Date:
www. bancroft-ae.com
3300 Dundee RD.
Northbrook, IL 60062
T: 847.952.9362
ISSUE FOR BID 03-18-22
3/18/2022
SHEET OF 279
Bancroft Project No: 18-121
ARCHITECTURAL - BUILDING 51 -
SECTIONS AND DETAILS
DA JM
A-51-102
PREFINISHED METAL STANDING -~
SEAM ROOF PANELS
ICE AND WATER SHIELD AT -~
BOTTOM 48" OF ROOF
CONTINUOUS FLASHING
PREFINISHED METAL FASCIA AND GUTTER.
MATCH SHAPE/Sn'LE OF EXISTING
GUTTER ON ADJACENT BUILDING.
GUTTER HANGER BRACKET -~
METAL END TRACK AT
END OF TRUSS
PREFINISHED METAL FASCIA. EXTEND
UP BEHIND GUTTER. FACE ANCHOR
THROUGH SOFFIT TO FRAMING.
SCREEN SOFFIT VENT (APPROX. 2" WIDTH)
PREFINISHED METAL S-SLIP RECEIVER
FOR SOFFIT SCREEN
GALVANIZED CONTINUOUS METAL
L -BRACKET TO SUPPORT S-SLIP RECEIVER
BUILDING 51 - EAVE DETAIL AT SIDING
1-1/2"=1'-o"
CONTINUOUS FLASHING
METAL END TRACK AT END OF
TRUSS
PREFINISHED METAL FASCIA AND GUTTER. +"-...-.:;,....,
MATCH SHAPE/Sn'LE OF EXISTING
GUTTER ON ADJACENT BUILDING.
SCREEN SOFFIT VENT (APPROX.
2" WIDTH)
'i' B.O. FIN. CLG.
9'-0"
STEEL LAP SIDING - 6"
EXPOSURE
2" RIGID INSULATION
MOISTURE BARRIER
1 /2" FIBERGLASS MAT GYPSUM SHEATHING --
6" METAL STUD W/ BATT INSULATION -~
5/8" GYPSUM BOARD
FLEXIBLE FLASHING W/ STAINLESS STEEL DRIP
EDGE. INSERT DRIP EDGE INTO SAWCUT IN SLAB
AND FILL WITH CONTINUOUS BED OF SEALANT.
LOXON XP (OR VA APPROVED EQUAL)
WATERPROOFING MASONRY COATING EXTEND MIN
2" BELLOW CONCRETE STOOP OR WALK
STOOP- CONG. OVER DECK--~
SEE STRUCT. DWGS.
I .
1/2'
SUSPENDED
A.C.T. CEILING
SCHED. BASE -
)XP.
½ ISOLATION
JOINT WITH
COMPRESSIBLE
FILLER
•. ~7'--------jg • , : • - ". . 11, A . • ... ·. ----~-~ -~-- _ ... , .. · .. •,,: ~ __ _.~ _·_ -..:..--,-.....:., ·r· L
VOID BELOW STOOP- SEE
STRUCT. DWGS.
. -..... · .r . ~.
: ... · .J .. ·•.
• A • J--:- - .• •
.•• 1 ..
. I ...
. . J
'!·- · I •.
• I : . i-
2' POLYS1YRENE
INSULATION AS
SPECIFIED
· .. I· :J::' ~;1--.~ CONC. FND. WALL
I :·+ ··. ~ AND FTG, 1YP.-
• • _ •1 •• ~ 1 SEE STRUCT.
_ .. _.. -~ ,. · • • DWGS.
.. .. . _. r :- -. -.. · . . ·L·~·· ..
CD BUILDING 51 - SECTION 11--------
3/4"=1'-o" , 11,· ,· , I'
MANUFACTURER'S METAL RIDGE
TRIM WITH PERFORATED VENT
1 1/t
COMPOSITE DECK
SEE STRUCT. DWGS.
8" CM
2-1/2'' MTL
STUDS @ 16
O.C.- EA. SID
u
E
5/8" GYPSUM BD
EA. SID E
SCHED. BASE-1'/P
1/2'' ISOLATIO
JOINT- EA. SID ~~
2" POLYS1YEREN
INSULATION A
SPECIFIED, 1YP
E s
· s '
STEEL BEAM, SEE
STRUCTURAL DWGS
1 HR RATED WALL
ASSEMBLY TO UNDERSIDE
OF CONCRETE/METAL
DECK ABOVE
1 HR RATED WALL
ASSEMBLY TO UNDERSIDE
OF CONCRETE/METAL
DECK ABOVE
L
/I CONC. FOUNDATION
/ , WALL AND FOOTING
SEE STRUCTURAL
DRWGS.
0 BUILDING 51 - SECTION 2 ------
3 / 4" = 1 '-o" o 111 ,. 2· :s·
CONTINUOUS FLASHING
PREFINISHED METAL FASCIA AND
GUTTER. MATCH SHAPE/Sn'LE OF
EXISTING GUTTER ON ADJACENT
BUILDING.
T.O CMU
13'-4"
...._...._-J..__ METAL END TRACK AT END
OF TRUSS
---._ ___ SCREEN SOFFIT VENT
(APPROX. 2.5" WIDTH)
~--- CONTINUOUS PREFINISHED
METAL L -BRACKET TO HOLD
SCREEN SOFFIT VENT
BUILDING 51 - EA VE DETAIL AT BRICK
1-1/2"=1'-0" 0 .......-- '0
,. 1 1ft I
STANDING SEAM STEEL METAL ROOF OVER 30# ROOFING
FELT OVER DENSDECK OVER PLYWOOD DECK OVER LIGHT
GAUGE STEEL TRUSSES. PROVIDE "HIGH-TEMPERATURE" 1YPE
ICE AND WATER SHIELD MEMBRANE AT BOTTOM 48" OF ROOF.
~- LIGHT GAUGE STEEL ROOF
TRUSSES- SEE STRUCT.
CONTINUOUS
FLASHING
PREFINISHED METAL
FASCIA AND GUTTER.
MATCH SHAPE/S1YLE OF 7 EXISTING GUTTER ON
ADJACENT BUILDING.
T.O CMU'i' 13'-4"
I METAL END TRACK AT
_J END OF TRUSS
B.O. TRUSS
11'-7"
T.O. BEAM
• 11 '-2"
SCREEN SOFFIT VENT
(APPROX. 2.5" WIDTH)
12" FOIL FACED BATT
INSULATION
CMU BOND BEAMS,
1YP.- SEE STRUCT.
DWGS.
------- FACE BRICK
------- AIR SPACE
....i------
----- MASONRY TIES @ 16"
O.C. VERT.
,.-.,.-- ~=,---- ------- 3" RIGID INSULA Tl ON
8" NOMINAL CMU -,
5/8" GYPSUM BOARD
2 1 /2'' METAL STUDS
@ 16" O.C.
1 /2'' ISOLATION JOINT
WITH COMPRESSIVE
FILLER
SLAB ON GRADE
SEE STRUCT. DWGS.
.,,,.-- FLUID-APPLIED VAPOR
BARRIER RETARDER
EXTEND UP AND OVER
CMU WALL
l""'l-J<..----,=-PRE-CAST WATER-TABLE
TO MATCH EXISTING
INSTALL WEEP VENTS AT
BASE @ 24' O.C.
tftLJ._.'.4'--:,;r- FLEXIBLE FLASHING
,,.------ STAINLESS STEEL DRIP
EDGE :.,. r ,__ .-· -.. ~, -. ,___,,_,,_ " . ~• ~. '--1" T.O. o~.:'6~"' ~g ~ ~ ~ ·~ • • •
· ·· · : ·• · FIN. PAVEMENT
2" POLYS1YERENE _.1.:..-----· tt1-~ ,.: •: :·•' COMPRESSIBLE
INSULATION AS • • · JOINT FILLER
SPECIFIED l 1'-5" l LOXON XP (OR VA
, ' APPROVED EQUAL)
WATERPROOFING MASONRY
COATING EXTEND MIN. 2"
CONG. FOUNDATION ~
WALL AND FOOTING- 1'\
SEE STRUCTURAL \ '\
DRWGS.
I
. . '4~ .. -·~ •, . ··. ... . . .· .
... 4 ... . .. .. . ·~ •• ..
BELOW CONCRETE STOOP
OR WALK
0 BUILDING 51 - SECTION 3 1--------
3/4":1'-o" o 112· r 2· 3•
-- I
-/3()./flu
BANCROFT ARCHITECTS+ ENGINEERS
EXIST. BUILDING
EXIST. RIGID INSULATION
EXIST. STEEL LAP SIDING
P.T. BLOCKING…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .