C-2 Attachment 7 DDC HVAC Control Record Drawings.pdf

PDF 1 MB Posted

Attached to
JRD Compound Heating - Ventilation - Air Conditioning & Envelope Improvements Federal contract opportunity
Solicitation number
1240BJ26Q0001
Issued by
Department of Agriculture Forest Service

About this file

This document is a set of record drawings and technical specifications for the ANM-JRD Shop Controls Upgrade project in Juneau, Alaska, prepared by Meridian Systems, Inc. The project involves a Building Automation/HVAC Control System upgrade (Project Number 2017-AK-33) and includes detailed control system design documentation, wiring specifications, equipment schedules, and control sequences of operation.

The technical specifications detail a comprehensive DDC (Direct Digital Control) system utilizing Automated Logic equipment including LGR25 gateway modules, SE6104 and M-series control modules, and ZN-series field controllers. Key components include standard cable specifications for Class 2 wiring (18/2 AWG twisted pair for I/O, 22/2 AWG shielded for ARC156/CMnet communication, and CAT5E for Ethernet), transformer schedules specifying 100VA units distributed across multiple panels, and a water control valve schedule with 23 fan terminal units (FTUs) using Spartan three-way modulating valves. The system architecture comprises four main control panels (PNL-1 through PNL-4) distributed across warehouse, storage, and administration buildings with CMnet (ARC156) network communication at 156 kbaud. The HVAC controls sequence of operation specifies boiler control with lead/standby pump operation, heat exchanger control with outdoor air reset, AHU-1 supply/return fan VFD speed control maintaining 0.375" static pressure setpoint, economizer operation, and 23 individually controlled fan terminal units with zone-level temperature setpoint adjustment, heating/cooling modulation, and occupancy-based scheduling. Installation requirements mandate plenum-rated cabling, proper wire labeling using Brady ID.Pro Plus system or equivalent, and adherence to national and local electrical codes with all DDC wiring terminations free of splices.

View the file

Other files for this federal contract opportunity

Show all 18

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ANM-JRD Shop Controls Upgrade

Juneau, Alaska

200 W 34th Ave #969 Anchorage, Alaska 99503

As Prepared By

Project Number:

Building Automation / HVAC Control System

2017-AK-33

Record Drawings

Phone Number: (907) 279-3320 Fax Number: (907) 279-2369

JOB NO: 2017-AK-3312/8/2017RecordREV: 0

Table of Contents

Table of Contents

Juneau, Alaska

ANM-JRD Shop Controls Upgrade

CHECK BY: CW

DSCODE: JK

1: Titlepage 2: Table of Contents 3: Cable Specification Chart 4: DDC Electrical Installer Notes 5: ARCnet/CMnet Wiring Guide 6: Summary Bill of Materials 7: Valve Schedule 8: Transformer Schedule 9: Control Module Schedule 10: Network Riser Diagram 11: PNL-1 Layout/Warehouse

Cable Specification Chart

Cable Specification Chart

Juneau, Alaska

ANM-JRD Shop Controls Upgrade

CHECK BY: CW

DSCODE: JK

Meridian Systems Conductor Color Standard:

All Input/Output wiring must adhere to the following color standard:

1) BLACK (B) conductor is always for the Ground (Gnd)/ Neutral (N)/ Common (Cmn) reference.

2) WHITE (W) conductor is for the Signal from any field device serving an Analog input, the switched leg of the Digital output to include one of the 2 switched legs of a tri-state / floating motor actuator or the 0/10 VDC signal of an Analog output.

3) RED (R) conductor is for 24 VAC/VDC supply voltage to either Input or Output devices or one of the 2 switched legs of a tri-state / floating motor actuator.

Cable Type / Tag AWG Conductors Shield Plenum Typical Application ConnectAir Part # Jacket Color Conductor Colors

18 2 No Yes 24V Power W181P-2051PRB Purple Red/Black

18 2 No Yes Input / Output (2 Cond) W181P-2051PRB White White/Black

18 3 No Yes Input / Output (3 Cond) W183C-2052PRB White White/Black/Red

22 2 Yes Yes BAS Communication - ARCnet, MSTP, Modbus W221P-2227RIB Green White/Black

22 4 Yes Yes Rnet Communication to ZS & RS Thermostats W224C-2057WBLB White w/ Blue Stripe Red/Green/White/Black

23 4PR No Yes CAT6 Ethernet W244P-2274ORGB Orange Multi-Color

- - - Fiber Optic (Prov ided by Others) - - -

Meridian Systems Standard Cable Specificat ions

DDC Electrical Installer Notes

DDC Electrical Installer Notes

Juneau, Alaska

ANM-JRD Shop Controls Upgrade

CHECK BY: CW

DSCODE: JK

General Notes:

Note the following items and return a copy of these drawings with “As-Built” notations on them. The DDC Installer shall provide the ARCnet and Power As-Builts, at a minimum, prior to DDC Network Start-up.

1) Electrical installation shall be in accordance with the project specifications, national, state, and local electrical codes.

2) Power sources (Panel # & Circuit #) for all DDC transformers.

3) Any renumbering or identification / references used in the field for transformers, devices, wiring, etc.

4) Locations of any devices mounted remotely from the Mechanical Rooms, e.g., above a ceiling spaces, isolated areas, etc.

5) Final locations of transformers, e.g., grouped on a gutter serving several DDC panels, electrical rooms, etc.

6) General routing diagram of wiring / cabling throughout facility on a floor plan view of the project.

7) Any unique wiring required when interfacing with existing equipment, e.g., HOA switches in starters, smoke detectors, fire alarm systems, control valves or actuators, etc.

8) Any equipment deficiencies or maintenance issues found, e.g., broken or slipping V-belts, dirty or missing filters, non-functional devices, motors, etc. or unusual noises or other indications of imminent failures.

9) Locate sensors in associated rooms according to Contract Drawings (site coordination may be required); sensors are to be centered 48" above finished floor.

10) All DDC wiring shall be in installed per contract requirements as noted in project specifications.

11) All DDC wiring shall be terminated at the locations designated and must be free of splices.

12) All DDC cable shall meet the multi-conductor cabling chart as noted on the Cable Specification Chart, sheet 3. Alternatives are not acceptable unless approved by the Operations Manager.

13) All DDC panels, ZN Module enclosures (including VAV boxes) and transformers shall have an MSI label affixed. DDC Installer shall fill in the associated information on the label using a fine point Sharpie and legible penmanship.

All poly tubing shall be plenum rated. Poly tubing installation shall meet the same electrical installation requirements of the project.

All DDC system power sources will have dedicated 120Vac circuits. A duplex receptacle shall be installed as shown on the Network Riser Diagram using the aforementioned dedicated circuit. All Ground/Neutral/Common conductors on the secondary side of a power supply transformer shall be earth grounded.

Every effort should be made to mount ZN Modules directly above the associated room sensor or as near as possible with the exception of factory mounted VAV modules. Any ceiling tile / T-bar shall be tagged/ labeled/ dotted to indicate a DDC device/ZN Module/etc. is located above it.

ZN/RC Module addressing dials shall be set by the DDC Installer using the Control Module Schedule.

MSI standardizes on switching the Hot (potential) leg of any control circuit not the Neutral.

DDC Installer shall reference manufacturer’s installation documentation for devices provided by DDC.

DDC Wire Labels:

The Meridian Systems, Inc. (MSI) Electrical Subcontractor is required to label each end of all installed cable(s). Adherence to this identification system is mandatory and must be followed using the Brady I.D. Pro Plus electronic labeling system or equivalent. Reference figures below for typical DDC wire labeling standards.

Figure 1: 24V Power Label Figure 2: ARCnet/Modbus Label Figure 3: M/SE Label Figure 4: ZN/RC Label Figure 5: ZS/RS Label

Typical DDC Pressure Settings:

Figure 6: Veris PXULX05S Jumper Settings Figure 7: Veris PH0X7S Jumper Settings

Device Address Expander Number Point Type and Address

Point Types – Analog Input (AI), Digital Input (DI), Analog Output (AO), Digital Output (DO).

The M/SE Line control modules are typically located inside a DDC panel.

Tab Label Text - Point Name : 2-0-AI01 Point Name (UI / UO)1

Unique number assigned to specific input/output.

Reference control drawings for tag number.

The ZN/RC Line control modules are typically located out in the field.

Rnet

The Rnet cable is wired from the control module Rnet port to the associated ZS or RS sensor.

ARCnet (CMnet) Label

Modbus Label

Transformer (XFMR) # Transformer Output #

The transformer output only applies to the Functional Devices PSH500A/PSH300A transformers.

XFMR 1-A

CMnet In – DEV: XX

CMnet Out – DEV: XX

This labeling method is used to assist the Technician in network troubleshooting if necessary.

Equipment Name

Label the Modbus cable with the equipment name, e.g., AHU-1 SF VFD, P-1 VFD, Electric Meter, etc.

Water System

Range: B (0-50psig) JP1: Volts

JP2: 0-5V

JP3: Slow

Steam System

Range: A (0-25psig) JP1: Volts

JP2: 0-5V

JP3: Slow

Filter

Range: 4 (0-2.5 WC) SW4: Volts

JP4: 0-5V

JP5: Unidirectional JP7: Inches WC JP8: Standard

Duct Static

Range: 4 (0-2.5 WC) SW4: Volts

JP4: 0-5V

JP5: Unidirectional JP7: Inches WC JP8: Standard

Building Static

Range: 0 (0-0.1 WC) SW4: Volts

JP4: 0-5V

JP5: Bidirectional JP7: Inches WC JP8: Standard

ARCnet/CMnet Wiring Guide

ARCnet/CMnet Wiring Guide

Juneau, Alaska

ANM-JRD Shop Controls Upgrade

CHECK BY: CW

DSCODE: JK

CMnet

ARC156 / CMnet Wiring Detail ARC156 / CMnet Daisy Chain Configuration

VAV-3

VAV-4

VAV-5

CMnet

ARC156 (CMnet) termination point on all Modules

(LG, M, S, ZN,

etc.).

Summary Bill of Materials

Summary Bill of Materials

Juneau, Alaska

ANM-JRD Shop Controls Upgrade

CHECK BY: CW

DSCODE: JK

Summary Bill of Materials

DID DESCRIPTION MANUFACTURER PART NUMBER QTY

RS RNET ZONE TEMP SENSOR WITH COMM AUTOMATED LOGIC RS 3 ea SDU500 SURGE PROTECTOR, 120VAC BATTERY BACK-UP SOLA SDU500 3 ea

Valve Schedule

Valve Schedule

Juneau, Alaska

ANM-JRD Shop Controls Upgrade

CHECK BY: CW

DSCODE: JK

Page intentionally left blank, the scope of work for this project updated did not require any additional valves.

Transformer Schedule

Transformer Schedule

Juneau, Alaska

ANM-JRD Shop Controls Upgrade

CHECK BY: CW

DSCODE: JK

Part # / XFMR # Output Dev ices Serv ed

VA

Load UPS Transformer Location

Panel Location Panel Circuit

TR100VA002 / 1 (Existing) - PNL-1 (DEV PWR) 44 TR100VA002 / 2 (Existing) - PNL-1 (FIELD PWR) 12 Warehouse 1 5 TR100VA002 / 3 (Existing) - PNL-1 (DEV PWR) 24 Storage Storage Bldg 2 15 TR100VA002 / 4 (Existing) - PNL-3 (DEV PWR) 20 TR100VA002 / 5 (Existing) - PNL-3 (FIELD PWR) 14 TR100VA002 / 6 (Existing) - PNL-4 (DEV PWR) 40 TR100VA002 / 7 (Existing) - PNL-4 (FIELD PWR) 24 TR100VA002 / 8 (Existing) - DEV:7, 8, 9, 10 80 Rm A 101 Rm A 101 - - TR100VA002 / 9 (Existing) - DEV:11, 12, 13, 14 80 Rm A 122 Rm A 122 - - TR100VA002 / 8 (Existing) - DEV:15, 16, 17, 18 80 Rm A 125 Rm A 125 - - TR100VA002 / 9 (Existing) - DEV:19, 20, 21, 22 80 Rm A 112 Rm A 112 - - TR100VA002 / 8 (Existing) - DEV:23, 24, 25 60 Rm A 203 Rm A 203 - - TR100VA002 / 9 (Existing) - DEV:26, 27, 28 60 Rm A 215 Rm A 215 - - Note: Each transformer output, e.g., 1-1, is rated for 100VA. Meridian Systems, Inc. recommends not exceeding 80 VA load. The VA calculations can be found on the DDC Control Module Schedule.

3 - Administration

Bldg.

1st Floor Boiler

Rm

4 - Administration

Bldg.

3rd Floor

Mech. Rm

Transformer Schedule

(NEW)

SDU500

(NEW)

SDU500

(NEW)

SDU500

Warehouse Mech Rm

Control Module Schedule

Control Module Schedule

Juneau, Alaska

ANM-JRD Shop Controls Upgrade

CHECK BY: CW

DSCODE: JK

Page intentionally left blank, the scope of work for this project updated did not require any additional control modules.

Network Riser Diagram

Network Riser Diagram

Juneau, Alaska

ANM-JRD Shop Controls Upgrade

CHECK BY: CW

DSCODE: JK

SDU500

120 VAC

PNL:1

Ckt: 5

SDU500

120 VAC

120 VAC

SDU500

Bill of Materials

DID DESCRIPTION MANUFACTURER PART NUMBER QTY

SDU500 SURGE PROTECTOR, 120VAC BATTERY BACK-UP SOLA SDU500 3 ea

1 3 SDU500s added to the system for power surges power outage protection

PNL-1 Layout/Warehouse

PNL-1 Layout/Warehouse

Juneau, Alaska

ANM-JRD Shop Controls Upgrade

CHECK BY: CW

DSCODE: JK

XFMR 1

CMnet – Out

W B Sh W B Sh

XFMR 2

CMnet – In

DEV: 2

AHU-1

Warehouse

Rnet

Gnd Rnet+ Rnet- +12V

AUTOMATED LOGIC

Rnet

Gnd Rnet+ Rnet- +12V i

RS

Typ of 3

1 New RS sensors added to existing system

1 82 3 4 5 6 7 O N

485-2w 485-4w

Port S1

Ext. Batt.

Int. Batt.

DCD

DTR

Rx Tx

EIA-2324 wire2 wire

Signal Ground

Rx- Rx+ Tx- Tx+ n/c n/c

Net- Net+

External Battery

Gnd +3V

Ground 24V ac/dc

Power

On Off

Module Status

3V Lithium Battery CR-123A10/100 BaseT

Ethernet Port E1

100 LAN LINK

Cmnet transmit Cmnet receive

Port S1 receive Port S1 transmit

Battery low

Blinking Dot = “Run”

Format

BACnet Over ARCNET156 KBaud

LGR25

Control Module

Without Keypad Display:

24Vac, 24VA, 1A, 50-60 Hz 26Vdc, 10W, 0.4A

Use Copper Conductors Only Class 2

Net +

Net -

Shield

CMnet

Rnet Local Access

Gnd Rnet + Rnet - +12V

Rnet

Off

On

Enhanced Access Port on S2 IP Addr

Module Address

10's 1's

BT485

Archive Valid

Power

LED

BT485

Port S2

BT485

Error Codes:

DCD

DTR

Rx Tx n/c n/c

Net- Net+

EIA-

485 232

EIA-232

EIA-485

EIA-232

EIA-485

Default

Assigned

+100

Disable

Enable

Disable

Enable

Address

MSTP

on S1

PTP

on S2

Tx

Rx

Option Comm

Signal Ground

Chase = OK 0 = Download required 1 = Control Program Error 2 = RAM full 3 = Comm setup error 4 = System error 8 = Formatting

LGR25

Module Pwr

DEV: 1

DDC Gateway

W B Sh

CMnet

R B

Field Pwr

Terminal Block

TB-2

B

R 24VAC

GND

Terminal Block

TB-1

R B

W B Sh W B Sh

CMnet

CMnet

B

R 24VAC

GND

Sh B W

SF Status : 2-0-DI01 W B

Freezestat : 2-0-DI02

MA Temp : 2-0-AI03

RA Temp : 2-0-AI04

DA Temp : 2-0-AI05

W B W R W B W B

CMnet

P-1 Start/Stop : 2-0-AO01

P-2 Start/Stop : 2-0-AO02

Point Name : 2-0-DO01

Point Name : 2-0-DO02

BACnet Over ARCNET156 KBaud

TM Class 2 24Vac, 50-60 Hz

20VA, 0.83A

Use Copper

Conductors Only

Caution:

To Reduce the Risk of Fire or Electrical Shock, Do Not interconnect the Outputs of Different Class 2 Circuits.

Module Address 10's 1's

+ Aux Power Out On Off

SE6104

CONTROL MODULE

1 2 3 4 O N

Gnd 24V-ac Gnd

Power

IN-1

Gnd

IN-2

Gnd

IN-3

Gnd

IN-4

Gnd

IN-5

Gnd

IN-6

Gnd

IN-7

Gnd

IN-8

Gnd

IN-9

Gnd

AO-4

DO-2

DO-1

DO-3

DO-4

DO-5

DO-6

7+

Gnd

AO-3

5+

Gnd

AO-2

3+

Gnd

AO-1

1+

Gnd

IN-10

Gnd

Select +5V +24V

AO Mode Select 0-10V 0-20mA

Tx

Rx

Batt

CR2032

BACnet

Shield

Net-

Net+

BT485

Inputs: All 10V Max, 20mA Max

IN-1, IN-2: Pulse Count Ability

Outputs 24V Max, 3A Max

Auto Off On

LogiStat Port

Rnet

Gnd

Temp

Sw

LS5v

Gnd

Rnet+

Rnet-

+12V

LogiStat (IN-9, 10 disabled)

Rnet

Stat Select

G nd

R ne t+ R ne t-

Se ns e +1

2V

Error

Run

Format mA VoltsThermister/ dry contact/

RTD

Local Access

MSTP Baud

Cmnet Mode

76.8k

38.4k

19.2k

9600 ARC156

MSTP

Universal Input Mode Select

SE6104

Made in USA

W B W B

W B W B

R

R

10 B W G R

AUTOMATED LOGIC

RS PRO

Bill of Materials

DID DESCRIPTION MANUFACTURER PART NUMBER QTY

RS RNET ZONE TEMP SENSOR WITH COMM AUTOMATED LOGIC RS 3 ea

Juneau, AK

Building Automation / HVAC Control System Specification Section 15900

200 W. 34th Avenue # 969 Anchorage, Alaska 99503- 3969 Phone 907 279 3320 Fax 907 279 2369

Project #: 2006-AK-41

Record Drawings

Project #: 2005-AK-31

Job #: 06-AK-419/20/07Record DrawingsRev: N/A

Table of Contents

Specification Section 15900

Juneau, AK ANM-JRD Facilities Phase I & II

Checked by: EP

Engineer: DMD

Table of Contents

1: Titlepage 2: Table of Contents 3: Cable Specification Chart 4: Installation Notes 5: Valve Schedule 6: Summary Bill of Materials 7: System Layout / Riser Diagram 8: PNL-1 Layout/Warehouse 9: AHU/EF-3 & 4 Control 10: PNL-2 Layout/Storage Bldg 11: PNL-3 Layout / Admin Bldg 12: Heating System Control 13: PNL-4 Layout / Admin Bldg 14: AHU-1 Control 15: EF 3-1 & 3-2 Control 16: EF 3-3 Control 17: Zone Control - FTU VAV Box 18: Zone Control - FTU VAV Box w/SP 19: Misc. non-DDC Controls

Cable Specification Chart

Specification Section 15900

Juneau, AK ANM-JRD Facilities Phase I & II

Checked by: EP

Engineer: DMD

Cable Specification Chart

MERIDIAN SYSTEMS STANDARD CABLE SPECIFICATIONS AND ABBREVIATIONS

Wire/Cable Line Type/Tag Wire Type

12 / 14 / 16 AWG THHN

(Gauge is as NEC dictates per amperes or match existing.)

Typical Application

NEC Class 1 Wiring

Circuit Type

120 VAC Power 120 VAC Neutral 120 VAC Ground

Conductor Color

Black White Green

18/2 AWG Twisted Pair, Plenum Rated, Unshielded

Input/Output Wiring Class 2 Wiring Only

INA

INB

White Black (with White Jacket)

18/2 AWG Twisted/Shielded Single Pair

Black Red (with White Jacket)

EIA-485-4W EIA-232-4W

Tx+ Tx Tx- Rx Rx+ DTR/RTS Rx- DCD/CTS

Black Red Green White (with White Jacket)

Portal 4 Wire Communication22/4 AWG Twisted/Shielded Double Pair, Plenum Rated

Black White (with Green Jacket)

Net+ Net- Shield

ARC156,

Unet Communication (no power wire)

22/2 AWG Twisted/Shielded Plenum Rated

Pair 1 (14 ga) Red Green Pair 2 (22 ga) Black White (with Pink Jacket)

Pair 1

24 VAC

Grd Pair 2 Unet+ Unet-

Unet (with power wire)(1) pair 14AWG for power and (1) pair 22AWG for communications (Plenum Rated)

Green Red Yellow Black (with White Jacket)

Grd Temp

SW

LS5v

RNet22/4 AWG Twisted, Unshielded, Plenum Rated, Stranded, Unshielded, Plenum

Pr.1 White/Blue & Blue Pr.2 White/Orange&Orange Pr.3 White/Green & Green Pr.4 White/Brown & Brown (with Blue Jacket)

Network CommunicationsEthernet24/8 AWG CAT 5 Enhanced, Plenum Rated 100MHz

Tight Buffered Tube Cable 6 Multi -mode 62.5/125 m terminated with ST connectors

Fiber Optic Network Communications N/A

Communication RS-485 2-Wire, Sitelink, I/O Requiring Shield

Net+ or Tx or + Net- or Rx or -

5 18/3 AWG Twisted Pair, Plenum Rated, Unshielded

Input/Output Wiring Class 2 Wiring Only

INA

INB

White Black Red (with White Jacket)

14 / 16 AWG Plenum Rated 14 Gauge 16 Gauge

NEC Class 2 Power Wiring Power to ZN Controllers

Wht Blk

UNet Comm Pair 2 (22 ga.)

UNet Power Pair 1 (14 ga.)

Input from Field Device Output to Field Device

N/A

Input to DDC Module Output from DDC Module

24 VAC Power (+) 24 VAC Neutral (Gnd) (-)

White Black

A B

For Future Use

N/A N/A N/A

IN-#

Gnd

Wht Blk

Wht Blk

Wht Blk

Wht Blk

Blk Wht Red

Blk Wht Red

Signal Gnd

24vac/vdc

N/A N/A

Gnd Hot

Gnd

24vac Blk Wht

Red

A B

24vac/vdc

Blk Wht Red

0/10vdc Gnd

24vac/vdc

0/10vdc

N/A N/A

N/A N/A

Blk Wht

Shld

# N/A

Blk Wht

Shld

S

Net + Net - Shield

Blk Wht

Shld+ S

Net + Net - Shield Blk

Wht

Shld

In

Out

N/AN/A

N/A N/A

N/A N/A

N/A N/A

Blk Wht

Grn

Tx -

Rx -

Rx +Red

N/A

N/A

N/A

-Gnd

24vac

-Net -

Net +

N/A N/A

Tx +

Blk Wht

Grn

Rx

DCD

DTRRed

Tx

RTS

CTS

EIA-485-4W EIA-232-4W

1 2 3 4

B W G R

B W G R

Gnd

Rnet+

+12V

Rnet-

G nd

R ne t+

+1 2V

R ne t-

Installation Notes

Specification Section 15900

Juneau, AK ANM-JRD Facilities Phase I & II

Checked by: EP

Engineer: DMD

Installation Notes

TAB LABEL TEXT - SPARE

BN-DR-DA-EN-PL

Cable Identification/Wire Labels

DA - Device Address EN - Expander Number PL - Point Location

TAB LABEL TEXT - SPARE

BN-DR-DA-FB-PL

DA - Device Address FB - Function Block Number PL - Point Location

U-Line Point NotationM & S-Line Point Notation

Monitoring and control points for remote equipment are identified by the Module Point representation shown above. The System and Service Provider's electrical contractor or installer must label both ends of each control or monitoring point cable using the following format : (BN-DR-DA-EN-PL) or (BN-DR-DA-FB-PL). Adherence to this identification system is mandatory and must be followed using an approved tagging system comparable to the Brady I.D.Pro Plus electronic labeling system or equivalent.

These tags are intended for the wiring for all Analog Inputs (AI's), Digital Inputs (DI's), Analog Outputs (AO's), and Digital Outputs (DO's) except VAV's and terminal equipment where the wire runs are short and the field termination point is seen, or is easily identified. Points using pneumatic tubing follow the same convention.

All communication cable, terminations "in" an "out" of a field module panel, terminal equipment or VAV's must be labeled with "from (equipment name)" and "to (equipment name)" locations. See Figure 1 below.

All ARC156 or RNet communication, serial interface, control, and monitoring wiring must be terminated at the locations designated and must be free of splices.

When stripping multi-conductor cables, use only strippers specifically designed for removal of outer sheath insulation so as not to damage the shielding or insulation of the conductors. Use Ideal Catalog #45-514 or #45-165 data cable strippers or equivalent.

When shielded cable is used, do not strip back sheath more than 1" in order to keep twisted pair from separating. Do not ground shield to the panel or chassis ground. The shield should only be connected to the 'Optional Shield' connection at a module.

Ungrounded shields must be cut back and taped to prevent contact with with metal surfaces (heat shrink is preferred). See figure 2 below.

Multi-conductor cabling other than specified or pre-approved by the System and Service Provider (SSP) is unacceptable.

Electrical installation shall be in accordance with the project specifications, national, state, and local electrical codes along with ALC standards as outlined in this and other documents.

All pneumatic tubing that exceeds ten feet in length must be rigid copper or poly tubing installed in conduit. All poly tubing in exposed areas must be installed in conduit. Use plenum rated poly tubing for runs made in hung ceilings. Short lengths of less than 16 inches are permitted to be exposed for connection to field devices.

All field module panels (FMPs) will have a dedicated 120vac circuit.

Figure 2.

1"

1/4"

Foil Inner

Insulation Outer Jacket

Figure 1.

Shield

From VAV-3

To VAV-5

VAV-3

VAV-5

Equipment Name

ARC156 or UNet termination point in FMP or Terminal Equipment

Wiring Details

0 to 10 VDC Analog Output G

Output Signal

0 to 5 VDC Input B A + From Field Xfmr

Note: Rnet wiring may be installed in a daisy-chain, star or hybrid configuration

RNet

9 Note: All inputs (AI & DI) terminate to terminals on left side of module/device. All outputs (AO & DO) terminate to terminal strip on right side of panel.

Field device terminal designations xx xx xx

Point Name

0-0-UI0

Panel terminal strip or controller device terminal designations

See Cable Identification/Wire Labels on sheet 4 for Device Address notations

Summary Bill of Materials

Specification Section 15900

Juneau, AK ANM-JRD Facilities Phase I & II

Checked by: EP

Engineer: DMD

Summary Bill of Materials

Summary Bill of Materials

DID DESCRIPTION MANUFACTURER PART NUMBER QTY

ADPA-DH AIR DIFF PRESS. ANALOG DUCT MOUNT, 0-10 IN. W.C. ALTA LABS PXDXX02S 2 ea ADPA-PL AIR DIFF PRESS. ANALOG PANEL MOUNT, 0-1 IN. W.C. ALTA LABS PXPXX01S 2 ea AE2PH-62a ACTUATOR ELECTRIC, 2-POS, 120V, SR, 62 IN. LB, W/END SWITCH DELTA DCS120-62A 1 ea AE2PL-60 ACTUATOR ELECTRIC, 2-POS, 24V, SR, 60 IN. LB BELIMO NF24 ALC 1 ea AE2PL-60S ACTUATOR ELECTRIC, 2-POS, 24V, SR, 60 IN/LB BELIMO NF24-S ALC 2 ea AE2PL-62A ACTUATOR ELECTRIC, 2-POS, 24V, SR, 62 IN. LB DELTA DCS24-62A 3 ea AEM-133 ACTUATOR ELEC., MOD, 24V, SR, 2-10V, 133 IN. LB BELIMO AF24-SR ALC 1 ea AEM-140 ACTUATOR ELEC., MOD, 24V, SR, 0-10V, 140 IN. LB DELTA DCMS24-140 2 ea AEM-62 ACTUATOR ELEC., MOD, 24V, SR, 0-10V, 62 IN. LB DELTA DCMS24-62 1 ea CV-1 3-WAY CONTROL VALVE, 1IN., 30.8 CV DELTA ST 1-3-31/DCMS24-62 2 ea CV-2 3-WAY CONTROL VALVE, 1IN., 14.9 CV DELTA CP ST 1-3-15/DCMS24-62 2 ea DTSA-24 DUCT TEMP SENSOR AVERAGING, THERMISTOR, 24' ELEMEN BAPI ALC/10K-2-A-24-EU 2 ea DTSP-12 DUCT TEMP SENSOR POINT, 12 IN. BAPI ALC/10K-2-D-12-EU 4 ea DTSP-18 DUCT TEMP SENSOR POINT, 18 IN. BAPI ALC/10K-2-D-18-EU 1 ea DTSP-4 DUCT TEMP SENSOR POINT, 4 IN. BAPI ALC/10K-2-D-4 - NB10-PL 23 ea EN106TP 10 BASE-T 6 PORT 10MBPS ETHERNET HUB NETGEAR EN106TP 0 ea ENCL-M ENCLOSURE CABINET-MEDIUM HOFFMAN A24N24ALP 2 ea ENCL-UC ENCLOSURE CABINET-U CARD VERSA PRODUCTS CSE-992 1 ea Hum HUMIDISTAT W43A JOHNSON W43A 1 ea ITS IMMERSION TEMPERATURE SENSOR, THERMISTOR BAPI ALC/10K-2-I-4-EU 3 ea ITSW IMMERSION TEMP. SENSOR, SS WELL 4 IN. BAPI BA/4 3 ea LGR25 LGR25 AUTOMATED LOGIC LGR25 1 ea LPA LIQUID PRESSURE ANALOG, PSI 0/25-50-100 ALTA LABS PHX075 2 ea LTDT-A LOW TEMP DETECT, AUTO RESET, SPDT SIEMENS 134-1510 2 ea LVT LINE VOLTAGE THERMOSTAT COLUMBUS ETD5-S-1S 2 ea M220nx M220NX AUTOMATED LOGIC M220NX 1 ea M4106nx M4106NX AUTOMATED LOGIC M4106NX 1 ea M8102nx M8102NX AUTOMATED LOGIC M8102NX 1 ea OAREF OUTSIDE AIR PRESSURE, REFERENCE HEAD DWYER A306 1 ea OAS OUTSIDE AIR TEMPERATURE SENSOR, WEATHERPROFF ENCL. BAPI ALC/10K-2-O-EU 1 ea PAM-1 SP/ST KELE PAM-1 23 ea RE RELAY-SPDT FUNCTIONAL DEVICES RIBTU1C 2 ea RE/CSRE RELAY-CURRENT SENSOR EXTERNAL CT FUNCTIONAL DEVICES RIBXLSRA 5 ea RE/CSRI RELAY-CURRENT SENSOR INTERNAL CT FUNCTIONAL DEVICES RIBX24SBA 1 ea RES REL/ELEC W HOA SW. FUNCTIONAL DEVICES RIBTU1S 3 ea RS RS STANDARD SPACE TEMPERATURE ALC RS 2 ea RSP RS PRO STANDARD SPACE TEMPERATURE W/LCD ALC RSP 23 ea SE6104 SE6104 AUTOMATED LOGIC SE6104 1 ea SPP STATIC PRESSURE PICKUP BAPI ZPSACC01 2 ea Type A FTU RHC VALVE 3/4 IN., 3 WAY SPARTAN VE325-34-ED1.0-ME4140 15 ea Type B FTU RHC VALVE 3/4 IN., 3 WAY SPARTAN VE325-34-ED2.0-ME4140 6 ea Type C FTU RHC VALVE 3/4 IN., 3 WAY SPARTAN VE325-34-ED3.0-ME4140 2 ea XFMR TRANSFORMER,120 TO 24VAC,100VA W/CB,DTHM ULL FUNCTIONAL DEVICES TR100VA002 10 ea ZN220 ZN220 AUTOMATED LOGIC ZN220 4 ea ZN341V+ VAV CONTROLLER 3DO,4UI,1AO W/ACTUATOR, FLOW SENSOR AUTOMATED LOGIC ZN341V+ 23 ea ZN551 UNITARY CONTROLLER 5DO, 5UI, 1 AO AUTOMATED LOGIC ZN551 1 ea

Valve Schedule

Specification Section 15900

Juneau, AK ANM-JRD Facilities Phase I & II

Checked by: EP

Engineer: DMD

Valve Schedule

WATER CONTROL VALVE SCHEDULE

HX-1 CV-1 1 100.0 57.7 74.0 1.8 2 1/2" Threaded Delta ST250-3-74DCMS24-62 A-AB Diverting AHU-1 CV-2 1 30.0 17.3 23.5 1.6 1 1/2" Threaded Delta ST150-3-24DCMS24-62 A-AB FTU-1 FTU-1 1 1.7 1.0 1.0 2.9 3/4" Solder Spartan VE325-34-ED1.0-ME4140 Last Type 1 FTU-2 FTU-2 1 2.0 1.2 2.0 1.00 3/4" Solder Spartan VE325-34-ED2.0-ME4140 Last Type 2 FTU-3 FTU-3 1 1.4 0.8 1.0 1.96 3/4" Solder Spartan VE325-34-ED1.0-ME4140 Last Type 1 FTU-4 FTU-4 1 1.5 0.9 1.0 2.25 3/4" Solder Spartan VE325-34-ED1.0-ME4140 Last Type 1 FTU-5 FTU-5 1 1.3 0.8 1.0 1.69 3/4" Solder Spartan VE325-34-ED1.0-ME4140 Last Type 1 FTU-6 FTU-6 1 1.0 0.6 1.0 1.00 3/4" Solder Spartan VE325-34-ED1.0-ME4140 Last Type 1 FTU-7 FTU-7 1 1.5 0.9 1.0 2.25 3/4" Solder Spartan VE325-34-ED1.0-ME4140 Last Type 1 FTU-8 FTU-8 1 0.9 0.5 1.0 0.81 3/4" Solder Spartan VE325-34-ED1.0-ME4140 Last Type 1 FTU-9 FTU-9 1 1.4 0.8 1.0 1.96 3/4" Solder Spartan VE325-34-ED1.0-ME4140 Last Type 1 FTU-10 FTU-10 1 1.4 0.8 1.0 1.96 3/4" Solder Spartan VE325-34-ED1.0-ME4140 Last Type 1 FTU-11 FTU-11 1 1.2 0.7 1.0 1.44 3/4" Solder Spartan VE325-34-ED1.0-ME4140 Last Type 1 FTU-12 FTU-12 1 1.3 0.8 1.0 1.69 3/4" Solder Spartan VE325-34-ED1.0-ME4140 Last Type 1 FTU-13 FTU-13 1 1.0 0.6 1.0 1.00 3/4" Solder Spartan VE325-34-ED1.0-ME4140 Last Type 1 FTU-14 FTU-14 1 3.8 2.2 3.0 1.60 3/4" Solder Spartan VE325-34-ED3.0-ME4140 Last Type 3 FTU-15 FTU-15 1 3.8 2.2 3.0 1.60 3/4" Solder Spartan VE325-34-ED3.0-ME4140 Last Type 3 FTU-16 FTU-16 1 1.4 0.8 1.0 1.96 3/4" Solder Spartan VE325-34-ED1.0-ME4140 Last Type 1 FTU-17 FTU-17 1 1.9 1.1 2.0 0.90 3/4" Solder Spartan VE325-34-ED2.0-ME4140 Last Type 2 FTU-18 FTU-18 1 1.4 0.8 1.0 1.96 3/4" Solder Spartan VE325-34-ED1.0-ME4140 Last Type 1 FTU-19 FTU-19 1 2.2 1.3 2.0 1.21 3/4" Solder Spartan VE325-34-ED2.0-ME4140 Last Type 2 FTU-20 FTU-20 1 1.9 1.1 2.0 0.90 3/4" Solder Spartan VE325-34-ED2.0-ME4140 Last Type 2 FTU-21 FTU-21 1 1.4 0.8 1.0 1.96 3/4" Solder Spartan VE325-34-ED1.0-ME4140 Last Type 1 FTU-22 FTU-22 1 2.0 1.2 2.0 1.00 3/4" Solder Spartan VE325-34-ED2.0-ME4140 Last Type 2 FTU-23 FTU-23 1 1.9 1.1 2.0 0.90 3/4" Solder Spartan VE325-34-ED2.0-ME4140 Last Type 2

Equipment Name Qty GPM TAG Cal Cv Valve Cv Actual

DP Valve Size Connection Type

CommentsFail Position

Valve Manufacturer Valve & Actuator Part Number

TYPE A

Type Valve & Acutator Quantity Type A VE-325-34-ED1.0-ME4140 15 Type B VE-325-34-ED2.0-ME4140 6 Type C VE-325-34-ED3.0-ME4140 2

TYPE B

TYPE C

Bill of Materials

DID DESCRIPTION MANUFACTURER PART NUMBER QTY

Type A FTU RHC VALVE 3/4 IN., 3 WAY SPARTAN VE325-34-ED1.0-ME4140 15 ea Type B FTU RHC VALVE 3/4 IN., 3 WAY SPARTAN VE325-34-ED2.0-ME4140 6 ea Type C FTU RHC VALVE 3/4 IN., 3 WAY SPARTAN VE325-34-ED3.0-ME4140 2 ea

System Layout / Riser Diagram

Specification Section 15900

Juneau, AK ANM-JRD Facilities Phase I & II

Checked by: EP

Engineer: DMD

System Layout / Riser Diagram

Storage Bldg

Warehouse

PNL-1

Warehouse Mech Room

Dev 2

SE6104

Site #55

LGR25

120 VAC

Pnl: 1 Ckt: 5 D

PNL-2

Storage Bldg

Dev 3

ZN551

ENCL-UC

XFMR

Typ. of 1

Transformer #3

120 VAC

Pnl: 2

Ckt: 15

CAT-JCK

120VAC

Duplex outlet

Administration Bldg

PNL-3

Admin Bldg 1st Floor

Boiler Rm

Dev 4 M8102nx

EN106TP ENCL-M

PNL-4

Admin Bldg 3rd Floor

Mech Rm

Dev 6 M220nx

Dev 5 M4106nx

ENCL-M

Power & Cmnet to ZN Cards

VAC XFMR

Typ. of 6

Transformer #8-13

Factory Mounted Enclosure

1st and 2nd Floor FTU

VAV's

Dev 7-29

ZN341V+

XFMR

Typ. of 2

Transformer #4-5

120 VAC

Pnl: ___ Ckt: ___

XFMR

Typ. of 2

Transformer #6-7

120 VAC

Pnl: ___ Ckt: ___

EF 3-3

Rm A-129

Dev 30

ZN220

ENCL-UC

XFMR

Typ. of 2

Transformer #1-2

120VAC

Duplex outlet

Router ACS DSL

Device IP Address Gateway Router Subnet Mask NAT WebCTRL Server 192.168.1.21 192.168.1.1 255.255.255.0

LGR25 172.168.1.13 172.168.1.254 255.255.255.0 216.67.11.174

External Address 209.193.4.7 / 209.193.4.8

DNS

NETWORK INFORMATION

Bill of Materials

DID DESCRIPTION MANUFACTURER PART NUMBER QTY

EN106TP 10 BASE-T 6 PORT 10MBPS ETHERNET HUB NETGEAR EN106TP 0 ea ENCL-M ENCLOSURE CABINET-MEDIUM HOFFMAN A24N24ALP 2 ea ENCL-UC ENCLOSURE CABINET-U CARD VERSA PRODUCTS CSE-992 1 ea XFMR TRANSFORMER,120 TO 24VAC,100VA W/CB,DTHM ULL FUNCTIONAL DEVICES TR100VA002 10 ea

PNL-1 Layout/Warehouse

Specification Section 15900

Juneau, AK ANM-JRD Facilities Phase I & II

Checked by: EP

Engineer: DMD

PNL-1 Layout/Warehouse

0 1 2

9 0 1 2

BACnet Over ARCNET156 KBaud

TM Class 2 24Vac, 50-60 Hz

20VA, 0.83A

Use Copper

Conductors Only

Caution:

To Reduce the Risk of Fire or Electrical Shock, Do Not interconnect the Outputs of Different Class 2 Circuits.

Module Address 10's 1's

+ Aux Power Out On Off

SE6104

CONTROL MODULE

1 2 3 4 O N

Gnd 24V-ac Gnd

Power

IN-1

Gnd

IN-2

Gnd

IN-3

Gnd

IN-4

Gnd

IN-5

Gnd

IN-6

Gnd

IN-7

Gnd

IN-8

Gnd

IN-9

Gnd

AO-4

DO-2

DO-1

DO-3

DO-4

DO-5

DO-6

7+

Gnd

AO-3

5+

Gnd

AO-2

3+

Gnd

AO-1

1+

Gnd

IN-10

Gnd

Select +5V +24V

AO Mode Select 0-10V 0-20mA

Tx

Rx

Batt

CR2032

CMnet

Shield

Net-

Net+

Bias

Inputs: All 10V Max, 20mA Max

IN-1, IN-2: Pulse Count Ability

Outputs 24V Max, 3A Max

Auto Off On

LogiStat Port

Rnet

Gnd

Temp

Sw

LS5v

Gnd

Rnet+

Rnet-

+12V

LogiStat (IN-9, 10 diabled)

Rnet

Stat Select

G nd

R ne t+ R ne t-

S en se +1

2V

Error

Run

Format

0-20mA 0-10V-dc Thermister/ dry contact/

RTD

Rnet Local Access

MSTP Baud

Cmnet Mode

76.8k

38.4k

19.2k

9600 ARC156

MSTP

Universal Input Mode Select

24Vac (+) Gnd (-)

H N G

Transformer Detail (Outside of Control Panel)

VAC

XFMR 1

XFMR 2

Wht

Shld Blk 156K CMnet - Out to PNL-3

1+ 2- 3+ 4-

Field Pwr

Module Pwr

TERMINAL

STRIP

G nd

R ne t+ R ne t-

+1 2V

MANUAL ON WARMER

INFO COOLER

AUTOMATED LOGIC

1 2 3 4

B W G R

B W G R

Located in hallway

SF Status

2-0-DI01

Freezestat

2-0-DI02

MA Temp

2-0-AI03

RA Temp

2-0-AI04

DA Temp

2-0-AI05

Spare

2-0-UI06

Spare

2-0-UI07

Spare

2-0-UI08

Spare

2-0-UI09

Spare

2-0-UI10

MA Damper

2-0-AO1 +

HW Valve

2-0-AO2 +

Spare

2-0-AO03

Spare

2-0-AO04

SF S/S

2-0-DO01

EF S/S

2-0-DO02

Spare

2-0-DO03

Spare

2-0-DO04

Spare

2-0-DO05

Spare

2-0-DO06

0 1 2

9 0 1 2

91 82 3 4 5 6 7 O N

485-2w 485-4w

Port S1

Ext. Batt.

Int. Batt.

DCD

DTR

Rx

Tx

EIA-2324 wire2 wire

Signal Ground

Rx- Rx+

Tx-

Tx+ n/c n/c

Net-

Net+

External Battery

Gnd +3V

Ground 24V ac/dc

Power

On Off

Module Status

3V Lithium Battery CR-123A10/100 BaseT

Ethernet Port E1

100 LAN LINK

Cmnet transmit Cmnet receive

Port S1 receive Port S1 transmit

Battery low

Blinking Dot = “Run”

Format

BACnet Over ARCNET156 KBaud

LGR25

Control Module

Without Keypad Display:

24Vac, 24VA, 1A, 50-60 Hz 26Vdc, 10W, 0.4A

Use Copper Conductors Only Class 2

Net +

Net -

Shield

CMnet

Rnet Local Access

Gnd

Rnet +

Rnet -

+12V

Rnet

Off

On

Enhanced Access Port on S2 IP Addr

Module Address

10's 1's

BT485

Archive Valid

Power

LED

BT485

Port S2

BT485

Error Codes:

DCD

DTR

Rx

Tx n/c n/c

Net-

Net+

EIA-

485 232

EIA-232

EIA-485

EIA-232

EIA-485

Default

Assigned

+100

Disable

Enable

Disable

Enable

Address

MSTP

on S1

PTP

on S2

Tx

Rx

Option Comm

Signal Ground

Chase = OK 0 = Download required 1 = Control Program Error 2 = RAM full 3 = Comm setup error 4 = System error 8 = Formatting

LGR25

SE6104

#2

AHU-1

Warehouse

Wht Blk Shld

156K CMnet - In from Dev 3

Bill of Materials

DID DESCRIPTION MANUFACTURER PART NUMBER QTY

LGR25 LGR25 AUTOMATED LOGIC LGR25 1 ea SE6104 SE6104 AUTOMATED LOGIC SE6104 1 ea

AHU/EF-3 & 4 Control

Specification Section 15900

Juneau, AK ANM-JRD Facilities Phase I & II

Checked by: EP

Engineer: DMD

AHU/EF-3 & 4 Control

Starter

N H

120 VAC

EA

EF-3

Starter

N H

120 VAC

EA

EF-4

W B

EF S/S

2-0-DO2

RES

W B

EF S/S

2-0-DO2

RES

CC

W B

DA Temp

2-0-AI5

W B

MA Temp

2-0-AI3

RA Temp

2-0-AI4

W B

HC

GHR GHS

SF

R B

W B

LTDT-A

Freezestat

2-0-DI2

1 2 3

MA Damper

2-0-AO1

OA DA

RA

39 + 40

NO

NC

W B W B

SF Status

2-0-DI1

SF S/S

2-0-DO1

HW Valve

2-0-AO2 CV-1

DTSP-12DTSA-24

DTSP-12

AEM-133

C

RE/CSRE

Auto

STARTER

Bill of Materials

DID DESCRIPTION MANUFACTURER PART NUMBER QTY

AEM-133 ACTUATOR ELEC., MOD, 24V, SR, 2-10V, 133 IN. LB BELIMO AF24-SR ALC 1 ea CV-1 3-WAY CONTROL VALVE, 1IN., 30.8 CV DELTA ST 1-3-31/DCMS24-62 1 ea DTSA-24 DUCT TEMP SENSOR AVERAGING, THERMISTOR, 24' ELEMEN BAPI ALC/10K-2-A-24-EU 1 ea DTSP-12 DUCT TEMP SENSOR POINT, 12 IN. BAPI ALC/10K-2-D-12-EU 2 ea LTDT-A LOW TEMP DETECT, AUTO RESET, SPDT SIEMENS 134-1510 1 ea RE/CSRE RELAY-CURRENT SENSOR EXTERNAL CT FUNCTIONAL DEVICES RIBXLSRA 1 ea RES REL/ELEC W HOA SW. FUNCTIONAL DEVICES RIBTU1S 2 ea

PNL-2 Layout/Storage Bldg

Specification Section 15900

Juneau, AK ANM-JRD Facilities Phase I & II

Checked by: EP

Engineer: DMD

PNL-2 Layout/Storage Bldg

24 VAC

From XFMR

T-

B W G R

T+

W B Sh

CmNet in from Pnl-1 B

R

CAUTION:

This product was designed to be mounted inside the building envelope. Warranty voided if mounted outside.

Power for D.O.'s

DO-3

DO-2

DO-1

BUSS

Pwr

BACnet

6 7 8 9

6 7 8 9

6 7 8 9

6 7 8 9

Rx

Tx

DO-4

DO-5

AO-1

Gnd

BT485

Net +

Net -

Shield

C M ne t

Te ns

O ne s

Batt

CR

Sense +12V Rnet- Rnet+ Gnd

Gnd

R ne tRnet +

Rnet -

+12V

IN-1

Gnd

IN-2

Gnd

IN-3

Gnd

Gnd

IN-4

IN-5

LED

Inputs: 5V Max

Class 2 24 Vac, 50-60 Hz

20VA, 0.83A

24Vdc, 0.2A, 5W

Use Copper Conductors Only

Ground

24 Vac

Run

Err

ZN551

CONTROLLER

Thermistor/dry contact 0-5Vdc

IN-1

Thermistor/dry contact 0-5Vdc

IN-2

O N

On

MSTP Baud

Communications Selection

9600 19.2k 38.4k 76.8k

MSTP

ARC156

CAUTION:

To Reduce the Risk of Fire or Electric Shock, Do Not Interconnect the Outputs of Different Class 2 Circuits.

Jumper: Gain1

Format

Lstat Rnet

Outputs 24V Max, 1A Max

T+ R B W

EF S/S 3T- B

W

T+

HW Valve 4 DA Temp1

Humidity Enable2

W B W

BB W G R

Terminating Resistor

1 2 4 6

W B

EA RA

EF S/S 3

EF-1

Humidity Enable 213H C

L

HUM

W B

DA

HW

CV-2

HW Valve4

R B W

NC

DTSP-18

OA

12 AE2PL-60

DA Temp1

EF S/S 3

B WW B

GHR GHS

G nd

R ne t+ R ne t-

+1 2V

RS

AUTOMATED LOGIC

1 2 3 4

AE2PL-60S

ZN551

C

RES

208 VAC H

208 VAC N

1 2 4 6

W B

EA RA

EF S/S 3

EF-2

AE2PL-60S

C

RES

208 VAC H

208 VAC N

Bill of Materials

DID DESCRIPTION MANUFACTURER PART NUMBER QTY

AE2PL-60 ACTUATOR ELECTRIC, 2-POS, 24V, SR, 60 IN. LB BELIMO NF24 ALC 1 ea AE2PL-60S ACTUATOR ELECTRIC, 2-POS, 24V, SR, 60 IN/LB BELIMO NF24-S ALC 2 ea CV-2 3-WAY CONTROL VALVE, 1IN., 14.9 CV DELTA CP ST 1-3-15/DCMS24-62 1 ea DTSP-18 DUCT TEMP SENSOR POINT, 18 IN. BAPI ALC/10K-2-D-18-EU 1 ea Hum HUMIDISTAT W43A JOHNSON W43A 1 ea RS RS STANDARD SPACE TEMPERATURE ALC RS 1 ea ZN551 UNITARY CONTROLLER 5DO, 5UI, 1 AO AUTOMATED LOGIC ZN551 1 ea

PNL-3 Layout / Admin Bldg

Specification Section 15900

Juneau, AK ANM-JRD Facilities Phase I & II

Checked by: EP

Engineer: DMD

PNL-3 Layout / Admin Bldg

Class 2 24Vac, 50-60 Hz

20VA, 0.83A

Use Copper

Conductors Only

Gnd

Caution:

To Reduce the Risk of Fire or Electrical Shock, Do Not interconnect the Outputs of Different Class 2 Circuits.

Digital Outputs 24V Max.

3A Max.

Module Address

10's 1's

A - Input Signal B - Gnd/Loop Power

Auxiliary Device

Port

BACnet Over ARCNET156 KBaud

TM

CMnet Mode

ARC1569600/

38.4k

Net +

Net - CMnet

Rx Tx Run Error Power

On Off

Access Port

DO1

DO8

DO2

DO3

DO4

DO5

DO6

DO7

NC NO

A

A

A

A

A

A

A

A

A

A

B

B

B

B

B

B

B

B

B

B

IN1

IN10

IN2

IN3

IN4

IN5

IN6

IN7

IN8

IN9

Universal Input Mode Select

0-5Vdc Thermistor/ dry-contact

0-20 mA

M8102nx

CONTROL MODULE

Gnd

Gnd

AO1

AO2

Format

24 Vac

38.4k

1 2 3 4 O N

0 1 2

9 0 1 2

M8102NX

Shield

Cmnet Baud

Inputs 5V Max, 20mA Max

XFMR 4

XFMR 5

Wht

Shld Blk 156K CMnet - Out to PNL-3

1+ 2- 3+ 4-

Field Pwr

Module Pwr

TERMINAL

STRIP

Heat Exchanger - Pump 1 Status

4-0-DI1

Heat Exchanger - Pump 2 Status

4-0-DI2

Heat Exchanger - HGS Temp

4-0-AI3

Heat Exchanger - HGR Temp

4-0-AI4

Boiler - P3 Status

4-0-DI6

Heat Exchanger - SYS Pressure

4-0-AI5+

Boiler - Boiler Status

4-0-DI7

Boiler - HWS Temp

4-0-AI8

Boiler - SYS Pressure

4-0-AI9+

OA Temp

4-0-AI10

Heat Exchanger - Pump 1 S/S

4-0-DO1

Heat Exchanger - Pump 2 S/S

4-0-DO2

Boiler - Pump 3 S/S

4-0-DO3

Boiler - Boiler Enable

4-0-DO4

Spare

4-0-DO05

Spare

4-0-DO06

Spare

4-0-DO07

Spare

4-0-DO08

Heat Exchanger - HX Valve

4-0-AO1 +

Spare

4-0-AO02

Wht

Shld Blk 156K CMnet - In from

Dev 3 or PNL-1

#4 Boiler & HX

Control

Bill of Materials

DID DESCRIPTION MANUFACTURER PART NUMBER QTY

M8102nx M8102NX AUTOMATED LOGIC M8102NX 1 ea

Heating System Control

Specification Section 15900

Juneau, AK ANM-JRD Facilities Phase I & II

Checked by: EP

Engineer: DMD

Heating System Control

A

HWS

Boiler Status

4-0-DI7

HWS Temp

4-0-AI8

SYS Pressure

4-0-AI9

RE

C

W B

Boiler

COV

R W B

LPA

W B

Air SeperatorITSW

ITSITSW

W B

ITS

HGS Temp

4-0-AI3

HGR Temp

4-0-AI4

CV-1

HX Valve

4-0-AO1

B

HXW

B W

BC

RE/CSRE

Auto

STARTER

CP-2

W B W

BC

RE/CSRE

Auto

STARTER

CP-1

HWR

B W R

HWS ( To Bldg )

( From Bldg )Air Seperator

CP-3

P3 Status

4-0-DI6

Pump 3 S/S

4-0-DO3

W B W B

C

RE/CSRI

N H

120 VAC

Boiler Enable

4-0-DO4

RES

C

W B

X

From Boiler Operating Control Circuit

Pump 2 Status

4-0-DI2

Pump 2 S/S

4-0-DO2

Pump 1 Status

4-0-DI1

Pump 1 S/S

4-0-DO1

Diverting

SYS Pressure

4-0-AI5

COV

R W B

LPA

W B

ITSW

ITS

OAS

W B

Mount on North Facing Wall

OA Temp

4-0-AI10

AB

Bill of Materials

DID DESCRIPTION MANUFACTURER PART NUMBER QTY

CV-1 SOFT TOUCH, 2 1/2IN., THREADED, 3 WAY DIVERTING, FAIL A-AB DELTA ST250-3-74/DCMS24-62 DIVERTING 1 ea ITS IMMERSION TEMPERATURE SENSOR, THERMISTOR BAPI ALC/10K-2-I-4-EU 3 ea ITSW IMMERSION TEMP. SENSOR, SS WELL 4 IN. BAPI BA/4 3 ea LPA LIQUID PRESSURE ANALOG, PSI 0/25-50-100 ALTA LABS PHX075 2 ea OAS OUTSIDE AIR TEMPERATURE SENSOR, WEATHERPROFF ENCL. BAPI ALC/10K-2-O-EU 1 ea RE RELAY-SPDT FUNCTIONAL DEVICES RIBTU1C 1 ea RE/CSRE RELAY-CURRENT SENSOR EXTERNAL CT FUNCTIONAL DEVICES RIBXLSRA 2 ea RE/CSRI RELAY-CURRENT SENSOR INTERNAL CT FUNCTIONAL DEVICES RIBX24SBA 1 ea RES REL/ELEC W HOA SW. FUNCTIONAL DEVICES RIBTU1S 1 ea

Old system layout. See next page for updated layout.

PNL-4 Layout / Admin Bldg

Specification Section 15900

Juneau, AK ANM-JRD Facilities Phase I & II

Checked by: EP

Engineer: DMD

PNL-4 Layout / Admin Bldg

XFMR 7

Wht

Shld Blk

Wht

Shld Blk

156K CMnet - In from PNL-3

1+ 2- 3+ 4-

Module Pwr

TERMINAL

STRIP

XFMR 6

Field Pwr

156K CMnet - Out to VAV box +

Class 2 24Vac, 50-60 Hz

20VA, 0.83A

Use Copper

Conductors Only

Caution:

To Reduce the Risk of Fire or Electrical Shock, Do Not interconnect the Outputs of Different Class 2 Circuits.

24V Max.

3A Max.A - Input Signal

B - Gnd/Loop Power

Auxiliary Device

Port

BACnet Over ARCNET156 KBaud

TM

Module Address

10's 1's

Gnd 24 Vac

M4106nx

CONTROL MODULE

Net +

Net - CMnet

Rx Tx Run Error

CMnet Mode

ARC1569600/

38.4k

Format

NO

NC

Access Port

Power

On Off

DO1

DO2

DO3

DO4

Gnd

AO2

2Gnd

AO1

Gnd

AO3

Gnd

AO4

Gnd

AO5

Gnd

AO6

A

A

A

A

A

A

A

A

A

A

B

B

B

B

B

B

B

B

B

B

IN1

IN10

IN2

IN3

IN4

IN5

IN6

IN7

IN8

IN9

Universal Input Mode Select

0-5Vdc Thermistor/ dry-contact

0-20 mA

38.4k

1 2 3 4 O N

0 1 2

9 0 1 2

M4106NX

Shield

Cmnet Baud

Inputs 5V Max, 20mA Max

SF S/S

5-0-DO01

RF S/S

5-0-DO02

Spare

5-0-DO03

Spare

5-0-DO04

SF VFD Speed

5-0-AO01

MA Damper

5-0-AO2 +

Relief Damper

5-0-AO3 +

RF VFD Speed

5-0-AO04

HC Valve

5-0-AO5 +

Spare

5-0-AO06

#5

AHU 3-1

Gnd 24 Vac

Access Port

Class 2 24Vac

50-60 Hz

20VA, 0.83A

Use Copper

Conductors Only

Caution:

To Reduce the Risk of Fire or Electrical Shock, Do Not interconnect the Outputs of Different Class 2 Circuits.

Format

BACnet Over ARCNET156 KBaud

TM

10's 1's Module Address

Auto Off On

Tx

Rx

Power On Off

Comm Select

ARC156CM

net

38.4k 9600

Baud Select

Net +

Net -

DO1

DO2

A

A

B

B

IN1

IN2

Error

Run Power

CONTROL MODULE

Universal Input Mode Select

0-5Vdc Thermistor/ dry-contact

0-20 mA

24V Max.

3A Max.

M220nx

0 1 2

9 0 1 2

9M220NX

Inputs 5V Max, 20mA Max

Shield

N/CCM

net

Use Single Class 2 Source Only

EF Status

6-0-DI1

EF Status

6-0-DI2

EF S/S

6-0-DO1

EF S/S

6-0-DO2

SF Status

5-0-DI1

RF Status

5-0-DI2

SA Temp

5-0-AI3

MA Temp

5-0-AI4

Freezestat

5-0-DI5

Duct Static

5-0-AI6+

Filter

5-0-AI7

RA Temp

5-0-AI8

Bldg Static

5-0-AI9+

Spare

5-0-UI10

#6

EF 3-1 & 3-2

Bill of Materials

DID DESCRIPTION MANUFACTURER PART NUMBER QTY

M220nx M220NX AUTOMATED LOGIC M220NX 1 ea M4106nx M4106NX AUTOMATED LOGIC M4106NX 1 ea

AHU 3-1 Control

Specification Section 15900

Juneau, AK ANM-JRD Facilities Phase I & II

Checked by: EP

Engineer: DMD

AHU 3-1 Control

Filter

5-0-AI7

- O +

B W R

ADPA-DH

LOHI

OAREF

LO

HI

- O +

B W R

ADPA-PL

SPP

Bldg Static

5-0-AI9

RA

RF

W B

RA Temp

5-0-AI8

CV-2

1 2 3

Relief Damper

5-0-AO3

NC

R W B

EA

B W R

SA Temp

5-0-AI3

Freezestat

5-0-DI5

MA Temp

5-0-AI4

HC Valve

5-0-AO5

W B

DTSA-24

HC

R B

W B

SF

HWR HWS

DA

W B

DTSP-12

DA

LO

HI

- O +

B W R

ADPA-DH

Duct Static

5-0-AI6

W B

SF S/S

5-0-DO1

SF VFD Fault

29-0-DI1

SF VFD Speed

5-0-AO1

SF

VFD SF Status

5-0-DI1

OA

NO

NC

LTDT-A

AEM-140

W B

RF S/S

5-0-DO2

RF VFD Fault

29-0-DI2

RF VFD Speed

5-0-AO4

RF

VFD RF Status

5-0-DI2

1 2 8

MA Damper

5-0-AO2

B W R

AEM-140

Lin ka ge

DTSP-12

1 Building Static Pressure Sensor to be located in mechanical room.

W B W B W B

A

B

AB

Bill of Materials

DID DESCRIPTION MANUFACTURER PART NUMBER QTY

ADPA-DH AIR DIFF PRESS. ANALOG DUCT MOUNT, 0-10 IN. W.C. ALTA LABS PXDXX02S 2 ea ADPA-PL AIR DIFF PRESS. ANALOG PANEL MOUNT, 0-1 IN. W.C. ALTA LABS PXPXX01S 1 ea AEM-140 ACTUATOR ELEC., MOD, 24V, SR, 0-10V, 140 IN. LB DELTA DCMS24-140 2 ea CV-2 AHU-1 HEATING COIL GLOBE VALVE 1 1/2 IN., 3 WAY DELTA ST150-3-24DCMS24-62 1 ea DTSA-24 DUCT TEMP SENSOR AVERAGING, THERMISTOR, 24' ELEMEN BAPI ALC/10K-2-A-24-EU 1 ea DTSP-12 DUCT TEMP SENSOR POINT, 12 IN. BAPI ALC/10K-2-D-12-EU 2 ea LTDT-A LOW TEMP DETECT, AUTO RESET, SPDT SIEMENS 134-1510 1 ea OAREF OUTSIDE AIR PRESSURE, REFERENCE HEAD DWYER A306 1 ea SPP STATIC PRESSURE PICKUP BAPI ZPSACC01 1 ea

W B W B W B

EF 3-1 & 3-2 Control

Specification Section 15900

Juneau, AK ANM-JRD Facilities Phase I & II

Checked by: EP

Engineer: DMD

EF 3-1 & 3-2 Control

EF 3-2

EF

EAEA NC

AE2PL-62A

EF S/S

6-0-DO2

2 1

W B EF Status

6-0-DI2

N

W B

C

RE/CSRE

Auto

STARTER

EF 3-1

EF

EAEA NC

AE2PL-62A

EF S/S

6-0-DO1

2 1

W B EF Status

6-0-DI1

N

1 W B

C

RE/CSRE

Auto

STARTER

Bill of Materials

DID DESCRIPTION MANUFACTURER PART NUMBER QTY

AE2PL-62A ACTUATOR ELECTRIC, 2-POS, 24V, SR, 62 IN. LB DELTA DCS24-62A 2 ea RE/CSRE RELAY-CURRENT SENSOR EXTERNAL CT FUNCTIONAL DEVICES RIBXLSRA 2 ea

EF 3-3 Control

Specification Section 15900

Juneau, AK ANM-JRD Facilities Phase I & II

Checked by: EP

Engineer: DMD

EF 3-3 Control

EF

EAEA NC

AE2PL-62A

EF S/S

30-0-DO1

2 1

W B

N H

120 VAC

N

24 VAC

From XFMR

T-

T+ CmNet out to next Device 7

W B Sh

W B Sh

CmNet in

B R

EF S/S

30-0-DO1 1T- B

W T+

#30

EF 3-3

CAUTION:

This product was designed to be mounted inside the building envelope. Warranty voided if mounted outside.

Power for D.O.'s

DO-2

DO-1

BUSS

Pwr

BACnet

7 8 9

6 7 8 9

7 8 9

6 7 8 9

Rx

Tx

Bias

Net +

Net -

Shield

C M ne t

Te ns

O ne s

Batt

CR

Sense +12V Rnet- Rnet+ Gnd

Gnd

R ne tRnet +

Rnet -

+12V

IN-1

Gnd

IN-2

Gnd

Inputs: 5V Max

Class 2 24 Vac, 50-60 Hz

20VA, 0.83A

24Vdc, 0.2A, 5W

Use Copper Conductors Only

Ground

24 Vac

Run

Err

ZN220

CONTROLLER

Thermistor/dry contact 0-5Vdc

IN-1

Thermistor/dry contact 0-5Vdc

IN-2

O N

On

MSTP Baud

Communications Selection

9600 19.2k 38.4k 76.8k

MSTP

ARC156

CAUTION:

To Reduce the Risk of Fire or Electric Shock, Do Not Interconnect the Outputs of Different Class 2 Circuits.

Jumper: Gain1

Format

Lstat Rnet

ZN220

RE

C

G nd

R ne t+ R ne t-

+1 2V

1 2 3 4

B W G R

B W G R

RS

AUTOMATED LOGIC

Thermostat Location ZCard

Address Zcard Type Coil/FT/CUH/RP Sensor Type

Device VA Draw

Servered by

Equipment

Device installation location XFMR # RM A-115 30 ZN220 n/a Blank Plate 20 VA EF3-4

Z Card Schedule

Bill of Materials

DID DESCRIPTION MANUFACTURER PART NUMBER QTY

AE2PL-62A ACTUATOR ELECTRIC, 2-POS, 24V, SR, 62 IN. LB DELTA DCS24-62A 1 ea RE RELAY-SPDT FUNCTIONAL DEVICES RIBTU1C 1 ea RS RS STANDARD SPACE TEMPERATURE ALC RS 1 ea ZN220 ZN220 AUTOMATED LOGIC ZN220 4 ea

Zone Control - FTU VAV Box

Specification Section 15900

Juneau, AK ANM-JRD Facilities Phase I & II

Checked by: EP

Engineer: DMD

Zone Control - FTU VAV Box

Thermostat Location ZCard

Address Zcard Type Coil/FT/CUH/RP Sensor Type

Device VA Draw

Served by Equipment

RM A-101 7 ZN341V+ DHC-1 Blank Plate 20 VA FTU-1 RM A101-A 8 ZN341V+ DHC-2 RS Pro 20 VA FTU-2 RM A-103 9 ZN341V+ DHC-3 RS Pro 20 VA FTU-3 RM A-106 10 ZN341V+ DHC-4 RS Pro 20 VA FTU-4 RM A-120 11 ZN341V+ DHC-5 RS Pro 20 VA FTU-5 RM A-122A 12 ZN341V+ DHC-6 RS Pro 20 VA FTU-6 RM A-122 13 ZN341V+ DHC-7 RS Pro 20 VA FTU-7 RM A-124 14 ZN341V+ DHC-8 RS Pro 20 VA FTU-8 RM A-125 15 ZN341V+ DHC-9 RS Pro 20 VA FTU-9 RM A-126 16 ZN341V+ DHC-10 RS Pro 20 VA FTU-10 RM A-128 17 ZN341V+ DHC-11 RS Pro 20 VA FTU-11 RM A-129 18 ZN341V+ DHC-12 RS Pro 20 VA FTU-12 RM A-112 19 ZN341V+ DHC-13 RS Pro 20 VA FTU-13 RM A-201South 20 ZN341V+ DHC-14 RS Pro 20 VA FTU-14 RM A-201North 21 ZN341V+ DHC-15 RS Pro 21 VA FTU-15 RM A-202 22 ZN341V+ DHC-16 RS Pro 22 VA FTU-16 RM A-203 23 ZN341V+ DHC-17 RS Pro 23 VA FTU-17 RM A-207 24 ZN341V+ DHC-18 RS Pro 24 VA FTU-18 RM A-216 25 ZN341V+ DHC-19 RS Pro 25 VA FTU-19 RM A-215 26 ZN341V+ DHC-20 RS Pro 26 VA FTU-20 RM A-214 27 ZN341V+ DHC-21 RS Pro 27 VA FTU-21 RM A-210South 28 ZN341V+ DHC-22 RS Pro 28 VA FTU-22

Z Card Schedule

Typ. of 22

Note! Manufacturer wire colors differ from MSI standards!

Cable Black

Red White

Actuator White Red Black terminates to:

Rnet+

D O

-3

P ow er fo r D .O

.s

BU

S

D O

-1

D O

-2

AO

-1

G nd

Analog Output

G nd

IN

-2

IN

-1

G nd

IN

-3

G nd

IN

-4

LE

D

G nd

R ne t +

R ne t -

+1 2V

R n e t CMnet

N et

N et

Sh ie ld

G ro un d

V ac

Power

Batt

CR2032

10's

1's

9 6

9 6

Therm/dry 0-5VdcIN-2

IN-1

Format

Rnet LogiStat

ARC156

MSTP

High (with filter)

Low

Flow

Outputs 24V Max, 1A Max

Conductors Only

Class 2

Use Copper 26Vdc, 0.1A, 3W

14VA, 0.58A

24Vac, 50-60 Hz Sense

+12V Rnet-

Gnd

BACnet ®

Inputs 1 & 2 0-5V, therm, dry

Inputs 3 & 4 Therm, dry

AO: 0-10 Vdc 5mA Max

Local Access

LStat/ZASF

Short pins LStat = or IN-3 =

B T4

LogiStat/IN3 & 4

ZASF

CW CCW

Motor

Error

Run

Power

Therm/dry 0-5Vdc

Made in USA

PortInputs

TxRx

MSTP Baud

76.8k38.4k19.2k9600

U.S. Patent No. 6,715,690 B2

CAUTION:

This product was designed to be mounted inside the building envelope. Warranty voided if mounted outside.

ZN341v+

On

CAUTION:

To Reduce the Risk of Fire or Electric Shock, Do Not Interconnect the Outputs of Different Class 2 Circuits.

Damper release button inside

24 VAC

From XFMR

B W Sh SA DA T-

T+

T+

T-

R B W

W B

CmNet out to next Device

B W Sh

B W Sh

CmNet in

R

DTSP-4

DA Temp 3

HW Valve1

R B

W B

ZN341V+

T-SF S/S2

DA Temp3

H L

SF HC

B W G R

Gnd Rnet+ Rnet-

+12V MANUAL ON WARMER

INFO COOLER

AUTOMATED LOGIC

RSP

B W G R

HW Valve1 Ccw

Com

Cw

Ground

HW Valve (close)

HW Valve (open)

W

B

R

HWR HWS

W B

C

PAM-1

VF ST/STP 2

120 VAC

N H

Typ. of 22

Typ. of 22

W B

RA

Bill of Materials

DID DESCRIPTION MANUFACTURER PART NUMBER QTY

DTSP-4 DUCT TEMP SENSOR POINT, 4 IN. BAPI ALC/10K-2-D-4 - NB10-PL 22 ea PAM-1 SP/ST KELE PAM-1 22 ea RSP RS PRO STANDARD SPACE TEMPERATURE W/LCD ALC RSP 22 ea ZN341V+ VAV CONTROLLER 3DO,4UI,1AO W/ACTUATOR, FLOW SENSOR AUTOMATED LOGIC ZN341V+ 22 ea

Zone Control - FTU VAV Box w/SP

Specification Section 15900

Juneau, AK ANM-JRD Facilities Phase I & II

Checked by: EP

Engineer: DMD

Zone Control - FTU VAV Box w/SP

LO

HI

- O +

B W R

ADPA-PL

Note! Manufacturer wire colors differ from MSI standards!

Cable Black

Red White

Actuator White Red Black terminates to:

Rnet+

D O

-3

P ow er fo r D .O

.s

BU

S D

O -1

D O

-2

AO

-1

G nd

Analog Output

G nd

IN

-2

IN

-1

G nd

IN

-3

G nd

IN

-4

LE

D

G nd

R ne t +

R ne t -

+1 2V

R n e t CMnet

N et

N et

Sh ie ld

G ro un d

V ac

Power

Batt

CR2032

10's

1's

9 6

9 6

Therm/dry 0-5VdcIN-2

IN-1

Format

Rnet LogiStat

ARC156

MSTP

High (with filter)

Low

Flow

Outputs 24V Max, 1A Max

Conductors Only

Class 2

Use Copper 26Vdc, 0.1A, 3W

14VA, 0.58A

24Vac, 50-60 Hz Sense

+12V Rnet-

Gnd

BACnet ®

Inputs 1 & 2 0-5V, therm, dry

Inputs 3 & 4 Therm, dry

AO: 0-10 Vdc 5mA Max

Local Access

LStat/ZASF

Short pins LStat = or IN-3 =

BT

LogiStat/IN3 & 4

ZASF

CW CCW

Motor

Error

Run

Power

Therm/dry 0-5Vdc

Made in USA

PortInputs

TxRx

MSTP Baud

76.8k38.4k19.2k9600

U.S. Patent No. 6,715,690 B2

CAUTION:

This product was designed to be mounted inside the building envelope. Warranty voided if mounted outside.

ZN341v+

On

CAUTION:

To Reduce the Risk of Fire or Electric Shock, Do Not Interconnect the Outputs of Different Class 2 Circuits.

Damper release button inside

24 VAC

From XFMR

B W Sh

SA DA

T- T+

T+

T-

R B W

CmNet out to next Device

B W Sh

B W Sh

CmNet in

R

DTSP-4

DA Temp 3

HW Valve1

R B

W B

ZN341V+

T-SF S/S2

DA Temp3

H L

SF HC

B W G R

Gnd Rnet+ Rnet-

+12V MANUAL ON WARMER

INFO COOLER

AUTOMATED LOGIC

RSP

B W G R

HW Valve1 Ccw

Com

Cw

Ground

HW Valve (close)

HW Valve (open)

W

B

R

HWR HWS

W B

C

PAM-1

N H

120 VAC

W B

W B

T+

SPP

RA

W B R

Space Pressure4

T+

W B R

RA Damper5

RAEA

1 2 8

R B W

AEM-62

Thermostat Location ZCard

Address Zcard Type Coil/FT/CUH/RP Sensor Type

Device VA Draw

Served by Equipment

RM A-210North 29 ZN341V+ DHC-23 RS Pro 29 VA FTU-23

Z Card Schedule

1 Building Static Pressure Sensor is located in Rm 210

SF S/S 2

Space Pressure4 RA Damper5

Bill of Materials

DID DESCRIPTION MANUFACTURER PART NUMBER QTY

ADPA-PL AIR DIFF PRESS. ANALOG PANEL MOUNT, 0-1 IN. W.C. ALTA LABS PXPXX01S 1 ea AEM-62 ACTUATOR ELEC., MOD, 24V, SR, 0-10V, 62 IN. LB DELTA DCMS24-62 1 ea DTSP-4 DUCT TEMP SENSOR POINT, 4 IN. BAPI ALC/10K-2-D-4 - NB10-PL 1 ea PAM-1 SP/ST KELE PAM-1 1 ea RSP RS PRO STANDARD SPACE TEMPERATURE W/LCD ALC RSP 1 ea SPP STATIC PRESSURE PICKUP BAPI ZPSACC01 1 ea ZN341V+ VAV CONTROLLER 3DO,4UI,1AO W/ACTUATOR, FLOW SENSOR AUTOMATED LOGIC ZN341V+ 1 ea

Misc. Non-DDC Controls

Specification Section 15900

Juneau, AK ANM-JRD Facilities Phase I & II

Checked by: EP

Engineer: DMD

Misc. Non-DDC Controls

UH 3-1 Control CUH 3-1 Control

CUH

Motor

SA

HW

HWS HWR

HWS

HWR

LVT LVT

120 V H

N 120 V

H

N

EA RAEF

120 V H

N

EF 3-4 Control

AE2PH-62A 4 3

RE

C

AC-1 Condenser Fan

SF

N H

120 VAC

Bill of Materials

DID DESCRIPTION MANUFACTURER PART NUMBER QTY

AE2PH-62a ACTUATOR ELECTRIC, 2-POS, 120V, SR, 62 IN. LB, W/END SWITCH DELTA DCS120-62A 1 ea LVT LINE VOLTAGE THERMOSTAT COLUMBUS ETD5-S-1S 2 ea

ANM-JRD Admin Facility

HVAC Controls Sequence of Operation

Boiler Control

Boiler System - Run Conditions:

Boiler Circulation Pump CP 3-4 will be enabled whenever there is a call for heat from any DDC monitored equipment at the AMN-JRD Facility or the outside air is less than 50°F (adj.). After CP 3-4 has been enabled for 5 minutes (adj.) the boiler will be enabled to run on its internal operating circuit and safeties.

To prevent short cycling, the Boiler and circulation pump will run for and be off for minimum adjustable times (both user definable), unless shutdown on safeties or outside air conditions.

Alarms will be provided as follows:

• Boiler Failure: Commanded on, but the status is off.

• Boiler Running in Hand: Commanded off, but the status is on.

• Hot Water Pump 3 o Failure: Commanded on, but the status is off.

o Running in Hand: Commanded off, but the status is on.

Primary Hot Water Temperature Monitoring:

The following temperatures will be monitored:

• Primary hot water supply.

Alarms will be provided as follows:

• High Primary Hot Water Supply Temp: If greater than 200°F (adj.).

• Low Primary Hot Water Supply Temp: If less than 100°F (adj.).

System Pressure Monitor:

The sensor will measure hot water return pressure and alarms will be provided as follows:

• Low Hot Water Return Pressure: If the hot water return water pressure is less than 8lbf/in2 (adj.).

Heat Exchanger Control

Heating Glycol System - Run Conditions:

The Heating Glycol system pumps will be enabled whenever there is a call for heat from any DDC monitored equipment at the AMN-JRD Facility or the outside air is less than 50°F (adj.).

Heating Glycol Pump Lead/Standby Operation:

The two heating glycol pumps will operate in a lead/standby fashion.

• The lead pump will run first.

• On failure of the lead pump, the standby pump will run and the lead pump will turn off.

• The designated lead pump will rotate each time the system is started or on a scheduled basis.

Alarms will be provided as follows:

• Heating Glycol Pump 1 & 2 o Failure: Commanded on, but the status is off.

o Running in Hand: Commanded off, but the status is on.

o Runtime Exceeded: Status runtime exceeds a user definable limit.

Heating Glycol Return Temperature Setpoint Reset:

The heating glycol return temperature setpoint will reset based on outside air temperature.

As outside air temperature rises from 0°F (adj.) to 60°F (adj.) the glycol return temperature setpoint will reset downwards from 180°F (adj.) to 120°F (adj.).

Alarms will be provided as follows:

• High Heating Glycol Return Temp: If greater than 200°F (adj.).

• Low Heating Glycol Return Temp: If less than 100°F (adj.).

Heat Exchanger 3-Way Valve Control:

The controller will measure the heating glycol return temperature and modulate the 3-way diverting valve to maintain its setpoint.

System Pressure Monitor:

The sensor will measure heating glycol return pressure and alarms will be provided as follows:

• Low Heating Glycol Return Pressure: If the heating glycol return…