C-2 Attachment 7 DDC HVAC Control Record Drawings.pdf
PDF 1 MB Posted
- Attached to
- JRD Compound Heating - Ventilation - Air Conditioning & Envelope Improvements Federal contract opportunity
- Solicitation number
- 1240BJ26Q0001
- Issued by
- Department of Agriculture Forest Service
About this file
This document is a set of record drawings and technical specifications for the ANM-JRD Shop Controls Upgrade project in Juneau, Alaska, prepared by Meridian Systems, Inc. The project involves a Building Automation/HVAC Control System upgrade (Project Number 2017-AK-33) and includes detailed control system design documentation, wiring specifications, equipment schedules, and control sequences of operation.
The technical specifications detail a comprehensive DDC (Direct Digital Control) system utilizing Automated Logic equipment including LGR25 gateway modules, SE6104 and M-series control modules, and ZN-series field controllers. Key components include standard cable specifications for Class 2 wiring (18/2 AWG twisted pair for I/O, 22/2 AWG shielded for ARC156/CMnet communication, and CAT5E for Ethernet), transformer schedules specifying 100VA units distributed across multiple panels, and a water control valve schedule with 23 fan terminal units (FTUs) using Spartan three-way modulating valves. The system architecture comprises four main control panels (PNL-1 through PNL-4) distributed across warehouse, storage, and administration buildings with CMnet (ARC156) network communication at 156 kbaud. The HVAC controls sequence of operation specifies boiler control with lead/standby pump operation, heat exchanger control with outdoor air reset, AHU-1 supply/return fan VFD speed control maintaining 0.375" static pressure setpoint, economizer operation, and 23 individually controlled fan terminal units with zone-level temperature setpoint adjustment, heating/cooling modulation, and occupancy-based scheduling. Installation requirements mandate plenum-rated cabling, proper wire labeling using Brady ID.Pro Plus system or equivalent, and adherence to national and local electrical codes with all DDC wiring terminations free of splices.
View the file
Other files for this federal contract opportunity
Show all 18
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ANM-JRD Shop Controls Upgrade
Juneau, Alaska
200 W 34th Ave #969 Anchorage, Alaska 99503
As Prepared By
Project Number:
Building Automation / HVAC Control System
2017-AK-33
Record Drawings
Phone Number: (907) 279-3320 Fax Number: (907) 279-2369
JOB NO: 2017-AK-3312/8/2017RecordREV: 0
Table of Contents
Table of Contents
Juneau, Alaska
ANM-JRD Shop Controls Upgrade
CHECK BY: CW
DSCODE: JK
1: Titlepage 2: Table of Contents 3: Cable Specification Chart 4: DDC Electrical Installer Notes 5: ARCnet/CMnet Wiring Guide 6: Summary Bill of Materials 7: Valve Schedule 8: Transformer Schedule 9: Control Module Schedule 10: Network Riser Diagram 11: PNL-1 Layout/Warehouse
Cable Specification Chart
Cable Specification Chart
Juneau, Alaska
ANM-JRD Shop Controls Upgrade
CHECK BY: CW
DSCODE: JK
Meridian Systems Conductor Color Standard:
All Input/Output wiring must adhere to the following color standard:
1) BLACK (B) conductor is always for the Ground (Gnd)/ Neutral (N)/ Common (Cmn) reference.
2) WHITE (W) conductor is for the Signal from any field device serving an Analog input, the switched leg of the Digital output to include one of the 2 switched legs of a tri-state / floating motor actuator or the 0/10 VDC signal of an Analog output.
3) RED (R) conductor is for 24 VAC/VDC supply voltage to either Input or Output devices or one of the 2 switched legs of a tri-state / floating motor actuator.
Cable Type / Tag AWG Conductors Shield Plenum Typical Application ConnectAir Part # Jacket Color Conductor Colors
18 2 No Yes 24V Power W181P-2051PRB Purple Red/Black
18 2 No Yes Input / Output (2 Cond) W181P-2051PRB White White/Black
18 3 No Yes Input / Output (3 Cond) W183C-2052PRB White White/Black/Red
22 2 Yes Yes BAS Communication - ARCnet, MSTP, Modbus W221P-2227RIB Green White/Black
22 4 Yes Yes Rnet Communication to ZS & RS Thermostats W224C-2057WBLB White w/ Blue Stripe Red/Green/White/Black
23 4PR No Yes CAT6 Ethernet W244P-2274ORGB Orange Multi-Color
- - - Fiber Optic (Prov ided by Others) - - -
Meridian Systems Standard Cable Specificat ions
DDC Electrical Installer Notes
DDC Electrical Installer Notes
Juneau, Alaska
ANM-JRD Shop Controls Upgrade
CHECK BY: CW
DSCODE: JK
General Notes:
Note the following items and return a copy of these drawings with “As-Built” notations on them. The DDC Installer shall provide the ARCnet and Power As-Builts, at a minimum, prior to DDC Network Start-up.
1) Electrical installation shall be in accordance with the project specifications, national, state, and local electrical codes.
2) Power sources (Panel # & Circuit #) for all DDC transformers.
3) Any renumbering or identification / references used in the field for transformers, devices, wiring, etc.
4) Locations of any devices mounted remotely from the Mechanical Rooms, e.g., above a ceiling spaces, isolated areas, etc.
5) Final locations of transformers, e.g., grouped on a gutter serving several DDC panels, electrical rooms, etc.
6) General routing diagram of wiring / cabling throughout facility on a floor plan view of the project.
7) Any unique wiring required when interfacing with existing equipment, e.g., HOA switches in starters, smoke detectors, fire alarm systems, control valves or actuators, etc.
8) Any equipment deficiencies or maintenance issues found, e.g., broken or slipping V-belts, dirty or missing filters, non-functional devices, motors, etc. or unusual noises or other indications of imminent failures.
9) Locate sensors in associated rooms according to Contract Drawings (site coordination may be required); sensors are to be centered 48" above finished floor.
10) All DDC wiring shall be in installed per contract requirements as noted in project specifications.
11) All DDC wiring shall be terminated at the locations designated and must be free of splices.
12) All DDC cable shall meet the multi-conductor cabling chart as noted on the Cable Specification Chart, sheet 3. Alternatives are not acceptable unless approved by the Operations Manager.
13) All DDC panels, ZN Module enclosures (including VAV boxes) and transformers shall have an MSI label affixed. DDC Installer shall fill in the associated information on the label using a fine point Sharpie and legible penmanship.
All poly tubing shall be plenum rated. Poly tubing installation shall meet the same electrical installation requirements of the project.
All DDC system power sources will have dedicated 120Vac circuits. A duplex receptacle shall be installed as shown on the Network Riser Diagram using the aforementioned dedicated circuit. All Ground/Neutral/Common conductors on the secondary side of a power supply transformer shall be earth grounded.
Every effort should be made to mount ZN Modules directly above the associated room sensor or as near as possible with the exception of factory mounted VAV modules. Any ceiling tile / T-bar shall be tagged/ labeled/ dotted to indicate a DDC device/ZN Module/etc. is located above it.
ZN/RC Module addressing dials shall be set by the DDC Installer using the Control Module Schedule.
MSI standardizes on switching the Hot (potential) leg of any control circuit not the Neutral.
DDC Installer shall reference manufacturer’s installation documentation for devices provided by DDC.
DDC Wire Labels:
The Meridian Systems, Inc. (MSI) Electrical Subcontractor is required to label each end of all installed cable(s). Adherence to this identification system is mandatory and must be followed using the Brady I.D. Pro Plus electronic labeling system or equivalent. Reference figures below for typical DDC wire labeling standards.
Figure 1: 24V Power Label Figure 2: ARCnet/Modbus Label Figure 3: M/SE Label Figure 4: ZN/RC Label Figure 5: ZS/RS Label
Typical DDC Pressure Settings:
Figure 6: Veris PXULX05S Jumper Settings Figure 7: Veris PH0X7S Jumper Settings
Device Address Expander Number Point Type and Address
Point Types – Analog Input (AI), Digital Input (DI), Analog Output (AO), Digital Output (DO).
The M/SE Line control modules are typically located inside a DDC panel.
Tab Label Text - Point Name : 2-0-AI01 Point Name (UI / UO)1
Unique number assigned to specific input/output.
Reference control drawings for tag number.
The ZN/RC Line control modules are typically located out in the field.
Rnet
The Rnet cable is wired from the control module Rnet port to the associated ZS or RS sensor.
ARCnet (CMnet) Label
Modbus Label
Transformer (XFMR) # Transformer Output #
The transformer output only applies to the Functional Devices PSH500A/PSH300A transformers.
XFMR 1-A
CMnet In – DEV: XX
CMnet Out – DEV: XX
This labeling method is used to assist the Technician in network troubleshooting if necessary.
Equipment Name
Label the Modbus cable with the equipment name, e.g., AHU-1 SF VFD, P-1 VFD, Electric Meter, etc.
Water System
Range: B (0-50psig) JP1: Volts
JP2: 0-5V
JP3: Slow
Steam System
Range: A (0-25psig) JP1: Volts
JP2: 0-5V
JP3: Slow
Filter
Range: 4 (0-2.5 WC) SW4: Volts
JP4: 0-5V
JP5: Unidirectional JP7: Inches WC JP8: Standard
Duct Static
Range: 4 (0-2.5 WC) SW4: Volts
JP4: 0-5V
JP5: Unidirectional JP7: Inches WC JP8: Standard
Building Static
Range: 0 (0-0.1 WC) SW4: Volts
JP4: 0-5V
JP5: Bidirectional JP7: Inches WC JP8: Standard
ARCnet/CMnet Wiring Guide
ARCnet/CMnet Wiring Guide
Juneau, Alaska
ANM-JRD Shop Controls Upgrade
CHECK BY: CW
DSCODE: JK
CMnet
ARC156 / CMnet Wiring Detail ARC156 / CMnet Daisy Chain Configuration
VAV-3
VAV-4
VAV-5
CMnet
ARC156 (CMnet) termination point on all Modules
(LG, M, S, ZN,
etc.).
Summary Bill of Materials
Summary Bill of Materials
Juneau, Alaska
ANM-JRD Shop Controls Upgrade
CHECK BY: CW
DSCODE: JK
Summary Bill of Materials
DID DESCRIPTION MANUFACTURER PART NUMBER QTY
RS RNET ZONE TEMP SENSOR WITH COMM AUTOMATED LOGIC RS 3 ea SDU500 SURGE PROTECTOR, 120VAC BATTERY BACK-UP SOLA SDU500 3 ea
Valve Schedule
Valve Schedule
Juneau, Alaska
ANM-JRD Shop Controls Upgrade
CHECK BY: CW
DSCODE: JK
Page intentionally left blank, the scope of work for this project updated did not require any additional valves.
Transformer Schedule
Transformer Schedule
Juneau, Alaska
ANM-JRD Shop Controls Upgrade
CHECK BY: CW
DSCODE: JK
Part # / XFMR # Output Dev ices Serv ed
VA
Load UPS Transformer Location
Panel Location Panel Circuit
TR100VA002 / 1 (Existing) - PNL-1 (DEV PWR) 44 TR100VA002 / 2 (Existing) - PNL-1 (FIELD PWR) 12 Warehouse 1 5 TR100VA002 / 3 (Existing) - PNL-1 (DEV PWR) 24 Storage Storage Bldg 2 15 TR100VA002 / 4 (Existing) - PNL-3 (DEV PWR) 20 TR100VA002 / 5 (Existing) - PNL-3 (FIELD PWR) 14 TR100VA002 / 6 (Existing) - PNL-4 (DEV PWR) 40 TR100VA002 / 7 (Existing) - PNL-4 (FIELD PWR) 24 TR100VA002 / 8 (Existing) - DEV:7, 8, 9, 10 80 Rm A 101 Rm A 101 - - TR100VA002 / 9 (Existing) - DEV:11, 12, 13, 14 80 Rm A 122 Rm A 122 - - TR100VA002 / 8 (Existing) - DEV:15, 16, 17, 18 80 Rm A 125 Rm A 125 - - TR100VA002 / 9 (Existing) - DEV:19, 20, 21, 22 80 Rm A 112 Rm A 112 - - TR100VA002 / 8 (Existing) - DEV:23, 24, 25 60 Rm A 203 Rm A 203 - - TR100VA002 / 9 (Existing) - DEV:26, 27, 28 60 Rm A 215 Rm A 215 - - Note: Each transformer output, e.g., 1-1, is rated for 100VA. Meridian Systems, Inc. recommends not exceeding 80 VA load. The VA calculations can be found on the DDC Control Module Schedule.
3 - Administration
Bldg.
1st Floor Boiler
Rm
4 - Administration
Bldg.
3rd Floor
Mech. Rm
Transformer Schedule
(NEW)
SDU500
(NEW)
SDU500
(NEW)
SDU500
Warehouse Mech Rm
Control Module Schedule
Control Module Schedule
Juneau, Alaska
ANM-JRD Shop Controls Upgrade
CHECK BY: CW
DSCODE: JK
Page intentionally left blank, the scope of work for this project updated did not require any additional control modules.
Network Riser Diagram
Network Riser Diagram
Juneau, Alaska
ANM-JRD Shop Controls Upgrade
CHECK BY: CW
DSCODE: JK
SDU500
120 VAC
PNL:1
Ckt: 5
SDU500
120 VAC
120 VAC
SDU500
Bill of Materials
DID DESCRIPTION MANUFACTURER PART NUMBER QTY
SDU500 SURGE PROTECTOR, 120VAC BATTERY BACK-UP SOLA SDU500 3 ea
1 3 SDU500s added to the system for power surges power outage protection
PNL-1 Layout/Warehouse
PNL-1 Layout/Warehouse
Juneau, Alaska
ANM-JRD Shop Controls Upgrade
CHECK BY: CW
DSCODE: JK
XFMR 1
CMnet – Out
W B Sh W B Sh
XFMR 2
CMnet – In
DEV: 2
AHU-1
Warehouse
Rnet
Gnd Rnet+ Rnet- +12V
AUTOMATED LOGIC
Rnet
Gnd Rnet+ Rnet- +12V i
RS
Typ of 3
1 New RS sensors added to existing system
1 82 3 4 5 6 7 O N
485-2w 485-4w
Port S1
Ext. Batt.
Int. Batt.
DCD
DTR
Rx Tx
EIA-2324 wire2 wire
Signal Ground
Rx- Rx+ Tx- Tx+ n/c n/c
Net- Net+
External Battery
Gnd +3V
Ground 24V ac/dc
Power
On Off
Module Status
3V Lithium Battery CR-123A10/100 BaseT
Ethernet Port E1
100 LAN LINK
Cmnet transmit Cmnet receive
Port S1 receive Port S1 transmit
Battery low
Blinking Dot = “Run”
Format
BACnet Over ARCNET156 KBaud
LGR25
Control Module
Without Keypad Display:
24Vac, 24VA, 1A, 50-60 Hz 26Vdc, 10W, 0.4A
Use Copper Conductors Only Class 2
Net +
Net -
Shield
CMnet
Rnet Local Access
Gnd Rnet + Rnet - +12V
Rnet
Off
On
Enhanced Access Port on S2 IP Addr
Module Address
10's 1's
BT485
Archive Valid
Power
LED
BT485
Port S2
BT485
Error Codes:
DCD
DTR
Rx Tx n/c n/c
Net- Net+
EIA-
485 232
EIA-232
EIA-485
EIA-232
EIA-485
Default
Assigned
+100
Disable
Enable
Disable
Enable
Address
MSTP
on S1
PTP
on S2
Tx
Rx
Option Comm
Signal Ground
Chase = OK 0 = Download required 1 = Control Program Error 2 = RAM full 3 = Comm setup error 4 = System error 8 = Formatting
LGR25
Module Pwr
DEV: 1
DDC Gateway
W B Sh
CMnet
R B
Field Pwr
Terminal Block
TB-2
B
R 24VAC
GND
Terminal Block
TB-1
R B
W B Sh W B Sh
CMnet
CMnet
B
R 24VAC
GND
Sh B W
SF Status : 2-0-DI01 W B
Freezestat : 2-0-DI02
MA Temp : 2-0-AI03
RA Temp : 2-0-AI04
DA Temp : 2-0-AI05
W B W R W B W B
CMnet
P-1 Start/Stop : 2-0-AO01
P-2 Start/Stop : 2-0-AO02
Point Name : 2-0-DO01
Point Name : 2-0-DO02
BACnet Over ARCNET156 KBaud
TM Class 2 24Vac, 50-60 Hz
20VA, 0.83A
Use Copper
Conductors Only
Caution:
To Reduce the Risk of Fire or Electrical Shock, Do Not interconnect the Outputs of Different Class 2 Circuits.
Module Address 10's 1's
+ Aux Power Out On Off
SE6104
CONTROL MODULE
1 2 3 4 O N
Gnd 24V-ac Gnd
Power
IN-1
Gnd
IN-2
Gnd
IN-3
Gnd
IN-4
Gnd
IN-5
Gnd
IN-6
Gnd
IN-7
Gnd
IN-8
Gnd
IN-9
Gnd
AO-4
DO-2
DO-1
DO-3
DO-4
DO-5
DO-6
7+
Gnd
AO-3
5+
Gnd
AO-2
3+
Gnd
AO-1
1+
Gnd
IN-10
Gnd
Select +5V +24V
AO Mode Select 0-10V 0-20mA
Tx
Rx
Batt
CR2032
BACnet
Shield
Net-
Net+
BT485
Inputs: All 10V Max, 20mA Max
IN-1, IN-2: Pulse Count Ability
Outputs 24V Max, 3A Max
Auto Off On
LogiStat Port
Rnet
Gnd
Temp
Sw
LS5v
Gnd
Rnet+
Rnet-
+12V
LogiStat (IN-9, 10 disabled)
Rnet
Stat Select
G nd
R ne t+ R ne t-
Se ns e +1
2V
Error
Run
Format mA VoltsThermister/ dry contact/
RTD
Local Access
MSTP Baud
Cmnet Mode
76.8k
38.4k
19.2k
9600 ARC156
MSTP
Universal Input Mode Select
SE6104
Made in USA
W B W B
W B W B
R
R
10 B W G R
AUTOMATED LOGIC
RS PRO
Bill of Materials
DID DESCRIPTION MANUFACTURER PART NUMBER QTY
RS RNET ZONE TEMP SENSOR WITH COMM AUTOMATED LOGIC RS 3 ea
Juneau, AK
Building Automation / HVAC Control System Specification Section 15900
200 W. 34th Avenue # 969 Anchorage, Alaska 99503- 3969 Phone 907 279 3320 Fax 907 279 2369
Project #: 2006-AK-41
Record Drawings
Project #: 2005-AK-31
Job #: 06-AK-419/20/07Record DrawingsRev: N/A
Table of Contents
Specification Section 15900
Juneau, AK ANM-JRD Facilities Phase I & II
Checked by: EP
Engineer: DMD
Table of Contents
1: Titlepage 2: Table of Contents 3: Cable Specification Chart 4: Installation Notes 5: Valve Schedule 6: Summary Bill of Materials 7: System Layout / Riser Diagram 8: PNL-1 Layout/Warehouse 9: AHU/EF-3 & 4 Control 10: PNL-2 Layout/Storage Bldg 11: PNL-3 Layout / Admin Bldg 12: Heating System Control 13: PNL-4 Layout / Admin Bldg 14: AHU-1 Control 15: EF 3-1 & 3-2 Control 16: EF 3-3 Control 17: Zone Control - FTU VAV Box 18: Zone Control - FTU VAV Box w/SP 19: Misc. non-DDC Controls
Cable Specification Chart
Specification Section 15900
Juneau, AK ANM-JRD Facilities Phase I & II
Checked by: EP
Engineer: DMD
Cable Specification Chart
MERIDIAN SYSTEMS STANDARD CABLE SPECIFICATIONS AND ABBREVIATIONS
Wire/Cable Line Type/Tag Wire Type
12 / 14 / 16 AWG THHN
(Gauge is as NEC dictates per amperes or match existing.)
Typical Application
NEC Class 1 Wiring
Circuit Type
120 VAC Power 120 VAC Neutral 120 VAC Ground
Conductor Color
Black White Green
18/2 AWG Twisted Pair, Plenum Rated, Unshielded
Input/Output Wiring Class 2 Wiring Only
INA
INB
White Black (with White Jacket)
18/2 AWG Twisted/Shielded Single Pair
Black Red (with White Jacket)
EIA-485-4W EIA-232-4W
Tx+ Tx Tx- Rx Rx+ DTR/RTS Rx- DCD/CTS
Black Red Green White (with White Jacket)
Portal 4 Wire Communication22/4 AWG Twisted/Shielded Double Pair, Plenum Rated
Black White (with Green Jacket)
Net+ Net- Shield
ARC156,
Unet Communication (no power wire)
22/2 AWG Twisted/Shielded Plenum Rated
Pair 1 (14 ga) Red Green Pair 2 (22 ga) Black White (with Pink Jacket)
Pair 1
24 VAC
Grd Pair 2 Unet+ Unet-
Unet (with power wire)(1) pair 14AWG for power and (1) pair 22AWG for communications (Plenum Rated)
Green Red Yellow Black (with White Jacket)
Grd Temp
SW
LS5v
RNet22/4 AWG Twisted, Unshielded, Plenum Rated, Stranded, Unshielded, Plenum
Pr.1 White/Blue & Blue Pr.2 White/Orange&Orange Pr.3 White/Green & Green Pr.4 White/Brown & Brown (with Blue Jacket)
Network CommunicationsEthernet24/8 AWG CAT 5 Enhanced, Plenum Rated 100MHz
Tight Buffered Tube Cable 6 Multi -mode 62.5/125 m terminated with ST connectors
Fiber Optic Network Communications N/A
Communication RS-485 2-Wire, Sitelink, I/O Requiring Shield
Net+ or Tx or + Net- or Rx or -
5 18/3 AWG Twisted Pair, Plenum Rated, Unshielded
Input/Output Wiring Class 2 Wiring Only
INA
INB
White Black Red (with White Jacket)
14 / 16 AWG Plenum Rated 14 Gauge 16 Gauge
NEC Class 2 Power Wiring Power to ZN Controllers
Wht Blk
UNet Comm Pair 2 (22 ga.)
UNet Power Pair 1 (14 ga.)
Input from Field Device Output to Field Device
N/A
Input to DDC Module Output from DDC Module
24 VAC Power (+) 24 VAC Neutral (Gnd) (-)
White Black
A B
For Future Use
N/A N/A N/A
IN-#
Gnd
Wht Blk
Wht Blk
Wht Blk
Wht Blk
Blk Wht Red
Blk Wht Red
Signal Gnd
24vac/vdc
N/A N/A
Gnd Hot
Gnd
24vac Blk Wht
Red
A B
24vac/vdc
Blk Wht Red
0/10vdc Gnd
24vac/vdc
0/10vdc
N/A N/A
N/A N/A
Blk Wht
Shld
# N/A
Blk Wht
Shld
S
Net + Net - Shield
Blk Wht
Shld+ S
Net + Net - Shield Blk
Wht
Shld
In
Out
N/AN/A
N/A N/A
N/A N/A
N/A N/A
Blk Wht
Grn
Tx -
Rx -
Rx +Red
N/A
N/A
N/A
-Gnd
24vac
-Net -
Net +
N/A N/A
Tx +
Blk Wht
Grn
Rx
DCD
DTRRed
Tx
RTS
CTS
EIA-485-4W EIA-232-4W
1 2 3 4
B W G R
B W G R
Gnd
Rnet+
+12V
Rnet-
G nd
R ne t+
+1 2V
R ne t-
Installation Notes
Specification Section 15900
Juneau, AK ANM-JRD Facilities Phase I & II
Checked by: EP
Engineer: DMD
Installation Notes
TAB LABEL TEXT - SPARE
BN-DR-DA-EN-PL
Cable Identification/Wire Labels
DA - Device Address EN - Expander Number PL - Point Location
TAB LABEL TEXT - SPARE
BN-DR-DA-FB-PL
DA - Device Address FB - Function Block Number PL - Point Location
U-Line Point NotationM & S-Line Point Notation
Monitoring and control points for remote equipment are identified by the Module Point representation shown above. The System and Service Provider's electrical contractor or installer must label both ends of each control or monitoring point cable using the following format : (BN-DR-DA-EN-PL) or (BN-DR-DA-FB-PL). Adherence to this identification system is mandatory and must be followed using an approved tagging system comparable to the Brady I.D.Pro Plus electronic labeling system or equivalent.
These tags are intended for the wiring for all Analog Inputs (AI's), Digital Inputs (DI's), Analog Outputs (AO's), and Digital Outputs (DO's) except VAV's and terminal equipment where the wire runs are short and the field termination point is seen, or is easily identified. Points using pneumatic tubing follow the same convention.
All communication cable, terminations "in" an "out" of a field module panel, terminal equipment or VAV's must be labeled with "from (equipment name)" and "to (equipment name)" locations. See Figure 1 below.
All ARC156 or RNet communication, serial interface, control, and monitoring wiring must be terminated at the locations designated and must be free of splices.
When stripping multi-conductor cables, use only strippers specifically designed for removal of outer sheath insulation so as not to damage the shielding or insulation of the conductors. Use Ideal Catalog #45-514 or #45-165 data cable strippers or equivalent.
When shielded cable is used, do not strip back sheath more than 1" in order to keep twisted pair from separating. Do not ground shield to the panel or chassis ground. The shield should only be connected to the 'Optional Shield' connection at a module.
Ungrounded shields must be cut back and taped to prevent contact with with metal surfaces (heat shrink is preferred). See figure 2 below.
Multi-conductor cabling other than specified or pre-approved by the System and Service Provider (SSP) is unacceptable.
Electrical installation shall be in accordance with the project specifications, national, state, and local electrical codes along with ALC standards as outlined in this and other documents.
All pneumatic tubing that exceeds ten feet in length must be rigid copper or poly tubing installed in conduit. All poly tubing in exposed areas must be installed in conduit. Use plenum rated poly tubing for runs made in hung ceilings. Short lengths of less than 16 inches are permitted to be exposed for connection to field devices.
All field module panels (FMPs) will have a dedicated 120vac circuit.
Figure 2.
1"
1/4"
Foil Inner
Insulation Outer Jacket
Figure 1.
Shield
From VAV-3
To VAV-5
VAV-3
VAV-5
Equipment Name
ARC156 or UNet termination point in FMP or Terminal Equipment
Wiring Details
0 to 10 VDC Analog Output G
Output Signal
0 to 5 VDC Input B A + From Field Xfmr
Note: Rnet wiring may be installed in a daisy-chain, star or hybrid configuration
RNet
9 Note: All inputs (AI & DI) terminate to terminals on left side of module/device. All outputs (AO & DO) terminate to terminal strip on right side of panel.
Field device terminal designations xx xx xx
Point Name
0-0-UI0
Panel terminal strip or controller device terminal designations
See Cable Identification/Wire Labels on sheet 4 for Device Address notations
Summary Bill of Materials
Specification Section 15900
Juneau, AK ANM-JRD Facilities Phase I & II
Checked by: EP
Engineer: DMD
Summary Bill of Materials
Summary Bill of Materials
DID DESCRIPTION MANUFACTURER PART NUMBER QTY
ADPA-DH AIR DIFF PRESS. ANALOG DUCT MOUNT, 0-10 IN. W.C. ALTA LABS PXDXX02S 2 ea ADPA-PL AIR DIFF PRESS. ANALOG PANEL MOUNT, 0-1 IN. W.C. ALTA LABS PXPXX01S 2 ea AE2PH-62a ACTUATOR ELECTRIC, 2-POS, 120V, SR, 62 IN. LB, W/END SWITCH DELTA DCS120-62A 1 ea AE2PL-60 ACTUATOR ELECTRIC, 2-POS, 24V, SR, 60 IN. LB BELIMO NF24 ALC 1 ea AE2PL-60S ACTUATOR ELECTRIC, 2-POS, 24V, SR, 60 IN/LB BELIMO NF24-S ALC 2 ea AE2PL-62A ACTUATOR ELECTRIC, 2-POS, 24V, SR, 62 IN. LB DELTA DCS24-62A 3 ea AEM-133 ACTUATOR ELEC., MOD, 24V, SR, 2-10V, 133 IN. LB BELIMO AF24-SR ALC 1 ea AEM-140 ACTUATOR ELEC., MOD, 24V, SR, 0-10V, 140 IN. LB DELTA DCMS24-140 2 ea AEM-62 ACTUATOR ELEC., MOD, 24V, SR, 0-10V, 62 IN. LB DELTA DCMS24-62 1 ea CV-1 3-WAY CONTROL VALVE, 1IN., 30.8 CV DELTA ST 1-3-31/DCMS24-62 2 ea CV-2 3-WAY CONTROL VALVE, 1IN., 14.9 CV DELTA CP ST 1-3-15/DCMS24-62 2 ea DTSA-24 DUCT TEMP SENSOR AVERAGING, THERMISTOR, 24' ELEMEN BAPI ALC/10K-2-A-24-EU 2 ea DTSP-12 DUCT TEMP SENSOR POINT, 12 IN. BAPI ALC/10K-2-D-12-EU 4 ea DTSP-18 DUCT TEMP SENSOR POINT, 18 IN. BAPI ALC/10K-2-D-18-EU 1 ea DTSP-4 DUCT TEMP SENSOR POINT, 4 IN. BAPI ALC/10K-2-D-4 - NB10-PL 23 ea EN106TP 10 BASE-T 6 PORT 10MBPS ETHERNET HUB NETGEAR EN106TP 0 ea ENCL-M ENCLOSURE CABINET-MEDIUM HOFFMAN A24N24ALP 2 ea ENCL-UC ENCLOSURE CABINET-U CARD VERSA PRODUCTS CSE-992 1 ea Hum HUMIDISTAT W43A JOHNSON W43A 1 ea ITS IMMERSION TEMPERATURE SENSOR, THERMISTOR BAPI ALC/10K-2-I-4-EU 3 ea ITSW IMMERSION TEMP. SENSOR, SS WELL 4 IN. BAPI BA/4 3 ea LGR25 LGR25 AUTOMATED LOGIC LGR25 1 ea LPA LIQUID PRESSURE ANALOG, PSI 0/25-50-100 ALTA LABS PHX075 2 ea LTDT-A LOW TEMP DETECT, AUTO RESET, SPDT SIEMENS 134-1510 2 ea LVT LINE VOLTAGE THERMOSTAT COLUMBUS ETD5-S-1S 2 ea M220nx M220NX AUTOMATED LOGIC M220NX 1 ea M4106nx M4106NX AUTOMATED LOGIC M4106NX 1 ea M8102nx M8102NX AUTOMATED LOGIC M8102NX 1 ea OAREF OUTSIDE AIR PRESSURE, REFERENCE HEAD DWYER A306 1 ea OAS OUTSIDE AIR TEMPERATURE SENSOR, WEATHERPROFF ENCL. BAPI ALC/10K-2-O-EU 1 ea PAM-1 SP/ST KELE PAM-1 23 ea RE RELAY-SPDT FUNCTIONAL DEVICES RIBTU1C 2 ea RE/CSRE RELAY-CURRENT SENSOR EXTERNAL CT FUNCTIONAL DEVICES RIBXLSRA 5 ea RE/CSRI RELAY-CURRENT SENSOR INTERNAL CT FUNCTIONAL DEVICES RIBX24SBA 1 ea RES REL/ELEC W HOA SW. FUNCTIONAL DEVICES RIBTU1S 3 ea RS RS STANDARD SPACE TEMPERATURE ALC RS 2 ea RSP RS PRO STANDARD SPACE TEMPERATURE W/LCD ALC RSP 23 ea SE6104 SE6104 AUTOMATED LOGIC SE6104 1 ea SPP STATIC PRESSURE PICKUP BAPI ZPSACC01 2 ea Type A FTU RHC VALVE 3/4 IN., 3 WAY SPARTAN VE325-34-ED1.0-ME4140 15 ea Type B FTU RHC VALVE 3/4 IN., 3 WAY SPARTAN VE325-34-ED2.0-ME4140 6 ea Type C FTU RHC VALVE 3/4 IN., 3 WAY SPARTAN VE325-34-ED3.0-ME4140 2 ea XFMR TRANSFORMER,120 TO 24VAC,100VA W/CB,DTHM ULL FUNCTIONAL DEVICES TR100VA002 10 ea ZN220 ZN220 AUTOMATED LOGIC ZN220 4 ea ZN341V+ VAV CONTROLLER 3DO,4UI,1AO W/ACTUATOR, FLOW SENSOR AUTOMATED LOGIC ZN341V+ 23 ea ZN551 UNITARY CONTROLLER 5DO, 5UI, 1 AO AUTOMATED LOGIC ZN551 1 ea
Valve Schedule
Specification Section 15900
Juneau, AK ANM-JRD Facilities Phase I & II
Checked by: EP
Engineer: DMD
Valve Schedule
WATER CONTROL VALVE SCHEDULE
HX-1 CV-1 1 100.0 57.7 74.0 1.8 2 1/2" Threaded Delta ST250-3-74DCMS24-62 A-AB Diverting AHU-1 CV-2 1 30.0 17.3 23.5 1.6 1 1/2" Threaded Delta ST150-3-24DCMS24-62 A-AB FTU-1 FTU-1 1 1.7 1.0 1.0 2.9 3/4" Solder Spartan VE325-34-ED1.0-ME4140 Last Type 1 FTU-2 FTU-2 1 2.0 1.2 2.0 1.00 3/4" Solder Spartan VE325-34-ED2.0-ME4140 Last Type 2 FTU-3 FTU-3 1 1.4 0.8 1.0 1.96 3/4" Solder Spartan VE325-34-ED1.0-ME4140 Last Type 1 FTU-4 FTU-4 1 1.5 0.9 1.0 2.25 3/4" Solder Spartan VE325-34-ED1.0-ME4140 Last Type 1 FTU-5 FTU-5 1 1.3 0.8 1.0 1.69 3/4" Solder Spartan VE325-34-ED1.0-ME4140 Last Type 1 FTU-6 FTU-6 1 1.0 0.6 1.0 1.00 3/4" Solder Spartan VE325-34-ED1.0-ME4140 Last Type 1 FTU-7 FTU-7 1 1.5 0.9 1.0 2.25 3/4" Solder Spartan VE325-34-ED1.0-ME4140 Last Type 1 FTU-8 FTU-8 1 0.9 0.5 1.0 0.81 3/4" Solder Spartan VE325-34-ED1.0-ME4140 Last Type 1 FTU-9 FTU-9 1 1.4 0.8 1.0 1.96 3/4" Solder Spartan VE325-34-ED1.0-ME4140 Last Type 1 FTU-10 FTU-10 1 1.4 0.8 1.0 1.96 3/4" Solder Spartan VE325-34-ED1.0-ME4140 Last Type 1 FTU-11 FTU-11 1 1.2 0.7 1.0 1.44 3/4" Solder Spartan VE325-34-ED1.0-ME4140 Last Type 1 FTU-12 FTU-12 1 1.3 0.8 1.0 1.69 3/4" Solder Spartan VE325-34-ED1.0-ME4140 Last Type 1 FTU-13 FTU-13 1 1.0 0.6 1.0 1.00 3/4" Solder Spartan VE325-34-ED1.0-ME4140 Last Type 1 FTU-14 FTU-14 1 3.8 2.2 3.0 1.60 3/4" Solder Spartan VE325-34-ED3.0-ME4140 Last Type 3 FTU-15 FTU-15 1 3.8 2.2 3.0 1.60 3/4" Solder Spartan VE325-34-ED3.0-ME4140 Last Type 3 FTU-16 FTU-16 1 1.4 0.8 1.0 1.96 3/4" Solder Spartan VE325-34-ED1.0-ME4140 Last Type 1 FTU-17 FTU-17 1 1.9 1.1 2.0 0.90 3/4" Solder Spartan VE325-34-ED2.0-ME4140 Last Type 2 FTU-18 FTU-18 1 1.4 0.8 1.0 1.96 3/4" Solder Spartan VE325-34-ED1.0-ME4140 Last Type 1 FTU-19 FTU-19 1 2.2 1.3 2.0 1.21 3/4" Solder Spartan VE325-34-ED2.0-ME4140 Last Type 2 FTU-20 FTU-20 1 1.9 1.1 2.0 0.90 3/4" Solder Spartan VE325-34-ED2.0-ME4140 Last Type 2 FTU-21 FTU-21 1 1.4 0.8 1.0 1.96 3/4" Solder Spartan VE325-34-ED1.0-ME4140 Last Type 1 FTU-22 FTU-22 1 2.0 1.2 2.0 1.00 3/4" Solder Spartan VE325-34-ED2.0-ME4140 Last Type 2 FTU-23 FTU-23 1 1.9 1.1 2.0 0.90 3/4" Solder Spartan VE325-34-ED2.0-ME4140 Last Type 2
Equipment Name Qty GPM TAG Cal Cv Valve Cv Actual
DP Valve Size Connection Type
CommentsFail Position
Valve Manufacturer Valve & Actuator Part Number
TYPE A
Type Valve & Acutator Quantity Type A VE-325-34-ED1.0-ME4140 15 Type B VE-325-34-ED2.0-ME4140 6 Type C VE-325-34-ED3.0-ME4140 2
TYPE B
TYPE C
Bill of Materials
DID DESCRIPTION MANUFACTURER PART NUMBER QTY
Type A FTU RHC VALVE 3/4 IN., 3 WAY SPARTAN VE325-34-ED1.0-ME4140 15 ea Type B FTU RHC VALVE 3/4 IN., 3 WAY SPARTAN VE325-34-ED2.0-ME4140 6 ea Type C FTU RHC VALVE 3/4 IN., 3 WAY SPARTAN VE325-34-ED3.0-ME4140 2 ea
System Layout / Riser Diagram
Specification Section 15900
Juneau, AK ANM-JRD Facilities Phase I & II
Checked by: EP
Engineer: DMD
System Layout / Riser Diagram
Storage Bldg
Warehouse
PNL-1
Warehouse Mech Room
Dev 2
SE6104
Site #55
LGR25
120 VAC
Pnl: 1 Ckt: 5 D
PNL-2
Storage Bldg
Dev 3
ZN551
ENCL-UC
XFMR
Typ. of 1
Transformer #3
120 VAC
Pnl: 2
Ckt: 15
CAT-JCK
120VAC
Duplex outlet
Administration Bldg
PNL-3
Admin Bldg 1st Floor
Boiler Rm
Dev 4 M8102nx
EN106TP ENCL-M
PNL-4
Admin Bldg 3rd Floor
Mech Rm
Dev 6 M220nx
Dev 5 M4106nx
ENCL-M
Power & Cmnet to ZN Cards
VAC XFMR
Typ. of 6
Transformer #8-13
Factory Mounted Enclosure
1st and 2nd Floor FTU
VAV's
Dev 7-29
ZN341V+
XFMR
Typ. of 2
Transformer #4-5
120 VAC
Pnl: ___ Ckt: ___
XFMR
Typ. of 2
Transformer #6-7
120 VAC
Pnl: ___ Ckt: ___
EF 3-3
Rm A-129
Dev 30
ZN220
ENCL-UC
XFMR
Typ. of 2
Transformer #1-2
120VAC
Duplex outlet
Router ACS DSL
Device IP Address Gateway Router Subnet Mask NAT WebCTRL Server 192.168.1.21 192.168.1.1 255.255.255.0
LGR25 172.168.1.13 172.168.1.254 255.255.255.0 216.67.11.174
External Address 209.193.4.7 / 209.193.4.8
DNS
NETWORK INFORMATION
Bill of Materials
DID DESCRIPTION MANUFACTURER PART NUMBER QTY
EN106TP 10 BASE-T 6 PORT 10MBPS ETHERNET HUB NETGEAR EN106TP 0 ea ENCL-M ENCLOSURE CABINET-MEDIUM HOFFMAN A24N24ALP 2 ea ENCL-UC ENCLOSURE CABINET-U CARD VERSA PRODUCTS CSE-992 1 ea XFMR TRANSFORMER,120 TO 24VAC,100VA W/CB,DTHM ULL FUNCTIONAL DEVICES TR100VA002 10 ea
PNL-1 Layout/Warehouse
Specification Section 15900
Juneau, AK ANM-JRD Facilities Phase I & II
Checked by: EP
Engineer: DMD
PNL-1 Layout/Warehouse
0 1 2
9 0 1 2
BACnet Over ARCNET156 KBaud
TM Class 2 24Vac, 50-60 Hz
20VA, 0.83A
Use Copper
Conductors Only
Caution:
To Reduce the Risk of Fire or Electrical Shock, Do Not interconnect the Outputs of Different Class 2 Circuits.
Module Address 10's 1's
+ Aux Power Out On Off
SE6104
CONTROL MODULE
1 2 3 4 O N
Gnd 24V-ac Gnd
Power
IN-1
Gnd
IN-2
Gnd
IN-3
Gnd
IN-4
Gnd
IN-5
Gnd
IN-6
Gnd
IN-7
Gnd
IN-8
Gnd
IN-9
Gnd
AO-4
DO-2
DO-1
DO-3
DO-4
DO-5
DO-6
7+
Gnd
AO-3
5+
Gnd
AO-2
3+
Gnd
AO-1
1+
Gnd
IN-10
Gnd
Select +5V +24V
AO Mode Select 0-10V 0-20mA
Tx
Rx
Batt
CR2032
CMnet
Shield
Net-
Net+
Bias
Inputs: All 10V Max, 20mA Max
IN-1, IN-2: Pulse Count Ability
Outputs 24V Max, 3A Max
Auto Off On
LogiStat Port
Rnet
Gnd
Temp
Sw
LS5v
Gnd
Rnet+
Rnet-
+12V
LogiStat (IN-9, 10 diabled)
Rnet
Stat Select
G nd
R ne t+ R ne t-
S en se +1
2V
Error
Run
Format
0-20mA 0-10V-dc Thermister/ dry contact/
RTD
Rnet Local Access
MSTP Baud
Cmnet Mode
76.8k
38.4k
19.2k
9600 ARC156
MSTP
Universal Input Mode Select
24Vac (+) Gnd (-)
H N G
Transformer Detail (Outside of Control Panel)
VAC
XFMR 1
XFMR 2
Wht
Shld Blk 156K CMnet - Out to PNL-3
1+ 2- 3+ 4-
Field Pwr
Module Pwr
TERMINAL
STRIP
G nd
R ne t+ R ne t-
+1 2V
MANUAL ON WARMER
INFO COOLER
AUTOMATED LOGIC
1 2 3 4
B W G R
B W G R
Located in hallway
SF Status
2-0-DI01
Freezestat
2-0-DI02
MA Temp
2-0-AI03
RA Temp
2-0-AI04
DA Temp
2-0-AI05
Spare
2-0-UI06
Spare
2-0-UI07
Spare
2-0-UI08
Spare
2-0-UI09
Spare
2-0-UI10
MA Damper
2-0-AO1 +
HW Valve
2-0-AO2 +
Spare
2-0-AO03
Spare
2-0-AO04
SF S/S
2-0-DO01
EF S/S
2-0-DO02
Spare
2-0-DO03
Spare
2-0-DO04
Spare
2-0-DO05
Spare
2-0-DO06
0 1 2
9 0 1 2
91 82 3 4 5 6 7 O N
485-2w 485-4w
Port S1
Ext. Batt.
Int. Batt.
DCD
DTR
Rx
Tx
EIA-2324 wire2 wire
Signal Ground
Rx- Rx+
Tx-
Tx+ n/c n/c
Net-
Net+
External Battery
Gnd +3V
Ground 24V ac/dc
Power
On Off
Module Status
3V Lithium Battery CR-123A10/100 BaseT
Ethernet Port E1
100 LAN LINK
Cmnet transmit Cmnet receive
Port S1 receive Port S1 transmit
Battery low
Blinking Dot = “Run”
Format
BACnet Over ARCNET156 KBaud
LGR25
Control Module
Without Keypad Display:
24Vac, 24VA, 1A, 50-60 Hz 26Vdc, 10W, 0.4A
Use Copper Conductors Only Class 2
Net +
Net -
Shield
CMnet
Rnet Local Access
Gnd
Rnet +
Rnet -
+12V
Rnet
Off
On
Enhanced Access Port on S2 IP Addr
Module Address
10's 1's
BT485
Archive Valid
Power
LED
BT485
Port S2
BT485
Error Codes:
DCD
DTR
Rx
Tx n/c n/c
Net-
Net+
EIA-
485 232
EIA-232
EIA-485
EIA-232
EIA-485
Default
Assigned
+100
Disable
Enable
Disable
Enable
Address
MSTP
on S1
PTP
on S2
Tx
Rx
Option Comm
Signal Ground
Chase = OK 0 = Download required 1 = Control Program Error 2 = RAM full 3 = Comm setup error 4 = System error 8 = Formatting
LGR25
SE6104
#2
AHU-1
Warehouse
Wht Blk Shld
156K CMnet - In from Dev 3
Bill of Materials
DID DESCRIPTION MANUFACTURER PART NUMBER QTY
LGR25 LGR25 AUTOMATED LOGIC LGR25 1 ea SE6104 SE6104 AUTOMATED LOGIC SE6104 1 ea
AHU/EF-3 & 4 Control
Specification Section 15900
Juneau, AK ANM-JRD Facilities Phase I & II
Checked by: EP
Engineer: DMD
AHU/EF-3 & 4 Control
Starter
N H
120 VAC
EA
EF-3
Starter
N H
120 VAC
EA
EF-4
W B
EF S/S
2-0-DO2
RES
W B
EF S/S
2-0-DO2
RES
CC
W B
DA Temp
2-0-AI5
W B
MA Temp
2-0-AI3
RA Temp
2-0-AI4
W B
HC
GHR GHS
SF
R B
W B
LTDT-A
Freezestat
2-0-DI2
1 2 3
MA Damper
2-0-AO1
OA DA
RA
39 + 40
NO
NC
W B W B
SF Status
2-0-DI1
SF S/S
2-0-DO1
HW Valve
2-0-AO2 CV-1
DTSP-12DTSA-24
DTSP-12
AEM-133
C
RE/CSRE
Auto
STARTER
Bill of Materials
DID DESCRIPTION MANUFACTURER PART NUMBER QTY
AEM-133 ACTUATOR ELEC., MOD, 24V, SR, 2-10V, 133 IN. LB BELIMO AF24-SR ALC 1 ea CV-1 3-WAY CONTROL VALVE, 1IN., 30.8 CV DELTA ST 1-3-31/DCMS24-62 1 ea DTSA-24 DUCT TEMP SENSOR AVERAGING, THERMISTOR, 24' ELEMEN BAPI ALC/10K-2-A-24-EU 1 ea DTSP-12 DUCT TEMP SENSOR POINT, 12 IN. BAPI ALC/10K-2-D-12-EU 2 ea LTDT-A LOW TEMP DETECT, AUTO RESET, SPDT SIEMENS 134-1510 1 ea RE/CSRE RELAY-CURRENT SENSOR EXTERNAL CT FUNCTIONAL DEVICES RIBXLSRA 1 ea RES REL/ELEC W HOA SW. FUNCTIONAL DEVICES RIBTU1S 2 ea
PNL-2 Layout/Storage Bldg
Specification Section 15900
Juneau, AK ANM-JRD Facilities Phase I & II
Checked by: EP
Engineer: DMD
PNL-2 Layout/Storage Bldg
24 VAC
From XFMR
T-
B W G R
T+
W B Sh
CmNet in from Pnl-1 B
R
CAUTION:
This product was designed to be mounted inside the building envelope. Warranty voided if mounted outside.
Power for D.O.'s
DO-3
DO-2
DO-1
BUSS
Pwr
BACnet
6 7 8 9
6 7 8 9
6 7 8 9
6 7 8 9
Rx
Tx
DO-4
DO-5
AO-1
Gnd
BT485
Net +
Net -
Shield
C M ne t
Te ns
O ne s
Batt
CR
Sense +12V Rnet- Rnet+ Gnd
Gnd
R ne tRnet +
Rnet -
+12V
IN-1
Gnd
IN-2
Gnd
IN-3
Gnd
Gnd
IN-4
IN-5
LED
Inputs: 5V Max
Class 2 24 Vac, 50-60 Hz
20VA, 0.83A
24Vdc, 0.2A, 5W
Use Copper Conductors Only
Ground
24 Vac
Run
Err
ZN551
CONTROLLER
Thermistor/dry contact 0-5Vdc
IN-1
Thermistor/dry contact 0-5Vdc
IN-2
O N
On
MSTP Baud
Communications Selection
9600 19.2k 38.4k 76.8k
MSTP
ARC156
CAUTION:
To Reduce the Risk of Fire or Electric Shock, Do Not Interconnect the Outputs of Different Class 2 Circuits.
Jumper: Gain1
Format
Lstat Rnet
Outputs 24V Max, 1A Max
T+ R B W
EF S/S 3T- B
W
T+
HW Valve 4 DA Temp1
Humidity Enable2
W B W
BB W G R
Terminating Resistor
1 2 4 6
W B
EA RA
EF S/S 3
EF-1
Humidity Enable 213H C
L
HUM
W B
DA
HW
CV-2
HW Valve4
R B W
NC
DTSP-18
OA
12 AE2PL-60
DA Temp1
EF S/S 3
B WW B
GHR GHS
G nd
R ne t+ R ne t-
+1 2V
RS
AUTOMATED LOGIC
1 2 3 4
AE2PL-60S
ZN551
C
RES
208 VAC H
208 VAC N
1 2 4 6
W B
EA RA
EF S/S 3
EF-2
AE2PL-60S
C
RES
208 VAC H
208 VAC N
Bill of Materials
DID DESCRIPTION MANUFACTURER PART NUMBER QTY
AE2PL-60 ACTUATOR ELECTRIC, 2-POS, 24V, SR, 60 IN. LB BELIMO NF24 ALC 1 ea AE2PL-60S ACTUATOR ELECTRIC, 2-POS, 24V, SR, 60 IN/LB BELIMO NF24-S ALC 2 ea CV-2 3-WAY CONTROL VALVE, 1IN., 14.9 CV DELTA CP ST 1-3-15/DCMS24-62 1 ea DTSP-18 DUCT TEMP SENSOR POINT, 18 IN. BAPI ALC/10K-2-D-18-EU 1 ea Hum HUMIDISTAT W43A JOHNSON W43A 1 ea RS RS STANDARD SPACE TEMPERATURE ALC RS 1 ea ZN551 UNITARY CONTROLLER 5DO, 5UI, 1 AO AUTOMATED LOGIC ZN551 1 ea
PNL-3 Layout / Admin Bldg
Specification Section 15900
Juneau, AK ANM-JRD Facilities Phase I & II
Checked by: EP
Engineer: DMD
PNL-3 Layout / Admin Bldg
Class 2 24Vac, 50-60 Hz
20VA, 0.83A
Use Copper
Conductors Only
Gnd
Caution:
To Reduce the Risk of Fire or Electrical Shock, Do Not interconnect the Outputs of Different Class 2 Circuits.
Digital Outputs 24V Max.
3A Max.
Module Address
10's 1's
A - Input Signal B - Gnd/Loop Power
Auxiliary Device
Port
BACnet Over ARCNET156 KBaud
TM
CMnet Mode
ARC1569600/
38.4k
Net +
Net - CMnet
Rx Tx Run Error Power
On Off
Access Port
DO1
DO8
DO2
DO3
DO4
DO5
DO6
DO7
NC NO
A
A
A
A
A
A
A
A
A
A
B
B
B
B
B
B
B
B
B
B
IN1
IN10
IN2
IN3
IN4
IN5
IN6
IN7
IN8
IN9
Universal Input Mode Select
0-5Vdc Thermistor/ dry-contact
0-20 mA
M8102nx
CONTROL MODULE
Gnd
Gnd
AO1
AO2
Format
24 Vac
38.4k
1 2 3 4 O N
0 1 2
9 0 1 2
M8102NX
Shield
Cmnet Baud
Inputs 5V Max, 20mA Max
XFMR 4
XFMR 5
Wht
Shld Blk 156K CMnet - Out to PNL-3
1+ 2- 3+ 4-
Field Pwr
Module Pwr
TERMINAL
STRIP
Heat Exchanger - Pump 1 Status
4-0-DI1
Heat Exchanger - Pump 2 Status
4-0-DI2
Heat Exchanger - HGS Temp
4-0-AI3
Heat Exchanger - HGR Temp
4-0-AI4
Boiler - P3 Status
4-0-DI6
Heat Exchanger - SYS Pressure
4-0-AI5+
Boiler - Boiler Status
4-0-DI7
Boiler - HWS Temp
4-0-AI8
Boiler - SYS Pressure
4-0-AI9+
OA Temp
4-0-AI10
Heat Exchanger - Pump 1 S/S
4-0-DO1
Heat Exchanger - Pump 2 S/S
4-0-DO2
Boiler - Pump 3 S/S
4-0-DO3
Boiler - Boiler Enable
4-0-DO4
Spare
4-0-DO05
Spare
4-0-DO06
Spare
4-0-DO07
Spare
4-0-DO08
Heat Exchanger - HX Valve
4-0-AO1 +
Spare
4-0-AO02
Wht
Shld Blk 156K CMnet - In from
Dev 3 or PNL-1
#4 Boiler & HX
Control
Bill of Materials
DID DESCRIPTION MANUFACTURER PART NUMBER QTY
M8102nx M8102NX AUTOMATED LOGIC M8102NX 1 ea
Heating System Control
Specification Section 15900
Juneau, AK ANM-JRD Facilities Phase I & II
Checked by: EP
Engineer: DMD
Heating System Control
A
HWS
Boiler Status
4-0-DI7
HWS Temp
4-0-AI8
SYS Pressure
4-0-AI9
RE
C
W B
Boiler
COV
R W B
LPA
W B
Air SeperatorITSW
ITSITSW
W B
ITS
HGS Temp
4-0-AI3
HGR Temp
4-0-AI4
CV-1
HX Valve
4-0-AO1
B
HXW
B W
BC
RE/CSRE
Auto
STARTER
CP-2
W B W
BC
RE/CSRE
Auto
STARTER
CP-1
HWR
B W R
HWS ( To Bldg )
( From Bldg )Air Seperator
CP-3
P3 Status
4-0-DI6
Pump 3 S/S
4-0-DO3
W B W B
C
RE/CSRI
N H
120 VAC
Boiler Enable
4-0-DO4
RES
C
W B
X
From Boiler Operating Control Circuit
Pump 2 Status
4-0-DI2
Pump 2 S/S
4-0-DO2
Pump 1 Status
4-0-DI1
Pump 1 S/S
4-0-DO1
Diverting
SYS Pressure
4-0-AI5
COV
R W B
LPA
W B
ITSW
ITS
OAS
W B
Mount on North Facing Wall
OA Temp
4-0-AI10
AB
Bill of Materials
DID DESCRIPTION MANUFACTURER PART NUMBER QTY
CV-1 SOFT TOUCH, 2 1/2IN., THREADED, 3 WAY DIVERTING, FAIL A-AB DELTA ST250-3-74/DCMS24-62 DIVERTING 1 ea ITS IMMERSION TEMPERATURE SENSOR, THERMISTOR BAPI ALC/10K-2-I-4-EU 3 ea ITSW IMMERSION TEMP. SENSOR, SS WELL 4 IN. BAPI BA/4 3 ea LPA LIQUID PRESSURE ANALOG, PSI 0/25-50-100 ALTA LABS PHX075 2 ea OAS OUTSIDE AIR TEMPERATURE SENSOR, WEATHERPROFF ENCL. BAPI ALC/10K-2-O-EU 1 ea RE RELAY-SPDT FUNCTIONAL DEVICES RIBTU1C 1 ea RE/CSRE RELAY-CURRENT SENSOR EXTERNAL CT FUNCTIONAL DEVICES RIBXLSRA 2 ea RE/CSRI RELAY-CURRENT SENSOR INTERNAL CT FUNCTIONAL DEVICES RIBX24SBA 1 ea RES REL/ELEC W HOA SW. FUNCTIONAL DEVICES RIBTU1S 1 ea
Old system layout. See next page for updated layout.
PNL-4 Layout / Admin Bldg
Specification Section 15900
Juneau, AK ANM-JRD Facilities Phase I & II
Checked by: EP
Engineer: DMD
PNL-4 Layout / Admin Bldg
XFMR 7
Wht
Shld Blk
Wht
Shld Blk
156K CMnet - In from PNL-3
1+ 2- 3+ 4-
Module Pwr
TERMINAL
STRIP
XFMR 6
Field Pwr
156K CMnet - Out to VAV box +
Class 2 24Vac, 50-60 Hz
20VA, 0.83A
Use Copper
Conductors Only
Caution:
To Reduce the Risk of Fire or Electrical Shock, Do Not interconnect the Outputs of Different Class 2 Circuits.
24V Max.
3A Max.A - Input Signal
B - Gnd/Loop Power
Auxiliary Device
Port
BACnet Over ARCNET156 KBaud
TM
Module Address
10's 1's
Gnd 24 Vac
M4106nx
CONTROL MODULE
Net +
Net - CMnet
Rx Tx Run Error
CMnet Mode
ARC1569600/
38.4k
Format
NO
NC
Access Port
Power
On Off
DO1
DO2
DO3
DO4
Gnd
AO2
2Gnd
AO1
Gnd
AO3
Gnd
AO4
Gnd
AO5
Gnd
AO6
A
A
A
A
A
A
A
A
A
A
B
B
B
B
B
B
B
B
B
B
IN1
IN10
IN2
IN3
IN4
IN5
IN6
IN7
IN8
IN9
Universal Input Mode Select
0-5Vdc Thermistor/ dry-contact
0-20 mA
38.4k
1 2 3 4 O N
0 1 2
9 0 1 2
M4106NX
Shield
Cmnet Baud
Inputs 5V Max, 20mA Max
SF S/S
5-0-DO01
RF S/S
5-0-DO02
Spare
5-0-DO03
Spare
5-0-DO04
SF VFD Speed
5-0-AO01
MA Damper
5-0-AO2 +
Relief Damper
5-0-AO3 +
RF VFD Speed
5-0-AO04
HC Valve
5-0-AO5 +
Spare
5-0-AO06
#5
AHU 3-1
Gnd 24 Vac
Access Port
Class 2 24Vac
50-60 Hz
20VA, 0.83A
Use Copper
Conductors Only
Caution:
To Reduce the Risk of Fire or Electrical Shock, Do Not interconnect the Outputs of Different Class 2 Circuits.
Format
BACnet Over ARCNET156 KBaud
TM
10's 1's Module Address
Auto Off On
Tx
Rx
Power On Off
Comm Select
ARC156CM
net
38.4k 9600
Baud Select
Net +
Net -
DO1
DO2
A
A
B
B
IN1
IN2
Error
Run Power
CONTROL MODULE
Universal Input Mode Select
0-5Vdc Thermistor/ dry-contact
0-20 mA
24V Max.
3A Max.
M220nx
0 1 2
9 0 1 2
9M220NX
Inputs 5V Max, 20mA Max
Shield
N/CCM
net
Use Single Class 2 Source Only
EF Status
6-0-DI1
EF Status
6-0-DI2
EF S/S
6-0-DO1
EF S/S
6-0-DO2
SF Status
5-0-DI1
RF Status
5-0-DI2
SA Temp
5-0-AI3
MA Temp
5-0-AI4
Freezestat
5-0-DI5
Duct Static
5-0-AI6+
Filter
5-0-AI7
RA Temp
5-0-AI8
Bldg Static
5-0-AI9+
Spare
5-0-UI10
#6
EF 3-1 & 3-2
Bill of Materials
DID DESCRIPTION MANUFACTURER PART NUMBER QTY
M220nx M220NX AUTOMATED LOGIC M220NX 1 ea M4106nx M4106NX AUTOMATED LOGIC M4106NX 1 ea
AHU 3-1 Control
Specification Section 15900
Juneau, AK ANM-JRD Facilities Phase I & II
Checked by: EP
Engineer: DMD
AHU 3-1 Control
Filter
5-0-AI7
- O +
B W R
ADPA-DH
LOHI
OAREF
LO
HI
- O +
B W R
ADPA-PL
SPP
Bldg Static
5-0-AI9
RA
RF
W B
RA Temp
5-0-AI8
CV-2
1 2 3
Relief Damper
5-0-AO3
NC
R W B
EA
B W R
SA Temp
5-0-AI3
Freezestat
5-0-DI5
MA Temp
5-0-AI4
HC Valve
5-0-AO5
W B
DTSA-24
HC
R B
W B
SF
HWR HWS
DA
W B
DTSP-12
DA
LO
HI
- O +
B W R
ADPA-DH
Duct Static
5-0-AI6
W B
SF S/S
5-0-DO1
SF VFD Fault
29-0-DI1
SF VFD Speed
5-0-AO1
SF
VFD SF Status
5-0-DI1
OA
NO
NC
LTDT-A
AEM-140
W B
RF S/S
5-0-DO2
RF VFD Fault
29-0-DI2
RF VFD Speed
5-0-AO4
RF
VFD RF Status
5-0-DI2
1 2 8
MA Damper
5-0-AO2
B W R
AEM-140
Lin ka ge
DTSP-12
1 Building Static Pressure Sensor to be located in mechanical room.
W B W B W B
A
B
AB
Bill of Materials
DID DESCRIPTION MANUFACTURER PART NUMBER QTY
ADPA-DH AIR DIFF PRESS. ANALOG DUCT MOUNT, 0-10 IN. W.C. ALTA LABS PXDXX02S 2 ea ADPA-PL AIR DIFF PRESS. ANALOG PANEL MOUNT, 0-1 IN. W.C. ALTA LABS PXPXX01S 1 ea AEM-140 ACTUATOR ELEC., MOD, 24V, SR, 0-10V, 140 IN. LB DELTA DCMS24-140 2 ea CV-2 AHU-1 HEATING COIL GLOBE VALVE 1 1/2 IN., 3 WAY DELTA ST150-3-24DCMS24-62 1 ea DTSA-24 DUCT TEMP SENSOR AVERAGING, THERMISTOR, 24' ELEMEN BAPI ALC/10K-2-A-24-EU 1 ea DTSP-12 DUCT TEMP SENSOR POINT, 12 IN. BAPI ALC/10K-2-D-12-EU 2 ea LTDT-A LOW TEMP DETECT, AUTO RESET, SPDT SIEMENS 134-1510 1 ea OAREF OUTSIDE AIR PRESSURE, REFERENCE HEAD DWYER A306 1 ea SPP STATIC PRESSURE PICKUP BAPI ZPSACC01 1 ea
W B W B W B
EF 3-1 & 3-2 Control
Specification Section 15900
Juneau, AK ANM-JRD Facilities Phase I & II
Checked by: EP
Engineer: DMD
EF 3-1 & 3-2 Control
EF 3-2
EF
EAEA NC
AE2PL-62A
EF S/S
6-0-DO2
2 1
W B EF Status
6-0-DI2
N
W B
C
RE/CSRE
Auto
STARTER
EF 3-1
EF
EAEA NC
AE2PL-62A
EF S/S
6-0-DO1
2 1
W B EF Status
6-0-DI1
N
1 W B
C
RE/CSRE
Auto
STARTER
Bill of Materials
DID DESCRIPTION MANUFACTURER PART NUMBER QTY
AE2PL-62A ACTUATOR ELECTRIC, 2-POS, 24V, SR, 62 IN. LB DELTA DCS24-62A 2 ea RE/CSRE RELAY-CURRENT SENSOR EXTERNAL CT FUNCTIONAL DEVICES RIBXLSRA 2 ea
EF 3-3 Control
Specification Section 15900
Juneau, AK ANM-JRD Facilities Phase I & II
Checked by: EP
Engineer: DMD
EF 3-3 Control
EF
EAEA NC
AE2PL-62A
EF S/S
30-0-DO1
2 1
W B
N H
120 VAC
N
24 VAC
From XFMR
T-
T+ CmNet out to next Device 7
W B Sh
W B Sh
CmNet in
B R
EF S/S
30-0-DO1 1T- B
W T+
#30
EF 3-3
CAUTION:
This product was designed to be mounted inside the building envelope. Warranty voided if mounted outside.
Power for D.O.'s
DO-2
DO-1
BUSS
Pwr
BACnet
7 8 9
6 7 8 9
7 8 9
6 7 8 9
Rx
Tx
Bias
Net +
Net -
Shield
C M ne t
Te ns
O ne s
Batt
CR
Sense +12V Rnet- Rnet+ Gnd
Gnd
R ne tRnet +
Rnet -
+12V
IN-1
Gnd
IN-2
Gnd
Inputs: 5V Max
Class 2 24 Vac, 50-60 Hz
20VA, 0.83A
24Vdc, 0.2A, 5W
Use Copper Conductors Only
Ground
24 Vac
Run
Err
ZN220
CONTROLLER
Thermistor/dry contact 0-5Vdc
IN-1
Thermistor/dry contact 0-5Vdc
IN-2
O N
On
MSTP Baud
Communications Selection
9600 19.2k 38.4k 76.8k
MSTP
ARC156
CAUTION:
To Reduce the Risk of Fire or Electric Shock, Do Not Interconnect the Outputs of Different Class 2 Circuits.
Jumper: Gain1
Format
Lstat Rnet
ZN220
RE
C
G nd
R ne t+ R ne t-
+1 2V
1 2 3 4
B W G R
B W G R
RS
AUTOMATED LOGIC
Thermostat Location ZCard
Address Zcard Type Coil/FT/CUH/RP Sensor Type
Device VA Draw
Servered by
Equipment
Device installation location XFMR # RM A-115 30 ZN220 n/a Blank Plate 20 VA EF3-4
Z Card Schedule
Bill of Materials
DID DESCRIPTION MANUFACTURER PART NUMBER QTY
AE2PL-62A ACTUATOR ELECTRIC, 2-POS, 24V, SR, 62 IN. LB DELTA DCS24-62A 1 ea RE RELAY-SPDT FUNCTIONAL DEVICES RIBTU1C 1 ea RS RS STANDARD SPACE TEMPERATURE ALC RS 1 ea ZN220 ZN220 AUTOMATED LOGIC ZN220 4 ea
Zone Control - FTU VAV Box
Specification Section 15900
Juneau, AK ANM-JRD Facilities Phase I & II
Checked by: EP
Engineer: DMD
Zone Control - FTU VAV Box
Thermostat Location ZCard
Address Zcard Type Coil/FT/CUH/RP Sensor Type
Device VA Draw
Served by Equipment
RM A-101 7 ZN341V+ DHC-1 Blank Plate 20 VA FTU-1 RM A101-A 8 ZN341V+ DHC-2 RS Pro 20 VA FTU-2 RM A-103 9 ZN341V+ DHC-3 RS Pro 20 VA FTU-3 RM A-106 10 ZN341V+ DHC-4 RS Pro 20 VA FTU-4 RM A-120 11 ZN341V+ DHC-5 RS Pro 20 VA FTU-5 RM A-122A 12 ZN341V+ DHC-6 RS Pro 20 VA FTU-6 RM A-122 13 ZN341V+ DHC-7 RS Pro 20 VA FTU-7 RM A-124 14 ZN341V+ DHC-8 RS Pro 20 VA FTU-8 RM A-125 15 ZN341V+ DHC-9 RS Pro 20 VA FTU-9 RM A-126 16 ZN341V+ DHC-10 RS Pro 20 VA FTU-10 RM A-128 17 ZN341V+ DHC-11 RS Pro 20 VA FTU-11 RM A-129 18 ZN341V+ DHC-12 RS Pro 20 VA FTU-12 RM A-112 19 ZN341V+ DHC-13 RS Pro 20 VA FTU-13 RM A-201South 20 ZN341V+ DHC-14 RS Pro 20 VA FTU-14 RM A-201North 21 ZN341V+ DHC-15 RS Pro 21 VA FTU-15 RM A-202 22 ZN341V+ DHC-16 RS Pro 22 VA FTU-16 RM A-203 23 ZN341V+ DHC-17 RS Pro 23 VA FTU-17 RM A-207 24 ZN341V+ DHC-18 RS Pro 24 VA FTU-18 RM A-216 25 ZN341V+ DHC-19 RS Pro 25 VA FTU-19 RM A-215 26 ZN341V+ DHC-20 RS Pro 26 VA FTU-20 RM A-214 27 ZN341V+ DHC-21 RS Pro 27 VA FTU-21 RM A-210South 28 ZN341V+ DHC-22 RS Pro 28 VA FTU-22
Z Card Schedule
Typ. of 22
Note! Manufacturer wire colors differ from MSI standards!
Cable Black
Red White
Actuator White Red Black terminates to:
Rnet+
D O
-3
P ow er fo r D .O
.s
BU
S
D O
-1
D O
-2
AO
-1
G nd
Analog Output
G nd
IN
-2
IN
-1
G nd
IN
-3
G nd
IN
-4
LE
D
G nd
R ne t +
R ne t -
+1 2V
R n e t CMnet
N et
N et
Sh ie ld
G ro un d
V ac
Power
Batt
CR2032
10's
1's
9 6
9 6
Therm/dry 0-5VdcIN-2
IN-1
Format
Rnet LogiStat
ARC156
MSTP
High (with filter)
Low
Flow
Outputs 24V Max, 1A Max
Conductors Only
Class 2
Use Copper 26Vdc, 0.1A, 3W
14VA, 0.58A
24Vac, 50-60 Hz Sense
+12V Rnet-
Gnd
BACnet ®
Inputs 1 & 2 0-5V, therm, dry
Inputs 3 & 4 Therm, dry
AO: 0-10 Vdc 5mA Max
Local Access
LStat/ZASF
Short pins LStat = or IN-3 =
B T4
LogiStat/IN3 & 4
ZASF
CW CCW
Motor
Error
Run
Power
Therm/dry 0-5Vdc
Made in USA
PortInputs
TxRx
MSTP Baud
76.8k38.4k19.2k9600
U.S. Patent No. 6,715,690 B2
CAUTION:
This product was designed to be mounted inside the building envelope. Warranty voided if mounted outside.
ZN341v+
On
CAUTION:
To Reduce the Risk of Fire or Electric Shock, Do Not Interconnect the Outputs of Different Class 2 Circuits.
Damper release button inside
24 VAC
From XFMR
B W Sh SA DA T-
T+
T+
T-
R B W
W B
CmNet out to next Device
B W Sh
B W Sh
CmNet in
R
DTSP-4
DA Temp 3
HW Valve1
R B
W B
ZN341V+
T-SF S/S2
DA Temp3
H L
SF HC
B W G R
Gnd Rnet+ Rnet-
+12V MANUAL ON WARMER
INFO COOLER
AUTOMATED LOGIC
RSP
B W G R
HW Valve1 Ccw
Com
Cw
Ground
HW Valve (close)
HW Valve (open)
W
B
R
HWR HWS
W B
C
PAM-1
VF ST/STP 2
120 VAC
N H
Typ. of 22
Typ. of 22
W B
RA
Bill of Materials
DID DESCRIPTION MANUFACTURER PART NUMBER QTY
DTSP-4 DUCT TEMP SENSOR POINT, 4 IN. BAPI ALC/10K-2-D-4 - NB10-PL 22 ea PAM-1 SP/ST KELE PAM-1 22 ea RSP RS PRO STANDARD SPACE TEMPERATURE W/LCD ALC RSP 22 ea ZN341V+ VAV CONTROLLER 3DO,4UI,1AO W/ACTUATOR, FLOW SENSOR AUTOMATED LOGIC ZN341V+ 22 ea
Zone Control - FTU VAV Box w/SP
Specification Section 15900
Juneau, AK ANM-JRD Facilities Phase I & II
Checked by: EP
Engineer: DMD
Zone Control - FTU VAV Box w/SP
LO
HI
- O +
B W R
ADPA-PL
Note! Manufacturer wire colors differ from MSI standards!
Cable Black
Red White
Actuator White Red Black terminates to:
Rnet+
D O
-3
P ow er fo r D .O
.s
BU
S D
O -1
D O
-2
AO
-1
G nd
Analog Output
G nd
IN
-2
IN
-1
G nd
IN
-3
G nd
IN
-4
LE
D
G nd
R ne t +
R ne t -
+1 2V
R n e t CMnet
N et
N et
Sh ie ld
G ro un d
V ac
Power
Batt
CR2032
10's
1's
9 6
9 6
Therm/dry 0-5VdcIN-2
IN-1
Format
Rnet LogiStat
ARC156
MSTP
High (with filter)
Low
Flow
Outputs 24V Max, 1A Max
Conductors Only
Class 2
Use Copper 26Vdc, 0.1A, 3W
14VA, 0.58A
24Vac, 50-60 Hz Sense
+12V Rnet-
Gnd
BACnet ®
Inputs 1 & 2 0-5V, therm, dry
Inputs 3 & 4 Therm, dry
AO: 0-10 Vdc 5mA Max
Local Access
LStat/ZASF
Short pins LStat = or IN-3 =
BT
LogiStat/IN3 & 4
ZASF
CW CCW
Motor
Error
Run
Power
Therm/dry 0-5Vdc
Made in USA
PortInputs
TxRx
MSTP Baud
76.8k38.4k19.2k9600
U.S. Patent No. 6,715,690 B2
CAUTION:
This product was designed to be mounted inside the building envelope. Warranty voided if mounted outside.
ZN341v+
On
CAUTION:
To Reduce the Risk of Fire or Electric Shock, Do Not Interconnect the Outputs of Different Class 2 Circuits.
Damper release button inside
24 VAC
From XFMR
B W Sh
SA DA
T- T+
T+
T-
R B W
CmNet out to next Device
B W Sh
B W Sh
CmNet in
R
DTSP-4
DA Temp 3
HW Valve1
R B
W B
ZN341V+
T-SF S/S2
DA Temp3
H L
SF HC
B W G R
Gnd Rnet+ Rnet-
+12V MANUAL ON WARMER
INFO COOLER
AUTOMATED LOGIC
RSP
B W G R
HW Valve1 Ccw
Com
Cw
Ground
HW Valve (close)
HW Valve (open)
W
B
R
HWR HWS
W B
C
PAM-1
N H
120 VAC
W B
W B
T+
SPP
RA
W B R
Space Pressure4
T+
W B R
RA Damper5
RAEA
1 2 8
R B W
AEM-62
Thermostat Location ZCard
Address Zcard Type Coil/FT/CUH/RP Sensor Type
Device VA Draw
Served by Equipment
RM A-210North 29 ZN341V+ DHC-23 RS Pro 29 VA FTU-23
Z Card Schedule
1 Building Static Pressure Sensor is located in Rm 210
SF S/S 2
Space Pressure4 RA Damper5
Bill of Materials
DID DESCRIPTION MANUFACTURER PART NUMBER QTY
ADPA-PL AIR DIFF PRESS. ANALOG PANEL MOUNT, 0-1 IN. W.C. ALTA LABS PXPXX01S 1 ea AEM-62 ACTUATOR ELEC., MOD, 24V, SR, 0-10V, 62 IN. LB DELTA DCMS24-62 1 ea DTSP-4 DUCT TEMP SENSOR POINT, 4 IN. BAPI ALC/10K-2-D-4 - NB10-PL 1 ea PAM-1 SP/ST KELE PAM-1 1 ea RSP RS PRO STANDARD SPACE TEMPERATURE W/LCD ALC RSP 1 ea SPP STATIC PRESSURE PICKUP BAPI ZPSACC01 1 ea ZN341V+ VAV CONTROLLER 3DO,4UI,1AO W/ACTUATOR, FLOW SENSOR AUTOMATED LOGIC ZN341V+ 1 ea
Misc. Non-DDC Controls
Specification Section 15900
Juneau, AK ANM-JRD Facilities Phase I & II
Checked by: EP
Engineer: DMD
Misc. Non-DDC Controls
UH 3-1 Control CUH 3-1 Control
CUH
Motor
SA
HW
HWS HWR
HWS
HWR
LVT LVT
120 V H
N 120 V
H
N
EA RAEF
120 V H
N
EF 3-4 Control
AE2PH-62A 4 3
RE
C
AC-1 Condenser Fan
SF
N H
120 VAC
Bill of Materials
DID DESCRIPTION MANUFACTURER PART NUMBER QTY
AE2PH-62a ACTUATOR ELECTRIC, 2-POS, 120V, SR, 62 IN. LB, W/END SWITCH DELTA DCS120-62A 1 ea LVT LINE VOLTAGE THERMOSTAT COLUMBUS ETD5-S-1S 2 ea
ANM-JRD Admin Facility
HVAC Controls Sequence of Operation
Boiler Control
Boiler System - Run Conditions:
Boiler Circulation Pump CP 3-4 will be enabled whenever there is a call for heat from any DDC monitored equipment at the AMN-JRD Facility or the outside air is less than 50°F (adj.). After CP 3-4 has been enabled for 5 minutes (adj.) the boiler will be enabled to run on its internal operating circuit and safeties.
To prevent short cycling, the Boiler and circulation pump will run for and be off for minimum adjustable times (both user definable), unless shutdown on safeties or outside air conditions.
Alarms will be provided as follows:
• Boiler Failure: Commanded on, but the status is off.
• Boiler Running in Hand: Commanded off, but the status is on.
• Hot Water Pump 3 o Failure: Commanded on, but the status is off.
o Running in Hand: Commanded off, but the status is on.
Primary Hot Water Temperature Monitoring:
The following temperatures will be monitored:
• Primary hot water supply.
Alarms will be provided as follows:
• High Primary Hot Water Supply Temp: If greater than 200°F (adj.).
• Low Primary Hot Water Supply Temp: If less than 100°F (adj.).
System Pressure Monitor:
The sensor will measure hot water return pressure and alarms will be provided as follows:
• Low Hot Water Return Pressure: If the hot water return water pressure is less than 8lbf/in2 (adj.).
Heat Exchanger Control
Heating Glycol System - Run Conditions:
The Heating Glycol system pumps will be enabled whenever there is a call for heat from any DDC monitored equipment at the AMN-JRD Facility or the outside air is less than 50°F (adj.).
Heating Glycol Pump Lead/Standby Operation:
The two heating glycol pumps will operate in a lead/standby fashion.
• The lead pump will run first.
• On failure of the lead pump, the standby pump will run and the lead pump will turn off.
• The designated lead pump will rotate each time the system is started or on a scheduled basis.
Alarms will be provided as follows:
• Heating Glycol Pump 1 & 2 o Failure: Commanded on, but the status is off.
o Running in Hand: Commanded off, but the status is on.
o Runtime Exceeded: Status runtime exceeds a user definable limit.
Heating Glycol Return Temperature Setpoint Reset:
The heating glycol return temperature setpoint will reset based on outside air temperature.
As outside air temperature rises from 0°F (adj.) to 60°F (adj.) the glycol return temperature setpoint will reset downwards from 180°F (adj.) to 120°F (adj.).
Alarms will be provided as follows:
• High Heating Glycol Return Temp: If greater than 200°F (adj.).
• Low Heating Glycol Return Temp: If less than 100°F (adj.).
Heat Exchanger 3-Way Valve Control:
The controller will measure the heating glycol return temperature and modulate the 3-way diverting valve to maintain its setpoint.
System Pressure Monitor:
The sensor will measure heating glycol return pressure and alarms will be provided as follows:
• Low Heating Glycol Return Pressure: If the heating glycol return…