Summary of ANM-JRD Compound HVAC Modernization Construction Drawings

This document set comprises architectural and mechanical construction drawings for the ANM-JRD Compound HVAC Modernization project located at the Juneau Ranger District of Tongass National Forest in Alaska. The project, prepared by Alaska Energy Engineering LLC under registered professional engineer James A. Rehfeldt (ME-8987), includes comprehensive specifications for heating system upgrades, direct bury piping installation, and digital direct control (DDC) system implementation across three buildings: the Office Building, Warehouse Building, and Storage Building.

The heating system (M601) replacement includes two concrete pad-mounted boilers (B-1 and B-2) connected to existing heat sink/heat recovery piping serving all three buildings at specified flow rates (72 GPM to Storage, 28 GPM to Warehouse, 72 GPM to Office). The project incorporates 2-inch and 1.5-inch heat source/heat recovery direct bury piping with expansion loops, eight boreholes for loopfield installation, wall penetrations, and anchors per manufacturer specifications. Control infrastructure (M702) requires installation of DDC conductors, CAT6 cables, and conduit routing between three control panels (PNL-3 in Office Building, PNL-1 in Warehouse, PNL-2 in Storage Building). The warehouse and storage building controls include supply fan sequencing with temperature reset, low-limit safeties set at 38°F, occupied/unoccupied mode scheduling, CO and NO2 monitoring sensors with alarm thresholds, exhaust fan control tied to humidity and air quality parameters, and energy metering with 5-minute interval archiving. All work must comply with utility locate requirements, record drawings, and manufacturer installation instructions, with pipe insulation repair required where balance valves are replaced.

View the file

Other files for this federal contract opportunity

Show all 18

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

STORAGE BUILDING LOOPFIELDEIGHT BOREHOLES,

DIRECT BURY 2" HS/HR [1] [2]

4/M203

DIRECT BURY 3" HS/HR [1] [2]

4/M203

EXPANSION LOOPS [3]

ROUTE HS/HR UNDER

SLAB 3/M203

WALL PENETRATION 2/M203

DIRECT BURY PIPING

ANCHOR 5/M203

1/M304

1/M501

1/M401

ROUTE HS/HR UNDER

SLAB 3/M203

DIRECT BURY PIPING

ANCHOR 5/M203

PROVIDE DDC CONTROL

CONDUCTORS [4]

DATENO.

REVISION / ISSUE

(R10)

ALASKA REGION

06.20.2025

Alaska

ENGINEERING LLC

25200 Amalga Harbor Phone: 907-789-1226 Juneau, Alaska 99801 jim@alaskaenergy.us

Energy

JR

JR / KB

JR

James A. Rehfeldt

ME-8987

R EGIS T ER E D PR O FE S S IO NA L ENGINEER

NOTE: 11"x 17" PRINT IS HALF SIZE

TONGASS NATIONAL

FOREST

JUNEAU RANGER DISTRICT

M202

SITE PLAN

ANM-JRD

COMPOUND

HVAC

MODERNIZATION

FOR

CONSTRUCTION

06/20/2025

DRAWING NOTES

[1] Locate the direct bury piping along the same routing as the existing piping. Refill excavations to allow vehicle use when work is not occurring.

[2] Install direct bury piping per manufacturer's instructions.

[3] Expansion loops sized by piping manufacturer. Install per manufacturer's instructions.

[4] Install control conduit and CAT6 cables from PNL-3 in the

Office Building to PNL-1 in the Warehouse and from PNL-1 to PNL-2 in the Storage Building. Install conduits in piping trench as detailed in the Civil Drawings and route through building as required.

GENERAL NOTES

· Refer to the record drawings for information on site utilities.

· Provide utility locates prior to excavation.

N

SITE PLAN

SCALE: 0 80'20' 40'M202

ADDENDUM 2 3-18-26

DN

UP

DN

RE

F

VENDVEND

RE

F

CORR.

A-211

ENTRY

A-207

RECREATION

A-201

JAN.

A-204

SECURITY

A-208

OFFICE

A-203A

MEN

A-206

CORR.

A-217

STAIR

A-218

FISH & WILDLIFE

A-216

OFFICE

A-216A

ENGINEERING

A-215

MINERALS

A-202

REC.

OFF.

A-201A

OFFICE

A-202A

MECHANICAL

SHAFT

SPECIAL USES

A-203

WOMEN

A-205

ELEV.

A-110

STAIR

A-213

RANGER

A-214

CORR.

A-212

LUNCH

A-209

CONF.

A-210

FEC

FEC

1 2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

(E) FTU-18

[1]

DATENO.

REVISION / ISSUE

(R10)

ALASKA REGION

06.20.2025

Alaska

ENGINEERING LLC

25200 Amalga Harbor Phone: 907-789-1226 Juneau, Alaska 99801 jim@alaskaenergy.us

Energy

JR

JR / KB

JR

James A. Rehfeldt

ME-8987

R EG IS T ER ED PR O FE S S IO NA L ENGINEER

NOTE: 11"x 17" PRINT IS HALF SIZE

TONGASS NATIONAL

FOREST

JUNEAU RANGER DISTRICT

M304

OFFICE BUILDING

SECOND FLOOR PLAN

ANM-JRD

COMPOUND

HVAC

MODERNIZATION

FOR

CONSTRUCTION

06/20/2025

4'SCALE: 0 1' 2'

N

OFFICE BUILDING SECOND FLOOR PLAN

4'SCALE: 0 16'8'

N

DRAWING NOTES

(1) Replace two balance valves 2/M801. Update DDC control sequence 3/M701.

General Notes

· Refer to the Record Drawings for balance valve replacement piping diagrams.

· Repair pipe insulation where balance valves are replaced. Match existing insulation.

M304

1 2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

DN

UP

DN

1 2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

(E) AHU3-1

[2]

(E) EF3-1

[4]

(E) EF3-2

[4]

(E) REF3-1

[3]

(E) FTU-15

[1]

(E) FTU-14

[1]

(E) FTU-16

[1]

(E) FTU-19

[1]

(E) FTU-17

[1]

(E) FTU-20

[1]

DN

1 2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

(E) FTU-22

[1]

(E) FTU-23

[1]

(E) FTU-21

[1]

DATENO.

REVISION / ISSUE

(R10)

ALASKA REGION

06.20.2025

Alaska

ENGINEERING LLC

25200 Amalga Harbor Phone: 907-789-1226 Juneau, Alaska 99801 jim@alaskaenergy.us

Energy

JR

JR / KB

JR

James A. Rehfeldt

ME-8987

R EG IS T ER ED PR O FE S S IO NA L ENGINEER

NOTE: 11"x 17" PRINT IS HALF SIZE

TONGASS NATIONAL

FOREST

JUNEAU RANGER DISTRICT

M305

OFFICE BUILDING ATTIC

PLAN

ANM-JRD

COMPOUND

HVAC

MODERNIZATION

FOR

CONSTRUCTION

06/20/2025

4'SCALE: 0 1' 2'

N

OFFICE BUILDING ATTIC PLAN

4'SCALE: 0 16'8'

N

DRAWING NOTES

[1] Replace two balance valves 2/M801. Update DDC control sequence 3/M701.

[2] Replace three balance valves 1/M801. Update DDC control sequence 2/M701.

[3] Update DDC control sequence 2/M701.

[4] Update DDC control sequence 4/M701.

GENERAL NOTES

· Refer to the Record Drawings for balance valve replacement piping diagrams.

· Repair pipe insulation where balance valves are replaced. Match existing insulation.M305

DATENO.

REVISION / ISSUE

(R10)

ALASKA REGION

06.20.2025

Alaska

ENGINEERING LLC

25200 Amalga Harbor Phone: 907-789-1226 Juneau, Alaska 99801 jim@alaskaenergy.us

Energy

JR

JR / KB

JR

James A. Rehfeldt

ME-8987

R EG IS T ER ED PR O FE S S IO NA L ENGINEER

NOTE: 11"x 17" PRINT IS HALF SIZE

TONGASS NATIONAL

FOREST

JUNEAU RANGER DISTRICT

M601

HEATING SYSTEM

DIAGRAM

ANM-JRD

COMPOUND

HVAC

MODERNIZATION

FOR

CONSTRUCTION

06/20/2025

T

T

B-1

CONCRETE PAD

P-1

T

B-2

P-2

T

T

(R) AS-1

ET-1 P-3A P-3B

3 (E) 2-1/2

(E) 2-1/2

(E) 2" HS/HR

TO OFFICE BLDG

2ND/3RD FLOORS

(E) 1-1/2" HS/HR

TO OFFICE BLDG

1ST FLOOR

DIRECT BURY PIPING

SCALE: NONE

HEATING SYSTEM DIAGRAM

OFFICE BUILDING

(E) 1-1/2" HS/HR TO

STORAGE BLDG

REPLACE BALANCE

VALVE 21 GPM

WAREHOUSE BUILDING STORAGE BUILDING

2 2

(E) 2" HS/HR TO

WAREHOUSE BLDG

28 GPM

65 GPM

114 GPM

72 GPM

72 GPM

(E) 1/2SET AT

20 PSIG

1/2

P

T

F

T

FLOW METER [2]

BTU METER [1]

T

F

T

FLOW METER [2]

BTU METER [1]

1-1/2 1-1/2

BTU METER [1]

T

T

F

FLOW METER [2]

DRAWING NOTES

[1] Alternative #2: Provide Omicon System 10 BTU meter with temperature sensors. Install sensor in thermowell filled with thermo-conductive paste. Install per manufacturers recommendations. Provide control monitoring 5/M702.

[2] Alternative #2: Provide Omicon FT-3400 Flow Meter. Install with 24” of straight and unobstructed pipe upstream of meter and 12” downstream of meter. Install per manufacturers recommendations.

P

M601

1/2

1/2

(R) CHEMICAL

FEEDER

DRAWING NOTES

[1] Provide CO and NO2 monitoring sensor (ToxAlert TOXEC) mounted at the level of the existing overhead lighting. Configure sensors for DDC monitoring of gas concentration level.

DATENO.

REVISION / ISSUE

(R10)

ALASKA REGION

06.20.2025

Alaska

ENGINEERING LLC

25200 Amalga Harbor Phone: 907-789-1226 Juneau, Alaska 99801 jim@alaskaenergy.us

Energy

JR

JR / KB

JR

James A. Rehfeldt

ME-8987

REG IST ER ED P R O FE S S IO NA L ENGINEER

NOTE: 11"x 17" PRINT IS HALF SIZE

TONGASS NATIONAL

FOREST

JUNEAU RANGER DISTRICT

M702

WAREHOUSE AND

STORAGE BUILDING

CONTROLS

ANM-JRD

COMPOUND

HVAC

MODERNIZATION

FOR

CONSTRUCTION

06/20/2025

(E) FILTER(E) OAD

(E) RAD

AO

AI

DA

T

(E) SUPPLY FAN

AO VA

T

AI

T

OUTSIDE

AIR

SUPPLY

AIR

(E)

(E)

(E)

(E)

HC

AIRAT

RETURN AIR

DO

C

AI

CS(E) (E) (E) (E)

(E)

A. Scope: Replace the existing DDC control, monitoring and alarm sequence with the following sequence.

B. Control

1. Supply Fan Controller: An existing magnetic starter supplies power to the fan motor.

a. Auto: Fan and system operate in accordance with the control sequence.

b. Hand: Fan and system operate in occupied mode.

c. Off: Fan is off and system is in unoccupied mode.

2. Safeties

a. Smoke/Fire Alarm (ASU-2 Only): When a fire alarm is activated at the fire alarm control panel, place the system in unoccupied mode.

b. Low Limit Thermostat: When the low limit temperature drops to 38℉, disable the fan, position the mixing dampers to full recirculation, and position the heating coil valve to fully open.

When the mixed air temperature rises to 50°F, automatically restore system operation. When the low limit control occurs three times in 24 hours, disable the system until manually reset.

3. Schedule: Schedule the system to operate in occupied and unoccupied modes.

4. Occupied Mode: Operate the system as follows.

a. Supply Fan: Enabled.

b. Supply Air Temperature Control

1) Supply Air Temperature Setpoint: Reset the setpoint with outside temperature as follows. Vary the setpoint linearly between the two control points.

a) Tosa<20°F, Tsa = 72°F

b) Tosa>60°F, Tsa=60°F

2) Warm Up: When the system enters occupied mode, position the dampers to the full recirculation position until the return air temperature reaches 68℉.

3) Normal: Sequentially modulate the mixing dampers and heating coil valve to maintain the supply air temperature setpoint.

a) Maintain a minimum mixed air temperature of 45°F.

b) Maintain a minimum outside airflow of 1,200 cfm as set by the TAB contractor with the FTU supply air dampers set to the minimum position.

5. Unoccupied Mode: Operate the system as follows.

a. Supply Fan: Disabled.

b. Dampers: Full recirculation position.

c. Heating Coil: Disabled.

B. Display and Monitoring: Provide a graphic display of the system and points. Archive all points at 5-minute intervals.

C. Alarms

1. Critical

a. Supply Fan: Activate when the fan status differs from command.

b. Low Limit: Activate if system is disabled due to low limit control.

2. Non-critical

a. Supply Air Temperature: Activate after the system has been in occupied mode 15 minutes and the supply air temperature differs from the setpoint by 5°F for 30 minutes.

b. Filter Alarm: Activate when the filter differential pressure exceeds 0.25" w.g.

c. Low Limit: Activate if a low limit safety occurs.

D. Trend Reports

1. Fans: Supply fan command; Supply fan status

2. Temperature: Outside air temperature; Room temperature setpoint, Room temperature; Supply air setpoint; Supply air temperature; Outside air damper position, Heating coil valve position.

A. Scope: Replace the existing DDC control, monitoring and alarm sequence with the following sequence.

B. Controller: A manual starter supplies power to the fan motor.

C. Control

1. Occupied Mode: When HV-1 is in normal occupied mode, enable the exhaust fan.

2. Unoccupied and Warmup Mode: When AHU3-1 is in unoccupied or warmup mode, disable the exhaust fan.

D. Display and Monitoring: Display and archive all points shown on the control diagram.

E. Alarms

1. Non-critical

a. Activate when the exhaust fan status differs from the command.

F. Exhaust Fan Trend Report: Fan command; Fan status

C

T

CH3-1

120VHS / HR

(E)

A. Control: Enable the fan when the room temperature is below the setpoint.

The heating coil has continuous flow.

B. Display and Monitoring: Display and archive all points shown on the control diagram.

(E)

DA C

C0-NO2 C0-NO2

H

DA C

DAT

(E) (E)

DO

(E) EF-2

AI AI

(E)

DO

(E) (E)

DO

(E) EF-1

(E)

(E) HC-1

AI

AO

A. Scope: Replace the existing DDC control, monitoring and alarm sequence with the following sequence.

B. Control

1. Enable EF-1 and EF-2 and Heating Coil HC-1 when any of the following occurs:

a. Humidity: Enable when building humidity level exceeds 60% for 5 minutes and disable when it is below 50% RH for 5 minutes.

b. Carbon Monoxide (CO): Enable when the CO level at any sensor exceeds 10 ppm for one minute and disable when CO level is below 5 ppm for 5 minutes.

c. Nitrogen Dioxide (NO2): Enable when the NO2 level at any sensor exceeds 5 ppm for one minute and enable when NO2 drops below 1 ppm for 5 minutes.

2. Heating Coil HC-1

a. Outside Temperature Above 32℉: When EF-1 or EF-2 is operating, open the outside air damper and modulate the control valve to maintain 50℉ supply air temperature.

b. Outside Temperature 32℉ of Below

1) When EF-1 and EF-2 are not operating, open the control valve to 30%.

2) When EF-1 or EF-2 is operating, modulate the control valve to maintain 50℉ supply air temperature.

3. Exhaust Fans EF-1 and EF-2: Open the respective exhaust air damper and enable the exhaust fan after the damper is fully open.

B. Display and Monitoring: Display and archive all points shown on the control diagram.

C. Alarms

1. Carbon Monoxide: Activate when the CO level exceeds 10 ppm for 5 minutes and provide an audio/visual alarm in the Storage Building.

2. Nitrogen Dioxide: Activate when the NO2 level exceeds 5 ppm for 5 minutes. and provide an audio/visual alarm in the Maintenance Bay.

D. Trend Reports: Collect the following points at 5-minute intervals

1. Air Quality

a. Relative Humidity

b. CO concentration

c. NO2 concentration

[1] [1]

(E)

DO

VA

HEATING / VENTILATING UNIT HV-1 CONTROL

EXHAUST FAN EF-3 AND EF-4 CONTROL

STORAGE BUILDING PURGE VENTILATION CONTROL

CABINET UNIT HEATER CH3-1 CONTROL

C

AI

CS

(E) EXHAUST FAN

(E) (E)

EXHAUST

AIR

EXHAUST

AIR

M702

M702

M702

M702

ADDENDUM 2 3-18-26

A. Scope: Monitor the heating supply and return flow and temperature to each building.

B. Display and Monitoring: Display and archive all points shown on the control diagram.

1. Sum monthly energy use for each building. Populate a 3-year table of monthly energy use for each building.

C. Trend Reports: Collect the following points at 5-minute intervals for each building.

1. Heating supply temperature (°F); heating return temperature (°F); flow rate (gpm), energy flow (MBH)

ENERGY METER CONTROL

M702

AO - THS

AO - THR

AO - GPM

AO - BTUH

BTU

METER

T

T

F