Design Automatic Dry Sprinkler System at YCC Mess Hall and Dorm Buildings
101, 102, & 103
Mammoth Hot Springs, Yellowstone National Park (YELL), WY
Calculations
Final Submittal Submitted: November 24, 2021
Ready to Advertise
Poole Fire Protection, Inc.
19910 West 161st Street Olathe, Kansas 66062 www.poolefire.com innovative leader trusted partner
NPS YELL YCC Dormitories and Mess Hall Sprinkler Replacement PPIMYELL42
A/E CONTRACT NO. 140P2120D0006 / ORDER NO. 140P1421F0168
THIS PAGE LEFT BLANK FOR DUPLEXING PURPOSES
PURPOSE
These calculations will establish the available water supply at the point of connection for each building included in this project by adjusting the hydrant flow test information for elevation differences between the test gauge location and the respective points of connection for each building.
ASSUMPTIONS
Original water supply available at the test gauge: Static = 39 psi, Residual = 25 psi, Flow = 1182 gpm Elevation of Test Gauge (on sprinkler riser in dormitory) = 6465 feet (Relative 0 ft) Elevation of Dormitory lead-in Point of Connection (POC) to main = 6454 feet (Relative -11 ft) Elevation of Mess Hall lead-in POC to main = 6447 feet (Relative -18 ft) There are 0.433 psi gained/lost per foot of elevation.
Lead-in piping remains a consistent depth of bury below grade (approximately 6 ft).
CALCULATIONS
Pressure change for Dormitory lead-in POC = 0.433 psi/ft * (-11 ft) = 4.763 psi gain Dormitory lead-in POC Static = 39 psi + 4.763 psi = 43.763 psi Dormitory lead-in POC Residual = 25 psi + 4.763 psi = 29.763 psi Dormitory lead-in POC Flow = 1182 gpm (no change)
Pressure change for Mess Hall lead-in POC = 0.433 psi/ft * (-18 ft) = 7.794 psi gain Mess Hall lead-in POC Static = 39 psi + 7.794 psi = 46.794 psi Mess Hall lead-in POC Residual = 25 psi + 7.794 psi = 32.794 psi Mess Hall lead-in POC Flow = 1182 gpm (no change)
CONCLUSIONS
Dormitory water supply available at the lead-in POC with the main: Static = 44 psi, Residual = 30 psi, Flow = 1182 gpm Mess Hall water supply available at the lead-in POC with the main: Static = 47 psi, Residual = 33 psi, Flow = 1182 gpm
Attachments
Copies: Owner A/E Contractor Consultants File
CALCULATIONS
Client National Park Service Calculated by Brad Austin, PE, CSP
Project Name Sprinkler Design YCC 101 102 103 Date November 2, 2021
Project # PF002240.05 Checked by Kevin Boyer, PE
Title Water Supply Adjustment Calculations Page 1 of 1
TEST GAUGE ON
SPRINKLER RISER
ELEV = 6465 FT
(estimated)
MESS HALL
LEAD-IN POC
ELEV = 6447 FT
(estimated)
GRADE OUTSIDE
DORMITORY
ELEV = 6460 FT
(from Google Earth)
DORMITORY
LEAD-IN POC
ELEV = 6454 FT
(estimated)
GRADE OUTSIDE
MESS HALL
ELEV = 6450 FT
(from Google Earth)
GRADE AT MESS
HALL LEAD-IN
POC
ELEV = 6453 FT
(from Google Earth) innovative leader trusted partner
Poole Fire Protection, Inc.
19910 West 161st Street Olathe, Kansas 66062 www.poolefire.com
Fire Hydrant Flow Test Report
Sprinkler Design YCC YCC Camp, Yellowstone Nat'l Park
Performed: 10/7/2021
FIRE HYDRANT FLOW TEST INSTRUCTIONS
Client 20211007
Signature Date
National Park Service Report Number Project Name Sprinkler Design YCC Signed By Brad Austin, PE Project #
INSTRUCTIONS:
4. After testing, transfer all hand written information compiled from the field into the excel worksheets.
Brad Austin, PE, CSP 10/7/2021
APPROVAL PRIOR TO TESTING
Flow test location and hydrants have been approved by:
2240.05
2 Print this sheet and complete the "Approval Prior to Testing " section by coordinating flow test location/hydrants with the project Engineer of Record or Technical Lead.
3. At the site, complete the other applicable portions of this report.
Date 10/7/2021 Location YCC Camp, Yellowstone Nat'l ParkPage
1. Prior to testing, review the "Guidelines for Hydrant Flow Testing and Reports" .
FIRE HYDRANT FLOW TEST INFORMATION
FIRE HYDRANT FLOW TEST INFORMATION
TABLES AND FIGURES
The Coefficient of Discharge, c, is different from the Pumper Outlet Coefficient. The Coefficient of Discharge is chosen using Figure 4.7.1. The Pumper Outlet Coefficient is based on the pitot pressure (velocity head) and selected from Table 4.8.2. Note also that the coefficient of discharge may be different depending on which flow testing diffusers are utilized during the test. If a diffuser is used, plug in the appropriate identifier for the diffuser rather than entering a coefficient of discharge number.
NFPA 291, Figure 4.7.1 - Three General Types of Hydrant Outlets and Their Coefficients of Discharge
NFPA 291, Table 4.8.2 - Pumper Outlet Coefficients
National Park Service Report Number Project Name Sprinkler Design YCC Signed By Brad Austin, PE Project # 2240.05 Date 10/7/2021 Location YCC Camp, Yellowstone Nat'l ParkPage
FIRE HYDRANT FLOW TEST INFORMATION
NOTES
The test was conducted using the Fire Riser located in the North Dormitory Building as the "test hydrant".
The existing system pressure gauge was replaced with calibrated gauge PFP179 for testing purposes.
The flow hydrant utilized two 2" Pitotless nozzles open to atmosphere using calibrated pressure gauges
PFP153 and PFP182.
Project # 2240.05 Date 10/7/2021 Location YCC Camp, Yellowstone Nat'l ParkPage
National Park Service Report Number Project Name Sprinkler Design YCC Signed By Brad Austin, PE
FIRE HYDRANT FLOW TEST REPORT
Gauges Used:
Static/Residual F2-2 F4-1 F5-P F1-1 F2-P F4-2 F6-1 F1-2 F3-1 F4-P F6-2 F1-P F3-2 F5-1 F6-P F2-1 F3-P F5-2
Consumption Rate During Test:
No
No
Underground Main fed by lake
YCC Camp, Yellowstone National Park Location:
Date:
Time:
Test Performed By:
Representative Of:
Water Purveyor Name and Contact Information:
Witness(es):
Purpose of Test:
Attachments (the following documents are attached to the end of this report):
Utility plan with hydrant ID (yes or no?)
National Park Service Sprinkler Design YCC
2240.05 YCC Camp, Yellowstone Nat'l Park
Brad Austin, PE 10/7/2021
Project Name
Location Project #
Report Number Signed By Date Page
GENERAL WATER FLOW TEST INFORMATION
4,408 Gallons
Thursday, October 7, 2021
0855 MT
Brad Austin & Zachary Parks
Poole Fire Protection
None
Establish available water supply for sprinkler system design.
Yellowstone National Park Service
Water quality analysis report (yes or no?)
Source of Water:
Water Quality Sample taken (yes or no?):
Do pumps affect test? If yes, indicate which pumps were operating:
PFP179
PFP153
Yes
No
PFP182
RESIDUAL HYDRANT [R] FLOW TEST INFORMATION
Location:
Elevation:
Static Pressure: DE = Dechlorination Unit
SWL = 2.5" Swivel Diffuser Residual Pressure: SWB = 4" Swivel Diffuser
HML = 1.125" Hose Monster HMM = 1.75" Hose Monster
FLOW HYDRANT [F] FLOW TEST INFORMATION HMB = 2.5" Hose Monster SS = Stream Straightener
Flow Hydrant 1 [F1] PNL = 1.75" Pitotless Nozzle with Little Hose Monster
Location: PNB = 2" Pitotless Nozzle with Little Hose Monster
Elevation:
Outlet
Pumper
Flow Hydrant 2 [F2] Location:
Elevation:
Outlet
Pumper
Flow Hydrant 3 [F3] Location:
Elevation:
Outlet
Pumper
PNOL = 1.75" Pitotless Nozzle Open to Atmosphere
PNOB = 2" Pitotless Nozzle Open to Atmosphere
Coeff. of Discharge , "c" Pitot (psi)
PNOB
PNOB
Project Name Sprinkler Design YCC Signed By Brad Austin, PE Project # 2240.05 Date 10/7/2021
Location YCC Camp, Yellowstone Nat'l ParkPage
National Park Service Report Number
Size (in.) Pumper Outlet Coeff.
Fire Riser in North Dormitory Mechanical Room
Relative 0 ft.
Hydrant north of north dormitory
Relative -10 ft.
Size (in.) Coeff. of Discharge , "c" Pitot (psi) Pumper Outlet Coeff.
Size (in.) Coeff. of Discharge , "c" Pitot (psi) Pumper Outlet Coeff.
Flow Hydrant 4 [F4] Location:
Elevation:
Outlet
Pumper
Flow Hydrant 5 [F5] Location:
Elevation:
Outlet
Pumper
Flow Hydrant 6 [F6] Location:
Elevation:
Outlet
Pumper
Flow Hydrant 7 [F7] Location:
Elevation:
Outlet
Pumper
National Park Service Report Number Project Name Sprinkler Design YCC Signed By Brad Austin, PE Project # 2240.05 Date 10/7/2021 Location YCC Camp, Yellowstone Nat'l ParkPage
Size (in.) Coeff. of Discharge , "c" Pitot (psi) Pumper Outlet Coeff.
Size (in.) Coeff. of Discharge , "c" Pitot (psi) Pumper Outlet Coeff.
Size (in.) Coeff. of Discharge , "c" Pitot (psi) Pumper Outlet Coeff.
Size (in.) Coeff. of Discharge , "c" Pitot (psi) Pumper Outlet Coeff.
FIRE HYDRANT FLOW TEST CALCULATION
Client Report Number Project Name Calculated By Project # Date
Location Page 1
PURPOSE
KNOWN DATA
Flow Hydrants d p c d p c p x
F1 2.00 12 PNOB2.00 13 0 0 0
F2 0.00 0 0 0.00 0 0 0 0
F3 0.00 0 0 0.00 0 0 0 0
F4 0.00 0 0 0.00 0 0 0 0
F5 0.00 0 0 0.00 0 0 0 0
F6 0.00 0 0 0.00 0 0 0 0
F7 0.00 0 0 0.00 0 0 0 0
CALCULATIONS
This calculation is based on NFPA 291, 2016 Edition.
Flow Calculation
Q=29.84cd2p1/2x (NFPA 291, Equation 4.7.3 & Section 4.8.2)
Q = discharge (gpm) c = coefficient of discharge d = diameter of the outlet (inches) p = pitot pressure or velocity head (psi) x = pumper outlet coefficient (if applicable)
Q2=[(S-20)0.54/(S-R)0.54]*Q1 (NFPA 291, Equation 4.10.1.2 & Section 4.10.1.2)
Q2 = discharge at 20 psi (gpm) S = static pressure (psi) R = residual pressure (psi) Q1 = discharge at R (gpm)
CONCLUSION
Available Water Supply:
Static: psi Residual: psi Flow: gpm gpm
0.00
0.00
0.00
National Park Service Sprinkler Design YCC
2240.05
YCC Camp, Yellowstone Nat'l Park
20211007
10/7/2021 Brad Austin, PE
1 of
Flow at 20 psi Residual:
1,394
Flow Available at 20 psi Residual Calculation
Outlet 1 Q
Outlet 2 Q
1,182 c
PNOB
The purpose of this calculation is to determine the water supply capabilities of the existing distribution system.
1,182 d Q
0.00 0 1,182
Subtotal Flow
0.00
0.00
Total Flow, Q:
Pumper
00 0 0 0.00 0
1,182
1,394 gpm @ psi gpm @ psi gpm @ psi
P re ss ur e (P
S I)
Flow (GPM)
FIRE HYDRANT FLOW TEST WATER SUPPLY GRAPH
Client Report Number Project Name Signed By Project # Date Location Page 1 of 1
National Park Service Sprinkler Design YCC
2240.05 YCC Camp, Yellowstone Nat'l Park
20211007 Brad Austin, PE
10/7/2021
Client Report Number Project Name Signed By Project # Date Location Page 1 of 1
National Park Service Sprinkler Design YCC
2240.05 YCC Camp, Yellowstone Nat'l Park
20211007 Brad Austin, PE
10/7/2021
STATIC/RESIDUAL
GAUGE PFP179
ON FIRE RISER
(STATIC: 39 psi, RESIDUAL: 25 psi)
FLOW HYDRANT
GAUGES PFP153
(12 psi) & PFP182 (13 psi)
THIS HYDRANT
FOUND TO BE
INOPERABLE.
Location: 101 102 103 YCC CAMP RD, YELLOWSTONE NATIONAL PARK, WY 82190
Project Name: SPRINKLER DESIGN YCC 101 102 103
Drawing Name: PF002240.05-F20_zparksLKHUF Calculation Date:11/22/2021
Hydraulic Calculations Summary for
Design
Light Hazard
1950 ft²
120 ft² (typical)
DORMITORY ATTIC LH
0.100 GPM/ft²
Remote Area Name:
Occupancy Classification:
Density
Area of Application:
Coverage per Sprinkler:
Type of Sprinklers Calculated:
No. of Sprinklers Calculated:
at Node:
Fire Protection Dry
N/AN/A
1100.000 GPM
286.1 galType of System:
In-rack Demand:
Hose Streams:
Volume of Dry or PreAction System:
at Node:
Type Allowance at Source
Total Water Required (including Hose Streams where applicable)
33.15 psi@385.137 GPMFROM: Water Supply at Node 1:
9.09 psiSafety Margin:
POOLE FIRE PROTECTION
BRITTON GRAY
19910 W 161ST ST, OLATHE KS 66062
913-829-8650 ZACHARY PARKS
Contact Name
Address:
Phone Number:
Authority Having Jurisdiction:
Name of Designer:
Automatic Peaking Results
Notes:
11/22/2021 Page 1AutoSPRINK RVT v2.2.27.0 3:57:40PMDORMITORY ATTIC LH@ M.E.P.CAD, Inc.
Hydraulic Graph
Water Supply
Node: 1
Job Name: SPRINKLER DESIGN YCC 101 102 103
Remote Area Name: DORMITORY ATTIC LH Date: 11/22/2021 N 1.85
Summary Sheet
No pressure is being required from the Source/Supply to meet the demand (by a margin of this negative value).
A negative result in Required Pressure indicates that the Pump is capable of furnishing all of the pressure required by the demand reported within this calculation.
11/22/2021 Page 1AutoSPRINK RVT v2.2.27.0 3:57:41PM@ M.E.P.CAD, Inc.
(GPM) (GPM) (K) (psi) (GPM/ft²)
Outflowing Devices Report Description: Light Hazard
Job Number: 2240.05
(ft²)Device
Actual Flow Minimum Flow K-Factor Pressure
Sprinkler 406 14.816 GPM 14.816 GPM 5.6 7.00 psi 0.123 GPM/ft² 120 ft²
Sprinkler 413 15.084 GPM 14.816 GPM 5.6 7.25 psi 0.126 GPM/ft² 120 ft²
Sprinkler 416 15.665 GPM 14.816 GPM 5.6 7.82 psi 0.131 GPM/ft² 120 ft²
Sprinkler 405 15.837 GPM 14.816 GPM 5.6 8.00 psi 0.132 GPM/ft² 120 ft²
Sprinkler 412 16.076 GPM 14.816 GPM 5.6 8.24 psi 0.134 GPM/ft² 120 ft²
Sprinkler 415 16.634 GPM 14.816 GPM 5.6 8.82 psi 0.139 GPM/ft² 120 ft²
Sprinkler 404 16.262 GPM 14.816 GPM 5.6 8.43 psi 0.136 GPM/ft² 120 ft²
Sprinkler 409 16.317 GPM 14.816 GPM 5.6 8.49 psi 0.136 GPM/ft² 120 ft²
Sprinkler 414 16.494 GPM 14.816 GPM 5.6 8.67 psi 0.137 GPM/ft² 120 ft²
Sprinkler 408 15.859 GPM 14.816 GPM 5.6 8.02 psi 0.132 GPM/ft² 120 ft²
Sprinkler 410 16.008 GPM 14.816 GPM 5.6 8.17 psi 0.133 GPM/ft² 120 ft²
Sprinkler 418 16.478 GPM 14.816 GPM 5.6 8.66 psi 0.137 GPM/ft² 120 ft²
Sprinkler 407 14.948 GPM 14.816 GPM 5.6 7.13 psi 0.125 GPM/ft² 120 ft²
Sprinkler 411 15.211 GPM 14.816 GPM 5.6 7.38 psi 0.127 GPM/ft² 120 ft²
Sprinkler 417 15.645 GPM 14.816 GPM 5.6 7.81 psi 0.130 GPM/ft² 120 ft²
Sprinkler 403 15.891 GPM 14.816 GPM 5.6 8.05 psi 0.132 GPM/ft² 120 ft²
Sprinkler 401 15.938 GPM 14.816 GPM 5.6 8.10 psi 0.133 GPM/ft² 120 ft²
Sprinkler 402 15.976 GPM 14.816 GPM 5.6 8.14 psi 0.133 GPM/ft² 120 ft²
Most Demanding Sprinkler Data
11/22/2021 Page 1AutoSPRINK RVT v2.2.27.0 3:57:41PM@ M.E.P.CAD, Inc.
Job Name: SPRINKLER DESIGN YCC 101 102 103
Remote Area Name: DORMITORY ATTIC LH Date: 11/22/2021
(psi) (psi)(GPM)(psi)(GPM)(psi)
Supply Analysis
Node Name Static Residual Flow Available Total Demand Required Pressure
30.00 psi1 33.15 psi385.137 GPM1182.000 GPM 42.24 psi44.00 psiWater Supply
Node Analysis
Discharge at
Node
(GPM)
Pressure at
Node
(psi)
Elevation (ft)Node Number Node Type Notes
12' - 1" 14.816 GPM7.00 psi Sprinklers
Coverage: 120 ft² Density: 0.123 GPM/ft²
12' - 1" 15.084 GPM7.25 psi Sprinklers
Coverage: 120 ft² Density: 0.126 GPM/ft²
12' - 1" 15.665 GPM7.82 psi Sprinklers
Coverage: 120 ft² Density: 0.131 GPM/ft²
10' - 0 1/2" 15.837 GPM8.00 psi Sprinklers
Coverage: 120 ft² Density: 0.132 GPM/ft²
10' - 1" 16.076 GPM8.24 psi Sprinklers
Coverage: 120 ft² Density: 0.134 GPM/ft²
10' - 1" 16.634 GPM8.82 psi Sprinklers
Coverage: 120 ft² Density: 0.139 GPM/ft²
14' - 1 1/2" 16.262 GPM8.43 psi Sprinklers
Coverage: 120 ft² Density: 0.136 GPM/ft²
14' - 1 1/2" 16.317 GPM8.49 psi Sprinklers
Coverage: 120 ft² Density: 0.136 GPM/ft²
14' - 1 1/2" 16.494 GPM8.67 psi Sprinklers
Coverage: 120 ft² Density: 0.137 GPM/ft²
9' - 10 1/2" 15.859 GPM8.02 psi Sprinklers
Coverage: 120 ft² Density: 0.132 GPM/ft²
9' - 11" 16.008 GPM8.17 psi Sprinklers
Coverage: 120 ft² Density: 0.133 GPM/ft²
9' - 10 1/2" 16.478 GPM8.66 psi Sprinklers
Coverage: 120 ft² Density: 0.137 GPM/ft²
12' - 1 3/4" 14.948 GPM7.13 psi Sprinklers
Coverage: 120 ft² Density: 0.125 GPM/ft²
11' - 11 3/4" 15.211 GPM7.38 psi Sprinklers
Coverage: 120 ft² Density: 0.127 GPM/ft²
12' - 0 1/2" 15.645 GPM7.81 psi Sprinklers
Coverage: 120 ft² Density: 0.130 GPM/ft²
9' - 11 1/4" 15.891 GPM8.05 psi Sprinklers
Coverage: 120 ft² Density: 0.132 GPM/ft²
9' - 11 1/4" 15.938 GPM8.10 psi Sprinklers
Coverage: 120 ft² Density: 0.133 GPM/ft²
9' - 9 3/4" 15.976 GPM8.14 psi Sprinklers
Coverage: 120 ft² Density: 0.133 GPM/ft²
-5' - 2 1/4" 285.137 GPM33.15 psi Supply
11/22/2021 Page 1AutoSPRINK RVT v2.2.27.0 3:57:42PM@ M.E.P.CAD, Inc.
Date: 11/22/2021
Remote Area Name: DORMITORY ATTIC LH
Flow added this step
Pipe Information
Node 1
Node 2
Elev 1 ft
Elev 2 ft
K-Factor
Q
Total Flow
Q
Nominal ID
Actual ID
Fittings &
Devices
Equiv.
Length ft
Length ft
Fitting ft
Total ft
C Factor or
Roughness
Pf Friction
Loss Per Unit psi
Total(Pt)
Elev(Pe)
Friction(Pf)
Notes
Fitting/Device (Equivalent Length)
Fixed Pressure Losses, when applicable, are added directly to (Pf) and shown as a negative value.
Velocity
3' - 6 3/4"
11' - 0 1/2" 4' - 8"
0.45 psi
0.49 psi
12' - 1" 1' - 1 1/4"
1.000
• • • • • Route 1 • • • • •
(See
Notes)
1.049
7.00 psi14.816 GPM
0.10 psi
Sprinkler,
14.816 GPM
5.6
T(3' - 6 3/4")
6 FPS
9' - 0 1/4" 6' - 5"
0.88 psi
0.18 psi
11' - 0 1/2" 6' - 5"
1.250
1.380
7.94 psi
0.03 psi14.816 GPM
3 FPS
4' - 3 1/4"
8' - 9 1/4" 5' - 0 1/2"
0.10 psi
0.53 psi
9' - 0 1/4" 0' - 9 1/4"
1.250 (See
Notes)
1.380
9.00 psi15.837 GPM
0.11 psi
Flow (q) from Route 7
30.653 GPM T(4' - 3 1/4")
7 FPS
8' - 9" 14' - 1"
0.01 psi
0.31 psi
8' - 9 1/4" 14' - 1"
2.500
2.469
9.63 psi29.617 GPM
0.02 psi
Flow (q) from Route 10
60.269 GPM
4 FPS
8' - 8 1/2" 14' - 1"
0.01 psi
0.66 psi
8' - 9" 14' - 1"
2.500
2.469
9.95 psi31.159 GPM
0.05 psi
Flow (q) from Route 3
91.428 GPM
6 FPS
12' - 10"
8' - 7 3/4" 48' - 9"
0.03 psi
4.00 psi
8' - 8 1/2" 35' - 11"
2.500 (See
Notes)
2.469
10.62 psi32.299 GPM
0.08 psi
Flow (q) from Route 6
123.727 GPM E(4' - 3 1/4"), T(8' - 6 3/4")
8 FPS
10' - 8 1/4"
8' - 7 1/4" 30' - 7 1/4"
0.01 psi
4.09 psi
8' - 7 3/4" 19' - 11"
3.000 (See
Notes)
3.068
14.66 psi161.409 GPM
0.13 psi
Flow (q) from Route 2
285.137 GPM T(10' - 8 1/4")
12 FPS
2' - 1 1/4" 6' - 6 1/4"
2.83 psi
4.75 psi
8' - 7 1/4" 6' - 6 1/4"
4.000 (See
Notes)
4.026
18.76 psi
0.04 psi285.137 GPM DPV(-0.52 psi), BOR, BFP(-4.
00 psi)
7 FPS
14' - 3"
-2' - 6 1/4" 41' - 4 1/2"
2.00 psi
1.47 psi
2' - 1 1/4" 27' - 1 1/4"
4.000 (See
Notes)
4.026
26.34 psi
0.04 psi285.137 GPM 2E(7' - 1 1/2")
7 FPS
7' - 1 1/2"
-5' - 2 1/4" 9' - 9 1/2"
1.16 psi
0.35 psi
-2' - 6 1/4" 2' - 8"
4.000 (See
Notes)
4.026
29.81 psi
0.04 psi285.137 GPM E(7' - 1 1/2")
7 FPS
1' - 5"
-5' - 2 1/4" 51' - 5 1/2" 1.83 psi
-5' - 2 1/4" 50' - 0 1/4"
4.000 (See
Notes)
4.026
31.32 psi
0.04 psi285.137 GPM PIV(1' - 5"), S
7 FPS
11/22/2021 Page 1AutoSPRINK RVT v2.2.27.0 3:57:43PMDORMITORY ATTIC LH@ M.E.P.CAD, Inc.
Remote Area Name: DORMITORY ATTIC LH
Flow added this step
Pipe Information
Node 1
Node 2
Elev 1 ft
Elev 2 ft
K-Factor
Q
Total Flow
Q
Nominal ID
Actual ID
Fittings &
Devices
Equiv.
Length ft
Length ft
Fitting ft
Total ft
C Factor or
Roughness
Pf Friction
Loss Per Unit psi
Total(Pt)
Elev(Pe)
Friction(Pf)
Notes
Fitting/Device (Equivalent Length)
Fixed Pressure Losses, when applicable, are added directly to (Pf) and shown as a negative value.
Velocity
100.000 GPM Hose Allowance At Source
385.137 GPM
Route 1
33.15 psi
Total(Pt)
1' - 5"
11' - 4" 2' - 3 1/4"
0.35 psi
0.24 psi
12' - 1 3/4" 0' - 10 1/4"
1.000
• • • • • Route 2 • • • • •
(See
Notes)
1.049
7.13 psi14.948 GPM
0.11 psi
Sprinkler,
14.948 GPM
5.6
E(1' - 5")
6 FPS
9' - 0 1/4" 7' - 1 1/2"
1.00 psi
0.20 psi
11' - 4" 7' - 1 1/2"
1.250
1.380
7.72 psi
0.03 psi14.948 GPM
3 FPS
4' - 3 1/4"
8' - 9 1/2" 5' - 0"
0.10 psi
0.53 psi
9' - 0 1/4" 0' - 8 3/4"
1.250 (See
Notes)
1.380
8.92 psi15.859 GPM
0.11 psi
Flow (q) from Route 8
30.808 GPM T(4' - 3 1/4")
7 FPS
8' - 9" 14' - 1"
0.01 psi
0.21 psi
8' - 9 1/2" 14' - 1"
2.500
2.469
9.55 psi18.187 GPM
0.01 psi
Flow (q) from Route 9
48.995 GPM
3 FPS
8' - 8 3/4" 14' - 1 1/4"
0.01 psi
0.52 psi
8' - 9" 14' - 1 1/4"
2.500
2.469
9.78 psi31.219 GPM
0.04 psi
Flow (q) from Route 4
80.214 GPM
5 FPS
4' - 3 1/4"
8' - 7 3/4" 41' - 11 1/2"
0.03 psi
2.88 psi
8' - 8 3/4" 37' - 8 1/4"
2.500 (See
Notes)
2.469
10.31 psi32.123 GPM
0.07 psi
Flow (q) from Route 5
112.337 GPM E(4' - 3 1/4")
8 FPS
8' - 6 3/4"
8' - 7 3/4" 10' - 5 1/4"
0.00 psi
1.40 psi
8' - 7 3/4" 1' - 10 1/2"
2.500 (See
Notes)
2.469
13.22 psi49.073 GPM
0.13 psi
Flow (q) from Route 14
161.409 GPM T(8' - 6 3/4")
11 FPS
8' - 7 3/4" 0' - 8 1/2"
0.00 psi
0.03 psi
8' - 7 3/4" 0' - 8 1/2"
3.000
3.068
14.63 psi
0.05 psi161.409 GPM
7 FPS
14.66 psi Route 2Total(Pt)
3' - 6 3/4"
11' - 0 1/4" 4' - 8 1/4"
0.46 psi
0.51 psi
12' - 1" 1' - 1 1/2"
1.000
• • • • • Route 3 • • • • •
(See
Notes)
1.049
7.25 psi15.084 GPM
0.11 psi
Sprinkler,
15.084 GPM
5.6
T(3' - 6 3/4")
6 FPS
11/22/2021 Page 2AutoSPRINK RVT v2.2.27.0 3:57:43PMDORMITORY ATTIC LH@ M.E.P.CAD, Inc.
Remote Area Name: DORMITORY ATTIC LH
Flow added this step
Pipe Information
Node 1
Node 2
Elev 1 ft
Elev 2 ft
K-Factor
Q
Total Flow
Q
Nominal ID
Actual ID
Fittings &
Devices
Equiv.
Length ft
Length ft
Fitting ft
Total ft
C Factor or
Roughness
Pf Friction
Loss Per Unit psi
Total(Pt)
Elev(Pe)
Friction(Pf)
Notes
Fitting/Device (Equivalent Length)
Fixed Pressure Losses, when applicable, are added directly to (Pf) and shown as a negative value.
Velocity
9' - 0 1/4" 6' - 4"
0.87 psi
0.18 psi
11' - 0 1/4" 6' - 4"
1.250
1.380
8.22 psi
0.03 psi15.084 GPM
3 FPS
4' - 3 1/4"
8' - 9" 5' - 1 3/4"
0.12 psi
0.56 psi
9' - 0 1/4" 0' - 10 1/4"
1.250 (See
Notes)
1.380
9.27 psi16.076 GPM
0.11 psi
Flow (q) from Route 13
31.159 GPM T(4' - 3 1/4")
7 FPS
9.95 psi Route 3Total(Pt)
1' - 5"
11' - 3" 2' - 2 1/4"
0.31 psi
0.24 psi
11' - 11 3/4" 0' - 9"
1.000
• • • • • Route 4 • • • • •
(See
Notes)
1.049
7.38 psi15.211 GPM
0.11 psi
Sprinkler,
15.211 GPM
5.6
E(1' - 5")
6 FPS
9' - 0 1/4" 7' - 0 1/4"
0.97 psi
0.20 psi
11' - 3" 7' - 0 1/4"
1.250
1.380
7.93 psi
0.03 psi15.211 GPM
3 FPS
4' - 3 1/4"
8' - 9" 5' - 1 1/2"
0.12 psi
0.56 psi
9' - 0 1/4" 0' - 10"
1.250 (See
Notes)
1.380
9.10 psi16.008 GPM
0.11 psi
Flow (q) from Route 12
31.219 GPM T(4' - 3 1/4")
7 FPS
9.78 psi Route 4Total(Pt)
1' - 5"
11' - 2 1/2" 2' - 3 1/2"
0.36 psi
0.27 psi
12' - 0 1/2" 0' - 10 1/2"
1.000
• • • • • Route 5 • • • • •
(See
Notes)
1.049
7.81 psi15.645 GPM
0.12 psi
Sprinkler,
15.645 GPM
5.6
E(1' - 5")
6 FPS
8' - 11 1/2" 7' - 1 1/2"
0.98 psi
0.22 psi
11' - 2 1/2" 7' - 1 1/2"
1.250
1.380
8.43 psi
0.03 psi15.645 GPM
3 FPS
4' - 3 1/4"
8' - 8 3/4" 5' - 0 1/4"
0.10 psi
0.58 psi
8' - 11 1/2" 0' - 9"
1.250 (See
Notes)
1.380
9.63 psi16.478 GPM
0.12 psi
Flow (q) from Route 16
32.123 GPM T(4' - 3 1/4")
7 FPS
10.31 psi Route 5Total(Pt)
3' - 6 3/4"
11' - 0" 4' - 8 1/2"
0.47 psi
0.55 psi
12' - 1" 1' - 1 3/4"
1.000
• • • • • Route 6 • • • • •
(See
Notes)
1.049
7.82 psi15.665 GPM
0.12 psi
Sprinkler,
15.665 GPM
5.6
T(3' - 6 3/4")
6 FPS
9' - 0" 6' - 4"
0.87 psi
0.19 psi
11' - 0" 6' - 4"
1.250
1.380
8.84 psi
0.03 psi15.665 GPM
3 FPS
11/22/2021 Page 3AutoSPRINK RVT v2.2.27.0 3:57:43PMDORMITORY ATTIC LH@ M.E.P.CAD, Inc.
Remote Area Name: DORMITORY ATTIC LH
Flow added this step
Pipe Information
Node 1
Node 2
Elev 1 ft
Elev 2 ft
K-Factor
Q
Total Flow
Q
Nominal ID
Actual ID
Fittings &
Devices
Equiv.
Length ft
Length ft
Fitting ft
Total ft
C Factor or
Roughness
Pf Friction
Loss Per Unit psi
Total(Pt)
Elev(Pe)
Friction(Pf)
Notes
Fitting/Device (Equivalent Length)
Fixed Pressure Losses, when applicable, are added directly to (Pf) and shown as a negative value.
Velocity
4' - 3 1/4"
8' - 8 1/2" 5' - 1 3/4"
0.12 psi
0.60 psi
9' - 0" 0' - 10 1/4"
1.250 (See
Notes)
1.380
9.91 psi16.634 GPM
0.12 psi
Flow (q) from Route 18
32.299 GPM T(4' - 3 1/4")
7 FPS
10.62 psi Route 6Total(Pt)
3' - 6 3/4"
9' - 0 1/4" 4' - 7 3/4"
0.45 psi
0.55 psi
10' - 0 1/2" 1' - 1"
1.000
• • • • • Route 7 • • • • •
(See
Notes)
1.049
8.00 psi15.837 GPM
0.12 psi
Sprinkler,
15.837 GPM
5.6
T(3' - 6 3/4")
6 FPS
9.00 psi Route 7Total(Pt)
3' - 6 3/4"
9' - 0 1/4" 4' - 5 1/2"
0.37 psi
0.53 psi
9' - 10 1/2" 0' - 10 3/4"
1.000
• • • • • Route 8 • • • • •
(See
Notes)
1.049
8.02 psi15.859 GPM
0.12 psi
Sprinkler,
15.859 GPM
5.6
T(3' - 6 3/4")
6 FPS
8.92 psi Route 8Total(Pt)
5' - 0"
8' - 9 3/4" 8' - 0 1/2"
0.49 psi
0.96 psi
9' - 11 1/4" 3' - 0 1/2"
1.000
• • • • • Route 9 • • • • •
(See
Notes)
1.049
8.05 psi15.891 GPM
0.12 psi
Sprinkler,
15.891 GPM
5.6
E(1' - 5"), T(3' - 6 3/4")
6 FPS
8' - 9 3/4" 12' - 6 1/4"
0.00 psi
0.00 psi
8' - 9 3/4" 12' - 6 1/4"
2.500
2.469
9.50 psi
0.00 psi2.212 GPM
0 FPS
4' - 3 1/4"
8' - 9 1/2" 17' - 10 3/4"
0.01 psi
0.04 psi
8' - 9 3/4" 13' - 7 1/2"
2.500 (See
Notes)
2.469
9.50 psi15.976 GPM
0.00 psi
Flow (q) from Route 11
18.187 GPM E(4' - 3 1/4")
1 FPS
9.55 psi Route 9Total(Pt)
5' - 0"
8' - 9 1/2" 7' - 9 1/2"
0.50 psi
0.93 psi
9' - 11 1/4" 2' - 9 1/2"
1.000
• • • • • Route 10 • • • • •
(See
Notes)
1.049
8.10 psi15.938 GPM
0.12 psi
Sprinkler,
15.938 GPM
5.6
E(1' - 5"), T(3' - 6 3/4")
6 FPS
4' - 3 1/4"
8' - 9 1/4" 17' - 3"
0.00 psi
0.10 psi
8' - 9 1/2" 12' - 11 1/2"
2.500 (See
Notes)
2.469
9.53 psi13.679 GPM
0.01 psi
Flow (q) from Route 19
29.617 GPM E(4' - 3 1/4")
2 FPS
9.63 psi Route 10Total(Pt)
5' - 0"
8' - 9 3/4" 7' - 9"
0.43 psi
0.93 psi
9' - 9 3/4" 2' - 9"
1.000
• • • • • Route 11 • • • • •
(See
Notes)
1.049
8.14 psi15.976 GPM
0.12 psi
Sprinkler,
15.976 GPM
5.6
E(1' - 5"), T(3' - 6 3/4")
6 FPS
9.50 psi Route 11Total(Pt)
11/22/2021 Page 4AutoSPRINK RVT v2.2.27.0 3:57:43PMDORMITORY ATTIC LH@ M.E.P.CAD, Inc.
Remote Area Name: DORMITORY ATTIC LH
Flow added this step
Pipe Information
Node 1
Node 2
Elev 1 ft
Elev 2 ft
K-Factor
Q
Total Flow
Q
Nominal ID
Actual ID
Fittings &
Devices
Equiv.
Length ft
Length ft
Fitting ft
Total ft
C Factor or
Roughness
Pf Friction
Loss Per Unit psi
Total(Pt)
Elev(Pe)
Friction(Pf)
Notes
Fitting/Device (Equivalent Length)
Fixed Pressure Losses, when applicable, are added directly to (Pf) and shown as a negative value.
Velocity
3' - 6 3/4"
9' - 0 1/4" 4' - 6"
0.39 psi
0.54 psi
9' - 11" 0' - 11 1/4"
1.000
• • • • • Route 12 • • • • •
(See
Notes)
1.049
8.17 psi16.008 GPM
0.12 psi
Sprinkler,
16.008 GPM
5.6
T(3' - 6 3/4")
6 FPS
9.10 psi Route 12Total(Pt)
3' - 6 3/4"
9' - 0 1/4" 4' - 8 1/4"
0.46 psi
0.57 psi
10' - 1" 1' - 1 1/2"
1.000
• • • • • Route 13 • • • • •
(See
Notes)
1.049
8.24 psi16.076 GPM
0.12 psi
Sprinkler,
16.076 GPM
5.6
T(3' - 6 3/4")
6 FPS
9.27 psi Route 13Total(Pt)
3' - 6 3/4"
13' - 3 1/2" 4' - 5"
0.37 psi
0.55 psi
14' - 1 1/2" 0' - 10"
1.000
• • • • • Route 14 • • • • •
(See
Notes)
1.049
8.43 psi16.262 GPM
0.12 psi
Sprinkler,
16.262 GPM
5.6
T(3' - 6 3/4")
6 FPS
13' - 3" 14' - 0 3/4"
0.01 psi
0.06 psi
13' - 3 1/2" 14' - 0 3/4"
2.000
2.067
9.35 psi
0.00 psi16.262 GPM
2 FPS
13' - 2 3/4" 12' - 0 1/2"
0.01 psi
0.20 psi
13' - 3" 12' - 0 1/2"
2.000
2.067
9.42 psi16.317 GPM
0.02 psi
Flow (q) from Route 15
32.579 GPM
3 FPS
3' - 6 3/4"
13' - 2" 29' - 3 1/4"
0.02 psi
1.03 psi
13' - 2 3/4" 25' - 8 1/2"
2.000 (See
Notes)
2.067
9.63 psi16.494 GPM
0.04 psi
Flow (q) from Route 17
49.073 GPM E(3' - 6 3/4")
5 FPS
3' - 6 3/4"
8' - 8" 8' - 1"
1.96 psi
0.29 psi
13' - 2" 4' - 6 1/4"
2.000 (See
Notes)
2.067
10.69 psi
0.04 psi49.073 GPM E(3' - 6 3/4")
5 FPS
7' - 1 1/2"
8' - 7 3/4" 8' - 1 3/4"
0.00 psi
0.29 psi
8' - 8" 1' - 0 1/4"
2.000 (See
Notes)
2.067
12.93 psi
0.04 psi49.073 GPM T(7' - 1 1/2")
5 FPS
13.22 psi Route 14Total(Pt)
3' - 6 3/4"
13' - 3" 4' - 5 1/4"
0.38 psi
0.56 psi
14' - 1 1/2" 0' - 10 1/2"
1.000
• • • • • Route 15 • • • • •
(See
Notes)
1.049
8.49 psi16.317 GPM
0.13 psi
Sprinkler,
16.317 GPM
5.6
T(3' - 6 3/4")
6 FPS
9.42 psi Route 15Total(Pt)
11/22/2021 Page 5AutoSPRINK RVT v2.2.27.0 3:57:43PMDORMITORY ATTIC LH@ M.E.P.CAD, Inc.
Remote Area Name: DORMITORY ATTIC LH
Flow added this step
Pipe Information
Node 1
Node 2
Elev 1 ft
Elev 2 ft
K-Factor
Q
Total Flow
Q
Nominal ID
Actual ID
Fittings &
Devices
Equiv.
Length ft
Length ft
Fitting ft
Total ft
C Factor or
Roughness
Pf Friction
Loss Per Unit psi
Total(Pt)
Elev(Pe)
Friction(Pf)
Notes
Fitting/Device (Equivalent Length)
Fixed Pressure Losses, when applicable, are added directly to (Pf) and shown as a negative value.
Velocity
3' - 6 3/4"
8' - 11 1/2" 4' - 6 1/4"
0.39 psi
0.58 psi
9' - 10 1/2" 0' - 11 1/2"
1.000
• • • • • Route 16 • • • • •
(See
Notes)
1.049
8.66 psi16.478 GPM
0.13 psi
Sprinkler,
16.478 GPM
5.6
T(3' - 6 3/4")
6 FPS
9.63 psi Route 16Total(Pt)
3' - 6 3/4"
13' - 2 3/4" 4' - 5 1/2"
0.39 psi
0.57 psi
14' - 1 1/2" 0' - 10 3/4"
1.000
• • • • • Route 17 • • • • •
(See
Notes)
1.049
8.67 psi16.494 GPM
0.13 psi
Sprinkler,
16.494 GPM
5.6
T(3' - 6 3/4")
6 FPS
9.63 psi Route 17Total(Pt)
3' - 6 3/4"
9' - 0" 4' - 8 1/2"
0.47 psi
0.61 psi
10' - 1" 1' - 1 3/4"
1.000
• • • • • Route 18 • • • • •
(See
Notes)
1.049
8.82 psi16.634 GPM
0.13 psi
Sprinkler,
16.634 GPM
5.6
T(3' - 6 3/4")
6 FPS
9.91 psi Route 18Total(Pt)
8' - 9 1/2" 12' - 6 3/4"
0.01 psi
0.02 psi
8' - 9 3/4" 12' - 6 3/4"
2.500
• • • • • Route 19 • • • • •
2.469
9.50 psi2.212 GPM
0.00 psi
Flow (q) from Route 9
13.679 GPM
1 FPS
9.53 psi Route 19Total(Pt)
11/22/2021 Page 6AutoSPRINK RVT v2.2.27.0 3:57:43PMDORMITORY ATTIC LH@ M.E.P.CAD, Inc.
Remote Area Name: DORMITORY ATTIC LH
1.51
Fittings Legend
BFP Backflow Preventer DPV Dry Pipe Valve E 90° Elbow
PIV Post Indicating Valve S Supply Spr Sprinkler
T Tee Flow Turn 90°
4.87
1.33
1.16
0.713
Equivalent Pipe Lengths of Valves and Fittings (C=120 only)
Actual Inside Diameter
Schedule 40 Steel Pipe Inside Diameter = Factor
C Value Multiplier
Value Of C
Multiplying Factor
11/22/2021 Page 7AutoSPRINK RVT v2.2.27.0 3:57:43PMDORMITORY ATTIC LH@ M.E.P.CAD, Inc.
THIS PAGE INTENTIONALLY LEFT BLANK
Drawing Name: PF002240.05-F20_zparksLKHUF Calculation Date:11/22/2021
Hydraulic Calculations Summary for
Design
Light Hazard
1950 ft²
122 ft² (average)
DORMITORY FLOOR LH
0.100 GPM/ft²
Remote Area Name:
Occupancy Classification:
Density
Area of Application:
Coverage per Sprinkler:
Type of Sprinklers Calculated:
No. of Sprinklers Calculated:
at Node:
Fire Protection Dry
N/AN/A
1100.000 GPM
286.1 galType of System:
In-rack Demand:
Hose Streams:
Volume of Dry or PreAction System:
at Node:
Type Allowance at Source
Total Water Required (including Hose Streams where applicable)
38.58 psi@398.415 GPMFROM: Water Supply at Node 1:
3.55 psiSafety Margin:
POOLE FIRE PROTECTION
BRITTON GRAY
19910 W 161ST ST, OLATHE KS 66062
913-829-8650 ZACHARY PARKS
Contact Name
Address:
Phone Number:
Authority Having Jurisdiction:
Name of Designer:
Automatic Peaking Results
11/22/2021 Page 1AutoSPRINK RVT v2.2.27.0 3:57:04PMDORMITORY FLOOR LH@ M.E.P.CAD, Inc.
Node: 1
Job Name: SPRINKLER DESIGN YCC 101 102 103
Remote Area Name: DORMITORY FLOOR LH Date: 11/22/2021 N 1.85
Summary Sheet
No pressure is being required from the Source/Supply to meet the demand (by a margin of this negative value).
A negative result in Required Pressure indicates that the Pump is capable of furnishing all of the pressure required by the demand reported within this calculation.
11/22/2021 Page 1AutoSPRINK RVT v2.2.27.0 3:57:05PM@ M.E.P.CAD, Inc.
Report Description: Light Hazard
Job Number: 2240.05
(ft²)Device
Actual Flow Minimum Flow K-Factor Pressure
Sprinkler 301 18.363 GPM 16.900 GPM 5.6 10.75 psi 0.109 GPM/ft² 169 ft²
Sprinkler 305 17.245 GPM 16.900 GPM 5.6 9.48 psi 0.102 GPM/ft² 169 ft²
Sprinkler 307 16.913 GPM 16.900 GPM 5.6 9.12 psi 0.100 GPM/ft² 169 ft²
Sprinkler 302 18.350 GPM 16.900 GPM 5.6 10.74 psi 0.109 GPM/ft² 169 ft²
Sprinkler 306 17.235 GPM 16.900 GPM 5.6 9.47 psi 0.102 GPM/ft² 169 ft²
Sprinkler 308 16.900 GPM 16.900 GPM 5.6 9.11 psi 0.100 GPM/ft² 169 ft²
Sprinkler 312 19.423 GPM 16.900 GPM 5.6 12.03 psi 0.115 GPM/ft² 169 ft²
Sprinkler 316 19.774 GPM 16.900 GPM 5.6 12.47 psi 0.117 GPM/ft² 169 ft²
Sprinkler 304 17.888 GPM 14.816 GPM 5.6 10.20 psi 0.199 GPM/ft² 90 ft²
Sprinkler 309 17.477 GPM 14.816 GPM 5.6 9.74 psi 0.194 GPM/ft² 90 ft²
Sprinkler 317 20.261 GPM 14.816 GPM 5.6 13.09 psi 0.225 GPM/ft² 90 ft²
Sprinkler 303 19.004 GPM 14.816 GPM 5.6 11.52 psi 0.396 GPM/ft² 48 ft²
Sprinkler 310 19.299 GPM 14.816 GPM 5.6 11.88 psi 0.643 GPM/ft² 30 ft²
Sprinkler 311 20.896 GPM 14.816 GPM 5.6 13.92 psi 0.174 GPM/ft² 120 ft²
Sprinkler 315 19.580 GPM 14.816 GPM 5.6 12.22 psi 0.529 GPM/ft² 37 ft²
Sprinkler 314 19.806 GPM 14.816 GPM 5.6 12.51 psi 0.220 GPM/ft² 90 ft²
11/22/2021 Page 1AutoSPRINK RVT v2.2.27.0 3:57:05PM@ M.E.P.CAD, Inc.
Remote Area Name: DORMITORY FLOOR LH Date: 11/22/2021
(psi) (psi)(GPM)(psi)(GPM)(psi)
Supply Analysis
Node Name Static Residual Flow Available Total Demand Required Pressure
30.00 psi1 38.58 psi398.415 GPM1182.000 GPM 42.13 psi44.00 psiWater Supply
Node Analysis
Discharge at
Node
(GPM)
Pressure at
Node
(psi)
Elevation (ft)Node Number Node Type Notes
8' - 0" 18.363 GPM10.75 psi Sprinklers
Coverage: 169 ft² Density: 0.109 GPM/ft²
8' - 0" 17.245 GPM9.48 psi Sprinklers
Coverage: 169 ft² Density: 0.102 GPM/ft²
8' - 0" 16.913 GPM9.12 psi Sprinklers
Coverage: 169 ft² Density: 0.100 GPM/ft²
8' - 0" 18.350 GPM10.74 psi Sprinklers
Coverage: 169 ft² Density: 0.109 GPM/ft²
8' - 0" 17.235 GPM9.47 psi Sprinklers
Coverage: 169 ft² Density: 0.102 GPM/ft²
8' - 0" 16.900 GPM9.11 psi Sprinklers
Coverage: 169 ft² Density: 0.100 GPM/ft²
8' - 0" 19.423 GPM12.03 psi Sprinklers
Coverage: 169 ft² Density: 0.115 GPM/ft²
8' - 0" 19.774 GPM12.47 psi Sprinklers
Coverage: 169 ft² Density: 0.117 GPM/ft²
8' - 0" 17.888 GPM10.20 psi Sprinklers
Coverage: 90 ft² Density: 0.199 GPM/ft²
8' - 0" 17.477 GPM9.74 psi Sprinklers
Coverage: 90 ft² Density: 0.194 GPM/ft²
8' - 0" 20.261 GPM13.09 psi Sprinklers
Coverage: 90 ft² Density: 0.225 GPM/ft²
8' - 0" 19.004 GPM11.52 psi Sprinklers
Coverage: 48 ft² Density: 0.396 GPM/ft²
8' - 0" 19.299 GPM11.88 psi Sprinklers
Coverage: 30 ft² Density: 0.643 GPM/ft²
8' - 0" 20.896 GPM13.92 psi Sprinklers
Coverage: 120 ft² Density: 0.174 GPM/ft²
8' - 0" 19.580 GPM12.22 psi Sprinklers
Coverage: 37 ft² Density: 0.529 GPM/ft²
8' - 0" 19.806 GPM12.51 psi Sprinklers
Coverage: 90 ft² Density: 0.220 GPM/ft²
-5' - 2 1/4" 298.415 GPM38.58 psi Supply
11/22/2021 Page 1AutoSPRINK RVT v2.2.27.0 3:57:06PM@ M.E.P.CAD, Inc.
Remote Area Name: DORMITORY FLOOR LH
Flow added this step
Pipe Information
Node 1
Node 2
Elev 1 ft
Elev 2 ft
K-Factor
Q
Total Flow
Q
Nominal ID
Actual ID
Fittings &
Devices
Equiv.
Length ft
Length ft
Fitting ft
Total ft
C Factor or
Roughness
Pf Friction
Loss Per Unit psi
Total(Pt)
Elev(Pe)
Friction(Pf)
Notes
Fitting/Device (Equivalent Length)
Fixed Pressure Losses, when applicable, are added directly to (Pf) and shown as a negative value.
Velocity
8' - 6 3/4"
8' - 11" 10' - 11 1/2"
-0.39 psi
1.46 psi
8' - 0" 2' - 4 3/4"
1.000
• • • • • Route 1 • • • • •
(See
Notes)
1.049
9.11 psi16.900 GPM
0.13 psi
Sprinkler,
16.900 GPM
5.6
2T(3' - 6 3/4"), Z, E(1' - 5")
6 FPS
8' - 10 1/4" 11' - 3 1/2"
0.02 psi
0.40 psi
8' - 11" 11' - 3 1/2"
1.250
1.380
10.18 psi
0.04 psi16.900 GPM
4 FPS
8' - 9 3/4" 11' - 3 1/2"
0.02 psi
1.46 psi
8' - 10 1/4" 11' - 3 1/2"
1.250
1.380
10.59 psi17.235 GPM
0.13 psi
Flow (q) from Route 3
34.135 GPM
7 FPS
4' - 3 1/4"
8' - 9 3/4" 7' - 7 3/4"
0.01 psi
2.18 psi
8' - 9 3/4" 3' - 4 1/2"
1.250 (See
Notes)
1.380
12.07 psi18.350 GPM
0.29 psi
Flow (q) from Route 5
52.486 GPM T(4' - 3 1/4")
11 FPS
4' - 3 1/4"
8' - 8 3/4" 44' - 1"
0.03 psi
1.48 psi
8' - 9 3/4" 39' - 9 3/4"
2.500 (See
Notes)
2.469
14.26 psi23.812 GPM
0.03 psi
Flow (q) from Route 11
76.298 GPM E(4' - 3 1/4")
5 FPS
4' - 3 1/4"
8' - 7 3/4" 40' - 6"
0.03 psi
2.13 psi
8' - 8 3/4" 36' - 2 1/2"
2.500 (See
Notes)
2.469
15.77 psi20.896 GPM
0.05 psi
Flow (q) from Route 16
97.194 GPM E(4' - 3 1/4")
7 FPS
8' - 6 3/4"
8' - 7 3/4" 14' - 7 1/4"
0.01 psi
1.43 psi
8' - 7 3/4" 6' - 0 1/2"
2.500 (See
Notes)
2.469
17.93 psi38.879 GPM
0.10 psi
Flow (q) from Route 12
136.073 GPM T(8' - 6 3/4")
9 FPS
8' - 7 3/4" 0' - 8 1/2"
0.00 psi
0.02 psi
8' - 7 3/4" 0' - 8 1/2"
3.000
3.068
19.37 psi
0.03 psi136.073 GPM
6 FPS
10' - 8 1/4"
8' - 7 1/4" 30' - 7 1/4"
0.01 psi
4.45 psi
8' - 7 3/4" 19' - 11"
3.000 (See
Notes)
3.068
19.39 psi162.342 GPM
0.15 psi
Flow (q) from Route 2
298.415 GPM T(10' - 8 1/4")
13 FPS
2' - 1 1/4" 6' - 6 1/4"
2.83 psi
4.77 psi
8' - 7 1/4" 6' - 6 1/4"
4.000 (See
Notes)
4.026
23.85 psi
0.04 psi298.415 GPM DPV(-0.52 psi), BOR, BFP(-4.
00 psi)
8 FPS
14' - 3"
-2' - 6 1/4" 41' - 4 1/2"
2.00 psi
1.60 psi
2' - 1 1/4" 27' - 1 1/4"
4.000 (See
Notes)
4.026
31.45 psi
0.04 psi298.415 GPM 2E(7' - 1 1/2")
8 FPS
11/22/2021 Page 1AutoSPRINK RVT v2.2.27.0 3:57:07PMDORMITORY FLOOR LH@ M.E.P.CAD, Inc.
Remote Area Name: DORMITORY FLOOR LH
Flow added this step
Pipe Information
Node 1
Node 2
Elev 1 ft
Elev 2 ft
K-Factor
Q
Total Flow
Q
Nominal ID
Actual ID
Fittings &
Devices
Equiv.
Length ft
Length ft
Fitting ft
Total ft
C Factor or
Roughness
Pf Friction
Loss Per Unit psi
Total(Pt)
Elev(Pe)
Friction(Pf)
Notes
Fitting/Device (Equivalent Length)
Fixed Pressure Losses, when applicable, are added directly to (Pf) and shown as a negative value.
Velocity
7' - 1 1/2"
-5' - 2 1/4" 9' - 9 1/2"
1.16 psi
0.38 psi
-2' - 6 1/4" 2' - 8"
4.000 (See
Notes)
4.026
35.05 psi
0.04 psi298.415 GPM E(7' - 1 1/2")
8 FPS
1' - 5"
-5' - 2 1/4" 51' - 5 1/2" 1.99 psi
-5' - 2 1/4" 50' - 0 1/4"
4.000 (See
Notes)
4.026
36.59 psi
0.04 psi298.415 GPM PIV(1' - 5"), S
8 FPS
100.000 GPM Hose Allowance At Source
398.415 GPM
Route 1
38.58 psi
Total(Pt)
8' - 6 3/4"
8' - 10 1/2" 10' - 9"
-0.38 psi
1.44 psi
8' - 0" 2' - 2 1/2"
1.000
• • • • • Route 2 • • • • •
(See
Notes)
1.049
9.12 psi16.913 GPM
0.13 psi
Sprinkler,
16.913 GPM
5.6
2T(3' - 6 3/4"), Z, E(1' - 5")
6 FPS
8' - 10" 11' - 3 1/2"
0.02 psi
0.40 psi
8' - 10 1/2" 11' - 3 1/2"
1.250
1.380
10.18 psi
0.04 psi16.913 GPM
4 FPS
8' - 9 1/2" 11' - 3 1/2"
0.02 psi
1.46 psi
8' - 10" 11' - 3 1/2"
1.250
1.380
10.59 psi17.245 GPM
0.13 psi
Flow (q) from Route 4
34.158 GPM
7 FPS
4' - 3 1/4"
8' - 9 1/2" 7' - 7 3/4"
0.01 psi
2.19 psi
8' - 9 1/2" 3' - 4 1/2"
1.250 (See
Notes)
1.380
12.07 psi18.363 GPM
0.29 psi
Flow (q) from Route 6
52.521 GPM T(4' - 3 1/4")
11 FPS
8' - 6 3/4"
8' - 8" 76' - 6 3/4"
0.05 psi
3.01 psi
8' - 9 1/2" 68' - 0"
2.500 (See
Notes)
2.469
14.26 psi30.557 GPM
0.04 psi
Flow (q) from Route 7
83.078 GPM 2E(4' - 3 1/4")
6 FPS
8' - 7 3/4" 8' - 0 1/2"
0.01 psi
0.65 psi
8' - 8" 8' - 0 1/2"
2.500
2.469
17.32 psi39.197 GPM
0.08 psi
Flow (q) from Route 8
122.275 GPM
8 FPS
8' - 6 3/4"
8' - 7 3/4" 10' - 4 3/4"
0.00 psi
1.41 psi
8' - 7 3/4" 1' - 10"
2.500 (See
Notes)
2.469
17.98 psi40.067 GPM
0.14 psi
Flow (q) from Route 14
162.342 GPM T(8' - 6 3/4")
11 FPS
19.39 psi Route 2Total(Pt)
11/22/2021 Page 2AutoSPRINK RVT v2.2.27.0 3:57:07PMDORMITORY FLOOR LH@ M.E.P.CAD, Inc.
Remote Area Name: DORMITORY FLOOR LH
Flow added this step
Pipe Information
Node 1
Node 2
Elev 1 ft
Elev 2 ft
K-Factor
Q
Total Flow
Q
Nominal ID
Actual ID
Fittings &
Devices
Equiv.
Length ft
Length ft
Fitting ft
Total ft
C Factor or
Roughness
Pf Friction
Loss Per Unit psi
Total(Pt)
Elev(Pe)
Friction(Pf)
Notes
Fitting/Device (Equivalent Length)
Fixed Pressure Losses, when applicable, are added directly to (Pf) and shown as a negative value.
Velocity
8' - 6 3/4"
8' - 10 1/4" 10' - 9 1/2"
-0.37 psi
1.49 psi
8' - 0" 2' - 2 3/4"
1.000
• • • • • Route 3 • • • • •
(See
Notes)
1.049
9.47 psi17.235 GPM
0.14 psi
Sprinkler,
17.235 GPM
5.6
2T(3' - 6 3/4"), Z, E(1' - 5")
6 FPS
10.59 psi Route 3Total(Pt)
8' - 6 3/4"
8' - 10" 10' - 7 1/2"
-0.36 psi
1.47 psi
8' - 0" 2' - 1"
1.000
• • • • • Route 4 • • • • •
(See
Notes)
1.049
9.48 psi17.245 GPM
0.14 psi
Sprinkler,
17.245 GPM
5.6
2T(3' - 6 3/4"), Z, E(1' - 5")
6 FPS
10.59 psi Route 4Total(Pt)
8' - 6 3/4"
8' - 9 3/4" 10' - 10"
-0.36 psi
1.68 psi
8' - 0" 2' - 3 1/4"
1.000
• • • • • Route 5 • • • • •
(See
Notes)
1.049
10.74 psi18.350 GPM
0.16 psi
Sprinkler,
18.350 GPM
5.6
2T(3' - 6 3/4"), Z, E(1' - 5")
7 FPS
12.07 psi Route 5Total(Pt)
8' - 6 3/4"
8' - 9 1/2" 10' - 8"
-0.35 psi
1.66 psi
8' - 0" 2' - 1 1/2"
1.000
• • • • • Route 6 • • • • •
(See
Notes)
1.049
10.75 psi18.363 GPM
0.16 psi
Sprinkler,
18.363 GPM
5.6
2T(3' - 6 3/4"), Z, E(1' - 5")
7 FPS
12.07 psi Route 6Total(Pt)
8' - 6 3/4"
8' - 10 1/2" 13' - 11 1/4"
-0.38 psi
1.98 psi
8' - 0" 5' - 4 3/4"
1.000
• • • • • Route 7 • • • • •
(See
Notes)
1.049
9.74 psi17.477 GPM
0.14 psi
Sprinkler,
17.477 GPM
5.6
2T(3' - 6 3/4"), Z, E(1' - 5")
6 FPS
8' - 10" 14' - 5 3/4"
0.02 psi
0.54 psi
8' - 10 1/2" 14' - 5 3/4"
1.250
1.380
11.34 psi
0.04 psi17.477 GPM
4 FPS
4' - 3 1/4"
8' - 9 1/2" 16' - 7 3/4"
0.02 psi
2.29 psi
8' - 10" 12' - 4 1/2"
1.250 (See
Notes)
1.380
11.90 psi17.888 GPM
0.14 psi
Flow (q) from Route 9
35.365 GPM T(4' - 3 1/4")
8 FPS
8' - 9 1/2" 7' - 7"
0.00 psi
0.05 psi
8' - 9 1/2" 7' - 7"
2.500
2.469
14.21 psi
0.01 psi30.557 GPM
2 FPS
14.26 psi Route 7Total(Pt)
8' - 6 3/4"
8' - 10 1/2" 10' - 8"
-0.38 psi
1.84 psi
8' - 0" 2' - 1 1/2"
1.000
• • • • • Route 8 • • • • •
(See
Notes)
1.049
12.03 psi19.423 GPM
0.17 psi
Sprinkler,
19.423 GPM
5.6
2T(3' - 6 3/4"), Z, E(1' - 5")
11/22/2021 Page 3AutoSPRINK RVT v2.2.27.0 3:57:07PMDORMITORY FLOOR LH@ M.E.P.CAD, Inc.
Remote Area Name: DORMITORY FLOOR LH
Flow added this step
Pipe Information
Node 1
Node 2
Elev 1 ft
Elev 2 ft
K-Factor
Q
Total Flow
Q
Nominal ID
Actual ID
Fittings &
Devices
Equiv.
Length ft
Length ft
Fitting ft
Total ft
C Factor or
Roughness
Pf Friction
Loss Per Unit psi
Total(Pt)
Elev(Pe)
Friction(Pf)
Notes
Fitting/Device (Equivalent Length)
Fixed Pressure Losses, when applicable, are added directly to (Pf) and shown as a negative value.
Velocity
8' - 9 1/4" 11' - 4 1/4"
0.04 psi
0.52 psi
8' - 10 1/2" 11' - 4 1/4"
1.250
1.380
13.49 psi
0.05 psi19.423 GPM
4 FPS
4' - 3 1/4"
8' - 8" 19' - 4 1/4"
0.05 psi
3.22 psi
8' - 9 1/4" 15' - 1"
1.250 (See
Notes)
1.380
14.05 psi19.774 GPM
0.17 psi
Flow (q) from Route 10
39.197 GPM T(4' - 3 1/4")
8 FPS
17.32 psi Route 8Total(Pt)
8' - 6 3/4"
8' - 10" 13' - 10 1/2"
-0.36 psi
2.06 psi
8' - 0" 5' - 4"
1.000
• • • • • Route 9 • • • • •
(See
Notes)
1.049
10.20 psi17.888 GPM
0.15 psi
Sprinkler,
17.888 GPM
5.6
2T(3' - 6 3/4"), Z, E(1' - 5")
7 FPS
11.90 psi Route 9Total(Pt)
8' - 6 3/4"
8' - 9 1/4" 10' - 9"
-0.34 psi
1.92 psi
8' - 0" 2' - 2 1/4"
1.000
• • • • • Route 10 • • • • •
(See
Notes)
1.049
12.47 psi19.774 GPM
0.18 psi
Sprinkler,
19.774 GPM
5.6
2T(3' - 6 3/4"), Z, E(1' - 5")
7 FPS
14.05 psi Route 10Total(Pt)
12' - 1 1/2"
8' - 9 3/4" 18' - 3 3/4"
-0.35 psi
3.04 psi
8' - 0" 6' - 2 1/4"
1.000
• • • • • Route 11 • • • • •
(See
Notes)
1.049
11.52 psi19.004 GPM
0.17 psi
Sprinkler,
19.004 GPM
5.6
3T(3' - 6 3/4"), 2Z, E(1' - 5")
7 FPS
8' - 9 3/4" 13' - 2"
0.00 psi
0.05 psi
8' - 9 3/4" 13' - 2"
2.500
2.469
14.20 psi4.808 GPM
0.00 psi
Flow (q) from Route 17
23.812 GPM
2 FPS
14.26 psi Route 11Total(Pt)
8' - 6 3/4"
8' - 9 1/4" 11' - 4"
-0.33 psi
1.93 psi
8' - 0" 2' - 9 1/4"
1.000
• • • • • Route 12 • • • • •
(See
Notes)
1.049
11.88 psi19.299 GPM
0.17 psi
Sprinkler,
19.299 GPM
5.6
2T(3' - 6 3/4"), Z, E(1' - 5")
7 FPS
8' - 9" 7' - 2"
0.01 psi
0.32 psi
8' - 9 1/4" 7' - 2"
1.250
1.380
13.48 psi
0.04 psi19.299 GPM
4 FPS
4' - 3 1/4"
8' - 7 3/4" 24' - 10 3/4"
0.04 psi
4.08 psi
8' - 9" 20' - 7 1/4"
1.250 (See
Notes)
1.380
13.81 psi19.580 GPM
0.16 psi
Flow (q) from Route 13
38.879 GPM T(4' - 3 1/4")
8 FPS
17.93 psi Route 12Total(Pt)
11/22/2021 Page 4AutoSPRINK RVT v2.2.27.0 3:57:07PMDORMITORY FLOOR LH@ M.E.P.CAD, Inc.
Remote Area Name: DORMITORY FLOOR LH
Flow added this step
Pipe Information
Node 1
Node 2
Elev 1 ft
Elev 2 ft
K-Factor
Q
Total Flow
Q
Nominal ID
Actual ID
Fittings &
Devices
Equiv.
Length ft
Length ft
Fitting ft
Total ft
C Factor or
Roughness
Pf Friction
Loss Per Unit psi
Total(Pt)
Elev(Pe)
Friction(Pf)
Notes
Fitting/Device (Equivalent Length)
Fixed Pressure Losses, when applicable, are added directly to (Pf) and shown as a negative value.
Velocity
8' - 6 3/4"
8' - 9" 10' - 10 1/2"
-0.32 psi
1.91 psi
8' - 0" 2' - 4"
1.000
• • • • • Route 13 • • • • •
(See
Notes)
1.049
12.22 psi19.580 GPM
0.18 psi
Sprinkler,
19.580 GPM
5.6
2T(3' - 6 3/4"), Z, E(1' - 5")
7 FPS
13.81 psi Route 13Total(Pt)
8' - 6 3/4"
8' - 10" 13' - 6 3/4"
-0.36 psi
2.43 psi
8' - 0" 5' - 0"
1.000
• • • • • Route 14 • • • • •
(See
Notes)
1.049
12.51 psi19.806 GPM
0.18 psi
Sprinkler,
19.806 GPM
5.6
2T(3' - 6 3/4"), Z, E(1' - 5")
7 FPS
8' - 8 3/4" 14' - 11 3/4"
0.05 psi
0.71 psi
8' - 10" 14' - 11 3/4"
1.250
1.380
14.58 psi
0.05 psi19.806 GPM
4 FPS
4' - 3 1/4"
8' - 7 3/4" 15' - 1"
0.03 psi
2.62 psi
8' - 8 3/4" 10' - 9 3/4"
1.250 (See
Notes)
1.380
15.33 psi20.261 GPM
0.17 psi
Flow (q) from Route 15
40.067 GPM T(4' - 3 1/4")
9 FPS
17.98 psi Route 14Total(Pt)
8' - 6 3/4"
8' - 8 3/4" 13' - 8"
-0.31 psi
2.55 psi
8' - 0" 5' - 1 1/4"
1.000
• • • • • Route 15 • • • • •
(See
Notes)
1.049
13.09 psi20.261 GPM
0.19 psi
Sprinkler,
20.261 GPM
5.6
2T(3' - 6 3/4"), Z, E(1' - 5")
8 FPS
15.33 psi Route 15Total(Pt)
8' - 6 3/4"
8' - 8 3/4" 10' - 11 1/4"
-0.32 psi
2.16 psi
8' - 0" 2' - 4 1/2"
1.000
• • • • • Route 16 • • • • •
(See
Notes)
1.049
13.92 psi20.896 GPM
0.20 psi
Sprinkler,
20.896 GPM
5.6
2T(3' - 6 3/4"), Z, E(1' - 5")
8 FPS
15.77 psi Route 16Total(Pt)
8' - 9 3/4" 2' - 9 1/2"
-0.01 psi
0.00 psi
8' - 9 1/2" 2' - 9 1/2"
2.500
• • • • • Route 17 • • • • •
2.469
14.21 psi30.557 GPM
0.00 psi
Flow (q) from Route 7
4.808 GPM
0 FPS
14.20 psi Route 17Total(Pt)
11/22/2021 Page 5AutoSPRINK RVT v2.2.27.0 3:57:07PMDORMITORY FLOOR LH@ M.E.P.CAD, Inc.
Remote Area Name: DORMITORY FLOOR LH
1.51
Fittings Legend
BFP Backflow Preventer DPV Dry Pipe Valve E 90° Elbow
PIV Post Indicating Valve S Supply Spr Sprinkler
T Tee Flow Turn 90° Z Cap
4.87
1.33
1.16
0.713
Equivalent Pipe Lengths of Valves and Fittings (C=120 only)
Actual Inside Diameter
Schedule 40 Steel Pipe Inside Diameter = Factor
C Value Multiplier
Value Of C
11/22/2021 Page 6AutoSPRINK RVT v2.2.27.0 3:57:07PMDORMITORY FLOOR LH@ M.E.P.CAD, Inc.
Drawing Name: PF002240.05-F20_zparksLKHUF Calculation Date:11/23/2021
Hydraulic Calculations Summary for
Design
Light Hazard
1950 ft²
104 ft² (typical)
MESS ATTIC LH
0.100 GPM/ft²
Remote Area Name:
Occupancy Classification:
Density
Area of Application:
Coverage per Sprinkler:
Type of Sprinklers Calculated:
No. of Sprinklers Calculated:
at Node:
Fire Protection Dry
N/AN/A
501100.000 GPM
502.9 galType of System:
In-rack Demand:
Hose Streams:
Volume of Dry or PreAction System:
at Node:
Type Allowance at Source
Total Water Required (including Hose Streams where applicable)
28.60 psi@380.720 GPMFROM: Water Supply at Node 501:
16.68 psiSafety Margin:
POOLE FIRE PROTECTION
BRITTON GRAY
19910 W 161ST ST, OLATHE KS 66062
913-829-8650 ZACHARY PARKS
Contact Name
Address:
Phone Number:
Authority Having Jurisdiction:
Name of Designer:
Automatic Peaking Results
11/22/2021 Page 1AutoSPRINK RVT v2.2.27.0 9:38:27AMMESS ATTIC LH@ M.E.P.CAD, Inc.
Node: 501
Job Name: SPRINKLER DESIGN YCC 101 102 103
Remote Area Name: MESS ATTIC LH Date: 11/22/2021 N 1.85
Summary Sheet
No pressure is being required from the Source/Supply to meet the demand (by a margin of this negative value).
A negative result in Required Pressure indicates that the Pump is capable of furnishing all of the pressure required by the demand reported within this calculation.
11/22/2021 Page 1AutoSPRINK RVT v2.2.27.0 9:38:28AM@ M.E.P.CAD, Inc.
Report Description: Light Hazard
Job Number: 2240.05
(ft²)Device
Actual Flow Minimum Flow K-Factor Pressure
Sprinkler 202 15.050 GPM 14.816 GPM 5.6 7.22 psi 0.145 GPM/ft² 104 ft²
Sprinkler 204 14.982 GPM 14.816 GPM 5.6 7.16 psi 0.144 GPM/ft² 104 ft²
Sprinkler 206 14.943 GPM 14.816 GPM 5.6 7.12 psi 0.144 GPM/ft² 104 ft²
Sprinkler 208 14.900 GPM 14.816 GPM 5.6 7.08 psi 0.143 GPM/ft² 104 ft²
Sprinkler 212 14.887 GPM 14.816 GPM 5.6 7.07 psi 0.143 GPM/ft² 104 ft²
Sprinkler 214 14.896 GPM 14.816 GPM 5.6 7.08 psi 0.143 GPM/ft² 104 ft²
Sprinkler 201 16.128 GPM 14.816 GPM 5.6 8.29 psi 0.155 GPM/ft² 104 ft²
Sprinkler 203 16.064 GPM 14.816 GPM 5.6 8.23 psi 0.154 GPM/ft² 104 ft²
Sprinkler 205 16.029 GPM 14.816 GPM 5.6 8.19 psi 0.154 GPM/ft² 104 ft²
Sprinkler 207 16.000 GPM 14.816 GPM 5.6 8.16 psi 0.154 GPM/ft² 104 ft²
Sprinkler 211 15.970 GPM 14.816 GPM 5.6 8.13 psi 0.154 GPM/ft² 104 ft²
Sprinkler 213 15.904 GPM 14.816 GPM 5.6 8.07 psi 0.153 GPM/ft² 104 ft²
Sprinkler 215 14.816 GPM 14.816 GPM 5.6 7.00 psi 0.142 GPM/ft² 104 ft²
Sprinkler 217 15.906 GPM 14.816 GPM 5.6 8.07 psi 0.153 GPM/ft² 104 ft²
Sprinkler 216 16.850 GPM 14.816 GPM 5.6 9.05 psi 0.162 GPM/ft² 104 ft²
Sprinkler 218 16.530 GPM 14.816 GPM 5.6 8.71 psi 0.159 GPM/ft² 104 ft²
Sprinkler 209 14.892 GPM 14.816 GPM 5.6 7.07 psi 0.143 GPM/ft² 104 ft²
Sprinkler 210 15.973 GPM 14.816 GPM 5.6 8.14 psi 0.154 GPM/ft² 104 ft²
11/22/2021 Page 1AutoSPRINK RVT v2.2.27.0 9:38:28AM@ M.E.P.CAD, Inc.
Remote Area Name: MESS ATTIC LH Date: 11/22/2021
(psi) (psi)(GPM)(psi)(GPM)(psi)
Supply Analysis
Node Name Static Residual Flow Available Total Demand Required Pressure
33.00 psi501 28.60 psi380.720 GPM1182.000 GPM 45.28 psi47.00 psiWater Supply
Node Analysis
Discharge at
Node
(GPM)
Pressure at
Node
(psi)
Elevation (ft)Node Number Node Type Notes
12' - 10 3/4" 15.050 GPM7.22 psi Sprinklers
Coverage: 104 ft² Density: 0.145 GPM/ft²
12' - 10 3/4" 14.982 GPM7.16 psi Sprinklers
Coverage: 104 ft² Density: 0.144 GPM/ft²
12' - 10 3/4" 14.943 GPM7.12 psi Sprinklers
Coverage: 104 ft² Density: 0.144 GPM/ft²
12' - 10 3/4" 14.900 GPM7.08 psi Sprinklers
Coverage: 104 ft² Density: 0.143 GPM/ft²
12' - 10 3/4" 14.887 GPM7.07 psi Sprinklers
Coverage: 104 ft² Density: 0.143 GPM/ft²
12' - 10 3/4" 14.896 GPM7.08 psi Sprinklers
Coverage: 104 ft² Density: 0.143 GPM/ft²
10' - 3 1/2" 16.128 GPM8.29 psi Sprinklers
Coverage: 104 ft² Density: 0.155 GPM/ft²
10' - 3 1/2" 16.064 GPM8.23 psi Sprinklers
Coverage: 104 ft² Density: 0.154 GPM/ft²
10' - 3 1/2" 16.029 GPM8.19 psi Sprinklers
Coverage: 104 ft² Density: 0.154 GPM/ft²
10' - 3 1/4" 16.000 GPM8.16 psi Sprinklers
Coverage: 104 ft² Density: 0.154 GPM/ft²
10' - 3 3/4" 15.970 GPM8.13 psi Sprinklers
Coverage: 104 ft² Density: 0.154 GPM/ft²
10' - 5 1/4" 15.904 GPM8.07 psi Sprinklers
Coverage: 104 ft² Density: 0.153 GPM/ft²
13' - 3" 14.816 GPM7.00 psi Sprinklers
Coverage: 104 ft² Density: 0.142 GPM/ft²
10' - 7 3/4" 15.906 GPM8.07 psi Sprinklers
Coverage: 104 ft² Density: 0.153 GPM/ft²
9' - 11 1/2" 16.850 GPM9.05 psi Sprinklers
Coverage: 104 ft² Density: 0.162 GPM/ft²
9' - 11 3/4" 16.530 GPM8.71 psi Sprinklers
Coverage: 104 ft² Density: 0.159 GPM/ft²
12' - 10 3/4" 14.892 GPM7.07 psi Sprinklers
Coverage: 104 ft² Density: 0.143 GPM/ft²
10' - 3 3/4" 15.973 GPM8.14 psi Sprinklers
Coverage: 104 ft² Density: 0.154 GPM/ft²
-2' - 10 1/2" 280.720 GPM28.60 psi Supply
11/22/2021 Page 1AutoSPRINK RVT v2.2.27.0 9:38:29AM@ M.E.P.CAD, Inc.
Remote Area Name: MESS ATTIC LH
Flow added this step
Pipe Information
Node 1
Node 2
Elev 1 ft
Elev 2 ft
K-Factor
Q
Total Flow
Q
Nominal ID
Actual ID
Fittings &
Devices
Equiv.
Length ft
Length ft
Fitting ft
Total ft
C Factor or
Roughness
Pf Friction
Loss Per Unit psi
Total(Pt)
Elev(Pe)
Friction(Pf)
Notes
Fitting/Device (Equivalent Length)
Fixed Pressure Losses, when applicable, are added directly to (Pf) and shown as a negative value.
Velocity
1' - 5"
12' - 11 1/4" 1' - 9"
0.13 psi
0.18 psi
13' - 3" 0' - 3 3/4"
1.000
• • • • • Route 1 • • • • •
(See
Notes)
1.049
7.00 psi14.816 GPM
0.10 psi
Sprinkler,
14.816 GPM
5.6
E(1' - 5")
6 FPS
10' - 4 1/4" 8' - 2 1/4"
1.12 psi
0.23 psi
12' - 11 1/4" 8' - 2 1/4"
1.250
1.380
7.31 psi
0.03 psi14.816 GPM
3 FPS
4' - 3 1/4"
9' - 4 1/2" 7' - 4 1/2"
0.42 psi
0.78 psi
10' - 4 1/4" 3' - 1 1/4"
1.250 (See
Notes)
1.380
8.66 psi15.906 GPM
0.11 psi
Flow (q) from Route 10
30.722 GPM T(4' - 3 1/4")
7 FPS
78' - 5 1/4"
9' - 3" 194' - 11 1/2"
0.05 psi
1.86 psi
9' - 4 1/2" 116' - 6 1/4"
4.000 (See
Notes)
4.026
9.87 psi109.407 GPM
0.01 psi
Flow (q) from Route 2
140.129 GPM 9E(7' - 1 1/2"), T(14' - 3")
4 FPS
7' - 1 1/2"
8' - 5 1/4" 7' - 11 1/4"
0.35 psi
0.27 psi
9' - 3" 0' - 9 3/4"
4.000 (See
Notes)
4.026
11.78 psi140.591 GPM
0.03 psi
Flow (q) from Route 5
280.720 GPM E(7' - 1 1/2")
7 FPS
14' - 3"
8' - 5 1/4" 17' - 1 1/2"
0.00 psi
0.59 psi
8' - 5 1/4" 2' - 10 1/4"
4.000 (See
Notes)
4.026
12.41 psi
0.03 psi280.720 GPM 2E(7' - 1 1/2")
7 FPS
4' - 3 1/4" 4' - 2"
1.80 psi
0.66 psi
8' - 5 1/4" 4' - 2"
4.000 (See
Notes)
4.026
13.01 psi
0.03 psi280.720 GPM DPV(-0.52 psi)
7 FPS
2' - 1 3/4" 2' - 1 1/2"
0.92 psi
4.07 psi
4' - 3 1/4" 2' - 1 1/2"
4.000 (See
Notes)
4.026
15.48 psi
0.03 psi280.720 GPM BOR, BFP(-4.00 psi)
7 FPS
7' - 1 1/2"
-5' - 10 3/4" 15' - 2"
3.49 psi
0.52 psi
2' - 1 3/4" 8' - 0 1/2"
4.000 (See
Notes)
4.026
20.47 psi
0.03 psi280.720 GPM E(7' - 1 1/2")
7 FPS
8' - 6 3/4"
-2' - 10 1/2" 156' - 11 1/2"
-1.31 psi
5.43 psi
-5' - 10 3/4" 148' - 5"
4.000 (See
Notes)
4.026
24.48 psi
0.03 psi280.720 GPM PIV(1' - 5"), E(7' - 1 1/2"), S
7 FPS
100.000 GPM Hose Allowance At Source
380.720 GPM
Route 1
28.60 psi
Total(Pt)
11/22/2021 Page 1AutoSPRINK RVT v2.2.27.0 9:38:30AMMESS ATTIC LH@ M.E.P.CAD, Inc.
Remote Area Name: MESS ATTIC LH
Flow added this step
Pipe Information
Node 1
Node 2
Elev 1 ft
Elev 2 ft
K-Factor
Q
Total Flow
Q
Nominal ID
Actual ID
Fittings &
Devices
Equiv.
Length ft
Length ft
Fitting ft
Total ft
C Factor or
Roughness
Pf Friction
Loss Per Unit psi
Total(Pt)
Elev(Pe)
Friction(Pf)
Notes
Fitting/Device (Equivalent Length)
Fixed Pressure Losses, when applicable, are added directly to (Pf) and shown as a negative value.
Velocity
1' - 5"
12' - 6 1/2" 1' - 9 1/2"
0.15 psi
0.19 psi
12' - 10 3/4" 0' - 4 1/2"
1.000
• • • • • Route 2 • • • • •
(See
Notes)
1.049
7.07 psi14.887 GPM
0.11 psi
Sprinkler,
14.887 GPM
5.6
E(1' - 5")
6 FPS
9' - 11 1/4" 8' - 2 1/2"
1.13 psi
0.23 psi
12' - 6 1/2" 8' - 2 1/2"
1.250
1.380
7.41 psi
0.03 psi14.887 GPM
3 FPS
4' - 3 1/4"
9' - 3 3/4" 6' - 3 1/4"
0.27 psi
0.67 psi
9' - 11 1/4" 1' - 11 3/4"
1.250 (See
Notes)
1.380
8.76…