B08_140P1422R0002_Attachment_J11_Dry_Sprinkler_System_Design_Calculations_2021-11-24.pdf

PDF 3 MB Posted

Attached to
National Park Service, Northern Rockies MABO, Mult
Solicitation number
140P1422R0002
Issued by

View the file

Other files

File Type Posted
B08_140P1422R0002_RFP_Amendment_Letter_6_Q_A_0006.pdf PDF
Sol_140P1422R0002_Amd_0006.pdf PDF
B08_140P1422R0002_RFP_Amendment_Letter_5_Q_A_0005.pdf PDF
Sol_140P1422R0002_Amd_0005.pdf PDF
B08_140P1422R0002_RFP_Amendment_Letter_4_Site_Visit_Sign_In_Form_0004.pdf PDF
Sol_140P1422R0002_Amd_0004.pdf PDF
B08_140P1422R0002_RFP_Amendment_Letter_4_Q_A_0004.pdf PDF
RFP_Amendment_Letter_3_Q_A_0003.pdf PDF
Sol_140P1422R0002_Amd_0003.pdf PDF
B08_140P1422R0002_MATOC_RFP_Revised_4May2023_0003.pdf PDF
RFP_Amendment_Letter_3_Asbestos_Sampling_Report2May2023_0003.pdf PDF
B08_140P1422R0002_Attachment_J10_Seed_TO_RFP_Form_Revised_4May2023_0003.pdf PDF
RFP_Amendment_Letter_3_Attachment_J6_SEED_TO_SOW_Revised_2May2023_0003.pdf PDF
B08_140P1422R0002_Attachment_J10_Seed_TO_RFP_Form_Revised_27Apr2023_0002.pdf PDF
RFP_Amendment_Letter_2_Drawing_YCC_MESS_HALL_0002.pdf PDF
Amendment_Questions_0002.pdf PDF
RFP_Amendment_Letter_2_Attachment_J6_SEED_TO_SOW_Revised_25Apr2023_0002.pdf PDF
B08_140P1422R0002_MATOC_RFP_Section_B_Revised_27Apr2023_0002.pdf PDF
Sol_140P1422R0002_Amd_0002.pdf PDF
RFP_Amendment_Letter_2_Site_visit_Sign_In_Log_0002.pdf PDF
Sol_140P1422R0002_Amd_0001.pdf PDF
B08_140P1422R0002_Attachment__J2_TO_RFP_Form_Sample.docx DOCX document
B08_140P1422R0002_Attachment_J9__SEED_TO_Proposed_Equals_Request.docx DOCX document
Sol_140P1422R0002.pdf PDF
B08_140P1422R0002_Attachment__J1_NPS_Safety_and_Checklist.pdf PDF
B08_140P1422R0002_Attachment__J4_Past_Performance_Questionnaire.docx DOCX document
B08_140P1422R0002_Attachment_J8_Wage_Determination_Park_Co_Bldg_WY20230013_Dated_27Jan2023.pdf PDF
B08_140P1422R0002_Attachment_J7_SEED_TO_Drawings_2021-11-24.pdf PDF
B08_140P1422R0002_Attachment__J3_Will_Not_Compete.docx DOCX document
B08_140P1422R0002_Attachment_J6_SEED_TO_SOW_Revised_30Mar2023.pdf PDF
B08_140P1422R0002_Attachment_J10_Seed_TO_RFP_Form.docx DOCX document
B08_140P1422R0002_Attachment__J5_LmtOnSubconRpt.xlsx XLSX spreadsheet
Show all 32

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Design Automatic Dry Sprinkler System at YCC Mess Hall and Dorm Buildings

101, 102, & 103

Mammoth Hot Springs, Yellowstone National Park (YELL), WY

Calculations

Final Submittal Submitted: November 24, 2021

Ready to Advertise

Poole Fire Protection, Inc.

19910 West 161st Street Olathe, Kansas 66062 www.poolefire.com innovative leader trusted partner

NPS YELL YCC Dormitories and Mess Hall Sprinkler Replacement PPIMYELL42

A/E CONTRACT NO. 140P2120D0006 / ORDER NO. 140P1421F0168

THIS PAGE LEFT BLANK FOR DUPLEXING PURPOSES

PURPOSE

These calculations will establish the available water supply at the point of connection for each building included in this project by adjusting the hydrant flow test information for elevation differences between the test gauge location and the respective points of connection for each building.

ASSUMPTIONS

Original water supply available at the test gauge: Static = 39 psi, Residual = 25 psi, Flow = 1182 gpm Elevation of Test Gauge (on sprinkler riser in dormitory) = 6465 feet (Relative 0 ft) Elevation of Dormitory lead-in Point of Connection (POC) to main = 6454 feet (Relative -11 ft) Elevation of Mess Hall lead-in POC to main = 6447 feet (Relative -18 ft) There are 0.433 psi gained/lost per foot of elevation.

Lead-in piping remains a consistent depth of bury below grade (approximately 6 ft).

CALCULATIONS

Pressure change for Dormitory lead-in POC = 0.433 psi/ft * (-11 ft) = 4.763 psi gain Dormitory lead-in POC Static = 39 psi + 4.763 psi = 43.763 psi Dormitory lead-in POC Residual = 25 psi + 4.763 psi = 29.763 psi Dormitory lead-in POC Flow = 1182 gpm (no change)

Pressure change for Mess Hall lead-in POC = 0.433 psi/ft * (-18 ft) = 7.794 psi gain Mess Hall lead-in POC Static = 39 psi + 7.794 psi = 46.794 psi Mess Hall lead-in POC Residual = 25 psi + 7.794 psi = 32.794 psi Mess Hall lead-in POC Flow = 1182 gpm (no change)

CONCLUSIONS

Dormitory water supply available at the lead-in POC with the main: Static = 44 psi, Residual = 30 psi, Flow = 1182 gpm Mess Hall water supply available at the lead-in POC with the main: Static = 47 psi, Residual = 33 psi, Flow = 1182 gpm

Attachments

Copies: Owner A/E Contractor Consultants File

CALCULATIONS

Client National Park Service Calculated by Brad Austin, PE, CSP

Project Name Sprinkler Design YCC 101 102 103 Date November 2, 2021

Project # PF002240.05 Checked by Kevin Boyer, PE

Title Water Supply Adjustment Calculations Page 1 of 1

TEST GAUGE ON

SPRINKLER RISER

ELEV = 6465 FT

(estimated)

MESS HALL

LEAD-IN POC

ELEV = 6447 FT

(estimated)

GRADE OUTSIDE

DORMITORY

ELEV = 6460 FT

(from Google Earth)

DORMITORY

LEAD-IN POC

ELEV = 6454 FT

(estimated)

GRADE OUTSIDE

MESS HALL

ELEV = 6450 FT

(from Google Earth)

GRADE AT MESS

HALL LEAD-IN

POC

ELEV = 6453 FT

(from Google Earth) innovative leader trusted partner

Poole Fire Protection, Inc.

19910 West 161st Street Olathe, Kansas 66062 www.poolefire.com

Fire Hydrant Flow Test Report

Sprinkler Design YCC YCC Camp, Yellowstone Nat'l Park

Performed: 10/7/2021

FIRE HYDRANT FLOW TEST INSTRUCTIONS

Client 20211007

Signature Date

National Park Service Report Number Project Name Sprinkler Design YCC Signed By Brad Austin, PE Project #

INSTRUCTIONS:

4. After testing, transfer all hand written information compiled from the field into the excel worksheets.

Brad Austin, PE, CSP 10/7/2021

APPROVAL PRIOR TO TESTING

Flow test location and hydrants have been approved by:

2240.05

2 Print this sheet and complete the "Approval Prior to Testing " section by coordinating flow test location/hydrants with the project Engineer of Record or Technical Lead.

3. At the site, complete the other applicable portions of this report.

Date 10/7/2021 Location YCC Camp, Yellowstone Nat'l ParkPage

1. Prior to testing, review the "Guidelines for Hydrant Flow Testing and Reports" .

FIRE HYDRANT FLOW TEST INFORMATION

FIRE HYDRANT FLOW TEST INFORMATION

TABLES AND FIGURES

The Coefficient of Discharge, c, is different from the Pumper Outlet Coefficient. The Coefficient of Discharge is chosen using Figure 4.7.1. The Pumper Outlet Coefficient is based on the pitot pressure (velocity head) and selected from Table 4.8.2. Note also that the coefficient of discharge may be different depending on which flow testing diffusers are utilized during the test. If a diffuser is used, plug in the appropriate identifier for the diffuser rather than entering a coefficient of discharge number.

NFPA 291, Figure 4.7.1 - Three General Types of Hydrant Outlets and Their Coefficients of Discharge

NFPA 291, Table 4.8.2 - Pumper Outlet Coefficients

National Park Service Report Number Project Name Sprinkler Design YCC Signed By Brad Austin, PE Project # 2240.05 Date 10/7/2021 Location YCC Camp, Yellowstone Nat'l ParkPage

FIRE HYDRANT FLOW TEST INFORMATION

NOTES

The test was conducted using the Fire Riser located in the North Dormitory Building as the "test hydrant".

The existing system pressure gauge was replaced with calibrated gauge PFP179 for testing purposes.

The flow hydrant utilized two 2" Pitotless nozzles open to atmosphere using calibrated pressure gauges

PFP153 and PFP182.

Project # 2240.05 Date 10/7/2021 Location YCC Camp, Yellowstone Nat'l ParkPage

National Park Service Report Number Project Name Sprinkler Design YCC Signed By Brad Austin, PE

FIRE HYDRANT FLOW TEST REPORT

Gauges Used:

Static/Residual F2-2 F4-1 F5-P F1-1 F2-P F4-2 F6-1 F1-2 F3-1 F4-P F6-2 F1-P F3-2 F5-1 F6-P F2-1 F3-P F5-2

Consumption Rate During Test:

No

No

Underground Main fed by lake

YCC Camp, Yellowstone National Park Location:

Date:

Time:

Test Performed By:

Representative Of:

Water Purveyor Name and Contact Information:

Witness(es):

Purpose of Test:

Attachments (the following documents are attached to the end of this report):

Utility plan with hydrant ID (yes or no?)

National Park Service Sprinkler Design YCC

2240.05 YCC Camp, Yellowstone Nat'l Park

Brad Austin, PE 10/7/2021

Project Name

Location Project #

Report Number Signed By Date Page

GENERAL WATER FLOW TEST INFORMATION

4,408 Gallons

Thursday, October 7, 2021

0855 MT

Brad Austin & Zachary Parks

Poole Fire Protection

None

Establish available water supply for sprinkler system design.

Yellowstone National Park Service

Water quality analysis report (yes or no?)

Source of Water:

Water Quality Sample taken (yes or no?):

Do pumps affect test? If yes, indicate which pumps were operating:

PFP179

PFP153

Yes

No

PFP182

RESIDUAL HYDRANT [R] FLOW TEST INFORMATION

Location:

Elevation:

Static Pressure: DE = Dechlorination Unit

SWL = 2.5" Swivel Diffuser Residual Pressure: SWB = 4" Swivel Diffuser

HML = 1.125" Hose Monster HMM = 1.75" Hose Monster

FLOW HYDRANT [F] FLOW TEST INFORMATION HMB = 2.5" Hose Monster SS = Stream Straightener

Flow Hydrant 1 [F1] PNL = 1.75" Pitotless Nozzle with Little Hose Monster

Location: PNB = 2" Pitotless Nozzle with Little Hose Monster

Elevation:

Outlet

Pumper

Flow Hydrant 2 [F2] Location:

Elevation:

Outlet

Pumper

Flow Hydrant 3 [F3] Location:

Elevation:

Outlet

Pumper

PNOL = 1.75" Pitotless Nozzle Open to Atmosphere

PNOB = 2" Pitotless Nozzle Open to Atmosphere

Coeff. of Discharge , "c" Pitot (psi)

PNOB

PNOB

Project Name Sprinkler Design YCC Signed By Brad Austin, PE Project # 2240.05 Date 10/7/2021

Location YCC Camp, Yellowstone Nat'l ParkPage

National Park Service Report Number

Size (in.) Pumper Outlet Coeff.

Fire Riser in North Dormitory Mechanical Room

Relative 0 ft.

Hydrant north of north dormitory

Relative -10 ft.

Size (in.) Coeff. of Discharge , "c" Pitot (psi) Pumper Outlet Coeff.

Size (in.) Coeff. of Discharge , "c" Pitot (psi) Pumper Outlet Coeff.

Flow Hydrant 4 [F4] Location:

Elevation:

Outlet

Pumper

Flow Hydrant 5 [F5] Location:

Elevation:

Outlet

Pumper

Flow Hydrant 6 [F6] Location:

Elevation:

Outlet

Pumper

Flow Hydrant 7 [F7] Location:

Elevation:

Outlet

Pumper

National Park Service Report Number Project Name Sprinkler Design YCC Signed By Brad Austin, PE Project # 2240.05 Date 10/7/2021 Location YCC Camp, Yellowstone Nat'l ParkPage

Size (in.) Coeff. of Discharge , "c" Pitot (psi) Pumper Outlet Coeff.

Size (in.) Coeff. of Discharge , "c" Pitot (psi) Pumper Outlet Coeff.

Size (in.) Coeff. of Discharge , "c" Pitot (psi) Pumper Outlet Coeff.

Size (in.) Coeff. of Discharge , "c" Pitot (psi) Pumper Outlet Coeff.

FIRE HYDRANT FLOW TEST CALCULATION

Client Report Number Project Name Calculated By Project # Date

Location Page 1

PURPOSE

KNOWN DATA

Flow Hydrants d p c d p c p x

F1 2.00 12 PNOB2.00 13 0 0 0

F2 0.00 0 0 0.00 0 0 0 0

F3 0.00 0 0 0.00 0 0 0 0

F4 0.00 0 0 0.00 0 0 0 0

F5 0.00 0 0 0.00 0 0 0 0

F6 0.00 0 0 0.00 0 0 0 0

F7 0.00 0 0 0.00 0 0 0 0

CALCULATIONS

This calculation is based on NFPA 291, 2016 Edition.

Flow Calculation

Q=29.84cd2p1/2x (NFPA 291, Equation 4.7.3 & Section 4.8.2)

Q = discharge (gpm) c = coefficient of discharge d = diameter of the outlet (inches) p = pitot pressure or velocity head (psi) x = pumper outlet coefficient (if applicable)

Q2=[(S-20)0.54/(S-R)0.54]*Q1 (NFPA 291, Equation 4.10.1.2 & Section 4.10.1.2)

Q2 = discharge at 20 psi (gpm) S = static pressure (psi) R = residual pressure (psi) Q1 = discharge at R (gpm)

CONCLUSION

Available Water Supply:

Static: psi Residual: psi Flow: gpm gpm

0.00

0.00

0.00

National Park Service Sprinkler Design YCC

2240.05

YCC Camp, Yellowstone Nat'l Park

20211007

10/7/2021 Brad Austin, PE

1 of

Flow at 20 psi Residual:

1,394

Flow Available at 20 psi Residual Calculation

Outlet 1 Q

Outlet 2 Q

1,182 c

PNOB

The purpose of this calculation is to determine the water supply capabilities of the existing distribution system.

1,182 d Q

0.00 0 1,182

Subtotal Flow

0.00

0.00

Total Flow, Q:

Pumper

00 0 0 0.00 0

1,182

1,394 gpm @ psi gpm @ psi gpm @ psi

P re ss ur e (P

S I)

Flow (GPM)

FIRE HYDRANT FLOW TEST WATER SUPPLY GRAPH

Client Report Number Project Name Signed By Project # Date Location Page 1 of 1

National Park Service Sprinkler Design YCC

2240.05 YCC Camp, Yellowstone Nat'l Park

20211007 Brad Austin, PE

10/7/2021

Client Report Number Project Name Signed By Project # Date Location Page 1 of 1

National Park Service Sprinkler Design YCC

2240.05 YCC Camp, Yellowstone Nat'l Park

20211007 Brad Austin, PE

10/7/2021

STATIC/RESIDUAL

GAUGE PFP179

ON FIRE RISER

(STATIC: 39 psi, RESIDUAL: 25 psi)

FLOW HYDRANT

GAUGES PFP153

(12 psi) & PFP182 (13 psi)

THIS HYDRANT

FOUND TO BE

INOPERABLE.

Location: 101 102 103 YCC CAMP RD, YELLOWSTONE NATIONAL PARK, WY 82190

Project Name: SPRINKLER DESIGN YCC 101 102 103

Drawing Name: PF002240.05-F20_zparksLKHUF Calculation Date:11/22/2021

Hydraulic Calculations Summary for

Design

Light Hazard

1950 ft²

120 ft² (typical)

DORMITORY ATTIC LH

0.100 GPM/ft²

Remote Area Name:

Occupancy Classification:

Density

Area of Application:

Coverage per Sprinkler:

Type of Sprinklers Calculated:

No. of Sprinklers Calculated:

at Node:

Fire Protection Dry

N/AN/A

1100.000 GPM

286.1 galType of System:

In-rack Demand:

Hose Streams:

Volume of Dry or PreAction System:

at Node:

Type Allowance at Source

Total Water Required (including Hose Streams where applicable)

33.15 psi@385.137 GPMFROM: Water Supply at Node 1:

9.09 psiSafety Margin:

POOLE FIRE PROTECTION

BRITTON GRAY

19910 W 161ST ST, OLATHE KS 66062

913-829-8650 ZACHARY PARKS

Contact Name

Address:

Phone Number:

Authority Having Jurisdiction:

Name of Designer:

Automatic Peaking Results

Notes:

11/22/2021 Page 1AutoSPRINK RVT v2.2.27.0 3:57:40PMDORMITORY ATTIC LH@ M.E.P.CAD, Inc.

Hydraulic Graph

Water Supply

Node: 1

Job Name: SPRINKLER DESIGN YCC 101 102 103

Remote Area Name: DORMITORY ATTIC LH Date: 11/22/2021 N 1.85

Summary Sheet

No pressure is being required from the Source/Supply to meet the demand (by a margin of this negative value).

A negative result in Required Pressure indicates that the Pump is capable of furnishing all of the pressure required by the demand reported within this calculation.

11/22/2021 Page 1AutoSPRINK RVT v2.2.27.0 3:57:41PM@ M.E.P.CAD, Inc.

(GPM) (GPM) (K) (psi) (GPM/ft²)

Outflowing Devices Report Description: Light Hazard

Job Number: 2240.05

(ft²)Device

Actual Flow Minimum Flow K-Factor Pressure

Sprinkler 406 14.816 GPM 14.816 GPM 5.6 7.00 psi 0.123 GPM/ft² 120 ft²

Sprinkler 413 15.084 GPM 14.816 GPM 5.6 7.25 psi 0.126 GPM/ft² 120 ft²

Sprinkler 416 15.665 GPM 14.816 GPM 5.6 7.82 psi 0.131 GPM/ft² 120 ft²

Sprinkler 405 15.837 GPM 14.816 GPM 5.6 8.00 psi 0.132 GPM/ft² 120 ft²

Sprinkler 412 16.076 GPM 14.816 GPM 5.6 8.24 psi 0.134 GPM/ft² 120 ft²

Sprinkler 415 16.634 GPM 14.816 GPM 5.6 8.82 psi 0.139 GPM/ft² 120 ft²

Sprinkler 404 16.262 GPM 14.816 GPM 5.6 8.43 psi 0.136 GPM/ft² 120 ft²

Sprinkler 409 16.317 GPM 14.816 GPM 5.6 8.49 psi 0.136 GPM/ft² 120 ft²

Sprinkler 414 16.494 GPM 14.816 GPM 5.6 8.67 psi 0.137 GPM/ft² 120 ft²

Sprinkler 408 15.859 GPM 14.816 GPM 5.6 8.02 psi 0.132 GPM/ft² 120 ft²

Sprinkler 410 16.008 GPM 14.816 GPM 5.6 8.17 psi 0.133 GPM/ft² 120 ft²

Sprinkler 418 16.478 GPM 14.816 GPM 5.6 8.66 psi 0.137 GPM/ft² 120 ft²

Sprinkler 407 14.948 GPM 14.816 GPM 5.6 7.13 psi 0.125 GPM/ft² 120 ft²

Sprinkler 411 15.211 GPM 14.816 GPM 5.6 7.38 psi 0.127 GPM/ft² 120 ft²

Sprinkler 417 15.645 GPM 14.816 GPM 5.6 7.81 psi 0.130 GPM/ft² 120 ft²

Sprinkler 403 15.891 GPM 14.816 GPM 5.6 8.05 psi 0.132 GPM/ft² 120 ft²

Sprinkler 401 15.938 GPM 14.816 GPM 5.6 8.10 psi 0.133 GPM/ft² 120 ft²

Sprinkler 402 15.976 GPM 14.816 GPM 5.6 8.14 psi 0.133 GPM/ft² 120 ft²

Most Demanding Sprinkler Data

11/22/2021 Page 1AutoSPRINK RVT v2.2.27.0 3:57:41PM@ M.E.P.CAD, Inc.

Job Name: SPRINKLER DESIGN YCC 101 102 103

Remote Area Name: DORMITORY ATTIC LH Date: 11/22/2021

(psi) (psi)(GPM)(psi)(GPM)(psi)

Supply Analysis

Node Name Static Residual Flow Available Total Demand Required Pressure

30.00 psi1 33.15 psi385.137 GPM1182.000 GPM 42.24 psi44.00 psiWater Supply

Node Analysis

Discharge at

Node

(GPM)

Pressure at

Node

(psi)

Elevation (ft)Node Number Node Type Notes

12' - 1" 14.816 GPM7.00 psi Sprinklers

Coverage: 120 ft² Density: 0.123 GPM/ft²

12' - 1" 15.084 GPM7.25 psi Sprinklers

Coverage: 120 ft² Density: 0.126 GPM/ft²

12' - 1" 15.665 GPM7.82 psi Sprinklers

Coverage: 120 ft² Density: 0.131 GPM/ft²

10' - 0 1/2" 15.837 GPM8.00 psi Sprinklers

Coverage: 120 ft² Density: 0.132 GPM/ft²

10' - 1" 16.076 GPM8.24 psi Sprinklers

Coverage: 120 ft² Density: 0.134 GPM/ft²

10' - 1" 16.634 GPM8.82 psi Sprinklers

Coverage: 120 ft² Density: 0.139 GPM/ft²

14' - 1 1/2" 16.262 GPM8.43 psi Sprinklers

Coverage: 120 ft² Density: 0.136 GPM/ft²

14' - 1 1/2" 16.317 GPM8.49 psi Sprinklers

Coverage: 120 ft² Density: 0.136 GPM/ft²

14' - 1 1/2" 16.494 GPM8.67 psi Sprinklers

Coverage: 120 ft² Density: 0.137 GPM/ft²

9' - 10 1/2" 15.859 GPM8.02 psi Sprinklers

Coverage: 120 ft² Density: 0.132 GPM/ft²

9' - 11" 16.008 GPM8.17 psi Sprinklers

Coverage: 120 ft² Density: 0.133 GPM/ft²

9' - 10 1/2" 16.478 GPM8.66 psi Sprinklers

Coverage: 120 ft² Density: 0.137 GPM/ft²

12' - 1 3/4" 14.948 GPM7.13 psi Sprinklers

Coverage: 120 ft² Density: 0.125 GPM/ft²

11' - 11 3/4" 15.211 GPM7.38 psi Sprinklers

Coverage: 120 ft² Density: 0.127 GPM/ft²

12' - 0 1/2" 15.645 GPM7.81 psi Sprinklers

Coverage: 120 ft² Density: 0.130 GPM/ft²

9' - 11 1/4" 15.891 GPM8.05 psi Sprinklers

Coverage: 120 ft² Density: 0.132 GPM/ft²

9' - 11 1/4" 15.938 GPM8.10 psi Sprinklers

Coverage: 120 ft² Density: 0.133 GPM/ft²

9' - 9 3/4" 15.976 GPM8.14 psi Sprinklers

Coverage: 120 ft² Density: 0.133 GPM/ft²

-5' - 2 1/4" 285.137 GPM33.15 psi Supply

11/22/2021 Page 1AutoSPRINK RVT v2.2.27.0 3:57:42PM@ M.E.P.CAD, Inc.

Date: 11/22/2021

Remote Area Name: DORMITORY ATTIC LH

Flow added this step

Pipe Information

Node 1

Node 2

Elev 1 ft

Elev 2 ft

K-Factor

Q

Total Flow

Q

Nominal ID

Actual ID

Fittings &

Devices

Equiv.

Length ft

Length ft

Fitting ft

Total ft

C Factor or

Roughness

Pf Friction

Loss Per Unit psi

Total(Pt)

Elev(Pe)

Friction(Pf)

Notes

Fitting/Device (Equivalent Length)

Fixed Pressure Losses, when applicable, are added directly to (Pf) and shown as a negative value.

Velocity

3' - 6 3/4"

11' - 0 1/2" 4' - 8"

0.45 psi

0.49 psi

12' - 1" 1' - 1 1/4"

1.000

• • • • • Route 1 • • • • •

(See

Notes)

1.049

7.00 psi14.816 GPM

0.10 psi

Sprinkler,

14.816 GPM

5.6

T(3' - 6 3/4")

6 FPS

9' - 0 1/4" 6' - 5"

0.88 psi

0.18 psi

11' - 0 1/2" 6' - 5"

1.250

1.380

7.94 psi

0.03 psi14.816 GPM

3 FPS

4' - 3 1/4"

8' - 9 1/4" 5' - 0 1/2"

0.10 psi

0.53 psi

9' - 0 1/4" 0' - 9 1/4"

1.250 (See

Notes)

1.380

9.00 psi15.837 GPM

0.11 psi

Flow (q) from Route 7

30.653 GPM T(4' - 3 1/4")

7 FPS

8' - 9" 14' - 1"

0.01 psi

0.31 psi

8' - 9 1/4" 14' - 1"

2.500

2.469

9.63 psi29.617 GPM

0.02 psi

Flow (q) from Route 10

60.269 GPM

4 FPS

8' - 8 1/2" 14' - 1"

0.01 psi

0.66 psi

8' - 9" 14' - 1"

2.500

2.469

9.95 psi31.159 GPM

0.05 psi

Flow (q) from Route 3

91.428 GPM

6 FPS

12' - 10"

8' - 7 3/4" 48' - 9"

0.03 psi

4.00 psi

8' - 8 1/2" 35' - 11"

2.500 (See

Notes)

2.469

10.62 psi32.299 GPM

0.08 psi

Flow (q) from Route 6

123.727 GPM E(4' - 3 1/4"), T(8' - 6 3/4")

8 FPS

10' - 8 1/4"

8' - 7 1/4" 30' - 7 1/4"

0.01 psi

4.09 psi

8' - 7 3/4" 19' - 11"

3.000 (See

Notes)

3.068

14.66 psi161.409 GPM

0.13 psi

Flow (q) from Route 2

285.137 GPM T(10' - 8 1/4")

12 FPS

2' - 1 1/4" 6' - 6 1/4"

2.83 psi

4.75 psi

8' - 7 1/4" 6' - 6 1/4"

4.000 (See

Notes)

4.026

18.76 psi

0.04 psi285.137 GPM DPV(-0.52 psi), BOR, BFP(-4.

00 psi)

7 FPS

14' - 3"

-2' - 6 1/4" 41' - 4 1/2"

2.00 psi

1.47 psi

2' - 1 1/4" 27' - 1 1/4"

4.000 (See

Notes)

4.026

26.34 psi

0.04 psi285.137 GPM 2E(7' - 1 1/2")

7 FPS

7' - 1 1/2"

-5' - 2 1/4" 9' - 9 1/2"

1.16 psi

0.35 psi

-2' - 6 1/4" 2' - 8"

4.000 (See

Notes)

4.026

29.81 psi

0.04 psi285.137 GPM E(7' - 1 1/2")

7 FPS

1' - 5"

-5' - 2 1/4" 51' - 5 1/2" 1.83 psi

-5' - 2 1/4" 50' - 0 1/4"

4.000 (See

Notes)

4.026

31.32 psi

0.04 psi285.137 GPM PIV(1' - 5"), S

7 FPS

11/22/2021 Page 1AutoSPRINK RVT v2.2.27.0 3:57:43PMDORMITORY ATTIC LH@ M.E.P.CAD, Inc.

Remote Area Name: DORMITORY ATTIC LH

Flow added this step

Pipe Information

Node 1

Node 2

Elev 1 ft

Elev 2 ft

K-Factor

Q

Total Flow

Q

Nominal ID

Actual ID

Fittings &

Devices

Equiv.

Length ft

Length ft

Fitting ft

Total ft

C Factor or

Roughness

Pf Friction

Loss Per Unit psi

Total(Pt)

Elev(Pe)

Friction(Pf)

Notes

Fitting/Device (Equivalent Length)

Fixed Pressure Losses, when applicable, are added directly to (Pf) and shown as a negative value.

Velocity

100.000 GPM Hose Allowance At Source

385.137 GPM

Route 1

33.15 psi

Total(Pt)

1' - 5"

11' - 4" 2' - 3 1/4"

0.35 psi

0.24 psi

12' - 1 3/4" 0' - 10 1/4"

1.000

• • • • • Route 2 • • • • •

(See

Notes)

1.049

7.13 psi14.948 GPM

0.11 psi

Sprinkler,

14.948 GPM

5.6

E(1' - 5")

6 FPS

9' - 0 1/4" 7' - 1 1/2"

1.00 psi

0.20 psi

11' - 4" 7' - 1 1/2"

1.250

1.380

7.72 psi

0.03 psi14.948 GPM

3 FPS

4' - 3 1/4"

8' - 9 1/2" 5' - 0"

0.10 psi

0.53 psi

9' - 0 1/4" 0' - 8 3/4"

1.250 (See

Notes)

1.380

8.92 psi15.859 GPM

0.11 psi

Flow (q) from Route 8

30.808 GPM T(4' - 3 1/4")

7 FPS

8' - 9" 14' - 1"

0.01 psi

0.21 psi

8' - 9 1/2" 14' - 1"

2.500

2.469

9.55 psi18.187 GPM

0.01 psi

Flow (q) from Route 9

48.995 GPM

3 FPS

8' - 8 3/4" 14' - 1 1/4"

0.01 psi

0.52 psi

8' - 9" 14' - 1 1/4"

2.500

2.469

9.78 psi31.219 GPM

0.04 psi

Flow (q) from Route 4

80.214 GPM

5 FPS

4' - 3 1/4"

8' - 7 3/4" 41' - 11 1/2"

0.03 psi

2.88 psi

8' - 8 3/4" 37' - 8 1/4"

2.500 (See

Notes)

2.469

10.31 psi32.123 GPM

0.07 psi

Flow (q) from Route 5

112.337 GPM E(4' - 3 1/4")

8 FPS

8' - 6 3/4"

8' - 7 3/4" 10' - 5 1/4"

0.00 psi

1.40 psi

8' - 7 3/4" 1' - 10 1/2"

2.500 (See

Notes)

2.469

13.22 psi49.073 GPM

0.13 psi

Flow (q) from Route 14

161.409 GPM T(8' - 6 3/4")

11 FPS

8' - 7 3/4" 0' - 8 1/2"

0.00 psi

0.03 psi

8' - 7 3/4" 0' - 8 1/2"

3.000

3.068

14.63 psi

0.05 psi161.409 GPM

7 FPS

14.66 psi Route 2Total(Pt)

3' - 6 3/4"

11' - 0 1/4" 4' - 8 1/4"

0.46 psi

0.51 psi

12' - 1" 1' - 1 1/2"

1.000

• • • • • Route 3 • • • • •

(See

Notes)

1.049

7.25 psi15.084 GPM

0.11 psi

Sprinkler,

15.084 GPM

5.6

T(3' - 6 3/4")

6 FPS

11/22/2021 Page 2AutoSPRINK RVT v2.2.27.0 3:57:43PMDORMITORY ATTIC LH@ M.E.P.CAD, Inc.

Remote Area Name: DORMITORY ATTIC LH

Flow added this step

Pipe Information

Node 1

Node 2

Elev 1 ft

Elev 2 ft

K-Factor

Q

Total Flow

Q

Nominal ID

Actual ID

Fittings &

Devices

Equiv.

Length ft

Length ft

Fitting ft

Total ft

C Factor or

Roughness

Pf Friction

Loss Per Unit psi

Total(Pt)

Elev(Pe)

Friction(Pf)

Notes

Fitting/Device (Equivalent Length)

Fixed Pressure Losses, when applicable, are added directly to (Pf) and shown as a negative value.

Velocity

9' - 0 1/4" 6' - 4"

0.87 psi

0.18 psi

11' - 0 1/4" 6' - 4"

1.250

1.380

8.22 psi

0.03 psi15.084 GPM

3 FPS

4' - 3 1/4"

8' - 9" 5' - 1 3/4"

0.12 psi

0.56 psi

9' - 0 1/4" 0' - 10 1/4"

1.250 (See

Notes)

1.380

9.27 psi16.076 GPM

0.11 psi

Flow (q) from Route 13

31.159 GPM T(4' - 3 1/4")

7 FPS

9.95 psi Route 3Total(Pt)

1' - 5"

11' - 3" 2' - 2 1/4"

0.31 psi

0.24 psi

11' - 11 3/4" 0' - 9"

1.000

• • • • • Route 4 • • • • •

(See

Notes)

1.049

7.38 psi15.211 GPM

0.11 psi

Sprinkler,

15.211 GPM

5.6

E(1' - 5")

6 FPS

9' - 0 1/4" 7' - 0 1/4"

0.97 psi

0.20 psi

11' - 3" 7' - 0 1/4"

1.250

1.380

7.93 psi

0.03 psi15.211 GPM

3 FPS

4' - 3 1/4"

8' - 9" 5' - 1 1/2"

0.12 psi

0.56 psi

9' - 0 1/4" 0' - 10"

1.250 (See

Notes)

1.380

9.10 psi16.008 GPM

0.11 psi

Flow (q) from Route 12

31.219 GPM T(4' - 3 1/4")

7 FPS

9.78 psi Route 4Total(Pt)

1' - 5"

11' - 2 1/2" 2' - 3 1/2"

0.36 psi

0.27 psi

12' - 0 1/2" 0' - 10 1/2"

1.000

• • • • • Route 5 • • • • •

(See

Notes)

1.049

7.81 psi15.645 GPM

0.12 psi

Sprinkler,

15.645 GPM

5.6

E(1' - 5")

6 FPS

8' - 11 1/2" 7' - 1 1/2"

0.98 psi

0.22 psi

11' - 2 1/2" 7' - 1 1/2"

1.250

1.380

8.43 psi

0.03 psi15.645 GPM

3 FPS

4' - 3 1/4"

8' - 8 3/4" 5' - 0 1/4"

0.10 psi

0.58 psi

8' - 11 1/2" 0' - 9"

1.250 (See

Notes)

1.380

9.63 psi16.478 GPM

0.12 psi

Flow (q) from Route 16

32.123 GPM T(4' - 3 1/4")

7 FPS

10.31 psi Route 5Total(Pt)

3' - 6 3/4"

11' - 0" 4' - 8 1/2"

0.47 psi

0.55 psi

12' - 1" 1' - 1 3/4"

1.000

• • • • • Route 6 • • • • •

(See

Notes)

1.049

7.82 psi15.665 GPM

0.12 psi

Sprinkler,

15.665 GPM

5.6

T(3' - 6 3/4")

6 FPS

9' - 0" 6' - 4"

0.87 psi

0.19 psi

11' - 0" 6' - 4"

1.250

1.380

8.84 psi

0.03 psi15.665 GPM

3 FPS

11/22/2021 Page 3AutoSPRINK RVT v2.2.27.0 3:57:43PMDORMITORY ATTIC LH@ M.E.P.CAD, Inc.

Remote Area Name: DORMITORY ATTIC LH

Flow added this step

Pipe Information

Node 1

Node 2

Elev 1 ft

Elev 2 ft

K-Factor

Q

Total Flow

Q

Nominal ID

Actual ID

Fittings &

Devices

Equiv.

Length ft

Length ft

Fitting ft

Total ft

C Factor or

Roughness

Pf Friction

Loss Per Unit psi

Total(Pt)

Elev(Pe)

Friction(Pf)

Notes

Fitting/Device (Equivalent Length)

Fixed Pressure Losses, when applicable, are added directly to (Pf) and shown as a negative value.

Velocity

4' - 3 1/4"

8' - 8 1/2" 5' - 1 3/4"

0.12 psi

0.60 psi

9' - 0" 0' - 10 1/4"

1.250 (See

Notes)

1.380

9.91 psi16.634 GPM

0.12 psi

Flow (q) from Route 18

32.299 GPM T(4' - 3 1/4")

7 FPS

10.62 psi Route 6Total(Pt)

3' - 6 3/4"

9' - 0 1/4" 4' - 7 3/4"

0.45 psi

0.55 psi

10' - 0 1/2" 1' - 1"

1.000

• • • • • Route 7 • • • • •

(See

Notes)

1.049

8.00 psi15.837 GPM

0.12 psi

Sprinkler,

15.837 GPM

5.6

T(3' - 6 3/4")

6 FPS

9.00 psi Route 7Total(Pt)

3' - 6 3/4"

9' - 0 1/4" 4' - 5 1/2"

0.37 psi

0.53 psi

9' - 10 1/2" 0' - 10 3/4"

1.000

• • • • • Route 8 • • • • •

(See

Notes)

1.049

8.02 psi15.859 GPM

0.12 psi

Sprinkler,

15.859 GPM

5.6

T(3' - 6 3/4")

6 FPS

8.92 psi Route 8Total(Pt)

5' - 0"

8' - 9 3/4" 8' - 0 1/2"

0.49 psi

0.96 psi

9' - 11 1/4" 3' - 0 1/2"

1.000

• • • • • Route 9 • • • • •

(See

Notes)

1.049

8.05 psi15.891 GPM

0.12 psi

Sprinkler,

15.891 GPM

5.6

E(1' - 5"), T(3' - 6 3/4")

6 FPS

8' - 9 3/4" 12' - 6 1/4"

0.00 psi

0.00 psi

8' - 9 3/4" 12' - 6 1/4"

2.500

2.469

9.50 psi

0.00 psi2.212 GPM

0 FPS

4' - 3 1/4"

8' - 9 1/2" 17' - 10 3/4"

0.01 psi

0.04 psi

8' - 9 3/4" 13' - 7 1/2"

2.500 (See

Notes)

2.469

9.50 psi15.976 GPM

0.00 psi

Flow (q) from Route 11

18.187 GPM E(4' - 3 1/4")

1 FPS

9.55 psi Route 9Total(Pt)

5' - 0"

8' - 9 1/2" 7' - 9 1/2"

0.50 psi

0.93 psi

9' - 11 1/4" 2' - 9 1/2"

1.000

• • • • • Route 10 • • • • •

(See

Notes)

1.049

8.10 psi15.938 GPM

0.12 psi

Sprinkler,

15.938 GPM

5.6

E(1' - 5"), T(3' - 6 3/4")

6 FPS

4' - 3 1/4"

8' - 9 1/4" 17' - 3"

0.00 psi

0.10 psi

8' - 9 1/2" 12' - 11 1/2"

2.500 (See

Notes)

2.469

9.53 psi13.679 GPM

0.01 psi

Flow (q) from Route 19

29.617 GPM E(4' - 3 1/4")

2 FPS

9.63 psi Route 10Total(Pt)

5' - 0"

8' - 9 3/4" 7' - 9"

0.43 psi

0.93 psi

9' - 9 3/4" 2' - 9"

1.000

• • • • • Route 11 • • • • •

(See

Notes)

1.049

8.14 psi15.976 GPM

0.12 psi

Sprinkler,

15.976 GPM

5.6

E(1' - 5"), T(3' - 6 3/4")

6 FPS

9.50 psi Route 11Total(Pt)

11/22/2021 Page 4AutoSPRINK RVT v2.2.27.0 3:57:43PMDORMITORY ATTIC LH@ M.E.P.CAD, Inc.

Remote Area Name: DORMITORY ATTIC LH

Flow added this step

Pipe Information

Node 1

Node 2

Elev 1 ft

Elev 2 ft

K-Factor

Q

Total Flow

Q

Nominal ID

Actual ID

Fittings &

Devices

Equiv.

Length ft

Length ft

Fitting ft

Total ft

C Factor or

Roughness

Pf Friction

Loss Per Unit psi

Total(Pt)

Elev(Pe)

Friction(Pf)

Notes

Fitting/Device (Equivalent Length)

Fixed Pressure Losses, when applicable, are added directly to (Pf) and shown as a negative value.

Velocity

3' - 6 3/4"

9' - 0 1/4" 4' - 6"

0.39 psi

0.54 psi

9' - 11" 0' - 11 1/4"

1.000

• • • • • Route 12 • • • • •

(See

Notes)

1.049

8.17 psi16.008 GPM

0.12 psi

Sprinkler,

16.008 GPM

5.6

T(3' - 6 3/4")

6 FPS

9.10 psi Route 12Total(Pt)

3' - 6 3/4"

9' - 0 1/4" 4' - 8 1/4"

0.46 psi

0.57 psi

10' - 1" 1' - 1 1/2"

1.000

• • • • • Route 13 • • • • •

(See

Notes)

1.049

8.24 psi16.076 GPM

0.12 psi

Sprinkler,

16.076 GPM

5.6

T(3' - 6 3/4")

6 FPS

9.27 psi Route 13Total(Pt)

3' - 6 3/4"

13' - 3 1/2" 4' - 5"

0.37 psi

0.55 psi

14' - 1 1/2" 0' - 10"

1.000

• • • • • Route 14 • • • • •

(See

Notes)

1.049

8.43 psi16.262 GPM

0.12 psi

Sprinkler,

16.262 GPM

5.6

T(3' - 6 3/4")

6 FPS

13' - 3" 14' - 0 3/4"

0.01 psi

0.06 psi

13' - 3 1/2" 14' - 0 3/4"

2.000

2.067

9.35 psi

0.00 psi16.262 GPM

2 FPS

13' - 2 3/4" 12' - 0 1/2"

0.01 psi

0.20 psi

13' - 3" 12' - 0 1/2"

2.000

2.067

9.42 psi16.317 GPM

0.02 psi

Flow (q) from Route 15

32.579 GPM

3 FPS

3' - 6 3/4"

13' - 2" 29' - 3 1/4"

0.02 psi

1.03 psi

13' - 2 3/4" 25' - 8 1/2"

2.000 (See

Notes)

2.067

9.63 psi16.494 GPM

0.04 psi

Flow (q) from Route 17

49.073 GPM E(3' - 6 3/4")

5 FPS

3' - 6 3/4"

8' - 8" 8' - 1"

1.96 psi

0.29 psi

13' - 2" 4' - 6 1/4"

2.000 (See

Notes)

2.067

10.69 psi

0.04 psi49.073 GPM E(3' - 6 3/4")

5 FPS

7' - 1 1/2"

8' - 7 3/4" 8' - 1 3/4"

0.00 psi

0.29 psi

8' - 8" 1' - 0 1/4"

2.000 (See

Notes)

2.067

12.93 psi

0.04 psi49.073 GPM T(7' - 1 1/2")

5 FPS

13.22 psi Route 14Total(Pt)

3' - 6 3/4"

13' - 3" 4' - 5 1/4"

0.38 psi

0.56 psi

14' - 1 1/2" 0' - 10 1/2"

1.000

• • • • • Route 15 • • • • •

(See

Notes)

1.049

8.49 psi16.317 GPM

0.13 psi

Sprinkler,

16.317 GPM

5.6

T(3' - 6 3/4")

6 FPS

9.42 psi Route 15Total(Pt)

11/22/2021 Page 5AutoSPRINK RVT v2.2.27.0 3:57:43PMDORMITORY ATTIC LH@ M.E.P.CAD, Inc.

Remote Area Name: DORMITORY ATTIC LH

Flow added this step

Pipe Information

Node 1

Node 2

Elev 1 ft

Elev 2 ft

K-Factor

Q

Total Flow

Q

Nominal ID

Actual ID

Fittings &

Devices

Equiv.

Length ft

Length ft

Fitting ft

Total ft

C Factor or

Roughness

Pf Friction

Loss Per Unit psi

Total(Pt)

Elev(Pe)

Friction(Pf)

Notes

Fitting/Device (Equivalent Length)

Fixed Pressure Losses, when applicable, are added directly to (Pf) and shown as a negative value.

Velocity

3' - 6 3/4"

8' - 11 1/2" 4' - 6 1/4"

0.39 psi

0.58 psi

9' - 10 1/2" 0' - 11 1/2"

1.000

• • • • • Route 16 • • • • •

(See

Notes)

1.049

8.66 psi16.478 GPM

0.13 psi

Sprinkler,

16.478 GPM

5.6

T(3' - 6 3/4")

6 FPS

9.63 psi Route 16Total(Pt)

3' - 6 3/4"

13' - 2 3/4" 4' - 5 1/2"

0.39 psi

0.57 psi

14' - 1 1/2" 0' - 10 3/4"

1.000

• • • • • Route 17 • • • • •

(See

Notes)

1.049

8.67 psi16.494 GPM

0.13 psi

Sprinkler,

16.494 GPM

5.6

T(3' - 6 3/4")

6 FPS

9.63 psi Route 17Total(Pt)

3' - 6 3/4"

9' - 0" 4' - 8 1/2"

0.47 psi

0.61 psi

10' - 1" 1' - 1 3/4"

1.000

• • • • • Route 18 • • • • •

(See

Notes)

1.049

8.82 psi16.634 GPM

0.13 psi

Sprinkler,

16.634 GPM

5.6

T(3' - 6 3/4")

6 FPS

9.91 psi Route 18Total(Pt)

8' - 9 1/2" 12' - 6 3/4"

0.01 psi

0.02 psi

8' - 9 3/4" 12' - 6 3/4"

2.500

• • • • • Route 19 • • • • •

2.469

9.50 psi2.212 GPM

0.00 psi

Flow (q) from Route 9

13.679 GPM

1 FPS

9.53 psi Route 19Total(Pt)

11/22/2021 Page 6AutoSPRINK RVT v2.2.27.0 3:57:43PMDORMITORY ATTIC LH@ M.E.P.CAD, Inc.

Remote Area Name: DORMITORY ATTIC LH

1.51

Fittings Legend

BFP Backflow Preventer DPV Dry Pipe Valve E 90° Elbow

PIV Post Indicating Valve S Supply Spr Sprinkler

T Tee Flow Turn 90°

4.87

1.33

1.16

0.713

Equivalent Pipe Lengths of Valves and Fittings (C=120 only)

Actual Inside Diameter

Schedule 40 Steel Pipe Inside Diameter = Factor

C Value Multiplier

Value Of C

Multiplying Factor

11/22/2021 Page 7AutoSPRINK RVT v2.2.27.0 3:57:43PMDORMITORY ATTIC LH@ M.E.P.CAD, Inc.

THIS PAGE INTENTIONALLY LEFT BLANK

Drawing Name: PF002240.05-F20_zparksLKHUF Calculation Date:11/22/2021

Hydraulic Calculations Summary for

Design

Light Hazard

1950 ft²

122 ft² (average)

DORMITORY FLOOR LH

0.100 GPM/ft²

Remote Area Name:

Occupancy Classification:

Density

Area of Application:

Coverage per Sprinkler:

Type of Sprinklers Calculated:

No. of Sprinklers Calculated:

at Node:

Fire Protection Dry

N/AN/A

1100.000 GPM

286.1 galType of System:

In-rack Demand:

Hose Streams:

Volume of Dry or PreAction System:

at Node:

Type Allowance at Source

Total Water Required (including Hose Streams where applicable)

38.58 psi@398.415 GPMFROM: Water Supply at Node 1:

3.55 psiSafety Margin:

POOLE FIRE PROTECTION

BRITTON GRAY

19910 W 161ST ST, OLATHE KS 66062

913-829-8650 ZACHARY PARKS

Contact Name

Address:

Phone Number:

Authority Having Jurisdiction:

Name of Designer:

Automatic Peaking Results

11/22/2021 Page 1AutoSPRINK RVT v2.2.27.0 3:57:04PMDORMITORY FLOOR LH@ M.E.P.CAD, Inc.

Node: 1

Job Name: SPRINKLER DESIGN YCC 101 102 103

Remote Area Name: DORMITORY FLOOR LH Date: 11/22/2021 N 1.85

Summary Sheet

No pressure is being required from the Source/Supply to meet the demand (by a margin of this negative value).

A negative result in Required Pressure indicates that the Pump is capable of furnishing all of the pressure required by the demand reported within this calculation.

11/22/2021 Page 1AutoSPRINK RVT v2.2.27.0 3:57:05PM@ M.E.P.CAD, Inc.

Report Description: Light Hazard

Job Number: 2240.05

(ft²)Device

Actual Flow Minimum Flow K-Factor Pressure

Sprinkler 301 18.363 GPM 16.900 GPM 5.6 10.75 psi 0.109 GPM/ft² 169 ft²

Sprinkler 305 17.245 GPM 16.900 GPM 5.6 9.48 psi 0.102 GPM/ft² 169 ft²

Sprinkler 307 16.913 GPM 16.900 GPM 5.6 9.12 psi 0.100 GPM/ft² 169 ft²

Sprinkler 302 18.350 GPM 16.900 GPM 5.6 10.74 psi 0.109 GPM/ft² 169 ft²

Sprinkler 306 17.235 GPM 16.900 GPM 5.6 9.47 psi 0.102 GPM/ft² 169 ft²

Sprinkler 308 16.900 GPM 16.900 GPM 5.6 9.11 psi 0.100 GPM/ft² 169 ft²

Sprinkler 312 19.423 GPM 16.900 GPM 5.6 12.03 psi 0.115 GPM/ft² 169 ft²

Sprinkler 316 19.774 GPM 16.900 GPM 5.6 12.47 psi 0.117 GPM/ft² 169 ft²

Sprinkler 304 17.888 GPM 14.816 GPM 5.6 10.20 psi 0.199 GPM/ft² 90 ft²

Sprinkler 309 17.477 GPM 14.816 GPM 5.6 9.74 psi 0.194 GPM/ft² 90 ft²

Sprinkler 317 20.261 GPM 14.816 GPM 5.6 13.09 psi 0.225 GPM/ft² 90 ft²

Sprinkler 303 19.004 GPM 14.816 GPM 5.6 11.52 psi 0.396 GPM/ft² 48 ft²

Sprinkler 310 19.299 GPM 14.816 GPM 5.6 11.88 psi 0.643 GPM/ft² 30 ft²

Sprinkler 311 20.896 GPM 14.816 GPM 5.6 13.92 psi 0.174 GPM/ft² 120 ft²

Sprinkler 315 19.580 GPM 14.816 GPM 5.6 12.22 psi 0.529 GPM/ft² 37 ft²

Sprinkler 314 19.806 GPM 14.816 GPM 5.6 12.51 psi 0.220 GPM/ft² 90 ft²

11/22/2021 Page 1AutoSPRINK RVT v2.2.27.0 3:57:05PM@ M.E.P.CAD, Inc.

Remote Area Name: DORMITORY FLOOR LH Date: 11/22/2021

(psi) (psi)(GPM)(psi)(GPM)(psi)

Supply Analysis

Node Name Static Residual Flow Available Total Demand Required Pressure

30.00 psi1 38.58 psi398.415 GPM1182.000 GPM 42.13 psi44.00 psiWater Supply

Node Analysis

Discharge at

Node

(GPM)

Pressure at

Node

(psi)

Elevation (ft)Node Number Node Type Notes

8' - 0" 18.363 GPM10.75 psi Sprinklers

Coverage: 169 ft² Density: 0.109 GPM/ft²

8' - 0" 17.245 GPM9.48 psi Sprinklers

Coverage: 169 ft² Density: 0.102 GPM/ft²

8' - 0" 16.913 GPM9.12 psi Sprinklers

Coverage: 169 ft² Density: 0.100 GPM/ft²

8' - 0" 18.350 GPM10.74 psi Sprinklers

Coverage: 169 ft² Density: 0.109 GPM/ft²

8' - 0" 17.235 GPM9.47 psi Sprinklers

Coverage: 169 ft² Density: 0.102 GPM/ft²

8' - 0" 16.900 GPM9.11 psi Sprinklers

Coverage: 169 ft² Density: 0.100 GPM/ft²

8' - 0" 19.423 GPM12.03 psi Sprinklers

Coverage: 169 ft² Density: 0.115 GPM/ft²

8' - 0" 19.774 GPM12.47 psi Sprinklers

Coverage: 169 ft² Density: 0.117 GPM/ft²

8' - 0" 17.888 GPM10.20 psi Sprinklers

Coverage: 90 ft² Density: 0.199 GPM/ft²

8' - 0" 17.477 GPM9.74 psi Sprinklers

Coverage: 90 ft² Density: 0.194 GPM/ft²

8' - 0" 20.261 GPM13.09 psi Sprinklers

Coverage: 90 ft² Density: 0.225 GPM/ft²

8' - 0" 19.004 GPM11.52 psi Sprinklers

Coverage: 48 ft² Density: 0.396 GPM/ft²

8' - 0" 19.299 GPM11.88 psi Sprinklers

Coverage: 30 ft² Density: 0.643 GPM/ft²

8' - 0" 20.896 GPM13.92 psi Sprinklers

Coverage: 120 ft² Density: 0.174 GPM/ft²

8' - 0" 19.580 GPM12.22 psi Sprinklers

Coverage: 37 ft² Density: 0.529 GPM/ft²

8' - 0" 19.806 GPM12.51 psi Sprinklers

Coverage: 90 ft² Density: 0.220 GPM/ft²

-5' - 2 1/4" 298.415 GPM38.58 psi Supply

11/22/2021 Page 1AutoSPRINK RVT v2.2.27.0 3:57:06PM@ M.E.P.CAD, Inc.

Remote Area Name: DORMITORY FLOOR LH

Flow added this step

Pipe Information

Node 1

Node 2

Elev 1 ft

Elev 2 ft

K-Factor

Q

Total Flow

Q

Nominal ID

Actual ID

Fittings &

Devices

Equiv.

Length ft

Length ft

Fitting ft

Total ft

C Factor or

Roughness

Pf Friction

Loss Per Unit psi

Total(Pt)

Elev(Pe)

Friction(Pf)

Notes

Fitting/Device (Equivalent Length)

Fixed Pressure Losses, when applicable, are added directly to (Pf) and shown as a negative value.

Velocity

8' - 6 3/4"

8' - 11" 10' - 11 1/2"

-0.39 psi

1.46 psi

8' - 0" 2' - 4 3/4"

1.000

• • • • • Route 1 • • • • •

(See

Notes)

1.049

9.11 psi16.900 GPM

0.13 psi

Sprinkler,

16.900 GPM

5.6

2T(3' - 6 3/4"), Z, E(1' - 5")

6 FPS

8' - 10 1/4" 11' - 3 1/2"

0.02 psi

0.40 psi

8' - 11" 11' - 3 1/2"

1.250

1.380

10.18 psi

0.04 psi16.900 GPM

4 FPS

8' - 9 3/4" 11' - 3 1/2"

0.02 psi

1.46 psi

8' - 10 1/4" 11' - 3 1/2"

1.250

1.380

10.59 psi17.235 GPM

0.13 psi

Flow (q) from Route 3

34.135 GPM

7 FPS

4' - 3 1/4"

8' - 9 3/4" 7' - 7 3/4"

0.01 psi

2.18 psi

8' - 9 3/4" 3' - 4 1/2"

1.250 (See

Notes)

1.380

12.07 psi18.350 GPM

0.29 psi

Flow (q) from Route 5

52.486 GPM T(4' - 3 1/4")

11 FPS

4' - 3 1/4"

8' - 8 3/4" 44' - 1"

0.03 psi

1.48 psi

8' - 9 3/4" 39' - 9 3/4"

2.500 (See

Notes)

2.469

14.26 psi23.812 GPM

0.03 psi

Flow (q) from Route 11

76.298 GPM E(4' - 3 1/4")

5 FPS

4' - 3 1/4"

8' - 7 3/4" 40' - 6"

0.03 psi

2.13 psi

8' - 8 3/4" 36' - 2 1/2"

2.500 (See

Notes)

2.469

15.77 psi20.896 GPM

0.05 psi

Flow (q) from Route 16

97.194 GPM E(4' - 3 1/4")

7 FPS

8' - 6 3/4"

8' - 7 3/4" 14' - 7 1/4"

0.01 psi

1.43 psi

8' - 7 3/4" 6' - 0 1/2"

2.500 (See

Notes)

2.469

17.93 psi38.879 GPM

0.10 psi

Flow (q) from Route 12

136.073 GPM T(8' - 6 3/4")

9 FPS

8' - 7 3/4" 0' - 8 1/2"

0.00 psi

0.02 psi

8' - 7 3/4" 0' - 8 1/2"

3.000

3.068

19.37 psi

0.03 psi136.073 GPM

6 FPS

10' - 8 1/4"

8' - 7 1/4" 30' - 7 1/4"

0.01 psi

4.45 psi

8' - 7 3/4" 19' - 11"

3.000 (See

Notes)

3.068

19.39 psi162.342 GPM

0.15 psi

Flow (q) from Route 2

298.415 GPM T(10' - 8 1/4")

13 FPS

2' - 1 1/4" 6' - 6 1/4"

2.83 psi

4.77 psi

8' - 7 1/4" 6' - 6 1/4"

4.000 (See

Notes)

4.026

23.85 psi

0.04 psi298.415 GPM DPV(-0.52 psi), BOR, BFP(-4.

00 psi)

8 FPS

14' - 3"

-2' - 6 1/4" 41' - 4 1/2"

2.00 psi

1.60 psi

2' - 1 1/4" 27' - 1 1/4"

4.000 (See

Notes)

4.026

31.45 psi

0.04 psi298.415 GPM 2E(7' - 1 1/2")

8 FPS

11/22/2021 Page 1AutoSPRINK RVT v2.2.27.0 3:57:07PMDORMITORY FLOOR LH@ M.E.P.CAD, Inc.

Remote Area Name: DORMITORY FLOOR LH

Flow added this step

Pipe Information

Node 1

Node 2

Elev 1 ft

Elev 2 ft

K-Factor

Q

Total Flow

Q

Nominal ID

Actual ID

Fittings &

Devices

Equiv.

Length ft

Length ft

Fitting ft

Total ft

C Factor or

Roughness

Pf Friction

Loss Per Unit psi

Total(Pt)

Elev(Pe)

Friction(Pf)

Notes

Fitting/Device (Equivalent Length)

Fixed Pressure Losses, when applicable, are added directly to (Pf) and shown as a negative value.

Velocity

7' - 1 1/2"

-5' - 2 1/4" 9' - 9 1/2"

1.16 psi

0.38 psi

-2' - 6 1/4" 2' - 8"

4.000 (See

Notes)

4.026

35.05 psi

0.04 psi298.415 GPM E(7' - 1 1/2")

8 FPS

1' - 5"

-5' - 2 1/4" 51' - 5 1/2" 1.99 psi

-5' - 2 1/4" 50' - 0 1/4"

4.000 (See

Notes)

4.026

36.59 psi

0.04 psi298.415 GPM PIV(1' - 5"), S

8 FPS

100.000 GPM Hose Allowance At Source

398.415 GPM

Route 1

38.58 psi

Total(Pt)

8' - 6 3/4"

8' - 10 1/2" 10' - 9"

-0.38 psi

1.44 psi

8' - 0" 2' - 2 1/2"

1.000

• • • • • Route 2 • • • • •

(See

Notes)

1.049

9.12 psi16.913 GPM

0.13 psi

Sprinkler,

16.913 GPM

5.6

2T(3' - 6 3/4"), Z, E(1' - 5")

6 FPS

8' - 10" 11' - 3 1/2"

0.02 psi

0.40 psi

8' - 10 1/2" 11' - 3 1/2"

1.250

1.380

10.18 psi

0.04 psi16.913 GPM

4 FPS

8' - 9 1/2" 11' - 3 1/2"

0.02 psi

1.46 psi

8' - 10" 11' - 3 1/2"

1.250

1.380

10.59 psi17.245 GPM

0.13 psi

Flow (q) from Route 4

34.158 GPM

7 FPS

4' - 3 1/4"

8' - 9 1/2" 7' - 7 3/4"

0.01 psi

2.19 psi

8' - 9 1/2" 3' - 4 1/2"

1.250 (See

Notes)

1.380

12.07 psi18.363 GPM

0.29 psi

Flow (q) from Route 6

52.521 GPM T(4' - 3 1/4")

11 FPS

8' - 6 3/4"

8' - 8" 76' - 6 3/4"

0.05 psi

3.01 psi

8' - 9 1/2" 68' - 0"

2.500 (See

Notes)

2.469

14.26 psi30.557 GPM

0.04 psi

Flow (q) from Route 7

83.078 GPM 2E(4' - 3 1/4")

6 FPS

8' - 7 3/4" 8' - 0 1/2"

0.01 psi

0.65 psi

8' - 8" 8' - 0 1/2"

2.500

2.469

17.32 psi39.197 GPM

0.08 psi

Flow (q) from Route 8

122.275 GPM

8 FPS

8' - 6 3/4"

8' - 7 3/4" 10' - 4 3/4"

0.00 psi

1.41 psi

8' - 7 3/4" 1' - 10"

2.500 (See

Notes)

2.469

17.98 psi40.067 GPM

0.14 psi

Flow (q) from Route 14

162.342 GPM T(8' - 6 3/4")

11 FPS

19.39 psi Route 2Total(Pt)

11/22/2021 Page 2AutoSPRINK RVT v2.2.27.0 3:57:07PMDORMITORY FLOOR LH@ M.E.P.CAD, Inc.

Remote Area Name: DORMITORY FLOOR LH

Flow added this step

Pipe Information

Node 1

Node 2

Elev 1 ft

Elev 2 ft

K-Factor

Q

Total Flow

Q

Nominal ID

Actual ID

Fittings &

Devices

Equiv.

Length ft

Length ft

Fitting ft

Total ft

C Factor or

Roughness

Pf Friction

Loss Per Unit psi

Total(Pt)

Elev(Pe)

Friction(Pf)

Notes

Fitting/Device (Equivalent Length)

Fixed Pressure Losses, when applicable, are added directly to (Pf) and shown as a negative value.

Velocity

8' - 6 3/4"

8' - 10 1/4" 10' - 9 1/2"

-0.37 psi

1.49 psi

8' - 0" 2' - 2 3/4"

1.000

• • • • • Route 3 • • • • •

(See

Notes)

1.049

9.47 psi17.235 GPM

0.14 psi

Sprinkler,

17.235 GPM

5.6

2T(3' - 6 3/4"), Z, E(1' - 5")

6 FPS

10.59 psi Route 3Total(Pt)

8' - 6 3/4"

8' - 10" 10' - 7 1/2"

-0.36 psi

1.47 psi

8' - 0" 2' - 1"

1.000

• • • • • Route 4 • • • • •

(See

Notes)

1.049

9.48 psi17.245 GPM

0.14 psi

Sprinkler,

17.245 GPM

5.6

2T(3' - 6 3/4"), Z, E(1' - 5")

6 FPS

10.59 psi Route 4Total(Pt)

8' - 6 3/4"

8' - 9 3/4" 10' - 10"

-0.36 psi

1.68 psi

8' - 0" 2' - 3 1/4"

1.000

• • • • • Route 5 • • • • •

(See

Notes)

1.049

10.74 psi18.350 GPM

0.16 psi

Sprinkler,

18.350 GPM

5.6

2T(3' - 6 3/4"), Z, E(1' - 5")

7 FPS

12.07 psi Route 5Total(Pt)

8' - 6 3/4"

8' - 9 1/2" 10' - 8"

-0.35 psi

1.66 psi

8' - 0" 2' - 1 1/2"

1.000

• • • • • Route 6 • • • • •

(See

Notes)

1.049

10.75 psi18.363 GPM

0.16 psi

Sprinkler,

18.363 GPM

5.6

2T(3' - 6 3/4"), Z, E(1' - 5")

7 FPS

12.07 psi Route 6Total(Pt)

8' - 6 3/4"

8' - 10 1/2" 13' - 11 1/4"

-0.38 psi

1.98 psi

8' - 0" 5' - 4 3/4"

1.000

• • • • • Route 7 • • • • •

(See

Notes)

1.049

9.74 psi17.477 GPM

0.14 psi

Sprinkler,

17.477 GPM

5.6

2T(3' - 6 3/4"), Z, E(1' - 5")

6 FPS

8' - 10" 14' - 5 3/4"

0.02 psi

0.54 psi

8' - 10 1/2" 14' - 5 3/4"

1.250

1.380

11.34 psi

0.04 psi17.477 GPM

4 FPS

4' - 3 1/4"

8' - 9 1/2" 16' - 7 3/4"

0.02 psi

2.29 psi

8' - 10" 12' - 4 1/2"

1.250 (See

Notes)

1.380

11.90 psi17.888 GPM

0.14 psi

Flow (q) from Route 9

35.365 GPM T(4' - 3 1/4")

8 FPS

8' - 9 1/2" 7' - 7"

0.00 psi

0.05 psi

8' - 9 1/2" 7' - 7"

2.500

2.469

14.21 psi

0.01 psi30.557 GPM

2 FPS

14.26 psi Route 7Total(Pt)

8' - 6 3/4"

8' - 10 1/2" 10' - 8"

-0.38 psi

1.84 psi

8' - 0" 2' - 1 1/2"

1.000

• • • • • Route 8 • • • • •

(See

Notes)

1.049

12.03 psi19.423 GPM

0.17 psi

Sprinkler,

19.423 GPM

5.6

2T(3' - 6 3/4"), Z, E(1' - 5")

11/22/2021 Page 3AutoSPRINK RVT v2.2.27.0 3:57:07PMDORMITORY FLOOR LH@ M.E.P.CAD, Inc.

Remote Area Name: DORMITORY FLOOR LH

Flow added this step

Pipe Information

Node 1

Node 2

Elev 1 ft

Elev 2 ft

K-Factor

Q

Total Flow

Q

Nominal ID

Actual ID

Fittings &

Devices

Equiv.

Length ft

Length ft

Fitting ft

Total ft

C Factor or

Roughness

Pf Friction

Loss Per Unit psi

Total(Pt)

Elev(Pe)

Friction(Pf)

Notes

Fitting/Device (Equivalent Length)

Fixed Pressure Losses, when applicable, are added directly to (Pf) and shown as a negative value.

Velocity

8' - 9 1/4" 11' - 4 1/4"

0.04 psi

0.52 psi

8' - 10 1/2" 11' - 4 1/4"

1.250

1.380

13.49 psi

0.05 psi19.423 GPM

4 FPS

4' - 3 1/4"

8' - 8" 19' - 4 1/4"

0.05 psi

3.22 psi

8' - 9 1/4" 15' - 1"

1.250 (See

Notes)

1.380

14.05 psi19.774 GPM

0.17 psi

Flow (q) from Route 10

39.197 GPM T(4' - 3 1/4")

8 FPS

17.32 psi Route 8Total(Pt)

8' - 6 3/4"

8' - 10" 13' - 10 1/2"

-0.36 psi

2.06 psi

8' - 0" 5' - 4"

1.000

• • • • • Route 9 • • • • •

(See

Notes)

1.049

10.20 psi17.888 GPM

0.15 psi

Sprinkler,

17.888 GPM

5.6

2T(3' - 6 3/4"), Z, E(1' - 5")

7 FPS

11.90 psi Route 9Total(Pt)

8' - 6 3/4"

8' - 9 1/4" 10' - 9"

-0.34 psi

1.92 psi

8' - 0" 2' - 2 1/4"

1.000

• • • • • Route 10 • • • • •

(See

Notes)

1.049

12.47 psi19.774 GPM

0.18 psi

Sprinkler,

19.774 GPM

5.6

2T(3' - 6 3/4"), Z, E(1' - 5")

7 FPS

14.05 psi Route 10Total(Pt)

12' - 1 1/2"

8' - 9 3/4" 18' - 3 3/4"

-0.35 psi

3.04 psi

8' - 0" 6' - 2 1/4"

1.000

• • • • • Route 11 • • • • •

(See

Notes)

1.049

11.52 psi19.004 GPM

0.17 psi

Sprinkler,

19.004 GPM

5.6

3T(3' - 6 3/4"), 2Z, E(1' - 5")

7 FPS

8' - 9 3/4" 13' - 2"

0.00 psi

0.05 psi

8' - 9 3/4" 13' - 2"

2.500

2.469

14.20 psi4.808 GPM

0.00 psi

Flow (q) from Route 17

23.812 GPM

2 FPS

14.26 psi Route 11Total(Pt)

8' - 6 3/4"

8' - 9 1/4" 11' - 4"

-0.33 psi

1.93 psi

8' - 0" 2' - 9 1/4"

1.000

• • • • • Route 12 • • • • •

(See

Notes)

1.049

11.88 psi19.299 GPM

0.17 psi

Sprinkler,

19.299 GPM

5.6

2T(3' - 6 3/4"), Z, E(1' - 5")

7 FPS

8' - 9" 7' - 2"

0.01 psi

0.32 psi

8' - 9 1/4" 7' - 2"

1.250

1.380

13.48 psi

0.04 psi19.299 GPM

4 FPS

4' - 3 1/4"

8' - 7 3/4" 24' - 10 3/4"

0.04 psi

4.08 psi

8' - 9" 20' - 7 1/4"

1.250 (See

Notes)

1.380

13.81 psi19.580 GPM

0.16 psi

Flow (q) from Route 13

38.879 GPM T(4' - 3 1/4")

8 FPS

17.93 psi Route 12Total(Pt)

11/22/2021 Page 4AutoSPRINK RVT v2.2.27.0 3:57:07PMDORMITORY FLOOR LH@ M.E.P.CAD, Inc.

Remote Area Name: DORMITORY FLOOR LH

Flow added this step

Pipe Information

Node 1

Node 2

Elev 1 ft

Elev 2 ft

K-Factor

Q

Total Flow

Q

Nominal ID

Actual ID

Fittings &

Devices

Equiv.

Length ft

Length ft

Fitting ft

Total ft

C Factor or

Roughness

Pf Friction

Loss Per Unit psi

Total(Pt)

Elev(Pe)

Friction(Pf)

Notes

Fitting/Device (Equivalent Length)

Fixed Pressure Losses, when applicable, are added directly to (Pf) and shown as a negative value.

Velocity

8' - 6 3/4"

8' - 9" 10' - 10 1/2"

-0.32 psi

1.91 psi

8' - 0" 2' - 4"

1.000

• • • • • Route 13 • • • • •

(See

Notes)

1.049

12.22 psi19.580 GPM

0.18 psi

Sprinkler,

19.580 GPM

5.6

2T(3' - 6 3/4"), Z, E(1' - 5")

7 FPS

13.81 psi Route 13Total(Pt)

8' - 6 3/4"

8' - 10" 13' - 6 3/4"

-0.36 psi

2.43 psi

8' - 0" 5' - 0"

1.000

• • • • • Route 14 • • • • •

(See

Notes)

1.049

12.51 psi19.806 GPM

0.18 psi

Sprinkler,

19.806 GPM

5.6

2T(3' - 6 3/4"), Z, E(1' - 5")

7 FPS

8' - 8 3/4" 14' - 11 3/4"

0.05 psi

0.71 psi

8' - 10" 14' - 11 3/4"

1.250

1.380

14.58 psi

0.05 psi19.806 GPM

4 FPS

4' - 3 1/4"

8' - 7 3/4" 15' - 1"

0.03 psi

2.62 psi

8' - 8 3/4" 10' - 9 3/4"

1.250 (See

Notes)

1.380

15.33 psi20.261 GPM

0.17 psi

Flow (q) from Route 15

40.067 GPM T(4' - 3 1/4")

9 FPS

17.98 psi Route 14Total(Pt)

8' - 6 3/4"

8' - 8 3/4" 13' - 8"

-0.31 psi

2.55 psi

8' - 0" 5' - 1 1/4"

1.000

• • • • • Route 15 • • • • •

(See

Notes)

1.049

13.09 psi20.261 GPM

0.19 psi

Sprinkler,

20.261 GPM

5.6

2T(3' - 6 3/4"), Z, E(1' - 5")

8 FPS

15.33 psi Route 15Total(Pt)

8' - 6 3/4"

8' - 8 3/4" 10' - 11 1/4"

-0.32 psi

2.16 psi

8' - 0" 2' - 4 1/2"

1.000

• • • • • Route 16 • • • • •

(See

Notes)

1.049

13.92 psi20.896 GPM

0.20 psi

Sprinkler,

20.896 GPM

5.6

2T(3' - 6 3/4"), Z, E(1' - 5")

8 FPS

15.77 psi Route 16Total(Pt)

8' - 9 3/4" 2' - 9 1/2"

-0.01 psi

0.00 psi

8' - 9 1/2" 2' - 9 1/2"

2.500

• • • • • Route 17 • • • • •

2.469

14.21 psi30.557 GPM

0.00 psi

Flow (q) from Route 7

4.808 GPM

0 FPS

14.20 psi Route 17Total(Pt)

11/22/2021 Page 5AutoSPRINK RVT v2.2.27.0 3:57:07PMDORMITORY FLOOR LH@ M.E.P.CAD, Inc.

Remote Area Name: DORMITORY FLOOR LH

1.51

Fittings Legend

BFP Backflow Preventer DPV Dry Pipe Valve E 90° Elbow

PIV Post Indicating Valve S Supply Spr Sprinkler

T Tee Flow Turn 90° Z Cap

4.87

1.33

1.16

0.713

Equivalent Pipe Lengths of Valves and Fittings (C=120 only)

Actual Inside Diameter

Schedule 40 Steel Pipe Inside Diameter = Factor

C Value Multiplier

Value Of C

11/22/2021 Page 6AutoSPRINK RVT v2.2.27.0 3:57:07PMDORMITORY FLOOR LH@ M.E.P.CAD, Inc.

Drawing Name: PF002240.05-F20_zparksLKHUF Calculation Date:11/23/2021

Hydraulic Calculations Summary for

Design

Light Hazard

1950 ft²

104 ft² (typical)

MESS ATTIC LH

0.100 GPM/ft²

Remote Area Name:

Occupancy Classification:

Density

Area of Application:

Coverage per Sprinkler:

Type of Sprinklers Calculated:

No. of Sprinklers Calculated:

at Node:

Fire Protection Dry

N/AN/A

501100.000 GPM

502.9 galType of System:

In-rack Demand:

Hose Streams:

Volume of Dry or PreAction System:

at Node:

Type Allowance at Source

Total Water Required (including Hose Streams where applicable)

28.60 psi@380.720 GPMFROM: Water Supply at Node 501:

16.68 psiSafety Margin:

POOLE FIRE PROTECTION

BRITTON GRAY

19910 W 161ST ST, OLATHE KS 66062

913-829-8650 ZACHARY PARKS

Contact Name

Address:

Phone Number:

Authority Having Jurisdiction:

Name of Designer:

Automatic Peaking Results

11/22/2021 Page 1AutoSPRINK RVT v2.2.27.0 9:38:27AMMESS ATTIC LH@ M.E.P.CAD, Inc.

Node: 501

Job Name: SPRINKLER DESIGN YCC 101 102 103

Remote Area Name: MESS ATTIC LH Date: 11/22/2021 N 1.85

Summary Sheet

No pressure is being required from the Source/Supply to meet the demand (by a margin of this negative value).

A negative result in Required Pressure indicates that the Pump is capable of furnishing all of the pressure required by the demand reported within this calculation.

11/22/2021 Page 1AutoSPRINK RVT v2.2.27.0 9:38:28AM@ M.E.P.CAD, Inc.

Report Description: Light Hazard

Job Number: 2240.05

(ft²)Device

Actual Flow Minimum Flow K-Factor Pressure

Sprinkler 202 15.050 GPM 14.816 GPM 5.6 7.22 psi 0.145 GPM/ft² 104 ft²

Sprinkler 204 14.982 GPM 14.816 GPM 5.6 7.16 psi 0.144 GPM/ft² 104 ft²

Sprinkler 206 14.943 GPM 14.816 GPM 5.6 7.12 psi 0.144 GPM/ft² 104 ft²

Sprinkler 208 14.900 GPM 14.816 GPM 5.6 7.08 psi 0.143 GPM/ft² 104 ft²

Sprinkler 212 14.887 GPM 14.816 GPM 5.6 7.07 psi 0.143 GPM/ft² 104 ft²

Sprinkler 214 14.896 GPM 14.816 GPM 5.6 7.08 psi 0.143 GPM/ft² 104 ft²

Sprinkler 201 16.128 GPM 14.816 GPM 5.6 8.29 psi 0.155 GPM/ft² 104 ft²

Sprinkler 203 16.064 GPM 14.816 GPM 5.6 8.23 psi 0.154 GPM/ft² 104 ft²

Sprinkler 205 16.029 GPM 14.816 GPM 5.6 8.19 psi 0.154 GPM/ft² 104 ft²

Sprinkler 207 16.000 GPM 14.816 GPM 5.6 8.16 psi 0.154 GPM/ft² 104 ft²

Sprinkler 211 15.970 GPM 14.816 GPM 5.6 8.13 psi 0.154 GPM/ft² 104 ft²

Sprinkler 213 15.904 GPM 14.816 GPM 5.6 8.07 psi 0.153 GPM/ft² 104 ft²

Sprinkler 215 14.816 GPM 14.816 GPM 5.6 7.00 psi 0.142 GPM/ft² 104 ft²

Sprinkler 217 15.906 GPM 14.816 GPM 5.6 8.07 psi 0.153 GPM/ft² 104 ft²

Sprinkler 216 16.850 GPM 14.816 GPM 5.6 9.05 psi 0.162 GPM/ft² 104 ft²

Sprinkler 218 16.530 GPM 14.816 GPM 5.6 8.71 psi 0.159 GPM/ft² 104 ft²

Sprinkler 209 14.892 GPM 14.816 GPM 5.6 7.07 psi 0.143 GPM/ft² 104 ft²

Sprinkler 210 15.973 GPM 14.816 GPM 5.6 8.14 psi 0.154 GPM/ft² 104 ft²

11/22/2021 Page 1AutoSPRINK RVT v2.2.27.0 9:38:28AM@ M.E.P.CAD, Inc.

Remote Area Name: MESS ATTIC LH Date: 11/22/2021

(psi) (psi)(GPM)(psi)(GPM)(psi)

Supply Analysis

Node Name Static Residual Flow Available Total Demand Required Pressure

33.00 psi501 28.60 psi380.720 GPM1182.000 GPM 45.28 psi47.00 psiWater Supply

Node Analysis

Discharge at

Node

(GPM)

Pressure at

Node

(psi)

Elevation (ft)Node Number Node Type Notes

12' - 10 3/4" 15.050 GPM7.22 psi Sprinklers

Coverage: 104 ft² Density: 0.145 GPM/ft²

12' - 10 3/4" 14.982 GPM7.16 psi Sprinklers

Coverage: 104 ft² Density: 0.144 GPM/ft²

12' - 10 3/4" 14.943 GPM7.12 psi Sprinklers

Coverage: 104 ft² Density: 0.144 GPM/ft²

12' - 10 3/4" 14.900 GPM7.08 psi Sprinklers

Coverage: 104 ft² Density: 0.143 GPM/ft²

12' - 10 3/4" 14.887 GPM7.07 psi Sprinklers

Coverage: 104 ft² Density: 0.143 GPM/ft²

12' - 10 3/4" 14.896 GPM7.08 psi Sprinklers

Coverage: 104 ft² Density: 0.143 GPM/ft²

10' - 3 1/2" 16.128 GPM8.29 psi Sprinklers

Coverage: 104 ft² Density: 0.155 GPM/ft²

10' - 3 1/2" 16.064 GPM8.23 psi Sprinklers

Coverage: 104 ft² Density: 0.154 GPM/ft²

10' - 3 1/2" 16.029 GPM8.19 psi Sprinklers

Coverage: 104 ft² Density: 0.154 GPM/ft²

10' - 3 1/4" 16.000 GPM8.16 psi Sprinklers

Coverage: 104 ft² Density: 0.154 GPM/ft²

10' - 3 3/4" 15.970 GPM8.13 psi Sprinklers

Coverage: 104 ft² Density: 0.154 GPM/ft²

10' - 5 1/4" 15.904 GPM8.07 psi Sprinklers

Coverage: 104 ft² Density: 0.153 GPM/ft²

13' - 3" 14.816 GPM7.00 psi Sprinklers

Coverage: 104 ft² Density: 0.142 GPM/ft²

10' - 7 3/4" 15.906 GPM8.07 psi Sprinklers

Coverage: 104 ft² Density: 0.153 GPM/ft²

9' - 11 1/2" 16.850 GPM9.05 psi Sprinklers

Coverage: 104 ft² Density: 0.162 GPM/ft²

9' - 11 3/4" 16.530 GPM8.71 psi Sprinklers

Coverage: 104 ft² Density: 0.159 GPM/ft²

12' - 10 3/4" 14.892 GPM7.07 psi Sprinklers

Coverage: 104 ft² Density: 0.143 GPM/ft²

10' - 3 3/4" 15.973 GPM8.14 psi Sprinklers

Coverage: 104 ft² Density: 0.154 GPM/ft²

-2' - 10 1/2" 280.720 GPM28.60 psi Supply

11/22/2021 Page 1AutoSPRINK RVT v2.2.27.0 9:38:29AM@ M.E.P.CAD, Inc.

Remote Area Name: MESS ATTIC LH

Flow added this step

Pipe Information

Node 1

Node 2

Elev 1 ft

Elev 2 ft

K-Factor

Q

Total Flow

Q

Nominal ID

Actual ID

Fittings &

Devices

Equiv.

Length ft

Length ft

Fitting ft

Total ft

C Factor or

Roughness

Pf Friction

Loss Per Unit psi

Total(Pt)

Elev(Pe)

Friction(Pf)

Notes

Fitting/Device (Equivalent Length)

Fixed Pressure Losses, when applicable, are added directly to (Pf) and shown as a negative value.

Velocity

1' - 5"

12' - 11 1/4" 1' - 9"

0.13 psi

0.18 psi

13' - 3" 0' - 3 3/4"

1.000

• • • • • Route 1 • • • • •

(See

Notes)

1.049

7.00 psi14.816 GPM

0.10 psi

Sprinkler,

14.816 GPM

5.6

E(1' - 5")

6 FPS

10' - 4 1/4" 8' - 2 1/4"

1.12 psi

0.23 psi

12' - 11 1/4" 8' - 2 1/4"

1.250

1.380

7.31 psi

0.03 psi14.816 GPM

3 FPS

4' - 3 1/4"

9' - 4 1/2" 7' - 4 1/2"

0.42 psi

0.78 psi

10' - 4 1/4" 3' - 1 1/4"

1.250 (See

Notes)

1.380

8.66 psi15.906 GPM

0.11 psi

Flow (q) from Route 10

30.722 GPM T(4' - 3 1/4")

7 FPS

78' - 5 1/4"

9' - 3" 194' - 11 1/2"

0.05 psi

1.86 psi

9' - 4 1/2" 116' - 6 1/4"

4.000 (See

Notes)

4.026

9.87 psi109.407 GPM

0.01 psi

Flow (q) from Route 2

140.129 GPM 9E(7' - 1 1/2"), T(14' - 3")

4 FPS

7' - 1 1/2"

8' - 5 1/4" 7' - 11 1/4"

0.35 psi

0.27 psi

9' - 3" 0' - 9 3/4"

4.000 (See

Notes)

4.026

11.78 psi140.591 GPM

0.03 psi

Flow (q) from Route 5

280.720 GPM E(7' - 1 1/2")

7 FPS

14' - 3"

8' - 5 1/4" 17' - 1 1/2"

0.00 psi

0.59 psi

8' - 5 1/4" 2' - 10 1/4"

4.000 (See

Notes)

4.026

12.41 psi

0.03 psi280.720 GPM 2E(7' - 1 1/2")

7 FPS

4' - 3 1/4" 4' - 2"

1.80 psi

0.66 psi

8' - 5 1/4" 4' - 2"

4.000 (See

Notes)

4.026

13.01 psi

0.03 psi280.720 GPM DPV(-0.52 psi)

7 FPS

2' - 1 3/4" 2' - 1 1/2"

0.92 psi

4.07 psi

4' - 3 1/4" 2' - 1 1/2"

4.000 (See

Notes)

4.026

15.48 psi

0.03 psi280.720 GPM BOR, BFP(-4.00 psi)

7 FPS

7' - 1 1/2"

-5' - 10 3/4" 15' - 2"

3.49 psi

0.52 psi

2' - 1 3/4" 8' - 0 1/2"

4.000 (See

Notes)

4.026

20.47 psi

0.03 psi280.720 GPM E(7' - 1 1/2")

7 FPS

8' - 6 3/4"

-2' - 10 1/2" 156' - 11 1/2"

-1.31 psi

5.43 psi

-5' - 10 3/4" 148' - 5"

4.000 (See

Notes)

4.026

24.48 psi

0.03 psi280.720 GPM PIV(1' - 5"), E(7' - 1 1/2"), S

7 FPS

100.000 GPM Hose Allowance At Source

380.720 GPM

Route 1

28.60 psi

Total(Pt)

11/22/2021 Page 1AutoSPRINK RVT v2.2.27.0 9:38:30AMMESS ATTIC LH@ M.E.P.CAD, Inc.

Remote Area Name: MESS ATTIC LH

Flow added this step

Pipe Information

Node 1

Node 2

Elev 1 ft

Elev 2 ft

K-Factor

Q

Total Flow

Q

Nominal ID

Actual ID

Fittings &

Devices

Equiv.

Length ft

Length ft

Fitting ft

Total ft

C Factor or

Roughness

Pf Friction

Loss Per Unit psi

Total(Pt)

Elev(Pe)

Friction(Pf)

Notes

Fitting/Device (Equivalent Length)

Fixed Pressure Losses, when applicable, are added directly to (Pf) and shown as a negative value.

Velocity

1' - 5"

12' - 6 1/2" 1' - 9 1/2"

0.15 psi

0.19 psi

12' - 10 3/4" 0' - 4 1/2"

1.000

• • • • • Route 2 • • • • •

(See

Notes)

1.049

7.07 psi14.887 GPM

0.11 psi

Sprinkler,

14.887 GPM

5.6

E(1' - 5")

6 FPS

9' - 11 1/4" 8' - 2 1/2"

1.13 psi

0.23 psi

12' - 6 1/2" 8' - 2 1/2"

1.250

1.380

7.41 psi

0.03 psi14.887 GPM

3 FPS

4' - 3 1/4"

9' - 3 3/4" 6' - 3 1/4"

0.27 psi

0.67 psi

9' - 11 1/4" 1' - 11 3/4"

1.250 (See

Notes)

1.380

8.76…