ATTCH 3_Appendix F - Calcs (FOUO).pdf

PDF 37 MB Posted

Attached to
UPGRADE BUILDING COMPLEX HILO Federal contract opportunity
Solicitation number
W50SLF-22-R-0001
Issued by
Department of the Army National Guard

About this file

This solicitation requests proposals for the construction of upgrades to five buildings at the 291st Combat Communications Squadron in Hilo, Hawaii. Work includes replacing windows and doors, repairing and coating roofs, installing suspended ceilings and lighting. Optional work includes additional roof coating. Proposals are due April 21, 2022. Evaluation will consider technical, past performance and price factors. The contract value is estimated between $1-5 million to be funded by the Army National Guard. The small business set-aside requires at least 85% of work be performed by similarly situated entities. A pre-proposal conference will be held on March 25, 2022 at the project site. The solicitation and plans are available through SAM.gov using the listed solicitation number.

View the file

Other files for this federal contract opportunity

Other files attached to UPGRADE BUILDING COMPLEX HILO, newest first.
File Type Posted
4. Q&A for Solicitation RFP W50SLF-22-R-0001 (10-May-2022).pdf PDF
4. Q&A for Solicitation RFP W50SLF-22-R-0001 (9-May-2022).pdf PDF
Solicitation RFP W50SLF22R0001 (5.5.2022 Conformed Document).pdf PDF
ATTCH 15_ 22-0503 HIANG_ADDENDUM_004.pdf PDF
4. Q&A for Solicitation RFP W50SLF-22-R-0001 (4-May-2022).pdf PDF
Solicitation Amendment W50SLF22R0001 0003.pdf PDF
Solicitation RFP W50SLF22R0001 (Conformed Document).pdf PDF
ATTCH 13_ 22-0428_HIANG_ADDENDUM_003.pdf PDF
ATTCH 14_22-0428-HIANG-Drwgs-ADD_3.pdf PDF
ATTCH 12_22-0427_HIANG_ADDENDUM_003.pdf PDF
Solicitation Amendment W50SLF22R0001 0002.pdf PDF
4. Q&A for Solicitation RFP W50SLF-22-R-0001 (28-Apr-2022).pdf PDF
4. Q&A for Solicitation RFP W50SLF-22-R-0001 (13-Apr-2022).pdf PDF
Solicitation Amendment W50SLF22R0001 0001.pdf PDF
5. A10-KTR Laydown Area.xlsx XLSX spreadsheet
4. Q&A for Solicitation RFP W50SLF-22-R-0001 (12-Apr-2022).pdf PDF
3. Pre-Proposal Meeting PPT Upgrade Bldg Complex Hilo.pptx PPTX presentation
1. MFR - Pre-Proposal Conference Site Visit.pdf PDF
4. Q&A for Solicitation RFP W50SLF-22-R-0001 (27-Mar-2022).pdf PDF
2. Attendance Sheet - Upgrade Bldg Complex Hilo.pdf PDF
ATTCH 10_88127 - Drawings - Mechanical R02 - Certified.pdf PDF
Solicitation RFP W50SLF22R0001.pdf PDF
ATTCH 8_Narrative of changes (Mech).pdf PDF
ATTCH 4_Appendix G - Specs FINAL.pdf PDF
ATTCH 2_Appendix B - Drawings FINAL.pdf PDF
ATTCH 6_Addendum 01 - Drawings.pdf PDF
ATTCH 5_Addendum 01 - Clarification Minor Construction_dwgs.pdf PDF
EXHIBIT B_Subcontractor Information and Consent Form.docx DOCX document
EXHIBIT A_Performance Relevancy Questionnaire.docx DOCX document
ATTCH 9_88127 - Basis of Design - Mechanical.pdf PDF
ATTCH 7_Addendum 02 - SOW Add Haz Matl Survey Info.pdf PDF
EXHIBIT D_Letter of Commitment.docx DOCX document
ATTCH 11_22-0128-HILO-ARCH-FINAL-PERMIT.pdf PDF
ATTCH 1_SOW_MABE152003 Upgrade Building Complex Hilo.docx DOCX document
EXHIBIT C_Reference_Questionnaire_Package.docx DOCX document
Show all 35

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

HONOLULU CHICAGO GUAM

1164 Bishop Street

Suite 600

Honolulu Hawaii 96813

Telephone

808.534.1300

Email info@baseengr.com

Structural Calculations For

Upgrade Building Complex, Hilo

MABE 152003

Hilo, Hawaii

November 7, 2017

MABE 152003

Basis of Design:

The analysis and design of the existing and new window jambs was completed using SBEDS v5.1 design software developed by the United States Army Corps of Engineers Protective Design Center. Per the documentation, SBEDS is based on Army TM 5-1300 (also designated as NAVFAC P-397 and AFR 88-22) and UFC 3-340-01, but also draws on other sources where improved methodologies are available.

The standoff distances used in our analysis were based upon Google Earth images and approximate measurements taken during our site visit on June 22, 2016. We will confirm these standoff distances with the architectural site plan once it is finalized.

The complex is located within a controlled perimeter, so the applicable TNT equivalent used in our blast analysis is Type II.

24 ft

52 ft

72 ft

61 ft

44 ft

92 ft

100 ft

All standoff distances are measured from curb line.

Windows shown in "red" shall be designed for reflected pressures at the appropriate standoff distance.

Windows shown in "blue" shall be designed for side-on pressures at the appropriate standoff distance.

ASSUMED STANDOFF DISTANCES AND WINDOW BLAST PRESSURES

BASE - JUNE 2016

Assumed Inhabited Occupancy (Very Low Level of Protection)

Assumed Primary Gathering Occupancy (Low Level of Protection)

Assumed Inhabited Occupancy (Very Low Level of Protection)

Building 701

Building 703

Building 705

Building 704

BLDG 703 BLDG 701

9'-4"

6'-0" 8"

EMJ3

NSJ3

8" 3'-0"

6'-0"

EMJ2

NSJ2

EMJ1

NSJ1

3'-0" 8"

9'-4"

EMJ1

NSJ1

9'-4"

8" 3'-0"

[Standoff Distance = 24'] [Standoff Distance = 52'] [Standoff Distance

= 72']

3'-0" 8"

10'-0"

EMJ6

NSJ6

3'-0" 8"8" 3'-0" 8" 3' -0

3' -0

EMJ6

NSJ6

EMJ6

NSJ6

EMJ6

NSJ6

8" 3'-0"

7'-6"

EMJ7

NSJ7

BLDG 703

[Standoff Distance = 44' (Side-On)]

8" 1' -6

7'-4"

EMJ4 NCJ1

1' -6

3' -4

3' -4

1' -6

1'

-6

8"

NCJ1 EMJ4

3'-4" 3' -4

3' -0

8"

NCJ1 EMJ5

3' -0

NCJ1EMJ5 EMJ5 EMJ5

3' -0

8"3' -0

8"

7'-4" 7'-4" 7'-4"

3' -0

8"

SBEDS Analysis Key Plan:

EMJ1 = "Existing Masonry Jamb" analysis 1 NSJ1 = "New Steel Jamb" Analysis 1 NCJ1 = "New Concrete Jamb" Analysis 1

SBEDS BLAST ANALYSIS KEYPLAN

BASE - APRIL 2017

SBEDS Blast Analysis

Existing CMU Walls

Connection Design

New Steel Jambs

ROOM PSYCHROMETRIC STATE POINTS

By BMcD

001 - B701 Squadron Admin Personnel

Humidity TemperatureDry Wet Relative Ratio DifferenceEnthalpyBulb Bulb Humidity gr/lb Btu/lb °F°F °F %

69.1 29.5Space 78.0 64.6 48.5

Main System

0.0Return Air Heat Pickup

0.0Return Fan

69.1 29.5Return Air 78.0 64.6 48.5

78.0 69.1 29.5Return/Outdoor Air Mix 64.6 48.5

Leaving OA preconditioning 56.9 55.7 92.5 63.7 23.6

Entering OA preconditioning 83.8 72.1 57.0 99.1 35.7

83.8 99.1 35.7Outdoor Air 72.1 57.0

54.8 57.9 22.1Leaving Coil 53.3 90.9

69.1 29.6Entering Coil 78.1 64.6 48.3

0.1Blow Through Fan

Coil Airflow cfm 2,358

Sensible Heat Ratio (SHR) 0.75

Percent Outside Air % 0.00

57.9 22.2Supply Air 55.0 53.4 90.3

Reheat Device

57.9 22.2Cold Deck Supply Air 55.0 53.4 90.3

0.0Supply Duct Heat Gain

0.2Fan Frictional Heat

0.0Draw Through Fan

0.0

Project Name: TRACE® 700 v6.3.2 calculated at 02:40 PM on 06/02/2017

Dataset Name: 88127 - B1345.TRC Alternative - 1 Room Psychrometric Report Page 1 of 25

002 - B701 Conference Room

Humidity TemperatureDry Wet Relative Ratio DifferenceEnthalpyBulb Bulb Humidity gr/lb Btu/lb °F°F °F %

48.4 26.3Space 78.0 60.1 34.1

Main System

0.0Return Air Heat Pickup

0.0Return Fan

48.4 26.3Return Air 78.0 60.1 34.1

78.0 48.4 26.3Return/Outdoor Air Mix 60.1 34.1

Leaving OA preconditioning 56.1 55.4 95.8 63.9 23.4

Entering OA preconditioning 84.5 73.5 59.7 106.2 36.9

84.5 106.2 36.9Outdoor Air 73.5 59.7

54.8 48.4 20.7Leaving Coil 50.8 76.1

48.4 26.3Entering Coil 78.1 60.1 34.0

0.1Blow Through Fan

Coil Airflow cfm 521

Sensible Heat Ratio (SHR) 0.99

Percent Outside Air % 0.00

48.4 20.7Supply Air 55.0 50.9 75.6

Reheat Device

48.5 20.7Cold Deck Supply Air 55.0 50.9 75.7

0.0Supply Duct Heat Gain

0.2Fan Frictional Heat

0.0Draw Through Fan

0.0

Dataset Name: 88127 - B1345.TRC Alternative - 1 Room Psychrometric Report Page 2 of 25

ZONE PSYCHROMETRIC STATE POINTS

By BMcDB702BBb

B702 - Zone - 001

Dry Wet Relative Humidity Temperature Bulb Bulb Humidity Ratio DifferenceEnthalpy

°F °F % gr/lb Btu/lb °F

Space 78.0 60.8 36.4 51.7 26.8

Main System

Return Air Heat Pickup 0.0

Return Fan 0.0

Return Air 78.0 60.8 36.4 51.7 26.8

Return/Outdoor Air Mix 78.9 62.2 38.4 56.3 27.7

Leaving OA preconditioning 87.1 72.7 50.2 96.9 36.1

Entering OA preconditioning 87.1 72.7 50.2 96.9 36.1

Outdoor Air 87.1 72.7 50.2 96.9 36.1

Leaving Coil 52.4 50.4 87.9 51.1 20.5

Entering Coil 78.9 62.2 38.4 56.3 27.7

0.0Blow Through Fan

0.97 %Sensible Heat Ratio (SHR)

Percent Outside Air 10.00

Supply Air 55.0 51.6 79.8 51.1 21.1

Reheat Device

55.0 51.6 79.8 51.1 21.1Cold Deck Supply Air

Fan Frictional Heat 1.8

Supply Duct Heat Gain 0.0

Draw Through Fan 0.9

Coil Airflow cfm 252

0.0

TRACE® 700 v6.3.2 calculated at 02:37 PM on 06/02/2017Project Name:

Dataset Name: 88127 - B2.TRC Alternative - 1 Zone Psychrometric Report Page 1 of 5

By BMcDB

B702 - Zone - 002

Dry Wet Relative Humidity Temperature Bulb Bulb Humidity Ratio DifferenceEnthalpy

°F °F % gr/lb Btu/lb °F

Space 78.0 60.8 36.4 51.7 26.8

Main System

Return Air Heat Pickup 0.0

Return Fan 0.0

Return Air 78.0 60.8 36.4 51.7 26.8

Return/Outdoor Air Mix 79.0 62.2 38.2 56.1 27.7

Leaving OA preconditioning 88.1 72.8 48.3 96.1 36.3

Entering OA preconditioning 88.1 72.8 48.3 96.1 36.3

Outdoor Air 88.1 72.8 48.3 96.1 36.3

Leaving Coil 52.4 50.4 87.8 51.1 20.5

Entering Coil 79.0 62.2 38.2 56.1 27.7

0.0Blow Through Fan

0.97 %Sensible Heat Ratio (SHR)

Percent Outside Air 10.00

Supply Air 55.0 51.6 79.7 51.1 21.1

Reheat Device

55.0 51.6 79.7 51.1 21.1Cold Deck Supply Air

Fan Frictional Heat 1.8

Supply Duct Heat Gain 0.0

Draw Through Fan 0.9

Coil Airflow cfm 256

0.0

Dataset Name: 88127 - B2.TRC Alternative - 1 Zone Psychrometric Report Page 2 of 5

B702 - Zone - 003

Dry Wet Relative Humidity Temperature Bulb Bulb Humidity Ratio DifferenceEnthalpy

°F °F % gr/lb Btu/lb °F

Space 78.0 60.8 36.4 51.7 26.8

Main System

Return Air Heat Pickup 0.0

Return Fan 0.0

Return Air 78.0 60.8 36.4 51.7 26.8

Return/Outdoor Air Mix 78.9 62.0 38.0 55.7 27.7

Leaving OA preconditioning 88.1 72.8 48.3 96.1 36.3

Entering OA preconditioning 88.1 72.8 48.3 96.1 36.3

Outdoor Air 88.1 72.8 48.3 96.1 36.3

Leaving Coil 52.4 50.4 87.6 50.9 20.5

Entering Coil 78.9 62.0 38.0 55.7 27.7

0.0Blow Through Fan

0.97 %Sensible Heat Ratio (SHR)

Percent Outside Air 9.05

Supply Air 55.0 51.5 79.5 50.9 21.1

Reheat Device

55.0 51.5 79.5 50.9 21.1Cold Deck Supply Air

Fan Frictional Heat 1.8

Supply Duct Heat Gain 0.0

Draw Through Fan 0.9

Coil Airflow cfm 221

0.0

Dataset Name: 88127 - B2.TRC Alternative - 1 Zone Psychrometric Report Page 3 of 5

By BMcDBB

B702 - Zone - 004

Dry Wet Relative Humidity Temperature Bulb Bulb Humidity Ratio DifferenceEnthalpy

°F °F % gr/lb Btu/lb °F

Space 78.0 61.2 37.7 53.5 27.1

Main System

Return Air Heat Pickup 0.0

Return Fan 0.0

Return Air 78.0 61.2 37.7 53.5 27.1

Return/Outdoor Air Mix 79.0 62.9 40.4 59.5 28.3

Leaving OA preconditioning 87.6 75.0 56.0 110.1 38.3

Entering OA preconditioning 87.6 75.0 56.0 110.1 38.3

Outdoor Air 87.6 75.0 56.0 110.1 38.3

Leaving Coil 52.4 50.7 89.6 52.1 20.6

Entering Coil 79.0 62.9 40.4 59.5 28.3

0.0Blow Through Fan

0.95 %Sensible Heat Ratio (SHR)

Percent Outside Air 10.46

Supply Air 55.0 51.9 81.3 52.1 21.3

Reheat Device

55.0 51.9 81.3 52.1 21.3Cold Deck Supply Air

Fan Frictional Heat 1.8

Supply Duct Heat Gain 0.0

Draw Through Fan 0.9

Coil Airflow cfm 287

0.0

Dataset Name: 88127 - B2.TRC Alternative - 1 Zone Psychrometric Report Page 4 of 5

B702 - Zone - 001

Dry Wet Relative Humidity Temperature Bulb Bulb Humidity Ratio DifferenceEnthalpy

°F °F % gr/lb Btu/lb °F

Space 78.0 65.0 49.9 71.2 29.9

Main System

Return Air Heat Pickup 0.0

Return Fan 0.0

Return Air 78.0 65.0 49.9 71.2 29.9

Return/Outdoor Air Mix 78.8 65.8 50.4 73.9 30.5

Leaving OA preconditioning 88.1 74.3 52.7 105.0 37.7

Entering OA preconditioning 88.1 74.3 52.7 105.0 37.7

Outdoor Air 88.1 74.3 52.7 105.0 37.7

Leaving Coil 62.1 59.3 84.7 70.4 25.9

Entering Coil 78.8 65.8 50.4 73.9 30.5

0.0Blow Through Fan

0.95 %Sensible Heat Ratio (SHR)

Percent Outside Air 8.16

Supply Air 62.4 59.3 84.0 70.4 25.9

Reheat Device

62.4 59.3 84.0 70.4 25.9Cold Deck Supply Air

Fan Frictional Heat 0.2

Supply Duct Heat Gain 0.0

Draw Through Fan 0.1

Coil Airflow cfm 1,127

0.0

Dataset Name: 88127 - B2.TRC Alternative - 2 Zone Psychrometric Report Page 5 of 5

007 - B703 Gym (classroom)

Humidity TemperatureDry Wet Relative Ratio DifferenceEnthalpyBulb Bulb Humidity gr/lb Btu/lb °F°F °F %

56.8 27.6Space 78.0 62.0 39.9

Main System

0.0Return Air Heat Pickup

0.0Return Fan

56.8 27.6Return Air 78.0 62.0 39.9

78.0 56.8 27.6Return/Outdoor Air Mix 62.0 39.9

Leaving OA preconditioning 56.1 55.4 95.8 63.9 23.4

Entering OA preconditioning 84.5 73.5 59.7 106.2 36.9

84.5 106.2 36.9Outdoor Air 73.5 59.7

54.8 54.1 21.5Leaving Coil 52.3 84.9

56.8 27.6Entering Coil 78.1 62.0 39.8

0.1Blow Through Fan

Coil Airflow cfm 926

Sensible Heat Ratio (SHR) 0.92

Percent Outside Air % 0.00

54.1 21.6Supply Air 55.0 52.4 84.4

Reheat Device

54.1 21.6Cold Deck Supply Air 55.0 52.4 84.4

0.0Supply Duct Heat Gain

0.2Fan Frictional Heat

0.0Draw Through Fan

0.0

Dataset Name: 88127 - B1345.TRC Alternative - 1 Room Psychrometric Report Page 3 of 25

008 - B703 Gym (testing room)

Humidity TemperatureDry Wet Relative Ratio DifferenceEnthalpyBulb Bulb Humidity gr/lb Btu/lb °F°F °F %

61.8 28.4Space 78.0 63.0 43.4

Main System

0.0Return Air Heat Pickup

0.0Return Fan

61.8 28.4Return Air 78.0 63.0 43.4

78.0 61.8 28.4Return/Outdoor Air Mix 63.0 43.4

Leaving OA preconditioning 56.1 55.4 95.8 63.9 23.4

Entering OA preconditioning 86.2 74.5 58.1 109.2 37.8

86.2 109.2 37.8Outdoor Air 74.5 58.1

54.8 56.0 21.8Leaving Coil 52.8 87.9

61.8 28.4Entering Coil 78.1 63.1 43.2

0.1Blow Through Fan

Coil Airflow cfm 433

Sensible Heat Ratio (SHR) 0.85

Percent Outside Air % 0.00

56.0 21.9Supply Air 55.0 52.9 87.4

Reheat Device

56.0 21.9Cold Deck Supply Air 55.0 52.9 87.4

0.0Supply Duct Heat Gain

0.2Fan Frictional Heat

0.0Draw Through Fan

0.0

Dataset Name: 88127 - B1345.TRC Alternative - 1 Room Psychrometric Report Page 4 of 25

009 - B703 ATC Simulator Room

Humidity TemperatureDry Wet Relative Ratio DifferenceEnthalpyBulb Bulb Humidity gr/lb Btu/lb °F°F °F %

51.7 26.8Space 78.0 60.8 36.4

Main System

0.0Return Air Heat Pickup

0.0Return Fan

51.7 26.8Return Air 78.0 60.8 36.4

78.0 51.7 26.8Return/Outdoor Air Mix 60.8 36.4

Leaving OA preconditioning 56.1 55.4 95.8 63.9 23.4

Entering OA preconditioning 86.2 74.5 58.1 109.2 37.8

86.2 109.2 37.8Outdoor Air 74.5 58.1

54.8 51.1 21.1Leaving Coil 51.5 80.3

51.7 26.8Entering Coil 78.1 60.8 36.3

0.1Blow Through Fan

Coil Airflow cfm 439

Sensible Heat Ratio (SHR) 0.97

Percent Outside Air % 0.00

51.1 21.1Supply Air 55.0 51.6 79.8

Reheat Device

51.1 21.1Cold Deck Supply Air 55.0 51.6 79.8

0.0Supply Duct Heat Gain

0.2Fan Frictional Heat

0.0Draw Through Fan

0.0

Dataset Name: 88127 - B1345.TRC Alternative - 1 Room Psychrometric Report Page 5 of 25

010 - B703 Squadron ATC Officer

Humidity TemperatureDry Wet Relative Ratio DifferenceEnthalpyBulb Bulb Humidity gr/lb Btu/lb °F°F °F %

50.8 26.7Space 78.0 60.6 35.7

Main System

0.0Return Air Heat Pickup

0.0Return Fan

50.8 26.7Return Air 78.0 60.6 35.7

78.0 50.8 26.7Return/Outdoor Air Mix 60.6 35.7

Leaving OA preconditioning 56.1 55.4 95.8 63.9 23.4

Entering OA preconditioning 86.2 74.5 58.1 109.2 37.8

86.2 109.2 37.8Outdoor Air 74.5 58.1

54.8 50.4 21.0Leaving Coil 51.3 79.2

50.8 26.7Entering Coil 78.1 60.6 35.6

0.1Blow Through Fan

Coil Airflow cfm 598

Sensible Heat Ratio (SHR) 0.98

Percent Outside Air % 0.00

50.4 21.0Supply Air 55.0 51.4 78.7

Reheat Device

50.4 21.0Cold Deck Supply Air 55.0 51.4 78.7

0.0Supply Duct Heat Gain

0.2Fan Frictional Heat

0.0Draw Through Fan

0.0

Dataset Name: 88127 - B1345.TRC Alternative - 1 Room Psychrometric Report Page 6 of 25

011 - B704 Squad Unit Supply & Issue Rm

Humidity TemperatureDry Wet Relative Ratio DifferenceEnthalpyBulb Bulb Humidity gr/lb Btu/lb °F°F °F %

61.1 28.3Space 78.0 62.9 42.9

Main System

0.0Return Air Heat Pickup

0.0Return Fan

61.1 28.3Return Air 78.0 62.9 42.9

78.0 61.1 28.3Return/Outdoor Air Mix 62.9 42.9

Leaving OA preconditioning 57.0 55.7 92.3 63.7 23.6

Entering OA preconditioning 87.1 72.7 50.2 96.9 36.1

87.1 96.9 36.1Outdoor Air 72.7 50.2

54.8 55.8 21.8Leaving Coil 52.8 87.6

61.1 28.3Entering Coil 78.1 62.9 42.8

0.1Blow Through Fan

Coil Airflow cfm 1,558

Sensible Heat Ratio (SHR) 0.86

Percent Outside Air % 0.00

55.8 21.8Supply Air 55.0 52.8 87.0

Reheat Device

55.8 21.8Cold Deck Supply Air 55.0 52.8 87.0

0.0Supply Duct Heat Gain

0.2Fan Frictional Heat

0.0Draw Through Fan

0.0

Dataset Name: 88127 - B1345.TRC Alternative - 1 Room Psychrometric Report Page 7 of 25

013 - B704 Squad Supply Officer

Humidity TemperatureDry Wet Relative Ratio DifferenceEnthalpyBulb Bulb Humidity gr/lb Btu/lb °F°F °F %

54.6 27.3Space 78.0 61.5 38.4

Main System

0.0Return Air Heat Pickup

0.0Return Fan

54.6 27.3Return Air 78.0 61.5 38.4

78.0 54.6 27.3Return/Outdoor Air Mix 61.5 38.4

Leaving OA preconditioning 57.1 55.7 92.0 63.7 23.6

Entering OA preconditioning 76.8 69.1 68.3 94.2 33.2

76.8 94.2 33.2Outdoor Air 69.1 68.3

54.8 52.9 21.4Leaving Coil 52.0 83.1

54.6 27.3Entering Coil 78.1 61.5 38.3

0.1Blow Through Fan

Coil Airflow cfm 145

Sensible Heat Ratio (SHR) 0.94

Percent Outside Air % 0.00

52.9 21.4Supply Air 55.0 52.1 82.6

Reheat Device

52.9 21.4Cold Deck Supply Air 55.0 52.1 82.6

0.0Supply Duct Heat Gain

0.2Fan Frictional Heat

0.0Draw Through Fan

0.0

Dataset Name: 88127 - B1345.TRC Alternative - 1 Room Psychrometric Report Page 8 of 25

014 - B704 Squad Supply Admin Office

Humidity TemperatureDry Wet Relative Ratio DifferenceEnthalpyBulb Bulb Humidity gr/lb Btu/lb °F°F °F %

54.3 27.2Space 78.0 61.4 38.2

Main System

0.0Return Air Heat Pickup

0.0Return Fan

54.3 27.2Return Air 78.0 61.4 38.2

78.0 54.3 27.2Return/Outdoor Air Mix 61.4 38.2

Leaving OA preconditioning 57.1 55.7 92.0 63.7 23.6

Entering OA preconditioning 76.8 69.1 68.3 94.2 33.2

76.8 94.2 33.2Outdoor Air 69.1 68.3

54.8 52.8 21.3Leaving Coil 52.0 82.9

54.3 27.2Entering Coil 78.1 61.4 38.1

0.1Blow Through Fan

Coil Airflow cfm 156

Sensible Heat Ratio (SHR) 0.95

Percent Outside Air % 0.00

52.8 21.4Supply Air 55.0 52.0 82.4

Reheat Device

52.8 21.4Cold Deck Supply Air 55.0 52.0 82.4

0.0Supply Duct Heat Gain

0.2Fan Frictional Heat

0.0Draw Through Fan

0.0

Dataset Name: 88127 - B1345.TRC Alternative - 1 Room Psychrometric Report Page 9 of 25

015 - B704 Squad Maintenance Management

Humidity TemperatureDry Wet Relative Ratio DifferenceEnthalpyBulb Bulb Humidity gr/lb Btu/lb °F°F °F %

61.0 28.3Space 78.0 62.9 42.9

Main System

0.0Return Air Heat Pickup

0.0Return Fan

61.0 28.3Return Air 78.0 62.9 42.9

78.0 61.0 28.3Return/Outdoor Air Mix 62.9 42.9

Leaving OA preconditioning 57.0 55.7 92.3 63.7 23.6

Entering OA preconditioning 87.1 72.7 50.2 96.9 36.1

87.1 96.9 36.1Outdoor Air 72.7 50.2

54.8 55.8 21.8Leaving Coil 52.8 87.6

61.0 28.3Entering Coil 78.1 62.9 42.7

0.1Blow Through Fan

Coil Airflow cfm 933

Sensible Heat Ratio (SHR) 0.86

Percent Outside Air % 0.00

55.8 21.8Supply Air 55.0 52.8 87.0

Reheat Device

55.8 21.8Cold Deck Supply Air 55.0 52.8 87.0

0.0Supply Duct Heat Gain

0.2Fan Frictional Heat

0.0Draw Through Fan

0.0

Dataset Name: 88127 - B1345.TRC Alternative - 1 Room Psychrometric Report Page 10 of 25

016 - B704 Squad Maintenance Officer

Humidity TemperatureDry Wet Relative Ratio DifferenceEnthalpyBulb Bulb Humidity gr/lb Btu/lb °F°F °F %

52.9 27.0Space 78.0 61.1 37.2

Main System

0.0Return Air Heat Pickup

0.0Return Fan

52.9 27.0Return Air 78.0 61.1 37.2

78.0 52.9 27.0Return/Outdoor Air Mix 61.1 37.2

Leaving OA preconditioning 57.1 55.7 92.0 63.7 23.6

Entering OA preconditioning 76.8 69.1 68.3 94.2 33.2

76.8 94.2 33.2Outdoor Air 69.1 68.3

54.8 52.0 21.2Leaving Coil 51.8 81.7

52.9 27.0Entering Coil 78.1 61.1 37.1

0.1Blow Through Fan

Coil Airflow cfm 256

Sensible Heat Ratio (SHR) 0.96

Percent Outside Air % 0.00

52.0 21.3Supply Air 55.0 51.8 81.2

Reheat Device

52.0 21.3Cold Deck Supply Air 55.0 51.8 81.2

0.0Supply Duct Heat Gain

0.2Fan Frictional Heat

0.0Draw Through Fan

0.0

Dataset Name: 88127 - B1345.TRC Alternative - 1 Room Psychrometric Report Page 11 of 25

017 - B704 Training Room

Humidity TemperatureDry Wet Relative Ratio DifferenceEnthalpyBulb Bulb Humidity gr/lb Btu/lb °F°F °F %

48.4 26.3Space 78.0 60.1 34.1

Main System

0.0Return Air Heat Pickup

0.0Return Fan

48.4 26.3Return Air 78.0 60.1 34.1

78.0 48.4 26.3Return/Outdoor Air Mix 60.1 34.1

Leaving OA preconditioning 56.1 55.4 95.8 63.9 23.4

Entering OA preconditioning 86.2 74.5 58.1 109.2 37.8

86.2 109.2 37.8Outdoor Air 74.5 58.1

54.8 48.4 20.7Leaving Coil 50.8 76.2

48.4 26.3Entering Coil 78.1 60.1 34.0

0.1Blow Through Fan

Coil Airflow cfm 1,396

Sensible Heat Ratio (SHR) 0.99

Percent Outside Air % 0.00

48.4 20.7Supply Air 55.0 50.9 75.7

Reheat Device

48.5 20.7Cold Deck Supply Air 55.0 50.9 75.8

0.0Supply Duct Heat Gain

0.2Fan Frictional Heat

0.0Draw Through Fan

0.0

Dataset Name: 88127 - B1345.TRC Alternative - 1 Room Psychrometric Report Page 12 of 25

018 - B705 NCMO / WLC / CP

Humidity TemperatureDry Wet Relative Ratio DifferenceEnthalpyBulb Bulb Humidity gr/lb Btu/lb °F°F °F %

55.7 27.4Space 78.0 61.7 39.1

Main System

0.0Return Air Heat Pickup

0.0Return Fan

55.7 27.4Return Air 78.0 61.7 39.1

78.0 55.7 27.4Return/Outdoor Air Mix 61.7 39.1

Leaving OA preconditioning 56.3 55.4 95.0 63.9 23.4

Entering OA preconditioning 82.1 71.9 61.5 100.8 35.5

82.1 100.8 35.5Outdoor Air 71.9 61.5

54.8 53.5 21.4Leaving Coil 52.1 84.0

55.7 27.5Entering Coil 78.1 61.7 39.0

0.1Blow Through Fan

Coil Airflow cfm 868

Sensible Heat Ratio (SHR) 0.93

Percent Outside Air % 0.00

53.5 21.5Supply Air 55.0 52.2 83.4

Reheat Device

53.5 21.5Cold Deck Supply Air 55.0 52.2 83.4

0.0Supply Duct Heat Gain

0.2Fan Frictional Heat

0.0Draw Through Fan

0.0

Dataset Name: 88127 - B1345.TRC Alternative - 1 Room Psychrometric Report Page 13 of 25

019 - B705 Comm Officer

Humidity TemperatureDry Wet Relative Ratio DifferenceEnthalpyBulb Bulb Humidity gr/lb Btu/lb °F°F °F %

57.0 27.6Space 78.0 62.0 40.0

Main System

0.0Return Air Heat Pickup

0.0Return Fan

57.0 27.6Return Air 78.0 62.0 40.0

78.0 57.0 27.6Return/Outdoor Air Mix 62.0 40.0

Leaving OA preconditioning 57.0 55.7 92.2 63.7 23.6

Entering OA preconditioning 88.1 72.8 48.3 96.1 36.3

88.1 96.1 36.3Outdoor Air 72.8 48.3

54.8 54.2 21.6Leaving Coil 52.3 85.1

57.0 27.7Entering Coil 78.1 62.0 39.9

0.1Blow Through Fan

Coil Airflow cfm 74

Sensible Heat Ratio (SHR) 0.92

Percent Outside Air % 0.00

54.2 21.6Supply Air 55.0 52.4 84.5

Reheat Device

54.2 21.6Cold Deck Supply Air 55.0 52.4 84.5

0.0Supply Duct Heat Gain

0.2Fan Frictional Heat

0.0Draw Through Fan

0.0

Dataset Name: 88127 - B1345.TRC Alternative - 1 Room Psychrometric Report Page 14 of 25

020 - B705 Message Center

Humidity TemperatureDry Wet Relative Ratio DifferenceEnthalpyBulb Bulb Humidity gr/lb Btu/lb °F°F °F %

57.8 27.8Space 78.0 62.2 40.6

Main System

0.0Return Air Heat Pickup

0.0Return Fan

57.8 27.8Return Air 78.0 62.2 40.6

78.0 57.8 27.8Return/Outdoor Air Mix 62.2 40.6

Leaving OA preconditioning 57.0 55.7 92.2 63.7 23.6

Entering OA preconditioning 88.1 72.8 48.3 96.1 36.3

88.1 96.1 36.3Outdoor Air 72.8 48.3

54.8 54.6 21.6Leaving Coil 52.4 85.8

57.8 27.8Entering Coil 78.1 62.2 40.5

0.1Blow Through Fan

Coil Airflow cfm 61

Sensible Heat Ratio (SHR) 0.91

Percent Outside Air % 0.00

54.6 21.7Supply Air 55.0 52.5 85.2

Reheat Device

54.6 21.7Cold Deck Supply Air 55.0 52.5 85.2

0.0Supply Duct Heat Gain

0.2Fan Frictional Heat

0.0Draw Through Fan

0.0

Dataset Name: 88127 - B1345.TRC Alternative - 1 Room Psychrometric Report Page 15 of 25

021 - B705 Radio Operations Classroom

Humidity TemperatureDry Wet Relative Ratio DifferenceEnthalpyBulb Bulb Humidity gr/lb Btu/lb °F°F °F %

72.2 30.0Space 78.0 65.2 50.6

Main System

0.0Return Air Heat Pickup

0.0Return Fan

72.2 30.0Return Air 78.0 65.2 50.6

78.0 72.2 30.0Return/Outdoor Air Mix 65.2 50.6

Leaving OA preconditioning 56.9 55.7 92.5 63.7 23.6

Entering OA preconditioning 85.6 72.6 53.8 98.9 36.1

85.6 98.9 36.1Outdoor Air 72.6 53.8

54.8 58.6 22.2Leaving Coil 53.5 92.0

72.2 30.0Entering Coil 78.1 65.3 50.4

0.1Blow Through Fan

Coil Airflow cfm 110

Sensible Heat Ratio (SHR) 0.72

Percent Outside Air % 0.00

58.6 22.3Supply Air 55.0 53.6 91.4

Reheat Device

58.6 22.3Cold Deck Supply Air 55.0 53.6 91.4

0.0Supply Duct Heat Gain

0.2Fan Frictional Heat

0.0Draw Through Fan

0.0

Dataset Name: 88127 - B1345.TRC Alternative - 1 Room Psychrometric Report Page 16 of 25

022 - B705 Maintenance

Humidity TemperatureDry Wet Relative Ratio DifferenceEnthalpyBulb Bulb Humidity gr/lb Btu/lb °F°F °F %

50.2 26.6Space 78.0 60.5 35.3

Main System

0.0Return Air Heat Pickup

0.0Return Fan

50.2 26.6Return Air 78.0 60.5 35.3

78.0 50.2 26.6Return/Outdoor Air Mix 60.5 35.3

Leaving OA preconditioning 57.1 55.7 92.0 63.7 23.6

Entering OA preconditioning 75.1 68.6 72.1 94.1 32.7

75.1 94.1 32.7Outdoor Air 68.6 72.1

54.8 49.9 20.9Leaving Coil 51.2 78.4

50.2 26.6Entering Coil 78.1 60.5 35.2

0.1Blow Through Fan

Coil Airflow cfm 190

Sensible Heat Ratio (SHR) 0.98

Percent Outside Air % 0.00

49.9 20.9Supply Air 55.0 51.3 77.9

Reheat Device

49.9 20.9Cold Deck Supply Air 55.0 51.3 77.9

0.0Supply Duct Heat Gain

0.2Fan Frictional Heat

0.0Draw Through Fan

0.0

Dataset Name: 88127 - B1345.TRC Alternative - 1 Room Psychrometric Report Page 17 of 25

023 - B705 Vestibule

Humidity TemperatureDry Wet Relative Ratio DifferenceEnthalpyBulb Bulb Humidity gr/lb Btu/lb °F°F °F %

38.5 24.7Space 78.0 57.7 27.1

Main System

0.0Return Air Heat Pickup

0.0Return Fan

38.5 24.7Return Air 78.0 57.7 27.1

78.0 38.5 24.7Return/Outdoor Air Mix 57.7 27.1

Leaving OA preconditioning 57.0 55.7 92.2 63.7 23.6

Entering OA preconditioning 88.1 72.8 48.3 96.1 36.3

88.1 96.1 36.3Outdoor Air 72.8 48.3

54.8 38.5 19.1Leaving Coil 48.0 60.6

38.5 24.8Entering Coil 78.1 57.8 27.1

0.1Blow Through Fan

Coil Airflow cfm 39

Sensible Heat Ratio (SHR) 1.00

Percent Outside Air % 0.00

38.5 19.2Supply Air 55.0 48.1 60.2

Reheat Device

38.8 19.2Cold Deck Supply Air 55.0 48.2 60.8

0.0Supply Duct Heat Gain

0.2Fan Frictional Heat

0.0Draw Through Fan

0.0

Dataset Name: 88127 - B1345.TRC Alternative - 1 Room Psychrometric Report Page 18 of 25

024 - B705 Communications Center

Humidity TemperatureDry Wet Relative Ratio DifferenceEnthalpyBulb Bulb Humidity gr/lb Btu/lb °F°F °F %

59.5 28.0Space 78.0 62.5 41.8

Main System

0.0Return Air Heat Pickup

0.0Return Fan

59.5 28.0Return Air 78.0 62.5 41.8

78.0 59.5 28.0Return/Outdoor Air Mix 62.5 41.8

Leaving OA preconditioning 56.1 55.4 95.8 63.9 23.4

Entering OA preconditioning 84.5 73.5 59.7 106.2 36.9

84.5 106.2 36.9Outdoor Air 73.5 59.7

54.8 55.2 21.7Leaving Coil 52.6 86.7

59.5 28.0Entering Coil 78.1 62.6 41.7

0.1Blow Through Fan

Coil Airflow cfm 538

Sensible Heat Ratio (SHR) 0.88

Percent Outside Air % 0.00

55.2 21.8Supply Air 55.0 52.7 86.2

Reheat Device

55.2 21.8Cold Deck Supply Air 55.0 52.7 86.2

0.0Supply Duct Heat Gain

0.2Fan Frictional Heat

0.0Draw Through Fan

0.0

Dataset Name: 88127 - B1345.TRC Alternative - 1 Room Psychrometric Report Page 19 of 25

025 - B705 Switchboard Room

Humidity TemperatureDry Wet Relative Ratio DifferenceEnthalpyBulb Bulb Humidity gr/lb Btu/lb °F°F °F %

58.1 27.8Space 78.0 62.2 40.8

Main System

0.0Return Air Heat Pickup

0.0Return Fan

58.1 27.8Return Air 78.0 62.2 40.8

78.0 58.1 27.8Return/Outdoor Air Mix 62.2 40.8

Leaving OA preconditioning 57.0 55.7 92.2 63.7 23.6

Entering OA preconditioning 88.1 72.8 48.3 96.1 36.3

88.1 96.1 36.3Outdoor Air 72.8 48.3

54.8 54.7 21.6Leaving Coil 52.5 86.0

58.1 27.8Entering Coil 78.1 62.3 40.7

0.1Blow Through Fan

Coil Airflow cfm 72

Sensible Heat Ratio (SHR) 0.90

Percent Outside Air % 0.00

54.7 21.7Supply Air 55.0 52.6 85.4

Reheat Device

54.7 21.7Cold Deck Supply Air 55.0 52.6 85.4

0.0Supply Duct Heat Gain

0.2Fan Frictional Heat

0.0Draw Through Fan

0.0

Dataset Name: 88127 - B1345.TRC Alternative - 1 Room Psychrometric Report Page 20 of 25

026 - B705 Crypto Maintenance

Humidity TemperatureDry Wet Relative Ratio DifferenceEnthalpyBulb Bulb Humidity gr/lb Btu/lb °F°F °F %

38.4 24.7Space 78.0 57.7 27.1

Main System

0.0Return Air Heat Pickup

0.0Return Fan

38.4 24.7Return Air 78.0 57.7 27.1

78.0 38.4 24.7Return/Outdoor Air Mix 57.7 27.1

Leaving OA preconditioning 57.0 55.7 92.2 63.7 23.6

Entering OA preconditioning 88.1 72.8 48.3 96.1 36.3

88.1 96.1 36.3Outdoor Air 72.8 48.3

54.8 38.4 19.1Leaving Coil 48.0 60.6

38.4 24.8Entering Coil 78.1 57.8 27.1

0.1Blow Through Fan

Coil Airflow cfm 153

Sensible Heat Ratio (SHR) 1.00

Percent Outside Air % 0.00

38.4 19.2Supply Air 55.0 48.1 60.2

Reheat Device

38.8 19.2Cold Deck Supply Air 55.0 48.2 60.8

0.0Supply Duct Heat Gain

0.2Fan Frictional Heat

0.0Draw Through Fan

0.0

Dataset Name: 88127 - B1345.TRC Alternative - 1 Room Psychrometric Report Page 21 of 25

027 - B705 Crypto Room

Humidity TemperatureDry Wet Relative Ratio DifferenceEnthalpyBulb Bulb Humidity gr/lb Btu/lb °F°F °F %

38.4 24.7Space 78.0 57.7 27.1

Main System

0.0Return Air Heat Pickup

0.0Return Fan

38.4 24.7Return Air 78.0 57.7 27.1

78.0 38.4 24.7Return/Outdoor Air Mix 57.7 27.1

Leaving OA preconditioning 57.0 55.7 92.2 63.7 23.6

Entering OA preconditioning 88.1 72.8 48.3 96.1 36.3

88.1 96.1 36.3Outdoor Air 72.8 48.3

54.8 38.4 19.1Leaving Coil 48.0 60.6

38.4 24.8Entering Coil 78.1 57.8 27.1

0.1Blow Through Fan

Coil Airflow cfm 203

Sensible Heat Ratio (SHR) 1.00

Percent Outside Air % 0.00

38.4 19.2Supply Air 55.0 48.1 60.2

Reheat Device

38.8 19.2Cold Deck Supply Air 55.0 48.2 60.8

0.0Supply Duct Heat Gain

0.2Fan Frictional Heat

0.0Draw Through Fan

0.0

Dataset Name: 88127 - B1345.TRC Alternative - 1 Room Psychrometric Report Page 22 of 25

028 - B705 AHTE

Humidity TemperatureDry Wet Relative Ratio DifferenceEnthalpyBulb Bulb Humidity gr/lb Btu/lb °F°F °F %

38.5 24.8Space 78.0 57.8 27.2

Main System

0.0Return Air Heat Pickup

0.0Return Fan

38.5 24.8Return Air 78.0 57.8 27.2

78.0 38.5 24.8Return/Outdoor Air Mix 57.8 27.2

Leaving OA preconditioning 56.1 55.4 95.8 63.9 23.4

Entering OA preconditioning 86.2 74.5 58.1 109.2 37.8

86.2 109.2 37.8Outdoor Air 74.5 58.1

54.8 38.5 19.1Leaving Coil 48.0 60.7

38.5 24.8Entering Coil 78.1 57.8 27.1

0.1Blow Through Fan

Coil Airflow cfm 15

Sensible Heat Ratio (SHR) 1.00

Percent Outside Air % 0.00

38.5 19.2Supply Air 55.0 48.1 60.3

Reheat Device

38.9 19.2Cold Deck Supply Air 55.0 48.2 60.9

0.0Supply Duct Heat Gain

0.2Fan Frictional Heat

0.0Draw Through Fan

0.0

Dataset Name: 88127 - B1345.TRC Alternative - 1 Room Psychrometric Report Page 23 of 25

029 - B705 Radio Relay / Telephone Maint

Humidity TemperatureDry Wet Relative Ratio DifferenceEnthalpyBulb Bulb Humidity gr/lb Btu/lb °F°F °F %

64.4 28.8Space 78.0 63.6 45.2

Main System

0.0Return Air Heat Pickup

0.0Return Fan

64.4 28.8Return Air 78.0 63.6 45.2

78.0 64.4 28.8Return/Outdoor Air Mix 63.6 45.2

Leaving OA preconditioning 56.1 55.4 95.8 63.9 23.4

Entering OA preconditioning 84.5 73.5 59.7 106.2 36.9

84.5 106.2 36.9Outdoor Air 73.5 59.7

54.8 56.8 22.0Leaving Coil 53.0 89.2

64.4 28.8Entering Coil 78.1 63.6 45.0

0.1Blow Through Fan

Coil Airflow cfm 994

Sensible Heat Ratio (SHR) 0.82

Percent Outside Air % 0.00

56.8 22.0Supply Air 55.0 53.1 88.6

Reheat Device

56.8 22.0Cold Deck Supply Air 55.0 53.1 88.6

0.0Supply Duct Heat Gain

0.2Fan Frictional Heat

0.0Draw Through Fan

0.0

Dataset Name: 88127 - B1345.TRC Alternative - 1 Room Psychrometric Report Page 24 of 25

030 - B705 Gnd Radio Radar Flight Fac

Humidity TemperatureDry Wet Relative Ratio DifferenceEnthalpyBulb Bulb Humidity gr/lb Btu/lb °F°F °F %

62.5 28.5Space 78.0 63.2 43.9

Main System

0.0Return Air Heat Pickup

0.0Return Fan

62.5 28.5Return Air 78.0 63.2 43.9

78.0 62.5 28.5Return/Outdoor Air Mix 63.2 43.9

Leaving OA preconditioning 56.1 55.4 95.8 63.9 23.4

Entering OA preconditioning 86.2 74.5 58.1 109.2 37.8

86.2 109.2 37.8Outdoor Air 74.5 58.1

54.8 56.3 21.9Leaving Coil 52.9 88.3

62.5 28.5Entering Coil 78.1 63.2 43.7

0.1Blow Through Fan

Coil Airflow cfm 1,338

Sensible Heat Ratio (SHR) 0.84

Percent Outside Air % 0.00

56.3 21.9Supply Air 55.0 53.0 87.8

Reheat Device

56.3 21.9Cold Deck Supply Air 55.0 53.0 87.8

0.0Supply Duct Heat Gain

0.2Fan Frictional Heat

0.0Draw Through Fan

0.0

Dataset Name: 88127 - B1345.TRC Alternative - 1 Room Psychrometric Report Page 25 of 25

ASHRAE Standard - 62-2007 with Appendix A Client 05/31/17

Project JHC

Proj. No. X

Checked By

Final

Assumptions:

Minimum Outside Air Requirements, Peak Design Conditions

Ez,cool: 1.0 Zone Air Distribution Effectiveness for cooling

Ez,heat: 1.0 Zone Air Distribution Effectiveness for heating

Zone Zone - sq. ft. Breathing Zone OA Voz Vdz Zd Voz VAV Zd or box Rp Ra RpPz RaAz Vbz Ez Min OA Design OA/SA Ez Min OA Min SA Min OA/SA Exhaust Bld. Pres Trace Delta

No. Tag cfm/pers cfm/sq-ft (cfm) (cfm) (cfm) Vent Eff. SA (cfm) % Vent Eff. (cfm) SA % % CFM CFM CFM CFM

1 DOAS-01 B703 - Weight Room Health club/weight rooms 20 0.06 2 633 40 37.98 78 1.0 78 825 9% 1.0 78 83 10% 95% 0 822 3

2 DOAS-01 B703 - Weight Room Health club/weight rooms 20 0.06 2 413 40 24.78 65 1.0 65 400 16% 1.0 65 40 10% 162% 0 396 4

3 DOAS-01 B703 - ATC Simulator Room Office space 5 0.06 1 327 5 19.62 25 1.0 25 395 6% 1.0 25 40 10% 62% 0 395 0

4 DOAS-01 B703 - Squadron ATC Officer Office space 5 0.06 1 320 5 19.20 24 1.0 24 565 4% 1.0 24 57 10% 43% 0 565 0

- DOAS-04 B701 - Squadron Administration / Personnel Conference/meeting 5 0.06 90 1,707 450 102.42 552 1.0 552 2,155 26% 1.0 552 216 10% 256% 0 2152 3

- DOAS-04 B701 - Conference Room Conference/meeting 5 0.06 5 269 25 16.14 41 1.0 41 480 9% 1.0 41 48 10% 86% 0 480 0

11 - B704 - Men NOT INCLUDED IN CALC - - 11 284 1.0 0 1.0 750 0 0

12 - B704 - Women NOT INCLUDED IN CALC - - 3 148 1.0 0 1.0 190 0 0

13 - B704 - Service Room NOT INCLUDED IN CALC - - 2 80 1.0 0 1.0 80 0 0

14 - B704 - Janitor's Closet NOT INCLUDED IN CALC - - 0 56 1.0 0 1.0 60 0 0

15 - B704 - Frame Room NOT INCLUDED IN CALC - - 0 60 1.0 0 1.0 0 0 0

18 DOAS-02 B704 - Squadron Supply Officer Office space 5 0.06 1 131 5 7.86 13 1.0 13 145 9% 1.0 13 15 10% 89% 0 145 0

19 DOAS-02 B704 - Squadron Supply Admin. Office Office space 5 0.06 1 139 5 8.34 13 1.0 13 160 8% 1.0 13 16 10% 83% 0 156 4

20 DOAS-02 B704 - Squadron Unit Supply & Issue Room Shipping/receiving 0 0.12 25 1,386 0 166.32 166 1.0 166 1,425 12% 1.0 166 143 10% 117% 0 1421 4

21 DOAS-02 B704 - Squadron Maintenance Management Shipping/receiving 0 0.12 15 1,073 0 128.76 129 1.0 129 860 15% 1.0 129 86 10% 150% 0 860 0

22 DOAS-02 B704 - Squadron Maintenance Officer Office space 5 0.06 1 221 5 13.26 18 1.0 18 260 7% 1.0 18 26 10% 70% 0 256 4

- DOAS-02 B704 - Training Room Computer (not printing) 5 0.06 0 1,600 0 96.00 96 1.0 96 1,300 7% 1.0 96 130 10% 74% 0 1296 4

23 DOAS-03 B705 - Ground Radio / Radar / Flight Facilities Maint. Office space 5 0.06 25 810 125 48.60 174 1.0 174 1,290 13% 1.0 174 129 10% 135% 0 1289 1

24 DOAS-03 B705 - Radio Relay / Telephone Maint. Office space 5 0.06 25 674 125 40.44 165 1.0 165 945 18% 1.0 165 95 10% 175% 0 945 0

25 - B705 - Mechanical Room NOT INCLUDED IN CALC - - 0 142 1.0 0 1.0 0 0 0

26 - B705 - Crypto Room Storage rooms 0 0.12 0 256 0 30.72 31 1.0 31 185 17% 1.0 31 19 10% 166% 0 184 1

27 - B705 - Crypto Maint. Electrical equipment rooms 0 0.06 0 175 0 10.50 11 1.0 11 145 7% 1.0 11 15 10% 72% 0 141 4

28 DOAS-03 B705 - Switchboard Room Office space 5 0.06 1 130 5 7.80 13 1.0 13 70 18% 1.0 13 7 10% 183% 0 66 4

29 DOAS-03 B705 - Vestibule Corridors 0 0.06 0 33 0 1.98 2 1.0 2 35 6% 1.0 2 4 10% 57% 0 35 0

30 DOAS-03 B705 - Message Center Office space 5 0.06 1 88 5 5.28 10 1.0 10 55 19% 1.0 10 6 10% 187% 0 55 0

31 DOAS-03 B705 - Comm. Officer Office space 5 0.06 1 135 5 8.10 13 1.0 13 70 19% 1.0 13 7 10% 187% 0 68 2

32 DOAS-03 B705 - Radio Operations Classroom Conference/meeting 5 0.06 7 227 35 13.62 49 1.0 49 105 46% 1.0 49 11 10% 463% 0 104 1

33 DOAS-03 B705 - Maintenance Storage rooms 0 0.12 0 198 0 23.76 24 1.0 24 190 13% 1.0 24 19 10% 125% 0 190 0

34 DOAS-03 B705 - Communications Center Dayroom 5 0.06 7 617 35 37.02 72 1.0 72 525 14% 1.0 72 53 10% 137% 0 525 0

36 - B705 - AHTE Corridors 0 0.06 0 29 0 1.74 2 1.0 2 15 12% 1.0 2 2 10% 116% 0 12 3

37 DOAS-03 B705 - NCMO / WLC / CP Office space 5 0.06 6 680 30 40.80 71 1.0 71 800 9% 1.0 71 80 10% 89% 0 800 0

5 - B702 - Janitor's Closet NOT INCLUDED IN CALC - - 0 20 1.0 0 1.0 20 0 0

6 - B702 - Battery Room NOT INCLUDED IN CALC - - 0 73 1.0 0 1.0 150 0 0

7 - B702 - Women NOT INCLUDED IN CALC - - 2 140 1.0 0 1.0 120 0 0

8 - B702 - Men NOT INCLUDED IN CALC - - 5 178 1.0 0 1.0 330 0 0

9 - B702 - Utility Room NOT INCLUDED IN CALC - - 0 225 1.0 0 1.0 0 0 0

11 FCU-018 B702 - Office Office space 5 0.06 1 144 5 8.64 14 1.0 14 205 7% 1.0 14 21 10% 67% 0 205 0

13 FCU-019 B702 - Vehicle Dispatch & Drivers Office space 5 0.06 1 193 5 11.58 17 1.0 17 215 8% 1.0 17 22 10% 77% 0 214 1

14 FCU-020 B702 - Office Office space 5 0.06 1 193 5 11.58 17 1.0 17 195 9% 1.0 17 20 10% 85% 0 194 1

20 FCU-021 B702 - Offices Office space 5 0.06 2 341 10 20.46 30 1.0 30 225 14% 1.0 30 23 10% 135% 0 224 1

LAST REF 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 45

Totals: 245 14,548 970 963 1,933 1933 14,240 46% 1933 1,424 463% 1700 0.0 14,192

Note: Trace CFM is BLOCK value.

Clg Htg

Maximum Zone Primary OA fraction: Max. Zp = Voz / SA 0.46 4.63 ---Cooling Based on Table 6-3 Outside air (OA) requirements are also a function of building

System Ventilation Efficiency: Ev = 0.687 -2.273 --- Heating Based on Appendix A (min Evz) exhaust and pressurization -

Occupant Diversity: D = Ps / ∑all zones Pz 1.00 1.00 ---System population/Sum of Space Population OA = Bldg Exhaust + Bldg Pressurization

Uncorrected OA Intake: Vou = D∑all zones RpPz + ∑all zones RaAz 1,933 1,933

Design OA Intake Flow: Vot = Vou / Ev 2,814 -851

This procedure is in accordance with ASHRAE Std 62-2007. Following are a list of terms used:

Hawaii Air National Guard Date

Upgrade Building Complex, Hilo Made By

88127 Preliminary

--- From Table 6.2 Cooling Heating cfm

Space Name

Ventilation information from table 6.1

Area Type Pz Az

"Minimum OA quantity", under design SA flow condition, is: 2,814 cfm Minimum OA quantity based on exhaust and pressurization, is: 1700

Ventilation.xlsm BLANK

Therefore, Outside Air Requirement is: CFM

And, the Design Air flow is: CFM

Percentage of Outside Air is:

[1]

Actual Outside Air : CFM

Eng Check: CFM/sq.ft

Eng Check: CFM/person

1. Actual outside air is calculated as a minimum of 10% of total design airflow. This shall help to maintain the pressurization requirement of the space.

2814.314432

0.193450263

11.48699768

20%

2,814

14,192

Ventilation.xlsm BLANK

Client Date 5/31/2017

Project Made By JHC

Checked By

Proj. No. Preliminary X

Final

ACH

METHOD

AREA

METHOD

PER

FIXTURE

BUILDING 704

11 Men 284 8 2,270 10/1 70/50 750 750 ASHRAE 62.1

12 Women 148 8 1,187 2/1 70/50 190 190 ASHRAE 62.1

13 Service Room 80 13 1,034 1.0 79.55 80 ASHRAE 62.1

14 Janitor's Closet 56 13 727 1.0 55.9 60 ASHRAE 62.1

BUILDING 702

5 Janitor's Closet 20 16 320 1.0 20 20 ASHRAE 62.1

6 Battery Room 73 16 1,168 2.0 146 150 DG 415-2

7 Women 140 8 1,120 1/1 70/50 120 120 ASHRAE 62.1

8 Men 178 8 1,424 4/1 70/50 330 330 ASHRAE 62.1

Notes:

NOTES

EXHAUST REQUIREMENTS

MINIMUM EXHAUST CFM

CALCULATED

EXHAUST CFM

DESIGN

EXHAUST CFM

FIXTURES

TOILETS/

SHOWERS

VOLUME

(ft

CEILING

HEIGHT (ft)AREA (ft

)DESCRIPTIONNO.

88127

Hawaii Air National Guard

Client Date

Project Made By

Checked By

Proj. No. Preliminary

Final

LOUVER

TAG

NO. WIDTH HEIGHT

CFM FPM % SQ-FT SQ-FT SQ-FT INCH INCH

L-02 EF-03 B702 - Janitor's Closer / Men's / Women's EXHAUST 520 500 45 1.04 2.31 2.67 32 12

L-04 Transfer B702 - Hallway Makeup Air INTAKE 420 500 45 0.84 1.87 2.17 26 12

L-05 EF-05 B702 - Utility Room EXHAUST 140 500 45 0.28 0.62 1.00 12 12

L-06 FCU-18 B702 - Office (011) INTAKE 50 500 45 0.1 0.22 1.00 12 12

L-07 FCU-19 B702 - Vehicle Dispatch & Drivers (013) INTAKE 50 500 45 0.1 0.22 1.00 12 12

L-08 FCU-20 B702 - Office (014) INTAKE 50 500 45 0.1 0.22 1.00 12 12

L-09 FCU-21 B702 - Offices (020) INTAKE 50 500 45 0.1 0.22 1.00 12 12

L-10 EF-06 B704 - Women's Bathroom EXHAUST 190 500 45 0.38 0.84 1.17 14 12

L-11 EF-07 B704 - Service Room EXHAUST 100 500 45 0.2 0.44 1.00 12 12

L-12 EF-08 B704 - Janitor's Room EXHAUST 130 500 45 0.26 0.58 1.00 12 12

L-13 EF-09 B704 - Frame Room EXHAUST 140 500 45 0.28 0.62 1.00 12 12

L-14 DOAS-3 B705 - Mechanical Room INTAKE 805 500 45 1.61 3.58 3.75 30 18

L-15 EF-12 B704 - Building Plenum Exhaust EXHAUST 215 500 45 0.43 0.96 1.33 16 12

L-16 EF-11 B701 - Building Plenum Exhaust EXHAUST 345 500 45 0.69 1.53 1.83 22 12

L-17 EF-14 B705 - Mechanical Room EXHAUST 50 500 45 0.1 0.22 1.00 12 12

NOTES:

1) 45% IS A CONSERVATIVE VALUE SELECTED TO ACCOUNT FOR THE VARIETY OF LOUVER BRANDS THAT COULD BE INSTALLED IN THE FIELD.

2) LOW VELOCITIES ARE USED FOR INTAKES AND EXHAUSTS ASSOCIATED WITH PANEL PROPELLOR FANS IN ORDER TO MAINTAIN LOW OVERAL STATIC PRESSURES FOR THESE FAN

3) DIMENSIONS MUST RANGE FROM 12 INCHES TO 120 INCHES

REQUIRED

FREE AREA

FREE AREA

(Note 1)

MINIMUM

SIZE

DESIGN LOUVER SELECTION

DIMENSIONS (Note 3)SELECTED

SIZE

ASSOCIATED

FAN

DESCRIPTION PURPOSE VELOCITY

(Note 2)

TOTAL

AIRFLOW

X

JHC

04/21/17

Louver Sizing

88127

Hilo HVAC

HIANG

Louver Sizing.xlsx

Selection Page 1 Building Complex Upgrade

Hilo

DOAS-01

FILE NAME: Static Calc

DATE: 05/25/17

CLIENT: Western States Lodging

PROJECT NO: 97758

PROJECT NAME: Marriott Residence Inn Kapolei

ENGINEER: JHC

PRELIMINARY: X FINAL: 0

Total CFM 390

Temperature of air (F): 89 ------- Refer to application requirement.

Density of air (lb/cu.ft): 0.07421 ------- Refer to Thermodynamic Property Table for Moist Air.

Roughness Factor: 0.0003 ------- ASHRAE Fundamental 1993, Pg 32.5 Table #1. **SMACNA Table 14-1

Reference - ASHRAE Handbook of Fundamentals - 2001, Chapter 32

SMACNA - HVAC Systems Duct Design 1990 - Third Edition

Duct Duct Airflow Velocity Velocity Duct Number Fitting Duct Total Additional

Section Element Round Pressure Length of Loss Pressure Pressure Loss

W H Hyd. Dia D Fittings Coefficients Loss / 100 ft Loss

CFM inch inch inch inch fpm in. W.C. ft Co in. W.C. in. W.C. in. W.C.

DOWNSTREAM OF FAN -

Duct 390 12 8 9.6 585 0.0213 15.0 0.0597 0.0090

Tee (Main - Main - air to branch) 390 12 8 9.6 585 0.0213 1 0.060 Upstream 0.0597 0.0013

Transition (Large - Small) 250 12 8 9.6 375 0.0088 1 0.060 Downstream 0.0269 0.0012

Duct 250 8 8 8.0 563 0.0197 40.0 0.0698 0.0279

Tee (Main - Main - air to branch) 250 8 8 8.0 563 0.0197 1 0.130 Upstream 0.0698 0.0026

Transition (Large - Small) 110 8 8 8.0 248 0.0038 1 0.060 Downstream 0.0161 0.0007

Duct 110 6 6 6.0 440 0.0121 15.0 0.0644 0.0097

Tee (Main - Main - air to branch) 110 6 6 6.0 440 0.0121 1 0.090 Upstream 0.0644 0.0011

Duct 60 6 6 6.0 240 0.0036 30.0 0.0219 0.0066

90° Elbow Bend 60 6 6 6.0 240 0.0036 1 1.200 Upstream 0.0219 0.0043

Transition (Rectangle - Round) 60 6 6 6.0 240 0.0036 1 0.180 Upstream 0.0219 0.0006

Duct 60 6.0 306 0.0058 5.0 0.0336 0.0017

Diffuser 60 6.0 306 0.0058 1 0.0336 0.016

Total Static Pressure (in. W.C.): 0.08 Factor of Safety (Note 1): 15.0%

******* Correction Factor for Altitude or Temperature:

External Static Pressure (in. W.C.): 0.10

******* Reference - SMACNA - HVAC Systems Duct Design 1990 - Third Edition Figure 6-5 Air Density Friction Chart Correction Factors on Pg 6.11

FAN STATIC

CALCULATION SUMMARY

Duct Size Upstream or

Downstream

Fitting Velocity

Pressure

Rectangular

Static Calc - B703.xlsx DOAS-01

DOAS-02

DATE: 05/25/17

CLIENT: Western States Lodging

PROJECT NO: 97758

PROJECT NAME: Marriott Residence Inn Kapolei

ENGINEER: JHC

PRELIMINARY: X FINAL: 0

Total CFM 500

Temperature of air (F): 89 ------- Refer to application requirement.

Density of air (lb/cu.ft): 0.07421 ------- Refer to Thermodynamic Property Table for Moist Air.

Roughness Factor: 0.0003 ------- ASHRAE Fundamental 1993, Pg 32.5 Table #1. **SMACNA Table 14-1

Reference - ASHRAE Handbook of Fundamentals - 2001, Chapter 32

SMACNA - HVAC Systems Duct Design 1990 - Third Edition

Duct Duct Airflow Velocity Velocity Duct Number Fitting Duct Total Additional

Section Element Round Pressure Length of Loss Pressure Pressure Loss

W H Hyd. Dia D Fittings Coefficients Loss / 100 ft Loss

CFM inch inch inch inch fpm in. W.C. ft Co in. W.C. in. W.C. in. W.C.

DOWNSTREAM OF FAN -

Duct 500 16 8 10.7 563 0.0197 15.0 0.0487 0.0073

90° Elbow Bend 500 16 8 10.7 563 0.0197 1 1.300 Upstream 0.0487 0.0256

Tee (Main - Main - air to branch) 500 16 8 10.7 563 0.0197 1 0.090 Upstream 0.0487 0.0018

Transition (Large - Small) 290 16 8 10.7 326 0.0066 1 0.060 Downstream 0.0184 0.0010

Duct 290 10 8 8.9 522 0.0170 10.0 0.0535 0.0054

90° Elbow Bend 290 10 8 8.9 522 0.0170 1 1.200 Upstream 0.0535 0.0204

Tee (Main - Main - air to branch) 290 10 8 8.9 522 0.0170 1 0.090 Upstream 0.0535 0.0015

Transition (Large - Small) 150 10 8 8.9 270 0.0045 1 0.060 Downstream 0.0165 0.0008

Duct 150 8 6 6.9 450 0.0126 30.0 0.0567 0.0170

Tee (Main - Branch) 150 8 6 6.9 450 0.0126 1 0.920 Upstream 0.0567 0.0116

Transition (Large - Small) 100 8 6 6.9 300 0.0056 1 0.060 Downstream 0.0275 0.0006

Duct 100 6 6 6.0 400 0.0100 10.0 0.0543 0.0054

Tee (Main - Main - air to branch) 100 6 6 6.0 400 0.0100 1 0.090 Upstream 0.0543 0.0009

Duct 50 6 6 6.0 200 0.0025 15.0 0.0158 0.0024

90° Elbow Bend 50 6 6 6.0 200 0.0025 1 1.200 Upstream 0.0158 0.0030

Transition (Rectangle - Round) 50 6 6 6.0 200 0.0025 1 0.180 Upstream 0.0158 0.0004

Duct 50 6.0 255 0.0040 5.0 0.0243 0.0012

Diffuser 50 6.0 255 0.0040 1 0.0243 0.016

Total Static Pressure (in. W.C.): 0.12 Factor of Safety (Note 1): 15.0%

******* Correction Factor for Altitude or Temperature:

External Static Pressure (in. W.C.): 0.15

******* Reference - SMACNA - HVAC Systems Duct Design 1990 - Third Edition Figure 6-5 Air Density Friction Chart Correction Factors on Pg 6.11

FAN STATIC

CALCULATION SUMMARY

Duct Size Upstream or

Downstream

Fitting Velocity

Pressure

Static Calc - B704.xlsx DOAS-02

DOAS-03

DATE: 05/25/17

CLIENT: Western States Lodging

PROJECT NO: 97758

PROJECT NAME: Marriott Residence Inn Kapolei

ENGINEER: JHC

PRELIMINARY: X FINAL: 0

Total CFM 805

Temperature of air (F): 89 ------- Refer to application requirement.

Density of air (lb/cu.ft): 0.07421 ------- Refer to Thermodynamic Property Table for Moist Air.

Roughness Factor: 0.0003 ------- ASHRAE Fundamental 1993, Pg 32.5 Table #1. **SMACNA Table 14-1

Reference - ASHRAE Handbook of Fundamentals - 2001, Chapter 32

SMACNA - HVAC Systems Duct Design 1990 - Third Edition

Duct Duct Airflow Velocity Velocity Duct Number Fitting Duct Total Additional

Section Element Round Pressure Length of Loss Pressure Pressure Loss

W H Hyd. Dia D Fittings Coefficients Loss / 100 ft Loss

CFM inch inch inch inch fpm in. W.C. ft Co in. W.C. in. W.C. in. W.C.

UPSTREAM OF DOAS -

Louver 805 30 18 22.5 215 0.0029 1 0.0034 0.0235

Insect Screen 805 30 18 22.5 215 0.0029 1 0.0034 0.0254

Damper 805 30 18 22.5 215 0.0029 1 0.0034 0.0952

Transition (Large - Small) 805 30 18 22.5 215 0.0029 1 0.070 Downstream 0.0034 0.0023

Duct 805 16 10 12.3 725 0.0327 15.0 0.0644 0.0097

Transition (Small - Large) 805 16 10 12.3 725 0.0327 1 0.290 Upstream 0.0644 0.0095

*** TO DOAS 805 16 16 16.0 453 0.0128 1 0.0199 N/A

DOWNSTREAM OF DOAS -

Transition (Large - Small) 805 16 16 16.0 453 0.0128 1 0.060 Downstream 0.0199 0.0020

Duct 805 16 10 12.3 725 0.0327 5.0 0.0644 0.0032

Tee (Main - Main - air to branch) 805 16 10 12.3 725 0.0327 1 0.090 Upstream 0.0644 0.0029

Transition (Large - Small) 460 16 10 12.3 414 0.0107 1 0.060 Downstream 0.0235 0.0016

Duct 460 10 10 10.0 662 0.0274 20.0 0.0710 0.0142

Tee (Main - Branch) 460 10 10 10.0 662 0.0274 1 0.660 Upstream 0.0710 0.0181

Duct 200 10 6 7.5 480 0.0144 15.0 0.0569 0.0085

Tee (Main - Branch) 200 10 6 7.5 480 0.0144 1 0.920 Upstream 0.0569 0.0132

Duct 130 6 6 6.0 520 0.0169 15.0 0.0869 0.0130

Tee (Main - Main - air to branch) 130 6 6 6.0 520 0.0169 1 0.090 Upstream 0.0869 0.0015

Duct 70 6 6 6.0 280 0.0049 15.0 0.0287 0.0043

90° Elbow Bend 70 6 6 6.0 280 0.0049 1 1.200 Upstream 0.0287 0.0059

Transition (Rectangle - Round) 70 6 6 6.0 280 0.0049 1 0.180 Upstream 0.0287 0.0009

Duct 70 6.0 357 0.0079 5.0 0.0442 0.0022

Diffuser 70 6.0 357 0.0079 1 0.0442 0.016

Total Static Pressure (in. W.C.): 0.27 Factor of Safety (Note 1): 15.0%

******* Correction Factor for Altitude or Temperature:

External Static Pressure (in. W.C.): 0.35

******* Reference - SMACNA - HVAC Systems Duct Design 1990 - Third Edition Figure 6-5 Air Density Friction Chart Correction Factors on Pg 6.11

FAN STATIC

CALCULATION SUMMARY

Duct Size Upstream or

Downstream

Fitting Velocity

Pressure

Static Calc - B705.xlsx DOAS-03

DOAS-04

DATE: 05/25/17

CLIENT: Western States Lodging

PROJECT NO: 97758

PROJECT NAME: Marriott Residence Inn Kapolei

ENGINEER: JHC

PRELIMINARY: X FINAL:

Total CFM 610

Temperature of air (F): 89 ------- Refer to application requirement.

Density of air (lb/cu.ft): 0.07421 ------- Refer to Thermodynamic Property Table for Moist Air.

Roughness Factor: 0.0003 ------- ASHRAE Fundamental 1993, Pg 32.5 Table #1. **SMACNA Table 14-1

Reference - ASHRAE Handbook of Fundamentals - 2001, Chapter 32

SMACNA - HVAC Systems Duct Design 1990 - Third Edition

Duct Duct Airflow Velocity Velocity Duct Number Fitting Duct Total Additional

Section Element Round Pressure Length of Loss Pressure Pressure Loss

W H Hyd. Dia D Fittings Coefficients Loss / 100 ft Loss

CFM inch inch inch inch fpm in. W.C. ft Co in. W.C. in. W.C. in. W.C.

DOWNSTREAM OF DOAS -

Duct 610 16 8 10.7 686 0.0294 45.0 0.0698 0.0314

Tee (Main - Main - air to branch) 610 16 8 10.7 686 0.0294 1 0.090 Upstream 0.0698 0.0026

Transition (Large - Small) 330 16 8 10.7 371 0.0086 1 0.060 Downstream 0.0231 0.0013

Duct 330 10 8 8.9 594 0.0220 25.0 0.0675 0.0169

Tee (Main - Main - air to branch) 330 10 8 8.9 594 0.0220 1 0.280 Upstream 0.0675 0.0062

Transition (Large - Small) 50 10 8 8.9 90 0.0005 1 0.070 Downstream 0.0024 0.0002

Duct 50 6 6 6.0 200 0.0025 15.0 0.0158 0.0024

Transition (Rectangle - Round) 50 6 6 6.0 200 0.0025 1 0.180 Upstream 0.0158 0.0004

Duct 50 6.0 255 0.0040 5.0 0.0243 0.0012

Diffuser 50 6.0 255 0.0040 1 0.0243 0.016

Total Static Pressure (in. W.C.): 0.08 Factor of Safety (Note 1): 15.0%

******* Correction Factor for Altitude or Temperature:

External Static Pressure (in. W.C.): 0.10

******* Reference - SMACNA - HVAC Systems Duct Design 1990 - Third Edition Figure 6-5 Air Density Friction Chart Correction Factors on Pg 6.11

FAN STATIC

CALCULATION SUMMARY

Duct Size Upstream or

Downstream

Fitting Velocity

Pressure

Static Calc - B701.xlsx DOAS-04

FCU-01

DATE: 05/25/17

CLIENT: Western States Lodging

PROJECT NO: 97758

PROJECT NAME: Marriott Residence Inn Kapolei

ENGINEER: JHC

PRELIMINARY: X FINAL: 0

Total CFM 615

Temperature of air (F): 89 ------- Refer to application requirement.

Density of air (lb/cu.ft): 0.07421 ------- Refer to Thermodynamic Property Table for Moist Air.

Roughness Factor: 0.0003 ------- ASHRAE Fundamental 1993, Pg 32.5 Table #1. **SMACNA Table 14-1

Reference - ASHRAE Handbook of Fundamentals - 2001, Chapter 32

SMACNA - HVAC Systems Duct Design 1990 - Third Edition

Duct Duct Airflow Velocity Velocity Duct Number Fitting Duct Total Additional

Section Element Round Pressure Length of Loss Pressure Pressure Loss

W H Hyd. Dia D Fittings Coefficients Loss / 100 ft Loss

CFM inch inch inch inch fpm in. W.C. ft Co in. W.C. in. W.C. in. W.C.

UPSTREAM OF FCU -

Diffuser 615 12 10 10.9 738 0.0340 1 0.0774 0.15

Duct 615 12 10 10.9 738 0.0340 15.0 0.0774 0.0116

90° Elbow Bend 615 12 10 10.9 738 0.0340 2 1.200 Upstream 0.0774 0.0815

Transition (Small - Large) 615 12 10 10.9 738 0.0340 1 0.680 Upstream 0.0774 0.0231

*** TO FCU 615 56 12 19.8 132 0.0011 1 0.0017 N/A

DOWNSTREAM OF FCU -

Transition (Large - Small) 615 56 12 19.8 132 0.0011 1 0.070 Downstream 0.0017 0.0024

Duct 615 12 10 10.9 738 0.0340 10.0 0.0774 0.0077

90° Elbow Bend 615 12 10 10.9 738 0.0340 1 1.200 Upstream 0.0774 0.0407

Transition (Rectangle - Round) 615 12 10 10.9 738 0.0340 1 0.220 Upstream 0.0774 0.0075

Duct 615 10.0 1128 0.0793 5.0 0.1869 0.0093

Diffuser 615 10.0 1128 0.0793 1 0.1869 0.149

Total Static Pressure (in. W.C.): 0.48 Factor of Safety (Note 1): 15.0%

******* Correction Factor for Altitude or Temperature:

External Static Pressure (in. W.C.): 0.60

******* Reference - SMACNA - HVAC Systems Duct Design 1990 - Third Edition Figure 6-5 Air Density Friction Chart Correction Factors on Pg 6.11

FAN STATIC

CALCULATION SUMMARY

Duct Size Upstream or

Downstream

Fitting Velocity

Pressure

Static Calc - B703.xlsx FCU-01

FCU-02

DATE: 05/25/17

CLIENT: Western States Lodging

PROJECT NO: 97758

PROJECT NAME: Marriott Residence Inn Kapolei

ENGINEER: JHC

PRELIMINARY: X FINAL: 0

Total CFM 615

Temperature of air (F): 89 ------- Refer to application requirement.

Density of air (lb/cu.ft): 0.07421 ------- Refer to Thermodynamic Property Table for Moist Air.

Roughness Factor: 0.0003 ------- ASHRAE Fundamental 1993, Pg 32.5 Table #1. **SMACNA Table 14-1

Reference - ASHRAE Handbook of Fundamentals - 2001, Chapter 32

SMACNA - HVAC Systems Duct Design 1990 - Third Edition

Duct Duct Airflow Velocity Velocity Duct Number Fitting Duct Total Additional

Section Element Round Pressure Length of Loss Pressure Pressure Loss

W H Hyd. Dia D Fittings Coefficients Loss / 100 ft Loss

CFM inch inch inch inch fpm in. W.C. ft Co in. W.C. in. W.C. in. W.C.

UPSTREAM OF FCU -

Diffuser 615 12 10 10.9 738 0.0340 1 0.0774 0.15

Duct 615 12 10 10.9 738 0.0340 15.0 0.0774 0.0116

90° Elbow Bend 615 12 10 10.9 738 0.0340 2 1.200 Upstream 0.0774 0.0815

Transition (Small - Large) 615 12 10 10.9 738 0.0340 1 0.680 Upstream 0.0774 0.0231

*** TO FCU 615 56 12 19.8 132 0.0011 1 0.0017 N/A

DOWNSTREAM OF FCU -

Transition (Large - Small) 615 56 12 19.8 132 0.0011 1 0.070 Downstream 0.0017 0.0024

Duct 615 12 10 10.9 738 0.0340 10.0 0.0774 0.0077

90° Elbow Bend 615 12 10 10.9 738 0.0340 1 1.200 Upstream 0.0774 0.0407

Transition (Rectangle - Round) 615 12 10 10.9 738 0.0340 1 0.220 Upstream 0.0774 0.0075

Duct 615 10.0 1128 0.0793 5.0 0.1869 0.0093

Diffuser 615 10.0 1128 0.0793 1 0.1869 0.149

Total Static Pressure (in. W.C.): 0.48 Factor of Safety (Note 1): 15.0%

******* Correction Factor for Altitude or Temperature:

External Static Pressure (in. W.C.): 0.60

******* Reference - SMACNA - HVAC Systems Duct Design 1990 - Third Edition Figure 6-5 Air Density Friction Chart Correction Factors on Pg 6.11

FAN STATIC

CALCULATION SUMMARY

Duct Size Upstream or

Downstream

Fitting Velocity

Pressure

Static Calc - B703.xlsx FCU-02

FCU-03

DATE: 05/25/17

CLIENT: Western States Lodging

PROJECT NO: 97758

PROJECT NAME: Marriott Residence Inn Kapolei

ENGINEER: JHC

PRELIMINARY: X FINAL: 0

Total CFM 970

Temperature of air (F): 89 ------- Refer to application requirement.

Density of air (lb/cu.ft): 0.07421 ------- Refer to Thermodynamic Property Table for Moist Air.

Roughness Factor: 0.0003 ------- ASHRAE Fundamental 1993, Pg 32.5 Table #1. **SMACNA Table 14-1

Refer…