ATTCH 10_88127 - Drawings - Mechanical R02 - Certified.pdf
PDF 9 MB Posted
- Attached to
- UPGRADE BUILDING COMPLEX HILO Federal contract opportunity
- Solicitation number
- W50SLF-22-R-0001
- Issued by
- Department of the Army National Guard
About this file
This document provides details of a federal contract opportunity for construction services. The U.S. Property and Fiscal Officer for Hawaii will award a firm fixed-price contract to upgrade five buildings at the 291st Combat Communications Squadron in Hilo, Hawaii. Work includes replacing windows and doors, repairing and coating roofs, installing ceilings and lights, and upgrading HVAC systems. The base value is estimated between $1-5 million, to be funded by SRM funds. The contract includes three options and has a period of performance of 360 days from notice to proceed. The NAICS code is 236220 and it is set aside for small businesses with average annual revenue under $39.5 million. The pre-proposal conference is March 25th and proposals are due April 21st. The source selection will be conducted per FAR Part 15.
View the file
Other files for this federal contract opportunity
Show all 35
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
S c a l e
F o r
M i c r o f i l m i n g
I n c h e s
M i l l i m e t e r s
1 1312111098765432
I
H
G
F
E
D
C
B
A date detailed checkeddesigned ofsheet sheets project contract rev.drawing file
HONOLULU, HAWAII
ENGINEERS ARCHITECTS & CONSULTANTS
Project No. - MABE152003
UPGRADE BUILDING
HAWAII AIR NATIONAL GUARD
KEAUKAHA ANG STATION, HAWAII
COMPLEX, HILO
01/28/220 FINAL SUBMITTAL BS
MABE 15200391701
C O
P Y
R I G
H T
05/01/2017 A. QUEVEDO
J. CHORIKI B. SEABAUGH
MECHANICAL LEGEND & ABBREVIATIONS
M-001 0
91701_M001.dwg
B U
R N
M
D
O N
N E
L L
E
N G
I N
E E
R I N
G
C
O M
P A
N Y
I N
C
DETAIL NUMBER
SCALE
TITLE
M
S
MECHANICAL ABBREVIATIONS
24x12
24x12 OV
12Ø
AFF
AHU
ARV
BOD
BW
CA
CD
CHR
CHS
CU
CRU
CFM
CUH
CONC
DH
DN
DOAS
DSS
EL
ELL
EA
EG
ER
ERC
EXIST
F
FCU
FF
FOB
FOT
GH
INV EL
L
LDP
LR
MA
MJ
MW
NC
NO
OA
OB
PB
PSIA
PSIG
RED
RMJ
RA
RG
RL
RS
SCH
SR
SO
STM
ST
SA
SRC
SR
SW
TOA
TOC
TOD
TOS
UH
VAV
V
WE
WN
RECTANGULAR DUCT DIMENSION - IN
OVAL DUCT DIMENSION - IN
ROUND DUCT DIMENSION - IN
ABOVE FINISHED FLOOR
AIR HANDLING UNIT
AIR RELEASE VALVE
BOTTOM OF DUCT
BUTT WELD
CONDENSER AIR
CONDENSATE DRAIN
CHILLED WATER RETURN
CHILLED WATER SUPPLY
CONDENSING UNIT
COMPUTER ROOM UNIT
CUBIC FEET PER MINUTE
CABINET UNIT HEATER
CONCENTRIC
DOOR HEATER
DOWN
DEDICATED OUTSIDE AIR HANDLING UNIT
DUCTLESS SPLIT SYSTEM
ELEVATION
ELBOW
EXHAUST AIR
EXHAUST GRILLE
EXHAUST REGISTER
ELECTRIC REHEAT COIL
EXISTING
FAN
FAN COIL UNIT
FLAT FACED
FLAT ON BOTTOM
FLAT ON TOP
GRAVITY HOOD
INVERT ELEVATION
LOUVER
LOCAL DISPLAY PANEL
LONG RADIUS
MIXED AIR
MECHANICAL JOINT
MAKE-UP WATER
NORMALLY CLOSED (FAIL POSITION)
NORMALLY OPEN (FAIL POSITION)
OUTSIDE AIR
OPPOSED BLADE
PARALLEL BLADE
POUNDS PER SQUARE INCH ABSOLUTE
POUNDS PER SQUARE INCH GAUGE
REDUCER-REDUCING
RESTRAINED MECHANICAL JOINT
RETURN AIR
RETURN AIR GRILLE
REFRIGERANT LIQUID
REFRIGERANT SUCTION
SCHEDULE
SHORT RADIUS
SLIP ON
STEAM
STEAM TRAP
SUPPLY AIR
SPRING RETURN CLOSED
SUPPLY REGISTER
SOCKET WELD
TEMPERED OUTSIDE AIR
TOP OF CONCRETE
TOP OF DUCT
TOP OF STEEL
UNIT HEATER
VARIABLE AIR VOLUME
VENT
WELD END
WELD NECK
GENERAL NOTES:
1. LEGEND IS GENERAL IN NATURE AND MAY INDICATE MORE INFORMATION THAN IS
APPLICABLE TO PROJECT. SEE DRAWINGS FOR SPECIFIC SYMBOLS AND
ABBREVIATIONS.
2. PROVIDE ALL MATERIALS, VALVES, HANGERS, ETC. AND EQUIPMENT AND
PERFORM ALL LABOR REQUIRED TO INSTALL COMPLETE AND OPERABLE
MECHANICAL SYSTEMS AS INDICATED ON THE DRAWINGS, AS SPECIFIED AND AS
REQUIRED BY CODE.
3. INSTALL ALL MECHANICAL EQUIPMENT AND APPURTENANCES IN ACCORDANCE
WITH MANUFACTURERS RECOMMENDATIONS, CONTRACT DOCUMENTS, AND
APPLICABLE CODES AND REGULATIONS.
4. COORDINATE CONSTRUCTION OF ALL MECHANICAL WORK WITH STRUCTURAL,
CIVIL, ELECTRICAL WORK, ETC., SHOWN ON OTHER CONTRACT DOCUMENT
DRAWINGS.
5. MAINTAIN A MINIMUM OF 6'-8" CLEARANCE TO UNDERSIDE OF PIPES, CONDUITS,
ETC., THROUGHOUT ACCESS ROUTES AND IN MECHANICAL ROOMS.
6. LOCATE ALL MECHANICAL EQUIPMENT FOR UNOBSTRUCTED ACCESS TO UNIT
ACCESS PANELS, CONTROLS, AND VALVING.
7. VERIFY DIMENSIONS AND CONNECTION SIZE WITH FURNISHED EQUIPMENT
8. ALL ELEVATIONS ARE ABOVE FINISHED FLOOR TO BOTTOM OF DUCT, PIPE, OR
PIPE INSULATION UNLESS NOTED OTHERWISE.
9. OUTSIDE AIR DUCTWORK AT INTAKE LOUVERS SHALL BE SLOPED TOWARDS THE
BUILDING EXTERIOR WALL.
10. PIPES ARE OFFSET FOR CLARITY. CONTRACTOR SHALL ROUTE PIPES AS TIGHT
TO STRUCTURE AS POSSIBLE. INSTALL VALVES IN ACCESSIBLE LOCATIONS FOR
MAINTENANCE. CONTRACTOR SHALL COORDINATE PIPE ELEVATIONS WITH
OTHER DISCIPLINES AS REQUIRED.
11. THE EXISTING CONDITIONS INDICATED ON THESE DRAWINGS ARE TAKEN FROM
THE BEST INFORMATION AVAILABLE, FROM VISUAL SITE OBSERVATIONS, AND
AVAILABLE DRAWINGS. THE INFORMATION IS SHOWN TO HELP ESTABLISH THE
EXTENT OF THE WORK TO BE DONE. THE CONTRACTOR SHALL VERIFY ALL
ACTUAL CONDITIONS AND THE INTENT OF THE WORK INDICATED ON THESE
DRAWINGS.
12. PATCH ALL PENETRATIONS ASSOCIATED WITH REMOVAL OF EXISTING
EQUIPMENT, DUCTWORK, PIPING, ETC.
13. ALL TAKEOFF DUCTS TO DIFFUSERS, REGISTERS, AND GRILLES ARE EQUAL TO
THE NECK SIZE UNLESS OTHERWISE NOTED.
14. INSTALL ALL CONDENSING UNITS WITH MANUFACTURER RECOMMENDED
MINIMUM CLEARANCE.
15. LOCATE TRANSFER AIR DUCTS AND OPENINGS 24" ABOVE HIGHEST CEILING
ELEVATION UNLESS OTHERWISE NOTED.
16. OCCUPANCY SENSORS AND CO2 SENSORS SHALL BE PROVIDED BY DIVISION 23.
WIRE OCCUPANCY SENSORS AND CO2 SENSORS BACK TO CORRESPONDING
DOAS UNITS AS SCHEDULED FOR VENTILATION CONTROL.
17. PROVIDE STRUCTURAL EQUIPMENT PADS IN ACCORDANCE WITH DETAIL IN
STRUCTURAL DRAWINGS.
18. ALL FERROUS MATERIALS USED FOR PIPE HANGERS, ANCHORS, AND OTHER
SUPPORTS, SHALL BE HOT-DIPPED GALVANIZED PER UFC 3-440-05N. JOINTS AND
DAMAGED SURFACES SHALL BE TOUCHED UP WITH A FIELD APPLIED ZINC-RICH
COMPOUND.
19. CONTRACTOR SHALL BALANCE ALL DIFFUSERS TO FLOW RATE SHOWN ON PLANS.
20. LOCATE ALL MECHANICAL EQUIPMENT FOR UNOBSTRUCTED ACCESS TO UNIT
ACCESS PANELS, CONTROLS, AND VALVING.
21. DUCT DIMENSIONS INDICATED REFER TO SHEET METAL DIMENSIONS. SHEET
METAL SIZE SHALL BE AIR OPENING DIMENSIONS PLUS THE THICKNESS OF
ACOUSTICAL LINER WHERE LINER IS INSTALLED. WHERE LINER IS NOT INSTALLED,
AIR OPENING SIZE AND SHEET METAL SIZE SHALL BE THE SAME.
22. DUCT STATIC PRESSURE CLASSIFICATION: UNLESS OTHERWISE INDICATED,
CONSTRUCT DUCTS ON THE DISCHARGE SIDE OF FANS TO HAVE A 1.0 IN. W.C.
POSITIVE PRESSURE AND DUCTS ON THE INLET SIDE OF FANS TO HAVE A 1.0 IN.
W.C. NEGATIVE PRESSURE CLASSIFICATION.
23. COORDINATE ALL WALL AND ROOF PENETRATIONS WITH STRUCTURAL AND
ARCHITECTURAL PLANS.
24. INSTALL TEMPERATURE CONTROLS AT 48" ABOVE FINISHED FLOOR AND
COORDINATE WITH OTHER DEVICES LOCATED ON WALLS. COORDINATE WITH
ARCHITECTURAL WALL FINISHES AND INTERIOR FURNITURE PLACEMENT.
SECTION
DESIGNATOR
INDICATES PERSPECTIVE
AND LIMITS OF SECTION
DRAWING WHERE
SECTION IS SHOWN
INDICATES
LIMITS OF
DETAIL
DETAIL
DESIGNATOR
DRAWING WHERE
DETAIL IS SHOWN
ROUND FLEXIBLE DUCT
5'-0" MAX LENGTH
NEW WORK
EXISTING
TO REMAIN DEMOLITION
EXISTING
LOUVERS AND SCREEN
915x610
[36x24]
HUMIDISTAT
THERMOSTAT
H
LINEAR SLOT DIFFUSER
ROUND DIFFUSER
SQUARE OR RECT. DIFFUSER
RETURN OR EXHAUST AIR DUCT SECTION
SUPPLY OR OUTSIDE AIR DUCT SECTION
POINT OF CHANGE IN DUCT
CONSTRUCTION (BY STATIC
PRESSURE CLASS "N" SUPERSCRIPT
INDICATES NEGATIVE PRESSURE.)
SQUARE OR RECTANGULAR TO
ROUND TRANSITION
DROP IN RESPECT TO AIR-FLOW
RISE IN RESPECT TO AIR-FLOW
R
D
TEE W/TURNING VANES
RECTANGULAR ELBOW W/TURNING VANES
FLEXIBLE DUCT CONNECTION
HEAT STOP FOR FIRE RATED CLG
DAMPERS: (SD)
SMOKE-
FIRE/SMOKE (F/SD)-
FIRE DAMPER:
SHOW VERTICAL (WALL)
SHOW HORIZ. (FLOOR)
ACCESS DOOR (AD), ACCESS PANEL (AP)
BACKDRAFT DAMPER
MANUAL BALANCE DAMPER
CONTROL DAMPER, MOTOR OPERATED
HVAC LEGEND
BD
AD
AD
AD
S
AD
CONSTRUCTION INTERFACE
APPLICATION
SPEC. TYPE
SA-A
(2)150-8Ø
NECK SIZE - IN
CFM
NUMBER OF DEVICES SHARING SAME
CHARACTERISTICS (OPTIONAL)
AIR DISTRIBUTION DEVICE IDENTIFICATION
DETAIL CALLOUT SYMBOL
SECTION CUT SYMBOL
DETAIL/SECTION TITLE
T
SECURITY MANBARS
CARBON DIOXIDE SENSOR
C2
DIFFERENTIAL PRESSURE SENSOR
DP
M003
A1
M001
A1
SCALE:
A1
DETAIL TITLE
NOT TO SCALE
DSP DUCT STATIC PRESSURE SENSOR
OS OCCUPANCY SENSOR
EXP:4/30/22
EXIST. SUPPLY &
MAINTENANCE
BLDG. 704
EXIST. COMMUNICATIONS
BLDG. 705
EXIST. CLASSROM ATC &
TESTING ROOMS
BLDG. 703
EXIST. ADMIN.
BLDG. 701
EXIST. AUTOMOTIVE MAINTENANCE
SUPPORT EQUIPMENT SHOP
BLDG. 702
314°35' → 600.00 (182 882)
134°35' ← 600.00 (182 882)
MD101
F6
MD101
F6
MD101
F6
MD101
F6
MD103
G6
MD102
I2
S c a r
M i c r o f i l m i n g
I n c h e s
M i l l i m e t e r s
1 1312111098765432
I
H
G
F
E
D
C
B
A date detailed checkeddesigned ofsheet sheets project contract rev.drawing file
HONOLULU, HAWAII
ENGINEERS ARCHITECTS & CONSULTANTS
Project No. - MABE 152003
UPGRADE BUILDING
HAWAII AIR NATIONAL GUARD
KEAUKAHA ANG STATION, HAWAII
COMPLEX, HILO
MABE 15200391701
01/28/220 FINAL SUBMITTAL BS
C O
P Y
R I G
HVAC OVERALL DEMO PLAN
MD100 0
88127_MD100.dwg
B U
R N
D
O N
N E
L L
E
N G
I N
E E
R I N
G
C
O M
P A
N Y
I N
C
1. FOR GENERAL NOTES, LEGEND, AND ABBREVIATIONS SEE DRAWING
M-001.
2. REMOVE POWER FEED FROM ALL HVAC EQUIPMENT TO BREAKER IN
PANELBOARD INCLUDING STARTERS, DISCONNECTS, MOTOR-RATED
SWITCHES AND CONDUCTORS.
GENERAL NOTES
SCALE:
I6
HVAC OVERALL DEMO PLAN
1/32" = 1'-0"
SCALE IN FEET
16'0 64'32'
KEYPLAN
1 2
S c a r
M i c r o f i l m i n g
I n c h e s
M i l l i m e t e r s
1 1312111098765432
I
H
G
F
E
D
C
B
A date detailed checkeddesigned ofsheet sheets project contract rev.drawing file
HONOLULU, HAWAII
ENGINEERS ARCHITECTS & CONSULTANTS
Project No. - MABE 152003
UPGRADE BUILDING
HAWAII AIR NATIONAL GUARD
KEAUKAHA ANG STATION, HAWAII
COMPLEX, HILO
MABE 15200391701
01/28/220 FINAL SUBMITTAL BS
C O
P Y
R I G
HVAC DEMO PLAN B701, B703, B704 & B705
MD101 0
88127_MD101.dwg
B U
R N
D
O N
N E
L L
E
N G
I N
E E
R I N
G
C
O M
P A
N Y
I N
C
DEMO EXISTING HVAC EQUIPMENT, DUCTWORK, PIPING, CONTROLS,
SUPPORTS, AND OTHER ASSOCIATED APPURTENANCES.
REMOVE POWER FEED FROM ALL HVAC EQUIPMENT TO BREAKER IN
PANELBOARD INCLUDING STARTERS, DISCONNECTS, MOTOR-RATED
SWITCHES AND CONDUCTORS.
REMOVE HVAC EQUIPMENT AND DUCTWORK THEN TEMPORARILY CAP
PENETRATION TO BE REUSED.
KEY NOTES
1. FOR GENERAL NOTES, LEGEND, AND ABBREVIATIONS SEE DRAWING M-001.
GENERAL PLAN NOTES
MD401
G9
S E
E
B
U I L D
I N
G
E
X T
E N
S I O
N
O
N
M
D
MD401
I3
SCALE:
F6
HVAC OVERALL DEMO PLAN
NOT TO SCALE
SCALE:
I3
HVAC ROOF DEMO PLAN
NOT TO SCALE
SCALE:
I9
B705 SITE DEMO PLAN
NOT TO SCALE
MD101
I3
1 2
MD101
I3
1 2
KEYPLAN
BUILDING 704
BUILDING 701
BUILDING 703
BUILDING 705
S c a r
M i c r o f i l m i n g
I n c h e s
M i l l i m e t e r s
1 1312111098765432
I
H
G
F
E
D
C
B
A date detailed checkeddesigned ofsheet sheets project contract rev.drawing file
HONOLULU, HAWAII
ENGINEERS ARCHITECTS & CONSULTANTS
Project No. - MABE 152003
UPGRADE BUILDING
HAWAII AIR NATIONAL GUARD
KEAUKAHA ANG STATION, HAWAII
COMPLEX, HILO
MABE 15200391701
01/28/220 FINAL SUBMITTAL BS
C O
P Y
R I G
HVAC DEMO PLAN B704 EXTENSION
MD102 0
88127_MD102.dwg
B U
R N
D
O N
N E
L L
E
N G
I N
E E
R I N
G
C
O M
P A
N Y
I N
C
DEMO EXISTING HVAC EQUIPMENT, DUCTWORK, PIPING, CONTROLS,
SUPPORTS, AND OTHER ASSOCIATED APPURTENANCES.
REMOVE POWER FEED FROM ALL HVAC EQUIPMENT TO BREAKER IN
PANELBOARD INCLUDING STARTERS, DISCONNECTS, MOTOR-RATED SWITCHES
AND CONDUCTORS.
REMOVE HVAC EQUIPMENT AND DUCTWORK THEN TEMPORARILY CAP
PENETRATION TO BE REUSED.
KEY NOTES
1. FOR GENERAL NOTES, LEGEND, AND ABBREVIATIONS SEE DRAWING M-001.
GENERAL PLAN NOTES
SCALE:
B2
HVAC B704 ELEVATION DEMO PLAN
NOT TO SCALE
SCALE:
I2
HVAC B704 EXTENSION DEMO PLAN
NOT TO SCALE SCALE:
I9
HVAC B704 ROOF DEMO PLAN
NOT TO SCALE
1 2
KEYPLAN
MD102
B2 a r
M i c r o f i l m i n g
I n c h e s
M i l l i m e t e r s
1 1312111098765432
I
H
G
F
E
D
C
B
A date detailed checkeddesigned ofsheet sheets project contract rev.drawing file
HONOLULU, HAWAII
ENGINEERS ARCHITECTS & CONSULTANTS
Project No. - MABE 152003
UPGRADE BUILDING
HAWAII AIR NATIONAL GUARD
KEAUKAHA ANG STATION, HAWAII
COMPLEX, HILO
MABE 15200391701
01/28/220 FINAL SUBMITTAL BS
C O
P Y
R I G
HVAC DEMO PLAN B702
MD103 0
88127_MD103.dwg
B U
R N
D
O N
N E
L L
E
N G
I N
E E
R I N
G
C
O M
P A
N Y
I N
C
DEMO EXISTING HVAC EQUIPMENT, DUCTWORK, PIPING, CONTROLS,
SUPPORTS, AND OTHER ASSOCIATED APPURTENANCES.
REMOVE POWER FEED FROM ALL HVAC EQUIPMENT TO BREAKER IN
PANELBOARD INCLUDING STARTERS, DISCONNECTS, MOTOR-RATED SWITCHES
AND CONDUCTORS.
KEY NOTES
1. FOR GENERAL NOTES, LEGEND, AND ABBREVIATIONS SEE DRAWING M-001.
GENERAL PLAN NOTES
SCALE:
G6
HVAC B702 DEMO PLAN
NOT TO SCALE
1 2
KEYPLAN
1 2 a r
M i c r o f i l m i n g
I n c h e s
M i l l i m e t e r s
1 1312111098765432
I
H
G
F
E
D
C
B
A date detailed checkeddesigned ofsheet sheets project contract rev.drawing file
HONOLULU, HAWAII
ENGINEERS ARCHITECTS & CONSULTANTS
Project No. - MABE 152003
UPGRADE BUILDING
HAWAII AIR NATIONAL GUARD
KEAUKAHA ANG STATION, HAWAII
COMPLEX, HILO
MABE 15200391701
01/28/220 FINAL SUBMITTAL BS
C O
P Y
R I G
HVAC ENLARGED DEMO PLANS
MD401 0
88127_MD401.dwg
B U
R N
D
O N
N E
L L
E
N G
I N
E E
R I N
G
C
O M
P A
N Y
I N
C
DEMO EXISTING HVAC EQUIPMENT, DUCTWORK, PIPING, CONTROLS,
SUPPORTS, AND OTHER ASSOCIATED APPURTENANCES.
REMOVE POWER FEED FROM ALL HVAC EQUIPMENT TO BREAKER IN
PANELBOARD INCLUDING STARTERS, DISCONNECTS, MOTOR-RATED SWITCHES
AND CONDUCTORS.
EXISTING COMPRESSED AIR SYSTEM TO REMAIN.
KEY NOTES
1. FOR GENERAL NOTES, LEGEND, AND ABBREVIATIONS SEE DRAWING M-001.
GENERAL PLAN NOTES
SCALE:
I3
HVAC B704 ENLARGED DEMO PLAN
NOT TO SCALE
SCALE:
G9
HVAC B705 ENLARGED DEMO PLAN
NOT TO SCALE
1 2
KEYPLAN
1 2
EXIST. SUPPLY &
MAINTENANCE
BLDG. 704
EXIST. COMMUNICATIONS
BLDG. 705
EXIST. CLASSROM ATC &
TESTING ROOMS
BLDG. 703
EXIST. ADMIN.
BLDG. 701
EXIST. AUTOMOTIVE MAINTENANCE
SUPPORT EQUIPMENT SHOP
BLDG. 702
314°35' → 600.00 (182 882)
134°35' ← 600.00 (182 882)
M-102
D5
M-101
D5
M-102
I6
M-103
I6
M-101
I6
S c a r
M i c r o f i l m i n g
I n c h e s
M i l l i m e t e r s
1 1312111098765432
I
H
G
F
E
D
C
B
A date detailed checkeddesigned ofsheet sheets project contract rev.drawing file
HONOLULU, HAWAII
ENGINEERS ARCHITECTS & CONSULTANTS
Project No. - MABE152003
UPGRADE BUILDING
HAWAII AIR NATIONAL GUARD
KEAUKAHA ANG STATION, HAWAII
COMPLEX, HILO
01/28/220 FINAL SUBMITTAL BS
MABE 15200391701
C O
P Y
R I G
HVAC OVERALL FLOOR PLAN
M-100 0
88127_M100.dwg
B U
R N
D
O N
N E
L L
E
N G
I N
E E
R I N
G
C
O M
P A
N Y
I N
C
1. FOR GENERAL NOTES, LEGEND, AND ABBREVIATIONS SEE DRAWINGS
M-001.
GENERAL NOTES
SCALE:
HVAC OVERALL FLOOR PLAN
1/32" = 1'-0"
SCALE IN FEET
16'0 64'32'
KEYPLAN
LUBRICATION
BAY
REPAIR BAY
REPAIR BAY
SHOP AREA
OFFICE
PARTS &
ISSUE
VEHICLE
DISPATCH &
DRIVERS
OFFICE
TOOLS &
STORAGE
UTILITY ROOM
MEN
WOMEN
BATTERY
RM.
JAN.
STORAGE
WASH &
PAINT BAY
CORR.
1 2 3 4 5 6 7 8 9 10
EE
DD
CC
BB
AA
STORAGE
OFFICES
EF-02
INTAKE THRU
DOOR LOUVER
INTAKE THRU
DOOR LOUVER
INTAKE THRU
DOOR LOUVER
INTAKE THRU
DOOR LOUVER
EF-05
L-04 12x12
140 CFM EA
FCU-18
L-05 12x12
25 CFM OA
6x6 OA
CU-DSS-01
FCU-19
6x6 OA
FCU-20
6x6 OA
FCU-21
L-08 12x12
30 CFM OA
6x6 OA
L-02 28x12
520 CFM EA
EF-03
6x6 EA
EA-G
280-12x6
EA-G
100-6x6
EA-G
140-8x6
8x6EA
RS/RL
M
BD
BD
BD
M
T
T
T
T
FCU-18
FCU-19 FCU-20
FCU-21
12x6 EA
12x6 EA
12x12 EA
CD4CD 4
CD
T
EF-05
DDC
PANEL
7 8
J
H
G1
G
F
E
SQUAD
ADMIN/PERSONNEL
CONF. ROOM
DOAS-04
10x8 OA
16x8 OA
10x8 OA
6x6 OA
FCU-04
12x12 RA
20x12 SA
12x12 SA
FCU-05
10x10 RA
HP-01
SEE M-102
OA-A
(2)280-8Ø
OA-A
50-6Ø
RA-B
NA-10x10
SA-A
480-10Ø
SA-A
(2)425-10Ø
SA-A
(2)665-12Ø
RA-B
(2)NA-12x12
10x8 OA
12x12 RA
12x12 SA
RS/RL
8x12 RA
RA-B
(2)NA-12x8
8x12 RA
10x10 SA
10x10 SA
10x10 SA
18x12 SA
24x12 RA
24x12 RA
T
FCU-05
CD4
T
FCU-04
S c a r
M i c r o f i l m i n g
I n c h e s
M i l l i m e t e r s
1 1312111098765432
I
H
G
F
E
D
C
B
A date detailed checkeddesigned ofsheet sheets project contract rev.drawing file
HONOLULU, HAWAII
ENGINEERS ARCHITECTS & CONSULTANTS
Project No. - MABE152003
UPGRADE BUILDING
HAWAII AIR NATIONAL GUARD
KEAUKAHA ANG STATION, HAWAII
COMPLEX, HILO
01/28/220 FINAL SUBMITTAL BS
MABE 15200391701
C O
P Y
R I G
HVAC FLOOR PLAN
BUILDINGS 701 AND 702
M-101 0
91701_M101.dwg
B U
R N
D
O N
N E
L L
E
N G
I N
E E
R I N
G
C
O M
P A
N Y
I N
C
SCALE:
D4
BUILDING 701 - HVAC FLOOR PLAN
1/8" = 1'-0"
SCALE:
I6
BUILDING 702 - HVAC FLOOR PLAN
1/8" = 1'-0"
1. FOR GENERAL NOTES, LEGEND, AND ABBREVIATIONS SEE DRAWING
M-001.
2. INSTALL ALL OUTDOOR CONDENSING UNITS WITH MANUFACTURER
RECOMMENDED MINIMUM CLEARANCE.
3. FOR GENERAL DETAILS SEE DRAWINGS M-501 THRU M-504.
4. CONTRACTOR SHALL COORDINATE BRANCH CIRCUITING
REFRIGERANT PIPE SIZES AND ACCESSORIES WITH EQUIPMENT
MANUFACTURER.
5. REFRIGERANT PIPING SHOWN IS FOR REFERENCE ONLY AND
DEMONSTRATES DESIRED ROUTING. SIZES ARE FOR REFERENCE
ONLY. ROUTING AND SIZES ARE FOR THE BASIS OF DESIGN
MANUFACTURER AND MAY VARY FROM THE INSTALLED
MANUFACTURER'S REQUIREMENTS. CONTRACTOR SHALL BE
RESPONSIBLE FOR DESIGNING FULL REFRIGERANT PIPING PLAN AND
COORDINATING WITH OTHER DISCIPLINES.
6. CONTRACTOR SHALL BE RESPONSIBLE FOR ADDED REFRIGERANT
BASED ON INSTALLED PIPING LENGTHS.
7. LIQUID AND SUCTION PIPING SHALL BE INSULATED PER
MANUFACTURER'S RECOMMENDATIONS.
8. CONDENSATE DRAIN PIPING SHALL BE DWV COPPER TUBING
CONFORMING TO ASTM B306 AND INSTALLED WITH A SLOPE OF NOT
LESS THAN 1% TOWARDS DISCHARGE.
GENERAL NOTES
16'8'4'0
SCALE IN FEET
KEYPLAN
16'8'4'0
SCALE IN FEET
LOCATE IN EXISTING WALL PENETRATION.
CONNECT TO DUCTWORK IN PLENUM SPACE ABOVE
(SEE M-110).
SIZE AND ROUTE REFRIGERANT LINES PER
MANUFACTURERS INSTRUCTIONS.
SIZE AND ROUTE CONDENSATE DRAIN LINES PER
MANUFACTURERS INSTRUCTIONS. PENETRATE WALLS IN
PLENUM SPACE, DOWN EXTERIOR SIDE OF WALL,
DISCHARGE INTO GRAVEL, AND TERMINATE WITH A 45
DEGREE ELBOW WITH SMOOTH BORE CORROSION
RESISTANT OUTLET POINTING DOWN.
ROUTE REFRIGERANT PIPING ABOVE GRADE, ALONG
THE GROUND, UP THE EXTERIOR SIDE OF WALL, AND
PENETRATE WALL IN PLENUM SPACE.
KEY NOTES
SQ. MAINT.
OFFICER
SQUADRON
MAINTENANCE
MANAGEMENT
SQUADRON
UNIT SUPPLY
ARMS
STORAGE RM
SQUADRON
SUPPLY
OFFICER
SQ. SUPPLY
ADMIN.
OFFICE
FRAME
JAN.
SERVICE
ROOM
MEN
WOMEN
ISSUE ROOM
9 10 11 12 13 14
L
K
J
H
G1
G
F
EF-08
L-11 12x12
130 CFM EA
EF-09
L-12 12x12
130 CFM EA
INTAKE THRU
DOOR LOUVER
INTAKE THRU
DOOR LOUVER
EF-07
L-10 12x12
100 CFM EA
INTAKE THRU
DOOR LOUVER
EF-10
10x10 EA
20x10 TOILET EXHAUST
DUCT UP THRU ROOF
INTAKE THRU
DOOR LOUVER
EF-06
L-09 12x14
190 CFM EA
210-6Ø
OA-D
FCU-06
10x10 RA
DOAS-02
16x8 OA
10x8 OA
8x8 OA
FCU-07
FCU-09
18x14 SA18x10 SA10x10 SA
8x8 SA
160-6Ø
SA-A
FCU-10
240-6x10 OA
THRU ROOF
SEE M-103
8x8 RA
FCU-08
NA-8x6
RA-B
12x8 RA
8x6 RA
8x6 SA
10x8 SA
NA-8x6
RA-B
145-6Ø
SA-A
6x6 OA
EA-C
(2)375-10x10
RA-F
(3)NA-10x10
SA-D
(3)475-10Ø
OA-A
140-6Ø
SA-A
(2)430-10Ø
RA-B
(2)NA-10x10
RA-B
NA-8x8
SA-A
260-8Ø
(3)50-6Ø
OA-A
NA-22x22
TA-G
10x10 EA
10x10 RA
10x10 RA
18x12 RA
18x16 RA
10x10 SA 10x10 SA
6x6 OA 6x6 OA
8x6 OA
8x6 OA
10x8 SA
RS/RL
M
T
T
T
T
FCU-07
FCU-06
FCU-09
FCU-08
T
FCU-10
CD 4 CD 4
CD 4
T
EF-09
SQUADRON
ATC OFFICER
ATC
SIMULATOR
ROOM
WEIGHT
ROOM
WEIGHT ROOM
1 2 3 4
E
D
C
DOAS-01
12x8 OA
FCU-01
12x10 RA
12x10 SA
12x10 SA
12x10 RA
8x8 OA
6x6 OA
SEE M-101
NA-12x8
RA-B
FCU
-03
12x10 SA
12x8 RA
OA-A
60-6Ø
OA-A
(2)140-6Ø
SA-A
610-10Ø
SA-A
610-10Ø
NA-12x10
RA-B
NA-12x10
RA-B
FCU-02
8x6 OA
8x6 OA 6x6 OA 6x6 OA
OA-A
50-6Ø
SA-A
565-12Ø
10x10 SA
18x12 SA
12x10 SA
RA-B
NA-12x10
SA-A
395-8Ø
RS/RL
T T
FCU-02
FCU-03
EF-15
L-17 12x12
130 CFM EA
CD 4 CD4 CD4
T
FCU-01
S c a r
M i c r o f i l m i n g
I n c h e s
M i l l i m e t e r s
1 1312111098765432
I
H
G
F
E
D
C
B
A date detailed checkeddesigned ofsheet sheets project contract rev.drawing file
HONOLULU, HAWAII
ENGINEERS ARCHITECTS & CONSULTANTS
Project No. - MABE152003
UPGRADE BUILDING
HAWAII AIR NATIONAL GUARD
KEAUKAHA ANG STATION, HAWAII
COMPLEX, HILO
01/28/220 FINAL SUBMITTAL BS
MABE 15200391701
C O
P Y
R I G
HVAC FLOOR PLAN
BUILDINGS 703 AND 704
M-102 0
91701_M102.dwg
B U
R N
D
O N
N E
L L
E
N G
I N
E E
R I N
G
C
O M
P A
N Y
I N
C
SCALE:
D5
BUILDING 703 - HVAC FLOOR PLAN
1/8" = 1'-0"
SCALE:
I5
BUILDING 704 - HVAC FLOOR PLAN
1/8" = 1'-0"
INSTALL EXHAUST FAN INSIDE BUILDING PLENUM SPACE
USING PENETRATION THROUGH EXISTING CLERESTORY
WINDOW OPENING. SEE M-111.
INSTALL THROUGH EXISTING ROOF PENETRATION.
SIZE AND ROUTE REFRIGERANT LINES PER
MANUFACTURERS INSTRUCTIONS.
SIZE AND ROUTE CONDENSATE DRAIN LINES PER
MANUFACTURERS INSTRUCTIONS. PENETRATE WALLS IN
PLENUM SPACE, DOWN EXTERIOR SIDE OF WALL,
DISCHARGE INTO GRAVEL, AND TERMINATE WITH A 45
DEGREE ELBOW WITH SMOOTH BORE CORROSION
RESISTANT OUTLET POINTING DOWN.
16'8'4'0
SCALE IN FEET
KEYPLAN
16'8'4'0
SCALE IN FEET
1. FOR GENERAL NOTES, LEGEND, AND ABBREVIATIONS SEE DRAWING
M-001.
2. INSTALL ALL OUTDOOR CONDENSING UNITS WITH MANUFACTURER
RECOMMENDED MINIMUM CLEARANCE.
3. FOR GENERAL DETAILS SEE DRAWINGS M-501 THRU M-504.
4. CONTRACTOR SHALL COORDINATE BRANCH CIRCUITING
REFRIGERANT PIPE SIZES AND ACCESSORIES WITH EQUIPMENT
MANUFACTURER.
5. REFRIGERANT PIPING SHOWN IS FOR REFERENCE ONLY AND
DEMONSTRATES DESIRED ROUTING. SIZES ARE FOR REFERENCE
ONLY. ROUTING AND SIZES ARE FOR THE BASIS OF DESIGN
MANUFACTURER AND MAY VARY FROM THE INSTALLED
MANUFACTURER'S REQUIREMENTS. CONTRACTOR SHALL BE
RESPONSIBLE FOR DESIGNING FULL REFRIGERANT PIPING PLAN AND
COORDINATING WITH OTHER DISCIPLINES.
6. CONTRACTOR SHALL BE RESPONSIBLE FOR ADDED REFRIGERANT
BASED ON INSTALLED PIPING LENGTHS.
7. LIQUID AND SUCTION PIPING SHALL BE INSULATED PER
MANUFACTURER'S RECOMMENDATIONS.
8. CONDENSATE DRAIN PIPING SHALL BE DWV COPPER TUBING
CONFORMING TO ASTM B306 AND INSTALLED WITH A SLOPE OF NOT
LESS THAN 1% TOWARDS DISCHARGE.
GENERAL NOTES
KEY NOTES
GROUND RADIO/
RADAR/FLIGHT
FACILITIES MAINT.
RADIO RELAY/
TELEPHONE
MAINT.
COMMUNICATIONS
CENTER
RADIO
OPERATIONS
CLASSROOM
MAINTENANCE
NCMO/WLC/CP
COMM.
OFFICER
SWITCHB'D
ROOM
CRYPTO
MAINT.
MESSAGE
CENTER
CRYPTO
ROOM
MECHANICAL
ROOM
VEST.
AHTE
9 10 11 12 13 14
E
D
C
B
A
DOAS-03
SEE M-102
FCU-11
20x10 RA
10x10 RA
16x10 SA
105-6Ø
SA-A
NA-6x6
RA-B
6x6 SA
6x6 RA
6x6 OA
NA-8x6
RA-B
8x6 SA
8x6 RA
FCU-15
12x10 SA
12x12 RA
6x6 OA
L-13 30x12
805 CFM OA
DDC
FCU-16
10x10
SA
18x10 SA
18x12 RA
10x10 RA
HP-02
FCU
-17
20x12 SA
24x12 RA
12x12 SA
8x6 OA
(2)NA-10x10
RA-B
FCU-13
(2)400-8Ø
SA-A
50-6Ø
OA-A
190-6Ø
SA-A
560-12Ø
SA-A
NA-12x12
RA-B
(2)475-10Ø
SA-A
(2)NA-10x10
RA-B
(2)NA-12x12
RA-B
(2)645-12Ø
SA-A
175-6Ø
OA-A
170-6Ø
OA-A
70-6Ø
OA-A
60-6Ø
OA-A
80-6Ø
OA-A
10x10
SA
145-6Ø
SA-A
L-14 32x12
600 CFM EA
6x8 SA
FCU-14
200-8x6
SA-D
6x8 SA
10x8 SA
6x8 SA
NA-8x6
RA-B
16x10 OA
NA-8x8
RA-F
10x10 RA
6x6 OA
6x6 OA
50-6Ø
OA-A
8x6 OA
6x6 OA
6x6 OA
10x6 OA
70-6Ø
OA-A
80-6Ø
OA-A
10x6 OA
M
12x12 RA
DSP
M
T
T
T
T
T
T
FCU-11
T
FCU-12
FCU-15
FCU-13
FCU-14
FCU-17
FCU-16
INTAKE THRU
DOOR LOUVER
16x12 OA
10x10 OA
50-6x6
EA-G
10x8 OA
RS/RL
HP-03
CD 4
CD4
CD4
FCU-12
CD4
M
T
EF-14
OS OS
EF-14
S c a r
M i c r o f i l m i n g
I n c h e s
M i l l i m e t e r s
1 1312111098765432
I
H
G
F
E
D
C
B
A date detailed checkeddesigned ofsheet sheets project contract rev.drawing file
HONOLULU, HAWAII
ENGINEERS ARCHITECTS & CONSULTANTS
Project No. - MABE152003
UPGRADE BUILDING
HAWAII AIR NATIONAL GUARD
KEAUKAHA ANG STATION, HAWAII
COMPLEX, HILO
01/28/220 FINAL SUBMITTAL BS
MABE 15200391701
C O
P Y
R I G
HVAC FLOOR PLAN
BUILDING 705
M-103 0
91701_M103.dwg
B U
R N
D
O N
N E
L L
E
N G
I N
E E
R I N
G
C
O M
P A
N Y
I N
C
SCALE:
I6
BUILDING 705 - HVAC FLOOR PLAN
1/8" = 1'-0"
INSTALL NEW EXHAUST FAN THROUGH EXISTING ROOF
PENETRATION AND DUCT INTO PLENUM SPACE. SEE
SHEET M-111.
INSTALL EXHAUST AIR GRILLE TO BOOT IN PLENUM
SPACE.
SIZE AND ROUTE REFRIGERANT LINES PER
MANUFACTURERS INSTRUCTIONS.
SIZE AND ROUTE CONDENSATE DRAIN LINES PER
MANUFACTURERS INSTRUCTIONS. PENETRATE WALLS IN
PLENUM SPACE, DOWN EXTERIOR SIDE OF WALL,
DISCHARGE INTO GRAVEL, AND TERMINATE WITH A 45
DEGREE ELBOW WITH SMOOTH BORE CORROSION
RESISTANT OUTLET POINTING DOWN.
ROUTE REFRIGERANT PIPING ABOVE GRADE, ALONG
THE GROUND, UP THE EXTERIOR SIDE OF WALL, AND
PENETRATE WALL IN PLENUM SPACE.
16'8'4'0
SCALE IN FEET
KEYPLAN
1. FOR GENERAL NOTES, LEGEND, AND ABBREVIATIONS SEE DRAWING
M-001.
2. INSTALL ALL OUTDOOR CONDENSING UNITS WITH MANUFACTURER
RECOMMENDED MINIMUM CLEARANCE.
3. FOR GENERAL DETAILS SEE DRAWINGS M-501 THRU M-504.
4. CONTRACTOR SHALL COORDINATE BRANCH CIRCUITING
REFRIGERANT PIPE SIZES AND ACCESSORIES WITH EQUIPMENT
MANUFACTURER.
5. REFRIGERANT PIPING SHOWN IS FOR REFERENCE ONLY AND
DEMONSTRATES DESIRED ROUTING. SIZES ARE FOR REFERENCE
ONLY. ROUTING AND SIZES ARE FOR THE BASIS OF DESIGN
MANUFACTURER AND MAY VARY FROM THE INSTALLED
MANUFACTURER'S REQUIREMENTS. CONTRACTOR SHALL BE
RESPONSIBLE FOR DESIGNING FULL REFRIGERANT PIPING PLAN AND
COORDINATING WITH OTHER DISCIPLINES.
6. CONTRACTOR SHALL BE RESPONSIBLE FOR ADDED REFRIGERANT
BASED ON INSTALLED PIPING LENGTHS.
7. LIQUID AND SUCTION PIPING SHALL BE INSULATED PER
MANUFACTURER'S RECOMMENDATIONS.
8. CONDENSATE DRAIN PIPING SHALL BE DWV COPPER TUBING
CONFORMING TO ASTM B306 AND INSTALLED WITH A SLOPE OF NOT
LESS THAN 1% TOWARDS DISCHARGE.
GENERAL NOTES
KEY NOTES
J
G1
G
F
EF-11
L-16 16x16
285 CFM EA
M
1 2 3 4 5 6 7 8 9 10
E
D
C
B
A
L-17 16x20
420 CFM OA
L-06 12x12
25 CFM OA
L-07 12x12
25 CFM OA
BDBD
2 2
M
KEYPLAN
S c a r
M i c r o f i l m i n g
I n c h e s
M i l l i m e t e r s
1 1312111098765432
I
H
G
F
E
D
C
B
A date detailed checkeddesigned ofsheet sheets project contract rev.drawing file
HONOLULU, HAWAII
ENGINEERS ARCHITECTS & CONSULTANTS
Project No. - MABE152003
UPGRADE BUILDING
HAWAII AIR NATIONAL GUARD
KEAUKAHA ANG STATION, HAWAII
COMPLEX, HILO
01/28/220 FINAL SUBMITTAL BS
MABE 15200391701
C O
P Y
R I G
HVAC ROOF PLAN
BUILDINGS 701 AND 702
M-110 0
91701_M110.dwg
B U
R N
D
O N
N E
L L
E
N G
I N
E E
R I N
G
C
O M
P A
N Y
I N
C
SCALE:
I4
BUILDINGS 702 - HVAC ROOF PLAN
1/8" = 1'-0"
INSTALL EXHAUST FAN INSIDE BUILDING PLENUM SPACE
USING PENETRATION THROUGH EXISTING CLERESTORY
WINDOW OPENING.
CONNECT TO DUCTWORK IN PLENUM SPACE BELOW
(SEE M-101).
INSTALL LOUVER IN EXISTING CLERESTORY WINDOW
OPENING (SEE ARCHITECTURAL).
KEY NOTES
1. FOR GENERAL NOTES, LEGEND, AND ABBREVIATIONS SEE DRAWING
M-001.
2. FOR GENERAL DETAILS SEE DRAWINGS M-501 THRU M-504.
GENERAL NOTES
16'8'4'0
SCALE IN FEET
SCALE:
D4
BUILDINGS 701 - HVAC ROOF PLAN
1/8" = 1'-0"
16'8'4'0
SCALE IN FEET
9 10 11 12 13 14
L
K
J
H
G1
G
F
E
D
C
B
A
M503
I1
M503
I1
EF-13
EF-12
L-15 16x16
165 CFM EA
M
M
S c a r
M i c r o f i l m i n g
I n c h e s
M i l l i m e t e r s
1 1312111098765432
I
H
G
F
E
D
C
B
A date detailed checkeddesigned ofsheet sheets project contract rev.drawing file
HONOLULU, HAWAII
ENGINEERS ARCHITECTS & CONSULTANTS
Project No. - MABE152003
UPGRADE BUILDING
HAWAII AIR NATIONAL GUARD
KEAUKAHA ANG STATION, HAWAII
COMPLEX, HILO
01/28/220 FINAL SUBMITTAL BS
MABE 15200391701
C O
P Y
R I G
HVAC ROOF PLAN
BUILDINGS 704 AND 705
M-111 0
91701_M111.dwg
B U
R N
D
O N
N E
L L
E
N G
I N
E E
R I N
G
C
O M
P A
N Y
I N
C
SCALE:
I4
BUILDINGS 704 AND 705 - HVAC ROOF PLAN
1/8" = 1'-0"
NEW DUCT WORK THRU EXISTING ROOF PENETRATION.
INSTALL EXHAUST FAN INSIDE BUILDING PLENUM SPACE
USING PENETRATION THROUGH EXISTING CLERESTORY
WINDOW OPENING.
DUCT DOWN THROUGH EXISTING ROOF PENETRATION
WITH DUCT BOOT INTO PLENUM SPACE.
10x20 EA GOOSENECH WITH INSECT SCREEN THROUGH
EXISTING PENETRATION.
6x10 OA GOOSENECH WITH INSECT SCREEN THROUGH
EXISTING PENETRATION.
KEY NOTES
1. FOR GENERAL NOTES, LEGEND, AND ABBREVIATIONS SEE DRAWING
M-001.
2. FOR GENERAL DETAILS SEE DRAWINGS M-501 THRU M-504.
GENERAL NOTES
16'8'4'0
SCALE IN FEET
KEYPLAN
a r
M i c r o f i l m i n g
I n c h e s
M i l l i m e t e r s
1 1312111098765432
I
H
G
F
E
D
C
B
A date detailed checkeddesigned ofsheet sheets project contract rev.drawing file
HONOLULU, HAWAII
ENGINEERS ARCHITECTS & CONSULTANTS
Project No. - MABE152003
UPGRADE BUILDING
HAWAII AIR NATIONAL GUARD
KEAUKAHA ANG STATION, HAWAII
COMPLEX, HILO
01/28/220 FINAL SUBMITTAL BS
MABE 15200391701
C O
P Y
R I G
11/07/2017 J. CHORIKI
AIR FLOW DIAGRAMS
BUILDINGS 701, 702, AND 703
M-201 0
91701_M-201.dwg
B U
R N
D
O N
N E
L L
E
N G
I N
E E
R I N
G
C
O M
P A
N Y
I N
C
SCALE:
D9
AIR FLOW DIAGRAM - BUILDING 703
N/A
1. FOR GENERAL NOTES, LEGEND, AND ABBREVIATIONS SEE DRAWING
M-001.
GENERAL NOTES
SCALE:
I5
AIR FLOW DIAGRAM - BUILDING 702
N/A
CFM
OA
DOAS-01
WEIGHT ROOM
CFM
CFM
CFM
CFM
CFM
CFM
150 CFM
PRESSURIZATION
FCU-01 FCU-02
SIMULATOR ROOM
CFM
CFM
CFM
50 CFM
PRESSURIZATION
FCU-03
SQUADRON
ATC OFFICES
CFM
CFM
CFM
60 CFM
PRESSURIZATION
CFM
OA
DOAS-04
CFM
CFM
CFM
50 CFM
PRESSURIZATION
FCU-05
SQUADRON
ADMIN PERSONNEL
CFM
CFM
CFM
CFM
CFM
CFM
275 CFM
PRESSURIZATION
FCU-04
CONFERENCE ROOM
CFM
SCALE:
D2
AIR FLOW DIAGRAM - BUILDING 701
N/A
OFFICE - 011
CFM
CFM
FCU-18
CFM
OA
25 CFM
PRESSURIZATION
VEHICLE DISPATCH
& DRIVERS
CFM
CFM
FCU-19
CFM
OA
25 CFM
PRESSURIZATION
OFFICE - 014
CFM
CFM
FCU-20
CFM
OA
25 CFM
PRESSURIZATION
OFFICES - 020
CFM
CFM
FCU-21
CFM
OA
30 CFM
PRESSURIZATION
MEN - 08
CFM
CFM
WOMEN - 07
CFM
CFM
JANITOR CLOSET
CFM
CFM
CFM
BATTERY ROOM
CFM
CFM
CFM
CFM
CFM
CFM
CFM
CFM
OA
CORRIDOR
EF-11
EF-03
EF-02
UTILITY
ROOM
CFM
CFM
OA
CFM
CFM
EF-05
CFM
OA
REPAIR BAYS
CFM
EF-15
a r
M i c r o f i l m i n g
I n c h e s
M i l l i m e t e r s
1 1312111098765432
I
H
G
F
E
D
C
B
A date detailed checkeddesigned ofsheet sheets project contract rev.drawing file
HONOLULU, HAWAII
ENGINEERS ARCHITECTS & CONSULTANTS
Project No. - MABE152003
UPGRADE BUILDING
HAWAII AIR NATIONAL GUARD
KEAUKAHA ANG STATION, HAWAII
COMPLEX, HILO
01/28/220 FINAL SUBMITTAL BS
MABE 15200391701
C O
P Y
R I G
11/07/2017 J. CHORIKI
AIR FLOW DIAGRAMS
BUILDINGS 704 AND 705
M-202 0
91701_M-202.dwg
B U
R N
D
O N
N E
L L
E
N G
I N
E E
R I N
G
C
O M
P A
N Y
I N
C
1. FOR GENERAL NOTES, LEGEND, AND ABBREVIATIONS SEE DRAWING
M-001.
GENERAL NOTES
SQUADRON UNIT
SUPPLY & ISSUE RM
CFM
CFM
CFM
FCU-06
165 CFM
PRESSURIZATION
CFM
OA
DOAS-02
CFM
SQUADRON MAINT.
MANAGEMENT
CFM
CFM
CFM
FCU-07
100 CFM
PRESSURIZATION
CFM
SQ SUPPLY
ADMIN OFFICE
CFM
CFM
CFM
20 CFM
PRESSURIZATION
CFM
SQ SUPPLY
OFFICER
CFM
CFM
CFM
20 CFM
PRESSURIZATION
CFM
FCU-08
SQ MAINT
OFFICER
CFM
CFM
CFM
FCU-09
30 CFM
PRESSURIZATION
CFM
CFM
FRAME
ROOM
CFM
CFM
OA
CFM
CFM
JANITOR
CLOSET
CFM
CFM
OA
CFM
CFM
SERVICE
ROOM
CFM
CFM
OA
CFM
CFM
MEN
CFM
CFM
OA
CFM
CFM
WOMEN
CFM
CFM
OA
CFM
CFM
TRAINING
ROOM
CFM
CFM
FCU-10
SCALE:
D5
AIR FLOW DIAGRAM - BUILDING 704
N/A
EF-09
EF-08EF-07
EF-10
EF-06
EF-12
NCMO/WLC/SP
CFM
CFM
FCU-11
80 CFM
PRESSURIZATION
CFM
OA
DOAS-03
CFM
COMM. OFFICER
CFM
CFM
10 CFM
PRESSURIZATION
RADIO OPERATIONS
CLASSROOM
CFM
CFM
CFM
FCU-12
15 CFM
PRESSURIZATION
CFM
MAINTENANCE
CFM
CFM
CFM
FCU-13
25 CFM
PRESSURIZATION
CFM
COMMUNICATIONS
CENTER
CFM
CFM
CFM
FCU-15
65 CFM
PRESSURIZATION
CFM
RADIO RELAY/
TELEPHONE MAINT.
CFM
CFM
CFM
FCU-16
110 CFM
PRESSURIZATION
CFM
GROUND RADIO/
RADAR/FLIGHT
FACILITIES MAINT.
CFM
CFM
CFM
FCU-17
150 CFM
PRESSURIZATION
CFM
CFM
EF-13
CFM
CFM
CFM
CFM
CFM
CFM
PLENUM
CFM
CFM
OA
CFM
CFM
EF-14
CFM
CFM
CFM
CFM
FCU-14
CRYPTO.
MAINT.
CRYPTO.
ROOM
MECHANICAL
ROOM
MESSAGE
CENTER
CFM
CFM
10 CFM
PRESSURIZATION
CFM
SWITCHB'D
ROOM
CFM
CFM
10 CFM
PRESSURIZATION
CFM
CFM
SCALE:
I5
AIR FLOW DIAGRAM - BUILDING 705
N/A
CFM
OA
240 CFM
PRESSURIZATION
SCALE:
C1
DUCTWORK CONNECTED TO EXTERIOR LOUVER
NONE
HANGER ROD
FLEX CONNECTION
VIBRATION ISOLATOR
FLEX CONNECTION
MOUNTING BRACKET OR
CHANNEL, USE UNIT
FACTORY INSTALLED
MOUNTING BRACKET
WHERE APPLICABLE
FAN COIL OR
EXHAUST FAN
LOUVER
EXTERIOR
WALL
SLOPE DUCTWORK CONNECTED
TO LOUVER TOWARDS THE
BUILDING EXTERIOR
AIR COOLED CONDENSING UNIT
CHARGING VALVE
LIQUID PIPING
INSULATED SUCTION PIPING
FILTER-DRIER
SIGHT GLASS
INSTALL SENSING BULB
45° ABOVE BOTTOM OF
PIPING, AS CLOSE TO
COIL AS POSSIBLE
CONDENSATE
DRAIN
NOTE:
CONTRACTOR IS RESPONSIBLE FOR COORDINATING
REFRIGERANT LIQUID AND SUCTION PIPING, SIZES, ROUTING,
AND ALL ACCESSORIES WITH EQUIPMENT MANUFACTURER.
MAINTAIN UNIFORM SLOPE TO PREVENT OIL FROM POOLING IN
LOW POINTS IN THE REFRIGERANT PIPING SYSTEM.
1.
EVAPORATOR COIL
THERMOSTATIC
EXPANSION VALVE
EQUALIZATION LINE
PROVIDE OIL TRAP ON
8'-0" OR GREATER LIFT
PITCH IN DIRECTION OF FLOW
REFRIGERATION DUTY FULL
PORT BALL VALVE (TYP.)
1-1/2" MIN. TO 3" MAX.
INSTALLED 6" NOMINAL
WITH MATERIAL TAUT
SHEET METAL AS
SPECIFIED FOR
DUCTWORK
AIRFLOW
J = 45°
L = 1/4 W, 4" MIN.
Ø = 30° MAX.
NOTES:
1. TAKEOFF ON BOTH SIDES OR SINGLE SIDE AS REQUIRED BY PLANS.
2. SEE SMACNA MANUAL FOR TAP-IN DETAILS.
3. WHEN FITTING HAS ONLY ONE SIDE SLOPED FOR A SINGLE SIDE
TAKE-OFF, THE TAP-IN SHALL BE INSTALLED IN SLOPED SIDE.
4. CLINCH LOCK CONNECTION TO DUCT SHALL HAVE CORNER SEALS. (SEE
SMACNA MANUAL
5. EXTRACTORS, SCOOPS, DEFLECTORS OR DAMPERS THAT PROTRUDE
INTO THE MAIN DUCT SHALL NOT BE USED. BALANCING DAMPERS SHALL
BE LOCATED TO PREVENT PROTRUSION INTO THE MAIN DUCT AND TO
PROVIDE STABLE AIR FLOW AND MINIMAL NOISE WHEN ADJUSTED.
6. PROVIDE 2" DUCT ON EITHER SIDE OF DAMPER LOCATION TO ALLOW
OPERATION OF DAMPER WITHOUT DAMAGE TO INSULATION.
L
J
W
Ø
1" FLANGE
AND HEM
ALTERNATE
POSITION
OF BOLT
BOLT ON 4"
CENTERS
1" x 1/8"
BAND IRON
FLEXIBLE MATERIAL
AS SPECIFIED
1-1/2"
SLIP
DUCT
WASHER
SHEET METAL AS
SPECIFIED FOR
DUCTWORK
FLANGED
CONNECTION ON
FAN SIDE.
VIBRATION ISOLATORHANGER ROD
CEILING
UNIT DIFFUSER/FACE
UNIT MOUNTING
BRACKET
FAN COIL UNIT
NOTE:
PROVIDE SEISMIC RESTRAINTS AS REQUIRED PER SECTION 13 45 00.00 10.
1.
NOTE:
PROVIDE SEISMIC RESTRAINTS AS REQUIRED PER SECTION 13 48 00.00 10
1.
VAV-01
CEILING TILE 1/4" - 20 x 1/2"
GALVANIZED
MACHINE
SCREWS
18 GAUGE SHEET
METAL ANGLE
WITH WHITE
ENAMEL FINISH
WHITE VINYL ADHESIVE LABEL WITH
1/2" HIGH BLACK PRE-PRINTED LETTERS
FRONT PANEL SIDE PANEL
NOTES:
1. PROVIDE FOR ALL MECHANICAL EQUIPMENT LOCATED ABOVE CEILING.
2. LOCATE EACH NAMEPLATE DIRECTLY UNDER THE DEVICE IT IDENTIFIES.
3. LETTERING ON BOTH SIDES OF NAMEPLATE.
SCALE:
C6
DX SPLIT SYSTEM PIPING DETAIL
NONE
SCALE:
I6
RECTANGULAR FLEXIBLE CONNECTION DETAIL
NONE
RADIUS
CORNERS
SCALE:
F1
CEILING MOUNTED CASSETTE FAN COIL DETAIL
NONE SCALE:
F5
INLINE EXHAUST FAN AND DUCTED FAN COIL DETAIL
NONE
SCALE:
D10
TYPICAL BRANCH DUCT TAKE-OFF
NONE
SCALE:
I1
DEVICE NAMEPLATE DETAIL
NONE
OA CONNECTION
(WHERE APPPLICABLE)
BALANCING DAMPER WITH
LOCKING QUADRANT
SCALE:
I10
LOW PRESSURE TEE DUCT FITTING
NONE
DIMENSION IS EQUAL TO +
DIMENSIONS, SEE PLANS FOR SIZES
(MAX)30°
AIRFLOW
15° (RECOMMENDED)
AIRFLOW
AIRFLOW
AIRFLOW
C
B
D
C
D
B
A
B
A C D
C D
TURNING VANES @ 45° (TYP.)
TURNING VANES @ 45° (TYP.)
BRANCH DUCT, SEE
PLAN FOR SIZE
RECTANGULAR DUCT,
SEE PLAN FOR SIZE
S c a r
M i c r o f i l m i n g
I n c h e s
M i l l i m e t e r s
1 1312111098765432
I
H
G
F
E
D
C
B
A date detailed checkeddesigned ofsheet sheets project contract rev.drawing file
HONOLULU, HAWAII
ENGINEERS ARCHITECTS & CONSULTANTS
Project No. - MABE152003
UPGRADE BUILDING
HAWAII AIR NATIONAL GUARD
KEAUKAHA ANG STATION, HAWAII
COMPLEX, HILO
01/28/220 FINAL SUBMITTAL BS
MABE 15200391701
C O
P Y
R I G
MECHANICAL DETAILS
M-501 0
91701_M501.dwg
B U
R N
D
O N
N E
L L
E
N G
I N
E E
R I N
G
C
O M
P A
N Y
I N
C
OPPOSED BLADE
DAMPER
RECTANGULAR
EXHAUST DUCT, SEE
PLANS FOR SIZE.
SIDE WALL GRILLE SEE PLANS
FOR SIZE
1.5 x W
OR
1.0 x W
W
W
TURNING
VANES
W
W
25 [1"]
R
R
25 [1"] 25 [1"]
NOTE:
1. USE THIS DESIGN WHERE SQUARE 90° ELBOWS
ARE SHOWN ON DRAWINGS OR IF SPACE DOES
NOT PERMIT RADIUS 90° ELBOWS.
RECTANGULAR DUCT
MAX. SLOPE 25
IN 100 [1" IN 4"]
ROUND
DUCT
RECTANGULAR TO
ROUND
TRANSITION
RADIUSED 90 ELBOW
SQUARE 90
ELBOW (NOTE 1)
TURNING VANES
DETAIL
FRAME 1
HINGE POSITION 1
FRAME 2
HINGE POS. 2
FRAME 3
HINGE POS. 3
DOOR A
DOOR B
LESS
BACK
DOOR NO. NO.
METAL GAGE
SIZE HINGES LOCKS
FRAME DOOR
2" W.G. 12" x12" 2 1-S 24 26
STATIC 16" x 20" 2 2-S 22 24
AND 24" x 24" 3 2-S 22 24
3" W.G.
12" x 12" 2 1-S 22 22
STATIC
16" x 20" 2 1-S, 1-T, 1-B 20 20
24" x 24" 3 2-S, 1-T, 1-B 20 20
B - BOTTOM
S - SIDE
T - TOP
DUCT
ACCESS PANEL
GASKET
DUCT
SASH LOCK
FRAME 2
DUCT
BUTT HINGE 1" x 1", OR PIANO HINGE
VIEW PORT IF SPECIFIED
LOCK TYPE 2
LOCK
TYPE 1
PANEL IS DUCT GAGE (MIN.)
WITH SCREWS AT 8" MAX. SPACING
SPIN-IN FITTING OR 45° BOOT
AS INDICATED WITH DAMPER
SUPPLY DUCT
FLEX DUCT
(MAX LENGTH = 5 FEET)
DIFFUSER DAMPER
SECTION (WHERE
SCHEDULED OR SPECIFIED)
T-BAR
CEILING
SUPPLY DIFFUSER
90° SHEET
METAL ELBOW
DRAW BAND
DIFFUSER DAMPER
SECTION (WHERE
SCHEDULED OR SPECIFIED)
T-BAR
CEILING
SUPPLY DIFFUSER
90° SHEET
METAL ELBOW
DRAW BAND
OPTION 1 OPTION 2
AIR FLOW
DUCT
AIR FLOW
DUCT
GRIDS AND DAMPERS MUST NOT DAMAGE LINERS
NOTE:
ADJUSTABLE DAMPER
SUPPLY OUTLET
ADJUSTABLE DAMPER
SUPPLY OUTLET
QUALIZING GRID (WHEN
SPECIFIED ALTERNATIVE
TO EXTRACTOR)
REGISTER AND DIFFUSER CONTAIN VOLUME
CONTROL AT GRILLE. GRILLE
HAS NO VOLUME CONTROL.
GRILLE FLANGES MUST
COVER DUCT FLANGES.
R=W
W
BEAD OR CROSSBREAK
IF REQUIRED
SEAMS ON ALL
CORNERS
STANDARD RADIUS ELBOW R=W.
WHERE SPACE PERMITS INSTALL FULL
RADIUS ELBOW WITH R= 1 1/2 W.
R S GA
SINGLE VANE SCH.
SMALL
LARGE
2" 1.5" 24
4.5" 2.25" 22
45°
45°
S
S S S S
W
W
D
S= D/6 (MIN.2")
W/S= NO. OF SPACES
R= 1 1/4 S
R
BOLT, SCREW OR
WELD TO DUCT
SCREW EVERY
SIXTH VANE
SCALE:
D1
DUCT ACCESS DOORS
NONE SCALE:
D6
LOW VELOCITY DUCT LAYOUT
NONE
NOTE: INSTALL PER OPTION 1 OR 2 FOR INDIVIDUAL INSTALLATIONS AS REQUIRED
TO MAINTAIN A BEND RADIUS OF THE FLEXIBLE DUCT EQUAL TO OR GREATER
THAN ONE DUCT DIAMETER. SEAL ALL CONNECTIONS WITH STAINLESS STEEL
BAND CLAMPS AND DUCT SEALANT.
BALANCING DAMPER WITH LOCKING QUADRANT.
PROVIDE 2" DUCT EXTENSION TO ALLOW OPERATION OF
DAMPER WITHOUT DAMAGE TO INSULATION.
SCALE:
D11
SIDE WALL GRILLE DETAILS
NONE
SCALE:
I1
DIFFUSER, GRILLE, & REGISTER CONNECTIONS
NONE
SCALE:
F8
FLEXIBLE DUCT AT DIFFUSER
NONE
SCALE:
B11
STANDARD CURVE AIR DUCT ELBOW
NONE
SCALE:
I6
RECTANGULAR AIR DUCT ELBOW TURNING VANES
NONE
NOTES:
2 X D
6"
D
BOOT SHALL BE SAME
RECTANGULAR SIZE AS GRILLE.
BOOT SHALL BE CONSTRUCTED
OF GALVANIZED STEEL WITH 1
INCH THICK DUCT LINER.
DIRECT EXHAUST BOOT OPENING
AWAY FROM ADJACENT
MECHANICAL EQUIPMENT.
1.
2.
3.
EXHAUST AIR
GRILLE
CEILING
SCALE:
I10
EXHAUST AIR GRILLE/BOOT
NONE
S c a r
M i c r o f i l m i n g
I n c h e s
M i l l i m e t e r s
1 1312111098765432
I
H
G
F
E
D
C
B
A date detailed checkeddesigned ofsheet sheets project contract rev.drawing file
HONOLULU, HAWAII
ENGINEERS ARCHITECTS & CONSULTANTS
Project No. - MABE152003
UPGRADE BUILDING
HAWAII AIR NATIONAL GUARD
KEAUKAHA ANG STATION, HAWAII
COMPLEX, HILO
01/28/220 FINAL SUBMITTAL BS
MABE 15200391701
C O
P Y
R I G
MECHANICAL DETAILS
M-502 0
91701_M502.dwg
B U
R N
D
O N
N E
L L
E
N G
I N
E E
R I N
G
C
O M
P A
N Y
I N
C
50" DIA.
MAX.
STRAP IS PLACED
UNDER A BOTTOM
REINFORCEMENT
STRAP HANGERS
HANGER
STRAPS
TRAPEZE HANGERS
STRAP OR ANGLE
ROD
SIZE BOLT(S)
FOR LOAD
SECURE
WIRE
BAND OF SAME
SIZE AS HANGER
STRAP
1" MIN.
SCREWS MAY BE OMITTED
IF HANGER LOOPS
LOAD
RATED
FASTENERS
ROD
STRAP
HANGER RODS,
WIRES OR
STRAPS
HANGERS
MUST NOT
DEFORM
DUCT SHAPE
24" DIA.
MAX.
10" DIA.
MAX.
ALTERNATE
LOCATION (VERIFY
UPPER TRAPEZE
LOAD CAPACITY)
REINFORCEMENT MAY BE USED
FOR ATTACHMENT IF IT QUALIFIES
FOR BOTH DUTIES DO NOT EXCEED
ALLOWABLE LOAD LIMITS
ONE HALF-ROUND MAY
BE USED IF DUCT SHAPE
IS MAINTAINED.
BAND
ANGLES
NUTS
6"
MAXIMUM
SCREWS
PITCH 1% 1/8"/FT TYPE "M"
COPPER (TYP)
C
UNIT DRAIN PAN
INTERNAL OPERATING
NEGATIVE
STATIC PRESSURE
B
A
2" MIN. SIZE,
SLOPE TO EQUIP.
DRAIN
AHU CABINET WALL
NPT DRAIN CONNECTION
ADAPTER
HAND-TIGHT
CLEANOUT PLUG
FAN INLET
PRESSURE
(NEGATIVE)
RETURN BEND
(CLOSED)
1. DIMENSION EQUAL TO MAXIMUM FAN INLET PRESSURE. +1" W.C. MINIMUM
2. DIMENSION EQUAL TO /2 (MIN.)
3. INCREASE PAD THICKNESS AS REQUIRED TO ACHIEVE REQUIRED
TRAP DEPTH. 4" MINIMUM
NOTES:
DRAW THRU
UNIT
A
C
A B
14 GAUGE SHIELD 455 [18"]
LONG TO PROTECT
INSULATION
HEAVY DUTY
CLEVIS HANGER
HANGER ROD
LOCKING NUT
SUPPORT NUT
INSULATION
PIPE
SCALE:
E1
LOWER DUCT HANGAR ATTACHMENT DETAIL
NONE
SCALE:
I6
HVAC CONDENSATE TRAP DRAIN
NONE
SCALE:
G11
PIPE HANGER - CLEVIS TYPE
NONE
1/2" MESH BIRD
SCREEN,
COATED GALV
OR 316
STAINLESS
STEEL
FLASHING
22 GAUGE
DUCT
LOCK JOINT
WOOD BLOCKING (TYP.)
WOOD CANT (TYP.)
CAP SHEET
OVER ROOFING
EXIST ROOF
1/2" ALL AROUND
OUTSIDE AIR DUCT
EXIST ROOF JOINT (TYP.)
M
I N
FLASHING AND
COUNTER
FLASHING
R
A
D
22 GAUGE
GALV BOLTS
METAL SCREEN
FRAME
NOTES:
1. PER UFC 3-440-05N, PAINT GALVANIZED STEEL DUCTWORK FOR
OUTDOOR USE WITH ONE COAT OF POLYAMIDE EPOXY PRIMER
AND ONE COAT OF POLYAMIDE EPOXY EXTERIOR TOP COAT.
2. USE GALVANIZED SHEET STEEL FOR DUCTWORK - (26 GAUGE) FOR
MAXIMUM SIDE DUCT UP TO 12" AND (24 GAUGE) FOR MAXIMUM
SIDE DUCT SIZE 13" TO 30".
MAXIMUM HORIZONTAL PIPE
HANGER AND SUPPORT SPACING
NOMINAL PIPE
OR
TUBE DIA.
STANDARD WEIGHT
AND HEAVIER
STEEL PIPE
WATER
SERVICE
VAPOR
SERVICE
COPPER TUBE
WATER
SERVICE
VAPOR
SERVICE
IN. FT. FT. FT. FT.
NOTES:
1. FOR SPACING SUPPORTS INCORPORATING TYPE 40
SHIELDS, SEE TABLE 5, MSS SP-69.
2. DOES NOT APPLY WHERE SPAN CALCULATIONS ARE
MADE OR WHERE THERE ARE CONCENTRATED LOADS
BETWEEN SUPPORTS SUCH AS FLANGES, VALVES,
SPECIALTIES, ETC, OR CHANGES IN DIRECTION
REQUIRING ADDITIONAL SUPPORTS.
3. FIRE PROTECTION PIPING: FOLLOW REQUIREMENTS
OF THE NATIONAL FIRE PROTECTION ASSOCIATION.
4. CAST IRON AND DUCTILE IRON PIPE: MIN. OF ONE (1)
HANGER PER PIPE SECTION CLOSE TO JOINT ON THE
BARREL ALSO AT CHANGE OF DIRECTION AND
BRANCH CONNECTIONS.
CAST IRON PRESSURE PIPE: 12 FT. MAX. SPACING.
CAST IRON SOIL PIPE: 10 FT. MAX. SPACING.
5. EXTRACTED FROM MSS SP-69, 1983, WITH
PERMISSION OF THE PUBLISHER, THE
MANUFACTURER'S STANDARDIZATION SOCIETY.
6. THIS TABLE PROVIDED FOR REFERENCE ONLY.
PROVIDE HANGER AND SUPPORT SPACING IN
ACCORDANCE WITH MSS SP-58, SP-69 AND
SPECIFICATIONS.
7. SPACING FOR HYDRAULIC PIPING SHALL MATCH
THAT INDICATED FOR WATER SERVICE.
1/4 5 5
3/8 7 8 5 6
1/2 7 8 5 6
3/4 7 9 5 7
1 7 9 6 8
1 1/4 7 9 7 9
1 1/2 9 12 8 10
2 10 13 8 11
2 1/2 11 14 9 13
3 12 15 10 14
3 1/2 13 16 11 15
4 14 17 12 16
MIN. ROD DIAMETER FOR
SINGLE ROD HANGERS
NOMINAL PIPE
OR TUBING DIA.
IN.
1/4 THROUGH 2
2 1/2, 3, 3 1/2
4, 5
8, 10, 12
16, 18
20, 24, 30
NOMINAL ROD DIAMETER
A
IN.
3/8
1/2
5/8
3/4
7/8
1 1/4
B
IN.
3/8
1/2
1/2
5/8
3/4
NOTES:
1. COLUMN A FOR USE WITH STD. WT. STEEL PIPE,
CAST IRON PRESS. PIPE, CAST IRON SOIL PIPE AND
GLASS PIPE.
2. COLUMN B FOR USE WITH COPPER TUBE, PLASTIC
PIPE AND FIBERGLASS REINFORCED PIPE.
3. EXTRACTED FROM MSS SP-69, 1983, WITH
PERMISSION OF THE PUBLISHER. THE
MANUFACTURERS STANDARDIZATION SOCIETY.
4. THIS TABLE PROVIDED FOR REFERENCE ONLY.
PROVIDE HANGER RODS IN ACCORDANCE WITH
MSS SP-58, SP-69 AND SPECIFICATIONS.
SCALE:
I1
ROOF GOOSENECK
NONE
S c a r
M i c r o f i l m i n g
I n c h e s
M i l l i m e t e r s
1 1312111098765432
I
H
G
F
E
D
C
B
A date detailed checkeddesigned ofsheet sheets project contract rev.drawing file
HONOLULU, HAWAII
ENGINEERS ARCHITECTS & CONSULTANTS
Project No. - MABE152003
UPGRADE BUILDING
HAWAII AIR NATIONAL GUARD
KEAUKAHA ANG STATION, HAWAII
COMPLEX, HILO
01/28/220 FINAL SUBMITTAL BS
MABE 15200391701
C O
P Y
R I G
MECHANICAL DETAILS
M-503 0
91701_M503.dwg
B U
R N
D
O N
N E
L L
E
N G
I N
E E
R I N
G
C
O M
P A
N Y
I N
C
3/8"
1/4"
3/8"
PIPE SLEEVE
BACKUP MATERIAL
SEALANT
INSULATION
CENTER OF PIPE
INSULATION
SEALANT
BACKUP MATERIAL
FLOOR
PIPE SLEEVE
PROVIDE SLEEVE FOR FLOOR
PENETRATION WITH 2" MORE
CLEARANCE. FILL CLEARANCE
WITH FIREPROOF MASTIC.
CENTER OF PIPE
PIPE
3/8"
PIPE
ESCUTCHEON
INTERIOR SIDE OF
EXTERIOR WALL
EXTERIOR SIDE
INTERIOR SIDE
ELEVATION
SECTION
MULTIPLE SECTION
RUBBER SEAL (SEE
SPECIFICATIONS)
PIPE
WALL SLEEVE
WALL
SLEEVE
CONTINUOUS SEALANT
AS SPECIFIED
Ø PIPE THRU WALL
INSTALL SUCH THAT
PIPE SEAL MAY BE
TIGHTENED FROM
INTERIOR SIDE
1/2Ø HEADED STUDS @ 12"
SPACED RADIALLY
AROUND SLEEVE (4 MIN.)
NOTE:
EA
SEE PLANS FOR EXHAUST FAN LOCATIONS AND UNIT
DESIGNATION. SEE SCHEDULES FOR PERFORMANCE DATA.
EXHAUST GRILLE, SEE
HVAC PLANS FOR SIZE,
TYPE AND FLOW RATE
BACKDRAFT DAMPER
EXTERIOR WALL, SEE ARCHITECTURAL
DRAWINGS FOR CONSTRUCTION DETAILS
EXHAUST FAN (EF)
ADHESIVE MASONRY ANCHOR
COORDINATE SIZE AND NUMBER
REQUIRED WITH FAN FURNISHED
INSTALL MECHANICAL GASKET
OR CAULK WATERTIGHT
NOTE 1
CEILING
T Y
P I C
A L
C
E I L
I N
G
H E
I G
H
RAISED OR
FINISHED
FLOOR
DEVICE MOUNTING NOTES:
1.
2.
3.
THERMOSTATS AND OTHER WALL-MOUNTED DEVICES SHALL BE MOUNTED WITHIN 12" OF DOOR FRAME.
COORDINATE WITH ARCHITECTURAL DRAWINGS. WHERE DEVICES ARE SHOWN ADJACENT TO THE DOOR ON THE
HINGE-SIDE OF THE DOOR, AND THE DOOR SWINGS IN A MANNER THAT SHALL BLOCK THE DEVICE, MOUNT THE
DEVICE 12" BEYOND THE DOOR SWING.
COORDINATE MOUNTING LOCATION WITH OTHER TRADES TO ENSURE A UNIFORM MOUNTING AND
AESTHETICALLY-PLEASING APPEARANCE. DIMENSIONS SHOWN ON ARCHITECTURAL DRAWINGS SHALL GOVERN.
MOUNTING HEIGHT INDICATED IN LEGEND AND ON THE DRAWINGS SHALL BE THE DISTANCE MEASURED FROM
THE CENTER OF THE DEVICE TO THE FINISHED FLOOR.
12" MAX.
S F
T
NOTE 3
NOTE 2
SCALE:
E1
PIPE PENETRATIONS THROUGH VARIOUS STRUCTURES
NONE SCALE:
E7
HYDROSTATIC SEAL FOR PIPES THRU EXTERIOR WALLS
NONE
SCALE:
I1
SIDE WALL CENTRIFUGAL EXHAUST FAN
NONE SCALE:
I7
TYPICAL DEVICE MOUNTING DETAIL
NONE
EA
EXHAUST FAN
BACKDRAFT DAMPER
BIRDSCREEN
ROOF CURB, COORDINATE
W/EQUIPMENT FURNISHED
SEE ARCHITECTURAL DWGS
FOR FLASHING DETAILS
SCALE:
E11
CENTRIFUGAL ROOF EXHAUST FAN
NONE
S c a r
M i c r o f i l m i n g
I n c h e s
M i l l i m e t e r s
1 1312111098765432
I
H
G
F
E
D
C
B
A date detailed checkeddesigned ofsheet sheets project contract rev.drawing file
HONOLULU, HAWAII
ENGINEERS ARCHITECTS & CONSULTANTS
Project No. - MABE152003
UPGRADE BUILDING
HAWAII AIR NATIONAL GUARD
KEAUKAHA ANG STATION, HAWAII
COMPLEX, HILO
01/28/220 FINAL SUBMITTAL BS
MABE 15200391701
C O
P Y
R I G
MECHANICAL DETAILS
M-504 0
91701_M504.dwg
B U
R N
D
O N
N E
L L
E
N G
I N
E E
R I N
G
C
O M
P A
N Y
I N
C
LEGEND & SYMBOLS
C
SEE "ACTUATOR, PNEUMATIC"
PRESSURE GAGE
FILTER
POSITIVE POSITIONER
XX-C
COIL, HEATING
COIL, PRECOOL
COIL, PREHEAT
COIL, COOLING, DIRECT-EXPANSION
COIL, COOLING
CHILLER
FAN
AFMA
P
W-X-Y-Z
REV
DIR
DDC
W-X-Y-Z
SEE "DEVICE SYMBOL, GENERIC"
VALVE, BALANCING
BOILER
AIR FLOW MEASUREMENT ARRAY,
WITH FLOW TRANSMITTER
ACTUATOR, PNEUMATIC
WITH POSITIVE POSITIONER
PRESSURE GAGE
AND LOCALLY MOUNTED
M
PP
ACTUATOR, ELECTRIC
ACTUATOR, PNEUMATIC
WITH LOCALLY MOUNTED
PRESSURE GAGE
MOTOR STARTER
MS-#
MAIN AIR
MOTORM#
DAMPER, PARALLEL BLADE
DAMPER, OPPOSED BLADE
NORMALLY OPEN OR CLOSED AS SHOWN
NORMALLY OPEN OR CLOSED AS SHOWN
DAMPER, BALANCING
## : DEVICE NUMBER
DEVICE SYMBOL, GENERIC
REV : REVERSE CONTROL ACTION
DIR : DIRECT CONTROL ACTION, OR
MULTIPLE OUTPUT DEVICE WHERE AT LEAST 1
OUTPUT IS ALWAYS SAFETY INTERLOCK
DDC : DIRECT DIGITAL CONTROL
DEVICE SYMBOL, CONTROLLER
GENERIC USAGE TO SHOW LOCATION OF DEVICE;
PROCESS OR DEVICE BEING MEASURED OR
CONTROLLED; SIGNAL TYPE; MODIFIERS AND
OTHER APPLICATION INFORMATION
USED TO REPRESENT SENSORS, INSTRUMENTS
W-X-Y-Z : (SEE ABBREVIATIONS AND ACRONYMS)
SAFETIES, AND OTHER CONTROL DEVICES
DEVICE SYMBOL, GENERIC
VARIABLE FREQUENCY DRIVE
XX = PROCESS/DEVICE BEING CONTROLLED
C = 4-20 mA, VDC, or SNVT CONTROL SIGNAL
SS = START/STOP COMMAND
S = STATUS FEEDBACK (ON/OFF)
XX-S
VFD
XX-SS
NC
V-##
NO
COM
NC
V-##
COM
NO
V-##
FL
NC/NO
V-##
THERMOWELL IN PIPE
THERMOSTAT WITH SPECIFIED I/O FUNCTIONS
TEMPERATURE SENSOR, POINT
SEE "DEVICE SYMBOL, GENERIC"
STAT
TEMPERATURE SENSOR, AVERAGING
or TEMPERATURE LOW LIMIT / FREEZESTAT
SEE "DEVICE SYMBOL, GENERIC"
TEMPERATURE GAGE
SMOKE DETECTOR, DUCT-MOUNTED
RESET BUTTON FOR SAFETY RESET
SEE "DEVICE SYMBOL, GENERIC"
RST-BUT
PRESSURE SWITCH, DIFFERENTIAL, WITH GAGE
H = HIGH PRESSURE TAP
L = LOW PRESSURE TAP
SEE "DEVICE SYMBOL, GENERIC"
PUMP
LOCAL DISPLAY PANEL
## = SEQUENTIAL NUMBER
(WHEN MORE THAN 1 LDP)
LDP
W-X-Y-Z
W-X-Y-Z : (SEE ABBREVIATIONS AND ACRONYMS)
GENERIC USAGE TO SHOW LOCATION OF DEVICE;
PROCESS OR DEVICE BEING MEASURED OR
CONTROLLED; SIGNAL TYPE; MODIFIERS AND
OTHER APPLICATION INFORMATION
SHELL AND TUBE
HEAT EXCHANGER
CONTROL SIGNAL LINE, LOW VOLTAGE
1. THE CONTROL DIAGRAMS AND SCHEMATICS ILLUSTRATE THE FUNCTIONAL REQUIREMENTS AND
CONTROL RELATIONSHIPS, ALL ACCESSORIES AND DEVICES MAY NOT BE SHOWN IN DETAIL
2. THE SPECIFICATIONS SHOULD BE CONSULTED FOR DETAILED REQUIREMENTS.
1.
2.
3.
4.
CELLS WITH "<___>" SHALL BE DETERMINED BY THE
CONTRACTOR
SPACES WHERE NO ENTRY IS REQUIRED CONTAIN " ~ "
AN ALARM PRIORITY OF CRITICAL (CRIT) INDICATES
THAT THE ALARM SHALL REMAIN IN ALARM UNTIL
ACKNOWLEDGED BY A SYSTEM OPERATOR AND UNTIL
THE ALARM CONDITION NO LONGER EXISTS.
AN ALARM PRIORITY OF INFORMATIONAL (INFO)
INDICATES THAT THE ALARM SHALL REMAIN IN ALARM
UNTIL THE ALARM CONDITION NO LONGER EXISTS OR
THE ALARM IS ACKNOWLEDGED.
HUMIDIFIER
FLOW METERFM
P
H
L
DX
H
PC
PH
P
P
T
CT
CURRENT TRANSFORMER/SWITCH
PP
MAIN
AIR
VALVE, WITH SPRING FAILSAFE
NO = NORMALLY OPEN
NC = NORMALLY CLOSED
## = VALVE NUMBER AS SHOWN
IN VALVE SCHEDULE
VALVE
FL = FAIL IN LAST POSITION
## = VALVE NUMBER AS SHOWN
IN VALVE SCHEDULE
VALVE, 3-WAY DIVERTING
WITH SPRING FAILSAFE
NO = NORMALLY OPEN
NC = NORMALLY CLOSED
COM = COMMON PORT
## = VALVE NUMBER AS SHOWN
IN VALVE SCHEDULE
VALVE, 3-WAY DIVERTING
WITH SPRING RETURN FAILSAFE
NO = NORMALLY OPEN
NC = NORMALLY CLOSED
COM = COMMON PORT
## = VALVE NUMBER AS SHOWN
IN VALVE SCHEDULE
2P TWO-POSITION (CONTROL SIGNAL)
ADJ ADJUSTABLE/ADJUSTMENT
AFMA AIRFLOW MEASUREMENT ARRAY
AI ANALOG INPUT
ALM ALARM
AO ANALOG OUTPUT
BI BINARY INPUT
BLDG BUILDING
BLR BOILER
BO BINARY OUTPUT
BUT BUTTON
BYP BYPASS
C COMMAND (MODULATING CONTROL SIGNAL)
CF CONDENSER FAN
CH CHILLER
CHW CHILLED WATER
CHS CHILLED WATER SUPPLY
CHR CHILLED WATER RETURN
CLD CLOSED
CLG COOLING
CO CARBON MONOXIDE
CO2 CARBON DIOXIDE
COM COMMON
COMP COMPRESSOR
COV CHANGE OF VALUE
CP CONFIGURATION PROPERTY
CSR CURRENT SENSING RELAY
CT COOLING TOWER
CT CURRENT TRANSFORMER/SWITCH
CTF COOLING TOWER FAN
CWR CONDENSER WATER RETURN
CWS CONDENSER WATER SUPPLY
CW CONDENSER WATER
D DAMPER
DA DISCHARGE AIR
DB DEADBAND
DDC DIRECT DIGITAL CONTROL(LER)
DIFF DIFFERENCE
DIR DIRECT (CONTROL ACTION)
DIS DISABLE
DISP DISPLAY
DPT DEW POINT TEMPERATURE
DX DIRECT EXPANSION (UNIT)
EA EXHAUST AIR
ECM ELECTRICALLY COMMUTATED MOTOR
ECO ECONOMIZER
EF EXHAUST FAN
ENA ENABLE
EP ELECTRIC TO PNEUMATIC TRANSDUCER
EPS ELECTRIC TO PNEUMATIC SWITCH
F FLOW
FACP FIRE ALARM CONTROL PANEL
FL FAIL IN LAST POSITION
FLT FILTER
H2 HYDROGEN
HL HIGH LIMIT
HTG HEATING
HUM HUMIDIFIER
HW HOT WATER
HWR HOT WATER RETURN
HWS HOT WATER SUPPLY
HX HEAT EXCHANGER
I/O INPUT/OUTPUT
IR INFRARED
L LEVEL
LDP LOCAL DISPLAY PANEL
LL LOW LIMIT
LVG LEAVING
M MOTOR or MAIN
M&C MONITORING & CONTROL (SOFTWARE)
MA MIXED AIR
MINOA MINIMUM OUTSIDE AIR
MS MOTOR STARTER
MUW MAKE-UP WATER
N/A NOT APPLICABLE
NC NORMALLY CLOSED
nci NETWORK CONFIGURATION INPUT
NO NORMALLY OPEN
NVI NETWORK VARIABLE INPUT
NVO NETWORK VARIABLE OUTPUT
OA OUTSIDE AIR
OCC OCCUPIED
ODT ON DELAY TIMER
OL OVERLOAD
OPN OPEN
OVRD OVERRIDE
OWS OPERATOR WORKSTATION
P PRESSURE
PID PROPORTIONAL INTEGRAL DERIVATIVE (CONTROL)
PMP PUMP
PP POSITIVE POSITIONER
PWR POWER
R RELAY
RA RETURN AIR
RE RELIEF AIR
REV REVERSE (CONTROL ACTION)
REF RELIEF FAN
RF RETURN FAN
RH RELATIVE HUMIDITY
RH REHEAT
RM ROOM
RQST REQUEST
RST RESET
RT RATE
S STATUS
SA SUPPLY AIR
SEC SECONDARY
SF SUPPLY FAN
SHUTDN SHUTDWON
SMK SMOKE
SNVT STANDARD NETWORK VARIABLE TYPE
SO SHUT-OFF
SP SETPOINT
SS START/STOP COMMAND
STAT THERMOSTAT
SYS SYSTEM
SCHD SCHEDULER
T TEMPERATURE
TAP TAP, PRESSURE
TRB TROUBLE
TSTAT THERMOSTAT
UNOCC UNOCCUPIED
UV ULTRA VIOLET LIGHT
V VALVE
VAV VARIABLE AIR VOLUME
VFD VARIABLE FREQUENCY DRIVE
VIB VIBRATION
WB WET BULB (TEMPERATURE)
XFMR TRANSFORMER
ZN ZONE
PLATE AND FRAME
HEAT EXCHANGER
ABBREVIATIONS & ACRONYMS
"HVAC CONTROLS" GENERAL NOTES:
SHEETS M-602 - M-606
"POINTS LIST SCHEDULE" GENERAL
NOTES: SHEETS M-602 - M-606
ELECTRIC-TO-PNEUMATIC TRANSDUCER
ELECTRIC-TO-PNEUMATIC SWITCH
(SOLENOID ACTUATED PNEUMATIC VALVE)
VDC OR mA INPUT / 3-15 PSI OUTPUT
## = SEQUENTIAL NUMBER
## = SEQUENTIAL NUMBER
(WHEN MORE THAN 1 EPS)
(WHEN MORE THAN 1 EP)
EP
EPS
DIFFERENTIAL PRESSURE SENSORDP
DSP
DUCT STATIC PRESSURE
ESS
EMERGENCY SHUTOFF SWITCH
S c a r
M i c r o f i l m i n g
I n c h e s
M i l l i m e t e r s
1 1312111098765432
I
H
G
F
E
D
C
B
A date detailed checkeddesigned ofsheet sheets project contract rev.drawing file
HONOLULU, HAWAII
ENGINEERS ARCHITECTS & CONSULTANTS
Project No. - MABE152003
UPGRADE BUILDING
HAWAII AIR NATIONAL GUARD
KEAUKAHA ANG STATION, HAWAII
COMPLEX, HILO
01/28/220 FINAL SUBMITTAL BS
MABE 15200391701
C O
P Y
R I G
HVAC CONTROLS
LEGENDS AND ABBREVIATIONS
M-601 0
91701_M601.dwg
B U
R N
D
O N
N E
L L
E
N G
I N
E E
R I N
G
C
O M
P A
N Y
I N
C
SCALE:
C3
CONTROLS SYSTEM ARCHITECTURE - B701, 703, 704, & 705
NONE
GENERAL NOTES
1. FOR GENERAL NOTES, LEGEND, AND ABBREVIATIONS SEE
DRAWING M-001.
2. FOR CONTROLS SPECIFIC GENERAL NOTES, LEGEND, AND
ABBREVIATIONS, SEE DRAWING M-601.
3. SYSTEM ARCHITECTURE IS SCHEMATIC. CONTRACTOR
SHALL PROVIDE ADDITIONAL DEVICES AS REQUIRED FOR A
COMPLETE AND FUNCTIONAL SYSTEM IN COMPLIANCE WITH
SPECIFICATION SECTION 23 09 23.13 20.
4. CONTRACTOR IS RESPONSIBLE FOR SELECTING FINAL
DETAILS OF THE ARCHITECTURE AND ENSURING THAT THE
SYSTEM (DEVICES AND NETWORK) MEETS THE BANDWIDTH
AND COMMUNICATIONS SPEEDS REQUIRED FOR A
PROPERLY OPERATING SYSTEM.
5. 120 VOLT SINGLE PHASE POWER CONNECTION JUNCTION
BOXES HAVE BE PROVIDED FOR USE TO POWER DDC SYSTEM
COMPONENTS. THESE JUNCTION BOXES ARE SHOWN ON THE
ELECTRICAL POWER PLAN DRAWINGS. THE DDC CONTROLS
CONTRACTOR IS RESPONSIBLE FOR ALL POWER WIRING AND
COMPONENTS DOWNSTREAM OF THESE JUNCTION BOXES
AND VERIFYING THE QUANTITY AND LOCATION OF THE
JUNCTION BOXES IS ADEQUATE. ADDITIONAL POWER
CONNECTIONS ARE THE RESPONSIBILITY OF THE DDC
CONTROLS CONTRACTOR.
6. HVAC CONTROLS FOR THESE BUILDINGS ARE DESIGNED TO BE
STANDALONE SYSTEMS AND ARE NOT INTENDED FOR
CONNECTION TO A CAMPUS WIDE SYSTEM. IF SUCH A
CONNECTION IS DESIRED IN THE FUTURE, ADDITIONAL
CONTROLS COMPONENTS MAY BE REQUIRED AND SHALL BE
COORDINATED WITH SITE UTILITIES.
7. VRF SYSTEMS SHALL BE PROVIDED WITH A MEDIA
CONVERTER, IF NEEDED, TO INTERFACE WITH THE BUILDING
NETWORK CONTROLLER VIA NON-PROPRIETARY PROTOCOL.
VRF SYSTEM
CONTROLLER
COMMUNICATION BUS
BUILDING NETWORK
CONTROLLER
B705 MECHANICAL ROOM
DOAS UNITS
OPERATOR
LAPTOP
(BY OTHERS)
VRF UNITS
EXHAUST
AND SUPPLY
FANS
SCALE:
H3
CONTROLS SYSTEM ARCHITECTURE - B702
NONE
DUCTLESS
SPLIT
SYSTEM
COMMUNICATION BUS
BUILDING NETWORK
CONTROLLER
B702 MECHANICAL ROOM
OPERATOR
LAPTOP
(BY OTHERS)
FAN COIL
UNITS
EXHAUST
AND SUPPLY
FANS
BY OTHERS NEW
BY OTHERS NEW
VISUAL DISPLAY
PANEL
VISUAL DISPLAY
PANEL
MEDIA
CONVERTER
S c a r
M i c r o f i l m i n g
I n c h e s
M i l l i m e t e r s
1 1312111098765432
I
H
G
F
E
D
C
B
A date detailed checkeddesigned ofsheet sheets project contract rev.drawing file
HONOLULU, HAWAII
ENGINEERS ARCHITECTS & CONSULTANTS
Project No. - MABE152003
UPGRADE BUILDING
HAWAII AIR NATIONAL GUARD
KEAUKAHA ANG STATION, HAWAII
COMPLEX, HILO
01/28/220 FINAL SUBMITTAL BS
MABE 15200391701
C O
P Y
R I G
HVAC CONTROLS
M-602 0
91701_M602.dwg
B U
R N
D
O N
N E
L L
E
N G
I N
E E
R I N
G
C
O M
P A
N Y
I N
C
SEQUENCE OF OPERATION DEDICATED OUTSIDE AIR SYSTEM (DOAS) AHU
DX
OA-T
OA-F
T
AFMA
D…