Attachment B - Oak_Creek_OYA-Control-Room-Upgrade-ARCH_REV1~1.pdf

PDF 2 MB Posted

Attached to
Control Room Renovations (EOYCF, OCYCF, and RVYCF)
Solicitation number
S-DASOBO-00009651
Issued by
Hood River County, Jackson County, Linn County, Albany City, Oregon

About this file

This document appears to be a set of architectural drawings and specifications related to the Control Room Renovations project for the Oregon Youth Authority, which encompasses facilities in Harney, Josephine, and Linn Counties, including the Eastern Oregon Youth Correctional Facility, Oak Creek Youth Correctional Facility, and Rogue Valley Youth Correctional Facility. The drawings provide detailed plans for the renovation of the control rooms at these facilities, including demolition, construction, finishes, electrical, mechanical, and security systems. The project aims to update the control rooms to support the operational needs of the Oregon Youth Authority. The documents indicate the project will be bid and constructed in 2023-2024.

The architectural drawings include floor plans, elevations, details, and finish schedules for the control room renovations. Key elements include the installation of new cabinetry, countertops, plumbing fixtures, electrical equipment, lighting, security systems, and accessibility improvements. The project will be competitively bid, with the successful contractor responsible for coordinating the work with the facilities to minimize disruptions to operations. Funding for the project is provided by the State of Oregon, and the contract term is expected to cover the duration of the renovation work.

View the file

Other files

Show all 17

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Date:

Proj. No.:

D

SG

N D

R C

H K

AP

VD

AP

VD

BY

R

EV

IS

IO

N

D

AT

E N

O

PLOT DATE/TIME:

Drawing No.:

Pr oj ec t T itl e:

D ra w in g Ti tle

D

C

B

A

1 2 3 4 5 6

REUSE OF DOCUMENTS: THIS DOCUMENT, AND THE IDEAS AND DESIGNS INCORPORATED HEREIN, AS AN INSTRUMENT OF PROFESSIONAL SERVICE, IS THE PROPERTY OF JACOBS AND IS NOT TO BE USED, IN WHOLE OR IN PART, FOR ANY OTHER PROJECT WITHOUT THE WRITTEN AUTHORIZATION OF JACOBS.

www.Jacobs.com

Ja co bs

E ng in ee rin g

G ro up In c.

A

LL

R

IG

H

TS

R

ES

ER

V

ED

04/04/2024

4/4/2024 6:40:14 PM BIM 360://US_D3482000_OYA Control Room Upgrade/Oak_Creek_OYA-Control-Room-Upgrade-ARCH_marcin.krzysik.rvt

IS

SU

E

FO

R R

EV

IS

IO

N

D3482000

M K

/ J A

M K

/ J A

JB

JB

OYA-000

O R

EG

O

N Y

O U

TH

A

U

TH

O R

IT

Y

O

AK

C R

EE

K

FA

C

IL

IT

Y

OAK CREEK FACILITY

4400 LOCHNER RD SE

ALBANY, OR 97322

PORTLAND OFFICE

PORTLAND, OR 97201

2020 SW 4TH AVE, SUITE 300

C O

VE

R

S H

EE

T

/1 0/

IS

SU

E

FO

R C

O N

ST

R

U C

TI

O

N

/0

4/

IS

SU

E

FO

R

R E V

IS

IO

N

OREGON YOUTH AUTHORITY

REGIONAL FACILITIES

CONTROL ROOM UPGRADE

OAK CREEK YOUTH CORRECTIONAL FACILITY

DECEMBER 2023

JACOBS PROJECT NO. D3482000

SHEET LIST

DRAWING DRAWING TITLE DISCIPLINE REV DATE

OYA-000 COVER SHEET COVER SHEET 1 04/04/2024

OYA-001 LEGENDS & MOUNTING HEIGHTS &

ABBREVIATIONS

ARCHITECTURE 0 12/10/2023

OYA-002 CODE PLAN ARCHITECTURE 0 12/10/2023

OYA-100 FIRST FLOOR PLAN OVERALL ARCHITECTURE 0 12/10/2023

OYA-200 DEMOLITION PLAN ARCHITECTURE 1 04/04/2024

OYA-300 ENLARGED FLOOR PLAN & FINISH ARCHITECTURE 1 04/04/2024

OYA-301 ENLARGED CEILING PLAN ARCHITECTURE 0 12/10/2023

OYA-302 ENLARGED FURNITURE PLAN & EQUIPMENT ARCHITECTURE 0 12/10/2023

OYA-500 INTERIOR ELEVATIONS ARCHITECTURE 1 04/04/2024

OYA-600 DETAILS ARCHITECTURE 1 04/04/2024

OYA-700 DOOR AND ROOM SCHEDULES & FINISH LEGEND ARCHITECTURE 1 04/04/2024

PROJECT LOCATION

OAK CREEK FACILITY

4400 LOCHNER RD SE

ALBANY, OR 97322

VICINITY MAP

OYA-E301 LIGHTING PLAN ELECTRICAL 0 12/10/2023

OYA-E302 POWER PLAN ELECTRICAL 0 12/10/2023

OYA-M100 FLOOR PLAN MECHANICAL 0 12/10/2023

OYA-ES0001 LEGEND ABBREVIATIONS & GENERAL NOTES SECURITY 0 12/10/2023

OYA-ES1000 SECURITY PLAN SECURITY 0 12/10/2023

OYA-ES4701A DOOR CONTROL LOOP TERM. WIRING - PANEL 1 SECURITY 0 12/10/2023

OYA-ES4701C DOOR CONTROL LOOP TERM. WIRING - PANEL 1 SECURITY 0 12/10/2023

OYA-ES4701E DOOR CONTROL LOOP TERM. WIRING - PANEL 1 SECURITY 0 12/10/2023

OYA-ES7201 SECURITY DOOR DETAILS SECURITY 0 12/10/2023

OYA-ES7210 SECURITY DETAILS SECURITY 0 12/10/2023

04/05/2024

DN

CONTROL

ROOM

RESTROOM

(D) RAISED ACCESS FLOOR PANELS,

SEE NEW SCOPE FOR REUSE OF

EXISTING PEDESTALS /

COMPONENTS WHERE POSSIBLE

EXISTING HOUSING UNIT

NOT PART OF PROJECT

SCOPE

EXISTING

ADMINISTRATION

BUILDING

NOT PART OF PROJECT

SCOPE

(D) EXISTING

OBSERVATION

WINDOWS AND

PORTION OF CMU WALL

TO ACCOMMODATE

FOR NEW WINDOWS

(D) EXISTING CMU WALL TO

ACCOMMODATE FOR NEW

DOOR OPENING. SEE NEW

FLOOR PLAN AND DOOR

SCHEDULE FOR DOOR SIZE.

PATCH AND REPAIR.

PREPARE SURFACE

FOR NEW FINISH.

SEE FINISH PLAN

FOR MORE

INFORMATION

(D) EXISTING FURNITURE,

CABINETS, RACKS, SHELVES.

COORDINATE DISPOSITION WITH

OWNER

(D) VCT

(D) VCT

(D) PANELS. (N) FINISH TO

BE INSTALLED ON STEPS

AND RAISED ACCESS

FLOOR SYSTEM

(D) EXISTING HANDRAIL

OYA-200

OYA-200

(D) EXISTING KEY

BOARD

(E) DOOR TO

REMAIN

(D) PORTION OF STAIRS TO

ACCOMMODATE NEW DOOR

OPENING

(D) ACT, LIGHTS

FIXTURES, SMOKE

DETECTORS,

SENSORS AND

CEILING GRIDS.

(E) GYPSUM

CEILING TO

REMAIN. PATCH

AND REPAIR IF

NECESSARY

(E) GYPSUM

CEILING TO

REMAIN. PATCH

AND REPAIR IF

NECESSARY

(D) GYPSUM SOFFIT

EXISTING HOUSING UNIT

NOT PART OF PROJECT

SCOPE

EXISTING

ADMINISTRATION

BUILDING

NOT PART OF PROJECT

SCOPE

(E) SPRINKLER.

REFER TO MEP

DRAWINGS FOR

MORE INFORMATION

(E) DIFFUSER.

REFER TO

MECHANICAL

DRAWINGS FOR

MORE INFORMATION

(D) ALL EXISTING LIGHT

FIXTURES. REFER TO

ELECTRICAL DARWINGS FOR

MORE INFORMATION

(D) EXISTING LIGHT

FIXTURES. REFER TO

ELECTRICAL DARWINGS FOR

MORE INFORMATION

(E) SPRINKLER.

REFER TO MEP

DRAWINGS FOR

MORE INFORMATION

RAISED ACCESS FLOOR

2' - 8"

FINISH FLOOR

0' - 0"

(D) EXISTING

WINDOW. OPENING

LOWERED TO JUST

ABOVE RAF

(E) FIRE ALARM

TO REMAIN

DEMO PART OF EXISTING CMU

WALL TO ACCOMMODATE FOR

NEW WINDOW. REFER TO

WINDOW SCHEDULE FOR SIZE.

(E) CMU WALL

PATCH/ INFILL

OPENING

EDGES WITH

MORTAR/GROUT

AS NECESSARY

EXISTING EXISTING

VI

F

VI

F

FINISH FLOOR

0' - 0"

DEMO EXISTING CMU

WALL TO

ACCOMMODATE FOR

NEW DOOR OPENING.

REFER TO DOOR

SCHEDULE FOR

DOOR SIZE

PATCH/ INFILL

OPENING

EDGES WITH

MORTAR/GROUT

AS NECESSARY

DEMO EXISTING

HANDRAIL

EXISTING PEDESTALS

TO REMAIN

WT5X11

REFER TO DEMO

NOTES AND LINTEL

DETAIL ON SHEET

OYA-600 FOR MORE

INFORMATION

(D) EXISTING PANELS.

PROVIDE NEW.

REFER TO FINISH

SCHEDULE

VI

F

6"

4" MIN.

BOLTS SPACED AT 8"TEMPORARY SHORING.

SEE DETAIL 5

2 BOLTS EA. SIDE IN

CONTINOUS CMU

EXISTING CMU WALL

16"

THRU-BOLTS

SPACED AT 8"

TEMP.

CHANNELS

16" 16"

C6X8.2

CONTROL ROOM

CMU ADMINISTRATION

OFFICE

NOTE: SHORING COULD BE 2 CHANNELS

(C6X8.2) SANDWITCHING THE WALL.

SEQUENCE:

1. DRILL HOLES THRU CMU WALL

2. THRU-BOLT AND ATTACH CHANNELS,

EXTENDING 6-8" PAST AREA BEING DEMO-ED

3. DEMO WALL AS SHOWN IN HATCHED AREA

4. INSTALL NEW CHANNEL

5. INFILL WITH BLOCK, RE-GROUT ALL JOINTS

6. REMOVE CHANNELS AND BOLTS

7. PATCH/PAINT WALL TO CONCEAL HOLES

Date:

Proj. No.:

D

SG

N D

R C

H K

AP

VD

AP

VD

BY

R

EV

IS

IO

N

D

AT

E N

O

PLOT DATE/TIME:

Drawing No.:

Pr oj ec t T itl e:

D ra w in g Ti tle

D

C

B

A

1 2 3 4 5 6

REUSE OF DOCUMENTS: THIS DOCUMENT, AND THE IDEAS AND DESIGNS INCORPORATED HEREIN, AS AN INSTRUMENT OF PROFESSIONAL SERVICE, IS THE PROPERTY OF JACOBS AND IS NOT TO BE USED, IN WHOLE OR IN PART, FOR ANY OTHER PROJECT WITHOUT THE WRITTEN AUTHORIZATION OF JACOBS.

www.Jacobs.com

Ja co bs

E ng in ee rin g

G ro up In c.

A

LL

R

IG

H

TS

R

ES

ER

V

ED

04/04/2024

4/4/2024 6:40:14 PM BIM 360://US_D3482000_OYA Control Room Upgrade/Oak_Creek_OYA-Control-Room-Upgrade-ARCH_marcin.krzysik.rvt

IS

SU

E

FO

R R

EV

IS

IO

N

D3482000

M K

/ J A

M K

/ J A

JB

JB

OYA-200

O R

EG

O

N Y

O U

TH

A

U

TH

O R

IT

Y

O

AK

C R

EE

K

FA

C

IL

IT

Y

OAK CREEK FACILITY

4400 LOCHNER RD SE

ALBANY, OR 97322

PORTLAND OFFICE

PORTLAND, OR 97201

2020 SW 4TH AVE, SUITE 300

AR

C

H

IT

EC

TU

R E

D

EM

O

LI

TI

O

N F

LO

O

R P

LA

N

C O

N

TR

O L

R O

O M

- 1/2" = 1'-0"

1 DEMOLITION FLOOR PLAN - CONTROL ROOM

/1 0/

IS

SU

E

FO

R C

O N

ST

R

U C

TI

O

N

/0

4/

IS

SU

E

FO

R

R E V

IS

IO

N

- 1/2" = 1'-0"

2 DEMOLITION REFLECTED CEILING PLAN - CONTROL ROOM

1. UNLESS OTHERWISE INDICATED ON THE DRAWINGS OR IN THE

SPECIFICATIONS, THE FOLLOWING NOTES SHALL APPLY.

2. BEFORE ANY DEMOLITION IS TO BE PERFORMED IN THE AREA OF

WORK, A PROTECTIVE BARRIER WILL HAVE TO BE IN PLACE TO

PROTECT THE WORK AREA FROM THE ADMINISTRATION AREA

SUCH AS A POLYETHYLENE FILM SHEETING.

3. REFER TO MECHANICAL, PLUMBING, FIRE PROTECTION AND

ELECTRICAL DEMOLITION DRAWINGS FOR EXTENT OF

DEMOLITION OF MECHANICAL, PLUMBING, FIRE PROTECTION AND

ELECTRICAL ITEMS.

4. REMOVE AND DISPOSE OF ALL EXISTING EQUIPMENT AS

INDICATED ON THE DRAWINGS AS REQUIRED. EQUIPMENT

DESIGNATED FOR REUSE IS TO BE REMOVED AND STORED PER

OWNER/ CONSTRUCTION MANAGER DIRECTION.

5. DEMOLITION CONTRACTOR TO REVIEW NEW WORK

CONSTRUCTION DOCUMENTS FOR SCOPE, INTENT AND

COORDINATION WITH DEMOLITION.

6. REVIEW AND VERIFY PATH FOR REMOVAL OF TRASH/ DEBRIS

FROM PROJECT LOCATION WITH CONSTRUCTION MANAGER

PRIOR TO BEGINNING WORK.

7. DEMOLITION CONTRACTOR TO REPORT ANY FIELD CONDITIONS

THAT VARY FROM THOSE INDICATED ON THE DOCUMENTS.

8. DEMOLITION CONTRACTOR TO ADVISE CONSTRUCTION

MANAGER OF PARTITIONS OR WALLS REMAINING THAT HAVE

BEEN WEAKENED AFTER DEMOLITION AND ARE UNSAFE OR

UNSALVAGEABLE.

9. DEMOLITION CONTRACTOR TO INDICATE ANY ELECTRICAL RISER

OR PLUMBING RISER UNCOVERED WITHIN A DEMOLISHED

PARTITION. INCLUDES MECHANICAL DUCT SHAFTS NOT

INDICATED ON DOCUMENTS.

10. DEMOLITION CONTRACTOR TO SAFELY SECURE ANY AND ALL

PIPING, WIRING, CABLES OR DEVICES THAT ARE NOT

SCHEDULED FOR DEMOLITION AND WHERE SECURED BY ITEMS

(PARTITIONS) THAT HAVE BEEN OR ARE SCHEDULED FOR

DEMOLITION.

11. DEMOLITION CONTRACTOR IS RESPONSIBLE FOR STRUCTURAL

INTEGRITY OF EXISTING BUILDING WHERE PART OR PORTIONS

OF STRUCTURE/WALLS HAVE BEEN REMOVED.

12. DEMOLITION CONTRACTOR IS RESPONSIBLE FOR PROTECTING

ALL STRUCTURE, WALLS, DOORS, MEP ITEMS, ETC. THAT ARE

REQUIRED TO REMAIN.

13. THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND

EXISTING CONDITIONS, INCLUDING BUT NOT LIMITED TO: WALLS,

FLOORS, MECHANICAL CONSTRUCTION, EXISTING

CONSTRUCTION TO REMAIN, EXISTING CONSTRUCTION TO BE

DEMOLISHED.

14. DEMOLITION CONTRACTOR TO VERIFY WITH OWNER AND/ OR

CONSTRUCTION MANAGER THOSE ITEMS THAT ARE TO BE

SALVAGED PER OWNER'S INSTRUCTIONS PRIOR TO BEGINNING

WORK.

15. COORDINATE WITH CONSTRUCTION MANAGER FOR TEMPORARY

PARTITIONS AS REQUIRED BY DEMOLITION WORK.

15. MARK THE OPENING SIZE FOR THE DOOR / WINDOWON BOTH

SIDES OF THE WALL. REFER TO SCHEDULE FOR DOOR/WINDOW

SIZE.

16. SAW CUT USING MASONRY CIRCULAR SAW BLADE. OPENING

SHOULD BE TWO INCHES WIDER THAN THE DOOR

FRAME, AND ABOUT AN INCH TALLER IN HEIGHT. ADD

ANOTHER SET OF MARKS ACROSS THE TOP OF THE

FRAME TO REPRESENT A STEEL LINTEL THAT WILL

SUPPORT THE LOAD ABOVE THE DOOR. THE LINTEL

SHOULD BE CENTERED OVER THE DOOR. IT SHOULD

ALSO EXTEND 6 INCHES PAST THE DOOR FRAME ON

EITHER SIDE. INFILL EACH SIDE OF THE OPENING BELOW LINTEL.

17. COORDINATE STORAGE OR DISPOSAL LOCATION WITH

CONSTRUCTION SUPERINTENDENT.

18. FOR MORE INFORMATION REFER TO SPECIFICATION 02 41 19

SELECTIVE DEMOLITION.

GENERAL DEMO NOTES:

- 1/2" = 1'-0"

4 ELEVATION - DEMO NEW WINDOW OPENING

- 1/2" = 1'-0"

3 ELEVATION - DEMO NEW DOOR OPENING

- 1" = 1'-0"

5 SHORING DETAIL

DN

CONTROL ROOM

(E) SECURITY

EQUP. BOARD

OYA-500

OYA-500 4OYA-500

(E) COFFEE MAKER

(E) MICROWAVE

(N) UNDER COUNTER

REFRIGERATOR

RESTROOM

(N) KEY

BOX

(N) STORAGE

/ CUBBY

CABINET

(E) ELEC

PANELS

(N) FLOOR FINISH ON RAISED

ACCESS FLOOR SYSTEM,

REFURBISH EXISTING TILES

IF AVAILABLE

(N) SMALL KITCHEN SINK,

PLUMBING CONNECTIONS

THROUGH ADJACENT TOILET

ROOM CHASE

(N)

WHITEBOARD

MOUNTED ON

(E) DOOR

(N) FLAT SCREEN

MONITOR ON WALL

MOUNT ABOVE

WINDOW. SEE

ELEVATIONS

(E) TRANSACTION

DRAWER, (N)

CUSTOM CASEWORK

BUILT TO FIT. SEE

SHEET OYA-302

(N) DOOR TO ADJACENT

ADMINISTRATION SPACE

MANUALLY KEY LOCKED

WITH DOOR POSITION

MONITORING. REFER TO

SHEET OYA-700 FOR MORE

INFORMATION.

EXISTING HOUSING UNIT

NOT PART OF PROJECT

SCOPE

EXISTING

ADMINISTRATION

BUILDING

NOT PART OF PROJECT

SCOPE

(N) BASE CABINETS. REFER

TO SHEET OYA-302

(N) ELECTRIC

MOTOR SUN

SHADE AT (E)

WINDOW

(N) WALL MOUNTED WASTE BASKET

(N) TOILET SEAT COVER DISPENSER

(N) GLOVE BOX HOLDER - 5 BOX

CAPACITY

PAPER TOWEL DISPENSER (OFOI)

SOAP DISPENSER (OFOI)

TOILET PAPER DISPENSER (OFOI)

EMPTY SPACE FOR SECOND

WORK STATION IF NEEDED

(N) DESK. REFER TO

SHEET OYA-302

(N) INSTANT HOT

WATER DISPENSER

(N) LOWER

WINDOWS, PROVIDE

(N) ONE-WAY FILM

AND (N) BLINDS.

(N) BUILT-IN CORNER

CASEWORK WITH

STORAGE. REFER TO

SHEET OYA-302

(E) DOOR TO

REMAIN

(E) STAIRS TO

ACCOMMODATE FOR NEW

DOOR OPENING. NEW

FINISH TO BE INSTALLED

(N) VCT

(E) FIRE ALARM

(R) DATA

RACK

3' - 1 1/8"

C O

U R

TY

AR

D

101A

101B

102A

01 01

3' - 10 3/8"

3' - 8"

(N) HANDRAIL.

SEE

ELEVATIONS

(N) ELECTRIC

MOTOR SUN

SHADE AT (E)

WINDOW

3' - 8"1' - 4 7/8"

C O

U R

TY

AR

D N

O T

PA

R

T O

F

PR

O

JE

C T

SC

O

PE

PATCH AND

REPAIR. SEE

FINISH PLAN

FOR MORE

INFORMATION

VI

F

(N) UPPER CABINETS.

REFER TO SHEET

OYA-302 FOR MORE

INFORMATION

(N) VCT

(N) FACIA TO

BE INSTALLED.

SEE DETAIL

10/OYA-600

(E)

FIREEXTINGUSHER

TO BE INSTALLED.

SEE OYA-001 FOR

MOUNTING HEIGHTS

OYA-500

OYA-500 4OYA-500

293 SF

CONTROL ROOM

35 SF

RESTROOM

101A

101B

102A

EXISTING

ADMINISTRATION

BUILDING

NOT PART OF PROJECT

SCOPE

PAINT PT1 SEMI-

GLOSS

A. ALL FLOORING TO EXTEND UNDER NEW MILLWORK, SHELVING AND EQUIPMENT.

B. FLOOR MATERIAL TRANSITIONS SHALL OCCUR UNDER THE CENTERLINE OF DOOR IN CLOSED POSITION.

C. NEW BASE THROUGHOUT SHALL BE RB1, UNO.

D. GWB CONSTRUCTION THROUGHOUT SHALL BE PT1 AND PT2 FOR RESTROOM, UNO. SEE SPEC 09 91 26 FOR MORE

INFORMATION

E. CLOSETS SHALL BE FINISHED TO MATCH ADJACENT SPACE, UNO.

F. GWB CEILINGS AND SOFFITS THROUGHOUT SHALL BE PAINTED PT1, UNO. .

G. DOORS, DOOR/ WINDOW FRAMES SHALL BE PAINTED IN SEMI-GLOSS FINISH. UNO. SEE SPEC 09 91 26 FOR MORE

INFORMATION

H. SEAMS IN RESILIENT BASE AT OUTSIDE CORNERS ARE NOT PERMITTED. ALL RESILIENT BASE TO BE PURCHASED IN 100'

ROLLED STOCK, NOT 48" INDIVIDUAL LENGTHS.

I. PROVIDE APPROPRIATE METAL TRANSITION STRIPS CENTERLINE AT EVERY FLOORING TRANSITION, UNLESS OTHERWISE

NOTED.

J. COORDINATE FLOORING INSTALLATION WITH ELECTRICAL DRAWINGS FOR ANY PROPOSED FLOOR POWER / DATA

RECEPTACLES. PATCH FLOOR SLAB AND FIT FLOOR FINISHES AROUND OUTLETS AS REQUIRED.

K. ALL GWB FINISH LEVELS AS INDICATED BY MANUFACTURER OF WALL-APPLIED PRODUCTS INCLUDING MARKERBOARDS, MARKERBOARD PAINTS, WALLCOVERING, AND TILE.

L. AT SOLID SURFACE SURFACES, ALL SEAMS TO BE FILLED W/ MANUFACTURER'S JOINT ADHESIVE. TO BE SANDED AND

BUFFED SMOOTH - NO VISIBLE SEAM, TYP

M. REFER TO SPECIFICATION 09 69 00 ACCESS FLOORING. FOR MORE INFORMATION.

FINISH PLAN GENERAL NOTES

CEILING

WALL

BASE

FLOOR

FINISH SYMBOL LEGEND:

PT2

RB1

VCT1

EXISTING

PT1

RB1

AFP1/VCT1

ACT1/GYP. BD.

Date:

Proj. No.:

D

SG

N D

R C

H K

AP

VD

AP

VD

BY

R

EV

IS

IO

N

D

AT

E N

O

PLOT DATE/TIME:

Drawing No.:

Pr oj ec t T itl e:

D ra w in g Ti tle

D

C

B

A

1 2 3 4 5 6

REUSE OF DOCUMENTS: THIS DOCUMENT, AND THE IDEAS AND DESIGNS INCORPORATED HEREIN, AS AN INSTRUMENT OF PROFESSIONAL SERVICE, IS THE PROPERTY OF JACOBS AND IS NOT TO BE USED, IN WHOLE OR IN PART, FOR ANY OTHER PROJECT WITHOUT THE WRITTEN AUTHORIZATION OF JACOBS.

www.Jacobs.com

Ja co bs

E ng in ee rin g

G ro up In c.

A

LL

R

IG

H

TS

R

ES

ER

V

ED

04/04/2024

4/4/2024 6:40:15 PM BIM 360://US_D3482000_OYA Control Room Upgrade/Oak_Creek_OYA-Control-Room-Upgrade-ARCH_marcin.krzysik.rvt

IS

SU

E

FO

R R

EV

IS

IO

N

D3482000

M K

/J A

M K

/ J A

JB

JB

OYA-300

O R

EG

O

N Y

O U

TH

A

U

TH

O R

IT

Y

O

AK

C R

EE

K

FA

C

IL

IT

Y

OAK CREEK FACILITY

4400 LOCHNER RD SE

ALBANY, OR 97322

PORTLAND OFFICE

PORTLAND, OR 97201

2020 SW 4TH AVE, SUITE 300

AR

C

H

IT

EC

TU

R E

FL

O

O R

P

LA

N

F

IN

IS

H

P

LA

N C

O N

TR

O

L R

O O

M

- 1/2" = 1'-0"

1 FLOOR PLAN - CONTROL ROOM

/1 0/

IS

SU

E

FO

R C

O N

ST

R

U C

TI

O

N

/0

4/

IS

SU

E

FO

R

R E V

IS

IO

N

- 1/2" = 1'-0"

2 FLOOR PLAN - CONTROL ROOM FINISH PLAN

RAISED ACCESS FLOOR

2' - 8"

(E) SECURITY EQUP.

BOARD

(N) MINI FRIDGE

(N) BASE CABINETS -

CABINETS TO ACCOMODATE

MISC. STORAGE INCLUDING

BUT NOT LIMITED TO

BINDERS, OFFICE SUPPLIES,

BREAK AREA SUPPLIES, ETC

(N) KEY

BOX

(N) WHITEBOARD

24"x36" MOUNTED ON

(E) DOORS

(N) FLAT SCREEN

MONITORS ON WALL

MOUNT ABOVE WINDOW

EQ EQ

EQ EQ

3'

4"

PT1

PT1

PT1

RB1

((N) UPPER CABINETS TYP. PROVIDE

KEYED CAM LOCK ON ALL WALL

CABINETS EXEPT CORNER CABINET.

CABINETS TO ACCOMODATE MISC.

PERSONAL BELONGINGS. SEE OYA-600

FOR MORE INFO.

18"15" 24"

23"

RAISED ACCESS FLOOR

2' - 8"

AP

PR

O X

0'

3/

8"

8'

0"

(N) WINDOWS

WITH ONE-WAY

FILM AND BLINDS.

SILL LOWERED TO

JUST ABOVE RAF.

REFER TO DETAIL

SHEET OYA-600

FOR MORE INFO.

AV

G

S

TA

N D

IN

G

E

YE

H

EI

G H

T

4'

1/

2"

.0

0°

30.00°

SE

AT

ED

E

YE

H

EI

G

H T

3'

1/

2"

30.00°

3' - 8"

5'

2"

(E) FIRE ALARM

TO REMAIN

(N) ELECTRIC

MOTOR SUN

SHADE AT (E)

WINDOW

PT1

WF1

WF1

(N) MONITORS.

FOLLOW MFR

RECOMENDATIONS

FOR MOUNTONG

AND BLOCKING

RB1

RB1

3' - 0" 1' - 6"

RAISED ACCESS FLOOR

2' - 8"

3' - 0"

(N) BASE CABINETS -

CABINETS TO ACCOMODATE

MISC. STORAGE INCLUDING

BUT NOT LIMITED TO

BINDERS, OFFICE SUPPLIES,

BREAK AREA SUPPLIES, ETC.

SEE OYA-600 FOR MORE

INFO.

(E) WINDOWS

(E) COFFEE

MAKER

(E) MICROWAVE

(N) MINI FRIDGE

PT1

RB1

(N) UPPER CABINETS TYP. WITH ABBILITY

TO PROVIDE EXTERNAL LOCK.

CABINETS TO ACCOMODATE MISC.

STORAGE INCLUDING PERSONAL

BELONGINGS. SEE OYA-600 FOR MORE

INFO.

15"15"15"15"15"24"

PT1

RAISED ACCESS FLOOR

2' - 8"

(N) (4)FLAT SCREEN

MONITORS ON WALL

MOUNT ABOVE

WINDOW

(N) (4) FLAT SCREEN

MONITORS

(N) BUILT-IN

CORNER

CASEWORK.

REFER TO DETAIL

SHEET OYA-600

FOR MORE

INFORMATION

(E) WINDOWS

(N) ACOUSTIC

CEILING @ 8' - 0"

ABOVE RAF

(E) GYPSUM CEILING

ABOVE STAIRS TO

REMAIN. PAINT PT1

8'

0"

FINISH FLOOR

0' - 0"

(E) TRANSACTION

DRAWER, (N)

CUSTOM CASEWORK

BUILT TO FIT

(N) ELECTRIC

MOTOR SUN

SHADE AT (E)

WINDOW

(N) ELECTRIC

MOTOR SUN

SHADE AT (E)

WINDOW

PAINT PT1

PAINT PT1

101B

RB1

(N) HANDRAIL. SEE

DETAIL SHEET

OYA-600

(N) HANDRAIL.

MOUNTED TO THE

WALL IF

NECESSARY

TALL

STORAGE

CABINET

OPEN

CUBBIES OR

PERSONAL

LOCKERS

RAISED ACCESS FLOOR

2' - 8"

(N) WALL MOUT

TRASH CAN.

REFER TO

SHEET OYA-001

FOR MOUNTING

HEIGHTS

2' - 6"

11 1/4"

EQ

EQ

EQ PT2

7'

0"

RB1

RAISED ACCESS FLOOR

2' - 8"

(N) GLOW BOX.

REFER TO

SHEET OYA-001

FOR MOUNTING

HEIGHTS

(N) TOILET SEAT

DISPENSER.

REFER TO

SHEET OYA-001

FOR MOUNTING

HEIGHTS

(N) WALL MOUT

TRASH CAN

(E) MIRROR

PT2

RB1

RAISED ACCESS FLOOR

2' - 8"

FINISH FLOOR

0' - 0"

101A

(E) SECURITY EQUP.

BOARD

(N) DOOR TO

ADMINISTRATION

BUILDING. REFER TO

DOOR SCHEDULE

FOR MORE

INFORMATION

(E) STAIRS TO

REMAIN. PROVIDE

NEW FINISH PANELS

IF NECESSARY AND

REUSE EXISTING

PEDESTALS

(N) NEW RAILING. SEE

DETAIL SHEET

OYA-600

(E) GYP. BD. SOFFIT

PT1

RB1

36"

Date:

Proj. No.:

D

SG

N D

R C

H K

AP

VD

AP

VD

BY

R

EV

IS

IO

N

D

AT

E N

O

PLOT DATE/TIME:

Drawing No.:

Pr oj ec t T itl e:

D ra w in g Ti tle

D

C

B

A

1 2 3 4 5 6

REUSE OF DOCUMENTS: THIS DOCUMENT, AND THE IDEAS AND DESIGNS INCORPORATED HEREIN, AS AN INSTRUMENT OF PROFESSIONAL SERVICE, IS THE PROPERTY OF JACOBS AND IS NOT TO BE USED, IN WHOLE OR IN PART, FOR ANY OTHER PROJECT WITHOUT THE WRITTEN AUTHORIZATION OF JACOBS.

www.Jacobs.com

Ja co bs

E ng in ee rin g

G ro up In c.

A

LL

R

IG

H

TS

R

ES

ER

V

ED

04/04/2024

4/4/2024 6:40:15 PM BIM 360://US_D3482000_OYA Control Room Upgrade/Oak_Creek_OYA-Control-Room-Upgrade-ARCH_marcin.krzysik.rvt

IS

SU

E

FO

R R

EV

IS

IO

N

D3482000

M K

/ J A

M K

/ J A

JB

JB

OYA-500

O R

EG

O

N Y

O U

TH

A

U

TH

O R

IT

Y

O

AK

C R

EE

K

FA

C

IL

IT

Y

OAK CREEK FACILITY

4400 LOCHNER RD SE

ALBANY, OR 97322

PORTLAND OFFICE

PORTLAND, OR 97201

2020 SW 4TH AVE, SUITE 300

AR

C

H

IT

EC

TU

R E

IN

TE

R

IO

R E

LE

VA

TI

O

N S

/1 0/

IS

SU

E

FO

R C

O N

ST

R

U C

TI

O

N

/0

4/

IS

SU

E

FO

R

R E V

IS

IO

N

- 1/2" = 1'-0"

1 ELEVATION - CONTROL ROOM NORTH

- 1/2" = 1'-0"

3 ELEVATION - CONTROL ROOM SOUTH

- 1/2" = 1'-0"

4 ELEVATION - CONTROL ROOM EAST

- 1/2" = 1'-0"

5 ELEVATION - CONTROL ROOM WEST

- 1/2" = 1'-0"

6 ELEVATION - RESTROOM NORTH

- 1/2" = 1'-0"

7 ELEVATION - RESTROOM EAST

- 1/2" = 1'-0"

2 ELEVATION - CONTROL ROOM NORTH 1A

1/ 4"

1/ 4"

FILL SOLID WITH NON-SHRINK GROUT

CONTROL JOINT SEE SPECIFICATIONS

HOLLOW METAL DOOR

AND DOOR FRAME

REFER TO DOOR SCHEDULE

CONCRETE FLOOR SLAB

REFER TO FINISH SCHEDULE

ALUMINUM THRESHOLD SET IN SEALANT

PROVIDE CLOSURE AT ENDS, TYP.

CMU/CONCRETE WALL

BEYOND

INTERIOREXTERIOR

RAISED ACCESS FLOOR

2' - 8"

36"

(N) BASE CABINETS TO

ACCOMODATE MISC.

STORAGE INCLUDING BUT

NOT LIMITED TO BINDERS,

OFFICE SUPPLIES, BREAK

AREA SUPPLIES, ETC

1/

4"

SS1

LT1

LT1

(N) BASE CORNER

CABINET WITH

SINK

24" 66"

36" 18"

1/

2"

LT1

(N) UPPER CABINETS TYP.

PROVIDE KEYED CAM LOCK ON

ALL WALL CABINETS EXEPT

CORNER CABINET.

CABINETS TO ACCOMODATE

MISC. PERSONAL BELONGINGS

15"15"15"15"15"24"

(N) UPPER

CORNER

CABINET TYP.

12"

CAM LOCK KEYED

4" BAR HANDLES.

STAINLESS STEEL FINISH

3"

15"

RAISED ACCESS FLOOR

2' - 8"

SS1 LT1

3/4" END

PANEL, LT1

OPEN

/4

1/

4"

23" 36"

(N) BASE CABINETS -

CABINETS TO

ACCOMODATE MISC.

STORAGE INCLUDING BUT

NOT LIMITED TO BINDERS,

OFFICE SUPPLIES, BREAK

AREA SUPPLIES, ETC

(N) UPPER CABINETS TYP.

PROVIDE KEYED CAM LOCK

ON ALL WALL CABINETS

EXEPT CORNER CABINET.

CABINETS TO ACCOMODATE

MISC. PERSONAL

BELONGINGS

(N) UPPER

CORNER CABINET

TYP.

18" 24"

21 1/2" 3 1/

2"

CAM LOCK

KEYED

4" BAR

HANDLES.

STAINLESS

STEEL

FINISH.

15"

3"

12"

(N) BUILT-IN

CORNER

CASEWORK

SS1

LT1

EQ

5"

OPEN

SHELVES

6" DEEP

1' - 0"

2'

2'

3/

4"

1/

4"

EQ

3/ 4"

3' - 2"

2' - 1"

3/4"

3/ 4"

1/

2"3"

1"

OPEN

(N) BUILT-IN

CORNER

CASEWORK

SS1LT1

OPEN

SHELVES

2'

1' - 10 1/2" 3' - 2"

3/4"

EQ

EQ

5"

6"

1/

2"

3/ 4"

1/

4"

3/4"

REFER TO PLAN

FOR DOOR SWING

HOLLOW METAL DOOR

AND DOOR FRAME

REFER TO DOOR SCHEDULE

CONTINUOUS BEAD OF SEALANT

AND BACKER ROD, EACH SIDE, TYP.

EXISTING CMU WALL

SHIM AS NECESSARY

6"2" A

T

JA

M B

4" A

T H

EA

D

GALV METAL

DRIP EDGE

INTERIOR

EXTERIOR

STEEL LINTEL INVERTED 'T' TYPE

SHOWN, OTHER STEEL LINTELS ALSO

ACCEPTABLE

6"

RAISED ACCESS FLOOR

2' - 8"

(E) HANDRAIL

(E) TRANSACTION

DRAWER, (N)

CUSTOM CASEWORK

BUILT TO FIT

(E) WALL1

1/

4"

2' - 6"

SS1

LT1

VIF

RAISED ACCESS FLOOR

2' - 8"

SS1

2'

LT1

(E)

TRANSACTION

DRAWER

VI

F

(E) WINDOW

(N) CUSTOM

CASEWORK BUILT TO

FIT

(E) CMU WALL

1/

2"

2' - 0"

VIF

3"21"

A

EXISTING CMU WALL.

INFILL WITH MORTAR

AS NECESSARY.

GLASS. REFER TO

WINDOW SCHEDULE.

VI

F

GLASS. REFER

TO WINDOW

SCHEDULE.

CONTINUOUS

BEAD OF SEALANT

AND BACKER ROD,

EACH SIDE, TYP.

CONTINUOUS BEAD OF

SEALANT AND BACKER

ROD, EACH SIDE, TYP.

SHIM AS NECESSARY

EXISTING

CMU WALL

EXTERIOR

EXTERIOR

CONTROL

ROOM

REMOVABLE 12 GA. 1-1/4"

ANGLE, STL. STOP,

SECURE TO FRAMES AS

SPECIFIED

1 1/4"0' - 2"

1/

2"

HM FRAME FILL SOLID

WITH RIGID INSUL.,

PAINT; TYP. REFER TO

WINDOW SCHEDULE

VIF

1/

4" 0'

2"

7 1/2"

CONTROL

ROOM

REMOVABLE 12 GA. 1-1/4"

ANGLE, STL. STOP,

SECURE TO FRAMES AS

SPECIFIED

B

HM FRAME FILL SOLID

WITH RIGID INSUL.,

PAINT; TYP. REFER TO

WINDOW SCHEDULE

SHIM AS NECESSARY

1/

4"

3 1/4"

GUARDRAIL, SEE

ARCHITECTURAL PLANS.

REFER TO MANUFACTURER

RECOMENDATIONS FOR

INSTALATION

Date:

Proj. No.:

D

SG

N D

R C

H K

AP

VD

AP

VD

BY

R

EV

IS

IO

N

D

AT

E N

O

PLOT DATE/TIME:

Drawing No.:

Pr oj ec t T itl e:

D ra w in g Ti tle

D

C

B

A

1 2 3 4 5 6

REUSE OF DOCUMENTS: THIS DOCUMENT, AND THE IDEAS AND DESIGNS INCORPORATED HEREIN, AS AN INSTRUMENT OF PROFESSIONAL SERVICE, IS THE PROPERTY OF JACOBS AND IS NOT TO BE USED, IN WHOLE OR IN PART, FOR ANY OTHER PROJECT WITHOUT THE WRITTEN AUTHORIZATION OF JACOBS.

www.Jacobs.com

Ja co bs

E ng in ee rin g

G ro up In c.

A

LL

R

IG

H

TS

R

ES

ER

V

ED

04/04/2024

4/4/2024 6:40:15 PM BIM 360://US_D3482000_OYA Control Room Upgrade/Oak_Creek_OYA-Control-Room-Upgrade-ARCH_marcin.krzysik.rvt

IS

SU

E

FO

R R

EV

IS

IO

N

D3482000

M K

/ J A

M K

/ J A

JB

JB

OYA-600

O R

EG

O

N Y

O U

TH

A

U

TH

O R

IT

Y

O

AK

C R

EE

K

FA

C

IL

IT

Y

OAK CREEK FACILITY

4400 LOCHNER RD SE

ALBANY, OR 97322

PORTLAND OFFICE

PORTLAND, OR 97201

2020 SW 4TH AVE, SUITE 300

AR

C

H

IT

EC

TU

R E

D

ET

AI

LS

/1 0/

IS

SU

E

FO

R C

O N

ST

R

U C

TI

O

N

/0

4/

IS

SU

E

FO

R

R E V

IS

IO

N

- 1 1/2" = 1'-0"

4 HM DOOR SILL @ CMU WALL SILL, TYP.

- 1/2" = 1'-0"

2 BREAK AREA CABINETS EAST VIEW

- 1/2" = 1'-0"

3 BREAK AREA CABINETS NORTH VIEW

- 1/2" = 1'-0"

5 CORNER CASEWORK FRONT VIEW

- 1/2" = 1'-0"

6 CORNER CASEWORK SIDE VIEW

- 1 1/2" = 1'-0"

1 HM DOOR DETAIL @ CMU WALL, TYP.

- 1/2" = 1'-0"

8 TRANSACTION DRAWER - FRONT VIEW

- 1/2" = 1'-0"

9 TRANSACTION DRAWER- SIDE VIEW

- 1 1/2" = 1'-0"

7 WINDOW JAMB & SILL, TYP.

- 1 1/2" = 1'-0"

10 GUARDRAIL CONNECTION @ AF EDGE, SIM.

AC

O

U

ST

IC

AL

C

EI

LI

N

G T

IL

E

G

R

ID

ACT 1

GRID

MANUFACTURER

MODEL

NUMBER / SIZE

COLOR

REMARKS

CLASSIFICATION

MANUFACTURER

STYLE NAME

NUMBER / SIZE

COLOR

AMSTRONG

CALLA

24" X 24"

BLACK

@ CONTROL ROOM

CLASS A

AMSTRONG

INTERLUDE XL

9/16"

BLACK

FL

O

O R

VCT1

AFP1

MANUFACTURER

MODEL

NUMBER / SIZE

COLOR

REMARKS

MANUFACTURER

MODEL

SIZE

TARKETT

12" X 12"

CORTINA GRANDE - BLACK & WHITE

@ RESTROOM / CONTROL ROOM

TATE

STONEWORKS DECORATIV CONCRETE

ACCESS FLOOR PANEL

24" X 24"

FINISH MIDNIGHT

R

ES

IL

IE

N T

BA

SE

RB1

MANUFACTURER

MODEL

NUMBER / SIZE

COLOR

REMARKS

NOTES

FLEXCO

4"

BLACK

@ RESTROOM / CONTROL ROOM

RUBBER, STRAIGHT

PA

IN

T

PT1

MANUFACTURER

FINISH

NUMBER

COLOR

NOTES

SHERWIN WILLIAMS

SNOWBOUND

@ CONTROL ROOM

EGGSHELL

SW 7004

PT2

MANUFACTURER

FINISH

NUMBER

COLOR

NOTES

SHERWIN WILLIAMS

SNOWBOUND

@ RESTROOM

SATIN

SW 7004

PT3

MANUFACTURER

FINISH

NUMBER

COLOR

NOTES

SHERWIN WILLIAMS

MATCH WITH EXISTING HM FRAMES

@ HM FRAMES

SEMI - GLOSS

TBD

SO

LI

D

SU

R

FA

C E

SS1

MANUFACTURER

FINISH

SIZE

NOTES

CORIAN

1 1/4"

@ COUNTERTOP

SPARKLING GRANITA

R

ES

IL

IE

N T

BA

SE

RB1

MANUFACTURER

MODEL

NUMBER / SIZE

COLOR

REMARKS

NOTES

FLEXCO

4"

BLACK

@ RESTROOM / CONTROL ROOM

RUBBER, STRAIGHT

W

IN

D O

W F

IL

M

WF1

MANUFACTURER

MODEL

NUMBER / SIZE

COLOR

NOTES

3M

@ CONTROL ROOM

PRIVACY FILM (ONE-WAY)

FI

N

IS

H

LT1

MANUFACTURER

MODEL

NUMBER / SIZE

COLOR

NOTES

FORMICA

@ CABINETS

FINISH OAK

1. VERIFY ALL EXISTING DOOR SIZES, DISCREPANCIES WITH SCHEDULE

SHOULD BE NOTED AND REVIEWED WITH ARCHITECT.

2. HARDWARE SCHEDULE HAS BEEN DEVELOPED FOR DESIGN INTENT ONLY.

HARDWARE PROVIDER IS RESPONSIBLE FOR VERIFYING THE FUNCTION AND

COMPATIBILITY OF ALL COMPONENTS.

3. UNLESS OTHERWISE NOTED, THE HEIGHT OF DOOR HARDWARE HANDSETS

ARE TO MATCH ADJACENT EXISTING HARDWARE.

4. DOOR HARDWARE TO BE COMPLETE IN ORDER TO FUNCTION AS

DESCRIBED IN THESE NOTES, SCHEDULES AND SPECIFICATIONS

5. PROVIDE ALL HARDWARE ACCESSORIES NOT LIMITED TO HINGES,

ASTRAGALS, BOLTS, AUTOMATIC BOLTS, FLUSH BOLTS, AUTOMATIC FLUSH

BOLTS, SMOKE SEALS, COORDINATORS, LOCK SETS, LATCHES, LEVERS

STRIKE PLATES, CLOSERS, KEYS CYLINDERS, STOPS, FLOOR AND WALL

STOPS, SILENCERS, BOTTOMS, SADDLES, TRIM, KICK PLATES, ETC. REFER

TO SPECIFICATIONS.

6. PROVIDE ELECTRIC CAPABILITY FOR DOOR CONTACTS, ACCESS CONTROL,

READERS, ELECTRIC HINGES AND ANY OTHER ELECTRIC REQUIREMENT TO

SATISFY THE FUNCTION OF THE DOORS AS DESCRIBED IN THESE NOTES,

SCHEDULES AND SPECIFICATIONS.

7. SECURITY INTEGRATOR TO INSTALL CARD READER HARDWARE. GC IS

RESPONSIBLE FOR COORDINATING AND INSTALLATION OF HARDWARE WITH

SECURITY AND ELECTRICAL REQUIREMENTS FOR DOORS. GC IS

RESPONSBILE FOR PROVIDING POWER & PATHWAYS AS NEEDED.

8. ALL DOORS AND FRAMES TO BE FACTORY PREPPED TO RECEIVE INTENDED

DOOR HARDWARE, RATED DOORS TO MAINTAIN FIRE RATING.

9. ARCHITECT IS NOT RESPONSIBLE FOR KEYING REQUIREMENTS. GC IS

RESPONSIBLE FOR PROCURING AND INSTALLING ALL CORES & LOCKSETS.

GC TO COORDINATE WITH OWNER'S PM AND BUILDING FACILITIES FOR

KEYING REQUIREMENTS.

10. LOCATION OF DOOR IS DETERMINED BY THE DOOR NUMBER, EXAMPLE:

101A (ROOM NUMBER- 101 DOOR- A).

11. SEE SPECIFICATION 08 34 60 DETENTION DOORS AND FRAMES, 08 71 00

DOOR HARDWARE, 08 80 00 GLAZING AND 08 51 00 METAL WINDOWS FOR

MORE INFORMATION.

WINDOW, DOOR & HARDWARE GENERAL NOTES:

ABS ABS PLASTIC

AL ALUMINIUM

(E) EXISTING

FGR FIRE RATED CERAMIC GLASS

FACT FACTORY FINISH

GL GLASS

HM HOLLOW METAL

MIN MINUTE

MATL MATERIAL

LSS LIFE SAFETY SYSTEM

NR NOT RATED

N/A NOT APPLICABLE

P PAINT

PT PAINTED FINISH

PR PAIR

(R) RELOCATED

SIM SIMILAR

STL STEEL

TEMP TEMPERED

SS STAINLESS STEEL

WD WOOD

WG WIRE GLASS

VN VENEER

DOOR SCHEDULE ABBREVIATIONS:

1. BY MANUFACTURER

2. PANIC HARDWARE

3. 90° SWING

4. 180° SWING

5. CARD READER

6. PROVIDE AUTOMATIC DOOR OPERATOR AND DOOR

ACTUATORS.

7. ELECTRIFIED HARDWARE FOR FUTURE USE.

8. CARD ACCESS CONTROLLED W/ADJACENT DOOR.

9. DOOR IS PART OF GLAZING ASSEMBLY. HARDWARE,

PULLS, AND HINGES PROVIDED BY GLASS VENDOR.

10. DOOR TYPE TO MATCH EXISTING.

11. FIRERATED 90 MIN.

DOOR SCHEDULE KEYNOTES:

STEEL FRAME TYPE

2" 2"

4"

SEE DOOR

SCHEDULE

SE

E

D O

O R

S C

H

ED

U

LE

STEEL DETENTION

FRAME, TYP.

REFER SPEC

08 34 60 FOR MORE

INFORMATION

WINDOW ELEVATION

DESCRIPTION:2 FIXED

SE

E

W

IN

D O

W S

C H

ED

U

LE

SEE WINDOW SCHEDULE

2"TYP.

1 3/8" SECURE-

TEM+POLY(SP035).

REFER TO SPEC 08 80 00

FOR MORE INFORMATION

STEEL DETENTION

FRAMES, TYP.

REFER TO WINDOW

SCHEDULE

OYA-600

Sim

OYA-600

Sim

STEEL FRAME TYPE

6" 2"

4"

SEE DOOR

SCHEDULE

SE

E

D O

O R

S C

H

ED

U

LE

STEEL DETENTION

FRAMES, TYP.

REFER SPEC

08 34 60 FOR

MORE

INFORMATION

1A

(2) 1/2 DIM. CONDUIT

FOR LOCK POWER

AND CONTROL; WELD

INTO FRAME, EXTEND

6" ABV. TOP OF

FRAME; SEE ELECT

STEEL DETENTION

DOOR, TYP.

REFER SPEC

08 34 60 FOR

MORE

INFORMATION

3/4 DIM. CONDUIT;

SEE ELECT FOR

MORE

INFORMATION

A B C

FLUSH PANEL FULL VISION LIGHT

PANEL

NARROW LIGHT

VISION PANEL -

TEMP. GLASS

/2

/2

8" 6 1/2"6" 6"

SE

E

D O

O R

S C

H

ED

U

LE

SEE DOOR SCHEDULE

SE

E

D O

O R

S C

H

ED

U

LE

SEE DOOR SCHEDULE

SE

E

D O

O R

S C

H

ED

U

LE

SEE DOOR SCHEDULE

6"

7"

4" x 25"

CLEAR

OPENING

.970" SECURE-

TEM+POLY(SP028). REFER

TO SPEC 08 80 00 FOR

MORE INFORMATION

Date:

Proj. No.:

D

SG

N D

R C

H K

AP

VD

AP

VD

BY

R

EV

IS

IO

N

D

AT

E N

O

PLOT DATE/TIME:

Drawing No.:

Pr oj ec t T itl e:

D ra w in g Ti tle

D

C

B

A

1 2 3 4 5 6

REUSE OF DOCUMENTS: THIS DOCUMENT, AND THE IDEAS AND DESIGNS INCORPORATED HEREIN, AS AN INSTRUMENT OF PROFESSIONAL SERVICE, IS THE PROPERTY OF JACOBS AND IS NOT TO BE USED, IN WHOLE OR IN PART, FOR ANY OTHER PROJECT WITHOUT THE WRITTEN AUTHORIZATION OF JACOBS.

www.Jacobs.com

Ja co bs

E ng in ee rin g

G ro up In c.

A

LL

R

IG

H

TS

R

ES

ER

V

ED

04/04/2024

4/4/2024 6:40:15 PM BIM 360://US_D3482000_OYA Control Room Upgrade/Oak_Creek_OYA-Control-Room-Upgrade-ARCH_marcin.krzysik.rvt

IS

SU

E

FO

R R

EV

IS

IO

N

D3482000

M K

/ J A

M K

/ J A

JB

JB

OYA-700

O R

EG

O

N Y

O U

TH

A

U

TH

O R

IT

Y

O

AK

C R

EE

K

FA

C

IL

IT

Y

OAK CREEK FACILITY

4400 LOCHNER RD SE

ALBANY, OR 97322

PORTLAND OFFICE

PORTLAND, OR 97201

2020 SW 4TH AVE, SUITE 300

AR

C

H

IT

EC

TU

R E

D O

O R

A N

D R

O O

M F

IN

IS

H

SC

H

ED

U

LE

S

FI

N

IS

H

L

EG

EN

D

/1 0/

IS

SU

E

FO

R C

O N

ST

R

U C

TI

O

N

/0

4/

IS

SU

E

FO

R

R E V

IS

IO

N

Level Number Name Area Floor Finish Base Finish North Wall - Finish East Wall - Finish South Wall - Finish West Wall - Finish Ceiling Finish

Level 1 101 CONTROL ROOM 297 SF AFP1 / VCT1 RB1 PT1 PT1 PT1 PT1 ACT1 Level 1 102 RESTROOM 33 SF VCT1 RB1 PT2 PT2 PT2 PT2 PT2

FINISH LEGEND ROOM FINISH SCHEDULE

Mark Room Name Width Height Door Type Door Finish Frame Type Head Detail Sill Detail Frame Finish Hardware Keynote

101A CONTROL ROOM 3' - 0" 7' - 0" C PT2 1 1/ OYA-600 4/ OYA-600 PT3 7, 11

101B CONTROL ROOM 3' - 0" 7' - 0" EXISTING PT2 EXISTING PT3 (E)

102A RESTROOM 3' - 0" 7' - 0" EXISTING PT2 EXISTING PT3 (E)

DOOR SCHEDULE

Mark Width Height Count Frame Type Glazing Thickness Glazing Type Sill Jamb Comments

01 3' - 8" 5' - 2" 1 2 1 3/8" SECUR-TEM + POLY 7/ OYA-600 7/ OYA-600 ONE WAY FILM AND MANUAL OPERATED HORIZONTAL BLINDS 01 3' - 8" 5' - 2" 1 2 1 3/8" SECUR-TEM + POLY 7/ OYA-600 7/ OYA-600 ONE WAY FILM AND MANUAL OPERATED HORIZONTAL BLINDS

WINDOW SCHEDULE

DOOR & WINDOW FRAME TYPE

DOOR TYPE

File details come from the government source that posted it. Updated .