Attachment 9 Drawing 08b_TELECOMMUNICATION.pdf

PDF 21 MB Posted

Attached to
Y1DA--610A4-21-701 EHRM Infrastructure Upgrades Construction Ft. Wayne Federal contract opportunity
Solicitation number
36C77622B0028
Issued by
Department of Veterans Affairs Technology Acquisition Center Austin

About this file

This document provides details for a federal solicitation from the Department of Veterans Affairs Technology Acquisition Center Austin. Solicitation number 36C77622B0028 is seeking proposals for infrastructure upgrades construction services at Fort Wayne to support the EHRM system. Offerors should provide pricing and plans for upgrading telecommunications and IT infrastructure as outlined in technical drawing Attachment 9 to modernize the facility's technology systems. Proposals are due by the date specified in the solicitation document. The award will be granted to a responsible offeror whose offer follows the terms of the solicitation and is determined most advantageous to the Government considering price and technical factors.

View the file

Other files for this federal contract opportunity

Other files attached to Y1DA--610A4-21-701 EHRM Infrastructure Upgrades Construction Ft. Wayne, newest first.
File Type Posted
Attachment 2 EHRM ICRA Form - Ft. Wayne.pdf PDF
Attachment 1 Technical Question Responses - Ft Wayne EHRM 20220722.pdf PDF
36C77622B0028 0008.pdf PDF
36C77622B0028 0007.pdf PDF
0006 Attachment 1 Technical Question Responses.pdf PDF
36C77622B0028 0006.pdf PDF
36C77622B0028 0005.pdf PDF
36C77622B0028 0004.pdf PDF
36C77622B0028 0003.pdf PDF
36C77622B0028 0002.pdf PDF
36C77622B0028 0001.pdf PDF
Attachment 15 CONTRACTOR SAFETY AND ENVIRONMENTAL RECORD EVALUATION FORM.docx DOCX document
Attachment 8 Drawing 08a_TELECOMMUNICATION.pdf PDF
Attachment 4 Drawing 04_ARCHITECTURAL_BID SET.pdf PDF
Attachment 1 Drawing 01_GENERAL_BID SET.pdf PDF
Attachment 12 610A4-21-701 Specifications Bound.pdf PDF
Attachment 3 Drawing 03_ENVIRONMENTAL.pdf PDF
Attachment 14 COVID-19 Safety Protocols 12-14-21.pdf PDF
36C77622B0028_1.docx DOCX document
Attachment 17 ELECTRICAL BID SET.pdf PDF
Attachment 16 Limitations on Subcontracting - Construction.docx DOCX document
Attachment 13 DBA Wage Determination - Ft Wayne 20220602.pdf PDF
Attachment 11 EHRM Ft Wayne Bid Documents Narrative.pdf PDF
Attachment 10 Drawing 09_SECURITY.pdf PDF
Attachment 7 Drawing 07_ELECTRICAL_BID SET.pdf PDF
Attachment 6 Drawing 06_MECHANICAL_BID SET.pdf PDF
Attachment 5 Drawing 05_FIRE PROTECTION_BID SET.pdf PDF
Attachment 2 Drawing 02_CIVIL_BID SET.pdf PDF
Show all 28

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

MECH

FAMILY

ROOM

VENDING

FAMILTY

TOILET

PUBLIC

TOILET

CORRIDOR

C4109

CORRIDOR

C4110

CORRIDOR

C4111

ELEVATOR

WAITING

BUILDING

SERVICES

4164A

ELEVATOR

UTILITY

CORRIDOR

C4302

MED/SURG

BARIATRIC

PHYSICAL

DISABILITIES

MED/SURG

BATH

4332A

ALCOVE

EQUIPMENT

STORAGE

ALCOVE

CORRIDOR

C4301

CORRIDOR

C4303

NURSE

MANAGER

OFFICE

ICU NURSE

MANAGER

OFFICE

SOCIAL

WORKER

DIETICIAN

NURSE

WORKROOM

NURSE

STATION

4317 4319

ELECTRICAL

TOILET

4331 BATH

4333A

STAIR 3-4

ST4.3

CLEAN

SUPPLY

MEDICATION

ROOM

SOILED

UTILITY/EQUIP

BATH

4353A

CORRIDOR

C4108

ELECTRICAL

BATH

4312A

BATH

4316A

CLEAN LINEN

H.A.C.

NOURISHMENT

BATH

4324A

CORRIDOR

C4304

ELEVATOR

MED/SURG

ALCOVE

STORAGE

MED/SURG

MED/SURG

BATH

4320A MED/SURG

MED/SURG

BATH

4326A

BATH

4346A

BATH

4348A

MED/SURG

4346 MED/SURG

BATH

4352A

PATIENT

ROOM

INTENSIVE

CARE

ISOLATION

NOURISHMENT

4356 UP

STAIR 4-4

ST4.4

CORRIDOR

C4305

ANTEROOM

PATIENT

TOILET

INTENSIVE

CARE

4364A

ANTEROOM

PATIENT

ROOM

INTENSIVE

ISOLATION

ICU

EQUIPMENT

STORAGE

CLEAN LINEN

ROOM

CLEAN

NURSE

STATION

SOILED LINEN

CLEAN

SUPPLY

4351 PATIENT

ROOM

INTENSIVE

CARE

MEDICATION

ROOM

NURSE

STATION

PATIENT

INTENSIVE

CARE

BATH

4365A

STAFF

LOUNGE

STAFF

TOILET

SUPPLY

ROOM

KITCHENETTE

STAFF

LOUNGE

4334B

INTER-DISCIPLINARY

ROOM

4334A

M

AT

C H

LI

N

E T1

-B

M

AT

C H

LI

N

E T1

-B

MATCHLINE

T-100-D

WAP

WAP

W

2 WAP

2 2 2

2 2

2 2

4 2

WAP

WAP

WAP

2 1 2 2

2 1 2

WAP

WAP 2

2 2

2 2

W

W

W W

WAP

W

4 2

W W2

WAP

W

T1

-A T1

-A

JH

JH

JH

JH

TR-4308

POWER PANELLENEL/ALTRONIX

LG

D

U A

L IN

V

ER

TER

A

C

(N ot e:

A ll W

AO

C ab le s in a re a T1

-A to b e ro ut ed to , a nd te rm in at ed in T

R -4

8)

(N ot e:

A ll W

AO

C ab le s in a re a T1

-A to b e ro ut ed to , a nd te rm in at ed in T

R -4

8)

(N ot e:

A ll W

AO

C ab le s in a re a T1

-B to b e ro ut ed to , a nd te rm in at ed in T

R -4

8)

(N ot e:

A ll W

AO

C ab le s in a re a T1

-B to b e ro ut ed to , a nd te rm in at ed in T

R -4

8)

2 2

2 4 2 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project NumberCONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. AR12100034 EXP. 12/31/2021

MECH ENGR REG. NO. PE12100220 EXP. 07/31/2022

ELEC ENGR REG. NO. PE12100195 EXP. 07/31/2022

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC / PLUMB / TECH ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(913) 369-7200

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

TELECOMMUNICATIONS

ASPEN ENGINEERING & CONTRACTING

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 85712

(928) 774-0992

PHYSCIAL SECURITY

FORCE PROTECT

3210 GULF BLVD, UNIT 304

BELLEAIR BEACH, FL 33786

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

BUILDING 1 - FOURTH FLOOR

TECHNOLOGY FLOOR PLAN - AREA B

BID DOCUMENTS

EHRM INFRASTRUCTURE

UPGRADES FORT WAYNE,

INDIANA

610A4-21-701

VANIHCS

T104B

No. REVISION DESCRIPTION DATE

SCALE: 1/8" = 1'0"

B1 - FORTH FLOOR LEVEL - TECHNOLOGY PLAN

N

11/12/2021 WAMAJS

2121 LAKE AVE,

FORT WAYNE, IN 46805

94 119

PROVIDE AND INSTALL 4"W x 4"D WIRE BASKET TYPE CABLE TRAY TO SUPPORT REDUNDANT FIBER OPTIC

BACKBONE 'A' CABLES. (SEE PLAN SHEET T-101 FOR MORE DETAILS)

PROVIDE AND INSTALL 4"W x 4"D WIRE BASKET TYPE CABLE TRAY TO SUPPORT REDUNDANT FIBER OPTIC

BACKBONE 'B' CABLES. (SEE PLAN SHEET T-101 FOR MORE DETAILS)

TECHNOLOGY KEYNOTES:

PROVIDE AND INSTALL 2"W x 2"D WIRE BASKET TYPE CABLE TRAY TO SUPPORT REDUNDANT FIBER OPTIC

BACKBONE 'A' CABLE. (SEE PLAN SHEET T-101 FOR MORE DETAILS)

PROVIDE AND INSTALL 2"W x 2"D WIRE BASKET TYPE CABLE TRAY TO SUPPORT REDUNDANT FIBER OPTIC

BACKBONE 'B' CABLE. (SEE PLAN SHEET T-101 FOR MORE DETAILS)

PROVIDE AND INSTALL 12"W x 4"D WIRE BASKET TYPE CABLE TRAY TO SUPPORT CATEGORY 6A UTP WORK AREA

OUTLET (WAO) STATION CABLES.

tiles and the floor above. If in the event that the cable tray cannot be installed , a J-Hook pathway shall be established to support the Category 6A station cables.

Note: Cable Tray Installation is contingent upon the amount of congestion evident in the space between the drop ceiling grid/

INTERSECTING CABLE TRAYS WILL BE SEPARATED VERTICALLY, SO AS TO AVOID CABLE ROUTING CONFLICTS

BETWEEN FIBER BACKBONE CABLES AND UTP STATION CABLES.

LEGEND:

VERTICAL PATHWAY FOR REDUNDANT-DIVERSE FIBER OPTIC BACKBONE 'A' CABLES. (SEE PLAN SHEET T-101

FOR MORE DETAILS)

VERTICAL PATHWAY FOR REDUNDANT-DIVERSE FIBER OPTIC BACKBONE 'B' CABLES. (SEE PLAN SHEET T-101

FOR MORE DETAILS)

W

WAP

WALL PHONE OUTLET CONTAINING (1) CATEGORY 6A UTP CABLE TERMINATED ONTO (1) CATEGORY 6A RJ-45 TYPE (8P-8C) JACK. UTP CABLE JACKET COLOR TO BE BLUE. TERMINATION SCHEME TO BE T568B.

(EXISTING WAO LOCATION TO BE INSTALLED IN PHASE 2)

WIRELESS ACCESS POINT CONTAINING (1) CATEGORY 6A UTP CABLE TERMINATED ONTO (1) CATEGORY 6A RJ-45 TYPE (8P-8C) JACK. UTP CABLE JACKET COLOR TO BE BLUE. TERMINATION SCHEME TO BE T568B

(EXISTING WAO LOCATION TO BE INSTALLED IN PHASE 2).

4-PORT WORK AREA OUTLET FACEPLATE CONTAINING (1) CATEGORY 6A UTP CABLE TERMINATED ONTO (1) CATEGORY 6A RJ-45 TYPE (8P-8C) JACK. UTP CABLE JACKET COLORE TO BE BLUE. TERMINATION SCHEME

TO BE T568B. (EXISTING WAO LOCATION TO BE INSTALLED IN PHASE 2)

4-PORT WORK AREA OUTLET FACEPLATE CONTAINING (2) CATEGORY 6A UTP CABLES TERMINATED ONTO (2) CATEGORY 6A RJ-45 TYPE (8P-8C) JACKS. UTP CABLE JACKET COLOR TO BE BLUE. TERMINATION SCHEME

TO BE T568B. (EXISTING WAO LOCATION TO BE INSTALLED IN PHASE 2)

4-PORT WORK AREA OUTLET FACEPLATE CONTAINING (4) CATEGORY 6A UTP CABLES TERMINATED ONTO (4) CATEGORY 6A RJ-45 TYPE (8P-8C) JACKS. UTP CABLE JACKET COLOR TO BE BLUE. TERMINATION SCHEME

TO BE T568B. (EXISTING WAO LOCATION TO BE INSTALLED IN PHASE 2)

PROVIDE AND INSTALL 18"W x 4"D WIRE BASKET TYPE CABLE TRAY TO SUPPORT CATEGORY 6A UTP WORK AREA

OUTLET (WAO) STATION CABLES.

PROVIDE AND INSTALL J-HOOK PATHWAYS TO SUPPORT CATEGORY 6A STATION CABLES FROM WAO TO MAIN CABLE TRAY OR MAIN J-HOOK PATHWAY BACK TO THE ASSOCIATED TR (TYPICAL). INSTALL AT 5' (MAXIMUM) .

INTERVALS O.C. (NOTE: J-HOOK PATHWAYS DEPICTED ARE JUST A FEW EXAMPLES. ALL STATION CABLING MUST BE SUPPORTED BY J-HOOK PATHWAYS THAT ARE PARALLEL AND PERPENDICULAR TO BUILDING LINES.)

= 4-PORT WORK AREA OUTLET FACEPLATE CONTAINING (2) CATEGORY 6A UTP CABLES TERMINATED ONTO (2)

CATEGORY 6A RJ-45 TYPE (8P-8C) JACKS. UTP CABLE JACKET COLOR TO BE BLUE. TERMINATION SCHEME

TO BE T568B. (NEW WAO LOCATION TO BE INSTALLED IN PHASE 1)

4-PORT WORK AREA OUTLET FACEPLATE CONTAINING (4) CATEGORY 6A UTP CABLES TERMINATED ONTO (4) CATEGORY 6A RJ-45 TYPE (8P-8C) JACKS. UTP CABLE JACKET COLOR TO BE BLUE. TERMINATION SCHEME

TO BE T568B. (NEW WAO LOCATION TO BE INSTALLED IN PHASE 1)

X

X = PHASE 1 - THESE NEW WORK AREA OUTLET LOCATIONS (NWAO's) ARE TO BE INSTALLED IN PHASE 1.

= PHASE 2 - THESE EXISTING WORK AREA OUTLET LOCATIONS (EWAO's) ARE TO BE INSTALLED IN PHASE 2.

ALL CATEGORY 6A STATION CABLING SHALL BE SUPPORTED USING A COMBINATION OF J-HOOKS AND CABLE TRAYS

(IF POSSIBLE) IN GENERAL PATHWAYS.

ENSURE THAT ALL GROUNDING AND BONDING IS COMPLETE. TWO SCREW BONDING LUGS NEED TO BE INSTALLED TO BOND ALL METALLIC COMPONENTS OF THE RACK AND CABLE TRAY SYSTEM, TO THE TELECOMMUNICATIONS

SECONDARY BONDING BUSBAR.

AFTER CUT-OVER TO THE NEW CABLING, DEMOLISH ALL OLD DATA AND TELEPHONE CABLING ALL THE WAY TO THE STATION END. ENSURE THAT ANY CABLES IN THE CEILING AREAS THAT ARE FOR SYSTEMS OTHER THAN THE IT DATA AND TELEPHONE, ARE NOT DISTURBED. BLANK OFF ANY UNUSED OLD DATA LOCATIONS. DEMOLISH ALL OLD PATCH PANELS AND ASSOCIATED HARDWARE. ALL OTHER ANCILLARY RACK-MOUNTED EQUIPMENT, NOT RELATED TO IT DATA AND TELEPHONE, TO BE RELOCATED TO A NEW RACK BY OIT PERSONNEL. FIRE-STOP ALL EXISTING SLEEVES

WHERE CABLING WAS REMOVED.

AFTER CUT-OVER, REMOVE ALL OLD IT FIBER OPTIC CABLING FROM THE TR ALL THE WAY BACK TO THE SERVER ROOM. DEMOLISH ALL ASSOCIATED HARDWARE AND TERMINATION EQUIPMENT. ENSURE THAT ANY CABLING IN THE

CEILING AREA THAT IS FOR OTHER SYSTEMS, IS NOT DISTURBED.

A.

B.

C.

D.

E.

F.

G.

H.

CONTRACTOR SHALL INCLUDE AN ADDITIONAL 10% OF CABLE DROPS IN THEIR BID FOR ADDS FOUND DURING

ADDITIONAL PATCH PANEL CAPACITY SHALL BE PROVIDED TO ACCOUNT FOR 15% GROWTH OF ADDITIONAL CABLE

DROPS.

ALL EXISTING DATA CABLES AND CIRCUITS MUST REMAIN IN PLACE AND OPERATIONAL UNTIL FINAL CUT-OVER TO

THE NEW CABLING.

EACH NEW WORK AREA OUTLET (WAO) LOCATION WILL CONSIST OF TWO OR FOUR CAT6A CABLES AS SHOWN ON THE PLANS. EACH CABLE WILL BE TERMINATED ON A 48-PORT CAT6A PATCH PANEL IN IT'S DESIGNATED TR.

EXISTING WAO LOCATIONS SHALL BE RE-USED WHEREVER POSSIBLE.

LABEL FIBER CABLE GOING INTO EACH FIBER PATCH PANEL. ALL FIBER STRANDS WILL BE TESTED UTILIZING AN

OLTS AND AN OTDR PER THE TIER 2 STANDARD.

PROVIDE (1) EACH SMALL DIAMETER CAT6A PATCH CORD FOR EACH NEW DATA PORT. PROVIDE VARIOUS LENGTHS AS REQUIRED FOR A NEAT AND ORDERLY INSTALLATION, UTILIZING THE VERTICAL AND HORIZONTAL WIRE

MANAGERS AS APPLICABLE. (SEE SPECIFICATIONS)

NEW FIRE-RATED SLEEVES SHALL BE INSTALLED EXITING THE TR AND IN ALL FIRE-RATED WALLS ALONG THE CABLE

PATHWAYS.

I. EXISTING CONDUITS TO REMAIN.

J. EXISTING DATA RACK/RACKS TO REMAIN UNTIL AFTER CUT-OVER.

K.

L.

M.

N.

PHASE 1 - INSTALL APPROXIMATELY (42) NEW CATEGORY 6A DATA CABLES ON THE FOURTH FLOOR LEVEL TO A

MIXTURE OF (19) SINGLE, DUAL & QUAD NEW WORK AREA OUTLET LOCATIONS.

O.

INSTALLATION..

GENERAL NOTES:

NOTE: THE FORTH FLOOR WAS RECENTLY REMODELED. BID SET DRAWINGS (dated 4//27/2016) DEPICTING VOICE & DATA WORK AREA OUTLET (WAO's), ALONG WITH A NEW CABLE TRAY RUNNING EAST TO WEST DOWN THE MAIN HALLWAY, WERE PROVIDED. AS A RESULT, IT WAS DECIDED THAT AN AUDIT WOULD NOT BE NECESSARY FOR THE

FOURTH FLOOR, AND SO, THE NEW CABLE TRAY IS NOT DEPICTED ON THESE DRAWINGS.

PHASE 2 - INSTALL APPROXIMATELY (426) NEW CATEGORY 6A DATA CABLES ON THE FOURTH FLOOR LEVEL TO A

MIXTURE OF (229) SINGLE, DUAL & QUAD EXISTING WORK AREA OUTLET LOCATIONS.

P.

Willam A. McClendon - 11/12/2021

CONFERENCE

OFFICE

CLOSET

551A

STORAGE

TOILET

TOILET

ELEVATOR

MED

515D1

MENS

OFFICE

515E

UP

STAIR

5-1

MED

515D

EXAM

515C

EXAM

515B

EXAM

515A

TOILET

NURSE

STATION

WOMENS

TOILET

WAITING

OFFICE

510A

OFFICE

510B

OFFICE

CLEAN

UTILITY

STORAGE

507C

VESTIBULE

OFFICE

507A

PAIN

OFFICE

507B

MANAGEMENT

SOILED

UTILITY

ELEC

UP

ELEVATOR

STORAGE

VESTIBULE

ELEVATOR

H.A.C.

STORAGE

OFFICE

546A

OFFICE

546B 545

EXAM

OFFICE

DATA

549A

STORAGE

540 CLOSET

539A

CLEAN

SUPPLY

BATH

543A

PYXIS

CLASSROOM

MECH

SOILED

UTILITY

515F

LOCKERS

LAB

OFFICE

OFFICE

BATH

521A

EXAM

EXAM

520A

EXAM

520B OFFICE

STAIR

5-2 OFFICE

SOILED

UTILITY

EXAM

EXAM

525A

EXAM

EXAM

526A

OFFICE

WAITING

CHECK-IN

COLLAB

EXAM

EXAM

EXAM

SOILED

UTILITY

EXAM

BATH

537A

STAIR

5-3 OFFICE

EXAM

MECH

TR-528C

LEN

EL/A

LTR

O

N

IX

LG DUAL INVERTER AC

PO

W

ER

PA

N

EL

ISP FIBER OPTIC BACKBONE KEYNOTES:

PROVIDE AND INSTALL 4"W x 4"D WIRE BASKET TYPE

CABLE TRAY.

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project NumberCONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. AR12100034 EXP. 12/31/2021

MECH ENGR REG. NO. PE12100220 EXP. 07/31/2022

ELEC ENGR REG. NO. PE12100195 EXP. 07/31/2022

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC / PLUMB / TECH ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(913) 369-7200

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

TELECOMMUNICATIONS

ASPEN ENGINEERING & CONTRACTING

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 85712

(928) 774-0992

PHYSCIAL SECURITY

FORCE PROTECT

3210 GULF BLVD, UNIT 304

BELLEAIR BEACH, FL 33786

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

BUILDING 1 - FIFTH FLOOR

TECHNOLOGY FLOOR PLAN

BID DOCUMENTS

EHRM INFRASTRUCTURE

UPGRADES FORT WAYNE,

INDIANA

610A4-21-701

VANIHCS

T-105

No. REVISION DESCRIPTION DATE

NOT TO SCALE (NTS)

B1 - FIFTH FLOOR - TECHNOLOGY PLAN

PROVIDE AND INSTALL 2"W x 2"D WIRE BASKET TYPE

CABLE TRAY.

PROVIDE AND INSTALL (1) EACH 12-STRAND SINGLEMODE (OS2)/

24-STRAND MULTIMODE (OM4) HYBRID, ARMORED, FIBER OPTIC

CABLE, WITH A GREEN JACKET, FOR ISP PATHWAY "A"

REDUNDANT HOMERUN TO TR-528C.

PROVIDE AND INSTALL (1) EACH 12-STRAND SINGLEMODE (OS2)/

24-STRAND MULTIMODE (OM4) HYBRID, ARMORED, FIBER OPTIC

CABLE, WITH A GREEN JACKET, FOR ISP PATHWAY "B"

REDUNDANT HOMERUN TO TR-528C.

N

11/12/2021 WAMAJS

2121 LAKE AVE,

FORT WAYNE, IN 46805

11995Willam A. McClendon - 11/12/2021 96 OF 120

CONFERENCE

OFFICE

CLOSET

551A

STORAGE

TOILET

TOILET

ELEVATOR

MED

515D1

MENS

OFFICE

515E

UP

STAIR

5-1

MED

515D

EXAM

515C

EXAM

515B

EXAM

515A

TOILET

NURSE

STATION

WOMENS

TOILET

WAITING

OFFICE

510A

OFFICE

510B

OFFICE

CLEAN

UTILITY

STORAGE

507C

VESTIBULE

OFFICE

507A

PAIN

OFFICE

507B

MANAGEMENT

SOILED

UTILITY

ELEC

UP

ELEVATOR

ELEVATOR

MECH

SOILED

UTILITY

515F

LOCKERS

LAB

OFFICE

OFFICE

BATH

521A

EXAM

EXAM

520A

EXAM

520B OFFICE

STAIR

5-2 OFFICE

SOILED

UTILITY

EXAM

EXAM

525A

EXAM

EXAM

526A

OFFICE

WAITING

CHECK-IN

MECH

2 2 2

2 4 2 2

2 2

2 2 2

2 2 2

2 2

M

AT

C H

LI

N

E T1

-B

M

AT

C H

LI

N

E T1

-B

T1

-A T1

-A

JH

JH

JH

TR-528C

LEN

EL/A

LTR

O

N

IX

LG DUAL INVERTER AC

PO

W

ER

PA

N

EL

(N ot e:

A ll W

AO

C ab le s in a re a T1

-A to b e ro ut ed to , a nd te rm in at ed in T

R -5

C

(N ot e:

A ll

W

AO

C ab le s in a re a

T1

-A to b e ro ut ed to

, a nd te rm in at ed in

T R

-5

C

(N ot e:

A ll W

AO

C ab le s in a re a T1

-B to b e ro ut ed to , a nd te rm in at ed in T

R -5

C

(N ot e:

A ll W

AO

C ab le s in a re a T1

-B to b e ro ut ed to , a nd te rm in at ed in T

R -5

C th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project NumberCONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. AR12100034 EXP. 12/31/2021

MECH ENGR REG. NO. PE12100220 EXP. 07/31/2022

ELEC ENGR REG. NO. PE12100195 EXP. 07/31/2022

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC / PLUMB / TECH ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(913) 369-7200

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

TELECOMMUNICATIONS

ASPEN ENGINEERING & CONTRACTING

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 85712

(928) 774-0992

PHYSCIAL SECURITY

FORCE PROTECT

3210 GULF BLVD, UNIT 304

BELLEAIR BEACH, FL 33786

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

BUILDING 1 - FIFTH FLOOR

TECHNOLOGY FLOOR PLAN - AREA A

BID DOCUMENTS

EHRM INFRASTRUCTURE

UPGRADES FORT WAYNE,

INDIANA

610A4-21-701

VANIHCS

T105A

No. REVISION DESCRIPTION DATE

SCALE: 1/8" = 1'0"

B1 - FIFTH FLOOR - TECHNOLOGY PLAN

N

11/12/2021 WAMAJS

2121 LAKE AVE,

FORT WAYNE, IN 46805

96 119

PROVIDE AND INSTALL 4"W x 4"D WIRE BASKET TYPE CABLE TRAY TO SUPPORT REDUNDANT FIBER OPTIC

BACKBONE 'A' CABLES. (SEE PLAN SHEET T-101 FOR MORE DETAILS)

PROVIDE AND INSTALL 4"W x 4"D WIRE BASKET TYPE CABLE TRAY TO SUPPORT REDUNDANT FIBER OPTIC

BACKBONE 'B' CABLES. (SEE PLAN SHEET T-101 FOR MORE DETAILS)

TECHNOLOGY KEYNOTES:

PROVIDE AND INSTALL 2"W x 2"D WIRE BASKET TYPE CABLE TRAY TO SUPPORT REDUNDANT FIBER OPTIC

BACKBONE 'A' CABLE. (SEE PLAN SHEET T-101 FOR MORE DETAILS)

PROVIDE AND INSTALL 2"W x 2"D WIRE BASKET TYPE CABLE TRAY TO SUPPORT REDUNDANT FIBER OPTIC

BACKBONE 'B' CABLE. (SEE PLAN SHEET T-101 FOR MORE DETAILS)

PROVIDE AND INSTALL 12"W x 4"D WIRE BASKET TYPE CABLE TRAY TO SUPPORT CATEGORY 6A UTP WORK AREA

OUTLET (WAO) STATION CABLES.

tiles and the floor above. If in the event that the cable tray cannot be installed , a J-Hook pathway shall be established to support the Category 6A station cables.

Note: Cable Tray Installation is contingent upon the amount of congestion evident in the space between the drop ceiling grid/

INTERSECTING CABLE TRAYS WILL BE SEPARATED VERTICALLY, SO AS TO AVOID CABLE ROUTING CONFLICTS

BETWEEN FIBER BACKBONE CABLES AND UTP STATION CABLES.

LEGEND:

VERTICAL PATHWAY FOR REDUNDANT-DIVERSE FIBER OPTIC BACKBONE 'A' CABLES. (SEE PLAN SHEET T-101

FOR MORE DETAILS)

VERTICAL PATHWAY FOR REDUNDANT-DIVERSE FIBER OPTIC BACKBONE 'B' CABLES. (SEE PLAN SHEET T-101

FOR MORE DETAILS)

ALL CATEGORY 6A STATION CABLING SHALL BE SUPPORTED USING A COMBINATION OF J-HOOKS AND CABLE TRAYS

(IF POSSIBLE) IN GENERAL PATHWAYS.

ENSURE THAT ALL GROUNDING AND BONDING IS COMPLETE. TWO SCREW BONDING LUGS NEED TO BE INSTALLED TO BOND ALL METALLIC COMPONENTS OF THE RACK AND CABLE TRAY SYSTEM, TO THE TELECOMMUNICATIONS

SECONDARY BONDING BUSBAR.

AFTER CUT-OVER TO THE NEW CABLING, DEMOLISH ALL OLD DATA AND TELEPHONE CABLING ALL THE WAY TO THE STATION END. ENSURE THAT ANY CABLES IN THE CEILING AREAS THAT ARE FOR SYSTEMS OTHER THAN THE IT DATA AND TELEPHONE, ARE NOT DISTURBED. BLANK OFF ANY UNUSED OLD DATA LOCATIONS. DEMOLISH ALL OLD PATCH PANELS AND ASSOCIATED HARDWARE. ALL OTHER ANCILLARY RACK-MOUNTED EQUIPMENT, NOT RELATED TO IT DATA AND TELEPHONE, TO BE RELOCATED TO A NEW RACK BY OIT PERSONNEL. FIRE-STOP ALL EXISTING SLEEVES

WHERE CABLING WAS REMOVED.

AFTER CUT-OVER, REMOVE ALL OLD IT FIBER OPTIC CABLING FROM THE TR ALL THE WAY BACK TO THE SERVER ROOM. DEMOLISH ALL ASSOCIATED HARDWARE AND TERMINATION EQUIPMENT. ENSURE THAT ANY CABLING IN THE

CEILING AREA THAT IS FOR OTHER SYSTEMS, IS NOT DISTURBED.

A.

B.

C.

D.

E.

F.

G.

H.

CONTRACTOR SHALL INCLUDE AN ADDITIONAL 10% OF CABLE DROPS IN THEIR BID FOR ADDS FOUND DURING

ADDITIONAL PATCH PANEL CAPACITY SHALL BE PROVIDED TO ACCOUNT FOR 15% GROWTH OF ADDITIONAL CABLE

DROPS.

ALL EXISTING DATA CABLES AND CIRCUITS MUST REMAIN IN PLACE AND OPERATIONAL UNTIL FINAL CUT-OVER TO

THE NEW CABLING.

EACH NEW WORK AREA OUTLET (WAO) LOCATION WILL CONSIST OF TWO OR FOUR CAT6A CABLES AS SHOWN ON THE PLANS. EACH CABLE WILL BE TERMINATED ON A 48-PORT CAT6A PATCH PANEL IN IT'S DESIGNATED TR.

EXISTING WAO LOCATIONS SHALL BE RE-USED WHEREVER POSSIBLE.

LABEL FIBER CABLE GOING INTO EACH FIBER PATCH PANEL. ALL FIBER STRANDS WILL BE TESTED UTILIZING AN

OLTS AND AN OTDR PER THE TIER 2 STANDARD.

PROVIDE (1) EACH SMALL DIAMETER CAT6A PATCH CORD FOR EACH NEW DATA PORT. PROVIDE VARIOUS LENGTHS AS REQUIRED FOR A NEAT AND ORDERLY INSTALLATION, UTILIZING THE VERTICAL AND HORIZONTAL WIRE

MANAGERS AS APPLICABLE. (SEE SPECIFICATIONS)

NEW FIRE-RATED SLEEVES SHALL BE INSTALLED EXITING THE TR AND IN ALL FIRE-RATED WALLS ALONG THE CABLE

PATHWAYS.

I. EXISTING CONDUITS TO REMAIN.

J. EXISTING DATA RACK/RACKS TO REMAIN UNTIL AFTER CUT-OVER.

K.

L.

M.

N.

PHASE 1 - INSTALL APPROXIMATELY (34) NEW CATEGORY 6A DATA CABLES ON THE FIFTH FLOOR LEVEL TO A MIXTURE

OF (14) DUAL AND QUAD NEW WORK AREA OUTLET LOCATIONS.

O.

W

WAP

WALL PHONE OUTLET CONTAINING (1) CATEGORY 6A UTP CABLE TERMINATED ONTO (1) CATEGORY 6A RJ-45 TYPE (8P-8C) JACK. UTP CABLE JACKET COLOR TO BE BLUE. TERMINATION SCHEME TO BE T568B.

(EXISTING WAO LOCATION TO BE INSTALLED IN PHASE 2)

WIRELESS ACCESS POINT CONTAINING (1) CATEGORY 6A UTP CABLE TERMINATED ONTO (1) CATEGORY 6A RJ-45 TYPE (8P-8C) JACK. UTP CABLE JACKET COLOR TO BE BLUE. TERMINATION SCHEME TO BE T568B

(EXISTING WAO LOCATION TO BE INSTALLED IN PHASE 2).

INSTALLATION..

4-PORT WORK AREA OUTLET FACEPLATE CONTAINING (1) CATEGORY 6A UTP CABLE TERMINATED ONTO (1) CATEGORY 6A RJ-45 TYPE (8P-8C) JACK. UTP CABLE JACKET COLORE TO BE BLUE. TERMINATION SCHEME

TO BE T568B. (EXISTING WAO LOCATION TO BE INSTALLED IN PHASE 2)

4-PORT WORK AREA OUTLET FACEPLATE CONTAINING (2) CATEGORY 6A UTP CABLES TERMINATED ONTO (2) CATEGORY 6A RJ-45 TYPE (8P-8C) JACKS. UTP CABLE JACKET COLOR TO BE BLUE. TERMINATION SCHEME

TO BE T568B. (EXISTING WAO LOCATION TO BE INSTALLED IN PHASE 2)

4-PORT WORK AREA OUTLET FACEPLATE CONTAINING (4) CATEGORY 6A UTP CABLES TERMINATED ONTO (4) CATEGORY 6A RJ-45 TYPE (8P-8C) JACKS. UTP CABLE JACKET COLOR TO BE BLUE. TERMINATION SCHEME

TO BE T568B. (EXISTING WAO LOCATION TO BE INSTALLED IN PHASE 2)

GENERAL NOTES:

PROVIDE AND INSTALL 18"W x 4"D WIRE BASKET TYPE CABLE TRAY TO SUPPORT CATEGORY 6A UTP WORK AREA

OUTLET (WAO) STATION CABLES.

PROVIDE AND INSTALL J-HOOK PATHWAYS TO SUPPORT CATEGORY 6A STATION CABLES FROM WAO TO MAIN CABLE TRAY OR MAIN J-HOOK PATHWAY BACK TO THE ASSOCIATED TR (TYPICAL). INSTALL AT 5' (MAXIMUM) .

INTERVALS O.C. (NOTE: J-HOOK PATHWAYS DEPICTED ARE JUST A FEW EXAMPLES. ALL STATION CABLING MUST BE SUPPORTED BY J-HOOK PATHWAYS THAT ARE PARALLEL AND PERPENDICULAR TO BUILDING LINES.)

= 4-PORT WORK AREA OUTLET FACEPLATE CONTAINING (2) CATEGORY 6A UTP CABLES TERMINATED ONTO (2)

CATEGORY 6A RJ-45 TYPE (8P-8C) JACKS. UTP CABLE JACKET COLOR TO BE BLUE. TERMINATION SCHEME

TO BE T568B. (NEW WAO LOCATION TO BE INSTALLED IN PHASE 1)

4-PORT WORK AREA OUTLET FACEPLATE CONTAINING (4) CATEGORY 6A UTP CABLES TERMINATED ONTO (4) CATEGORY 6A RJ-45 TYPE (8P-8C) JACKS. UTP CABLE JACKET COLOR TO BE BLUE. TERMINATION SCHEME

TO BE T568B. (NEW WAO LOCATION TO BE INSTALLED IN PHASE 1)

X

X = PHASE 1 - THESE NEW WORK AREA OUTLET LOCATIONS (NWAO's) ARE TO BE INSTALLED IN PHASE 1.

= PHASE 2 - THESE EXISTING WORK AREA OUTLET LOCATIONS (EWAO's) ARE TO BE INSTALLED IN PHASE 2.

PHASE 2 - INSTALL APPROXIMATELY (170) NEW CATEGORY 6A DATA CABLES ON THE FIFTH FLOOR LEVEL TO A MIXTURE

OF (80) DUAL AND QUAD EXISTING WORK AREA OUTLET LOCATIONS.

P.

Willam A. McClendon - 11/12/2021

OFFICE

CLOSET

551A

TOILET

TOILET

ELEVATOR

ELEC

UP

ELEVATOR

STORAGE

VESTIBULE

ELEVATOR

H.A.C.

STORAGE

OFFICE

546A

OFFICE

546B 545

EXAM

OFFICE

DATA

549A

STORAGE

540 CLOSET

539A

CLEAN

SUPPLY

BATH

543A

PYXIS

CLASSROOM

WAITING

CHECK-IN

COLLAB

EXAM

EXAM

EXAM

SOILED

UTILITY

EXAM

BATH

537A

STAIR

5-3 OFFICE

EXAM

2 2

2 24

M

AT

C H

LI

N

E T1

-B

M

AT

C H

LI

N

E T1

-B

T1

-A T1

-A

JHJH JH JH JH

JH

JH

JH

JH

JH

LEN

EL/A

LTR

O

N

IX

LG DUAL INVERTER AC

PO

W

ER

PA

N

EL

(N ot e:

A ll W

AO

C ab le s in a re a T1

-A to b e ro ut ed to , a nd te rm in at ed in T

R -5

C

(N ot e:

A ll

W

AO

C ab le s in a re a

T1

-A to b e ro ut ed to

, a nd te rm in at ed in

T R

-5

C

(N ot e:

A ll W

AO

C ab le s in a re a T1

-B to b e ro ut ed to , a nd te rm in at ed in T

R -5

C

(N ot e:

A ll W

AO

C ab le s in a re a T1

-B to b e ro ut ed to , a nd te rm in at ed in T

R -5

C

2 2 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project NumberCONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. AR12100034 EXP. 12/31/2021

MECH ENGR REG. NO. PE12100220 EXP. 07/31/2022

ELEC ENGR REG. NO. PE12100195 EXP. 07/31/2022

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC / PLUMB / TECH ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(913) 369-7200

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

TELECOMMUNICATIONS

ASPEN ENGINEERING & CONTRACTING

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 85712

(928) 774-0992

PHYSCIAL SECURITY

FORCE PROTECT

3210 GULF BLVD, UNIT 304

BELLEAIR BEACH, FL 33786

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

BUILDING 1 - FIFTH FLOOR

TECHNOLOGY FLOOR PLAN - AREA B

BID DOCUMENTS

EHRM INFRASTRUCTURE

UPGRADES FORT WAYNE,

INDIANA

610A4-21-701

VANIHCS

T105B

No. REVISION DESCRIPTION DATE

SCALE: 1/8" = 1'0"

B1 - FIFTH FLOOR - TECHNOLOGY PLAN

N

11/12/2021 WAMAJS

2121 LAKE AVE,

FORT WAYNE, IN 46805

97 119

PROVIDE AND INSTALL 4"W x 4"D WIRE BASKET TYPE CABLE TRAY TO SUPPORT REDUNDANT FIBER OPTIC

BACKBONE 'A' CABLES. (SEE PLAN SHEET T-101 FOR MORE DETAILS)

PROVIDE AND INSTALL 4"W x 4"D WIRE BASKET TYPE CABLE TRAY TO SUPPORT REDUNDANT FIBER OPTIC

BACKBONE 'B' CABLES. (SEE PLAN SHEET T-101 FOR MORE DETAILS)

TECHNOLOGY KEYNOTES:

PROVIDE AND INSTALL 2"W x 2"D WIRE BASKET TYPE CABLE TRAY TO SUPPORT REDUNDANT FIBER OPTIC

BACKBONE 'A' CABLE. (SEE PLAN SHEET T-101 FOR MORE DETAILS)

PROVIDE AND INSTALL 2"W x 2"D WIRE BASKET TYPE CABLE TRAY TO SUPPORT REDUNDANT FIBER OPTIC

BACKBONE 'B' CABLE. (SEE PLAN SHEET T-101 FOR MORE DETAILS)

PROVIDE AND INSTALL 12"W x 4"D WIRE BASKET TYPE CABLE TRAY TO SUPPORT CATEGORY 6A UTP WORK AREA

OUTLET (WAO) STATION CABLES.

tiles and the floor above. If in the event that the cable tray cannot be installed , a J-Hook pathway shall be established to support the Category 6A station cables.

Note: Cable Tray Installation is contingent upon the amount of congestion evident in the space between the drop ceiling grid/

INTERSECTING CABLE TRAYS WILL BE SEPARATED VERTICALLY, SO AS TO AVOID CABLE ROUTING CONFLICTS

BETWEEN FIBER BACKBONE CABLES AND UTP STATION CABLES.

LEGEND:

VERTICAL PATHWAY FOR REDUNDANT-DIVERSE FIBER OPTIC BACKBONE 'A' CABLES. (SEE PLAN SHEET T-101

FOR MORE DETAILS)

VERTICAL PATHWAY FOR REDUNDANT-DIVERSE FIBER OPTIC BACKBONE 'B' CABLES. (SEE PLAN SHEET T-101

FOR MORE DETAILS)

ALL CATEGORY 6A STATION CABLING SHALL BE SUPPORTED USING A COMBINATION OF J-HOOKS AND CABLE TRAYS

(IF POSSIBLE) IN GENERAL PATHWAYS.

ENSURE THAT ALL GROUNDING AND BONDING IS COMPLETE. TWO SCREW BONDING LUGS NEED TO BE INSTALLED TO BOND ALL METALLIC COMPONENTS OF THE RACK AND CABLE TRAY SYSTEM, TO THE TELECOMMUNICATIONS

SECONDARY BONDING BUSBAR.

AFTER CUT-OVER TO THE NEW CABLING, DEMOLISH ALL OLD DATA AND TELEPHONE CABLING ALL THE WAY TO THE STATION END. ENSURE THAT ANY CABLES IN THE CEILING AREAS THAT ARE FOR SYSTEMS OTHER THAN THE IT DATA AND TELEPHONE, ARE NOT DISTURBED. BLANK OFF ANY UNUSED OLD DATA LOCATIONS. DEMOLISH ALL OLD PATCH PANELS AND ASSOCIATED HARDWARE. ALL OTHER ANCILLARY RACK-MOUNTED EQUIPMENT, NOT RELATED TO IT DATA AND TELEPHONE, TO BE RELOCATED TO A NEW RACK BY OIT PERSONNEL. FIRE-STOP ALL EXISTING SLEEVES

WHERE CABLING WAS REMOVED.

AFTER CUT-OVER, REMOVE ALL OLD IT FIBER OPTIC CABLING FROM THE TR ALL THE WAY BACK TO THE SERVER ROOM. DEMOLISH ALL ASSOCIATED HARDWARE AND TERMINATION EQUIPMENT. ENSURE THAT ANY CABLING IN THE

CEILING AREA THAT IS FOR OTHER SYSTEMS, IS NOT DISTURBED.

A.

B.

C.

D.

E.

F.

G.

H.

CONTRACTOR SHALL INCLUDE AN ADDITIONAL 10% OF CABLE DROPS IN THEIR BID FOR ADDS FOUND DURING

ADDITIONAL PATCH PANEL CAPACITY SHALL BE PROVIDED TO ACCOUNT FOR 15% GROWTH OF ADDITIONAL CABLE

DROPS.

ALL EXISTING DATA CABLES AND CIRCUITS MUST REMAIN IN PLACE AND OPERATIONAL UNTIL FINAL CUT-OVER TO

THE NEW CABLING.

EACH NEW WORK AREA OUTLET (WAO) LOCATION WILL CONSIST OF TWO OR FOUR CAT6A CABLES AS SHOWN ON THE PLANS. EACH CABLE WILL BE TERMINATED ON A 48-PORT CAT6A PATCH PANEL IN IT'S DESIGNATED TR.

EXISTING WAO LOCATIONS SHALL BE RE-USED WHEREVER POSSIBLE.

LABEL FIBER CABLE GOING INTO EACH FIBER PATCH PANEL. ALL FIBER STRANDS WILL BE TESTED UTILIZING AN

OLTS AND AN OTDR PER THE TIER 2 STANDARD.

PROVIDE (1) EACH SMALL DIAMETER CAT6A PATCH CORD FOR EACH NEW DATA PORT. PROVIDE VARIOUS LENGTHS AS REQUIRED FOR A NEAT AND ORDERLY INSTALLATION, UTILIZING THE VERTICAL AND HORIZONTAL WIRE

MANAGERS AS APPLICABLE. (SEE SPECIFICATIONS)

NEW FIRE-RATED SLEEVES SHALL BE INSTALLED EXITING THE TR AND IN ALL FIRE-RATED WALLS ALONG THE CABLE

PATHWAYS.

I. EXISTING CONDUITS TO REMAIN.

J. EXISTING DATA RACK/RACKS TO REMAIN UNTIL AFTER CUT-OVER.

K.

L.

M.

N.

PHASE 1 - INSTALL APPROXIMATELY (34) NEW CATEGORY 6A DATA CABLES ON THE FIFTH FLOOR LEVEL TO A MIXTURE

OF (14) DUAL AND QUAD NEW WORK AREA OUTLET LOCATIONS.

O.

W

WAP

WALL PHONE OUTLET CONTAINING (1) CATEGORY 6A UTP CABLE TERMINATED ONTO (1) CATEGORY 6A RJ-45 TYPE (8P-8C) JACK. UTP CABLE JACKET COLOR TO BE BLUE. TERMINATION SCHEME TO BE T568B.

(EXISTING WAO LOCATION TO BE INSTALLED IN PHASE 2)

WIRELESS ACCESS POINT CONTAINING (1) CATEGORY 6A UTP CABLE TERMINATED ONTO (1) CATEGORY 6A RJ-45 TYPE (8P-8C) JACK. UTP CABLE JACKET COLOR TO BE BLUE. TERMINATION SCHEME TO BE T568B

(EXISTING WAO LOCATION TO BE INSTALLED IN PHASE 2).

INSTALLATION..

4-PORT WORK AREA OUTLET FACEPLATE CONTAINING (1) CATEGORY 6A UTP CABLE TERMINATED ONTO (1) CATEGORY 6A RJ-45 TYPE (8P-8C) JACK. UTP CABLE JACKET COLORE TO BE BLUE. TERMINATION SCHEME

TO BE T568B. (EXISTING WAO LOCATION TO BE INSTALLED IN PHASE 2)

4-PORT WORK AREA OUTLET FACEPLATE CONTAINING (2) CATEGORY 6A UTP CABLES TERMINATED ONTO (2) CATEGORY 6A RJ-45 TYPE (8P-8C) JACKS. UTP CABLE JACKET COLOR TO BE BLUE. TERMINATION SCHEME

TO BE T568B. (EXISTING WAO LOCATION TO BE INSTALLED IN PHASE 2)

4-PORT WORK AREA OUTLET FACEPLATE CONTAINING (4) CATEGORY 6A UTP CABLES TERMINATED ONTO (4) CATEGORY 6A RJ-45 TYPE (8P-8C) JACKS. UTP CABLE JACKET COLOR TO BE BLUE. TERMINATION SCHEME

TO BE T568B. (EXISTING WAO LOCATION TO BE INSTALLED IN PHASE 2)

GENERAL NOTES:

PROVIDE AND INSTALL 18"W x 4"D WIRE BASKET TYPE CABLE TRAY TO SUPPORT CATEGORY 6A UTP WORK AREA

OUTLET (WAO) STATION CABLES.

PROVIDE AND INSTALL J-HOOK PATHWAYS TO SUPPORT CATEGORY 6A STATION CABLES FROM WAO TO MAIN CABLE TRAY OR MAIN J-HOOK PATHWAY BACK TO THE ASSOCIATED TR (TYPICAL). INSTALL AT 5' (MAXIMUM) .

INTERVALS O.C. (NOTE: J-HOOK PATHWAYS DEPICTED ARE JUST A FEW EXAMPLES. ALL STATION CABLING MUST BE SUPPORTED BY J-HOOK PATHWAYS THAT ARE PARALLEL AND PERPENDICULAR TO BUILDING LINES.)

= 4-PORT WORK AREA OUTLET FACEPLATE CONTAINING (2) CATEGORY 6A UTP CABLES TERMINATED ONTO (2)

CATEGORY 6A RJ-45 TYPE (8P-8C) JACKS. UTP CABLE JACKET COLOR TO BE BLUE. TERMINATION SCHEME

TO BE T568B. (NEW WAO LOCATION TO BE INSTALLED IN PHASE 1)

4-PORT WORK AREA OUTLET FACEPLATE CONTAINING (4) CATEGORY 6A UTP CABLES TERMINATED ONTO (4) CATEGORY 6A RJ-45 TYPE (8P-8C) JACKS. UTP CABLE JACKET COLOR TO BE BLUE. TERMINATION SCHEME

TO BE T568B. (NEW WAO LOCATION TO BE INSTALLED IN PHASE 1)

X

X = PHASE 1 - THESE NEW WORK AREA OUTLET LOCATIONS (NWAO's) ARE TO BE INSTALLED IN PHASE 1.

= PHASE 2 - THESE EXISTING WORK AREA OUTLET LOCATIONS (EWAO's) ARE TO BE INSTALLED IN PHASE 2.

PHASE 2 - INSTALL APPROXIMATELY (170) NEW CATEGORY 6A DATA CABLES ON THE FIFTH FLOOR LEVEL TO A MIXTURE

OF (80) DUAL AND QUAD EXISTING WORK AREA OUTLET LOCATIONS.

P.

Willam A. McClendon - 11/12/2021 98 OF 120

UP

BATH

ROOM

DN

LOCKER

TOILET

ROOM

UP

STORAGE

HVAC SHOP

UP

UP

CARP SHOP

CARP SHOP

GARAGE

PIPE SHOP

211A

UP

ROOM

OFFICE

BREAK

ROOM

OFFICE

OFFICE

4 4 4

U P

U P

4 U P

U P

LO

C

KS

M

IT

H

5A

PA

IN

T

SH

O P

U P

BASEMENT 1ST FLOOR

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project NumberCONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. AR12100034 EXP. 12/31/2021

MECH ENGR REG. NO. PE12100220 EXP. 07/31/2022

ELEC ENGR REG. NO. PE12100195 EXP. 07/31/2022

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC / PLUMB / TECH ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(913) 369-7200

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

TELECOMMUNICATIONS

ASPEN ENGINEERING & CONTRACTING

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 85712

(928) 774-0992

PHYSCIAL SECURITY

FORCE PROTECT

3210 GULF BLVD, UNIT 304

BELLEAIR BEACH, FL 33786

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

BUILDING 2 - TECHNOLOGY FLOOR PLANS

BID DOCUMENTS

EHRM INFRASTRUCTURE

UPGRADES FORT WAYNE,

INDIANA

610A4-21-701

VANIHCS

T-106

No. REVISION DESCRIPTION DATE

SCALE: 1/8" = 1'0"

B2 - TECHNOLOGY PLAN

N

11/12/2021 WBM

ALL CATEGORY 6A STATION CABLING SHALL BE SUPPORTED USING A COMBINATION OF J-HOOKS AND CABLE TRAYS

(IF POSSIBLE) IN GENERAL PATHWAYS.

ENSURE THAT ALL GROUNDING AND BONDING IS COMPLETE. TWO SCREW BONDING LUGS NEED TO BE INSTALLED TO BOND ALL METALLIC COMPONENTS OF THE RACK AND CABLE TRAY SYSTEM, TO THE TELECOMMUNICATIONS

SECONDARY BONDING BUSBAR.

AFTER CUT-OVER TO THE NEW CABLING, DEMOLISH ALL OLD DATA AND TELEPHONE CABLING ALL THE WAY TO THE STATION END. ENSURE THAT ANY CABLES IN THE CEILING AREAS THAT ARE FOR SYSTEMS OTHER THAN THE IT DATA AND TELEPHONE, ARE NOT DISTURBED. BLANK OFF ANY UNUSED OLD DATA LOCATIONS. DEMOLISH ALL OLD PATCH PANELS AND ASSOCIATED HARDWARE. ALL OTHER ANCILLARY RACK-MOUNTED EQUIPMENT, NOT RELATED TO IT DATA AND TELEPHONE, TO BE RELOCATED TO A NEW RACK BY OIT PERSONNEL. FIRE-STOP ALL EXISTING SLEEVES

WHERE CABLING WAS REMOVED.

AFTER CUT-OVER, REMOVE ALL OLD IT FIBER OPTIC CABLING FROM THE TR ALL THE WAY BACK TO THE SERVER ROOM. DEMOLISH ALL ASSOCIATED HARDWARE AND TERMINATION EQUIPMENT. ENSURE THAT ANY CABLING IN THE

CEILING AREA THAT IS FOR OTHER SYSTEMS, IS NOT DISTURBED.

A.

B.

C.

D.

E.

F.

G.

H.

CONTRACTOR SHALL INCLUDE AN ADDITIONAL 10% OF CABLE DROPS IN THEIR BID FOR ADDS FOUND DURING

ADDITIONAL PATCH PANEL CAPACITY SHALL BE PROVIDED TO ACCOUNT FOR 15% GROWTH OF ADDITIONAL CABLE

DROPS.

ALL EXISTING DATA CABLES AND CIRCUITS MUST REMAIN IN PLACE AND OPERATIONAL UNTIL FINAL CUT-OVER TO

THE NEW CABLING.

EACH NEW WORK AREA OUTLET (WAO) LOCATION WILL CONSIST OF TWO OR FOUR CAT6A CABLES AS SHOWN ON THE PLANS. EACH CABLE WILL BE TERMINATED ON A 48-PORT CAT6A PATCH PANEL IN IT'S DESIGNATED TR.

EXISTING WAO LOCATIONS SHALL BE RE-USED WHEREVER POSSIBLE.

LABEL FIBER CABLE GOING INTO EACH FIBER PATCH PANEL. ALL FIBER STRANDS WILL BE TESTED UTILIZING AN

OLTS AND AN OTDR PER THE TIER 2 STANDARD.

PROVIDE (1) EACH SMALL DIAMETER CAT6A PATCH CORD FOR EACH NEW DATA PORT. PROVIDE VARIOUS LENGTHS AS REQUIRED FOR A NEAT AND ORDERLY INSTALLATION, UTILIZING THE VERTICAL AND HORIZONTAL WIRE

MANAGERS AS APPLICABLE. (SEE SPECIFICATIONS)

NEW FIRE-RATED SLEEVES SHALL BE INSTALLED LEAVING THE TR AND IN ALL FIRE-RATED WALLS ALONG THE CABLE

PATHWAYS.

GENERAL NOTES:

I. EXISTING CONDUITS TO REMAIN.

J. EXISTING DATA RACK/RACKS TO REMAIN UNTIL AFTER CUT-OVER.

K.

L.

M.

N.

INSTALL APPROXIMATELY (58) NEW CATEGORY 6A DATA CABLES IN BUILDING 2 TO A MIXTURE OF (15) DUAL & QUAD

WORK AREA OUTLET LOCATIONS.

O.

LEGEND:

W

WAP

WALL PHONE OUTLET CONTAINING (1) CATEGORY 6A UTP CABLE TERMINATED ONTO (1) CATEGORY 6A RJ-45 TYPE (8P-8C) JACK. UTP CABLE JACKET COLOR TO BE BLUE. TERMINATION SCHEME TO BE T568B.

WIRELESS ACCESS POINT CONTAINING (1) CATEGORY 6 UTP CABLE TERMINATED ONTO (1) CATEGORY 6A RJ-45 TYPE (8P-8C) JACK. UTP CABLE JACKET COLOR TO BE BLUE. TERMINATION SCHEME TO BE T568B.

INSTALLATION.

4-PORT WORK AREA OUTLET FACEPLATE CONTAINING (1) CATEGORY 6A UTP CABLE TERMINATED ONTO (1) CATEGORY 6A RJ-45 TYPE (8P-8C) JACK. UTP CABLE JACKET COLORE TO BE BLUE. TERMINATION SCHEME

TO BE T568B.

4-PORT WORK AREA OUTLET FACEPLATE CONTAINING (2) CATEGORY 6A UTP CABLES TERMINATED ONTO (2) CATEGORY 6A RJ-45 TYPE (8P-8C) JACKS. UTP CABLE JACKET COLOR TO BE BLUE. TERMINATION SCHEME

TO BE T568B.

4-PORT WORK AREA OUTLET FACEPLATE CONTAINING (4) CATEGORY 6A UTP CABLES TERMINATED ONTO (4) CATEGORY 6A RJ-45 TYPE (8P-8C) JACKS. UTP CABLE JACKET COLOR TO BE BLUE. TERMINATION SCHEME

TO BE T568B.

AJS

PROVIDE AND INSTALL (1) NEW 4" EMT FROM PULL BOX INTO THE TR. ROUTE CONDUIT THROUGH CRAWL SPACE AND ATTACH TO BUILDING STRUCTURE ALONG THE ROUTE. PROVIDE AND INSTALL (1) 4" 3-CELL FABRIC INNERUCT (e.g.: MAXCELL)

PROVIDE AND INSTALL (1) NEW NEMA 3R PULL BOX (18"W x 18"L x 12"D).

PROVIDE AND INSTALL (1) EACH 24-STRAND, INDOOR/OUTDOOR, ARMORED, OS2, SINGLEMODE FIBER OPTIC CABLE (OFCP), WITH A GREEN JACKET. REDUNDANT/DIVERSE FIBER CABLE "A" SHALL BE HOMERUN BACK TO THE NEW

MCR/DC/SR IN BUILDING 1.

PROVIDE AND INSTALL (1) EACH 24-STRAND, INDOOR/OUTDOOR, ARMORED, OS2, SINGLEMODE FIBER OPTIC CABLE (OFCP), WITH A GREEN JACKET. REDUNDANT/DIVERSE FIBER CABLE "B" SHALL BE HOMERUN BACK TO THE NEW

MCR/DC/SR IN BUILDING 1.

EXISTING CONDUIT, FROM EXISTING MAINTENANCE HOLE (MH), CONTAINING EXISTING COPPER & FIBER FEED CABLES. REMOVE EXISTING FEED CABLES BACK TO EXISTING MH . EXTEND EXISTING CONDUIT INTO NEW TR LOCATION. PROVIDE AND INSTALL (1) 4" 3-CELL FABRIC INNERDUCT (e.g.: MAXCELL) FROM EXISTING MH INTO TR.

LEGEND:

2121 LAKE AVE,

98 119Willam A. McClendon - 11/12/2021 99 OF 120

H.A.C.

120 119A

OFFICE

VEST

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

BREAK/COPY

UP

MECH

OFFICE

WOMEN

TOILET

MEN TOILET

OFFICE

103A

VEST

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

UP UP

UP

4 4

4 4

4 4 4 4 4

4 4

BASEMENT 1ST FLOOR

LEN

EL/A

LTR

O

N

IX

LG

D

U A

L IN

V

ER

TER

A

C

BASEMENT

TR-301

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project NumberCONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. AR12100034 EXP. 12/31/2021

MECH ENGR REG. NO. PE12100220 EXP. 07/31/2022

ELEC ENGR REG. NO. PE12100195 EXP. 07/31/2022

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC / PLUMB / TECH ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(913) 369-7200

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

TELECOMMUNICATIONS

ASPEN ENGINEERING & CONTRACTING

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 85712

(928) 774-0992

PHYSCIAL SECURITY

FORCE PROTECT

3210 GULF BLVD, UNIT 304

BELLEAIR BEACH, FL 33786

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

BUILDING 3 - TECHNOLOGY FLOOR PLAN

BID DOCUMENTS

EHRM INFRASTRUCTURE

UPGRADES FORT WAYNE,

INDIANA

610A4-21-701

VANIHCS

T-107

No. REVISION DESCRIPTION DATE

SCALE: 1/8" = 1'0"

B3 - TECHNOLOGY PLAN

N

11/12/2021 WBM

ALL CATEGORY 6A STATION CABLING SHALL BE SUPPORTED USING A COMBINATION OF J-HOOKS AND CABLE TRAYS

(IF POSSIBLE) IN GENERAL PATHWAYS.

ENSURE THAT ALL GROUNDING AND BONDING IS COMPLETE. TWO SCREW BONDING LUGS NEED TO BE INSTALLED TO BOND ALL METALLIC COMPONENTS OF THE RACK AND CABLE TRAY SYSTEM, TO THE TELECOMMUNICATIONS

SECONDARY BONDING BUSBAR.

AFTER CUT-OVER TO THE NEW CABLING, DEMOLISH ALL OLD DATA AND TELEPHONE CABLING ALL THE WAY TO THE STATION END. ENSURE THAT ANY CABLES IN THE CEILING AREAS THAT ARE FOR SYSTEMS OTHER THAN THE IT DATA AND TELEPHONE, ARE NOT DISTURBED. BLANK OFF ANY UNUSED OLD DATA LOCATIONS. DEMOLISH ALL OLD PATCH PANELS AND ASSOCIATED HARDWARE. ALL OTHER ANCILLARY RACK-MOUNTED EQUIPMENT, NOT RELATED TO IT DATA AND TELEPHONE, TO BE RELOCATED TO A NEW RACK BY OIT PERSONNEL. FIRE-STOP ALL EXISTING SLEEVES

WHERE CABLING WAS REMOVED.

AFTER CUT-OVER, REMOVE ALL OLD IT FIBER OPTIC CABLING FROM THE TR ALL THE WAY BACK TO THE SERVER ROOM. DEMOLISH ALL ASSOCIATED HARDWARE AND TERMINATION EQUIPMENT. ENSURE THAT ANY CABLING IN THE

CEILING AREA THAT IS FOR OTHER SYSTEMS, IS NOT DISTURBED.

A.

B.

C.

D.

E.

F.

G.

H.

CONTRACTOR SHALL INCLUDE AN ADDITIONAL 10% OF CABLE DROPS IN THEIR BID FOR ADDS FOUND DURING

ADDITIONAL PATCH PANEL CAPACITY SHALL BE PROVIDED TO ACCOUNT FOR 15% GROWTH OF ADDITIONAL CABLE

DROPS.

ALL EXISTING DATA CABLES AND CIRCUITS MUST REMAIN IN PLACE AND OPERATIONAL UNTIL FINAL CUT-OVER TO

THE NEW CABLING.

EACH NEW WORK AREA OUTLET (WAO) LOCATION WILL CONSIST OF TWO OR FOUR CAT6A CABLES AS SHOWN ON THE PLANS. EACH CABLE WILL BE TERMINATED ON A 48-PORT CAT6A PATCH PANEL IN IT'S DESIGNATED TR.

EXISTING WAO LOCATIONS SHALL BE RE-USED WHEREVER POSSIBLE.

LABEL FIBER CABLE GOING INTO EACH FIBER PATCH PANEL.. ALL FIBER STRANDS WILL BE TESTED UTILIZING AN

OLTS AND AN OTDR PER THE TIER 2 STANDARD.

PROVIDE (1) EACH SMALL DIAMETER CAT6A PATCH CORD FOR EACH NEW DATA PORT. PROVIDE VARIOUS LENGTHS AS REQUIRED FOR A NEAT AND ORDERLY INSTALLATION, UTILIZING THE VERTICAL AND HORIZONTAL WIRE

MANAGERS AS APPLICABLE. (SEE SPECIFICATIONS)

NEW FIRE-RATED SLEEVES SHALL BE INSTALLED LEAVING THE TR AND IN ALL FIRE-RATED WALLS ALONG THE CABLE

PATHWAYS.

GENERAL NOTES:

I. EXISTING CONDUITS TO REMAIN.

J. EXISTING DATA RACK/RACKS TO REMAIN UNTIL AFTER CUT-OVER.

K.

L.

M.

N.

INSTALL APPROXIMATELY (114) NEW CATEGORY 6A DATA CABLES IN BUILDING 3 TO A MIXTURE OF (29) DUAL & QUAD

WORK AREA OUTLET LOCATIONS.

O.

LEGEND:

W

WAP

WALL PHONE OUTLET CONTAINING (1) CATEGORY 6A UTP CABLE TERMINATED ONTO (1) CATEGORY 6A RJ-45 TYPE (8P-8C) JACK. UTP CABLE JACKET COLOR TO BE BLUE. TERMINATION SCHEME TO BE T568B.

WIRELESS ACCESS POINT CONTAINING (1) CATEGORY 6 UTP CABLE TERMINATED ONTO (1) CATEGORY 6A RJ-45 TYPE (8P-8C) JACK. UTP CABLE JACKET COLOR TO BE BLUE. TERMINATION SCHEME TO BE T568B.

INSTALLATION.

4-PORT WORK AREA OUTLET FACEPLATE CONTAINING (1) CATEGORY 6A UTP CABLE TERMINATED ONTO (1) CATEGORY 6A RJ-45 TYPE (8P-8C) JACK. UTP CABLE JACKET COLORE TO BE BLUE. TERMINATION SCHEME

TO BE T568B.

4-PORT WORK AREA OUTLET FACEPLATE CONTAINING (2) CATEGORY 6A UTP CABLES TERMINATED ONTO (2) CATEGORY 6A RJ-45 TYPE (8P-8C) JACKS. UTP CABLE JACKET COLOR TO BE BLUE. TERMINATION SCHEME

TO BE T568B.

4-PORT WORK AREA OUTLET FACEPLATE CONTAINING (4) CATEGORY 6A UTP CABLES TERMINATED ONTO (4) CATEGORY 6A RJ-45 TYPE (8P-8C) JACKS. UTP CABLE JACKET COLOR TO BE BLUE. TERMINATION SCHEME

TO BE T568B.

AJS

PROVIDE AND INSTALL (1) NEW 4" EMT FROM PULL BOX INTO THE TR. ROUTE CONDUIT THROUGH CRAWL SPACE AND ATTACH TO BUILDING STRUCTURE ALONG THE ROUTE. PROVIDE AND INSTALL (1) 4" 3-CELL FABRIC INNERUCT (e.g.: MAXCELL)

PROVIDE AND INSTALL (1) NEW NEMA 3R PULL BOX (18"W x 18"L x 12"D).

PROVIDE AND INSTALL (1) EACH 24-STRAND, INDOOR/OUTDOOR, ARMORED, OS2, SINGLEMODE FIBER OPTIC CABLE (OFCP), WITH A GREEN JACKET. REDUNDANT/DIVERSE FIBER CABLE "A" SHALL BE HOMERUN BACK TO THE NEW

MCR/DC/SR IN BUILDING 1.

PROVIDE AND INSTALL (1) EACH 24-STRAND, INDOOR/OUTDOOR, ARMORED, OS2, SINGLEMODE FIBER OPTIC CABLE (OFCP), WITH A GREEN JACKET. REDUNDANT/DIVERSE FIBER CABLE "B" SHALL BE HOMERUN BACK TO THE NEW

MCR/DC/SR IN BUILDING 1.

EXISTING CONDUIT, FROM EXISTING MAINTENANCE HOLE (MH), CONTAINING EXISTING COPPER & FIBER FEED CABLES. REMOVE EXISTING FEED CABLES BACK TO EXISTING MH . EXTEND EXISTING CONDUIT INTO NEW TR LOCATION. PROVIDE AND INSTALL (1) 4" 3-CELL FABRIC INNERDUCT (e.g.: MAXCELL) FROM EXISTING MH INTO TR.

KEYNOTES:

2121 LAKE AVE,

99 119Willam A. McClendon - 11/12/2021 100 OF 120

MECH/HAC

CONFERENCE

COPY/BREAK

OFFICE

OFFICE

OFFICE

STORAGE

OFFICE

CONFERENCE

OFFICE

U P

D N

U P

U P

4 4

TR-401

LE

N

EL

/A

LT

R O

N

IX

LG DUAL INVERTER AC

BASEMENT

BASEMENT 1ST FLOOR

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project NumberCONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. AR12100034 EXP. 12/31/2021

MECH ENGR REG. NO. PE12100220 EXP. 07/31/2022

ELEC ENGR REG. NO. PE12100195 EXP. 07/31/2022

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC / PLUMB / TECH ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(913) 369-7200

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

TELCOMMUNICATIONS

ASPEN ENGINEERING & CONTRACTING

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 85712

(928) 774-0992

PHYSCIAL SECURITY

FORCE PROTECT

3210 GULF BLVD, UNIT 304

BELLEAIR BEACH, FL 33786

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

BUILDING 4 - TECHNOLOGY FLOOR PLAN

BID DOCUMENTS

EHRM INFRASTRUCTURE

UPGRADES FORT WAYNE,

INDIANA

610A4-21-701

VANIHCS

T-108

No. REVISION DESCRIPTION DATE

SCALE: 1/8" = 1'0"

B4 - TECHNOLOGY PLAN

N

11/12/2021 WBM

ALL CATEGORY 6A STATION CABLING SHALL BE SUPPORTED USING A COMBINATION OF J-HOOKS AND CABLE TRAYS

(IF POSSIBLE) IN GENERAL PATHWAYS.

ENSURE THAT ALL GROUNDING AND BONDING IS COMPLETE. TWO SCREW BONDING LUGS NEED TO BE INSTALLED TO BOND ALL METALLIC COMPONENTS OF THE RACK AND CABLE TRAY SYSTEM, TO THE TELECOMMUNICATIONS

SECONDARY BONDING BUSBAR.

AFTER CUT-OVER TO THE NEW CABLING, DEMOLISH ALL OLD DATA AND TELEPHONE CABLING ALL THE WAY TO THE STATION END. ENSURE THAT ANY CABLES IN THE CEILING AREAS THAT ARE FOR SYSTEMS OTHER THAN THE IT DATA AND TELEPHONE, ARE NOT DISTURBED. BLANK OFF ANY UNUSED OLD DATA LOCATIONS. DEMOLISH ALL OLD PATCH PANELS AND ASSOCIATED HARDWARE. ALL OTHER ANCILLARY RACK-MOUNTED EQUIPMENT, NOT RELATED TO IT DATA AND TELEPHONE, TO BE RELOCATED TO A NEW RACK BY OIT PERSONNEL. FIRE-STOP ALL EXISTING SLEEVES

WHERE CABLING WAS REMOVED.

AFTER CUT-OVER, REMOVE ALL OLD IT FIBER OPTIC CABLING FROM THE TR ALL THE WAY BACK TO THE SERVER ROOM. DEMOLISH ALL ASSOCIATED HARDWARE AND TERMINATION EQUIPMENT. ENSURE THAT ANY CABLING IN THE

CEILING AREA THAT IS FOR OTHER SYSTEMS, IS NOT DISTURBED.

A.

B.

C.

D.

E.

F.

G.

H.

CONTRACTOR SHALL INCLUDE AN ADDITIONAL 10% OF CABLE DROPS IN THEIR BID FOR ADDS FOUND DURING

ADDITIONAL PATCH PANEL CAPACITY SHALL BE PROVIDED TO ACCOUNT FOR 15% GROWTH OF ADDITIONAL CABLE

DROPS.

ALL EXISTING DATA CABLES AND CIRCUITS MUST REMAIN IN PLACE AND OPERATIONAL UNTIL FINAL CUT-OVER TO

THE NEW CABLING.

EACH NEW WORK AREA OUTLET (WAO) LOCATION WILL CONSIST OF TWO OR FOUR CAT6A CABLES AS SHOWN ON THE PLANS. EACH CABLE WILL BE TERMINATED ON A 48-PORT CAT6A PATCH PANEL IN IT'S DESIGNATED TR.

EXISTING WAO LOCATIONS SHALL BE RE-USED WHEREVER POSSIBLE.

LABEL FIBER CABLE GOING INTO EACH FIBER PATCH PANEL. ALL FIBER STRANDS WILL BE TESTED UTILIZING AN

OLTS AND AN OTDR PER THE TIER 2 STANDARD.

PROVIDE (1) EACH SMALL DIAMETER CAT6A PATCH CORD FOR EACH NEW DATA PORT. PROVIDE VARIOUS LENGTHS AS REQUIRED FOR A NEAT AND ORDERLY INSTALLATION, UTILIZING THE VERTICAL AND HORIZONTAL WIRE

MANAGERS AS APPLICABLE. (SEE SPECIFICATIONS)

NEW FIRE-RATED SLEEVES SHALL BE INSTALLED LEAVING THE TR AND IN ALL FIRE-RATED WALLS ALONG THE CABLE

PATHWAYS.

GENERAL NOTES:

I. EXISTING CONDUITS TO REMAIN.

J. EXISTING DATA RACK/RACKS TO REMAIN UNTIL AFTER CUT-OVER.

K.

L.

M.

N.

INSTALL APPROXIMATELY (58) NEW CATEGORY 6A DATA CABLES IN BUILDING 4 TO A MIXTURE OF (15) DUAL & QUAD

WORK AREA OUTLET LOCATIONS.

O.

LEGEND:

W

WAP

WALL PHONE OUTLET CONTAINING (1) CATEGORY 6A UTP CABLE TERMINATED ONTO (1) CATEGORY 6A RJ-45 TYPE (8P-8C) JACK. UTP CABLE JACKET COLOR TO BE BLUE. TERMINATION SCHEME TO BE T568B.

WIRELESS ACCESS POINT CONTAINING (1) CATEGORY 6A UTP CABLE TERMINATED ONTO (1) CATEGORY 6A RJ-45 TYPE (8P-8C) JACK. UTP CABLE JACKET COLOR TO BE BLUE. TERMINATION SCHEME TO BE T568B.

INSTALLATION.

4-PORT WORK AREA OUTLET FACEPLATE CONTAINING (1) CATEGORY 6A UTP CABLE TERMINATED ONTO (1) CATEGORY 6A RJ-45 TYPE (8P-8C) JACK. UTP CABLE JACKET COLORE TO BE BLUE. TERMINATION SCHEME

TO BE T568B.

4-PORT WORK AREA OUTLET FACEPLATE CONTAINING (2) CATEGORY 6A UTP CABLES TERMINATED ONTO (2) CATEGORY 6A RJ-45 TYPE (8P-8C) JACKS. UTP CABLE JACKET COLOR TO BE BLUE. TERMINATION SCHEME

TO BE T568B.

4-PORT WORK AREA OUTLET FACEPLATE CONTAINING (4) CATEGORY 6A UTP CABLES TERMINATED ONTO (4) CATEGORY 6A RJ-45 TYPE (8P-8C) JACKS. UTP CABLE JACKET COLOR TO BE BLUE. TERMINATION SCHEME

TO BE T568B.

AJS

PROVIDE AND INSTALL (1) NEW 4" EMT FROM PULL BOX INTO THE TR. ROUTE CONDUIT THROUGH CRAWL SPACE AND ATTACH TO BUILDING STRUCTURE ALONG THE ROUTE. PROVIDE AND INSTALL (1) 4" 3-CELL FABRIC INNERUCT (e.g.: MAXCELL)

PROVIDE AND INSTALL (1) NEW NEMA 3R PULL BOX (18"W x 18"L x 12"D).

PROVIDE AND INSTALL (1) EACH 24-STRAND, INDOOR/OUTDOOR, ARMORED, OS2, SINGLEMODE FIBER OPTIC CABLE (OFCP), WITH A GREEN JACKET. REDUNDANT/DIVERSE FIBER CABLE "A" SHALL BE HOMERUN BACK TO THE NEW

MCR/DC/SR IN BUILDING 1.

PROVIDE AND INSTALL (1) EACH 24-STRAND, INDOOR/OUTDOOR, ARMORED, OS2, SINGLEMODE FIBER OPTIC CABLE (OFCP), WITH A GREEN JACKET. REDUNDANT/DIVERSE FIBER CABLE "B" SHALL BE HOMERUN BACK TO THE NEW

MCR/DC/SR IN BUILDING 1.

EXISTING CONDUIT, FROM EXISTING MAINTENANCE HOLE (MH), CONTAINING EXISTING COPPER & FIBER FEED CABLES. REMOVE EXISTING FEED CABLES BACK TO EXISTING MH . EXTEND EXISTING CONDUIT INTO NEW TR LOCATION. PROVIDE AND INSTALL (1) 4" 3-CELL FABRIC INNERDUCT (e.g.: MAXCELL) FROM EXISTING MH INTO TR.

KEYNOTES:

2121 LAKE AVE,

100 119Willam A. McClendon - 11/12/2021 101 OF 120

105 107

OFFICE

OFFICE

104 102

BATH

OFFICE

UP

UP

UP

UP

4 4

CLOSET

CLOSET

OFFICE

OFFICE

H.A.C.

OFFICE

UP BATH

UP

1ST FLOOR

2ND FLOOR

BASEMENT

BASEMENT

UP

TR-501BASEMENT

LG

D

U A L

IN

V

ER

TE

R A

C

LENEL/ALTRONIX

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn