This document package includes construction drawings and specifications for fire protection system upgrades at several Department of Veterans Affairs buildings in Fort Wayne, Indiana. The scope of work involves expanding existing fire alarm, fire suppression, and clean agent fire extinguishing systems into telecommunications spaces to comply with NFPA and VA requirements. Drawings show fire alarm device locations and wiring, hazard classifications, sprinkler scope, and a NOVEC 1230 clean agent system for the main server room. General notes provide design and installation standards. The related solicitation is for the EHRM Infrastructure Upgrades Construction project at the VA Health Care System in Fort Wayne. The solicitation number is 36C77622B0028.
View the file
Other files for this federal contract opportunity
Show all 28
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FACU
SPD
NOTES:
1. TO DEDICATED 120VAC BRANCH CIRCUIT
2. EXISTING FIRE ALARM CONTROL UNIT
3. THIS RISER DIAGRAM IS INTENDED ONLY TO CAPTURE THE SYSTEM DESIGN INTENT, PANEL
CONNECTIONS, AND GENERAL CIRCUIT ROUTING REQUIREMENTS. EXACT QUANTITIES AND
TYPES OF DEVICES NECESSARY TO ACCOMPLISH THE DESIGN GOALS ARE NOT INDICATED.
THE INTENT OF THIS RISER DIAGRAM IS TO INDICATE THE GENERAL SYSTEM CONFIGURATION
AFTER SUCCESSFUL COMPLETION OF THE PROJECT.
2 3
BASEMENT
WF VS
AIM AIMAIM
ASD
AOM
AHU
AOM
SEE SHEET SH-001
FOR CONTINUATION
AIM
CT
AIM
CT
AIM
CT
S U
P E
R V
IS
O
R Y
T R
O U
B L E
A L A
R M
RSFACU
SEE SHEET SH-001
FOR CONTINUATION
S
FIRE ALARM LEGEND
OUT OF SCOPE AREA
1. THE SCOPE OF THIS PROJECT IS TO BRING
TELECOMMUNCIATION SPACES WITHIN THE EHRM
PROGRAM INTO COMPLIANCE WITH CURRENT
CODE REQUIREMENTS. THIS INCLUDES THE
EXPANSION OF EXISTING FIRE ALARM SYSTEMS
INTO THE SCOPE OF WORK AREAS. EXPANSION OF
THE EXISTING FIRE ALARM SYSTEM SHALL BE
DESIGNED AND INSTALLED IN ACCORDANCE WITH
THE VA FIRE PROTECTION DESIGN MANUAL-EIGHTH
EDITION, NFPA 70-2020, AND NFPA 72-2022. FIRE
ALARM CONTRACTOR IS RESPONSIBLE FOR
DEVELOPING CALCULATIONS AND SHOP
DRAWINGS.
2. SYSTEM MODIFICATION SHALL BE CONSIDERED
WITH RESPECT TO FLOOR PLAN CHANGES.
3. NOTIFICATION APPLIANCES SHALL MATCH
EXISTING MANUFACTURER AND MODEL OR BE
COMPATIBLE WITH THE EXISTING SYSTEM.
SPEAKERS AND STROBES SHALL BE WHITE FINISH
TO MATCH EXISTING DEVICES.
4. CONTRACTOR SHALL COORDINATE AND VERIFY
DEMOLITION OR RELOCATION OF ITEMS WITH
OWNER PRIOR TO COMMENCING WORK TO
PREVENT INTERRUPTION OF SERVICE.
5. FIRE ALARM INPUT/OUTPUT MATRIX IS PROVIDED
FOR NEW DEVICES LOCATED IN THE PROJECT
AREA. ALL OTHER INPUTS SHALL MATCH EXISTING
PANEL.
FIRE ALARM GENERAL NOTES:
SPD EXISTING SURGE PROTECTIVE DEVICE
FACU EXISTING FIRE ALARM CONTROL UNIT
WF NEW WATERFLOW DEVICE
VS NEW VALVE SUPERVISORY SWITCH
AIM NEW ADDRESSABLE INPUT MODULE
ASPIRATING SMOKE DETECTION SYSTEM PANELASD
AOM NEW ADDRESSABLE OUTPUT MODULE
AIR HANDLING UNIT CONTROLLERAHU
CT
RELEASING SERVICE FIRE ALARM CONTROL UNITRSFACU
DISCRETE OUTPUT - DRY CONTACT
1 WATERFLOW/PRESSURE SWITCH X X X X X X X X 1
4 RSFACU - CLEAN AGENT COMMON SUPERVISORY X X X 4
5 CONTROL VALVE SUPERVISORY SWITCH X X X 5
12 RSFACU - CLEAN AGENT COMMON TROUBLE X X X 12
13 ANY OTHER SYSTEM TROUBLE X X X 13
SYSTEM OUTPUTS
SYSTEM INPUTS
F A
C U
A N
N U
N C
IA
T
IO
N
A C
T
IV
A T
E C
O M
M O
N A
L A
R M
S
IG
N A
L I
N D
IC
A
T O
R
A C
T
IV
A T
E A
U D
IB
L E
A L A
R M
S
IG
N A
L
A C
T
IV
A T
E C
O M
M O
N S
U P
E R
V
IS
O R
Y S
IG
N
A L I
N D
IC
A
T O
R
A C
T
IV
A T
E A
U D
IB
L E
S U
P E
R V
IS
O
R Y
S
IG
N A
L
A C
T
IV
A T
E C
O M
M O
N T
R O
U B
L E
S
IG
N A
L I
N D
IC
A
T O
R
A C
T
IV
A T
E A
U D
IB
L E
T R
O U
B L E
S
IG
N A
L
D
IS
P L A
Y /P
R
IN
T C
H A
N G
E O
F S
T A
T U
S
N O
T
IF
IC
A
T
IO
N
A C
T
IV
A T
E T
E M
P O
R A
L
A L E
R T
T O
N E
A N
D P
R E
-R E
C O
R D
E D
F
IR
E
V
A C
U A
T
IO
N M
E S
S A
G E
T H
R O
U G
H O
U T
T H
E A
S S
O C
IA
T
E D
Z O
N E
A C
T
IV
A T
E S
T R
O B
E S
T H
R O
U G
H O
U T
T H
E A
S S
O C
IA
T
E D
Z O
N E
A C
T
IV
A T
E P
R E
-R E
C O
R D
E D
S T
A F
F A
L E
R T
M E
S S
A G
E T
H R
O U
G H
O U
T T
H
B
U
IL
D
IN
G
N O
T
IF
Y S
U P
E R
V
IS
IN
G
S T
A T
IO
N
/F
IR
E D
E P
A R
T M
E N
T
A U
X
IL
IA
R
Y F
U N
C T
IO
N
S
S H
U T
D O
W N
A S
S O
C
IA
T E
D A
IR
H
A N
D L
IN
G U
N
IT
A C
T
IV
A T
E E
L E
C T
R
IC
A L D
IS
C
O N
N E
C T
O F
E Q
U
IP
M E
N T
I N
I T
E S
P A
C E
S
ALARM CONDITIONS A B C D E F G H I J K L M
2 RSFACU - CLEAN AGENT SYSTEM ACTIVATION X X X X X X 2
SUPERVISORY CONDITIONS A B C D E F G H I J K L M
3 SMOKE DETECTOR - DUCT TYPE X X X X 3
A B C D E F G H I J K L M
X PERFORM OPERATION/REPORT DEVICE STATUS
TROUBLE CONDITIONS A B C D E F G H I J K L M
6 AC POWER FAILURE X X X 6
7 LOW BATTERY X X X 7
8 OPEN CIRCUIT X X X 8
9 GROUND FAULT X X X 9
10 NOTIFICATION APPLIANCE CIRCUIT SHORT X X X 10
11 REMOTE POWER SUPPLY COMMON TROUBLE X X X 11
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
IN ARCH REG. NO. AR12100034 EXP. 12/31/2021
IN MECH ENGR REG. NO. PE12100220 EXP. 07/31/2022
IN ELEC ENGR REG. NO. PE12100195 EXP. 07/31/2022
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(913) 369-7200
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
HEALTHCARE PLANNER
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 85712
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
/9
/2
:5 :1
P
M
BLDG 1 FIRE ALARM GENERAL NOTES,
DIAGRAMS, AND LEGEND
SAB 35 119DBN
BID DOCUMENTS
EHRM INFRASTRUCTURE
UPGRADES FORT WAYNE,
INDIANA
11/12/2021
610A4-21-701
VANIHCS
2121 LAKE AVE,
FORT WAYNE, IN 46805
FA001
1, 2, 3, 4, 5, 6, T4, T5, T6
SCALE: NONE
BLDG 1 - FIRE ALARM RISER DIAGRAM1SCALE: NONE
BLDG 1 - FACU INPUT/OUTPUT MATRIX2
NOTES:
1. THIS INPUT/OUTPUT MATRIX IS REPRESENTATIVE OF THE SCOPE OF WORK OF THIS PROJECT IN BUILDING 1. NOT ALL EXISTING
INPUTS AND OUTPUTS ARE REPRESENTED ON THIS MATRIX. PLEASE REFER TO THE EXISTING FIRE ALARM PANEL LOCATED IN
BUILDING 1 FOR ALL OF THE INPUTS AND OUTPUTS.
2. ELECTRICAL DISCONNECT SHALL ONLY BE INITIATED FOR ALARM CONDITIONS DETECTED IN THE SERVER ROOM 057.
No. REVISION DESCRIPTION DATE
TELECOMMUNICATION
FA111
FA111
2 SH001
FA111
FA111
FA111
FA111
FA111
FA111
BLDG 1
N
HATCHING LEGEND
THIS AREA IS NOT WITHIN THE
SCOPE OF THIS PROJECT.
THIS AREA IS WITHIN THE SCOPE
OF THIS PROJECT.
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
IN ARCH REG. NO. AR12100034 EXP. 12/31/2021
IN MECH ENGR REG. NO. PE12100220 EXP. 07/31/2022
IN ELEC ENGR REG. NO. PE12100195 EXP. 07/31/2022
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(913) 369-7200
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
HEALTHCARE PLANNER
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 85712
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
/9
/2
:5 :1
P
M
BLDG 1 OVERALL FIRE ALARM PLANS
SAB 36 119DBN
BID DOCUMENTS
EHRM INFRASTRUCTURE
UPGRADES FORT WAYNE,
INDIANA
11/12/2021
610A4-21-701
VANIHCS
2121 LAKE AVE,
FORT WAYNE, IN 46805
FA101
1, 2, 3, 4, 5, 6, T4, T5, T6
N
1" = 40'-0"
BLDG 1 - BASEMENT FIRE ALARM OVERALL PLAN1
N
1" = 40'-0"
BLDG 1 - FIRST FLOOR FIRE ALARM OVERALL PLAN2
N
1" = 40'-0"
BLDG 1 - SECOND FLOOR FIRE ALARM OVERALL PLAN3
N
1" = 40'-0"
BLDG 1 - THIRD FLOOR FIRE ALARM OVERALL PLAN4
N
1" = 40'-0"
BLDG 1 - FOURTH FLOOR FIRE ALARM OVERALL PLAN5
N
1" = 40'-0"
BLDG 1 - FIFTH FLOOR FIRE ALARM OVERALL PLAN6
No. REVISION DESCRIPTION DATE
UP U
P
U P
U P
U P
U P
UP
FA112
BLDG 3
BLDG T4
BLDG 6BLDG 5
BLDG 2 BLDG 4
BLDG 1
N
FA112
FA112
FA112
FA112
FA112
-6
FA-112 ---
-6
FA-112
T4 T5 T6
HATCHING LEGEND
THIS AREA IS NOT WITHIN THE
SCOPE OF THIS PROJECT.
THIS AREA IS WITHIN THE SCOPE
OF THIS PROJECT.
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
IN ARCH REG. NO. AR12100034 EXP. 12/31/2021
IN MECH ENGR REG. NO. PE12100220 EXP. 07/31/2022
IN ELEC ENGR REG. NO. PE12100195 EXP. 07/31/2022
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(913) 369-7200
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
HEALTHCARE PLANNER
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 85712
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
/9
/2
:5 :1
P
M
BLDG 2,3,4,5,6 & T4-T6 OVERALL FIRE
ALARM PLANS
SAB 37 119DBN
BID DOCUMENTS
EHRM INFRASTRUCTURE
UPGRADES FORT WAYNE,
INDIANA
11/12/2021
610A4-21-701
VANIHCS
2121 LAKE AVE,
FORT WAYNE, IN 46805
FA102
1, 2, 3, 4, 5, 6, T4, T5, T6
N
1/16" = 1'-0"
BLDG 2 - FIRST FLOOR FIRE ALARM OVERALL PLAN1
N
1/16" = 1'-0"
BLDG 3 - BASEMENT FIRE ALARM OVERALL PLAN2
N
1/16" = 1'-0"
BLDG 4 - BASEMENT FIRE ALARM OVERALL PLAN3
N
1/16" = 1'-0"
BLDG 5 - BASEMENT FIRE ALARM OVERALL PLAN4
N
1/16" = 1'-0"
BLDG 6 - FIRST FLOOR FIRE ALARM OVERALL PLAN5
N
1/16" = 1'-0"
BLDG T4-T6 - FIRST FLOOR FIRE ALARM OVERALL PLAN6
2, 3, 4, 5, 6, T4, T5, T6
No. REVISION DESCRIPTION DATE
MAIN
SERVER
ROOM
ASD
AOM ITE SPACE ELECTRICAL
DISCONNECT
VS WF
3 4 5
REFER TO SHEET SH001 FOR
ADDITIONAL FIRE ALARM
DETAIL IN THIS SPACE.
S
CRU-1-057
S
CRU-2-057
RSFACU
TELECOM
ROOM /
TCB
TELECOM
ROOM
176A
TELECOM
ROOM
176A
210C
TELECOM
ROOM
210C
TELECOM
ROOM
TELECOM
ROOM
528C
TELECOM
ROOM
528C th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
IN ARCH REG. NO. AR12100034 EXP. 12/31/2021
IN MECH ENGR REG. NO. PE12100220 EXP. 07/31/2022
IN ELEC ENGR REG. NO. PE12100195 EXP. 07/31/2022
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(913) 369-7200
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
HEALTHCARE PLANNER
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 85712
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
/9
/2
:5 :1
P
M
BLDG 1 ENLARGED FIRE ALARM PLANS
SAB 38 119DBN
BID DOCUMENTS
EHRM INFRASTRUCTURE
UPGRADES FORT WAYNE,
INDIANA
11/12/2021
610A4-21-701
VANIHCS
2121 LAKE AVE,
FORT WAYNE, IN 46805
FA111
1, 2, 3, 4, 5, 6, T4, T5, T6
N
1/4" = 1'-0"
BLDG 1 - BASEMENT FIRE ALARM PLAN - RM 0571
N
1/4" = 1'-0"
BLDG 1 - BASEMENT FIRE ALARM PLAN - RM 063A2
N
1/4" = 1'-0"
BLDG 1 - FIRST FLOOR FIRE ALARM PLAN - RM 1553
N
1/4" = 1'-0"
BLDG 1 - FIRST FLOOR FIRE ALARM PLAN - RM 1764
N
1/4" = 1'-0"
BLDG 1 - SECOND FLOOR FIRE ALARM PLAN - RM 2105
N
1/4" = 1'-0"
BLDG 1 - THIRD FLOOR FIRE ALARM PLAN - RM 33026
N
1/4" = 1'-0"
BLDG 1 - FOURTH FLOOR FIRE ALARM PLAN - RM 43087
N
1/4" = 1'-0"
BLDG 1 - FIFTH FLOOR FIRE ALARM PLAN - RM 528C8
SHEET KEYNOTES
MARK KEYNOTE
1 THIS TELECOMMUNICATION SPACE HAS BEEN
DESIGNATED AS AN ANSI/TIA-942-B RATING 1
SPACE/NON-MISSION CRITICAL AND WILL
THEREFORE NOT REQUIRE SMOKE DETECTION IN
ACCORDANCE WITH VA FIRE PROTECTION DESIGN
MANUAL SECTION 3.7.C.
2 THIS TELECOMMUNICATION SPACE IS TO BE
PROTECTED IN ACCORDANCE WITH THE VA FIRE
PROTECTION DESIGN MANUAL 8TH EDITION AND
HEFP SEP DESIGN ALERT 5 DATED 17 AUGUST 2021.
THIS SPACE HAS BEEN DESIGNATED A
ANSI/TIA-942-B RATING 3/MISSION CRITICAL IN
ACCORDANCE WITH THE OI&T DESIGN GUIDE
VERSION 3.1.
3 AN ASPIRATING SMOKE DETECTION SYSTEM SHALL
BE INSTALLED IN THE SERVER ROOM TO PROVIDE
EARLY WARNING OF A POTENTIAL FIRE EVENT.
SAMPLING PORTS FOR THE ASPIRATING SMOKE
DETECTION SHALL BE INSTALLED AND LOCATED IN
ACCORDANCE WITH NFPA 72. ASPIRATING SMOKE
DETECTION CONTROL UNIT SHALL BE UL LISTED
AND FM APPROVED. THE SYSTEM SHALL MEET THE
REQUIREMENTS OF NFPA 75. REFER TO
INPUT/OUTPUT MATRIX ON SHEET SH001 FOR
SENSITIVITY SETTINGS. SAMPLING PORTS ARE
ONLY TO BE INSTALLED AT THE CEILING. THIS
SPACE DOES NOT HAVE A RAISED FLOOR.
4 ASPIRATING SMOKE DETECTION CONTROL PANEL
SHALL BE POWERED FROM THE EXISTING FIRE
ALARM CONTROL UNIT OR BY A REMOTE POWER
SUPPLY.
5 THIS SPACE WILL BE PROTECTED BY A CLEAN
AGENT FIRE EXTINGUISHMENT SYSTEM TO BE
MONITORED BY THE RSFACU SHOWN ON SHEET
SH001.
No. REVISION DESCRIPTION DATE
TELECOMMUNICATION
WAIVER APPROVED TO
DEFER RENOVATION OF
THIS ROOM.
BID ALTERNATE OPTION 2
UP
TELECOM
ROOM
BASEMENT
FACU
OFFICE
TELECOM
ROOM
TELECOM
ROOM
S
F A
C U
TELECOM
ROOM
TELECOM
ROOM
106 1
TELECOM
ROOM
BASEMENT
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
IN ARCH REG. NO. AR12100034 EXP. 12/31/2021
IN MECH ENGR REG. NO. PE12100220 EXP. 07/31/2022
IN ELEC ENGR REG. NO. PE12100195 EXP. 07/31/2022
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(913) 369-7200
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
HEALTHCARE PLANNER
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 85712
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
/9
/2
:5 :1
P
M
BLDG 2,3,4,5,6 & T4-T6 ENLARGED FIRE
ALARM PLANS
SAB 39 119DBN
BID DOCUMENTS
EHRM INFRASTRUCTURE
UPGRADES FORT WAYNE,
INDIANA
11/12/2021
610A4-21-701
VANIHCS
2121 LAKE AVE,
FORT WAYNE, IN 46805
FA112
1, 2, 3, 4, 5, 6, T4, T5, T6
N
1/4" = 1'-0"
BLDG 3 - BASEMENT FIRE ALARM PLAN - RM 3012
N
1/4" = 1'-0"
BLDG 2 - FIRST FLOOR FIRE ALARM PLAN - RM 2011
N
1/4" = 1'-0"
BLDG 5 - BASEMENT FIRE ALARM PLAN - RM 5014
N
1/4" = 1'-0"
BLDG 6 - FIRST FLOOR FIRE ALARM PLAN - RM 1075
N
1/4" = 1'-0"
BLDG T4-T6 - FIRST FLOOR FIRE ALARM PLAN - RM 1066
N
1/4" = 1'-0"
BLDG 4 - BASEMENT FIRE ALARM PLAN - RM 4013
2, 3, 4, 5, 6, T4, T5, T6
SHEET KEYNOTES
MARK KEYNOTE
1 THIS TELECOMMUNICATION SPACE HAS BEEN
DESIGNATED AS AN ANSI/TIA-942-B RATING 1
SPACE/NON-MISSION CRITICAL AND WILL
THEREFORE NOT REQUIRE SMOKE DETECTION IN
ACCORDANCE WITH VA FIRE PROTECTION DESIGN
MANUAL SECTION 3.7.C.
No. REVISION DESCRIPTION DATE
FX111
FX111
FX111
FX111
FX111
FX111
6FX111
FX111
BLDG 1
N
HAZARD CLASSIFICATION LEGEND
ORDINARY HAZARD 1
(0.15 GPM/FT² OVER 1,500 FT² WITH
250 GPM EXTERIOR HOSE DEMAND)
OUT OF SCOPE AREA
1. ADDITIONS TO EXISTING FIRE PROTECTION WET PIPE
SYSTEM SHALL BE DESIGNED AND INSTALLED IN
ACCORDANCE WITH THE VA FIRE PROTECTION DESIGN
MANUAL - EIGTH EDITION AND NFPA 13-2022.
2. SPRINKLERS AND SPRINKLER PIPING ARE PERMITTED TO
BE INSTALLED IN TELECOMMUNICATION SPACES.
SPRINKLER AND SPRINKLER PIPING ARE REQUIRED TO BE
INSTALLED OUTSIDE OF THE DEDICATED ELECTRICAL
ZONE AS DEFINED BY NFPA 13 SECTION 26.30.2 AND NFPA
70 SECTIONS 110.26 (E) (1) (B) AND 110.26 (E) (1) (C).
3. SPRINKLERS INSTALLED IN TELECOMMUNCIATION SPACES
DESIGNATED AS ANSI/TIA-942-B RATING 1 SPACES/NON-
MISSION CRITICAL SHALL BE QUICK RESPONSE TYPE.
4. SPRINKLERS INSTALLED IN TELECOMMUNCIATION SPACES
DESIGNATED AS ANSI/TIA-942-B RATING 3
SPACES/MISSION CRITICAL SHALL BE FUSIBLE-LINK,
STANDARD-RESPONSE TYPE. THESE SPRINKLERS ARE
REQURIED TO BE INSTALLED WITH PROTECTIVE CAGES AS
REQUIRED BY THE VA FIRE PROTECTION DESIGN MANUAL
SECTION 3.7.B.
5. AS REQUIRED BY VA FIRE PROTECTION DESIGN MANUAL
SECTION 3.7, REFER TO THE LIFE SAFETY SHEETS FOR
LOCATION AND TYPE OF FIRE EXTINGUISHERS.
6. SEISMIC BRACING REQUIRED IN ACCORDANCE WITH NFPA
13.
FIRE SUPPRESSION GENERAL NOTES:
THIS SPACE IS WITHIN THE SCOPE OF WORK OF
THIS PROJECT BUT WILL NOT HAVE ANY FIRE
SPRINKLER SCOPE.
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
IN ARCH REG. NO. AR12100034 EXP. 12/31/2021
IN MECH ENGR REG. NO. PE12100220 EXP. 07/31/2022
IN ELEC ENGR REG. NO. PE12100195 EXP. 07/31/2022
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(913) 369-7200
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
HEALTHCARE PLANNER
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 85712
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
/9
/2
:5 :1
P
M
BLDG 1 OVERALL FIRE SUPPRESSION
HAZARD CLASSIFICATION PLANS
SAB 40 119DBN
BID DOCUMENTS
EHRM INFRASTRUCTURE
UPGRADES FORT WAYNE,
INDIANA
11/12/2021
610A4-21-701
VANIHCS
2121 LAKE AVE,
FORT WAYNE, IN 46805
FX101
1, 2, 3, 4, 5, 6, T4, T5, T6
N
1" = 40'-0"
BLDG 1 - BASEMENT HAZARD CLASSIFICATION OVERALL PLAN1
N
1" = 40'-0"
BLDG 1 - FIRST FLOOR HAZARD CLASSIFICATION OVERALL PLAN2
N
1" = 40'-0"
BLDG 1 - SECOND FLOOR HAZARD CLASSIFICATION OVERALL PLAN3
N
1" = 40'-0"
BLDG 1 - THIRD FLOOR HAZARD CLASSIFICATION OVERALL PLAN4
N
1" = 40'-0"
BLDG 1 - FOURTH FLOOR HAZARD CLASSIFICATION OVERALL PLAN5
N
1" = 40'-0"
BLDG 1 - FIFTH FLOOR HAZARD CLASSIFICATION OVERALL PLAN6
No. REVISION DESCRIPTION DATE
UP U
P
U P
U P
U P
U P
UP
FX112
BLDG 3
BLDG T4
BLDG 6BLDG 5
BLDG 2 BLDG 4
BLDG 1
N
FX112
FX112
FX112
FX112
FX112
FX-112
FX-112
T4 T5 T6
HAZARD CLASSIFICATION LEGEND
ORDINARY HAZARD 1
(0.15 GPM/FT² OVER 1,500 FT² WITH
250 GPM EXTERIOR HOSE DEMAND)
OUT OF SCOPE AREA
1. ADDITIONS TO EXISTING FIRE PROTECTION WET PIPE
SYSTEM SHALL BE DESIGNED AND INSTALLED IN
ACCORDANCE WITH THE VA FIRE PROTECTION DESIGN
MANUAL - EIGTH EDITION AND NFPA 13-2022.
2. SPRINKLERS AND SPRINKLER PIPING ARE PERMITTED TO
BE INSTALLED IN TELECOMMUNICATION SPACES.
SPRINKLER AND SPRINKLER PIPING ARE REQUIRED TO BE
INSTALLED OUTSIDE OF THE DEDICATED ELECTRICAL
ZONE AS DEFINED BY NFPA 13 SECTION 26.30.2 AND NFPA
70 SECTIONS 110.26 (E) (1) (B) AND 110.26 (E) (1) (C).
3. SPRINKLERS INSTALLED IN TELECOMMUNCIATION SPACES
DESIGNATED AS ANSI/TIA-942-B RATING 1 SPACES/NON-
MISSION CRITICAL SHALL BE QUICK RESPONSE TYPE.
4. SPRINKLERS INSTALLED IN TELECOMMUNCIATION SPACES
DESIGNATED AS ANSI/TIA-942-B RATING 3
SPACES/MISSION CRITICAL SHALL BE FUSIBLE-LINK,
STANDARD-RESPONSE TYPE. THESE SPRINKLERS ARE
REQURIED TO BE INSTALLED WITH PROTECTIVE CAGES AS
REQUIRED BY THE VA FIRE PROTECTION DESIGN MANUAL
SECTION 3.7.B.
5. AS REQUIRED BY VA FIRE PROTECTION DESIGN MANUAL
SECTION 3.7, REFER TO THE LIFE SAFETY SHEETS FOR
LOCATION AND TYPE OF FIRE EXTINGUISHERS.
6. SEISMIC BRACING REQUIRED IN ACCORDANCE WITH NFPA
13.
FIRE SUPPRESSION GENERAL NOTES:
THIS SPACE IS WITHIN THE SCOPE OF WORK OF
THIS PROJECT BUT WILL NOT HAVE ANY FIRE
SPRINKLER SCOPE.
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
IN ARCH REG. NO. AR12100034 EXP. 12/31/2021
IN MECH ENGR REG. NO. PE12100220 EXP. 07/31/2022
IN ELEC ENGR REG. NO. PE12100195 EXP. 07/31/2022
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(913) 369-7200
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
HEALTHCARE PLANNER
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 85712
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
/9
/2
:5 :1
P
M
BLDG 2,3,4,5,6 & T4-T6 OVERALL FIRE
SUPPRESSION HAZARD
CLASSIFICATION PLANS
SAB 41 119DBN
BID DOCUMENTS
EHRM INFRASTRUCTURE
UPGRADES FORT WAYNE,
INDIANA
11/12/2021
610A4-21-701
VANIHCS
2121 LAKE AVE,
FORT WAYNE, IN 46805
FX102
1, 2, 3, 4, 5, 6, T4, T5, T6
N
1/16" = 1'-0"
BLDG 2 - FIRST FLOOR HAZARD CLASSIFICATION OVERALL PLAN1
N
1/16" = 1'-0"
BLDG 3 - BASEMENT HAZARD CLASSIFICATION OVERALL PLAN2
N
1/16" = 1'-0"
BLDG 4 - BASEMENT HAZARD CLASSIFICATION OVERALL PLAN3
N
1/16" = 1'-0"
BLDG 5 - BASEMENT HAZARD CLASSIFICATION OVERALL PLAN4
N
1/16" = 1'-0"
BLDG 6 - FIRST FLOOR HAZARD CLASSIFICATION OVERALL PLAN5
N
1/16" = 1'-0"
BLDG T4-T6 - FIRST FLOOR HAZARD CLASSIFICATION OVERALL PLAN6
2, 3, 4, 5, 6, T4, T5, T6
No. REVISION DESCRIPTION DATE
MAIN
SERVER
ROOM
TELECOM
ROOM /
TCB
TELECOM
ROOM
DATA
176A
TELECOM
ROOM
176A
210C
TELECOM
ROOM
210C
TELECOM
ROOM
TELECOM
ROOM
528C
TELECOM
ROOM
528C
HAZARD CLASSIFICATION LEGEND
ORDINARY HAZARD 1
(0.15 GPM/FT² OVER 1,500 FT² WITH
250 GPM EXTERIOR HOSE DEMAND)
OUT OF SCOPE AREA
1. ADDITIONS TO EXISTING FIRE PROTECTION WET PIPE
SYSTEM SHALL BE DESIGNED AND INSTALLED IN
ACCORDANCE WITH THE VA FIRE PROTECTION DESIGN
MANUAL - EIGTH EDITION AND NFPA 13-2022.
2. SPRINKLERS AND SPRINKLER PIPING ARE PERMITTED TO
BE INSTALLED IN TELECOMMUNICATION SPACES.
SPRINKLER AND SPRINKLER PIPING ARE REQUIRED TO BE
INSTALLED OUTSIDE OF THE DEDICATED ELECTRICAL
ZONE AS DEFINED BY NFPA 13 SECTION 26.30.2 AND NFPA
70 SECTIONS 110.26 (E) (1) (B) AND 110.26 (E) (1) (C).
3. SPRINKLERS INSTALLED IN TELECOMMUNCIATION SPACES
DESIGNATED AS ANSI/TIA-942-B RATING 1 SPACES/NON-
MISSION CRITICAL SHALL BE QUICK RESPONSE TYPE.
4. SPRINKLERS INSTALLED IN TELECOMMUNCIATION SPACES
DESIGNATED AS ANSI/TIA-942-B RATING 3
SPACES/MISSION CRITICAL SHALL BE FUSIBLE-LINK,
STANDARD-RESPONSE TYPE. THESE SPRINKLERS ARE
REQURIED TO BE INSTALLED WITH PROTECTIVE CAGES AS
REQUIRED BY THE VA FIRE PROTECTION DESIGN MANUAL
SECTION 3.7.B.
5. AS REQUIRED BY VA FIRE PROTECTION DESIGN MANUAL
SECTION 3.7, REFER TO THE LIFE SAFETY SHEETS FOR
LOCATION AND TYPE OF FIRE EXTINGUISHERS.
6. SEISMIC BRACING REQUIRED IN ACCORDANCE WITH NFPA
13.
FIRE SUPPRESSION GENERAL NOTES:
THIS SPACE IS WITHIN THE SCOPE OF WORK OF
THIS PROJECT BUT WILL NOT HAVE ANY FIRE
SPRINKLER SCOPE.
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
IN ARCH REG. NO. AR12100034 EXP. 12/31/2021
IN MECH ENGR REG. NO. PE12100220 EXP. 07/31/2022
IN ELEC ENGR REG. NO. PE12100195 EXP. 07/31/2022
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(913) 369-7200
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
HEALTHCARE PLANNER
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 85712
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
/9
/2
:5 :2
P
M
BLDG 1 ENLARGED FIRE SUPPRESSION
HAZARD CLASSIFICATION PLANS
SAB 42 119DBN
BID DOCUMENTS
EHRM INFRASTRUCTURE
UPGRADES FORT WAYNE,
INDIANA
11/12/2021
610A4-21-701
VANIHCS
2121 LAKE AVE,
FORT WAYNE, IN 46805
FX111
1, 2, 3, 4, 5, 6, T4, T5, T6
N
1/4" = 1'-0"
BLDG 1 - BASEMENT HAZARD CLASSIFICATION PLAN - RM 0571
N
1/4" = 1'-0"
BLDG 1 - BASEMENT HAZARD CLASSIFICATION PLAN - RM 063A2
N
1/4" = 1'-0"
BLDG 1 - FIRST FLOOR HAZARD CLASSIFICATION PLAN - RM 1553
N
1/4" = 1'-0"
BLDG 1 - FIRST FLOOR HAZARD CLASSIFICATION OVERALL PLAN - RM 1764
N
1/4" = 1'-0"
BLDG 1 - SECOND FLOOR HAZARD CLASSIFICATION PLAN - RM 2105
N
1/4" = 1'-0"
BLDG 1 - THIRD FLOOR HAZARD CLASSIFICATION PLAN - RM 33026
N
1/4" = 1'-0"
BLDG 1 - FOURTH FLOOR HAZARD CLASSIFICATION PLAN - RM 43087
N
1/4" = 1'-0"
BLDG 1 - FIFTH FLOOR HAZARD CLASSIFICATION PLAN - RM528C8
SHEET KEYNOTES
MARK KEYNOTE
1 THIS TELECOMMUNICATION SPACE HAS BEEN
DESIGNATED AS AN ANSI/TIA-942-B RATING 1
SPACE/NON-MISSION CRITICAL IN ACCORDANCE
WITH VA FIRE PROTECTION DESIGN MANUAL
SECTION 3.7.C. THE BUILDING IS PROTECTED WITH A
WET-PIPE FIRE SPRINKLER SYSTEM THROUGHOUT,
THIS SPACE IS CURRENTLY PROTECTED WITH A
QUICK-RESPONSE SPRINKLER IN ACCORDANCE WITH
VA FIRE PROTECTION DESIGN MANUAL SECTION 3.7.
2 THIS TELECOMMUNICATION SPACE IS TO BE
PROTECTED IN ACCORDANCE WITH THE VA FIRE
PROTECTION DESIGN MANUAL 8TH EDITION AND
HEFP SEP DESIGN ALERT 5 DATED 17 AUGUST 2021.
THIS SPACE HAS BEEN DESIGNATED A ANSI/TIA-942-B
RATING 3/MISSION CRITICAL IN ACCORDANCE WITH
THE OI&T DESIGN GUIDE VERSION 3.1.
3 CONTRACTOR TO PROVIDE NEW ISOLATION VALVE
ASSEMBLY TO DESIGNATE ROOM 057 A SINGLE FIRE
SPRINKLER ZONE. CONTRACTOR TO COORDINATE
THE LOCATION OF THE FLOW AND TAMPER
SWITCHES WITH THE FIRE ALARM CONTRACTOR.
VALVE ASSEMBLY SHALL BE INSTALLED ABOVE THE
DROP-IN CEILING AND IN AN ACCESSIBLE
LOCATION.CONTRACTOR TO COORDINATE WITH VA
PERSONNEL ON LOCATION OF CONTROL VALVE FOR
THIS ZONE BEFORE WORK BEGINS. CONTRACTOR TO
COORDINATE WITH VA ON IMPAIRMENT OF FIRE
SPRINKLER SYSTEM DURING CONSTRUCTION.
No. REVISION DESCRIPTION DATE
TELECOMMUNICATION
BID ALTERNATE OPTION 2
WAIVER APPROVED TO
DEFER RENOVATION OF
THIS ROOM.
UP
TELECOM
ROOM
BASEMENT
OFFICE
TELECOM
ROOM
TELECOM
ROOM
BASEMENT
BASEMENT
TELECOM
ROOM
TELECOM
ROOM
TELECOM
ROOM
106 1
HAZARD CLASSIFICATION LEGEND
ORDINARY HAZARD 1
(0.15 GPM/FT² OVER 1,500 FT² WITH
250 GPM EXTERIOR HOSE DEMAND)
OUT OF SCOPE AREA
1. ADDITIONS TO EXISTING FIRE PROTECTION WET PIPE
SYSTEM SHALL BE DESIGNED AND INSTALLED IN
ACCORDANCE WITH THE VA FIRE PROTECTION DESIGN
MANUAL - EIGTH EDITION AND NFPA 13-2022.
2. SPRINKLERS AND SPRINKLER PIPING ARE PERMITTED TO
BE INSTALLED IN TELECOMMUNICATION SPACES.
SPRINKLER AND SPRINKLER PIPING ARE REQUIRED TO BE
INSTALLED OUTSIDE OF THE DEDICATED ELECTRICAL
ZONE AS DEFINED BY NFPA 13 SECTION 26.30.2 AND NFPA
70 SECTIONS 110.26 (E) (1) (B) AND 110.26 (E) (1) (C).
3. SPRINKLERS INSTALLED IN TELECOMMUNCIATION SPACES
DESIGNATED AS ANSI/TIA-942-B RATING 1 SPACES/NON-
MISSION CRITICAL SHALL BE QUICK RESPONSE TYPE.
4. SPRINKLERS INSTALLED IN TELECOMMUNCIATION SPACES
DESIGNATED AS ANSI/TIA-942-B RATING 3
SPACES/MISSION CRITICAL SHALL BE FUSIBLE-LINK,
STANDARD-RESPONSE TYPE. THESE SPRINKLERS ARE
REQURIED TO BE INSTALLED WITH PROTECTIVE CAGES AS
REQUIRED BY THE VA FIRE PROTECTION DESIGN MANUAL
SECTION 3.7.B.
5. AS REQUIRED BY VA FIRE PROTECTION DESIGN MANUAL
SECTION 3.7, REFER TO THE LIFE SAFETY SHEETS FOR
LOCATION AND TYPE OF FIRE EXTINGUISHERS.
6. SEISMIC BRACING REQUIRED IN ACCORDANCE WITH NFPA
13.
FIRE SUPPRESSION GENERAL NOTES:
THIS SPACE IS WITHIN THE SCOPE OF WORK OF
THIS PROJECT BUT WILL NOT HAVE ANY FIRE
SPRINKLER SCOPE.
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
IN ARCH REG. NO. AR12100034 EXP. 12/31/2021
IN MECH ENGR REG. NO. PE12100220 EXP. 07/31/2022
IN ELEC ENGR REG. NO. PE12100195 EXP. 07/31/2022
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(913) 369-7200
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
HEALTHCARE PLANNER
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 85712
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
/9
/2
:5 :2
P
M
BLDG 2,3,4,5,6 & T4-T6 ENLARGED FIRE
SUPPRESSION HAZARD
CLASSIFICATION PLAN
SAB 43 119DBN
BID DOCUMENTS
EHRM INFRASTRUCTURE
UPGRADES FORT WAYNE,
INDIANA
11/12/2021
610A4-21-701
VANIHCS
2121 LAKE AVE,
FORT WAYNE, IN 46805
FX112
1, 2, 3, 4, 5, 6, T4, T5, T6
N
1/4" = 1'-0"
BLDG 3 - BASEMENT HAZARD CLASSIFICATION PLAN - RM 3012
SHEET KEYNOTES
MARK KEYNOTE
1 THIS TELECOMMUNICATION SPACE HAS BEEN
DESIGNATED AS AN ANSI/TIA-942-B RATING 1
SPACE/NON-MISSION CRITICAL IN ACCORDANCE
WITH VA FIRE PROTECTION DESIGN MANUAL
SECTION 3.7.C. THE BUILDING CURRENTLY DOES NOT
HAVE A FIRE SPRINKLER SYSTEM INSTALLED, THE
DIRECTION PROVIDED BY THE VA IS THAT A NEW
FIRE SPRINKLER SYSTEM IS NOT REQUIRED TO BE
INSTALLED TO PROTECT THIS SPACE. THE BUILDING
WILL REMAIN UNSPRINKLERED.
2 THIS TELECOMMUNICATION SPACE HAS BEEN
DESIGNATED AS AN ANSI/TIA-942-B RATING 1
SPACE/NON-MISSION CRITICAL IN ACCORDANCE
WITH VA FIRE PROTECTION DESIGN MANUAL
SECTION 3.7.C. THIS SPACE DOES NOT HAVE
EXISTING FIRE SPRINKLER PROTECTION.
CONTRACTOR TO MODIFY THE EXISTING BUILDING
FIRE SPRINKLER SYSTEM TO PROVIDE FIRE
SPRINKLER PROTECTION IN THIS SPACE.
CONTRACTOR TO ROUTE PIPING TO AVOID
DEDICATED ELECTRICAL SPACE.
3 THIS TELECOMMUNICATION SPACE HAS BEEN
DESIGNATED AS AN ANSI/TIA-942-B RATING 1
SPACE/NON-MISSION CRITICAL IN ACCORDANCE
WITH VA FIRE PROTECTION DESIGN MANUAL
SECTION 3.7.C. THERE IS NOT AN EXISTING
SPRINKLER SYSTEM IN THIS PORTION OF BUILDING 2.
THE INTENT IS NOT TO EXPAND THE EXISTING
SPRINKLER SYSTEM THAT IS IN THE OTHER PORTION
OF BUILDING 2 TO THIS AREA.
N
1/4" = 1'-0"
BLDG 2 - FIRST FLOOR HAZARD CLASSIFICATION PLAN - RM 2011
N
1/4" = 1'-0"
BLDG 4 - BASEMENT HAZARD CLASSIFICATION PLAN - RM 4013
N
1/4" = 1'-0"
BLDG 5 - BASEMENT HAZARD CLASSIFICATION PLAN - RM 5014
N
1/4" = 1'-0"
BLDG 6 - FIRST FLOOR HAZARD CLASSIFICATION PLAN - RM 1075
N
1/4" = 1'-0"
BLDG T4-T6 - FIRST FLOOR HAZARD CLASSIFICATION PLAN - RM 1066
2, 3, 4, 5, 6, T4, T5, T6
No. REVISION DESCRIPTION DATE
CLEAN AGENT LEGEND
SYMBOL DESCRIPTION
F FIRE ALARM MANUAL PULL STATION
FIRE ALARM HORN/STROBE COMBINATION DEVICE
SUPPRESSION HORN
VS VALVE SUPERVISORY SWITCH
WF WATER FLOW SWITCH
AIM ADDRESSABLE INPUT MODULE
AOM ADDRESSABLE OUTPUT MODULE
SYMBOL MODIFIERS
nCD CANDELA RATING
CA CLEAN AGENT MANUAL PULL STATION
CA CLEAN AGENT ABORT STATION
KM KEYED MAINTENANCE SWITCH
CLEAN AGENT DISCHARGE STROBEB
CLEAN AGENT PRE-DISCHARGE STROBER
s
ASD
ASPIRATING SMOKE DETECTOR
SOV
CA
CLEAN AGENT ACTUATOR
DISCRETE OUTPUT - DRY CONTACTCT
PS PRESSURE SWITCH
ASPIRATING SMOKE DETECTOR CONTROL PANEL
SURGE PROTECTIVE DEVICE
ASD
SPD
RSFACU RELEASING SERVICE FIRE ALARM CONTROL UNIT
F
SUPRESSION BELL
WARNING!
LEAVE AREA IMMEDIATELY
WHEN ALARM SOUNDS
NOVEC 1230
BEING RELEASED
WARNING!
THIS AREA IS PROTECTED BY A
NOVEC 1230 EXTINGUISHING
SYSTEM. DO NOT ENTER
WITHOUT AUTHORIZATION
DURING OR AFTER DISCHARGE.
PUSH
PULL
PUSH/HOLD
SUPPRESSION SYSTEM ABORT
FIRE
SUPPRESSION
MANUAL
RELEASE
FIRE
SUPPRESSION
ABORT
PUSH BUTTON
AND HOLD
AIM AIM
PS VS
AIM
CT
AIM
CT
AIM
CT
RSFACU
S U
P E
R V
IS
O
R Y
T R
O U
B L E
A L A
R M
SPD
120VAC DEDICATED
BRANCH CIRCUIT
s CA CA
B R
KM
SOV
CA
AIM
CT
AIM
CT
AIM
CT
A L E
R T
T R
O U
B L E
A L A
R M
AIM
CT
A L A
R M
ASD
s
ASD
ASPIRATING SMOKE
DETECTION SYSTEM
TO PRIMARY
POWER
SUPPLY
SEE SHEET
FA-001 FOR
CONTINUATION
F
MAIN
SERVER
ROOM
VS
PS
KM
CACA ASD
S
ASD
SOV
CA
30cd
B c d
B c d
R
75cd
R
75cd
B
F
RSFACU
15 ASD DETECTOR - DISABLE • • • •
• PERFORM OPERATION/REPORT DEVICE STATUS
A B C D E F G H I J K L M N N O P Q R S T U
12 SCP SYSTEM LOW BATTERY • • •
13 OPEN CIRCUIT OR GROUND FAULT • • •
14 CLASS B NOTIFICATION CIRCUIT (NAC) - SHORT • • •
15 LOCAL MANUAL ACTUATOR ON TANK • • • • • • • • • •
13 ASD DETECTOR - URGENT FAULT • • • •
14 ASD DETECTOR - MINOR FAULT • • • •
9 MAINTENANCE SWITCH • • • •
10 SOLENOID SUPERVISORY SWITCH • • • •
11 ACTUATOR PLACEMENT INDICATOR • • • •
12 DISCHARGE PRESSURE SWITCH • • • • • • • •
13 LOW PRESSURE SWITCH • • • •
11 SCP AC POWER FAILURE • • •
3 ASD DETECTOR - FIRE 1 - 1.0% OBS/FT (w/ 15 SECOND DELAY) • • • • • • • • 4 ASD DETECTOR - FIRE 2 - 3.0% OBS/FT (w/ 30 SECOND DELAY) • • • • • • • • •
5 COMPLETION OF 30 SECOND COUNTDOWN TIMER AFTER FIRE 2 • • •
6 ABORT SWITCH - CONTINUOUSLY HELD DOWN • • • •
7 MANUAL RELEASING PULL STATION • • • • • • • • •
8 AFTER 10 SECOND AGENT RELEASE DELAY • • •
AT 4007ES SCP NOTIFICATION AND FIRE SAFETY CONTROLS
S Y
S T
E M
O U
T P
U T
S
A C
T U
A T
E C
O M
M O
N A
L A
R M
S
IG
N A
L I
N D
IC
A
T O
R
A C
T U
A T
E A
U D
IB
L E
A L A
R M
S
IG
N A
L
A C
T U
A T
E C
O M
M O
N S
U P
E R
V
IS
O R
Y S
IG
N
A L I
N D
IC
A
T O
R
A C
T U
A T
E A
U D
IB
L E
S U
P E
R V
IS
O
R Y
S
IG
N A
L
A C
T U
A T
E C
O M
M O
N T
R O
U B
L E
S
IG
N A
L I
N D
IC
A
T O
R
A C
T U
A T
E A
U D
IB
L E
T R
O U
B L E
S
IG
N A
L
D
IS
P L A
Y C
H A
N G
E O
F S
T A
T U
S
T R
A N
S M
IT
A
L A
R M
S
IG
N A
L T
O M
A
IN
F A
C
IL
IT
Y
F A
C P
T R
A N
S M
IT
S
U P
E R
V
IS
O R
Y S
IG
N
A L T
O M
A
IN
I F
A C
IL
IT
Y F
A C
P
T R
A N
S M
IT
T
R O
U B
L E
S
IG
N A
L T
O M
A
IN
F A
C
IL
IT
Y
F A
C P
A C
T U
A T
E S
U P
P R
E S
S
IO
N B
E L L
A C
T U
A T
E S
U P
P R
E S
S
IO
N H
O R
N A
T
B
P M
A C
T U
A T
E S
U P
P R
E S
S
IO
N H
O R
N A
T S
T E
A D
Y T
O N
E
A C
T U
A T
E P
R E
-D
IS
C H
A R
G E
S T
R O
B E
A C
T U
A T
E S
U P
P R
E S
S
IO
N S
T R
O B
E
B E
G
IN
S
E C
O N
D C
O U
N T
D O
W N
A G
E N
T R
E L E
A S
E I
N T
O A
L L H
A Z
A R
D S
P A
C E
S
B E
G
IN
S
E C
O N
D A
G E
N T
R E
L E
A S
E D
E L A
Y
H V
A C
S H
U T
D O
W N
D A
M P
E R
C L O
S U
R E
S
IL
E N
C E
S S
U P
P R
E S
S
IO
N B
E L L
S T
O P
S F
IR
E
-S
E C
O N
D C
O U
N T
D O
W N
T
IM
E R
SYSTEM INPUTS A B C D E F G H I J K L M N N O P Q R S T U
1 ASD DETECTOR - ALERT - 0.2% OBS/FT (w/ 30 SECOND DELAY) • • • • 2 ASD DETECTOR - ACTION - 0.6% OBS/FT (w/ 30 SECOND DELAY) • • • • th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
IN ARCH REG. NO. AR12100034 EXP. 12/31/2021
IN MECH ENGR REG. NO. PE12100220 EXP. 07/31/2022
IN ELEC ENGR REG. NO. PE12100195 EXP. 07/31/2022
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(913) 369-7200
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
HEALTHCARE PLANNER
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 85712
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
/9
/2
:5 :2
P
M
CLEAN AGENT NOTES, DETAILS, AND
PLAN
SAB 44 119DBN
BID DOCUMENTS
EHRM INFRASTRUCTURE
UPGRADES FORT WAYNE,
INDIANA
11/12/2021
610A4-21-701
VANIHCS
2121 LAKE AVE,
FORT WAYNE, IN 46805
SH001
1, 2, 3, 4, 5, 6, T4, T5, T6
SCALE: NONE
CLEAN AGENT SIGNAGE2 SCALE: NONE
CLEAN AGENT START/STOP STATIONS1SCALE: NONE
CLEAN AGENT TYPICAL RISER DIAGRAM3
CLEAN AGENT GENERAL NOTES:
1. PROVIDE A NEW CLEAN AGENT (NOVEC 1230) FIRE
EXTINGUISHMENT SYSTEM THAT IS DESIGNED AND INSTALLED
IN ACCORDANCE WITH NFPA 2001.
2. CLEAN AGENT TO BE USED IS NOVEC 1230 (FK-5-1-12) AT
DESIGN CONCENTRATION OF 4.5%, AS DIRECTED BY OWNER.
3. ALL PIPE AND FITTINGS SHALL BE IN ACCORDANCE WITH THE
REQUIREMENTS OF NFPA 2001.
4. ALL PIPE AN FITTINGS SHALL BE BLACK SCALE FREE STEEL
CONFORMING TO ONE OF THE FOLLOWING REQUIREMENTS:
A. ASTM A-106, SEAMLESS, GRADE A OR B SCHEDULE 40
THROUGH 8 INCHES
B. ASTM A-53, SEAMLESS, GRADE A OR B SCHEDULE 40
THROUGH 8 INCHES
C. ASTM A-53 ERW, GRADE A OR B SHALL NOT BE USED
WITHOUT PRIOR WRITTEN APPROVAL FROM AHJ.
D. ASTM A-53, CLASS F AND ASTM A-120 SHALL NOT BE USED.
5. STENCILED PIPE IDENTIFICATION SHALL NOT BE PAINTED OVER,
CONCEALED OR REMOVED PRIOR TO APPROVAL BY AHJ.
6. ALL FITTINGS SHALL BE BLACK MALLEABLE IRON OR FORGED
STEEL CONFORMING TO THE FOLLOWING REQUIREMENTS:
A. CLASS 300 MALLEABLE IRON THROUGH 3 INCHES
B. 1000# RATED FORGED STEEL GREATER THAN 3 INCHES
C. ALL GROOVED FITTINGS MUST BE UL LISTED AND
CONFORM TO THE PRESSURE REQUIREMENTS OUTLINED
IN NFPA 2001
D. CAST IRON FITTINGS ARE NOT ACCEPTABLE.
7. ALL PIPE ENDS SHALL BE REAMED AFTER CUTTING.
8. EACH PIPE SECTION SHALL BE CLEANED INTERNALLY AFTER
PREPARATION AND BEFORE ASSEMBLY BY SWABBING WITH A
SUITABLE NONFLAMMABLE CLEANER.
9. TEFLON THREAD SEAL TAPE SHALL BE USED ON ALL MALE
THREADED JOINTS ONLY. ALL GROOVED COUPLING GASKETS
SHALL BE LUBRICATED PER THE MANUFACTURER'S
SPECIFICATIONS.
10. ALL PIPING SHALL BE RIGIDLY AND SECURELY ANCHORED TO
BUILDING STRUCTURE USING U.L. APPROVED HANGERS.
11. ALL STORAGE CONTAINERS SHALL BE MOUNTED PLUMB AND
LEVEL AND SECURELY ANCHORED TO BUILDING STRUCTURE.
12. PRIOR TO INSTALLATION OF NOZZLES, THE PIPING SYSTEM
SHALL BE PNEUMATICALLY TESTED PER MANUFACTURERS
INSTRUCTIONS.
13. REFER TO ARCHITECTURAL SIGNAGE DETAILS FOR MATERIAL,
FINISH COLOR, ETC. OF CLEAN AGENT SIGNAGE AND
START/STOP STATIONS.
SAMPLING PIPE NETWORK REQUIREMENTS
(ASD):
1. ALL PIPING SHALL BE CPVC.
2. ATTACH PIPES TO STRUCTURE AS APPLICABLE, USING
STANDARD PIPE SECURING HARDWARE AT INTERVALS OF NO
MORE THAN 5 FEET.
3. ALL CONNECTIONS AND JOINTS SHALL BE MADE WITH
STANDARD CONNECTIONS DESIGNED TO BE COMPATIBLE WITH
PIPE MATERIAL.
4. ALL JOINTS SHALL BE AIR TIGHT TO PREVENT INFILTRATION AT
OTHER THAN SAMPLING PORT LOCATIONS.
5. COORDINATE THE LOCATION OF PIPING AND SAMPLING PORTS
WITH OTHER TRADES TO PERMIT PROPER ACCESS TO ALL
EQUIPMENT.
6. THE SAMPLING PIPE NETWORK SHALL BE CLEARED OF ALL DIRT
AND DEBRIS BY RUNNING AIR THROUGH THE PIPE NETWORK
FOR A MINIMUM OF 30 MINUTES PRIOR TO CONNECTION AND
OPERATION OF THE SYSTEM.
7. ALL PIPING SHALL BE LABELED AT EACH SAMPLING PORT AND
AT 20 FOOT INTERVALS USING MANUFACTURERS
IDENTIFICATION LABELS.
8. DO NOT GLUE PIPE(S) INTO SOCKET(S) OF INLET MANIFOLD.
PIPES MUST BE INSERTED INTO THE SOCKET(S) AT A MINIMUM
OF 1/2 INCH.
9. SENSITIVITY SETTINGS SHOWN IN THE MATRIX SHALL BE
ACHIEVED AT THE END OF EACH SAMPLING PORT.
N
1/4" = 1'-0"
BLDG 1 - CLEAN AGENT PLAN - RM 0574
SCALE: NONE
CLEAN AGENT INPUT/OUTPUT MATRIX5
SHEET KEYNOTES
MARK KEYNOTE
1 SPACE TO BE PROTECTED WITH A CLEAN AGENT
FIRE EXTINGUISHMENT SYSTEM. PROTECTION TO
INCLUDE ABOVE AND BELOW THE RAISED FLOOR.
AIR-ASPIRATING SMOKE DETECTION SAMPLING
PORTS TO BE PROVIDED ABOVE AND BELOW THE
RAISED FLOOR.
No. REVISION DESCRIPTION DATE
| Sheets |
| FA001 - BLDG 1 FIRE ALARM GENERAL NOTES, DIAGRAMS, AND LEGEND |
| FA101 - BLDG 1 OVERALL FIRE ALARM PLANS |
| FA102 - BLDG 2,3,4,5,6 & T4-T6 OVERALL FIRE ALARM PLANS |
| FA111 - BLDG 1 ENLARGED FIRE ALARM PLANS |
| FA112 - BLDG 2,3,4,5,6 & T4-T6 ENLARGED FIRE ALARM PLANS |
| FX101 - BLDG 1 OVERALL FIRE SUPPRESSION HAZARD CLASSIFICATION PLANS |
| FX102 - BLDG 2,3,4,5,6 & T4-T6 OVERALL FIRE SUPPRESSION HAZARD CLASSIFICATION PLANS |
| FX111 - BLDG 1 ENLARGED FIRE SUPPRESSION HAZARD CLASSIFICATION PLANS |
| FX112 - BLDG 2,3,4,5,6 & T4-T6 ENLARGED FIRE SUPPRESSION HAZARD CLASSIFICATION PLAN |
| SH001 - CLEAN AGENT NOTES, DETAILS, AND PLAN |