Attachment 5 Drawing 05_FIRE PROTECTION_BID SET.pdf

PDF 4 MB Posted

Attached to
Y1DA--610A4-21-701 EHRM Infrastructure Upgrades Construction Ft. Wayne Federal contract opportunity
Solicitation number
36C77622B0028
Issued by
Department of Veterans Affairs Technology Acquisition Center Austin

About this file

This document package includes construction drawings and specifications for fire protection system upgrades at several Department of Veterans Affairs buildings in Fort Wayne, Indiana. The scope of work involves expanding existing fire alarm, fire suppression, and clean agent fire extinguishing systems into telecommunications spaces to comply with NFPA and VA requirements. Drawings show fire alarm device locations and wiring, hazard classifications, sprinkler scope, and a NOVEC 1230 clean agent system for the main server room. General notes provide design and installation standards. The related solicitation is for the EHRM Infrastructure Upgrades Construction project at the VA Health Care System in Fort Wayne. The solicitation number is 36C77622B0028.

View the file

Other files for this federal contract opportunity

Other files attached to Y1DA--610A4-21-701 EHRM Infrastructure Upgrades Construction Ft. Wayne, newest first.
File Type Posted
Attachment 2 EHRM ICRA Form - Ft. Wayne.pdf PDF
Attachment 1 Technical Question Responses - Ft Wayne EHRM 20220722.pdf PDF
36C77622B0028 0008.pdf PDF
36C77622B0028 0007.pdf PDF
0006 Attachment 1 Technical Question Responses.pdf PDF
36C77622B0028 0006.pdf PDF
36C77622B0028 0005.pdf PDF
36C77622B0028 0004.pdf PDF
36C77622B0028 0003.pdf PDF
36C77622B0028 0002.pdf PDF
36C77622B0028 0001.pdf PDF
Attachment 15 CONTRACTOR SAFETY AND ENVIRONMENTAL RECORD EVALUATION FORM.docx DOCX document
Attachment 8 Drawing 08a_TELECOMMUNICATION.pdf PDF
Attachment 4 Drawing 04_ARCHITECTURAL_BID SET.pdf PDF
Attachment 1 Drawing 01_GENERAL_BID SET.pdf PDF
Attachment 14 COVID-19 Safety Protocols 12-14-21.pdf PDF
36C77622B0028_1.docx DOCX document
Attachment 12 610A4-21-701 Specifications Bound.pdf PDF
Attachment 3 Drawing 03_ENVIRONMENTAL.pdf PDF
Attachment 9 Drawing 08b_TELECOMMUNICATION.pdf PDF
Attachment 17 ELECTRICAL BID SET.pdf PDF
Attachment 16 Limitations on Subcontracting - Construction.docx DOCX document
Attachment 13 DBA Wage Determination - Ft Wayne 20220602.pdf PDF
Attachment 11 EHRM Ft Wayne Bid Documents Narrative.pdf PDF
Attachment 10 Drawing 09_SECURITY.pdf PDF
Attachment 7 Drawing 07_ELECTRICAL_BID SET.pdf PDF
Attachment 6 Drawing 06_MECHANICAL_BID SET.pdf PDF
Attachment 2 Drawing 02_CIVIL_BID SET.pdf PDF
Show all 28

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FACU

SPD

NOTES:

1. TO DEDICATED 120VAC BRANCH CIRCUIT

2. EXISTING FIRE ALARM CONTROL UNIT

3. THIS RISER DIAGRAM IS INTENDED ONLY TO CAPTURE THE SYSTEM DESIGN INTENT, PANEL

CONNECTIONS, AND GENERAL CIRCUIT ROUTING REQUIREMENTS. EXACT QUANTITIES AND

TYPES OF DEVICES NECESSARY TO ACCOMPLISH THE DESIGN GOALS ARE NOT INDICATED.

THE INTENT OF THIS RISER DIAGRAM IS TO INDICATE THE GENERAL SYSTEM CONFIGURATION

AFTER SUCCESSFUL COMPLETION OF THE PROJECT.

2 3

BASEMENT

WF VS

AIM AIMAIM

ASD

AOM

AHU

AOM

SEE SHEET SH-001

FOR CONTINUATION

AIM

CT

AIM

CT

AIM

CT

S U

P E

R V

IS

O

R Y

T R

O U

B L E

A L A

R M

RSFACU

SEE SHEET SH-001

FOR CONTINUATION

S

FIRE ALARM LEGEND

OUT OF SCOPE AREA

1. THE SCOPE OF THIS PROJECT IS TO BRING

TELECOMMUNCIATION SPACES WITHIN THE EHRM

PROGRAM INTO COMPLIANCE WITH CURRENT

CODE REQUIREMENTS. THIS INCLUDES THE

EXPANSION OF EXISTING FIRE ALARM SYSTEMS

INTO THE SCOPE OF WORK AREAS. EXPANSION OF

THE EXISTING FIRE ALARM SYSTEM SHALL BE

DESIGNED AND INSTALLED IN ACCORDANCE WITH

THE VA FIRE PROTECTION DESIGN MANUAL-EIGHTH

EDITION, NFPA 70-2020, AND NFPA 72-2022. FIRE

ALARM CONTRACTOR IS RESPONSIBLE FOR

DEVELOPING CALCULATIONS AND SHOP

DRAWINGS.

2. SYSTEM MODIFICATION SHALL BE CONSIDERED

WITH RESPECT TO FLOOR PLAN CHANGES.

3. NOTIFICATION APPLIANCES SHALL MATCH

EXISTING MANUFACTURER AND MODEL OR BE

COMPATIBLE WITH THE EXISTING SYSTEM.

SPEAKERS AND STROBES SHALL BE WHITE FINISH

TO MATCH EXISTING DEVICES.

4. CONTRACTOR SHALL COORDINATE AND VERIFY

DEMOLITION OR RELOCATION OF ITEMS WITH

OWNER PRIOR TO COMMENCING WORK TO

PREVENT INTERRUPTION OF SERVICE.

5. FIRE ALARM INPUT/OUTPUT MATRIX IS PROVIDED

FOR NEW DEVICES LOCATED IN THE PROJECT

AREA. ALL OTHER INPUTS SHALL MATCH EXISTING

PANEL.

FIRE ALARM GENERAL NOTES:

SPD EXISTING SURGE PROTECTIVE DEVICE

FACU EXISTING FIRE ALARM CONTROL UNIT

WF NEW WATERFLOW DEVICE

VS NEW VALVE SUPERVISORY SWITCH

AIM NEW ADDRESSABLE INPUT MODULE

ASPIRATING SMOKE DETECTION SYSTEM PANELASD

AOM NEW ADDRESSABLE OUTPUT MODULE

AIR HANDLING UNIT CONTROLLERAHU

CT

RELEASING SERVICE FIRE ALARM CONTROL UNITRSFACU

DISCRETE OUTPUT - DRY CONTACT

1 WATERFLOW/PRESSURE SWITCH X X X X X X X X 1

4 RSFACU - CLEAN AGENT COMMON SUPERVISORY X X X 4

5 CONTROL VALVE SUPERVISORY SWITCH X X X 5

12 RSFACU - CLEAN AGENT COMMON TROUBLE X X X 12

13 ANY OTHER SYSTEM TROUBLE X X X 13

SYSTEM OUTPUTS

SYSTEM INPUTS

F A

C U

A N

N U

N C

IA

T

IO

N

A C

T

IV

A T

E C

O M

M O

N A

L A

R M

S

IG

N A

L I

N D

IC

A

T O

R

A C

T

IV

A T

E A

U D

IB

L E

A L A

R M

S

IG

N A

L

A C

T

IV

A T

E C

O M

M O

N S

U P

E R

V

IS

O R

Y S

IG

N

A L I

N D

IC

A

T O

R

A C

T

IV

A T

E A

U D

IB

L E

S U

P E

R V

IS

O

R Y

S

IG

N A

L

A C

T

IV

A T

E C

O M

M O

N T

R O

U B

L E

S

IG

N A

L I

N D

IC

A

T O

R

A C

T

IV

A T

E A

U D

IB

L E

T R

O U

B L E

S

IG

N A

L

D

IS

P L A

Y /P

R

IN

T C

H A

N G

E O

F S

T A

T U

S

N O

T

IF

IC

A

T

IO

N

A C

T

IV

A T

E T

E M

P O

R A

L

A L E

R T

T O

N E

A N

D P

R E

-R E

C O

R D

E D

F

IR

E

V

A C

U A

T

IO

N M

E S

S A

G E

T H

R O

U G

H O

U T

T H

E A

S S

O C

IA

T

E D

Z O

N E

A C

T

IV

A T

E S

T R

O B

E S

T H

R O

U G

H O

U T

T H

E A

S S

O C

IA

T

E D

Z O

N E

A C

T

IV

A T

E P

R E

-R E

C O

R D

E D

S T

A F

F A

L E

R T

M E

S S

A G

E T

H R

O U

G H

O U

T T

H

B

U

IL

D

IN

G

N O

T

IF

Y S

U P

E R

V

IS

IN

G

S T

A T

IO

N

/F

IR

E D

E P

A R

T M

E N

T

A U

X

IL

IA

R

Y F

U N

C T

IO

N

S

S H

U T

D O

W N

A S

S O

C

IA

T E

D A

IR

H

A N

D L

IN

G U

N

IT

A C

T

IV

A T

E E

L E

C T

R

IC

A L D

IS

C

O N

N E

C T

O F

E Q

U

IP

M E

N T

I N

I T

E S

P A

C E

S

ALARM CONDITIONS A B C D E F G H I J K L M

2 RSFACU - CLEAN AGENT SYSTEM ACTIVATION X X X X X X 2

SUPERVISORY CONDITIONS A B C D E F G H I J K L M

3 SMOKE DETECTOR - DUCT TYPE X X X X 3

A B C D E F G H I J K L M

X PERFORM OPERATION/REPORT DEVICE STATUS

TROUBLE CONDITIONS A B C D E F G H I J K L M

6 AC POWER FAILURE X X X 6

7 LOW BATTERY X X X 7

8 OPEN CIRCUIT X X X 8

9 GROUND FAULT X X X 9

10 NOTIFICATION APPLIANCE CIRCUIT SHORT X X X 10

11 REMOTE POWER SUPPLY COMMON TROUBLE X X X 11

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

IN ARCH REG. NO. AR12100034 EXP. 12/31/2021

IN MECH ENGR REG. NO. PE12100220 EXP. 07/31/2022

IN ELEC ENGR REG. NO. PE12100195 EXP. 07/31/2022

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC / PLUMB / TECH ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(913) 369-7200

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

HEALTHCARE PLANNER

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 85712

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

/9

/2

:5 :1

P

M

BLDG 1 FIRE ALARM GENERAL NOTES,

DIAGRAMS, AND LEGEND

SAB 35 119DBN

BID DOCUMENTS

EHRM INFRASTRUCTURE

UPGRADES FORT WAYNE,

INDIANA

11/12/2021

610A4-21-701

VANIHCS

2121 LAKE AVE,

FORT WAYNE, IN 46805

FA001

1, 2, 3, 4, 5, 6, T4, T5, T6

SCALE: NONE

BLDG 1 - FIRE ALARM RISER DIAGRAM1SCALE: NONE

BLDG 1 - FACU INPUT/OUTPUT MATRIX2

NOTES:

1. THIS INPUT/OUTPUT MATRIX IS REPRESENTATIVE OF THE SCOPE OF WORK OF THIS PROJECT IN BUILDING 1. NOT ALL EXISTING

INPUTS AND OUTPUTS ARE REPRESENTED ON THIS MATRIX. PLEASE REFER TO THE EXISTING FIRE ALARM PANEL LOCATED IN

BUILDING 1 FOR ALL OF THE INPUTS AND OUTPUTS.

2. ELECTRICAL DISCONNECT SHALL ONLY BE INITIATED FOR ALARM CONDITIONS DETECTED IN THE SERVER ROOM 057.

No. REVISION DESCRIPTION DATE

TELECOMMUNICATION

FA111

FA111

2 SH001

FA111

FA111

FA111

FA111

FA111

FA111

BLDG 1

N

HATCHING LEGEND

THIS AREA IS NOT WITHIN THE

SCOPE OF THIS PROJECT.

THIS AREA IS WITHIN THE SCOPE

OF THIS PROJECT.

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

IN ARCH REG. NO. AR12100034 EXP. 12/31/2021

IN MECH ENGR REG. NO. PE12100220 EXP. 07/31/2022

IN ELEC ENGR REG. NO. PE12100195 EXP. 07/31/2022

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC / PLUMB / TECH ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(913) 369-7200

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

HEALTHCARE PLANNER

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 85712

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

/9

/2

:5 :1

P

M

BLDG 1 OVERALL FIRE ALARM PLANS

SAB 36 119DBN

BID DOCUMENTS

EHRM INFRASTRUCTURE

UPGRADES FORT WAYNE,

INDIANA

11/12/2021

610A4-21-701

VANIHCS

2121 LAKE AVE,

FORT WAYNE, IN 46805

FA101

1, 2, 3, 4, 5, 6, T4, T5, T6

N

1" = 40'-0"

BLDG 1 - BASEMENT FIRE ALARM OVERALL PLAN1

N

1" = 40'-0"

BLDG 1 - FIRST FLOOR FIRE ALARM OVERALL PLAN2

N

1" = 40'-0"

BLDG 1 - SECOND FLOOR FIRE ALARM OVERALL PLAN3

N

1" = 40'-0"

BLDG 1 - THIRD FLOOR FIRE ALARM OVERALL PLAN4

N

1" = 40'-0"

BLDG 1 - FOURTH FLOOR FIRE ALARM OVERALL PLAN5

N

1" = 40'-0"

BLDG 1 - FIFTH FLOOR FIRE ALARM OVERALL PLAN6

No. REVISION DESCRIPTION DATE

UP U

P

U P

U P

U P

U P

UP

FA112

BLDG 3

BLDG T4

BLDG 6BLDG 5

BLDG 2 BLDG 4

BLDG 1

N

FA112

FA112

FA112

FA112

FA112

-6

FA-112 ---

-6

FA-112

T4 T5 T6

HATCHING LEGEND

THIS AREA IS NOT WITHIN THE

SCOPE OF THIS PROJECT.

THIS AREA IS WITHIN THE SCOPE

OF THIS PROJECT.

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

IN ARCH REG. NO. AR12100034 EXP. 12/31/2021

IN MECH ENGR REG. NO. PE12100220 EXP. 07/31/2022

IN ELEC ENGR REG. NO. PE12100195 EXP. 07/31/2022

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC / PLUMB / TECH ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(913) 369-7200

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

HEALTHCARE PLANNER

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 85712

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

/9

/2

:5 :1

P

M

BLDG 2,3,4,5,6 & T4-T6 OVERALL FIRE

ALARM PLANS

SAB 37 119DBN

BID DOCUMENTS

EHRM INFRASTRUCTURE

UPGRADES FORT WAYNE,

INDIANA

11/12/2021

610A4-21-701

VANIHCS

2121 LAKE AVE,

FORT WAYNE, IN 46805

FA102

1, 2, 3, 4, 5, 6, T4, T5, T6

N

1/16" = 1'-0"

BLDG 2 - FIRST FLOOR FIRE ALARM OVERALL PLAN1

N

1/16" = 1'-0"

BLDG 3 - BASEMENT FIRE ALARM OVERALL PLAN2

N

1/16" = 1'-0"

BLDG 4 - BASEMENT FIRE ALARM OVERALL PLAN3

N

1/16" = 1'-0"

BLDG 5 - BASEMENT FIRE ALARM OVERALL PLAN4

N

1/16" = 1'-0"

BLDG 6 - FIRST FLOOR FIRE ALARM OVERALL PLAN5

N

1/16" = 1'-0"

BLDG T4-T6 - FIRST FLOOR FIRE ALARM OVERALL PLAN6

2, 3, 4, 5, 6, T4, T5, T6

No. REVISION DESCRIPTION DATE

MAIN

SERVER

ROOM

ASD

AOM ITE SPACE ELECTRICAL

DISCONNECT

VS WF

3 4 5

REFER TO SHEET SH001 FOR

ADDITIONAL FIRE ALARM

DETAIL IN THIS SPACE.

S

CRU-1-057

S

CRU-2-057

RSFACU

TELECOM

ROOM /

TCB

TELECOM

ROOM

176A

TELECOM

ROOM

176A

210C

TELECOM

ROOM

210C

TELECOM

ROOM

TELECOM

ROOM

528C

TELECOM

ROOM

528C th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

IN ARCH REG. NO. AR12100034 EXP. 12/31/2021

IN MECH ENGR REG. NO. PE12100220 EXP. 07/31/2022

IN ELEC ENGR REG. NO. PE12100195 EXP. 07/31/2022

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC / PLUMB / TECH ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(913) 369-7200

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

HEALTHCARE PLANNER

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 85712

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

/9

/2

:5 :1

P

M

BLDG 1 ENLARGED FIRE ALARM PLANS

SAB 38 119DBN

BID DOCUMENTS

EHRM INFRASTRUCTURE

UPGRADES FORT WAYNE,

INDIANA

11/12/2021

610A4-21-701

VANIHCS

2121 LAKE AVE,

FORT WAYNE, IN 46805

FA111

1, 2, 3, 4, 5, 6, T4, T5, T6

N

1/4" = 1'-0"

BLDG 1 - BASEMENT FIRE ALARM PLAN - RM 0571

N

1/4" = 1'-0"

BLDG 1 - BASEMENT FIRE ALARM PLAN - RM 063A2

N

1/4" = 1'-0"

BLDG 1 - FIRST FLOOR FIRE ALARM PLAN - RM 1553

N

1/4" = 1'-0"

BLDG 1 - FIRST FLOOR FIRE ALARM PLAN - RM 1764

N

1/4" = 1'-0"

BLDG 1 - SECOND FLOOR FIRE ALARM PLAN - RM 2105

N

1/4" = 1'-0"

BLDG 1 - THIRD FLOOR FIRE ALARM PLAN - RM 33026

N

1/4" = 1'-0"

BLDG 1 - FOURTH FLOOR FIRE ALARM PLAN - RM 43087

N

1/4" = 1'-0"

BLDG 1 - FIFTH FLOOR FIRE ALARM PLAN - RM 528C8

SHEET KEYNOTES

MARK KEYNOTE

1 THIS TELECOMMUNICATION SPACE HAS BEEN

DESIGNATED AS AN ANSI/TIA-942-B RATING 1

SPACE/NON-MISSION CRITICAL AND WILL

THEREFORE NOT REQUIRE SMOKE DETECTION IN

ACCORDANCE WITH VA FIRE PROTECTION DESIGN

MANUAL SECTION 3.7.C.

2 THIS TELECOMMUNICATION SPACE IS TO BE

PROTECTED IN ACCORDANCE WITH THE VA FIRE

PROTECTION DESIGN MANUAL 8TH EDITION AND

HEFP SEP DESIGN ALERT 5 DATED 17 AUGUST 2021.

THIS SPACE HAS BEEN DESIGNATED A

ANSI/TIA-942-B RATING 3/MISSION CRITICAL IN

ACCORDANCE WITH THE OI&T DESIGN GUIDE

VERSION 3.1.

3 AN ASPIRATING SMOKE DETECTION SYSTEM SHALL

BE INSTALLED IN THE SERVER ROOM TO PROVIDE

EARLY WARNING OF A POTENTIAL FIRE EVENT.

SAMPLING PORTS FOR THE ASPIRATING SMOKE

DETECTION SHALL BE INSTALLED AND LOCATED IN

ACCORDANCE WITH NFPA 72. ASPIRATING SMOKE

DETECTION CONTROL UNIT SHALL BE UL LISTED

AND FM APPROVED. THE SYSTEM SHALL MEET THE

REQUIREMENTS OF NFPA 75. REFER TO

INPUT/OUTPUT MATRIX ON SHEET SH001 FOR

SENSITIVITY SETTINGS. SAMPLING PORTS ARE

ONLY TO BE INSTALLED AT THE CEILING. THIS

SPACE DOES NOT HAVE A RAISED FLOOR.

4 ASPIRATING SMOKE DETECTION CONTROL PANEL

SHALL BE POWERED FROM THE EXISTING FIRE

ALARM CONTROL UNIT OR BY A REMOTE POWER

SUPPLY.

5 THIS SPACE WILL BE PROTECTED BY A CLEAN

AGENT FIRE EXTINGUISHMENT SYSTEM TO BE

MONITORED BY THE RSFACU SHOWN ON SHEET

SH001.

No. REVISION DESCRIPTION DATE

TELECOMMUNICATION

WAIVER APPROVED TO

DEFER RENOVATION OF

THIS ROOM.

BID ALTERNATE OPTION 2

UP

TELECOM

ROOM

BASEMENT

FACU

OFFICE

TELECOM

ROOM

TELECOM

ROOM

S

F A

C U

TELECOM

ROOM

TELECOM

ROOM

106 1

TELECOM

ROOM

BASEMENT

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

IN ARCH REG. NO. AR12100034 EXP. 12/31/2021

IN MECH ENGR REG. NO. PE12100220 EXP. 07/31/2022

IN ELEC ENGR REG. NO. PE12100195 EXP. 07/31/2022

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC / PLUMB / TECH ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(913) 369-7200

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

HEALTHCARE PLANNER

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 85712

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

/9

/2

:5 :1

P

M

BLDG 2,3,4,5,6 & T4-T6 ENLARGED FIRE

ALARM PLANS

SAB 39 119DBN

BID DOCUMENTS

EHRM INFRASTRUCTURE

UPGRADES FORT WAYNE,

INDIANA

11/12/2021

610A4-21-701

VANIHCS

2121 LAKE AVE,

FORT WAYNE, IN 46805

FA112

1, 2, 3, 4, 5, 6, T4, T5, T6

N

1/4" = 1'-0"

BLDG 3 - BASEMENT FIRE ALARM PLAN - RM 3012

N

1/4" = 1'-0"

BLDG 2 - FIRST FLOOR FIRE ALARM PLAN - RM 2011

N

1/4" = 1'-0"

BLDG 5 - BASEMENT FIRE ALARM PLAN - RM 5014

N

1/4" = 1'-0"

BLDG 6 - FIRST FLOOR FIRE ALARM PLAN - RM 1075

N

1/4" = 1'-0"

BLDG T4-T6 - FIRST FLOOR FIRE ALARM PLAN - RM 1066

N

1/4" = 1'-0"

BLDG 4 - BASEMENT FIRE ALARM PLAN - RM 4013

2, 3, 4, 5, 6, T4, T5, T6

SHEET KEYNOTES

MARK KEYNOTE

1 THIS TELECOMMUNICATION SPACE HAS BEEN

DESIGNATED AS AN ANSI/TIA-942-B RATING 1

SPACE/NON-MISSION CRITICAL AND WILL

THEREFORE NOT REQUIRE SMOKE DETECTION IN

ACCORDANCE WITH VA FIRE PROTECTION DESIGN

MANUAL SECTION 3.7.C.

No. REVISION DESCRIPTION DATE

FX111

FX111

FX111

FX111

FX111

FX111

6FX111

FX111

BLDG 1

N

HAZARD CLASSIFICATION LEGEND

ORDINARY HAZARD 1

(0.15 GPM/FT² OVER 1,500 FT² WITH

250 GPM EXTERIOR HOSE DEMAND)

OUT OF SCOPE AREA

1. ADDITIONS TO EXISTING FIRE PROTECTION WET PIPE

SYSTEM SHALL BE DESIGNED AND INSTALLED IN

ACCORDANCE WITH THE VA FIRE PROTECTION DESIGN

MANUAL - EIGTH EDITION AND NFPA 13-2022.

2. SPRINKLERS AND SPRINKLER PIPING ARE PERMITTED TO

BE INSTALLED IN TELECOMMUNICATION SPACES.

SPRINKLER AND SPRINKLER PIPING ARE REQUIRED TO BE

INSTALLED OUTSIDE OF THE DEDICATED ELECTRICAL

ZONE AS DEFINED BY NFPA 13 SECTION 26.30.2 AND NFPA

70 SECTIONS 110.26 (E) (1) (B) AND 110.26 (E) (1) (C).

3. SPRINKLERS INSTALLED IN TELECOMMUNCIATION SPACES

DESIGNATED AS ANSI/TIA-942-B RATING 1 SPACES/NON-

MISSION CRITICAL SHALL BE QUICK RESPONSE TYPE.

4. SPRINKLERS INSTALLED IN TELECOMMUNCIATION SPACES

DESIGNATED AS ANSI/TIA-942-B RATING 3

SPACES/MISSION CRITICAL SHALL BE FUSIBLE-LINK,

STANDARD-RESPONSE TYPE. THESE SPRINKLERS ARE

REQURIED TO BE INSTALLED WITH PROTECTIVE CAGES AS

REQUIRED BY THE VA FIRE PROTECTION DESIGN MANUAL

SECTION 3.7.B.

5. AS REQUIRED BY VA FIRE PROTECTION DESIGN MANUAL

SECTION 3.7, REFER TO THE LIFE SAFETY SHEETS FOR

LOCATION AND TYPE OF FIRE EXTINGUISHERS.

6. SEISMIC BRACING REQUIRED IN ACCORDANCE WITH NFPA

13.

FIRE SUPPRESSION GENERAL NOTES:

THIS SPACE IS WITHIN THE SCOPE OF WORK OF

THIS PROJECT BUT WILL NOT HAVE ANY FIRE

SPRINKLER SCOPE.

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

IN ARCH REG. NO. AR12100034 EXP. 12/31/2021

IN MECH ENGR REG. NO. PE12100220 EXP. 07/31/2022

IN ELEC ENGR REG. NO. PE12100195 EXP. 07/31/2022

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC / PLUMB / TECH ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(913) 369-7200

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

HEALTHCARE PLANNER

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 85712

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

/9

/2

:5 :1

P

M

BLDG 1 OVERALL FIRE SUPPRESSION

HAZARD CLASSIFICATION PLANS

SAB 40 119DBN

BID DOCUMENTS

EHRM INFRASTRUCTURE

UPGRADES FORT WAYNE,

INDIANA

11/12/2021

610A4-21-701

VANIHCS

2121 LAKE AVE,

FORT WAYNE, IN 46805

FX101

1, 2, 3, 4, 5, 6, T4, T5, T6

N

1" = 40'-0"

BLDG 1 - BASEMENT HAZARD CLASSIFICATION OVERALL PLAN1

N

1" = 40'-0"

BLDG 1 - FIRST FLOOR HAZARD CLASSIFICATION OVERALL PLAN2

N

1" = 40'-0"

BLDG 1 - SECOND FLOOR HAZARD CLASSIFICATION OVERALL PLAN3

N

1" = 40'-0"

BLDG 1 - THIRD FLOOR HAZARD CLASSIFICATION OVERALL PLAN4

N

1" = 40'-0"

BLDG 1 - FOURTH FLOOR HAZARD CLASSIFICATION OVERALL PLAN5

N

1" = 40'-0"

BLDG 1 - FIFTH FLOOR HAZARD CLASSIFICATION OVERALL PLAN6

No. REVISION DESCRIPTION DATE

UP U

P

U P

U P

U P

U P

UP

FX112

BLDG 3

BLDG T4

BLDG 6BLDG 5

BLDG 2 BLDG 4

BLDG 1

N

FX112

FX112

FX112

FX112

FX112

FX-112

FX-112

T4 T5 T6

HAZARD CLASSIFICATION LEGEND

ORDINARY HAZARD 1

(0.15 GPM/FT² OVER 1,500 FT² WITH

250 GPM EXTERIOR HOSE DEMAND)

OUT OF SCOPE AREA

1. ADDITIONS TO EXISTING FIRE PROTECTION WET PIPE

SYSTEM SHALL BE DESIGNED AND INSTALLED IN

ACCORDANCE WITH THE VA FIRE PROTECTION DESIGN

MANUAL - EIGTH EDITION AND NFPA 13-2022.

2. SPRINKLERS AND SPRINKLER PIPING ARE PERMITTED TO

BE INSTALLED IN TELECOMMUNICATION SPACES.

SPRINKLER AND SPRINKLER PIPING ARE REQUIRED TO BE

INSTALLED OUTSIDE OF THE DEDICATED ELECTRICAL

ZONE AS DEFINED BY NFPA 13 SECTION 26.30.2 AND NFPA

70 SECTIONS 110.26 (E) (1) (B) AND 110.26 (E) (1) (C).

3. SPRINKLERS INSTALLED IN TELECOMMUNCIATION SPACES

DESIGNATED AS ANSI/TIA-942-B RATING 1 SPACES/NON-

MISSION CRITICAL SHALL BE QUICK RESPONSE TYPE.

4. SPRINKLERS INSTALLED IN TELECOMMUNCIATION SPACES

DESIGNATED AS ANSI/TIA-942-B RATING 3

SPACES/MISSION CRITICAL SHALL BE FUSIBLE-LINK,

STANDARD-RESPONSE TYPE. THESE SPRINKLERS ARE

REQURIED TO BE INSTALLED WITH PROTECTIVE CAGES AS

REQUIRED BY THE VA FIRE PROTECTION DESIGN MANUAL

SECTION 3.7.B.

5. AS REQUIRED BY VA FIRE PROTECTION DESIGN MANUAL

SECTION 3.7, REFER TO THE LIFE SAFETY SHEETS FOR

LOCATION AND TYPE OF FIRE EXTINGUISHERS.

6. SEISMIC BRACING REQUIRED IN ACCORDANCE WITH NFPA

13.

FIRE SUPPRESSION GENERAL NOTES:

THIS SPACE IS WITHIN THE SCOPE OF WORK OF

THIS PROJECT BUT WILL NOT HAVE ANY FIRE

SPRINKLER SCOPE.

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

IN ARCH REG. NO. AR12100034 EXP. 12/31/2021

IN MECH ENGR REG. NO. PE12100220 EXP. 07/31/2022

IN ELEC ENGR REG. NO. PE12100195 EXP. 07/31/2022

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC / PLUMB / TECH ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(913) 369-7200

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

HEALTHCARE PLANNER

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 85712

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

/9

/2

:5 :1

P

M

BLDG 2,3,4,5,6 & T4-T6 OVERALL FIRE

SUPPRESSION HAZARD

CLASSIFICATION PLANS

SAB 41 119DBN

BID DOCUMENTS

EHRM INFRASTRUCTURE

UPGRADES FORT WAYNE,

INDIANA

11/12/2021

610A4-21-701

VANIHCS

2121 LAKE AVE,

FORT WAYNE, IN 46805

FX102

1, 2, 3, 4, 5, 6, T4, T5, T6

N

1/16" = 1'-0"

BLDG 2 - FIRST FLOOR HAZARD CLASSIFICATION OVERALL PLAN1

N

1/16" = 1'-0"

BLDG 3 - BASEMENT HAZARD CLASSIFICATION OVERALL PLAN2

N

1/16" = 1'-0"

BLDG 4 - BASEMENT HAZARD CLASSIFICATION OVERALL PLAN3

N

1/16" = 1'-0"

BLDG 5 - BASEMENT HAZARD CLASSIFICATION OVERALL PLAN4

N

1/16" = 1'-0"

BLDG 6 - FIRST FLOOR HAZARD CLASSIFICATION OVERALL PLAN5

N

1/16" = 1'-0"

BLDG T4-T6 - FIRST FLOOR HAZARD CLASSIFICATION OVERALL PLAN6

2, 3, 4, 5, 6, T4, T5, T6

No. REVISION DESCRIPTION DATE

MAIN

SERVER

ROOM

TELECOM

ROOM /

TCB

TELECOM

ROOM

DATA

176A

TELECOM

ROOM

176A

210C

TELECOM

ROOM

210C

TELECOM

ROOM

TELECOM

ROOM

528C

TELECOM

ROOM

528C

HAZARD CLASSIFICATION LEGEND

ORDINARY HAZARD 1

(0.15 GPM/FT² OVER 1,500 FT² WITH

250 GPM EXTERIOR HOSE DEMAND)

OUT OF SCOPE AREA

1. ADDITIONS TO EXISTING FIRE PROTECTION WET PIPE

SYSTEM SHALL BE DESIGNED AND INSTALLED IN

ACCORDANCE WITH THE VA FIRE PROTECTION DESIGN

MANUAL - EIGTH EDITION AND NFPA 13-2022.

2. SPRINKLERS AND SPRINKLER PIPING ARE PERMITTED TO

BE INSTALLED IN TELECOMMUNICATION SPACES.

SPRINKLER AND SPRINKLER PIPING ARE REQUIRED TO BE

INSTALLED OUTSIDE OF THE DEDICATED ELECTRICAL

ZONE AS DEFINED BY NFPA 13 SECTION 26.30.2 AND NFPA

70 SECTIONS 110.26 (E) (1) (B) AND 110.26 (E) (1) (C).

3. SPRINKLERS INSTALLED IN TELECOMMUNCIATION SPACES

DESIGNATED AS ANSI/TIA-942-B RATING 1 SPACES/NON-

MISSION CRITICAL SHALL BE QUICK RESPONSE TYPE.

4. SPRINKLERS INSTALLED IN TELECOMMUNCIATION SPACES

DESIGNATED AS ANSI/TIA-942-B RATING 3

SPACES/MISSION CRITICAL SHALL BE FUSIBLE-LINK,

STANDARD-RESPONSE TYPE. THESE SPRINKLERS ARE

REQURIED TO BE INSTALLED WITH PROTECTIVE CAGES AS

REQUIRED BY THE VA FIRE PROTECTION DESIGN MANUAL

SECTION 3.7.B.

5. AS REQUIRED BY VA FIRE PROTECTION DESIGN MANUAL

SECTION 3.7, REFER TO THE LIFE SAFETY SHEETS FOR

LOCATION AND TYPE OF FIRE EXTINGUISHERS.

6. SEISMIC BRACING REQUIRED IN ACCORDANCE WITH NFPA

13.

FIRE SUPPRESSION GENERAL NOTES:

THIS SPACE IS WITHIN THE SCOPE OF WORK OF

THIS PROJECT BUT WILL NOT HAVE ANY FIRE

SPRINKLER SCOPE.

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

IN ARCH REG. NO. AR12100034 EXP. 12/31/2021

IN MECH ENGR REG. NO. PE12100220 EXP. 07/31/2022

IN ELEC ENGR REG. NO. PE12100195 EXP. 07/31/2022

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC / PLUMB / TECH ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(913) 369-7200

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

HEALTHCARE PLANNER

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 85712

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

/9

/2

:5 :2

P

M

BLDG 1 ENLARGED FIRE SUPPRESSION

HAZARD CLASSIFICATION PLANS

SAB 42 119DBN

BID DOCUMENTS

EHRM INFRASTRUCTURE

UPGRADES FORT WAYNE,

INDIANA

11/12/2021

610A4-21-701

VANIHCS

2121 LAKE AVE,

FORT WAYNE, IN 46805

FX111

1, 2, 3, 4, 5, 6, T4, T5, T6

N

1/4" = 1'-0"

BLDG 1 - BASEMENT HAZARD CLASSIFICATION PLAN - RM 0571

N

1/4" = 1'-0"

BLDG 1 - BASEMENT HAZARD CLASSIFICATION PLAN - RM 063A2

N

1/4" = 1'-0"

BLDG 1 - FIRST FLOOR HAZARD CLASSIFICATION PLAN - RM 1553

N

1/4" = 1'-0"

BLDG 1 - FIRST FLOOR HAZARD CLASSIFICATION OVERALL PLAN - RM 1764

N

1/4" = 1'-0"

BLDG 1 - SECOND FLOOR HAZARD CLASSIFICATION PLAN - RM 2105

N

1/4" = 1'-0"

BLDG 1 - THIRD FLOOR HAZARD CLASSIFICATION PLAN - RM 33026

N

1/4" = 1'-0"

BLDG 1 - FOURTH FLOOR HAZARD CLASSIFICATION PLAN - RM 43087

N

1/4" = 1'-0"

BLDG 1 - FIFTH FLOOR HAZARD CLASSIFICATION PLAN - RM528C8

SHEET KEYNOTES

MARK KEYNOTE

1 THIS TELECOMMUNICATION SPACE HAS BEEN

DESIGNATED AS AN ANSI/TIA-942-B RATING 1

SPACE/NON-MISSION CRITICAL IN ACCORDANCE

WITH VA FIRE PROTECTION DESIGN MANUAL

SECTION 3.7.C. THE BUILDING IS PROTECTED WITH A

WET-PIPE FIRE SPRINKLER SYSTEM THROUGHOUT,

THIS SPACE IS CURRENTLY PROTECTED WITH A

QUICK-RESPONSE SPRINKLER IN ACCORDANCE WITH

VA FIRE PROTECTION DESIGN MANUAL SECTION 3.7.

2 THIS TELECOMMUNICATION SPACE IS TO BE

PROTECTED IN ACCORDANCE WITH THE VA FIRE

PROTECTION DESIGN MANUAL 8TH EDITION AND

HEFP SEP DESIGN ALERT 5 DATED 17 AUGUST 2021.

THIS SPACE HAS BEEN DESIGNATED A ANSI/TIA-942-B

RATING 3/MISSION CRITICAL IN ACCORDANCE WITH

THE OI&T DESIGN GUIDE VERSION 3.1.

3 CONTRACTOR TO PROVIDE NEW ISOLATION VALVE

ASSEMBLY TO DESIGNATE ROOM 057 A SINGLE FIRE

SPRINKLER ZONE. CONTRACTOR TO COORDINATE

THE LOCATION OF THE FLOW AND TAMPER

SWITCHES WITH THE FIRE ALARM CONTRACTOR.

VALVE ASSEMBLY SHALL BE INSTALLED ABOVE THE

DROP-IN CEILING AND IN AN ACCESSIBLE

LOCATION.CONTRACTOR TO COORDINATE WITH VA

PERSONNEL ON LOCATION OF CONTROL VALVE FOR

THIS ZONE BEFORE WORK BEGINS. CONTRACTOR TO

COORDINATE WITH VA ON IMPAIRMENT OF FIRE

SPRINKLER SYSTEM DURING CONSTRUCTION.

No. REVISION DESCRIPTION DATE

TELECOMMUNICATION

BID ALTERNATE OPTION 2

WAIVER APPROVED TO

DEFER RENOVATION OF

THIS ROOM.

UP

TELECOM

ROOM

BASEMENT

OFFICE

TELECOM

ROOM

TELECOM

ROOM

BASEMENT

BASEMENT

TELECOM

ROOM

TELECOM

ROOM

TELECOM

ROOM

106 1

HAZARD CLASSIFICATION LEGEND

ORDINARY HAZARD 1

(0.15 GPM/FT² OVER 1,500 FT² WITH

250 GPM EXTERIOR HOSE DEMAND)

OUT OF SCOPE AREA

1. ADDITIONS TO EXISTING FIRE PROTECTION WET PIPE

SYSTEM SHALL BE DESIGNED AND INSTALLED IN

ACCORDANCE WITH THE VA FIRE PROTECTION DESIGN

MANUAL - EIGTH EDITION AND NFPA 13-2022.

2. SPRINKLERS AND SPRINKLER PIPING ARE PERMITTED TO

BE INSTALLED IN TELECOMMUNICATION SPACES.

SPRINKLER AND SPRINKLER PIPING ARE REQUIRED TO BE

INSTALLED OUTSIDE OF THE DEDICATED ELECTRICAL

ZONE AS DEFINED BY NFPA 13 SECTION 26.30.2 AND NFPA

70 SECTIONS 110.26 (E) (1) (B) AND 110.26 (E) (1) (C).

3. SPRINKLERS INSTALLED IN TELECOMMUNCIATION SPACES

DESIGNATED AS ANSI/TIA-942-B RATING 1 SPACES/NON-

MISSION CRITICAL SHALL BE QUICK RESPONSE TYPE.

4. SPRINKLERS INSTALLED IN TELECOMMUNCIATION SPACES

DESIGNATED AS ANSI/TIA-942-B RATING 3

SPACES/MISSION CRITICAL SHALL BE FUSIBLE-LINK,

STANDARD-RESPONSE TYPE. THESE SPRINKLERS ARE

REQURIED TO BE INSTALLED WITH PROTECTIVE CAGES AS

REQUIRED BY THE VA FIRE PROTECTION DESIGN MANUAL

SECTION 3.7.B.

5. AS REQUIRED BY VA FIRE PROTECTION DESIGN MANUAL

SECTION 3.7, REFER TO THE LIFE SAFETY SHEETS FOR

LOCATION AND TYPE OF FIRE EXTINGUISHERS.

6. SEISMIC BRACING REQUIRED IN ACCORDANCE WITH NFPA

13.

FIRE SUPPRESSION GENERAL NOTES:

THIS SPACE IS WITHIN THE SCOPE OF WORK OF

THIS PROJECT BUT WILL NOT HAVE ANY FIRE

SPRINKLER SCOPE.

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

IN ARCH REG. NO. AR12100034 EXP. 12/31/2021

IN MECH ENGR REG. NO. PE12100220 EXP. 07/31/2022

IN ELEC ENGR REG. NO. PE12100195 EXP. 07/31/2022

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC / PLUMB / TECH ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(913) 369-7200

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

HEALTHCARE PLANNER

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 85712

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

/9

/2

:5 :2

P

M

BLDG 2,3,4,5,6 & T4-T6 ENLARGED FIRE

SUPPRESSION HAZARD

CLASSIFICATION PLAN

SAB 43 119DBN

BID DOCUMENTS

EHRM INFRASTRUCTURE

UPGRADES FORT WAYNE,

INDIANA

11/12/2021

610A4-21-701

VANIHCS

2121 LAKE AVE,

FORT WAYNE, IN 46805

FX112

1, 2, 3, 4, 5, 6, T4, T5, T6

N

1/4" = 1'-0"

BLDG 3 - BASEMENT HAZARD CLASSIFICATION PLAN - RM 3012

SHEET KEYNOTES

MARK KEYNOTE

1 THIS TELECOMMUNICATION SPACE HAS BEEN

DESIGNATED AS AN ANSI/TIA-942-B RATING 1

SPACE/NON-MISSION CRITICAL IN ACCORDANCE

WITH VA FIRE PROTECTION DESIGN MANUAL

SECTION 3.7.C. THE BUILDING CURRENTLY DOES NOT

HAVE A FIRE SPRINKLER SYSTEM INSTALLED, THE

DIRECTION PROVIDED BY THE VA IS THAT A NEW

FIRE SPRINKLER SYSTEM IS NOT REQUIRED TO BE

INSTALLED TO PROTECT THIS SPACE. THE BUILDING

WILL REMAIN UNSPRINKLERED.

2 THIS TELECOMMUNICATION SPACE HAS BEEN

DESIGNATED AS AN ANSI/TIA-942-B RATING 1

SPACE/NON-MISSION CRITICAL IN ACCORDANCE

WITH VA FIRE PROTECTION DESIGN MANUAL

SECTION 3.7.C. THIS SPACE DOES NOT HAVE

EXISTING FIRE SPRINKLER PROTECTION.

CONTRACTOR TO MODIFY THE EXISTING BUILDING

FIRE SPRINKLER SYSTEM TO PROVIDE FIRE

SPRINKLER PROTECTION IN THIS SPACE.

CONTRACTOR TO ROUTE PIPING TO AVOID

DEDICATED ELECTRICAL SPACE.

3 THIS TELECOMMUNICATION SPACE HAS BEEN

DESIGNATED AS AN ANSI/TIA-942-B RATING 1

SPACE/NON-MISSION CRITICAL IN ACCORDANCE

WITH VA FIRE PROTECTION DESIGN MANUAL

SECTION 3.7.C. THERE IS NOT AN EXISTING

SPRINKLER SYSTEM IN THIS PORTION OF BUILDING 2.

THE INTENT IS NOT TO EXPAND THE EXISTING

SPRINKLER SYSTEM THAT IS IN THE OTHER PORTION

OF BUILDING 2 TO THIS AREA.

N

1/4" = 1'-0"

BLDG 2 - FIRST FLOOR HAZARD CLASSIFICATION PLAN - RM 2011

N

1/4" = 1'-0"

BLDG 4 - BASEMENT HAZARD CLASSIFICATION PLAN - RM 4013

N

1/4" = 1'-0"

BLDG 5 - BASEMENT HAZARD CLASSIFICATION PLAN - RM 5014

N

1/4" = 1'-0"

BLDG 6 - FIRST FLOOR HAZARD CLASSIFICATION PLAN - RM 1075

N

1/4" = 1'-0"

BLDG T4-T6 - FIRST FLOOR HAZARD CLASSIFICATION PLAN - RM 1066

2, 3, 4, 5, 6, T4, T5, T6

No. REVISION DESCRIPTION DATE

CLEAN AGENT LEGEND

SYMBOL DESCRIPTION

F FIRE ALARM MANUAL PULL STATION

FIRE ALARM HORN/STROBE COMBINATION DEVICE

SUPPRESSION HORN

VS VALVE SUPERVISORY SWITCH

WF WATER FLOW SWITCH

AIM ADDRESSABLE INPUT MODULE

AOM ADDRESSABLE OUTPUT MODULE

SYMBOL MODIFIERS

nCD CANDELA RATING

CA CLEAN AGENT MANUAL PULL STATION

CA CLEAN AGENT ABORT STATION

KM KEYED MAINTENANCE SWITCH

CLEAN AGENT DISCHARGE STROBEB

CLEAN AGENT PRE-DISCHARGE STROBER

s

ASD

ASPIRATING SMOKE DETECTOR

SOV

CA

CLEAN AGENT ACTUATOR

DISCRETE OUTPUT - DRY CONTACTCT

PS PRESSURE SWITCH

ASPIRATING SMOKE DETECTOR CONTROL PANEL

SURGE PROTECTIVE DEVICE

ASD

SPD

RSFACU RELEASING SERVICE FIRE ALARM CONTROL UNIT

F

SUPRESSION BELL

WARNING!

LEAVE AREA IMMEDIATELY

WHEN ALARM SOUNDS

NOVEC 1230

BEING RELEASED

WARNING!

THIS AREA IS PROTECTED BY A

NOVEC 1230 EXTINGUISHING

SYSTEM. DO NOT ENTER

WITHOUT AUTHORIZATION

DURING OR AFTER DISCHARGE.

PUSH

PULL

PUSH/HOLD

SUPPRESSION SYSTEM ABORT

FIRE

SUPPRESSION

MANUAL

RELEASE

FIRE

SUPPRESSION

ABORT

PUSH BUTTON

AND HOLD

AIM AIM

PS VS

AIM

CT

AIM

CT

AIM

CT

RSFACU

S U

P E

R V

IS

O

R Y

T R

O U

B L E

A L A

R M

SPD

120VAC DEDICATED

BRANCH CIRCUIT

s CA CA

B R

KM

SOV

CA

AIM

CT

AIM

CT

AIM

CT

A L E

R T

T R

O U

B L E

A L A

R M

AIM

CT

A L A

R M

ASD

s

ASD

ASPIRATING SMOKE

DETECTION SYSTEM

TO PRIMARY

POWER

SUPPLY

SEE SHEET

FA-001 FOR

CONTINUATION

F

MAIN

SERVER

ROOM

VS

PS

KM

CACA ASD

S

ASD

SOV

CA

30cd

B c d

B c d

R

75cd

R

75cd

B

F

RSFACU

15 ASD DETECTOR - DISABLE • • • •

• PERFORM OPERATION/REPORT DEVICE STATUS

A B C D E F G H I J K L M N N O P Q R S T U

12 SCP SYSTEM LOW BATTERY • • •

13 OPEN CIRCUIT OR GROUND FAULT • • •

14 CLASS B NOTIFICATION CIRCUIT (NAC) - SHORT • • •

15 LOCAL MANUAL ACTUATOR ON TANK • • • • • • • • • •

13 ASD DETECTOR - URGENT FAULT • • • •

14 ASD DETECTOR - MINOR FAULT • • • •

9 MAINTENANCE SWITCH • • • •

10 SOLENOID SUPERVISORY SWITCH • • • •

11 ACTUATOR PLACEMENT INDICATOR • • • •

12 DISCHARGE PRESSURE SWITCH • • • • • • • •

13 LOW PRESSURE SWITCH • • • •

11 SCP AC POWER FAILURE • • •

3 ASD DETECTOR - FIRE 1 - 1.0% OBS/FT (w/ 15 SECOND DELAY) • • • • • • • • 4 ASD DETECTOR - FIRE 2 - 3.0% OBS/FT (w/ 30 SECOND DELAY) • • • • • • • • •

5 COMPLETION OF 30 SECOND COUNTDOWN TIMER AFTER FIRE 2 • • •

6 ABORT SWITCH - CONTINUOUSLY HELD DOWN • • • •

7 MANUAL RELEASING PULL STATION • • • • • • • • •

8 AFTER 10 SECOND AGENT RELEASE DELAY • • •

AT 4007ES SCP NOTIFICATION AND FIRE SAFETY CONTROLS

S Y

S T

E M

O U

T P

U T

S

A C

T U

A T

E C

O M

M O

N A

L A

R M

S

IG

N A

L I

N D

IC

A

T O

R

A C

T U

A T

E A

U D

IB

L E

A L A

R M

S

IG

N A

L

A C

T U

A T

E C

O M

M O

N S

U P

E R

V

IS

O R

Y S

IG

N

A L I

N D

IC

A

T O

R

A C

T U

A T

E A

U D

IB

L E

S U

P E

R V

IS

O

R Y

S

IG

N A

L

A C

T U

A T

E C

O M

M O

N T

R O

U B

L E

S

IG

N A

L I

N D

IC

A

T O

R

A C

T U

A T

E A

U D

IB

L E

T R

O U

B L E

S

IG

N A

L

D

IS

P L A

Y C

H A

N G

E O

F S

T A

T U

S

T R

A N

S M

IT

A

L A

R M

S

IG

N A

L T

O M

A

IN

F A

C

IL

IT

Y

F A

C P

T R

A N

S M

IT

S

U P

E R

V

IS

O R

Y S

IG

N

A L T

O M

A

IN

I F

A C

IL

IT

Y F

A C

P

T R

A N

S M

IT

T

R O

U B

L E

S

IG

N A

L T

O M

A

IN

F A

C

IL

IT

Y

F A

C P

A C

T U

A T

E S

U P

P R

E S

S

IO

N B

E L L

A C

T U

A T

E S

U P

P R

E S

S

IO

N H

O R

N A

T

B

P M

A C

T U

A T

E S

U P

P R

E S

S

IO

N H

O R

N A

T S

T E

A D

Y T

O N

E

A C

T U

A T

E P

R E

-D

IS

C H

A R

G E

S T

R O

B E

A C

T U

A T

E S

U P

P R

E S

S

IO

N S

T R

O B

E

B E

G

IN

S

E C

O N

D C

O U

N T

D O

W N

A G

E N

T R

E L E

A S

E I

N T

O A

L L H

A Z

A R

D S

P A

C E

S

B E

G

IN

S

E C

O N

D A

G E

N T

R E

L E

A S

E D

E L A

Y

H V

A C

S H

U T

D O

W N

D A

M P

E R

C L O

S U

R E

S

IL

E N

C E

S S

U P

P R

E S

S

IO

N B

E L L

S T

O P

S F

IR

E

-S

E C

O N

D C

O U

N T

D O

W N

T

IM

E R

SYSTEM INPUTS A B C D E F G H I J K L M N N O P Q R S T U

1 ASD DETECTOR - ALERT - 0.2% OBS/FT (w/ 30 SECOND DELAY) • • • • 2 ASD DETECTOR - ACTION - 0.6% OBS/FT (w/ 30 SECOND DELAY) • • • • th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

IN ARCH REG. NO. AR12100034 EXP. 12/31/2021

IN MECH ENGR REG. NO. PE12100220 EXP. 07/31/2022

IN ELEC ENGR REG. NO. PE12100195 EXP. 07/31/2022

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC / PLUMB / TECH ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(913) 369-7200

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

HEALTHCARE PLANNER

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 85712

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

/9

/2

:5 :2

P

M

CLEAN AGENT NOTES, DETAILS, AND

PLAN

SAB 44 119DBN

BID DOCUMENTS

EHRM INFRASTRUCTURE

UPGRADES FORT WAYNE,

INDIANA

11/12/2021

610A4-21-701

VANIHCS

2121 LAKE AVE,

FORT WAYNE, IN 46805

SH001

1, 2, 3, 4, 5, 6, T4, T5, T6

SCALE: NONE

CLEAN AGENT SIGNAGE2 SCALE: NONE

CLEAN AGENT START/STOP STATIONS1SCALE: NONE

CLEAN AGENT TYPICAL RISER DIAGRAM3

CLEAN AGENT GENERAL NOTES:

1. PROVIDE A NEW CLEAN AGENT (NOVEC 1230) FIRE

EXTINGUISHMENT SYSTEM THAT IS DESIGNED AND INSTALLED

IN ACCORDANCE WITH NFPA 2001.

2. CLEAN AGENT TO BE USED IS NOVEC 1230 (FK-5-1-12) AT

DESIGN CONCENTRATION OF 4.5%, AS DIRECTED BY OWNER.

3. ALL PIPE AND FITTINGS SHALL BE IN ACCORDANCE WITH THE

REQUIREMENTS OF NFPA 2001.

4. ALL PIPE AN FITTINGS SHALL BE BLACK SCALE FREE STEEL

CONFORMING TO ONE OF THE FOLLOWING REQUIREMENTS:

A. ASTM A-106, SEAMLESS, GRADE A OR B SCHEDULE 40

THROUGH 8 INCHES

B. ASTM A-53, SEAMLESS, GRADE A OR B SCHEDULE 40

THROUGH 8 INCHES

C. ASTM A-53 ERW, GRADE A OR B SHALL NOT BE USED

WITHOUT PRIOR WRITTEN APPROVAL FROM AHJ.

D. ASTM A-53, CLASS F AND ASTM A-120 SHALL NOT BE USED.

5. STENCILED PIPE IDENTIFICATION SHALL NOT BE PAINTED OVER,

CONCEALED OR REMOVED PRIOR TO APPROVAL BY AHJ.

6. ALL FITTINGS SHALL BE BLACK MALLEABLE IRON OR FORGED

STEEL CONFORMING TO THE FOLLOWING REQUIREMENTS:

A. CLASS 300 MALLEABLE IRON THROUGH 3 INCHES

B. 1000# RATED FORGED STEEL GREATER THAN 3 INCHES

C. ALL GROOVED FITTINGS MUST BE UL LISTED AND

CONFORM TO THE PRESSURE REQUIREMENTS OUTLINED

IN NFPA 2001

D. CAST IRON FITTINGS ARE NOT ACCEPTABLE.

7. ALL PIPE ENDS SHALL BE REAMED AFTER CUTTING.

8. EACH PIPE SECTION SHALL BE CLEANED INTERNALLY AFTER

PREPARATION AND BEFORE ASSEMBLY BY SWABBING WITH A

SUITABLE NONFLAMMABLE CLEANER.

9. TEFLON THREAD SEAL TAPE SHALL BE USED ON ALL MALE

THREADED JOINTS ONLY. ALL GROOVED COUPLING GASKETS

SHALL BE LUBRICATED PER THE MANUFACTURER'S

SPECIFICATIONS.

10. ALL PIPING SHALL BE RIGIDLY AND SECURELY ANCHORED TO

BUILDING STRUCTURE USING U.L. APPROVED HANGERS.

11. ALL STORAGE CONTAINERS SHALL BE MOUNTED PLUMB AND

LEVEL AND SECURELY ANCHORED TO BUILDING STRUCTURE.

12. PRIOR TO INSTALLATION OF NOZZLES, THE PIPING SYSTEM

SHALL BE PNEUMATICALLY TESTED PER MANUFACTURERS

INSTRUCTIONS.

13. REFER TO ARCHITECTURAL SIGNAGE DETAILS FOR MATERIAL,

FINISH COLOR, ETC. OF CLEAN AGENT SIGNAGE AND

START/STOP STATIONS.

SAMPLING PIPE NETWORK REQUIREMENTS

(ASD):

1. ALL PIPING SHALL BE CPVC.

2. ATTACH PIPES TO STRUCTURE AS APPLICABLE, USING

STANDARD PIPE SECURING HARDWARE AT INTERVALS OF NO

MORE THAN 5 FEET.

3. ALL CONNECTIONS AND JOINTS SHALL BE MADE WITH

STANDARD CONNECTIONS DESIGNED TO BE COMPATIBLE WITH

PIPE MATERIAL.

4. ALL JOINTS SHALL BE AIR TIGHT TO PREVENT INFILTRATION AT

OTHER THAN SAMPLING PORT LOCATIONS.

5. COORDINATE THE LOCATION OF PIPING AND SAMPLING PORTS

WITH OTHER TRADES TO PERMIT PROPER ACCESS TO ALL

EQUIPMENT.

6. THE SAMPLING PIPE NETWORK SHALL BE CLEARED OF ALL DIRT

AND DEBRIS BY RUNNING AIR THROUGH THE PIPE NETWORK

FOR A MINIMUM OF 30 MINUTES PRIOR TO CONNECTION AND

OPERATION OF THE SYSTEM.

7. ALL PIPING SHALL BE LABELED AT EACH SAMPLING PORT AND

AT 20 FOOT INTERVALS USING MANUFACTURERS

IDENTIFICATION LABELS.

8. DO NOT GLUE PIPE(S) INTO SOCKET(S) OF INLET MANIFOLD.

PIPES MUST BE INSERTED INTO THE SOCKET(S) AT A MINIMUM

OF 1/2 INCH.

9. SENSITIVITY SETTINGS SHOWN IN THE MATRIX SHALL BE

ACHIEVED AT THE END OF EACH SAMPLING PORT.

N

1/4" = 1'-0"

BLDG 1 - CLEAN AGENT PLAN - RM 0574

SCALE: NONE

CLEAN AGENT INPUT/OUTPUT MATRIX5

SHEET KEYNOTES

MARK KEYNOTE

1 SPACE TO BE PROTECTED WITH A CLEAN AGENT

FIRE EXTINGUISHMENT SYSTEM. PROTECTION TO

INCLUDE ABOVE AND BELOW THE RAISED FLOOR.

AIR-ASPIRATING SMOKE DETECTION SAMPLING

PORTS TO BE PROVIDED ABOVE AND BELOW THE

RAISED FLOOR.

No. REVISION DESCRIPTION DATE

Sheets
FA001 - BLDG 1 FIRE ALARM GENERAL NOTES, DIAGRAMS, AND LEGEND
FA101 - BLDG 1 OVERALL FIRE ALARM PLANS
FA102 - BLDG 2,3,4,5,6 & T4-T6 OVERALL FIRE ALARM PLANS
FA111 - BLDG 1 ENLARGED FIRE ALARM PLANS
FA112 - BLDG 2,3,4,5,6 & T4-T6 ENLARGED FIRE ALARM PLANS
FX101 - BLDG 1 OVERALL FIRE SUPPRESSION HAZARD CLASSIFICATION PLANS
FX102 - BLDG 2,3,4,5,6 & T4-T6 OVERALL FIRE SUPPRESSION HAZARD CLASSIFICATION PLANS
FX111 - BLDG 1 ENLARGED FIRE SUPPRESSION HAZARD CLASSIFICATION PLANS
FX112 - BLDG 2,3,4,5,6 & T4-T6 ENLARGED FIRE SUPPRESSION HAZARD CLASSIFICATION PLAN
SH001 - CLEAN AGENT NOTES, DETAILS, AND PLAN

File details come from the government source that posted it. Updated .