Attachment 6 Drawing 06_MECHANICAL_BID SET.pdf

PDF 4 MB Posted

Attached to
Y1DA--610A4-21-701 EHRM Infrastructure Upgrades Construction Ft. Wayne Federal contract opportunity
Solicitation number
36C77622B0028
Issued by
Department of Veterans Affairs Technology Acquisition Center Austin

About this file

This document package includes mechanical drawings and schedules for infrastructure upgrades at a Department of Veterans Affairs medical center. The project involves upgrades to HVAC, plumbing and controls systems across multiple buildings on the campus. Key project components include replacement of computer room units, split system fan coil units, air cooled condensing units and associated ductwork, piping and controls. Detailed drawings and schedules provide specifications for equipment, materials, construction and installation. Controls sequences of operation are included along with points lists and trending intervals. The project is a design-bid-build construction contract with an anticipated award date in late 2021.

View the file

Other files for this federal contract opportunity

Other files attached to Y1DA--610A4-21-701 EHRM Infrastructure Upgrades Construction Ft. Wayne, newest first.
File Type Posted
36C77622B0028 0008.pdf PDF
Attachment 2 EHRM ICRA Form - Ft. Wayne.pdf PDF
Attachment 1 Technical Question Responses - Ft Wayne EHRM 20220722.pdf PDF
36C77622B0028 0007.pdf PDF
0006 Attachment 1 Technical Question Responses.pdf PDF
36C77622B0028 0006.pdf PDF
36C77622B0028 0005.pdf PDF
36C77622B0028 0004.pdf PDF
36C77622B0028 0003.pdf PDF
36C77622B0028 0002.pdf PDF
36C77622B0028 0001.pdf PDF
Attachment 12 610A4-21-701 Specifications Bound.pdf PDF
Attachment 3 Drawing 03_ENVIRONMENTAL.pdf PDF
Attachment 9 Drawing 08b_TELECOMMUNICATION.pdf PDF
Attachment 15 CONTRACTOR SAFETY AND ENVIRONMENTAL RECORD EVALUATION FORM.docx DOCX document
Attachment 8 Drawing 08a_TELECOMMUNICATION.pdf PDF
Attachment 4 Drawing 04_ARCHITECTURAL_BID SET.pdf PDF
Attachment 1 Drawing 01_GENERAL_BID SET.pdf PDF
Attachment 14 COVID-19 Safety Protocols 12-14-21.pdf PDF
36C77622B0028_1.docx DOCX document
Attachment 17 ELECTRICAL BID SET.pdf PDF
Attachment 16 Limitations on Subcontracting - Construction.docx DOCX document
Attachment 13 DBA Wage Determination - Ft Wayne 20220602.pdf PDF
Attachment 11 EHRM Ft Wayne Bid Documents Narrative.pdf PDF
Attachment 10 Drawing 09_SECURITY.pdf PDF
Attachment 7 Drawing 07_ELECTRICAL_BID SET.pdf PDF
Attachment 5 Drawing 05_FIRE PROTECTION_BID SET.pdf PDF
Attachment 2 Drawing 02_CIVIL_BID SET.pdf PDF
Show all 28

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ABBREVIATIONS

THIS LEGEND DEFINING TYPICAL ABBREVIATIONS AND SYMBOLS IS INTENDED TO BE AN OVERALL LEGEND FOR ALL PROJECTS. PLEASE UNDERSTAND THAT NOT ALL ABBREVIATIONS OR SYMBOLS WILL BE UTILIZED FOR EVERY PROJECT. MANY OF THE SYMBOLS WILL BE UTILIZED IN DETAILS AND DIAGRAMS VIA PLAN SHEETS.

HVAC PIPING TYPES

GENERAL DUCT SYMBOLS

A/E ARCHITECT / ENGINEER

AAHX AIR TO AIR HEAT EXCHANGER

AB AIR BLENDER

AAV AUTOMATIC AIR VENT

ACC AIR COOLED CONDENSER

ACU AIR CONDITIONING UNIT

AF AFTER FILTER

AFCV AIR FLOW CONTROL VALVE

AFF ABOVE FINISHED FLOOR

AFW AIR FOIL WHEEL (FAN)

AHU AIR-HANDLING UNIT

AMP AMPERAGE

AP ACCESS PANEL

APD AIR PRESSURE DROP

ARI AIR CONDITIONING AND REFRIGERATION

INSTITUTE

AS AIR SEPARATOR

ASME AMERICAN SOCIETY OF MECHANICAL

ENGINEERS

AW AIR WASHER

AXF AXIAL FLOW

B

B BOILER

BD BUTTERFLY DAMPER

BDD BACKDRAFT DAMPER

BFP BACKFLOW PREVENTER

BHP BRAKE HORSEPOWER

BHX BOILER BLOWDOWN HEAT EXCHANGER

BIW BACKWARD INCLINED WHEEL (FAN)

BSC BIOLOGICAL SAFETY CABINETS

BT BLOWOFF TANK

BTU BRITISH THERMAL UNIT

BTUH BRITISH THERMAL UNIT PER HOUR

C

C CENTIGRADE (CELSIUS)

CC COOLING COIL

CCD COOLING COIL CONDENSATE DRAIN

CENT CENTRIFUGAL

CFH CUBIC FEET PER HOUR

CFM CUBIC FEET PER MINUTE

CFT CUBIC FEET

CFP CHEMICAL FEED PUMP

CH CHILLER

CHP CHILLED WATER PUMP

CHW CHILLER WATER

CHR CHILLED WATER RETURN

CHS CHILLED WATER SUPPLY

CI CAST IRON

CM CUBIC METER

CM/S CUBIC METER PER SECOND

CO CARBON MONOXIDE

CO2 CARBON DIOXIDE

COMP COMPRESSOR UNIT

COP COEFFICIENT OF PERFORMANCE

CP CONDENSATE PUMP

CS CONDENSATE STORAGE TANK

CSG CLEAN STEAM GENERATOR

CT COOLING TOWER

CU CONDENSING UNIT

CUH CABINET UNIT HEATER

CV CONSTANT VOLUME

CW COLD WATER (POTABLE)

CC CHILLED WATER COOLING COIL

CWP CONDENSER WATER PUMP

CWR CONDENSER WATER RETURN

CWS CONDENSER WATER SUPPLY

A

F

F FAHRENHEIT

F&T FLOAT AND THERMOSTATIC

FA FREE AREA

FC FLEXIBLE CONNECTION

FCU FAN COIL UNIT

FCUC FAN COIL UNIT COOLING ONLY

FCUH FAN COIL UNIT HEATING ONLY

FCW FORWARD CURVED WHEEL (FAN)

E

EA EXHAUST AIR

EAT ENTERING AIR TEMPERATURE

EC EVAPORATIVE COOLER

ECC ENGINEERING CONTROL CENTER

ECU EVAPORATIVE CONDENSER UNIT

EDH ELECTRIC DUCT HEATER

EER ENERGY EFFICIENCY RATIO

EF EXHAUST FAN

EGS EMERGENCY GAS SHUTOFF

EGT ENTERING GLYCOL TEMPERATURE

EH EXHAUST HOOD

EJ EXPANSION JOINT

EMD END OF MAIN DRIP (STEAM)

ENT ENTERING

ERC ELECTRIC REHEAT COIL

ERP ELECTRIC RADIANT PANEL

ESP EXTERNAL STATIC PRESSURE

ET EXPANSION TANK

ETO ETHYLENE OXIDE

ETR EXISTING TO REMAIN

EUH ELECTRIC UNIT HEATER

EWC EVAPORATIVE WATER COOLER

EWT ENTERING WATER TEMPERATURE

EX. EXISTING

D

DB DECIBELS

Db DRY-BULB TEMPERATURE

DDC DIRECT DIGITAL CONTROLS

DEG DEGREE

DIA DIAMETER

DIW DEIONIZED WATER

DP DEW POINT TEMPERATURE

DPA DIFFERENTIAL PRESSURE ASSEMBLY

DPS DIFFERENTIAL PRESSURE SENSOR

DX DIRECT EXPANSION

FD FIRE DAMPER

FF FINAL FILTER

FHX FLUE GAS/FEEDWATER HEAT EXCHANGER

FM FLOW METER

FOP FUEL OIL PUMP

FOT FUEL OIL TANK

FOHX FUEL OIL HEAT EXCHANGER

FPM FEET PER MINUTE

FPS FEET PER SECOND

FPTU FAN POWERED TERMINAL UNIT

FRP FIBER REINFORCED POLYESTER

FS FLOW SWITCH

FSTAT FREEZESTAT

FT FEET

FT-LB FOOT-POUND

FTR FIN TUBE RADIATION

FV FACE VELOCITY

FSD COMBINATION FIRE / SMOKE DAMPER

G

GA GAUGE

GAL GALLONS

GH GRAVITY HOOD

GPD GALLONS PER DAY

GPH GALLONS PER HOUR

GPM GALLONS PER MINUTE

GPR GAS PRESSURE REGULATOR

GS GALVANIZED STEEL

K kg KILOGRAM kg/HR KILOGRAM PER HOUR kPa KILOPASCAL kW KILOWATT kWh KILOWATT HOUR

J

J INTENTIONALLY LEFT BLANK

I/O INPUT/OUTPUT

IAQ INDOOR AIR QUALITY

IBT INVERTED BUCKET TRAP

ICF IN-LINE CENTRIFUGAL FAN

ID INSIDE DIAMETER

IFB INTEGRAL FACE AND BYPASS

IN INCHES

IN HG INCHES OF MERCURY

IN WC INCH WATER COLUMN

IN WG INCH WATER GAUGE

IN-LB INCH-POUND

IPLV INTEGRATED PART LOAD VALUE

IRH INFRARED HEATER

IS INSECT SCREEN

IU INDUCTION UNIT

IV INLET VANES

H

H HUMIDIFIER

H&CW HOT & COLD WATER

HAC HOUSEKEEPING AID CLOSET

HB HOSE BIBB

HC HEATING COIL

HD HEAD

HOA HAND/OFF/AUTOMATIC

HP HEAT PUMP

HP HORSEPOWER

HPDT HIGH PRESSURE DRIP TRAP

HPR HIGH PRESSURE RETURN

(STEAM CONDENSATE)

HPS HIGH PRESSURE SUPPLY (STEAM)

(61-300 PSIG)

HRC HEAT RECOVERY COIL

HRD HEAT RECOVERY DEVICE

HRP HYDRONIC RADIANT (CEILING) PANEL

HRW HEAT RECOVERY WHEEL

HSTAT HUMIDISTAT

HTM HUMIDIFIER TERMINAL

HUM HUMIDIFIER UNIT MOUNTED

HVU HEATING AND VENTILATING UNIT

HW HOT WATER

HC HOT WATER HEATING COIL

HHP HEATING HOT WATER PUMP

HHR HEATING HOT WATER RETURN

HHS HEATING HOT WATER SUPPLY

HHUH HOT WATER UNIT HEATER

HX HEAT EXCHANGER

HZ HERTZ

I

L

L LITER

L/h LITERS PER HOUR (OR LITERS/HOUR) L/m LITERS PER MINUTE (OR LITERS/MINUTE) L/s LITERS PER SECOND (OR LITERS/SECOND)

LAT LEAVING AIR TEMPERATURE

LBS/HR POUNDS PER HOUR

LF LINEAR FOOT (FEET)

LGT LEAVING GLYCOL TEMPERATURE

LH LATENT HEAT

LPG LIQUID PROPANE GAS

LPR LOW PRESSURE RETURN (STEAM

CONDENSATE)

LPRC LOW PRESSURE STEAM RETURN (CLEAN)

LLHX LIQUID TO LIQUID HEAT EXCHANGER

LPS LOW PRESSURE SUPPLY (STEAM)

(0-15 PSIG)

LPSC LOW PRESSURE STEAM (CLEAN)

LSD LINEAR SLOT DIFFUSER

LTCP LOCAL TEMPERATURE CONTROL PANEL

LVG LEAVING

LVR LOUVER

LWT LEAVING WATER TEMPERATURE

NOM NOMINAL

NPLV NON-STANDARD PART LOAD VALUE

NPSH NET POSITIVE SUCTION HEAD

NTS NOT TO SCALE

N

NA NOT APPLICABLE

NC NOISE CRITERIA

NG NATURAL GAS

NGFM NATURAL GAS FLOWMETER

NOAA NATIONAL OCEANIC & ATMOSPHERIC

ADMINISTRATION

M

M METER, SI UNIT

M/s METERS PER SECOND

(OR METERS/SECOND)

MA MIXED AIR

MAT MIXED AIR TEMPERATURE

MAU MAKE-UP AIR UNIT

MAV MANUAL AIR VENT

MAX MAXIMUM

MB MIXING BOX

MBH 1000 BTUH

MCA MINIMUM BRANCH CIRCUIT AMPACITY

MERV MINIMUM EFFICIENCY REPORTING VALUE

MH MANHOLE

MHP MOTOR HORSEPOWER

MIN MINIMUM

MM MILLIMETER

MOV MOTOR OPERATED VALVE

MPR MEDIUM PRESSURE RETURN

(STEAM CONDENSATE)

MPS MEDIUM PRESSURE SUPPLY (STEAM)

(16-60 PSIG)

MTD MEAN TEMPERATURE DIFFERENCE

MVD MANUAL VOLUME DAMPER

MZ MULTI-ZONE

P

P PUMP

PA PASCAL

PC PUMPED CONDENSATE

PCF POUNDS PER CUBIC FOOT (FEET)

PD PRESSURE DROP

PF PRE-FILTER

PG PRESSURE GAGE

PGW PROPYLENE GLYCOL-WATER (SOLUTION)

PHC PREHEAT COIL

PPM PARTS PER MILLION

PRS PRESSURE REGULATING (VALVE) STATION

PRV PRESSURE REGULATING VALVE

PSI POUNDS PER SQUARE INCH

PSIA POUNDS PER SQUARE INCH – ABSOLUTE

PSIG POUNDS PER SQUARE INCH – GAGE

PSS PRIMARY SECONDARY SYSTEM

PSV PRESSURE SAFETY VALVE

PTAC PACKAGED TERMINAL AIR CONDITIONER

O

OA OUTSIDE AIR

OAI OUTSIDE AIR INTAKE

OD OUTSIDE DIAMETER

OFM OIL FLOWMETER

OSD ORGANIC SOIL FILTER

Q

Q INTENTIONALLY LEFT BLANK

T&PCV TEMPERATURE AND PRESSURE

CONTROL VALVE

TAB TESTING, ADJUSTING, BALANCE

TD TEMPERATURE DIFFERENCE

TDH TOTAL DYNAMIC HEAD

TDS TOTAL DISSOLVED SOLIDS

TG TRANSFER GRILLE

TP TRAP

TSP TOTAL STATIC PRESSURE

TSTAT THERMOSTAT

TU TERMINAL UNIT

TWU THRU-WALL UNIT

SA SUPPLY AIR

SAD SOUND ATTENUATING DEVICE

SAT SUPPLY AIR TEMPERATURE

SC SHADING COEFFICIENT

SCFM STANDARD CUBIC FEET PER MINUTE

SCR SILICON CONTROLLED RECTIFIER

DSD DUCT SMOKE DETECTOR

SD SMOKE DAMPER

SEN SENSIBLE HEAT

SF SUPPLY FAN

SH STEAM HUMIDIFIER

SHC STEAM HEATING COIL

SI SQUARE INCHES

SP STATIC PRESSURE

SP GR SPECIFIC GRAVITY

SPS STATIC PRESSURE SENSOR

SQ FT SQUARE FOOT (FEET)

SS STAINLESS STEEL

SSHX STEAM TO STEAM HEAT EXCHANGER

SSR SOLID SEPARATOR

ST STEAM TRAP

SUH STEAM UNIT HEATER

SVS STEAM VENT SILENCER

SWHX STEAM TO WATER HEAT EXCHANGER

R

R/E RETURN OR EXHAUST

RA RETURN AIR

RAD REFRIGERANT AIR DRYER

RAF RADIO FREQUENCY

RAHX ROTARY AIR HEAT EXCHANGER

RAT RETURN AIR TEMPERATURE

RCCH REMOTE CONDENSER CHILLER

RCU RECIPROCATING CHILLER UNIT

RD REFRIGERANT DISCHARGE

REA RELIEF AIR

RF RETURN FAN

RH RELATIVE HUMIDITY

RHC REHEAT COIL

RHG REFRIGERANT HOT GAS

RL REFRIGERANT LIQUID LINE

RLA RUN LOAD AMPERE

RO REVERSE OSMOSIS

RPM REVOLUTIONS PER MINUTE

RS REFRIGERANT SUCTION

RTU ROOF TOP UNIT

RV RELIEF VALVE

T

UC UNDER CUT

UH UNIT HEATER

UL UNDERWRITERS LABORATORY

URV UPBLAST UNIT VENTILATOR

U

X INTENTIONALLY LEFT BLANK

W

W WATTS

WAG WASTE ANESTHESIA GAS

Wb WET-BULB (TEMPERATURE)

WC WATER COOLED

WCCH WATER COOLED CHILLER

WCCU WATER COOLED CONDENSING UNIT

WCHP WATER COOLED HEAT PUMPS

WCPU WATER COOLED PACKAGED UNIT

WF WATER FILTER

WFM WATER FLOWMETER

WG WATER GAGE

WPD WATER SIDE PRESSURE DROP

V VALVE

VAF VANE-AXIAL FAN

VAV VARIABLE AIR VOLUME

VD VOLUME DAMPER (MANUAL OPPOSED BLADE)

VFD VARIABLE FREQUENCY DRIVE

VI VIBRATION ISOLATOR

VIV VARIABLE INLET VANES

VP VACUUM PUMP

VPS VARIABLE PRIMARY SYSTEM

VR VACUUM (STEAM CONDENSATE) RETURN

VSD VARIABLE SPEED DRIVE

VUH VERTICAL UNIT HEATER

X

V

GENERAL NOTES:

A. MECHANICAL PLANS AND SECTIONS ARE INTENDED TO ACCURATELY ILLUSTRATE THE

SCOPE OF WORK BUT ARE STILL DIAGRAMMATIC IN NATURE.

B. MECHANICAL DRAWINGS DO NOT SHOW ALL ACCESSORIES TO BE INSTALLED. THE

CONTRACTOR IS RESPONSIBLE FOR ENSURING THAT ALL SYSTEMS ARE FULLY

FUNCTIONAL AND COMPLIANT WITH APPLICABLE CODES.

C. THE EXISTING CONDITIONS DEPICTED IN THESE PLANS ARE BASED ON AS-BUILT

DOCUMENTATION AND INFORMATION OBTAINED FROM FIELD SURVEYS AND ARE AS

ACCURATE AS POSSIBLE. DUE TO OBSTRUCTIONS, CEILINGS, ETC., NOT ALL CONDITIONS

COULD BE VERIFIED. THE CONTRACTOR SHALL SURVEY THE SITE PRIOR TO BID AND

NOTIFY THE ARCHITECT/ENGINEER OF ANY CONFLICTS, OBSTRUCTIONS, OR

INCONSISTENCIES PREVENTING INSTALLATION OF THE MECHANICAL SYSTEM.

D. ALL EXPOSED UNINSULATED PIPING SHALL BE PAINTED PER THE SPECIFICATION SECTION

"PAINTING".

E. COORDINATE FAN COIL (FCU) AND TERMINAL UNIT (TU/VAV/CV) REHEAT COIL RIGHT OR

LEFT HAND COIL CONNECTIONS WITH PIPING PLANS.

F. ALL FLUE AND COMBUSTION AIR PIPING FROM GAS-FIRED EQUIPMENT SHALL BE SIZED BY

THE GAS-FIRED EQUIPMENT MANUFACTURER BASED ON THE SPECIFIC PIPE ROUTING AND

ELEVATIONS FOR THIS PROJECT. REFER TO MANUFACTURERS INSTALLATION MANUAL AND

LOCAL CODE REQUIREMENTS FOR REQUIRED FLUE AND COMBUSTION AIR PIPING

MATERIALS.

G. PROVIDE VIBRATION ISOLATION FOR ALL MECHANICAL EQUIPMENT TO PREVENT

TRANSMISSION OF VIBRATION TO BUILDING STRUCTURE.

H. PROVIDE VIBRATION ISOLATORS FOR ALL PIPING SUPPORTS CONNECTED TO AND WITHIN

50' OF ISOLATED EQUIPMENT (EXCEPT AT BASE ELBOW SUPPORTS AND ANCHOR POINTS)

THROUGHOUT MECHANICAL EQUIPMENT ROOMS. DO THE SAME FOR SUPPORTS OF STEAM

MAINS WITHIN 50' OF BOILER OR PRESSURE REDUCING VALVES.

I. COORDINATE CONSTRUCTION OF ALL MECHANICAL WORK WITH ARCHITECTURAL,

STRUCTURAL, CIVIL, ELECTRICAL WORK, ETC., SHOWN ON OTHER CONTRACT DOCUMENT

DRAWINGS.

J. MAINTAIN A MINIMUM OF 6′-8″ CLEARANCE TO UNDERSIDE OF PIPES, DUCTS, CONDUITS,

SUSPENDED EQUIPMENT, ETC., THROUGHOUT ACCESS ROUTES IN MECHANICAL ROOMS.

K. ALL TESTS SHALL BE COMPLETED BEFORE ANY MECHANICAL EQUIPMENT OR PIPING

INSULATION IS APPLIED.

L. LOCATE ALL TEMPERATURE, PRESSURE, AND FLOW MEASURING DEVICES IN ACCESSIBLE

LOCATIONS WITH STRAIGHT SECTION OF PIPE OR DUCT UP AND DOWNSTREAM AS

RECOMMENDED BY THE MANUFACTURER FOR GOOD ACCURACY.

M. COORDINATE ALL EQUIPMENT CONNECTIONS WITH MANUFACTURERS CERTIFIED

DRAWINGS. COORDINATE AND PROVIDE ALL DUCT AND PIPING TRANSITIONS REQUIRED

FOR FINAL EQUIPMENT CONNECTIONS TO FURNISHED EQUIPMENT. FIELD VERIFY AND

COORDINATE ALL DUCT AND PIPING DIMENSIONS BEFORE FABRICATION.

CWR

CWS

CD

LPC

LPS

MPC

MPS

HPC

HPS

CONDENSATE DRAIN

CONDENSER WATER SUPPLY

CONDENSER WATER RETURN

HIGH PRESSURE STEAM CONDENSATE

HIGH PRESSURE STEAM SUPPLY

MEDIUM PRESSURE STEAM CONDENSATE

MEDIUM PRESSURE STEAM SUPPLY

LOW PRESSURE STEAM CONDENSATE

LOW PRESSURE STEAM SUPPLY

VACUUM RETURN

FEEDWATER PUMP DISCHARGE

FEEDWATER PUMP SUCTION

VR

CONTINUOUS BLOWDOWN

CHEMICAL FEED

BOILER BLOWOFF BO

CF

CBD

FWPD

FWPS

A. PROVIDE ALL MATERIALS AND EQUIPMENT AND PERFORM ALL LABOR REQUIRED TO

INSTALL COMPLETE AND OPERABLE PIPING SYSTEMS AS INDICATED ON THE DRAWINGS, AS

SPECIFIED AND AS REQUIRED BY CODE.

B. ELEVATIONS AS SHOWN ON THE DRAWINGS ARE TO THE CENTERLINE OF ALL PRESSURE

PIPING AND TO THE INVERT OF ALL GRAVITY PIPING.

C. MAINTAIN A MINIMUM OF 3′-6″ OF GROUND COVER OVER ALL UNDERGROUND HVAC PIPING

(EDIT DEPTH OF GROUND COVER TO SUIT FROST LINE DEPTH AND PROJECT

REQUIREMENTS).

D. UNLESS OTHERWISE NOTED, ALL CHILLED WATER AND HEATING WATER PIPING SHALL BE

3/4" SIZE (EDIT SYSTEM TYPE OR PIPE SIZE TO SUIT PROJECT REQUIREMENTS).

E. PROVIDE AN AIR VENT AT THE HIGH POINT OF EACH DROP IN THE HEATING WATER, CHILLED

WATER, AND OTHER CLOSED WATER PIPING SYSTEMS (EDIT SYSTEM TYPES TO SUIT

PROJECT REQUIREMENTS). ALL PIPING SHALL GRADE TO LOW POINTS. PROVIDE HOSE END

DRAIN VALVES AT THE BOTTOM OF ALL RISERS AND LOW POINTS.

F. UNLESS OTHERWISE NOTED, ALL PIPING IS OVERHEAD, TIGHT TO UNDERSIDE OF

STRUCTURE OR SLAB, WITH SPACE FOR INSULATION IF REQUIRED.

G. INSTALL PIPING SO THAT ALL VALVES, STRAINERS, UNIONS, TRAPS, FLANGES, AND OTHER

APPURTENANCES REQUIRING ACCESS ARE ACCESSIBLE.

H. ALL VALVES SHALL BE INSTALLED SO THAT VALVE REMAINS IN SERVICE WHEN EQUIPMENT

OR PIPING ON EQUIPMENT SIDE OF VALVE IS REMOVED.

I. ALL BALANCING VALVES AND BUTTERFLY VALVES SHALL BE PROVIDED WITH POSITION

INDICATORS AND MAXIMUM ADJUSTABLE STOPS (MEMORY STOPS).

J. PROVIDE CHAINWHEEL OPERATORS FOR ALL VALVES IN EQUIPMENT ROOMS MOUNTED

GREATER THAN 7′-0″ ABOVE FLOOR LEVEL; CHAIN SHALL EXTEND TO 7′-0″ ABOVE FLOOR

LEVEL.

K. ALL VALVES (EXCEPT CONTROL VALVES) AND STRAINERS SHALL BE FULL SIZE OF PIPE

BEFORE REDUCING SIZE TO MAKE CONNECTIONS TO EQUIPMENT AND CONTROLS.

L. UNIONS AND/OR FLANGES SHALL BE INSTALLED AT EACH PIECE OF EQUIPMENT, IN

BYPASSES, AND IN LONG PIPING RUNS (100' OR MORE) TO PERMIT DISASSEMBLY FOR

ALTERATION AND REPAIRS.

M. PITCH STEAM PIPING DOWNWARD IN THE DIRECTION OF FLOW 1/4" IN 10' (1" IN 40') MINIMUM.

PITCH ALL STEAM RETURN LINES DOWNWARD IN THE DIRECTION OF CONDENSATE FLOW

1/2" PER 10' (1" IN 20') MINIMUM. WHERE LENGTH OF BRANCH LINES ARE LESS THAN 8', PITCH

BRANCH LINES TOWARD MAINS 1/2" PER FOOT MINIMUM.

N. PITCH UP ALL STEAM AND CONDENSATE RUNOUTS TO RISERS AND EQUIPMENT 1/2" PER

FOOT. WHERE THIS PITCH CANNOT BE OBTAINED, RUNOUTS OVER 8' IN LENGTH SHALL BE

ONE SIZE LARGER THAN NOTED.

O. TAP ALL BRANCH LINES FROM TOP OF STEAM MAINS (45° PREFERRED, 90° ACCEPTABLE).

A. PROVIDE ALL MATERIALS AND EQUIPMENT AND PERFORM ALL LABOR REQUIRED TO

INSTALL COMPLETE AND OPERABLE HVAC SYSTEMS AS INDICATED ON THE DRAWINGS, AS

SPECIFIED AND AS REQUIRED BY CODE.

B. CERTAIN ITEMS SUCH AS RISES AND DROPS IN DUCTWORK, ACCESS DOORS, VOLUME

DAMPERS, ETC., ARE INDICATED ON THE CONTRACT DOCUMENT DRAWINGS FOR CLARITY

FOR A SPECIFIC LOCATION REQUIREMENT AND SHALL NOT BE INTERPRETED AS THE

EXTENT OF THE REQUIREMENTS FOR THESE ITEMS.

C. IN CORRIDORS WHERE CEILING SPEAKERS AND AIR DIFFUSERS ARE INDICATED BETWEEN

THE SAME LIGHT FIXTURES, INSTALL BOTH DEVICES AT THE QUARTER POINTS BETWEEN

THE SAME FIXTURE.

D. UNLESS OTHERWISE SHOWN, LOCATE ALL ROOM THERMOSTATS AND HUMIDISTATS 4′-0″

(CENTERLINE) ABOVE FINISHED FLOOR.

E. ALL DUCTWORK SHALL CLEAR DOORS AND WINDOWS.

F. ALL DUCTWORK DIMENSIONS, AS SHOWN ON THE DRAWINGS, ARE INTERNAL CLEAR

DIMENSIONS AND DUCT SIZE SHALL BE INCREASED TO COMPENSATE FOR DUCT LINING

THICKNESS.

G. PROVIDE ALL 90° SQUARE ELBOWS WITH DOUBLE RADIUS TURNING VANES UNLESS

OTHERWISE INDICATED. ELBOWS IN DISHWASHER, KITCHEN, AND LAUNDRY EXHAUST

SHALL BE UNVANED SMOOTH RADIUS CONSTRUCTION WITH A RADIUS EQUAL TO 1.5 TIMES

THE WIDTH OF THE DUCT. PROVIDE ACCESS DOORS UPSTREAM OF ALL ELBOWS WITH

TURNING VANES.

H. COORDINATE DIFFUSER, REGISTER, AND GRILLE LOCATIONS WITH ARCHITECTURAL

REFLECTED CEILING PLANS, LIGHTING, AND OTHER CEILING ITEMS AND MAKE MINOR DUCT

MODIFICATIONS TO SUIT.

I. FIELD ERECTED AND FACTORY ASSEMBLED AIR HANDLING UNIT COILS SHALL BE

ARRANGED FOR REMOVAL FROM THE UPSTREAM SIDE WITHOUT DISMANTLING SUPPORTS.

PROVIDE GALVANIZED STRUCTURAL STEEL SUPPORTS FOR ALL COILS (EXCEPT LOWEST

COIL) IN BANKS OVER TWO COILS HIGH TO PERMIT INDEPENDENT REMOVAL OF ANY COIL.

J. ALL AIR HANDLING UNITS SHALL OPERATE WITHOUT MOISTURE CARRYOVER.

K. LOCATE ALL MECHANICAL EQUIPMENT (SINGLE DUCT, DUAL DUCT, VARIABLE VOLUME,

CONSTANT VOLUME AND FAN POWERED BOXES, FAN COIL UNITS, CABINET HEATERS, UNIT

HEATERS, UNIT VENTILATORS, COILS, STEAM HUMIDIFIERS, ETC.) FOR UNOBSTRUCTED

ACCESS TO UNIT ACCESS PANELS, CONTROLS AND VALVING.

L. FINNED TUBE RADIATION ENCLOSURES SHALL BE WALL TO WALL UNLESS OTHERWISE

INDICATED.

M. PROVIDE FLEXIBLE CONNECTIONS IN ALL DUCTWORK SYSTEMS (SUPPLY, RETURN, AND

EXHAUST) CONNECTED TO AIR HANDLING UNITS, FANS, AND OTHER EQUIPMENT WHICH

REQUIRE VIBRATION ISOLATION. FLEXIBLE CONNECTIONS SHALL BE PROVIDED AT THE

POINT OF CONNECTION TO THE EQUIPMENT UNLESS OTHERWISE INDICATED.

PIPING GENERAL NOTES: HVAC/SHEET METAL GENERAL NOTES:

EXISTING TO BE DEMOLISHED

LIMIT OF DEMOLITION

CONNECT NEW TO EXISTINGEXISTING TO REMAIN

NEW DUCT (INSIDE DIMENSIONS: W" X D")

RS

RL

REFRIGERANT SUCTION

REFRIGERANT LIQUID

SUPPLY AIR DUCT UP

SUPPLY AIR DUCT DOWN

H

T

H

T

26-P-3

MH-100

PUMP NO. 3 IN BUILDING NO. 26

EQUIPMENT ABBREVIATION (PUMP)

DETAIL NUMBER

SHEET NUMBER

SHEET NUMBER

SECTION NUMBER

THERMOSTAT

HUMIDISTAT

TEMPERATURE SENSOR

HUMIDITY SENSOR

BUILDING NUMBER WHERE EQUIPMENT

IS LOCATED

26-TU-1-1

ITEM NUMBER (TERMINAL UNIT NO. 1)

ITEM (TERMINAL UNIT)

BUILDING NUMBER WHERE EQUIPMENT

IS LOCATED

SERVED BY AIR HANDLER UNIT NO. 1

TERMINAL UNIT TAG

MECHANICAL EQUIPMENT TAG

1 OWNER FURNISHED, CONTRACTOR

INSTALLED EQUIPMENT DESIGNATION

EXISTING TO BE DEMOLISHED

EXISTING TO REMAIN

NEW PIPE

CONNECT NEW TO EXISTING

LIMIT OF DEMOLITION

GENERAL PIPING SYMBOLS

GENERAL ANNOTATIONS

AV

STRAINERFLOAT & THERMOSTATIC

STEAM TRAP

INVERTED BUCKET

STEAM TRAP

FLANGE CONNECTION PIPE DROP

PIPE RISER TEE DOWN

TEE UP

UNION

PRESSURE REDUCING

VALVE

BALL VALVE

ANGLE GLOBE VALVE

SAFETY RELIEF VALVE

GLOBE VALVE

MANUAL OR

AUTOMATIC AIR VENT

EXPANSION JOINT

EJ

PRESSURE AND

TEMPERATURE TEST PLUG

QUICK-COUPLE HOSE

CONNECTOR

FLOW METER

HVAC PIPING SYMBOLS

CHILLED WATER RETURN

CHILLED WATER SUPPLY

CHR

CHS

HEATING HOT WATER RETURN

HEATING HOT WATER SUPPLY

HHR

HHS QV CRYOGEN VENT

DR DRIP RETURN

CAP

REDUCER (ECCENTRIC)

TYPE

AIRFLOW (CFM)

SD-1

TYPE

AIRFLOW (CFM)

RG-1

TYPE

AIRFLOW (CFM)

EG-1

SQUARE TO ROUND TRANSITION

ELBOW WITH TURNING

VANES

ROUND ELBOW

EXHAUST, RELIEF, MAKE UP, OR

OUTSIDE AIR DUCT DOWN

EXHAUST, RELIEF, MAKE UP, OR

OUTSIDE AIR DUCT UP

RETURN DUCT DOWN

RETURN DUCT UP

BRANCH DUCT WITH HIGH EFFICIENCY

TAKE-OFF (HETO) BRANCH FITTING &

MANUAL VOLUME DAMPER

BRANCH DUCT WITH CONICAL

FITTING & MANUAL VOLUME

DAMPER

DAMPERS: (BD, FD, FSD, MD, SD, VD)

BD

XX-XX

ANCHOR

TEEDIRECTION OF FLOW

S

N. CONCRETE HOUSEKEEPING PADS TO SUIT MECHANICAL EQUIPMENT SHALL BE SIZED AND

LOCATED BY THE MECHANICAL CONTRACTOR. MINIMUM CONCRETE PAD THICKNESS SHALL

BE 4". PAD SHALL EXTEND BEYOND THE EQUIPMENT A MINIMUM OF 4" ON EACH SIDE.

CONCRETE HOUSEKEEPING PADS SHALL BE PROVIDED BY THE GENERAL CONTRACTOR. IT

SHALL BE THE RESPONSIBILITY OF THE MECHANICAL CONTRACTOR TO COORDINATE SIZE

AND LOCATION OF CONCRETE HOUSEKEEPING PADS.

O. WHEN MECHANICAL WORK (HVAC, PLUMBING, SHEET METAL, ETC.) IS SUB-CONTRACTED, IT

SHALL BE THE MECHANICAL CONTRACTOR’S RESPONSIBILITY TO COORDINATE

SUBCONTRACTORS AND THE ASSOCIATED CONTRACTS. WHEN DISCREPANCIES ARISE

PERTAINING TO WHICH CONTRACTOR PROVIDES A PARTICULAR ITEM OF THE MECHANICAL

CONTRACT OR WHICH CONTRACTOR PROVIDES FINAL CONNECTIONS FOR A PARTICULAR

ITEM OF THE MECHANICAL CONTRACT, IT SHALL BE BROUGHT TO THE ATTENTION OF THE

MECHANICAL CONTRACTOR, WHOSE DECISION SHALL BE FINAL.

P. THE LOCATIONS OF ALL ITEMS SHOWN ON THE DRAWINGS OR CALLED FOR IN THE

SPECIFICATIONS THAT ARE NOT DEFINITELY FIXED BY DIMENSIONS ARE APPROXIMATE

ONLY. THE EXACT LOCATIONS NECESSARY TO SECURE THE BEST CONDITIONS AND

RESULTS MUST BE DETERMINED BY THE PROJECT SITE CONDITIONS AND SHALL HAVE THE

APPROVAL OF THE ENGINEER BEFORE BEING INSTALLED. DO NOT SCALE DRAWINGS.

Q. ALL MISCELLANEOUS STEEL REQUIRED TO ENSURE PROPER INSTALLATION AND AS SHOWN

IN DETAILS FOR PIPING, DUCTWORK, AND EQUIPMENT (UNLESS OTHERWISE NOTED) SHALL

BE FURNISHED AND INSTALLED BY THE MECHANICAL CONTRACTOR.

R. PROVIDE ACCESS PANELS FOR INSTALLATION IN WALLS AND CEILINGS WHERE REQUIRED

TO SERVICE DAMPERS, VALVES, SMOKE DETECTORS, AND OTHER CONCEALED

MECHANICAL EQUIPMENT.

S. ALL DUCTWORK, PIPING AND EQUIPMENT SUPPORTED FROM STRUCTURAL STEEL SHALL

BE COORDINATED WITH GENERAL CONTRACTOR. ALL ATTACHMENTS TO STEEL BAR

JOISTS, TRUSSES, OR JOIST GIRDERS SHALL BE AT PANEL POINTS. PROVIDE BEAM CLAMPS

MEETING MSS STANDARDS.WELDING TO STRUCTURAL MEMBERS SHALL NOT BE

PERMITTED. THE USE OF C-CLAMPS SHALL NOT BE PERMITTED.

T. ALL ROOF MOUNTED EQUIPMENT CURBS FOR EQUIPMENT PROVIDED BY THE MECHANICAL

CONTRACTOR SHALL BE FURNISHED BY THE MECHANICAL CONTRACTOR. COORDINATE

INSTALLATION WITH GENERAL CONTRACTOR.

U. LOCATIONS AND SIZES OF ALL FLOOR, WALL, AND ROOF OPENINGS SHALL BE

COORDINATED WITH ALL OTHER TRADES INVOLVED.

V. ALL OPENINGS IN FIRE WALLS DUE TO DUCTWORK, PIPING, CONDUIT, ETC., SHALL BE FIRE

STOPPED WITH AN APPROVED FIRE STOPPING MATERIAL.

W. ALL AIR CONDITIONING CONDENSATE DRAIN LINES FROM EACH AIR HANDLING UNIT AND

ROOFTOP UNIT SHALL BE PIPED FULL SIZE OF THE UNIT DRAIN OUTLET, WITH P-TRAP, AND

PIPED TO NEAREST DRAIN. SEE DETAILS AND SPECIFICATIONS FOR DEPTH OF AIR

CONDITIONING CONDENSATE TRAP.

X. REFER TO TYPICAL DETAILS FOR DUCTWORK, PIPING, AND EQUIPMENT INSTALLATION.

P. PROVIDE AN END OF MAIN DRIP AT EACH RISE IN THE STEAM MAIN. PROVIDE CONDENSATE

DRIPS AT THE BOTTOM OF ALL STEAM RISERS, DOWNFED RUNOUTS TO EQUIPMENT,

RADIATORS, ETC., AT END OF MAINS AND LOW POINTS, AND AHEAD OF ALL PRESSURE

REGULATORS, CONTROL VALVES, ISOLATION VALVES, AND EXPANSION JOINTS.

Q. ON STRAIGHT STEAM PIPING RUNS WITH NO NATURAL DRAINAGE POINTS, INSTALL DRIP

LEGS AT INTERVALS NOT EXCEEDING 200' WHERE PIPE IS PITCHED DOWNWARD IN THE

DIRECTION OF STEAM FLOW AND A MAXIMUM OF 100' WHERE THE PIPE IS PITCHED UP SO

THAT CONDENSATE FLOW IS OPPOSITE OF STEAM FLOW.

R. STEAM TRAPS SHALL BE MINIMUM 3/4″ IN SIZE.

S. INSTALL ALL PIPING WITHOUT FORCING OR SPRINGING.

T. ALL PIPING SHALL CLEAR DOORS AND WINDOWS.

U. ALL VALVES SHALL BE ADJUSTED FOR SMOOTH AND EASY OPERATION.

V. ALL PIPING WORK SHALL BE COORDINATED WITH ALL TRADES INVOLVED. OFFSETS IN

PIPING AROUND OBSTRUCTIONS SHALL BE PROVIDED AT NO ADDITIONAL COST TO THE

OWNER.

W. PROVIDE FLEXIBLE CONNECTIONS IN ALL PIPING SYSTEMS CONNECTED TO PUMPS,

CHILLERS, COOLING TOWERS, AND OTHER EQUIPMENT WHICH REQUIRE VIBRATION

ISOLATION EXCEPT WATER COILS. FLEXIBLE CONNECTIONS SHALL BE PROVIDED AS CLOSE

TO THE EQUIPMENT AS POSSIBLE OR AS INDICATED ON THE DRAWINGS.

X. SLOPE REFRIGERANT PIPING ONE PERCENT IN THE DIRECTION OF OIL RETURN. LIQUID

LINES MAY BE INSTALLED LEVEL.

Y. INSTALL HORIZONTAL REFRIGERANT HOT GAS DISCHARGE PIPING WITH 1/2″ PER 10'

DOWNWARD SLOPE AWAY FROM THE COMPRESSOR.

Z. INSTALL HORIZONTAL REFRIGERANT SUCTION LINES WITH 1/2″ PER 10' DOWNWARD SLOPE

TO THE COMPRESSOR, WITH NO LONG TRAPS OR DEAD ENDS WHICH MAY CAUSE OIL TO

SEPARATE FROM THE SUCTION GAS AND RETURN TO THE COMPRESSOR IN DAMAGING

SLUGS.

AA. PROVIDE LINE SIZE LIQUID INDICATORS IN MAIN LIQUID LINE LEAVING CONDENSER OR

RECEIVER. INSTALL MOISTURE LIQUID INDICATORS IN LIQUID LINES BETWEEN FILTER

DRYERS AND THERMOSTATIC EXPANSION VALVES AND IN LIQUID LINE TO RECEIVER.

BB. PROVIDE LINE SIZE STRAINER UPSTREAM OF EACH AUTOMATIC VALVE. PROVIDE SHUTOFF

VALVE ON EACH SIDE OF STRAINER.

CC. PROVIDE PERMANENT FILTER DRYERS IN LOW TEMPERATURE SYSTEMS AND SYSTEMS

USING HERMETIC COMPRESSORS.

DD. PROVIDE REPLACEABLE CARTRIDGE FILTER DRYERS WITH THREE-WAY VALVE BYPASS A

ASSEMBLY FOR SOLENOID VALVES, ADJACENT TO RECEIVERS.

EE. PROVIDE REFRIGERANT CHARGING VALVE CONNECTIONS IN LIQUID LINE BETWEEN

RECEIVER SHUTOFF VALVE AND EXPANSION VALVE.

N. UNLESS OTHERWISE NOTED, ALL DUCTWORK IS OVERHEAD, TIGHT TO THE UNDERSIDE OF

THE STRUCTURE, WITH SPACE FOR INSULATION IF REQUIRED.

M. RUNS OF FLEXIBLE DUCT SHALL NOT EXCEED 5' MAXIMUM LENGTH.

O. ALL DUCTWORK SHALL BE COORDINATED WITH ALL TRADES INVOLVED. OFFSETS IN

DUCTS, INCLUDING DIVIDED DUCTS AND TRANSITIONS AROUND OBSTRUCTIONS, SHALL BE

PROVIDED AT NO ADDITIONAL COST TO THE OWNER.

P. PROVIDE ACCESS DOORS IN DUCTWORK TO PROVIDE ACCESS FOR ALL SMOKE

DETECTORS, FIRE DAMPERS, SMOKE DAMPERS, VOLUME DAMPERS, HUMIDIFIERS, COILS,

AND OTHER ITEMS LOCATED IN THE DUCTWORK WHICH REQUIRE SERVICE AND/OR

INSPECTION.

Q. PROVIDE ACCESS DOORS IN DUCTWORK FOR OPERATION, ADJUSTMENT, AND

MAINTENANCE OF ALL FANS, VALVES, AND MECHANICAL EQUIPMENT.

R. ALL DUCTS SHALL BE GROUNDED ACROSS FLEXIBLE CONNECTIONS WITH FLEXIBLE

COPPER GROUNDING STRAPS. GROUNDING STRAPS SHALL BE BOLTED OR SOLDERED TO

BOTH THE EQUIPMENT AND THE DUCT.

S. SMOKE DETECTORS SHALL BE FURNISHED AND WIRED BY THE ELECTRICAL CONTRACTOR.

THE MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR MOUNTING THE SMOKE

DETECTOR IN DUCTWORK AS SHOWN ON THE DRAWINGS AND IN ACCORDANCE WITH

MANUFACTURER’S PRINTED INSTRUCTIONS.

T. TERMINATE GAS VENTS FOR UNIT HEATERS, WATER HEATERS, HIGH PRESSURE PARTS

WASHER, HIGH PRESSURE CLEANER, AND OTHER GAS APPLIANCES A MINIMUM OF 3′-0″

ABOVE ROOF WITH RAIN CAP (NOTE TO DESIGNER: EDIT APPLIANCES AND HEIGHT ABOVE

ROOF TO MEET CODE AND TO SUIT PROJECT REQUIREMENTS).

U. SEE SPECIFICATIONS FOR DUCTWORK GAUGES, BRACING, HANGERS, AND OTHER

REQUIREMENTS.

V. LOUVER SIZES, LOCATIONS, MOUNTING, AND DETAILS SHALL BE COORDINATED WITH

OTHER TRADES INVOLVED. REFER TO ARCHITECTURAL SPECIFICATIONS FOR DETAILED

DESCRIPTIONS.

DIRECTION OF PIPE

PITCH (DOWN)

FM

MV

HVAC VALVE SYMBOLS

PC PUMPED CONDENSATE

ROOM TAG

FLEXIBLE CONNECTOR

PUMP

REDUCER (CONCENTRIC)

GATE VALVE

BUTTERFLY VALVE

CHECK VALVE

THERMOMETER

PRESSURE GAUGE

STRAINER WITH BLOWOFF

AND HOSE CONNECTION

YR YEAR

Y

Z INTENTIONALLY LEFT BLANK

Z

M

CONTROL VALVE

CONTROL VALVE, THREE WAY

MOTOR CONTROLLED

VALVE

M

M th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

FULLY SPRINKLERED

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

IN ARCH REG. NO. AR12100034 EXP. 12/31/2021

IN MECH ENGR REG. NO. PE12100220 EXP. 07/31/2022

IN ELEC ENGR REG. NO. PE12100195 EXP. 07/31/2022

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC / PLUMB / TECH ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(913) 369-7200

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

HEALTHCARE PLANNER

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 85712

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

SPUR # 1791.10

/9

/2

:5 :1

P

M

MECHANICAL LEGEND, ABBREVIATIONS

AND GENERAL NOTES

SCP 45 119JRM

BID DOCUMENTS

EHRM INFRASTRUCTURE

UPGRADES FORT WAYNE,

INDIANA

11/12/2021

610A4-21-701

VANIHCS

2121 LAKE AVE,

FORT WAYNE, IN 46805

M-000

1,3,4,5,6,T4,T5,T6

No. REVISION DESCRIPTION DATE

TELECOMMUNICATION

A154

POLICE

SUPPLY

187A

STORAGE

A156K

BATH

186A

STORAGE

STAIR

UP

VESTIBULE

A170

WAITING

A116

EXAM

A115

EXAM

A131

EXAM

A133

OFFICE

A135

TRIAGE

A136

OFFICE

A138

UP

UP

BREAK

EXAM

A114

TOILET

A113

EXAM

A112

EXAM

A111

EXAM

A110

EXAM

A109

EXAM

A108

EXAM

A126

TOILET

A125

OFFICE

A144

SOILED

UTILITY

A107

CLEAN

UTILITY

A124

TOILET

A123

NURSE

STATION

A145

TOILET

A146 192C

STORAGE

194D

UP

OFFICE

A106

NURSE

STATION

A122

OFFICE

A121

EXAM

A143

EXAM

A152 EXAM

A153

OFFICE

A156A

EXAM

A105

CLINIC

A102

A149

A102A

ONCOLOGY

WAITING

A101

OFFICE

A156D A156E

OFFICE

EXAM

A103

EXAM

A118

EXAM

A117

EXAM

A141

EXAM

A148

A156C

OFFICE

A156F

STORAGE

MED

A120

A140 A119

EXAM

A142

EXAM

A150

STORAGE

A151

MECH

A156G

OFFICE

A156B CHAPEL

H.A.C.

CLOSET

180A

OFFICE

OFFICE

OFFICE

OFFICE

A156

STORAGE

194B 194A STORAGE

OFFICE

KITCHEN

192B CLOSET

184A

EXAM

A128

OBSERVATION

A127A

BATH

A127B

MED

A137

STORAGE

A130

H.A.C.

A129

SOILED

UTILITY

A132

A127

MECH

A155

CLEAN

UTILITY

A134 STAIR 5

UP

EMERGENCY

A139

AUDITORIUM

WELCOME

DESK

A104 MENS

VENDING

SECURITY

WELCOME

LOUNGE

A167

TOILET

A165

A157 CASHIER

A158 A159

REGISTRATION

A164

ON CALL

169E

LOCKERS

A169

DATA

176A

TOILET

A166 BATH

TOILET

110B

PHARMACY

EXAM

121H

OFFICE

117 VESTIBULE

EXAM

MECH

LAB

EXAM

EXAM

120A

EXAM

121A

EXAM

121B

EXAM

121E

CORRIDOR

LACTATION

121D

STAIR #2

OFFICE

121F

CONSULT

121G

UUPP

UP

FIRE

PROTECTION

123D PATIENT

EDUCATION

GARAGE

BREAK

CORRIDOR

128A

EXAM

OFFICE

STORAGE

134A TOILET

MED

133A

TOILET

126A

EXAM

EXAM

TOILET

STORAGE

135A

MECHANICAL

DW

TOILET

1-C-132

OFFICE

OFFICE

OFFICE

EXAM

WAITING

1-C-133

PATIENT

CORR.

1-C-C2

DW

1-C-123

INTAKE #2

1-C-130

CONSULT

1-C-129

EXAM 12

1-C-128

HYBRID 13

1-C-127

EXAM 14

1-C-126

EXAM 15

1-C-125

MED ROOM 1

1-C-124

CONSULT 16

1-C-122

CONSULT 17

1-C-121

CONSULT 18

1-C-120

CONSULT 19

1-C-119

EQUIPMENT

STORAGE

1-C-118

TOILET

1-C-146

CORRIDOR

1-C-C3

STORAGE

1-C-134

HYBRID 20

1-C-135

EXAM 21

1-C-136

EXAM 22

1-C-137

HYBRID 23

1-C-138

ELECTRICAL

1-C-140

FUTURE HAC

148A

NURSE

MANAGER

EGRESS

CORRIDOR

1-C-C4

TEAM ROOM

(FUTURE

ELEV.)

1-C-EL1-2

MED ROOM 2

1-C-141

OIT

1-C-139

SPECIALTY

1-C-154

EXAM 24

1-C-142

EXAM 25

1-C-143

CONSULT 26

1-C-144

CLEAN

UTILITY

1-C-145

TOILET

1-C-147

TEAM ROOM

(FUTURE

ELEV.)

1-C-EL3

OPEN

OFFICE

1-C-148

STAIRS 9-1

1-C-ST9

EXAM

EXAM

123A

EXAM

123B 123C

WAITING

137 PATIENT

REGISTRATION

RECEP

MEANS

ELIGIBILITY

138A

TESTING

138B

STAFF

LOUNGE

SMALL

CONFERENCE

TOILET

TOILET

UP

H.A.C.

SOILED

UTILITY

SOILED

UTILITY

STAIR

1-B-ST3

OFFICE

RECEP

HYBRID 5-1

EXAM 5-2

154A

OFFICE

RECEP

CHECK-IN

EXAM 4-2

EXAM 4-1

158A CORRIDOR

1E-4

OFFICE

DN

ENGINEERING

109D

OFFICE

OFFICE

UP

UP

6' - 3 1/2"

CORRIDOR

1E-3

RN-3

TOILET

UP

OFFICE

109C

MECH

A109B A109A 109

EXAM

EXAM

107A

EXAM

OFFICE

STORAGE

STORAGE

MULTIPURPOSE

100A

OFFICE

DATA

WAITING

REGISTER

MED

EXAM 1-1

175A

EXAM 1-2

RN-1

OFFICE

EXAM 2-1

169A

RN-2

CHECK OUT

168 PROCEDURE

OFFICE

CLEAN

UTILITY 2

165 OFFICE

OFFICE

UP

STAIR

EXAM 3-2

162A

EXAM 3-1

STAFF

LOUNGE

1-C-116

WAITING

1-C-101

COFFEE

1-C-101D

RECEPTION

1-C-102

OPEN

OFFICE

1-C-117

KIOSKS

1-C-101C

CORRIDOR

1-C-C5

CONCIERGE

1-C-101A

NEG.

PRESSURE

HYBRID

1-C-104

UP

STAIRS10-1

1-C-ST10

INTAKE #1

1-C-103

PATIENT

CORR.

1-C-C1

EXAM 2

1-C-105

EXAM 3

1-C-106

EXAM 4

1-C-107

EXAM 5

1-C-108

EXAM 6

1-C-109

P. TOILET

1-C-110

HYBRID 7

1-C-111

EXAM 8

1-C-112

EXAM 9

1-C-113

EXAM 10

1-C-114

MULTIPURPOSE

1-C-115

VESTIBULE

1-C-100

MECH

FAMILY

ROOM

VENDING

FAMILTY

TOILET

PUBLIC

TOILET

CONSULT

CORRIDOR

C4109

CORRIDOR

C4110

CORRIDOR

C4111

ELEVATOR

WAITING

BATH

4124A

BATH

4104A

MED/SURG/

ISOLATION

ANTEROOM

(AIRBORNE

INFECTION

ISOLATION)

MED/SURG/

ISOLATION

BATH

4108A

UP

STAIR 1-4

ST4.1

SOILED

HOLD

ALCOVE

C4103

BATH

4114A

BATH

4116A

BATH

4118A

BATH

4120A

MED/SURG

MED/SURG

MED/SURG

MED/SURG

MED/SURG

CLOSET

ALCOVE

BATH

4130A

MED/SURG

4130 MED/SURG

MED/SURG

WASHROOM

MED/SURG

PERSONAL

STORAGE

BUILDING

SERVICES

4164A

ELEVATOR

UTILITY

CORRIDOR

C4104

ELEC.

SOILED

HOLD

CORRIDOR

C4101

STAIR 2-4

ST4.2

SOILED

UTILITY

ROOM

SOILED

EQUIPMENT

CLEAN

UTILITY

MEDICATION

ROOM

NURSE

STATION

NOURISHMENT

CLEAN

SUPPLY

CLEAN LINEN

EKG

STORAGE

OPEN

OFFICE

STORAGE

(EMS)

BATH

4143A

BATH

4144A

STAFF

TOILET

CORRIDOR

C4302

CORRIDOR

C4106

MED/SURG

MED/SURG

BARIATRIC/PHYSICAL

DISABILITIES

MED/SURG

BARIATRIC

PHYSICAL

DISABILITIES

MED/SURG

BATH

4332A

CORRIDOR

C4105

ELECTRICAL

NURSE

STATION

CORRIDOR

C4107

ALCOVE

EQUIPMENT

STORAGE

ALCOVE

CORRIDOR

C4301

CORRIDOR

C4303

NURSE

WORKROOM

LEADER

CLINICAL

NURSE

OFFICE

SOCIAL

WORKER

OFFICE

NURSE

MANAGER

OFFICE

ICU NURSE

MANAGER

OFFICE

SOCIAL

WORKER

DIETICIAN

NURSE

WORKROOM

NURSE

STATION

4317 4319

ELECTRICAL

TOILET

4331 BATH

4333A

STAIR 3-4

ST4.3

CLEAN

SUPPLY

MEDICATION

ROOM

SOILED

UTILITY/EQUIP

BATH

4353A

MED/SURG

4150A

MED/SURG

4154A

MED/SURG

4156A

MED/SURG

4160A CORRIDOR

C4108

ELECTRICAL

BATH

4312A

BATH

4316A

CLEAN LINEN

H.A.C.

4322 ELEC.

NOURISHMENT

BATH

4324A

CORRIDOR

C4304

ELEVATOR

MED/SURG

DATA

ALCOVE

STORAGE

MED/SURG

MED/SURG

SECURITY

CLOSET

BATH

4320A

MED/SURG

MED/SURG

BATH

4326A

BATH

4346A

BATH

4348A

MED/SURG

MED/SURG

BATH

4352A

PATIENT

ROOM

INTENSIVE

CARE

ISOLATION

NOURISHMENT

UP

STAIR 4-4

ST4.4

CORRIDOR

C4305

ANTEROOM

PATIENT

TOILET

INTENSIVE

CARE

4364A

ANTEROOM

PATIENT

ROOM

INTENSIVE

ISOLATION

ICU

EQUIPMENT

STORAGE

CLEAN LINEN

ROOM

CLEAN

NURSE

STATION

4345 ELEC

CLEAN

SUPPLY

4351 PATIENT

ROOM

INTENSIVE

CARE

MEDICATION

ROOM

NURSE

STATION

PATIENT

INTENSIVE

CARE

BATH

4365A

STAFF

LOUNGE

STAFF

TOILET

SUPPLY

ROOM

KITCHENETTE

OPEN

TOILET

4146A

ON CALL

ROOM

OFFICE

STAFF

DICTATION

4147A

LOUNGE

4334B

INTER-DISCIOLINARY

ROOM

4334A

CONFERENCE

OFFICE

CLOSET

551A

STORAGE

TOILET

TOILET

ELEVATOR

MED

515D1

MENS

OFFICE

515E

UP

STAIR

5-1

MED

515D

EXAM

515C

EXAM

515B

EXAM

515A

TOILET

NURSE

STATION

WOMENS

TOILET

WAITING

OFFICE

510A

OFFICE

510B

OFFICE

CLEAN

UTILITY

STORAGE

507C

VESTIBULE

OFFICE

507A

PAIN

OFFICE

507B

MANAGEMENT

SOILED

UTILITY

ELEC

UP

ELEVATOR

STORAGE

VESTIBULE

ELEVATOR

H.A.C.

STORAGE

OFFICE

546A

OFFICE

546B 545

EXAM

OFFICE

DATA

549A

STORAGE

CLOSET

539A

CLEAN

SUPPLY

BATH

543A

PYXIS

CLASSROOM

MECH

MECH

SOILED

UTILITY

515F

LOCKERS

LAB

OFFICE

OFFICE

BATH

521A

EXAM

EXAM

520A

EXAM

520B OFFICE

STAIR

5-2 OFFICE

SOILED

UTILITY

EXAM

EXAM

525A

EXAM

EXAM

526A

OFFICE

DATA

528C

WAITING

CHECK-IN

COLLAB

EXAM

EXAM

EXAM

SOILED

UTILITY

EXAM

BATH

537A

STAIR

5-3 OFFICE

EXAM

MECH

MECH

MD111

M-121

MD111

M-121

MD111

M-121

MD111

M-121

MD111

M-121

MD111

M-121

MD111

M-121

MD111

M-121

BLDG 3

BLDG T4, T5, T6

BLDG 6BLDG 5

BLDG 2 BLDG 4

N

KEY PLAN - BLDG 1, 2, 3, 4, 5, 6 T4, T5, & T6

BLDG 1

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

FULLY SPRINKLERED

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

IN ARCH REG. NO. AR12100034 EXP. 12/31/2021

IN MECH ENGR REG. NO. PE12100220 EXP. 07/31/2022

IN ELEC ENGR REG. NO. PE12100195 EXP. 07/31/2022

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC / PLUMB / TECH ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(913) 369-7200

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

HEALTHCARE PLANNER

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 85712

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

SPUR # 1791.10

/9

/2

:5 :1

P

M

BLDG 1 - MECHANICAL REFERENCE

PLANS

SCP 46 119JRM

BID DOCUMENTS

EHRM INFRASTRUCTURE

UPGRADES FORT WAYNE,

INDIANA

11/12/2021

610A4-21-701

VANIHCS

2121 LAKE AVE,

FORT WAYNE, IN 46805

M-101

N

1" = 40'-0"

BLDG 1 - BASEMENT OVERALL PLAN1

N

1" = 40'-0"

BLDG 1 - FIRST FLOOR OVERALL PLAN2

N

1" = 40'-0"

BLDG 1 - FOURTH FLOOR OVERALL PLAN3

N

1" = 40'-0"

BLDG 1 - FIFTH FLOOR OVERALL PLAN4

No. REVISION DESCRIPTION DATE

MD112

M-122

MD112

M-122

MD112

M-122

MD112

M-122

M-122

M-122

M-122

MD112

MD112

MD112

BLDG 3

BLDG T4, T5, T6

BLDG 6BLDG 5

BLDG 2 BLDG 4

N

KEY PLAN - BLDG 1, 2, 3, 4, 5, 6 T4, T5, & T6

BLDG 1

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

FULLY SPRINKLERED

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

IN ARCH REG. NO. AR12100034 EXP. 12/31/2021

IN MECH ENGR REG. NO. PE12100220 EXP. 07/31/2022

IN ELEC ENGR REG. NO. PE12100195 EXP. 07/31/2022

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC / PLUMB / TECH ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(913) 369-7200

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

HEALTHCARE PLANNER

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 85712

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

SPUR # 1791.10

/9

/2

:5 :1

P

M

BLDG 3,4,5,6 & T4-T6 MECHANICAL

REFERENCE PLANS

SCP 47 119JRM

BID DOCUMENTS

EHRM INFRASTRUCTURE

UPGRADES FORT WAYNE,

INDIANA

11/12/2021

610A4-21-701

VANIHCS

2121 LAKE AVE,

FORT WAYNE, IN 46805

M-102

3,4,5,6,T4,T5,T6

N

1/16" = 1'-0"

BLDG 3 - BASEMENT OVERALL PLAN1

N

1/16" = 1'-0"

BLDG 4 - BASEMENT OVERALL PLAN2

N

1/16" = 1'-0"

BLDG 5 - BASEMENT OVERALL PLAN3

N

1/16" = 1'-0"

BLDG 6 - FIRST FLOOR OVERALL PLAN4

N

1/16" = 1'-0"

BLDG T4-T6 - FIRST FLOOR OVERALL PLAN5

No. REVISION DESCRIPTION DATE

OFFICE

D1

D1

D2D2

D5D5

DATA

MECH

A155

D3

A154

D4

Corridor

AC-1-A63

ACCU-1-A63

TELECOM ROOM /

TCB

063 D4

(ON FIRST FLOOR

ROOF ABOVE)

TELECOM ROOM

176A

AC-1-176A

ACCU-1-176A

(ON FIRST FLOOR

ROOF OUTSIDE)D4

TELECOM ROOM

AC-1-4308

D4

SECURITY

CLOSET

AC-1-528C

ACCU-1-528C

TELECOM ROOM

528C D4

(ON SIXTH FLOOR

ROOF ABOVE)

TELECOM ROOM

B606

D7

D7

DATA

053A

AC-1-053A

D4

HAC

FIRST FLOOR ROOF

OFFICE

OFFICE

OFFICE

D4 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

FULLY SPRINKLERED

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

IN ARCH REG. NO. AR12100034 EXP. 12/31/2021

IN MECH ENGR REG. NO. PE12100220 EXP. 07/31/2022

IN ELEC ENGR REG. NO. PE12100195 EXP. 07/31/2022

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC / PLUMB / TECH ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(913) 369-7200

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

HEALTHCARE PLANNER

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 85712

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

SPUR # 1791.10

/9

/2

:5 :2

P

M

BLDG 1 - MECHANICAL DEMOLITION

PLANS

SCP 48 119JRM

BID DOCUMENTS

EHRM INFRASTRUCTURE

UPGRADES FORT WAYNE,

INDIANA

11/12/2021

610A4-21-701

VANIHCS

2121 LAKE AVE,

FORT WAYNE, IN 46805

MD111

DEMOLITION KEYNOTES

D1 REMOVE AND DEMOLISH COMPUTER ROOM UNIT AND ASSOCIATED CONDENSING UNIT OUTSIDE BY THE LOADING DOCK. REMOVE AND DEMOLISH

ASSOCIATED DUCTWORK, PIPING, AND ACCESSORIES IN ITS ENTIRETY.

D2 REMOVE AND DEMOLISH ALL CEILING MOUNTED DIFFUSERS, ASSOCIATED DUCTWORK, AND ACCESSORIES IN ITS ENTIRETY.

D3 REMOVE ICE MACHINE AND ASSOCIATED ACCESSORIES AND PREPARE ICE MACHINE TO BE RELOCATED. COORDINATE NEW LOCATION WITH THE VA

COR.

D4 NO MECHANICAL DEMOLITION WORK REQUIRED IN THIS ROOM/AREA.

D5 REMOVE AND DEMOLISH ALL CEILING MOUNTED DIFFUSERS, ASSOCIATED DUCTWORK UP TO THE END OF BRANCH LINE, AND ACCESSORIES.

D7 REMOVE AND DEMOLISH AIR GRILLE, ASSOCIATED DUCTOWRK, AND ALL ACCESSORIES BACK TO NEAREST BRANCH AND CAP.

N

1/4" = 1'-0"

BLDG 1 - BASEMENT MECHANICAL DEMO - RM 057/058 ENLARGED PLAN1

N

1/4" = 1'-0"

BLDG 1 - FIRST FLOOR MECHANICAL DEMO - RM A154/A155 ENLARGED PLAN6

N

1/4" = 1'-0"

BLDG 1 - BASEMENT MECHANICAL DEMO - RM 063 ENLARGED PLAN3

N

1/4" = 1'-0"

BLDG 1 - FIRST FLOOR MECHANICAL DEMO - RM 176A ENLARGED PLAN5

N

1/4" = 1'-0"

BLDG 1 - FOURTH FLOOR MECHANICAL DEMO - RM 4308 ENLARGED PLAN7

N

1/4" = 1'-0"

BLDG 1 - FIFTH FLOOR MECHANICAL DEMO - RM 528C ENLARGED PLAN8

N

1/4" = 1'-0"

BLDG 1 - BASEMENT MECHANICAL DEMO - RM B606 & 053A ENLARGED PLAN2

N

1/4" = 1'-0"

BLDG 1 - FIRST FLOOR MECHANICAL DEMO - ROOF ENLARGED PLAN4

No. REVISION DESCRIPTION DATE

TELECOM ROOM

301AC-3.01

ACCU-3.01

(ON GROUND OUTSIDE)

D6

BASEMENT

TELECOM ROOM

AC-4.01

ACCU-4.01

(ON GROUND OUTSIDE)

D4

BASEMENT

AC-5.01

ACCU-5.01

(ON GROUND OUTSIDE)

TELECOM ROOM

D6

BASEMENT

TELECOM ROOM

AC-6-107

ACCU-6-107

(ON GROUND OUTSIDE)

D4

D4

D4 D4

ROOM

HAC

ROOM

HAC

ROOM

HAC

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

FULLY SPRINKLERED

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

IN ARCH REG. NO. AR12100034 EXP. 12/31/2021

IN MECH ENGR REG. NO. PE12100220 EXP. 07/31/2022

IN ELEC ENGR REG. NO. PE12100195 EXP. 07/31/2022

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC / PLUMB / TECH ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(913) 369-7200

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

HEALTHCARE PLANNER

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 85712

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

SPUR # 1791.10

/9

/2

:5 :2

P

M

BLDG 3,4,5,6 & T4-T6 MECHANICAL

DEMOLITION PLANS

SCP 49 119JRM

BID DOCUMENTS

EHRM INFRASTRUCTURE

UPGRADES FORT WAYNE,

INDIANA

11/12/2021

610A4-21-701

VANIHCS

2121 LAKE AVE,

FORT WAYNE, IN 46805

MD112

3,4,5,6,T4,T5,T6

DEMOLITION KEYNOTES

D4 NO MECHANICAL DEMOLITION WORK REQUIRED IN THIS ROOM/AREA.

D6 REMOVE SPLIT SYSTEM FAN COIL UNIT, ASSOCIATED PIPING AND ACCESSORIES. PREPARE FAN COIL UNIT TO BE RELOCATED. REFER TO SHEET M-122

FOR NEW LOCATION.

N

1/4" = 1'-0"

BLDG 3 - BASEMENT MECHANICAL DEMO - RM 301 ENLARGED PLAN1

N

1/4" = 1'-0"

BLDG 4 - BASEMENT MECHANICAL DEMO - RM 401 ENLARGED PLAN2

N

1/4" = 1'-0"

BLDG 5 - BASEMENT MECHANICAL DEMO - RM 501 ENLARGED PLAN3

N

1/4" = 1'-0"

BLDG 6 - FIRST FLOOR MECHANICAL DEMO - RM 107 ENLARGED PLAN4

N

1/4" = 1'-0"

BLDG T4 - FIRST FLOOR MECHANICAL DEMO - RM 118 ENLARGED PLAN5

N

1/4" = 1'-0"

BLDG T5 - FIRST FLOOR MECHANICAL DEMO - RM 129 ENLARGED PLAN6

N

1/4" = 1'-0"

BLDG T6 - FIRST FLOOR MECHANICAL DEMO - RM 107 ENLARGED PLAN7

No. REVISION DESCRIPTION DATE

VD

MAIN SERVER ROOM

CRU-1-057 1

L-1-057 4

CRU-2-057

1" CD

1" CD

24"x18" OA

36"x30" RA

24"x18" OA14

RL

RL

H T P

101010

MECH

A155

TELECOM ROOM

FCU-1-154

CU-1-154

(ON SECOND FLOOR

ROOF ABOVE)

3/4" CD 8

Corridor

A154

TELECOM ROOM /

TCB

AC-1-A63

ACCU-1-A63

(ON FIRST FLOOR

ROOF ABOVE)

TELECOM ROOM

176A

AC-1-176A

ACCU-1-176A

(ON FIRST FLOOR

ROOF OUTSIDE)

TELECOM ROOM

AC-1-4308

TELECOM ROOM

528C

AC-1-528C

ACCU-1-528C

(ON SIXTH FLOOR

ROOF ABOVE)

TELECOM ROOM

B606

FCU-1-B606

CU-1-B606

(ON SECOND FLOOR

ROOF ABOVE)

3/4" CD

DATA

053A

HAC

AC-1-053A

ACCU-1-057

ACCU-2-057

FIRST FLOOR ROOF

OFFICE

OFFICE

OFFICE

RL

RL

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

FULLY SPRINKLERED

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

IN ARCH REG. NO. AR12100034 EXP. 12/31/2021

IN MECH ENGR REG. NO. PE12100220 EXP. 07/31/2022

IN ELEC ENGR REG. NO. PE12100195 EXP. 07/31/2022

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC / PLUMB / TECH ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(913) 369-7200

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

HEALTHCARE PLANNER

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 85712

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

SPUR # 1791.10

/9

/2

:5 :1

P

M

BLDG 1 - MECHANICAL ENLARGED

PLANS

SCP 50 119JRM

BID DOCUMENTS

EHRM INFRASTRUCTURE

UPGRADES FORT WAYNE,

INDIANA

11/12/2021

610A4-21-701

VANIHCS

2121 LAKE AVE,

FORT WAYNE, IN 46805

M-121

KEYNOTES

1 PROVIDE REFRIGERANT PIPING FROM COMPUTER ROOM UNIT TO THE ASSOCIATED AIR-COOLED CONDENSING UNIT ON THE FIRST FLOOR ROOF.

2 PROVIDE REFRIGERANT PIPING FROM SPLIT SYSTEM FAN COIL UNIT TO THE ASSOCIATED SPLIT SYSTEM CONDENSING UNIT ON THE SECOND FLOOR

ROOF.

4 PROVIDE AND INSTALL OUTSIDE AIR LOUVER AND ASSOCIATED ACCESSORIES.

5 ADEQUATE COOLING EXISTS FOR THIS ROOM. NO NEW MECHANICAL WORK REQUIRED IN THIS ROOM.

7 CONNECT FULL SIZE RETURN DUCT FROM THE SERVER CABINET DUCT OPENING TO THE RETURN DUCT ABOVE (TYPICAL FOR ALL SERVER CABINETS).

8 ROUTE 3/4" CONDENSATE PIPE FROM SPLIT SYSTEM FAN COIL UNIT TO EXISTING FLOOR DRAIN IN ROOM A155 (MECH). SLOPE CONDENSATE PIPING A MINIMUM OF 1/8" PER FOOT TOWARD THE FLOOR DRAIN. TERMINATE WITH MINIMUM 2" AIR GAP.

9 ROUTE 1" CONDENSATE PIPE FROM COMPUTER ROOM UNIT TO EXISTING JANITOR'S SINK IN ROOM 052 (HAC). SLOPE CONDENSATE PIPING A MINIMUM

OF 1/8" PER FOOT TOWARD THE JANITOR'S SINK. TERMINATE WITH MINIMUM 2" AIR GAP.

10 PROVIDE HUMIDITY SENSOR AND TEMPERATURE SENSOR FOR COMPUTER ROOM UNITS. PROVIDE ROOM PRESSURE SENSOR FOR OUTSIDE AIR DAMPER. COORDINATE EXACT LOCATION WITH OWNER AND CONTROLS CONTRACTOR. REFER SHEET M-702 FOR CONTROLS.

11 PROVIDE AND INSTALL AIR-COOLED CONDENSING UNIT ON THE FIRST FLOOR ROOF KEEPING THE MANUFACTURER RECOMMENDED CLEARANCES IN MIND. ROUTE REFRIGERANT LINES PARALLEL TO THE EXTERIOR WALL OF THE BUILDING FROM THE CONDENSING UNIT AND CONNECT TO THE ASSOCIATED COMPUTER ROOM UNIT IN ROOM 057 (MAIN SERVER ROOM) ON THE BASEMENT LEVEL.

12 ROUTE 3/4" CONDENSATE PIPE FROM SPLIT SYSTEM FAN COIL UNIT THROUGH THE CORRIDOR TO CONNECT INTO EXISTING LAVATORY TRAP IN ROOM B608 (LOUNGE, STAFF). DO NOT ROUTE ANY PIPING THROUGH ROOM B607 (ELECTRICAL). SLOPE CONDENSATE PIPING A MINIMUM OF 1/8" PER FOOT

TOWARD THE LAVATORY TRAP.

14 ELBOW 24" X 18" OUTSIDE AIR DUCT UP JUST OUTSIDE THE EXTERIOR WALL AND ROUTE AS CLOSE TO THE EXTERIOR WALL AS POSSIBLE. TERMINATE DUCT WITH A GOOSENECK TURN, BIRD SCREEN, AND INSECT SCREEN SUCH THAT IT IS AT LEAST 30' ABOVE FINISHED GRADE.

16 CONTRACTOR SHALL PROVIDE TEMPORARY SPOT COOLERS IN ROOM 053A (DATA) TOTALLING 10 TONS OF COOLING FOR TEMPORARY SERVER RACK RELOCATION FROM EXISTING ROOM 057 (DATA) TO ROOM 053A (DATA). ROUTE TEMPORARY FLEXIBLE EXHAUST DUCT FROM SPOT COOLERS IN ROOM 053A (DATA) THROUGH THE CEILING IN THE CORRIDOR TO EXISTING ROOM 057 (DATA), THEN TO EXISTING ROOM 058 (OFFICE) AND EVENTUALLY OUT

THE WEST WINDOW.

N

1/4" = 1'-0"

BLDG 1 - BASEMENT MECHANICAL HVAC - RM 057 ENLARGED PLAN1

N

1/4" = 1'-0"

BLDG 1 - FIRST FLOOR MECHANICAL HVAC - RM 154 ENLARGED PLAN6

N

1/4" = 1'-0"

BLDG 1 - BASEMENT MECHANICAL HVAC - RM 063 ENLARGED PLAN3

N

1/4" = 1'-0"

BLDG 1 - FIRST FLOOR MECHANICAL HVAC - RM 176A ENLARGED PLAN5

N

1/4" = 1'-0"

BLDG 1 - FOURTH FLOOR MECHANICAL HVAC - RM 4308 ENLARGED PLAN7

N

1/4" = 1'-0"

BLDG 1 - FIFTH FLOOR MECHANICAL HVAC - RM 528C ENLARGED PLAN8

N

1/4" = 1'-0"

BLDG 1 - BASEMENT MECHANICAL HVAC - RM B606 & 053A ENLARGED PLAN2

N

1/4" = 1'-0"

BLDG 1 - FIRST FLOOR MECHANICAL HVAC - ROOF ENLARGED PLAN4

No. REVISION DESCRIPTION DATE

CONTROLLED UNCLASSIFIED INFORMATION - CUI

CONTROLLED UNCLASSIFIED INFORMATION - CUI

C O

N T

R O

L L

E D

U N

C L

A S

S

IF

IE

D

I N

F O

R M

A T

IO

N

C

U I

FCU-1-118

CU-1-118

TELECOM ROOM

EXISTING RAMP EDGE

3/4" CD13

(ON GROUND OUTSIDE)

HAC

FCU-1-129

CU-1-129

TELECOM ROOM

EXISTING RAMP EDGE

3/4" CD13

HAC

(ON GROUND OUTSIDE)

FCU-1-107

CU-1-107

TELECOM ROOM

3/4" CD13

HAC

(ON GROUND OUTSIDE)

ACCU-3.01

(ON GROUND OUTSIDE)

TELECOM ROOM

DH-1-301 6

AC-3.01 15

BASEMENT

AC-4.01

ACCU-4.01

TELECOM ROOM

(ON GROUND OUTSIDE)

DH-1-401 6

BASEMENT

ACCU-5.01

TELECOM ROOM

(ON GROUND OUTSIDE)

DH-1-5016

AC-3.02 15

BASEMENT

AC-6-107

ACCU-6-107

(ON GROUND OUTSIDE)

TELECOM ROOM

107 5 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

FULLY SPRINKLERED

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

IN ARCH REG. NO. AR12100034 EXP. 12/31/2021

IN MECH ENGR REG. NO. PE12100220 EXP. 07/31/2022

IN ELEC ENGR REG. NO. PE12100195 EXP. 07/31/2022

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC / PLUMB / TECH ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(913) 369-7200

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

HEALTHCARE PLANNER

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 85712

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

SPUR # 1791.10

/9

/2

:5 :2

P

M

BLDG 3,4,5,6 & T4-T6 MECHANICAL

ENLARGED PLANS

SCP 51 119JRM

BID DOCUMENTS

EHRM INFRASTRUCTURE

UPGRADES FORT WAYNE,

INDIANA

11/12/2021

610A4-21-701

VANIHCS

2121 LAKE AVE,

FORT WAYNE, IN 46805

M-122

3,4,5,6,T4,T5,T6

KEYNOTES

3 PROVIDE REFRIGERANT PIPING FROM SPLIT SYSTEM FAN COIL UNIT TO THE ASSOCIATED SPLIT SYSTEM CONDENSING UNIT OUTSIDE.

5 ADEQUATE COOLING EXISTS FOR THIS ROOM. NO NEW MECHANICAL WORK REQUIRED IN THIS ROOM.

6 PROVIDE AND INSTALL WALL MOUNT DEHUMIDIFIER (ULTRA-AIRE 4035900 OR APPROVED EQUAL) AND ASSOCIATED ACCESSORIES. ROUTE 1/2" CONDENSATE PIPE TO CONNECT INTO EXISTING CONDENSATE PIPING FROM THE FAN COIL UNIT.

13 ROUTE 3/4" CONDENSATE PIPE FROM SPLIT SYSTEM FAN COIL UNIT TO EXISTING FLOOR DRAIN IN ROOM 105 (HAC). SLOPE CONDENSATE PIPING A MINIMUM OF 1/8" PER FOOT TOWARD THE FLOOR DRAIN. TERMINATE WITH MINIMUM 2" AIR GAP.

15 INSTALL EXISTING TO RELOCATE SPLIT SYSTEM FAN COIL UNIT IN THE LOCATION SHOWN. RE-ROUTE ASSOCIATED REFRIGERANT AND CONDENSATE

PIPING AS REQUIRED.

N

1/4" = 1'-0"

BLDG T4 - FIRST FLOOR MECHANICAL HVAC - RM 118 ENLARGED PLAN5

N

1/4" = 1'-0"

BLDG T5 - FIRST FLOOR MECHANICAL HVAC - RM 129 ENLARGED PLAN6

N

1/4" = 1'-0"

BLDG T6 - FIRST FLOOR MECHANICAL HAVC - RM 107 ENLARGED PLAN7

N

1/4" = 1'-0"

BLDG 3 - BASEMENT MECHANICAL HVAC - RM 301 ENLARGED PLAN1

N

1/4" = 1'-0"

BLDG 4 - BASEMENT MECHANICAL HVAC - RM 401 ENLARGED PLAN2

N

1/4" = 1'-0"

BLDG 5 - BASEMENT MECHANICAL…

This is the start of the file's text. The full file is on GovTribe.